You are on page 1of 13

European Building Automation Controls Association

EPBD BACS COMPLIANCE


VERIFICATION CHECKLIST
STEP 1: The BACS compliance verification shall be conducted only if the effective rated output for heating (Art.14)/air-conditioning (Art.15) systems
or systems for combined space heating/air-conditioning and ventilation in the building is over 290kW.
SELF-DECLARATION
COMPLIANCE COMPLIANCE VERIFICATION Boundary Conditions /
SELF-DECLARATION COMPLIANCE QUESTIONS SUPPORTING CHECKS PREREQUISITES for the
ID RESPONSE
(answered by Building Owner) RECORDS (conducted by Building BACS capabilities to be
(provided by Building Inspector) effective
Owner)
I Information Section: 290 kW COVERAGE
What is the effective rated output (calorific output as PDF list of Heating Check equipment nameplates
per EPBD) of the Heating equipment in the building system main equipment of main Heating system
Heating systems (output of all heat generators in the with indication of the equipment in main HVAC plant
building including main Heating equipment in maximum calorific or the building Operation &
plantrooms, e.g. boiler, solar heat system, CHP and output, expressed in kW, Maintenance Manual.
I1 heat-generating terminal equipment in rooms, e.g. per piece of equipment <kW>
electric direct heater)?
NOTE: Every heat generator that adds heat to the
building space regardless of its location (generation in
main HVAC plant, distribution and emission in the
room) should be added in the sum for the output.

What is the effective rated output (calorific output as PDF list of Air- Check equipment nameplates
per EPBD) of the Air-conditioning systems in the conditioning system of main Air-conditioning
building (output of all cold generators in the building main equipment with systems equipment in HVAC
including main cooling equipment in plantrooms, e.g. indication of the main plant or the building
chiller, heat-pump, and cooling-generating terminal maximum calorific Operation & Maintenance
I2 equipment in rooms)? output, expressed in kW, Manual. <kW>
NOTE: Every cooling generator that adds cooling to the per piece of equipment
building space regardless of its location (generation in
main plant, distribution and emission in the room)
should be added in the sum for the output.

1
European Building Automation Controls Association

SELF-DECLARATION
COMPLIANCE COMPLIANCE VERIFICATION Boundary Conditions /
SELF-DECLARATION COMPLIANCE QUESTIONS SUPPORTING CHECKS PREREQUISITES for the
ID RESPONSE
(answered by Building Owner) RECORDS (conducted by Building BACS capabilities to be
(provided by Building Inspector) effective
Owner)
What are the 3 representative rooms in this building in PDF floor plans with Check PDF floor plans where Room 1: type,
which the heating, cooling and/or ventilation is/are marked representative the 3 representative rooms are name, size in
BACS controlled? Please enter their types, names, and rooms marked. m2
floor area in the Response column. Room 2: type,
I3 NOTE: Representative rooms/spaces should represent name, size in
the room/space types that are the most typical for the m2
inspected building, e.g. an individual office, an open Room 3: type,
office zone and a meeting room in an office building. name, size in
m2

2
European Building Automation Controls Association

STEP 2: The compliance verification shall be conducted only if building automation and control systems (BACS) capabilities apply to a considerable
extent in the building
SELF-DECLARATION
COMPLIANCE
SELF-DECLARATION COMPLIANCE COMPLIANCE SUPPORTING Boundary Conditions /
VERIFICATION CHECKS
ID QUESTIONS (answered by Building RECORDS RESPONSE PREREQUISITES for the BACS
(conducted by Building
Owner) (provided by Building capabilities to be effective
Inspector)
Owner)

S Starting Section: BACS COVERAGE


Is 80% of the effective rated output in Indicate in the list of I1 which Spot-check BACS heating YES ☐ BACS should control a minimum 80%
kW for Heating systems in the building, heat-generating controls equipment in of the Heating systems in the
equipment/devices are NO ☐
both main equipment and terminal HVAC main plant to building for it to have any effect on
S1 integrated in BACS and provide
equipment, controlled by BACS - relates confirm the information the heating energy performance
to the figure in I1 corresponding diagrams of provided by the Building
controls Owner

Is 80% of the effective rated output in Indicate in the list of I2 which Check BACS air- YES ☐ BACS should control a minimum 80%
kW for Air-Conditioning systems in the cold-generating conditioning controls of the Air-conditioning systems in
NO ☐ the building for it to have any effect
building, both main equipment and equipment/devices are equipment in HVAC main
terminal equipment, controlled by BACS integrated in BACS and provide plant to confirm the on the heating energy performance
- relates to the figure in I2 corresponding diagrams of information provided by To count stand-alone split units in
S2 controls the Building Owner the 80% these units should be at
least monitored by BACS, e.g. energy
consumption, status, interlock with
heating control

Is 80% of the nominal electrical output in Indicate in the list of all Check BACS ventilation YES ☐ BACS should control a minimum 80%
kW for Ventilation systems in the ventilation equipment/devices controls equipment in of the Ventilation systems in the
NO ☐
building, both main equipment and with corresponding electrical HVAC main plant to building for it to have any effect on
terminal equipment, controlled by output in KW which of them are confirm the information the ventilation energy performance
BACS? integrated in BACS and provide provided by the Building Stand-alone occupancy-driven
S3 corresponding diagrams of Owner control of exhaust fans (through
controls presence detectors) should be
included in the 80%, e.g. toilet
exhaust fans.

3
European Building Automation Controls Association

SELF-DECLARATION
COMPLIANCE
SELF-DECLARATION COMPLIANCE COMPLIANCE SUPPORTING Boundary Conditions /
VERIFICATION CHECKS
ID QUESTIONS (answered by Building RECORDS RESPONSE PREREQUISITES for the BACS
(conducted by Building
Owner) (provided by Building capabilities to be effective
Inspector)
Owner)
Does 80% of the building floor area PDF floor plans with marked Check the availability of YES ☐ BACS should control a minimum 80%
designed for continuous occupancy individual room controls PDF floor plans with of the building floor area designed
NO ☐
during building operating hours marked individual room for continuous occupancy during
(rooms/zones) have room/zone controls building operating hours for it to
automation controls integrated into have any effect on the building
S4 BACS? energy performance and IEQ
Rooms/zones that are designed for
continuous occupancy during
operating hours shall have controls
equipment that meet at least class B
according to EN ISO 52120.

4
European Building Automation Controls Association

STEP 3: The building automation and control systems shall be CAPABLE of:
SELF-DECLARATION COMPLIANCE
SELF-DECLARATION COMPLIANCE COMPLIANCE SUPPORTING VERIFICATION Boundary Conditions /
ID QUESTIONS (answered by Building RECORDS CHECKS RESPONSE PREREQUISITES for the BACS
Owner) (provided by Building (conducted by capabilities to be effective
Owner) Building Inspector)
(a) CONTINUOUSLY MONITORING, LOGGING, ANALYSING and ALLOWING for ADJUSTING ENERGY USAGE
Is the building energy meter data PDF energy consumption Check the availability YES ☐ Energy metering should cover a
integrated and analysed in BACS with at reports for building electricity, of energy minimum 80% of total HVAC building
NO ☐
least hourly data granularity to identify heating and cooling consumption reports energy consumption. A process to
energy optimisation opportunities in the consumption respectively that that compare current audit/validate/certify the meters’
building? (according to EN ISO 52120 class compare energy values over values with previous readings should be in place. The energy
B: 7.4.1 Trending functions and different time periods, e.g. periods and indicate data measuring systems relevant for
consumption determination) Including as cumulated daily values from deviations. HVAC shall be regularly checked for their
A1 a minimum the following total energy data last month (before the function and accuracy.
for: inspection) compared to the Monitoring and logging are prerequisites
- total building thermal energy for space daily values for the same month for the analysing capability. Data should
heating, and from last year be retained for historical analysis, so
- total building thermal energy for space trends can be observed.
cooling and
- total building electrical energy

5
European Building Automation Controls Association

COMPLIANCE
SELF-DECLARATION Boundary Conditions /
SELF-DECLARATION COMPLIANCE SUPPORTING VERIFICATION
COMPLIANCE QUESTIONS PREREQUISITES for the
ID RECORDS CHECKS RESPONSE
(answered by Building BACS capabilities to be
(provided by Building Owner) (conducted by
Owner) effective
Building Inspector)
Is HVAC energy-relevant "PDF snapshot of output used for analytics with 2 Check the availability YES ☐ There should be a process in
process data monitored and example views and a rationale on how corrective of example snapshots place to regularly analyse the
NO ☐
analysed to detect recurring actions can be derived from it. for consistency and information provided by BACS
energy wasting deviations and Example 1. A graph with runtime values for main HVAC continuity and track corrective actions.
to trigger respective corrective equipment vs room occupancy times for the 3 Additional information on
actions? representative rooms of the last 6 months before the occupant feedback/behaviour
planned inspection, ideally 1-minute log interval should be considered to
Example 2. A graph including room setpoint +/- define corrective actions.
A2
deadband, room temperature values, action/control
signal on the terminal unit (or the equipment
controlling the temperature) and room occupancy for
the 3 representative rooms for four 24 hour periods
(one in each season), ideally 1 minute log interval
OR SIMILAR examples accompanied with an
explanation of how this proof is similar in fulfilling the
specific requirement"

Does BACS allow adjustment Print screen/photo of the BACS interface that shows Check the availability YES ☐
of setpoints (fixed or the possibility for setpoint adjustment from a central of selected print
NO ☐
calculated) of all relevant GUI (e.g. work station, web operation; room operating screens for main
A3 supplying HVAC plants to units are excluded) for HVAC main plant (main HVAC plants that
optimize demand-driven generation and distribution equipment), combined clearly show setpoint
operation? with a clear naming /description of the setpoints adjustment
linked to energy. possibilities

6
European Building Automation Controls Association

COMPLIANCE
SELF-DECLARATION Boundary Conditions /
SELF-DECLARATION COMPLIANCE SUPPORTING VERIFICATION
COMPLIANCE QUESTIONS PREREQUISITES for the
ID RECORDS CHECKS RESPONSE
(answered by Building BACS capabilities to be
(provided by Building Owner) (conducted by
Owner) effective
Building Inspector)
Is there a runtime Print screens showing that runtime schedules for HVAC Check the availability YES ☐
management as per EN ISO equipment could be adjusted. The number of print of selected print
NO ☐
52120 class A: 7.2.2 Individual screens depends on the HVAC systems present in the screens for main
setting following a predefined specific building (one per system): HVAC plants that
time schedule; adaptation Example 1. Adjusting runtime of heating system clearly show runtime
from a central point (e.g. including the runtime schedule for at least 1 heat management
workstation, web operation; generator possibilities
room operating units are
A4 Example 2. Adjusting runtime of air-conditioning
excluded)?
system including the runtime schedule for at least 1
cooling generator
Example 3. Adjusting runtime of ventilation system
including the runtime schedule for at least 1 major fan
Example 4. Adjusting runtime of room HVAC
equipment (e.g. FCU, VRF unit) for at least one of the
representative rooms

Is there a setpoint adjustment Print screens from the BACS User Interface where the Check the availability YES ☐ eu.bac recommend applying
or reset from a central point temperature setpoint for cooling, the temperature of selected print EN ISO 52120 7.1.3 class A
NO ☐
(e.g. workstation, web setpoint for heating and the ventilation setpoint (CO2 screens for the which ensures automatic
A5 operation) for individual or air flow), for the selected representative rooms are representative rooms reset back to the present
spaces? (according to EN ISO clearly visible. that clearly show setpoint.
52120 class B 7.1.2) setpoint adjustment
possibilities

7
European Building Automation Controls Association

COMPLIANCE
SELF-DECLARATION VERIFICATION
SELF-DECLARATION COMPLIANCE SUPPORTING Boundary Conditions /
COMPLIANCE QUESTIONS CHECKS
ID RECORDS RESPONSE PREREQUISITES for the BACS
(answered by Building (conducted by
(provided by Building Owner) capabilities to be effective
Owner) Building
Inspector)
BENCHMARKING the building's energy efficiency, DETECTING LOSSES in efficiency of technical building systems, and INFORMING THE PERSON
(b)
RESPONSIBLE for technical building management about opportunities for EE improvement
Is the building's HVAC plant PDF report that clearly shows that data is collected Check the YES ☐ Documented rationale and
energy consumption data or regularly, including benchmarking data, for at least the availability of an justification that collected data
NO ☐
its energy consumption data last month (preceding the inspection). Data can be HVAC plant and reference data are
recorded at least once a day presented as a table with numeric values, if it includes energy comparable (e.g. normalisation,
and benchmarked to defined the time stamp for each reading, or a in a graph. consumption similarities, previous time
reference objects (e.g. Example 1: A report that benchmarks HVAC plant report that intervals, exceptions) should be
B1 different HVAC plant in the energy consumption data against a target value(s) compares current available.
same building) or reference values with
Example 2: PDF weather-normalised energy reports
time intervals for the same previous periods
(HDD and CDD) for the last 12 months compared to the
building (e.g. monthly using
previous year or a baseline year or a target value.
TBM)?
OR SIMILAR reports accompanied with an explanation of
how this alternative proof fulfils the specific
requirement

Is there energy-relevant PDF report for at least the last month (preceding the Check the YES ☐
process data from HVAC sub- inspection) containing energy performance data for availability of
NO ☐
systems that is used to relevant HVAC sub-systems: benchmark report
analyse deviations compared Example 1: A report that compares the actual efficiency for a significant
to defined benchmarks (e.g. of heating/cooling generators, e.g. “coefficient of HVAC sub-system
big deviation from design performance”, with the design COP; (consuming over
B2 coefficient of performance 15% of total
Example 2: A report that compares the measured supply
COP) using TBM? building energy
and return water temperature difference for a heat
consumption)
generator with the design temperature difference;
that compares
OR SIMILAR reports accompanied with an explanation of current values
how this alternative proof fulfils the specific with defined
requirement benchmarks

8
European Building Automation Controls Association

COMPLIANCE
SELF-DECLARATION Boundary Conditions /
SELF-DECLARATION COMPLIANCE SUPPORTING VERIFICATION
COMPLIANCE QUESTIONS PREREQUISITES for the
ID RECORDS CHECKS RESPONSE
(answered by Building BACS capabilities to be
(provided by Building Owner) (conducted by
Owner) effective
Building Inspector)
B3 Is there automatic detection PDF report showing manual override events for main Check the availability YES ☐
of HVAC equipment running in HVAC plant items. It is not necessary to cover a specific of a record (e.g. use
NO ☐
manual override/exception period (the building may be running always in auto) but activity log print-out)
mode logged and flagged the report must show at least the last test run on site or for the last 3 examples
centrally? the commissioning of the BACS of when HVAC
equipment was set in
manual operation for
more than 24hrs

B4 Is there automatic detection A PDF report showing fault alarms for main HVAC plant Check the availability YES ☐
of faults in HVAC equipment items. of a record showing
NO ☐
that is it logged and flagged The proof depends on the HVAC systems present in the fault alarms related to
centrally? specific building main HVAC plant
equipment were
- equipment faults in heating system including the
reported by the BACS
equipment fault for at least 1 heat generator
- equipment faults in air-conditioning system including
the equipment fault for at least 1 cooling generator
- equipment faults in ventilation system including the
equipment fault for at least 1 major fan
- equipment faults of room HVAC equipment for at least
1 of the representative rooms

9
European Building Automation Controls Association

COMPLIANCE
SELF-DECLARATION Boundary Conditions /
SELF-DECLARATION COMPLIANCE SUPPORTING VERIFICATION
COMPLIANCE QUESTIONS PREREQUISITES for the
ID RECORDS CHECKS RESPONSE
(answered by Building BACS capabilities to be
(provided by Building Owner) (conducted by
Owner) effective
Building Inspector)
B5 Is there automatic detection PDF report showing relevant HVAC system Check the availability YES ☐
of loss in efficiency in the events/alarms: of an event report for
NO ☐
HVAC-related TBS with central Example 1: A report that notifies deviations of current considerable
indication of detected faults efficiency for heating/cooling generator, e.g. deviations in the
and alarms/diagnosing “coefficient of performance”, from its efficiency in the operating parameters
functions that is used to last heating/cooling season; of a main HVAC sub-
derive corrective actions and system
Example 2: A report that notifies deviations in pressure
fix recurring suboptimal
drop across a main AHU;
energy performance?
(according to EN ISO 52120 OR SIMILAR reports accompanied with an explanation of
7.3.2) how this alternative proof fulfils the specific
requirement

B6 Is the person responsible for A PDF extract/print screen from Alarm/Activity log, Check the availability YES ☐ There has to be a
TBM informed by BACS about provided by the BACS, that shows the last 3 examples of BACS activity log nominated responsible
NO ☐
any main HVAC equipment when the BACS system sent a message/alarm about record person(s) for the operation
faults? faults on main HVAC equipment to the responsible and optimization of the
person, also including the status of this alarm (e.g. TBM. There should be a
acknowledged status) process in place to inform &
involve the nominated
Building operators instantly
to implement corrective
actions for HVAC
equipment faults

10
European Building Automation Controls Association

COMPLIANCE
SELF-DECLARATION Boundary Conditions /
SELF-DECLARATION COMPLIANCE SUPPORTING VERIFICATION
COMPLIANCE QUESTIONS PREREQUISITES for the
ID RECORDS CHECKS RESPONSE
(answered by Building BACS capabilities to be
(provided by Building Owner) (conducted by
Owner) effective
Building Inspector)
B7 Is the person responsible for A PDF extract/print screen from Alarm/Activity log, Check the availability YES ☐ There must be a nominated
TBM/ responsible Building provided by the BACS, that shows the last 3 examples of BACS activity log responsible person(s) for
NO ☐
Operator reliably and quickly when the BACS system sent a message/alarm about record the operation and
informed by BACS about deviations from expected energy performance of HVAC optimization of the TBM.
energy waste and/or comfort and / or indoor comfort conditions to the responsible There should be a process
compromised operation of person, also including the status of this alarm (e.g. in place to inform & involve
HVAC systems with an acknowledged status) the nominated Building
indication of where/how to Examples for Energy Waste: operator instantly to
take corrective action? implement corrective
1. Notification of pre-defined % deviation (for a pre-
defined duration) between the measured supply and actions to maintain and
return water temperature difference for a heating coil improve EE
and the design temperature difference;
2. Notification of pre-defined % deviation (for a pre-
defined duration) between the actual efficiency of
heating/cooling generators, e.g. “coefficient of
performance”, and the design efficiency
3. Notification related to any of the evidence provided
in the supporting records used in B1-B6 checks
Examples for Comfort-Compromised Operation:
1. Notification of deviations in space temperature
outside of operator-defined comfort range.
2. Notification of deviations in CO2 level above the
operator-defined comfort acceptable limit.

11
European Building Automation Controls Association

COMPLIANCE
SELF-DECLARATION Boundary Conditions
SELF-DECLARATION COMPLIANCE SUPPORTING VERIFICATION
COMPLIANCE QUESTIONS / PREREQUISITES for
ID RECORDS CHECKS RESPONSE
(answered by Building the BACS capabilities
(provided by Building Owner) (conducted by
Owner) to be effective
Building Inspector)
(c) ALLOWING COMMUNICATION with CONNECTED TBS and OTHER APPLIANCES inside the building, and BEING INTEROPERABLE with TBS across
DIFFERENT TYPES of PROPRIETARY TECHNOLOGIES, DEVICES and MANUFACTURERS
Can BACS manage relevant A PDF report of an example that shows coordination in the Check the availability YES ☐
information with other operation of 2 or more individual systems/devices: of an example BACS
NO ☐
connected TBS and devices, Example 1: Interlock between heating and cooling control to report that proves
and enable "global" cross prevent simultaneous heating and cooling exchange of
TBS optimization strategies information between
Example 2: Combined light/blind/HVAC control in rooms
while improving operation BACS connected
at "individual" equipment Example 3: Sequencing of different heat/cold generators systems / devices
level? OR SIMILAR reports accompanied with an explanation of how
C1 this alternative proof fulfils the specific requirement

Does BACS control the A PDF print screen/photo of BACS connected and controlled Check the availability YES ☐ Only connected HVAC-
start/stop of HVAC-related equipment / devices, e.g. chiller, fan coil unit, lighting system, of selected print related systems and
NO ☐
systems / devices? solar protection system, solar heat system, CHP screens that show appliances in the sense
If possible, provide an example with different proprietary BACS control of various of EPBD are in scope –
C2 technologies. systems / devices refer to the Starting
section S
Example: Re-use the check for A4, and add the make/model
number of the system/device, e.g. air handling unit, domestic
hot water system, room controls from different manufacturer
that BACS interfaces with

12
European Building Automation Controls Association

COMPLIANCE
SELF-DECLARATION Boundary Conditions
SELF-DECLARATION COMPLIANCE SUPPORTING VERIFICATION
COMPLIANCE QUESTIONS / PREREQUISITES for
ID RECORDS CHECKS RESPONSE
(answered by Building the BACS capabilities
(provided by Building Owner) (conducted by
Owner) to be effective
Building Inspector)
Does BACS have the A PDF print screen/photo of BACS interface that shows the Check the availability YES ☐ Only connected HVAC-
possibility potential to set possibility for setpoint adjustment for BACS connected and of selected print related systems and
NO ☐
and modify setpoints for controlled systems / devices, e.g. air handling unit, domestic screens that clearly appliances in the sense
HVAC-related systems / hot water system, room controls by different manufacturer show setpoint of EPBD are in scope –
C3 devices? adjustment refer to the Starting
Example: Re-use the check for A5, and add the make/model
number of the system/device, e.g. air handling unit, domestic possibilities section S
hot water system, room controls from different manufacturer
that BACS interfaces with

13

You might also like