TEST REPORT .
REPORTNO.: 2011FE0286 PAGE 1 OF 4 |
Sdn Bh. This Test Report shal
Applicant’
Manufacturer
Product
Reference Standard
Method of Test
Description of Test
Specimen
Date Received
Date of Test
Job No, Ref No.
Test Result
Issued Date
WAN MOHD Ki
writen agproval om Managing Director of SIRIM QAS Inlenatonal Sch. Bhd Please rer everleal for conditions tothe use of Tet Repo
‘This Test Report refers only to samples submited by he applcartto SIRIM GAS Inlemalional Sdn. Bhd and ested by SIRIM GAS Ttemalionar |
I not be reprodu:
‘excep! in fll and shal not be used for adversing purposes by any means or forms without
K -FLEX MALAYSIA SDN. BHD.
Lot 2752, Jalan Raja Nong,
Taman Klang Jaya,
41200 Klang,
Selangor Darul Ehsan,
(Attn: Mr. Gan Kok Leong)
ELASTOMERIC THERMAL INSULATION
BS 476: Part 6: 1989
Fire Test on Building Materials and Structures
Part 6: Method of Test for Fire Propagation for Products.
3 pieces of Elastomeric Thermal Insulations,
Size of Specimen
Brand
Model
Nominal Thickness
Nominal Density
Measured Density
225mm x 225mm * 32.0 mm (measured thickness)
K-FLEX EC
SHEET
32.0 mm
55 ky/m’
51.5 kg/m?
‘The specimens were tested with the face side exposed to the specified heating condition
of the fire test.
The test specimens were sampled by En, Irfan Abdullah Khalit of Product
Certification Section, SIRIM QAS International Sdn. Bhd. on 27,07.201 1 The test was
requested through PP2 Form Ref. No, LK046601 dated 22.08.2011
12.09.2011
23.11.2011
20111280253 /SQAS/FPS/15/1-S
Subindex
Subindex it |
sl
29 Oy 201
>
— -
WAN YAHYA ZiGAT AHMAD
feutive Group Leader
Fire Protection Section
Testing Services Department
SIRIM QAS International Sdn. Bhd.TEST REPORT _
REPORT NO.: 2011FE0286 PAGE 2 OF 4
‘Tis Test Repo refers only to Samples submitied by the applicant to SINT OAS Tntermational San. Ghd. and tesied by SIM OAS
International Son. Bhe. This Test Report shall not be reproduced, except in ful and shall not be used for advertising puiposes by any means
‘or forms without witten approval rom Managing Diteetor of SIRIM QAS Inleinational Stn. hd
Product : ELASTOMERIC THERMAL INSULATION
Brand K-FLEX EC Nominal Density 55 kg/m?
Model SHEET Measured Density 51.5 kg/ m*
Nominal Thickness 2 32.0mm Date of Test 23.11.2011
Measured Thickness > 320mm
‘Temperature Rise Above Ambient ("C)
Time | Calibration] Specimen Specimen] Specinien Specimen]
(Min, A 8 c Average
05 eles "7 a |
10 oe 20 19 °
1s 1 2 6 2 20
20 2 2% 4 5 2
26 ol 9 a |
30 2» M ey |
40 less 25 38 ~
50 9s 2 2 0 87
60 M9 no | 99 18 2
10 137 46 143 i |
80 1583, 167 sl 164 160
90 168 19 168 ist 176
oo 181 190 181 193 188
120 202 203 199 an 204
140 216 an 209 216
160 28 21s 216 216
so | 236 220 24 218
20 | 28 24 29 226
SubnGNT TS TS TS
Subindex 2 oa os 03
Subindex 3 oo on 00
Tndex of Pevfammanee 5
an unu anesTEST REPORT
REPORTNO.: 2011FE0286 PAGE 3 OF 4
‘This Test Report eters only fo samples submiied by The applicant to SIRIM GAS Intemational Sdn Ghd. and ested by SIRI GAS
leternational Sén. Bhd. This Test Repor shail not be reproduced. except in fll and shall not be used for advertising purposes by ary Means
or forms without wien approval from Managing Directr of SIRIM GAS Intemational Sdn. Bh
Date of Test : 23.11.2011
No. of Specimen Tested : 3 nos.
The Fite Propagation Index I is 1.8 for the Elastomerie Thermal Insulations with known density of 51.5 kg/m’
and measured thickness of 32.0 mm.
The Subindex il is 1s
The Subindex i2 is 03
‘The Subindex i3 is 0.0
The test results relate only to the behavior of the test specimens of the product under the particular
conditions of test; they are not intended to be the sole criterion for assessing the potential fire hazard
of the product in use.
29 NOV 2011TEST REPORT
REPORT NO.: 20114FE0286 PAGE 4 OF 4
‘This Test Report refers only to samples subried by tho applicant To SIRIW GAS International Sah. Bhd_and Tested by SIRI OAS
International Sdn. Bh. Ths Test Report shall not be reproduced, except in fll and shall not be used for advertising purposes by any mean
forms without wien approval from Managing Director of SIRIMI GAS International S¢n, Bh
Product : ELASTOMERIC THERMAL INSULATION
Brand K-FLEX EC Nominal Density 55 kg/m’
Model 2 SHEET Measured Density 51.5 kg/m"
Nominal Thickness 3.0mm Date of Test 23.11.2011
Measured Thickness 32.0 mm
300 - ~ — —
250 |
9
e
% 20
a
=
=
3 150
<
a
z 100
a
=
i
#
50
0
ry 50 10.0 15.0
TIME (MIN)
—eCalibration _~#-Elastomeric Thermal Insulation
29 NOY 2011TERNATIONAL
STRIM QAS International Sdn. Bhd,
Xo I.Pesaran Dat Ment PO Bs 735 Seay 2.40700 Shh Alam, Selangor Darl Ehsan
Malaysia
Tel OF Sstast65 Fr onssi4oase by stim my
SIRIM (Company No" #1033468)
QAS:
. _TEST REPORT
REPORT NO.: 2011FE0287 [Pace 1 OF 4
This Test Report rls ony to
Sdn Bhd. This Test Repo shal
switten approval from Managing
Applicant!
Manufacturer
Product
Reference Standard/
Method of Test
Description of Test
Specimen
Date Received
Date of Test
Job No/ Ref No,
Test Result
Issued Date
WAN MOHD Ki
Testing Executive
mples ubrified by the appleai o SIRIM GAS Twersaional Sde. Bhd, dnd ented by SIRI GAS sinatra
not be reproduced, exept in full and shall not be used for advertsing purposes by any means ot forms without
Director of SIRIM QAS International Sdn. Bhd. Please refer overia! fo conditions tothe use of Test Report
K ~ FLEX MALAYSIA SDN. BHD.
Lot 2752, Jalan Raja Nong,
Taman Klang Jaya,
41200 Klang,
Selangor Darul Ehsan,
(Attn: Mr, Gan Kok Leong)
ELASTOMERIC THERMAL INSULATION
BS 476: Part 6: 1989
Fire Test on Building Materials and Structures
Part 6: Method of Test for Fire Propagation for Products.
3 pieces of Elastomeric Thermal Insulations.
Size of Specimen 225mm * 225mm * 19.0 mm (measured thickness)
Brand K-FLEX EC
Model SHEET
Nominal Thickness 19.0 mm
Nominal Density 55 kg/m!
Measured Density 56 kg/m’
The specimens were tested with the face side exposed to the specified heating condition
of the fire test
‘The test specimens were sampled by En. Irfan Abdullah Khalit of Product
Certification Section, SIRIM QAS International Sdn. Bhd. on 27.07.2011. The test was
requested through PP2 Form Ref. No, LK046601 dated 22.08.2011
12.09.2011
23.11.2011
12011 1280257 /SQAS/FPS/IS/L-
ubindex il | Subindexi2 | Subindexi3 | Fire Propagation Index (I)
4 54 08 108 |
i)
>
28 HOY 201
Po
IRI WAN YAHYA
EStiN,
i
prorection e
ZARAE AHMAD
Group Leader
Fire Protection Section
a,
ft Services Department
SIRIM QAS International Sdn, Bhd.TEST REPORT
REPORT NO.: 2011FE0287 PAGE 2 OF 4
‘This Test Report refers only fo saniplas submited by the applicant To SIRI GAS Intemational Sdn Bhd. and Wested by SIAM GAS
International San. Bhd. This Test Report shall not be reproduced, except in fll and shall not be used for advertising purposes by any meane
or forms without writen approval from Managing Director of SIRIM GAS International Sdn. Bho,
Product : ELASTOMERIC THERMAL INSULATION
Brand : K-FLEX EC Nominal Density 2 55 kg/m?
Model : SHEET Measured Density 56 ka/ m°
Nominal Thickness 19.0 mm Date of Test 23.11.2011
Measured Thickness: 19.0 mm
Temperature Rise Above Ambient (°C)
Time] Calibrator] Specimen | Specimen] Specimen] — Specimen
(Min) A B c Average
05 14 2 «| 20 21
(1s 2 26 4
Ls 23 3 29 31 30
20 n a1 40 8 4l
fs 30 49 si 50
30 6 55 |
so | 96 96 ie |
5.0 ” le | i M7
60 19 ns gg tne 7
10 137 92 196 193 193,
80 156 203 209 208
9.0 M1 215 20 219
100 183 234 230 228
120 204 249 243
M40 216 oa | ae up|
160 230 244 252
180 23 mT 258 24
20.0 2a 27 357 255 253
[Sabtadex 7 7] a2 7 ae
Subindex 2 5a 35 so 5a
Subindex 3 06 10 09 08
Tad oF Performance TO TOT 1s TO
29 NOV 2011TEST REPORT
REPORT NO.: 2011FE0287 PAGE 3 OF 4
This Test Report refers only to samples submited by the appicant To SIRIMT GAS Inleimationa’ Sdn Ghd_ and Tested by SIRI GAS
International Sdn. Bhd. This Test Report shall nol be reproduces, except in full and shall not be used for advertising purposes by any means
or fms without witten aparoval from Managing Directr of SIRIM OAS Intemational Son. Bhd
Date of Test : 23.11.2011
No, of Specimen Tested : 3 nos.
‘The Fire Propagation Index T is 10.8 for the Elastomeric Thermal Insulations with known density of 56 kg/m?
and measured thickness of 19.0 mm.
‘The Subindex il is 46
‘The Subindex i2 is 54
‘The Subindex i3 is 0.8
The test results relate only to the behavior of the test specimens of the product under the particular
conditions of test; they are not intended to be the sole criterion for assessing the potential fire hazard
of the product in use
28 NOY 20:1TEST REPORT
REPORTNO.: 2011FE0287 PAGE 4 OF 4
This Test Report refers only t samples submited by the applicant to STAIN GAS International San. Bhd and Tested by SIRIM GAS
International Sdn. Bhd. This Test Report shall not be reproduced, except in full and shall not be used for advertsing purposes by any means
‘forms without writen approval rom Managing Director of SIRIM OAS international Sdn. Sha
Product ELASTOMERIC THERMAL INSULATION
Brand : K-PLEX EC Nominal Density 55 ke! m*
Model SHEET Measured Density 56 ky m*
Nominal Thickness: 19.0mm Date of Test 23.11.2011
Measured Thickness: 19.0 mm
300 - — —
8
‘
200
ENT (°C)
150
100
TEMP. RISE ABOVE AMBI
50
00 50 10.0 150 200
TIME (MIN)
Calibration —™~Elastomeric Thermal Insulation
SH
29 HOY 2011SIRIM QAS International Sdn. Bhd.
Not, Pesaran Dato’ Meter, POBox 7035, Sekiyen 2, 40911 Shh Alam, Selangor Dal Ehsan
MALAYSIA
Toho acess ac onssits4 tp stay
SIRIME Sr sone
QAS:
TEST REPORT
REPORT NO.: 2011FE0288 PAGE 1 OF 4
‘This Test Report refers any to samples submited by the appheal fo STRIM GAS Tniemational Sdn Ghd) and lested by SIRIM OAS Internalional
Sdn Bh. This Test Report shall not be reprocuced. except in full and shall nat be used for advertising purposes by ary means ot forme without
\wntten approval from Managing Director of SIRIM QAS international Sdn. Bhd, Please refer overlea for conditions to Ihe use of Test Rear
Applicant! K ~ FLEX MALAYSIA SDN. BHD.
Manufacturer Lot 2752, Jalan Raja Nong,
Taman Klang Jaya,
41200 Klang.
Selangor Darul Ehsan,
(Attn: Mr. Gan Kok Leong)
Product ELASTOMERIC THERMAL INSULATION
Reference Standard’: BS 476: Part 6: 1989
Method of Test
Fire Test on Building Materials and Structures
Part 6: Method of Test for Fire Propagation for Products.
Description of Test 3 pieces of Blastomeric Thermal Insulations.
Specimen Size of Specimen 225mm * 225mm x {0.0 mm (measured thickness)
Brand K-FLEX EC
Model SHEET
Nominal Thickness 10.0 mm
Nominal Density 55 kw/m’
Measured Density 53.4 kg/m?
Date Received
Date of Test
Job No! Ref No.
‘Test Result
Issued Date
The specimens were tested with the face side exposed to the specified heati
of the fire test
The test specimens were sampled by En, Irfan Abdullah Khalit of Product
Certification Section, SIRIM QAS International Sdn. Bhd. on 27.07.2011 The test was
requested through PP2 Form Ref. No. LK046601 dated 22.08.2011
12.09.2011
05.10.2011
120111280256 /SQAS/FPS/15/1-5
[ Subindexit |” Subindexi2 | Subinde Fire Propagatic
[as 29 08 52
of UCE 2 7
yy
eer ae
onorecvon 2) :
WAN MOHG KHAIRI WAN VAHYA ZAG AHMAD
Group Leader
Fire Protection Section
Vesting Services Department
SIRIM QAS Intemational Sdn. Bb
Testing ExecutiveTEST REPORT
r
[REPORT NO.: 2011FE0288 PAGE 2 OF 4
This Test Report refers only to samples submilied by the applicant fo SIRIM GAS Tnernational
International Sdn. Bhs, This Test Report shall not be reproduced, except in fll and shall not be used for advertising purposes by any means
or forms without written approval om Managing Diectorof SIRIM GAS international Stn. Bhd
in” Bh and tested by SIRINN GAS
Produet : BLASTOMERIC THERMAL INSULATION
Brand K-FLEX EC Nominal Density 55 kg/m’
Model SHEET Measured Density 53.4 kg/m?
Nominal Thickness: —10.0mm Date of Test 05.10.2011
Measured Thickness: 10.0 mm
| Temperature Rise Above Ambient (°C)
Time | “Calibration | Specimen [Specimen] Specimen] Specimen
(Min, B c Average
05 2 16 " 5
10 ” 20 20 21 2»
1s 21 2 n 2B 2
23 24 26 2 28
26 2s 28 29 28
2 32 30 3B
40 9 1 39 R or
so 122 29 127
60 137 Ist 130
70 \2 ie 166 168 169
80 189 182 18s 185
90 201 197 200
10.0 isi 216 22 214
120 202 237 as | |
140 216 27 25 246
16.0 251
180 236 255
200 23 287
Subindex 7 0 TS I TS
Subindex 2 32 24 3
ibindex 3 09 07 os
Tadex oF Performance TTEST REPORT
REPORTNO., 2011FE0288 PAGE 3 OF 4
‘This Test Raper refers only to sansias submiled by the apalcant Te SIRI GAS International Sdn. Ohd. and tested by SIRIM OAS
Interatonal Sdn. Bhd. This Test Repor shall not be reproduced. except in full and shall nat be used for advertising purposes by any means
Cr forms without writen approval from Managing Diractar of SIRIM QAS International Sdn, Bhd
Date of Test : 05.10.2011
No. of Specimen Tested : 3 nos,
‘The Fire Propagation Index I is 5.2 for the Elastomeric Thermal Insulations with known density of 53.4 kg/m’
and measured thickness of 10.0 mm.
‘The Subindex il is Ls
The Subindex i2 is 2.9
‘The Subindex i3 is 0.8
‘The test results relate only to the behavior of the test specimens of the product under the particular
conditions of test; they are not intended to be the sole criterion for assessing the potential fire hazard
of the product in use.TEST REPORT
REPORT NO.
2011FE0288 PAGE 4 OF 4
This Test Repor! refers only to sample
or forms without writen approval from Managing Director of SIRIM OAS Intemational Sdn. Bhd
Product
Brand
Model
Nominal Thickness
Measured Thickness
TEMP. RISE ABOVE AMBIENT (°C )
300
250
200
150
3
00
ELASTOMERIC THERMAL INSULATION
K-PLEX EC Nominal Density
SHEET Measured Density
10.0 mm Date of Test,
10.0 mm
50 10.0 150
TIME (MIN)
—* Calibration _-t#~Elastomeric Thermal Insulation
‘submitted by The applicant to SIRIM GAS Intemational Sar
Incemationsl Sen. Bhd. This Test Report shall not be reproduced, except in fll and shall not be used for
Bhd, and Tested by SIRIN' GAS
sdversing purposes by any means
55 kg! m?
53.4 kg/m!
05.10.2011