Features
Microgrid Grid Support
Stabilizes a microgrid against transient events • UL1741 (pending)
caused by step loads and renewable power • IEEE1547:2018
sources. • Grid following
• 2 per unit (P.U.) fault current • Provide Reactive Power
• Grid firming and forming mode • Voltage and Frequency Ride Through
• Open Phase Detection and Anti-islanding
Seamless Mode Transfer • High Rate of Change of Frequency Ride Through
Seamless transfer between grid forming, firming (ROCOF) (> 100Hz/s)
and following mode†. • Voltage Regulation by Power
Flexibility Parallel Ready
Designed for a wide range of applications and Plug-and-play paralleling with other power
compatible with virtually any power source. sources.
Lower Fuel Consumption Energy Storage Management
Integrated control of generating system which Built-in intelligent controls for charging,
minimizes fuel consumption and emissions. discharging, equalization, and state-of-charge
Islanding Detection estimation for energy storage elements.
Automatic islanding detection to meet anti- Operational in Autonomous or Remote-Control
islanding UL1741/IEEE1547 and synchronization modes (works in conjunction with supervisory
back to grid to guarantee continuous power to controller).
the load. Touch Screen
Patented Non-Linear Droop Control User friendly touch-screen display offers real-time
• Ultra-fast response with reduced dead bands. system information, configurable data logging,
• Nonlinear droop maximizes ESS early remote access, and more.
contribution while maintaining off grid stability.
• Overall lower freq. deviation and improved
power quality.
†
Subject to grid and local load conditions.
Technical Specifications
Configuration
DC Input Voltage 800 VDC to 1000 VDC
Max. DC Input Current 1250A
DC Isolating Switch Contactor and Manual Disconnect with Lockout Feature
Rated Output Power 1000 kVA
150% for 10 sec (preliminary)
Overload Capacity
125% for 4 mins (preliminary)
Fault Current Capability 2 per unit (P.U.)
*Output Voltage Range (L-L) 380 - 690V
Output Frequency Range 50 or 60 Hz
Output Power Factor Controllable from Supervisory Controller
Total Harmonic Distortion <5%
AC Disconnect and Protection Electrically Operated Breaker with ***LSI Trip Unit
**Peak Efficiency > 98% (preliminary)
**CEC Weighted Efficiency 97% (preliminary)
Modbus TCP, SunSpec, others configurable on request and via MMC
Communication and Control Interface ††
DNP3
P
Switchgear
P
ATS*
BDP Static
Switch G BDP Load(s) Load(s) BDP G
Load(s)
BDP
* Closed transition ATS
Load(s)
Dimensions
A B C Weight dry
mm (in) mm (in) mm (in) kg (lbs)
1505 (59.25) 711 (28.0) 2199 (86.6) 1515 (3340)
A B
©2020 Caterpillar
LEHE2622-00 (HTS 31Augl20 Preliminary) Page 3 of 3 All rights reserved.