Burnertronic Fault Codes

Version
1.02
Datum
d Bearbeiter
07.12.10 A. Röver
Kommentar
Ergänzung zu Störung 600: die
Freigabe

Referenz Nummer ist die angezeigte


Meldung
1.01 18.11.10 A. Röver Errors with channel number are A. Röver
groups of errors
1.00 18.11.10 S. Burkersroda Initial Version

Dokument basierend auf Dokumentenvorlage: V1.02

LAMTEC Meß- und Regeltechnik


für Feuerungen GmbH & Co KG Tel. +49 341 49 12 335 Email: info@lamtec.de
Karl-Heine-Straße 99 Fax. +49 341 49 12 336 Web: www.lamtec.de
D-04229 Leipzig
LAMTEC Meß- und Regeltechnik
für Feuerungen GmbH & Co KG

1 Content
1 Content................................................................................................................................2
2 Faults...................................................................................................................................3
2.1 Fault codes 0 - 99..............................................................................................................3
2.2 Fault codes 100 - 199........................................................................................................4

t
2.3 Fault codes 200 - 299........................................................................................................5
2.4 Fault codes 300 - 399........................................................................................................6
2.5 Fault codes 400 - 499........................................................................................................7
2.6 Fault codes 600 - 699........................................................................................................7

f
2.7 Fault codes 700 - 799........................................................................................................8
2.8 Fault codes 800 - 899......................................................................................................11
2.9 Fault codes 900 - 999......................................................................................................12
3 Assignment of Configuration fault 107................................................................................14
4 Assignment of internal fault 999.........................................................................................15

r a
d
Burnertronic Fault Codes 2 von 25
4 Assignment of internal fault 999 LAMTEC Meß- und Regeltechnik
für Feuerungen GmbH & Co KG

2 Faults
Note: If the item “additional information” is declared, the given information can be found in
parameter 1 and parameter 2 of the fault message.

2.1 Fault codes 0 - 99

t
Fault Code 0:
Description: Unknown Fault (internal failure)

f
Additional Information: -

Fault Code 1:
Description: Pre-ventilation signal still active.
Additional Information: -

a
Fault Code 2:
Description: Extraneous light detected.
Additional Information: -

r
Fault Code 3:
Description: Flame extinguished during the ignition.
Additional Information: -

Fault Code 4:

d
Description: Flame extinguished during the operation.
Additional Information: -

Fault Code 5:
Description: Flame signal doesn’t appear during the first safety time.
Additional Information: -

Fault Code 6:
Description: Flame signal extinguishes during the stabilization time.
Additional Information: -

Fault Code 7:
Description: Flame signal extinguishes during the first safety time.
Additional Information: -

Fault Code 8:
Description: Flame signal extinguishes during the second safety time.
Additional Information: -

Fault Code 9:
Description: Flame signal does not appear during the safety time.
Additional Information: -

Burnertronic Fault Codes 3 von 25


4 Assignment of internal fault 999 LAMTEC Meß- und Regeltechnik
für Feuerungen GmbH & Co KG

Fault Code 10:


Description: Flame signal extinguishes during the safety time.
Additional Information: -

Fault Code 11:


Description: Monitoring for extraneous light does not last the required 5

t
seconds.
Additional Information: -

f
Fault Code 13:
Description: Main flame appears during the ignition.
Additional Information: -

2.2 Fault codes 100 - 199

a
Fault Code 103:
Description: Uncorrectable error in Miscell-Data.
Additional Information: -

r
Fault Code 105:
Description: Uncorrectable error in Curve set!
Additional information: Curve set / Fuel number

Fault Code 106:

d
Description: Parameters between both controllers are inconsistent.
Additional information: Parameter number

Fault Code 107:


Description: Invalid configuration
Additional information: For details see chapter 3 Assignment of Configuration fault 107

Fault Code 120:


Description: Different operation modes on both controllers.
Additional information: -

Fault Code 121+x:


Description: Correction is out of range.
Additional information: Channel number (x)

Fault Code 141+x:


Description: Channel feedback changes too fast.
Additional information: Channel number (x)

Fault Code 151+x:


Description: Recirculation flap is deactivated.
Additional information: Channel number (x)

Burnertronic Fault Codes 4 von 25


4 Assignment of internal fault 999 LAMTEC Meß- und Regeltechnik
für Feuerungen GmbH & Co KG

Fault Code 160:


Description: Actuator doesn’t move, i.e. gives no position feedback.
Additional information: Par1: channel number
Par2: desired direction: 0-backward, 1-forward

Fault Code 161:

t
Description: Actuator can’t find reference position.
Additional information: Channel number

f
Fault Code 162:
Description: Actuator returns invalid position (difference to target position too
large).
Additional information: Channel number

Fault Code 163:

a
Description: Actuator position changes too fast, e.g. slippage.
Additional information: Channel number

r
Fault Code 170:
Description: Short circuit of LDR flame detector.
Additional information: -

Fault Code 191+x:


Description: First monitoring region/band exceeded.

d
Additional information: Channel number (x)

2.3 Fault codes 200 - 299

Fault Code 201+x:


Description: First monitoring region/band undercut.
Additional information: Channel number (x)

Fault Code 211+x:


Description: Second monitoring region/band exceeded.
Additional information: Channel number (x)

Fault Code 221+x:


Description: Second monitoring region/band undercut.
Additional information: Channel number (x)

Fault Code 231+x:


Description: Air / fuel ratio control is stuck.
Additional information: Channel number (x)

Burnertronic Fault Codes 5 von 25


4 Assignment of internal fault 999 LAMTEC Meß- und Regeltechnik
für Feuerungen GmbH & Co KG

2.4 Fault codes 300 - 399

Fault Code 320:


Description: Open circuit / broken wire of Load input.
Additional information: -

t
Fault Code 321+x:
Description: Open circuit / broken wire of feedback channel.
Additional information: Channel number (x)

f
Fault Code 351:
Description: Invalid change of fuel while burner is running.
Additional information: -

a
Fault Code 352:
Description: Invalid combination of fuel selection signals (no signals).
Additional information: -

r
Fault Code 353:
Description: Invalid combination of fuel selection signals (several signals).
Additional information: -

Fault Code 362:

d
Description: Fault shut-down because of burner maintenance was not
executed.
Additional information: -

Fault Code 363:


Description: Lowest valid O2 value deceeded.
Additional information: -

Fault Code 371:


Description: Output for internal load is defective.
Additional information: -

Fault Code 372:


Description: Difference of the load values between main and supervisor
controller too large.
Additional information: -

Fault Code 381+x:


Description: Difference of correction values between main and supervisor
controller too large.
Additional information: Channel number (x)

Burnertronic Fault Codes 6 von 25


4 Assignment of internal fault 999 LAMTEC Meß- und Regeltechnik
für Feuerungen GmbH & Co KG

Fault Code 391:


Description: Curve-set has changed during programming.
Additional information: -

Fault Code 393:


Description: Emergency shutdown activated.

t
Additional information: -

Fault Code 394:

f
Description: Burner on/off signal from the user interface turned off
unexpectedly.
Additional information: -

2.5 Fault codes 400 - 499

a
Fault Code 451+x:
Description: Not all channels in ignition position while in operating mode for
ignition.
Additional information: Channel number (x)

r
2.6 Fault codes 600 - 699

Fault Code 600:


Description: Program monitoring time (FAT) exceeded.

d
Additional information: Reference no. (old message number, see
UserInterface_Menüstruktur.doc in UI references)

Fault Code 601:


Description: Failure during leakage test: gas pressure still active.
Additional information: -

Fault Code 602:


Description: Failure during leakage test: no gas pressure detected
Additional information: -

Fault Code 603:


Description: Manual venting of the gas line required!
Additional information: -

Fault Code 607:


Description: Invalid drop of the recognition of ignition position.
Additional information: -

Fault Code 608:


Description: Invalid drop of the boiler safety chain.
Additional information: -

Burnertronic Fault Codes 7 von 25


4 Assignment of internal fault 999 LAMTEC Meß- und Regeltechnik
für Feuerungen GmbH & Co KG

Fault Code 609:


Description: Invalid drop of the gas safety chain.
Additional information: -

Fault Code 610:


Description: Invalid drop of the oil safety chain.

t
Additional information: -

Fault Code 611:

f
Description: Gas pressure too low.
Additional information: -

Fault Code 613:


Description: Air pressure signal missing.

a
Additional information: -

Fault Code 617:


Description: Permanent ignition flame extinguished during the operation.

r
Additional information: -

Fault Code 624:


Description: Oil pressure too low.
Additional information: -

d
2.7 Fault codes 700 - 799

Fault Code 711:


Description: Invalid change of the operation mode.
Additional information: Internal state information

Fault Code 713:


Description: Invalid signal combination at input terminals during operation mode
“Burner OFF”.
Additional information: -

Fault Code 714:


Description: Invalid signal combination at input terminals during operation mode
“Burner Ready”.
Additional information: -

Fault Code 715:


Description: Invalid signal combination at input terminals during operation mode
“Pre-ventilation”.
Additional information: -

Burnertronic Fault Codes 8 von 25


4 Assignment of internal fault 999 LAMTEC Meß- und Regeltechnik
für Feuerungen GmbH & Co KG

Fault Code 716:


Description: Invalid signal combination at input terminals during operation mode
“Ignition position”.
Additional information: -

Fault Code 717:

t
Description: Invalid signal combination at input terminals during operation mode
“Ignition”.
Additional information: -

f
Fault Code 719:
Description: Fuel valves opened too long without a flame.
Additional information: -

Fault Code 720:

a
Description: Ignition transformer activated too long.
Additional information: -

r
Fault Code 721:
Description: Ignition valve opened too long.
Additional information: -

Fault Code 722:


Description: Fuel valves opened in maintenance mode.

d
Additional information: -

Fault Code 723:


Description: Ignition process takes too long.
Additional information: -

Fault Code 724:


Description: Gas valves opened while oil is selected.
Additional information: -

Fault Code 725:


Description: Oil valves opened while gas is selected.
Additional information: -

Fault Code 726:


Description: Main gas 1 opened without main gas 2.
Additional information: -

Fault Code 727:


Description: Main gas 1 opened unexpectedly.
Additional information: -

Burnertronic Fault Codes 9 von 25


4 Assignment of internal fault 999 LAMTEC Meß- und Regeltechnik
für Feuerungen GmbH & Co KG

Fault Code 728:


Description: All three gas valves opened too long.
Additional information: -

Fault Code 729:


Description: Ignition process takes too long (without ignition burner).

t
Additional information: -

Fault Code 730:

f
Description: Maintenance mode without ignition burner.
Additional information: -

Fault Code 731:


Description: Ignition valve opened without ignition burner.

a
Additional information: -

Fault Code 732:


Description: Invalid signal combination at input terminals during operation.

r
Additional information: -

Fault Code 734:


Description: Pre-ventilation time exceeded.
Additional information: -

d
Fault Code 739:
Description: Leakage test: Main gas valve 2 opened too long.
Additional information: -

Fault Code 740:


Description: Leakage test: Main gas valve 1 leaky.
Additional information: -

Fault Code 741:


Description: Leakage test: Main gas valve 1 opened too long
Additional information: -

Fault Code 742:


Description: Leakage test: Main gas valve 2 leaky.
Additional information: -

Fault Code 743:


Description: Flame monitoring: flame burns too long after shutdown.
Additional information: -

Burnertronic Fault Codes 10 von 25


4 Assignment of internal fault 999 LAMTEC Meß- und Regeltechnik
für Feuerungen GmbH & Co KG

Fault Code 745:


Description: Program monitoring time exceeded.
Additional information: -

Fault Code 746:


Description: Solenoid valve cannot be switched off.

t
Additional information: -

Fault Code 747:

f
Description: Leakage test: Venting into the burner not allowed.
Additional information: -

Fault Code 759:


Description: “Setting-mode” left automatically after 24 hours.

a
Additional information: -

Fault Code 760:


Description: Fuel change is not allowed during setting-mode.

r
Additional information: -

Fault Code 763:


Description: Different curve selection on main and supervisor controller.
Additional information: -

d
Fault Code 764:
Description: CO-regulator – internal failure
Additional information: -

2.8 Fault codes 800 - 899

Fault Code 800:


Description: Parameter defective.
Additional information: Parameter number

Fault Code 801:


Description: Channel control mode is inconsistent between both controllers
(Fatal error, no automatic restart)
Additional information: Channel number

Fault Code 802:


Description: Integration of a channel into the fuel/air ratio control takes too long
(one automatic restart)
Additional information: Channel number

Burnertronic Fault Codes 11 von 25


4 Assignment of internal fault 999 LAMTEC Meß- und Regeltechnik
für Feuerungen GmbH & Co KG

Fault Code 803:


Description: Channel is locked too long (fatal error, no automatic restart)
Additional information: Channel number

Fault Code 804:


Description: Channel mode of the fuel/air ratio control does not fit to the

t
selection (fatal error, no automatic restart)
Additional information: Channel number

f
Fault Code 805:
Description: Directly controlled channel drives to an invalid position, i.e. a
channel that is not deactivated nor controlled by fuel/air ratio
control
Additional information: Channel number + Date

a
Fault Code 806:
Description: Implausible Channel setpoint of the main controller.
Additional information: Channel number, difference

r
Fault Code 888:
Description: Fault lock out active!
Additional information: Reference number

Fault Code 889:

d
Description: Remote fault release occurred in a too short interval.
Additional information: -

2.9 Fault codes 900 - 999

Fault Code 921:


Description: Output terminal for oil valve defective
Additional information: -

Fault Code 922:


Description: Output terminal for ignition valve defective
Additional information: -

Fault Code 923:


Description: Output terminal for gas valve 1 defective
Additional information: -

Fault Code 924:


Description: Output terminal for gas valve 2 defective
Additional information: -

Burnertronic Fault Codes 12 von 25


4 Assignment of internal fault 999 LAMTEC Meß- und Regeltechnik
für Feuerungen GmbH & Co KG

Fault Code 925:


Description: Output terminal for ignition transformer defective
Additional information: -

Fault Code 928:


Description: Output terminal for oil pump defective

t
Additional information: -

Fault Code 929:

f
Description: Output terminals for fan defective
Additional information: -

Fault Code 986:


Description: Dynamic range test recognized invalid feedback.

a
Additional information: Channel number

Fault Code 987:


Description: Change-over during staged operation takes too long.

r
Additional information: -

Fault Code 988:


Description: Fuel selection relay in the DFM is defective.
Additional information: -

d
Fault Code 989:
Description: Plausibility test of actuator feedback with programmed curve set
failed.
Additional information: -

Fault Code 990:


Description: Low voltage of mains supply detected.
Additional information: -

Fault Code 996:


Description: Secure parameter writing could not be finished. Device blocked
Additional information: -

Fault Code 999:


Description: Internal failure! For details see chapter 4 Assignment of internal
fault 999
Additional information: -

Burnertronic Fault Codes 13 von 25


4 Assignment of internal fault 999 LAMTEC Meß- und Regeltechnik
für Feuerungen GmbH & Co KG

3 Assignment of Configuration fault 107

Parameter1 Description
1 Too many channels in configuration parameter 804.

t
Permanent ignition burner configured (parameter 302, 303), but no ignition
3 flame monitoring device present. (parameter 800).
4 No fuel change via Off or ignition burner allowed with the mixed firing.

f
7 Fuel change via Off and an unlimited post ventilation configured.
13 Australian flame monitoring configured, but no ignition flame monitoring device.
17 Operation of the Auxiliary burner not allowed at the BT300.
18 Standby operation at BT300 not allowed.

a
19 Invalid fuel change selected.
20 BT300 only with separate ignition point.
21 "Ignition With Fan", only useful with pure oil devices.

r
22 Staged operation only useful with pure oil devices.
23 3-staged operation only works without ignition burner.
There are missing points in the curve, which are necessary in a staged
50 operation
24 Permanent operation not allowed (Featureflag)

d
25 Fuel change not allowed (Featureflag)
26 Too many channels (Featureflag)
30 Multiple terminals defined for one signal, Terminal configuration invalid
31 No output terminal for fan or transformer available
An output terminal is needed for the ignition valve, but is not available in the
31 actual terminal configuration.
32 Necessary outputs for operation with oil not available (Oil pump or oil valve)
33 Necessary outputs for operation with gas not available (gas valve)
40 No input terminal for the air pressure monitor available.
No input terminal for the oil safety chain available (oil pressure min will not be
41 monitored directly, because it can be included in the safety chain)
42 No input terminal for the gas safety chain or minimum gas pressure available.
43 The feedback line for the fuel selection is not mapped, but is required
At the staged oil operation the LOAD_UP und LOAD_DOWN signals have to be
connected, if no burner-firing-rate controller is connected, because the stages
44 are selected by those inputs.

Burnertronic Fault Codes 14 von 25


4 Assignment of internal fault 999 LAMTEC Meß- und Regeltechnik
für Feuerungen GmbH & Co KG

4 Assignment of internal fault 999

t
Param1 Param2 Comment
0-1999 Internal Faults generated from within System API

f
10 return value of m_PwrOn_uiInitAPI() m_PwrOn_uiInitAPI() failed
20 0 CRC32 check of ROM failed
21 0 Cyclic CRC32 check of ROM during runtime failed
40 0 m_PwrOn_bLoadEEPROM() failed

200
201
202
203
204
0
0
0
0
0

r a
last destination element is no member of sER.sP
last destination element is no member of sER.sM
last destination element is no member of sER.sC
last destination element is no member of sER.sH
destination is no member of sER.sX

d
210 Start address of EEPROM block refresh cycle timeout expired
211 Start address of EEPROM block uncorrectable error in EEPROM block
212 State of refresh cycle invalid state
215 EEPROM error address uncorrectable error in Parameter Set
216 EEPROM error address uncorrectable error in Miscell-Data
217 EEPROM error address uncorrectable error in Curve Set
220 0 pucDst == NULL
222 EEPROM start address invalid EEPROM address
240 EEPROM start address write beyond end of safety area!
241 EEPROM start address start address in safety area is no multiple of 3
242 EEPROM start address write beyond end of non-safety area!
243 EEPROM start address start address is in reserved area!
244 Required FIFO Space not enough FIFO space
250 Destination address in RAM Readback error while refreshing - possibly defective RAM cell

Burnertronic Fault Codes 15 von 25


4 Assignment of internal fault 999 LAMTEC Meß- und Regeltechnik
für Feuerungen GmbH & Co KG

Param1 Param2 Comment

300 0 Timout sICom.uiRxLiveTimer expired

t
301 0 Timout sICom.uiTxLiveTimer expired
350 0 Timeout sICom.uixLiveTimer expired

f
360 0 Timeout at the waiting of the acknowledgment of DUAL_BEF_CHECK_PARAM
361 0 FIFO full!
380 uiBPP_HPPunktNr Error at the call of uiPutPunkt()
381 0 The command leakage test during BM_FAT_KALTCHECK occurred!

a
382 0 Timeout at the cyclic parameter verification
383 uiBCP_AnzParam[0] Value of parameter DUAL_BEF_CHANGE_PARAM1: Invalid value in the input buffer
384 uiBCP_AnzParam[1] Value of parameter DUAL_BEF_CHANGE_PARAM2: Invalid value in the input buffer

r
385 sRx.Buffer.ui[ucRxOK-1] Cyclic parameter verification: different parameters between HP and UP!
[uiSTARTBEF+47]
386 Parameter index PowerOn parameter verification: different parameters between HP and UP!
410 Mask for negative half wave inputs Detected positive half-wave on terminal input!

d
411 input status received from UP different input status between controllers
412 0 The readback input of the fuel selection relays contacts in the dual fuel is invalid. DFM
probably defect.
420 uiI Input status of digital input on HP and UP is inconsistent (>20ms)
430 ucPin2Test Pin short circuit test detected an error!
currently tested pin not configured as output or is stuck at 1
431 ucPin2Test Pin short circuit test detected an error!
short-circuit between pins, pull-up of input stage defective or pin is externally stuck at 0
440 0 sIO.sIn.uiTestSignalTimeout expired
450 0 Main power relay (K2) does not switch correctly to off when out of power.
451 Relay Relay does not switch correctly, when relay power is enabled (for details see enum
teRelais)
460 Error parameter Failure of relays power switching or readback of relay coils of K1 or K2
Param2: Bit 0 is set if readback line of K1 is erroneous, Bit 1 is set if readback line of K2 is
erroneous

Burnertronic Fault Codes 16 von 25


4 Assignment of internal fault 999 LAMTEC Meß- und Regeltechnik
für Feuerungen GmbH & Co KG

Param1 Param2 Comment


461 Error parameter Readback status of relay K1 or K2 differs from desired switching status, relay probably
defect.

t
Param2:
Bit 0: nominal state of K1
Bit 1: nominal state of K2

f
Bit 8: state of readback line of K1
Bit 9: state of readback line of K2

500 0 timeout while waiting for end of write cycle

a
501 0 SLA+W has been transmitted; NO ACK has been received
502 0 SLA+R has been transmitted; NO ACK has been received
503 0 Data byte has been transmitted; NO ACK has been received

r
504 0 BUS error due to an illegal START or STOP condition
505 0 Arbitration lost in SLA+R/W or Data bytes
510 content of I²C status register unknown/invalid state!
600 sSRCtrl.uiOffset correction of defective triple in Safety RAM structure failed

d
610 Destination address invalid destination address
620 Destination address invalid destination address
630 Destination address invalid destination address

700 0 CPU selftest failed


701 State of selfttest state machine state-event-machine failed with AC_ERR
710 Watchdog test error state Watchdog selftest failed
711 Watchdog test state invalid default case
720 Voltage monitor test to perform invalid default case
721 Voltage monitor error state Supply voltage monitor selftest failed
722 Voltage monitor test state invalid default case
730 Relay release error state Relay release circuit selftest failed
731 Relay release test state invalid default case
740 Relay PWM error state Relay PWR release circuit selftest failed

Burnertronic Fault Codes 17 von 25


4 Assignment of internal fault 999 LAMTEC Meß- und Regeltechnik
für Feuerungen GmbH & Co KG

Param1 Param2 Comment


741 Relay PWM test state invalid default case

t
800 Watchdog release pattern Trigger release patterns are invalid!
810 Feed index invalid Feed Index

f
820 Watchdog Trigger mode invalid Trigger Mode
830 0 no valid watchdog trigger received (frequency or duty cycle invalid)

900 Error code fault from LPC_API error handler

a
920 0 invalid entry in iStoerResRam
930 Masked Fault Code uiMaskedFaultCode out of range!

r
1200 0 flame signal doesn't disappear during self-test
1200 0 flame signal doesn't disappear during self-test
1210 Ionization flame detector test state invalid default case
1220 Ionization flame detector test duration UP is missing test impulses

d
1221 Ionization flame detector test duration test signal duration too short
1222 Ionization flame detector test duration test signal duration too long

1240 0 detected short circuit of LDR


1240 0 detected short circuit of LDR
1250 AD Value circuit selftest failed, A/D value out of expected range
1250 AD Value circuit selftest failed, A/D value out of expected range
1260 LDR flame detector test state invalid default case
1270 LDR flame detector test duration test interval too long
1271 LDR flame detector test duration HP released test pin too late
1272 LDR flame detector test duration HP released test pin too early

1290 uiMyFlames XOR uiPartnerFlames Flame signals on both controllers are inconsistent (bit 0: main flame, bit 1: ignition flame)

Burnertronic Fault Codes 18 von 25


4 Assignment of internal fault 999 LAMTEC Meß- und Regeltechnik
für Feuerungen GmbH & Co KG

Param1 Param2 Comment


1300 0 pointer to transmit buffer is NULL

t
1400 Actuator number H_SA_INTERFACE_INVALID_ACTUATOR_TYPE
1401 Actuator number H_SA_INTERFACE_INVALID_DIRECTION

f
1405 0 H_SA_INTERFACE_WRONG_RAMP_CALCULATION
1406 0 ulGradientMax <= ulGradientDesired
1410 0 H_SA_INTERFACE_WRONG_RAMP_CALCULATION
1411 0 H_SA_INTERFACE_ERROR_TIMING

a
1415 Actuator number psActuator->ucSANumber Invalid!
1416 Actuator number psActuator->ucSANumber Invalid!
1420 Actuator number H_SA_INTERFACE_WRONG_RAMP_CALCULATION

r
1430 Actuator number H_SA_FEEDBACK_WRONG_FEEDBACK
1435 Actuator number H_SA_PLAUSIB_ACTUATOR_OUT_OF_RANGE
1436 Actuator number H_SA_PLAUSIB_SECTION_COUNT_OUT_OF_RANGE
1440 Actuator number H_SA_REFERENCE_SEARCH_NO_REFERENCE_FOUND

d
1450 Actuator number H_SA_STEPCALC_CALL_COUNT_OVERFLOW
1451 Actuator number H_SA_STEPCALC_SECTIONCOUNT_OUT_OF_RANGE
1452 Actuator number H_SA_STEPCALC_INVALID_DIRECTION
1453 Actuator number H_SA_STEPCALC_SECTIONCOUNT_OUT_OF_RANGE
1454 Actuator number H_SA_STEPCALC_INVALID_DIRECTION
1455 Actuator number H_SA_STEPCALC_WRONG_STATUS
1460 0 U_SA_INTERFACE_INVALID_ACTUATOR_TYPE
1461 0 U_SA_INTERFACE_INVALID_DIRECTION
1470 Actuator number U_SA_FEEDBACK_INVALID_DIRECTION
1471 Actuator number U_SA_FEEDBACK_INVALID_DIRECTION
1472 Actuator number U_SA_FEEDBACK_WRONG_FEEDBACK
1480 Actuator number U_SA_REFERENCE_SEARCH_INVALID_ACTUATOR_TYPE
1490 Actuator number psActuator->ucSANumber Invalid!

Burnertronic Fault Codes 19 von 25


4 Assignment of internal fault 999 LAMTEC Meß- und Regeltechnik
für Feuerungen GmbH & Co KG

Param1 Param2 Comment

1500 0 timeout while sending ICOM command

t
1501 0 timeout while waiting for ACK of ICOM command
1502 0 timeout while waiting for end of actuator initilization

f
1503 0 timeout while waiting for end of actuator initilization
1504 0 timeout while waiting for end of actuator initilization
1505 Actuator Number HP: Invalid configuration. Parameter for Actuator Type should never be different from 1 or 2
1505 Actuator Number ÜP: Invalid configuration. Parameter for Actuator Type should never be different from 1 or 2

2000
2001

2100

r a
2000-3999 Internal faults generated from within application (FAT and System)

unknown event, for the event handling mechanism


too many events for even queue

Invalid buffer input

d
2101 EEProm probably defective

2200 Invalid Index for SQBLData00


2201 Invalid Index for SQBLData01
2202 Invalid Index for SQBLData02
2203 Invalid Index for SQBLData03
2204 Invalid Index for SQBLData04
2205 Invalid Index for SQBLData05
2206 Invalid Index for SQBLDataKurven
2207 Invalid Index for SQBLDataPara
2208 Invalid Index for SQBLData15
2209 Data request for data block, but no transmission.

2300 Invalid state

Burnertronic Fault Codes 20 von 25


4 Assignment of internal fault 999 LAMTEC Meß- und Regeltechnik
für Feuerungen GmbH & Co KG

Param1 Param2 Comment


2301 Invalid state
2302 Deleting curve

t
2303 Invalid state
2304 Invalid state

f
2305 Unauthorized parameter number (does not exist)
2306 Invalid state (cold check)
2307 Cold check
2308 Cold check

a
2309 Cold check
2310 Invalid state
2350- Cold check

r
2354

2400 Attempt to write to a modbus register


2401 Modbus register described

2500

2600
2601

2700

2800
d
Parameter with access level > 4

Does not find the operating mode


Transfer forbidden

Deleting curve, left EI

The air pressure was not droped but the burner still starts
2801 It was opened more than one valve in the cold check
2802 Maintenance mode on the main controller is active, but there is no maintenance mode
parameterized
2803 Maintenance mode active but it is still ignite

Burnertronic Fault Codes 21 von 25


4 Assignment of internal fault 999 LAMTEC Meß- und Regeltechnik
für Feuerungen GmbH & Co KG

Param1 Param2 Comment


2804 Burner starts, while the supervisor controller is blocked
2805 Burner starts, while no reference test was made

2900

3000

3100
Program load by the timer to high

f t
All errors, for which no error number was registered

Error message of a password module

a
3101 Error message of the password module

3200 Internal overflow, intermediate result does not fit in the variable

r
3201 Overflow of the end result

3230 UP Version differs from HP version

d
3250 Invalid parameter for staged burner-firing-rate controller

3300 Sequence control BrennUm default case entered


3301 Sequence control leakage test default case entered
3302 Sequence control FAT default case
3303 Sequence control post ventilation default case
3304 Sequence control pre ventilation default case entered
3305 Sequence control Ingnition default case entered

4000-4999 Internal faults generated from within Application (Air/Fuel Ratio Control)

4000 0 No curve point to the load of the ignition point


4001 0 ucPIdx_R >= ucPunktAnzahl
4001 0 ucPIdx_R >= ucPunktAnzahl

Burnertronic Fault Codes 22 von 25


4 Assignment of internal fault 999 LAMTEC Meß- und Regeltechnik
für Feuerungen GmbH & Co KG

Param1 Param2 Comment

4100 sRampe.ucState invalid value of sRampe.ucState

4200

4300
4301
4302
Fuel/air ratio control mode

sAsyVBDta.iRSFakt
0
0
Invalid value of ucVBMode

f t
Curve: value range of feedback 16 times bigger than value range of set value
Curve: value range of setpoint or feedback value too small
No active air channel is defined (parameterization error)

4400
4401
4402
4403
4404
4405
ucSteuerArtEx
0
ucSteuerArtEx
ucKanStat
0
ucKanStat
a
invalid value of ucSteuerArtEx
Time out while waiting

r
invalid value of ucSteuerArtEx
(ucKanStat & Def_VKM2_MSK) != Def_VKM2_DVAL
Time out while waiting
Disabled channel is moving!

d
4406 ucRzStState[ucKnr] invalid value of ucRzStState[ucKnr]
4407 ucVBStat invalid value of ucVBStat

4500 0 Ramp time == 0!


4501 Channel number IfKM_VB() returned 0

4600 Desired value invalid value of ucVorgabe


4601 (sRampe.uc2VBKMsk | In mode VSM_NOVB control channels must not be active
sRampe.ucVBKMsk)
4602 sRampT.ucNState Unknown default-State
4603 sRampe.ucState invalid value of sRampe.ucState

4700 0 Ramp time expired!


4701 Transferred channel number out of the permitted range

Burnertronic Fault Codes 23 von 25


4 Assignment of internal fault 999 LAMTEC Meß- und Regeltechnik
für Feuerungen GmbH & Co KG

Param1 Param2 Comment


4702 Transferred channel number out of the permitted range
4703 Transferred channel number out of the permitted range

t
4704 Transferred channel number out of the permitted range
4705 Channel number Transferred channel number out of the permitted range

f
4706 Channel number Transferred channel number out of the permitted range
4707 Channel number Transferred channel number out of the permitted range
4708 Channel number Transferred channel number out of the permitted range
4709 Channel number Transferred channel number out of the permitted range

a
4710 Channel number Transferred channel number out of the permitted range
4711 Channel number Transferred channel number out of the permitted range
4712 Channel number Transferred channel number out of the permitted range

r
4713 Channel number Transferred channel number out of the permitted range
4714 Channel number Transferred channel number out of the permitted range
4715 Channel number Transferred channel number out of the permitted range
4716 Channel number Transferred channel number out of the permitted range

d
4717 Channel number Transferred channel number out of the permitted range

4800 uiActTmr ucErg > 0!


4801 ucSgIdx Parameter modification Knf_uiActuatorDirX while fuel/air ratio control is active or outside the
operation modes “Burner Off” or “Fault”
4900 ucKnr Division by 0

5000-5999 Internal faults generated from within Application (Load control)

5000 enInterneLastSeq invalid value of enInterneLastSeq


5001 0 Ambiguous DPS+ / DPS- for load stage selection
5002 0 Curve error: curve for n-staged oil or channel speed for actuators was not determined
5003 0 Invalid parameter in function call

Burnertronic Fault Codes 24 von 25


4 Assignment of internal fault 999 LAMTEC Meß- und Regeltechnik
für Feuerungen GmbH & Co KG

Param1 Param2 Comment


5004 0 Timers for the control of the stage switching time do not fit together: Switching time of
internal load < supervised time for set load

t
5005 0 Invalid stage curve with internal load set by the stage controller
5007 0 Invalid load value while adjusting the staged oil curve

f
5008 0 Invalid stage- activation control mode

6000-6999 Internal faults generated from within UP Application-Control (Air/Fuel Ratio Control)

a
6000 ucSteuerArtEx unknown Mode of Channel-Control
6001 ucBetrMoNr Overadressing of Array was detected
6100 Channel number unknown Mode of Channel-Control

r
6200 0 Avoid an endless loop
6201 0 Avoid an endless loop
6300 ucSMState Detect undefined State of Statemachine
6400 Channel number Division by 0

d
Burnertronic Fault Codes 25 von 25