You are on page 1of 5

Lightning Attachment Models and

Perfect Shielding Angle of Transmission Lines


Pantelis N. Mikropoulos' and Thomas E. Tsovilis
High Voltage Laboratory, School of Electrical & Computer Engineering, Faculty of Engineering,
Aristotle University ofThessaloniki, Thessaloniki, Greece,
lpnm@eng.auth.gr

proposed statistical model. The interdependence of perfect


Abstract- General relationships for the estimation of the shielding angle, transmission line height and minimum
perfect shielding angle of overhead transmission lines have been current causing flashover of insulation is demonstrated as
derived by performing shielding analysis on the basis of several influenced by the lightning attachment model employed in
lightning attachment models, including a recently introduced
statistical one. The interdependence of perfect shielding angle, shielding analysis. Findings are discussed and further
transmission line height and minimum current causing flashover elucidated through an application to typical 150 kV and
of insulation is demonstrated as influenced by the lightning 400 kV lines of the Hellenic transmission system. The
attachment model employed in shielding analysis. There is a applicability of lightning attachment models in perfect
great variability in perfect shielding angle among lightning shielding angle calculations has been evaluated based on the
attachment models; this is demonstrated for 150 kV and 400 kV
lines of the Hellenic transmission system. The applicability of shielding performance of transmission lines.
lightning attachment models in perfect shielding angle
calculations is evaluated based on the shielding performance of II. PERFECT SHIELDING ANGLE FORMULATION BASED ON
transmission lines; the IEEE Std 1243:1997 yields consistent
DIFFERENT LIGHTNING ATTACHMENT MODELS
results with respect to the shielding performance of the lines.
Index Terms-- Direct stroke shielding, lightning, perfect A. Electrogeometric models
shielding angle, overhead transmission lines. Electrogeometric models have historically been employed
in transmission line shielding providing acceptable protection
I. INTRODUCTION
against direct lightning strokes to phase conductors and they
The shielding design of transmission lines against direct are still widely used [2]. Shielding analysis according to
lightning strokes to phase conductors, that is the appropriate electrogeometric models follows based on Fig.l. The striking
positioning of shield wires with respect to phase conductors, distance to conductors, S, is assumed to be related solely to
can be achieved by implementing electrogeometric models the prospective lightning peak current, I and can be associated
[1], representative of their application is the method to striking distance to earth surface, D, by using a factor y as
suggested by IEEE Standard 1243:1997 [2], which employ a
B
relation between striking distance and lightning peak current S=AI =yD (1)
in their calculations [3]-[12]. Alternatively, shielding design
may be realized by employing models based on more solid where I is in kA, S, D are in meters and factors A, Band yare
physical ground of lightning attractiveness [13]-[21], called given in Table I as proposed by different authors. For a
hereafter, in accordance with Waters [22], generic models. design lightning peak current equal to the minimum current
Recently, a statistical approach in shielding design has been causing flashover of insulation, L, the latter can be calculated
introduced [23]-[25] by implementing a lightning attachment based on the geometrical and electrical characteristics of the
model derived from scale model experiments [26]-[28]. transmission line [2], a descending lightning leader will strike
A perfect shielding is achieved when lightning strokes to the phase conductor when reaching the arc between M and
possessing peak current greater than the minimum current N; hence, a shielding failure width, W, is defmed (Fig. 1).
causing flashover of insulation are intercepted. Apparently, With decreasing shielding angle a, W decreases, thus there is
some of the less intense strokes may not be intercepted by the a critical shielding angle which corresponds to W = 0,
shield wires and strike to phase conductors, however these are hereafter called perfect shielding angle, ape Geometrical
not expected to cause flashover. In practice, an effective analysis similar to that given in [29] yields the following
shielding of transmission lines against direct lightning strokes expression, approximating well the perfect shielding angle
to phase conductors is realized based on an acceptable
shielding failure flashover rate.
The present study provides general relationships for the
a
p
= sin- l (1_r hm+hpJ
2AI:
(2)
estimation of the perfect shielding angle of transmission lines,
which have been derived by performing shielding analysis on where, factors A, B, yare given in Table I, Ie is in kA, and
the basis of electrogeometric, generic and the recently h« (m), hp (m) are defmed in Fig. 1.

978-0-947649-44-9/09/$26.00 ©2009 IEEE

Authorized licensed use limited to: Stantec Inc. HQ. Downloaded on May 12,2023 at 06:15:27 UTC from IEEE Xplore. Restrictions apply.
C. Generic models
Following Eriksson's work, generic lightning attachment
models have been developed which also consider the
inception of the upward connecting discharge emerging from
the prospective struck object [14]-[21]. Thus, based on
different leader inception criteria, expressions of the attractive
I'
~, radius of an object, R, defined as the longest lateral distance
,
I
from the object where lightning attachment occurs, have been
I
hm I
I D proposed in the general form
I hp
I
I
I (5)
I

Fig. 1. Shielding analysis according to electrogeometric models. h m shield where R is in meters, I (kA) is the prospective lightning peak
wire height; hp phase conductor height; a shielding angle; S striking distance
to shield wire and phase conductor; D striking distance to earth surface; current, h (m) is the struck object height and factors ~ E and
W shielding failure width. F are listed in Table II according to different authors.
TABLE I TABLE II
FACTORS A, B AND )ITO BE USED IN(I) FACTORS ?,E AND F TO BE USED IN(5)

Electrogeometric model A B )I Generic model ? E F


Wagner & Hileman [3] 14.2 0.42 I Rizk [I5] 1.57 0.45 0.69
Iforh <18m Petrov et al. [19]' 0.47 0.67 0.67
S. Ait-Amar & Berger [21] 3 0.20 0.67
Young et al. [4] 27)1 0.32 ~forh >18m
462-h • using as h in (5) the object height plus 15 m.
h: shield wire height
Armstrong & Whitehead [5] 6.72 0.80 l.ll Following a shielding analysis similar to that of Rizk [15],
Brown & Whitehead [6] 7.1 0.75 l.ll
according to Fig. 2 a shielding failure will occur when the
Love [7] 10 0.65 I
descending lightning leader enters the shielding failure width
Whitehead [8] 9.4 0.67 I
W, which is given as
Anderson [Ill and IEEE WG [121 8 0.65 liP'

. IEEE Std 1243 [2] 10 0.65 liP"


p = 0.64 for UHV lines, 0.8 for EHV lines, and I for other hnes
(6)
•'p = 0.36+0.17In(43-h) for h < 40 rn, p = 0.55 for h > 40 m where h is
the phase conductor height Thus, for a design lightning peak current equal to the
B. Eriksson's model minimum current causing flashover of insulation L; the
Eriksson [13], proposed a modified electrogeometric model perfect shielding angle, corresponding to W = 0, is given with
by introducing the attractive radius in shielding design, the aid of(5) and (6) as
defmed as the "capture" radius at which the upward leader
initiated at the struck object intercepts the downward
lightning leader. Attractive radius, R, is given as (7)

R = 0.67ho.6 I°.74 (3)


where factors ~, E, and F are given in Table II, Ie is in kA,
where R is in meters, h (m) is the struck object height and I and h« (m) and hp (m) are defmed in Fig. 2. It must be
(kA) is the prospective lightning peak current. Eriksson, mentioned that models [19] and [21] do not refer to the
performing a shielding analysis similar to that of the transmission line geometry; however, employing these
electrogeometric models, used, instead of S in Fig. I, the models in perfect shielding angle calculations may provide
attractive radius to draw arcs from the shield wire and phase useful information concerning their applicability.
conductor up to the phase conductor height. Based on D. Statistical model
geometrical analysis similar to that given in [29], the perfect Recently, investigations on the interception probability of
shielding angle can be expressed as an air terminal through scale model experiments made
possible the formulation of distributions for striking distance
and interception radius [27], and, thus, a statistical approach
(4) in shielding design has been proposed in [24]. Interception
radius is considered as statistical quantity with a mean value,
referring to 50% interception probability , called critical
where hm (m) and hp (m) are defined in Fig.l, and Rm (m), interception radius, Rei> and a standard deviation a. It is given
Rp (m) are calculated from (3) for I = L; with reference the striking distance to earth surface as

Authorized licensed use limited to: Stantec Inc. HQ. Downloaded on May 12,2023 at 06:15:27 UTC from IEEE Xplore. Restrictions apply.
Adopting from [7] the values of 10 and 0.65 for factors A' and
B', respectively and by using the value of CI for negative
- -0- - :..=- - '" lightning according to Table III, equation (11) becomes
L>
: a ""o---.-----"-i---l~
[2.72I~.65ln(11m/ hp )-0.0I zh1,;3 ]
I
I _ -I
I
I ap-tan () . (12)
I
I
l1m-hp
I
I
I
Equation (12) refers to critical interception and is used
hereafter for perfect shielding angle calculations according to
the statistical model. It is important to note that for a given
Fig. 2. Shielding analysis according to generic models . a shielding angle; h m,
hp height of shield wire and phase conductor, respectively ; Rm, Rp attractive
transmission line geometry the interception radii Rm and Rp
radius of shield wire and phase conductor, respectively; W shielding failure are statistical quantities; they vary, besides lightning peak
width; LlR horizontal separation distance between shield wire and phase current, with interception probability according to (8).
conductor . Therefore also the shielding failure width, as given by (6), is
accordingly statistically distributed indicating, thus, a non
(8) deterministic value for the perfect shielding angle.

III. RESULTS AND DISCUSSION


where Rei is in meters, h (m) is the struck object height and
D (m) is the striking distance to earth surface. The Fig. 3 shows the variation of the perfect shielding angle, ap ,
coefficients CI and Cz, and (J in formula form are given in with shield wire height, as calculated by employing the
Table III [27]. lightning attachment models described in Section II. It is
obvious that there is a great variability in ap among models;
TABLE III
however, all models are consistent in predicting a smaller ap
COEFFICIENTS C], Cz AND EXPRESSION OF a TO BE USED IN (8)
with increasing shield wire height and decreasing minimum
Positive Lightning Negative Lightning current causing flashover of insulation, L: Considering that
the curves in Fig. 3 were obtained for a fixed ratio of hlhm
0.235 0.90 1.9(h/DYO.7S 0.272 1.24 5.0{h/ D t A3
and that Ie is directly related to the basic insulation level of
the transmission line, it can be deduced that all models are
Equation (8) can be used for shielding analysis by using a consistent in predicting a smaller perfect shielding angle with
known relation between striking distance to earth surface, D, increasing transmission line height and decreasing insulation
and lightning peak current, I, commonly expressed as level of the line. However, the effect of transmission line
D = A'IB' . Thus, based on Fig. 2 and by using the critical height is much more pronounced for the electrogeometric
interception radii of shield wire and phase conductor as models; the latter, thus also IEEE Std [2], generally yield
calculated from (8), the shielding failure width W at critical smaller ap , even negative values for relatively high lines
interception is contrary to the generic, Eriksson's and statistical model
yielding positive ap values. The variability of perfect
(9) shielding angle among lightning attachment models is also
obvious in Table IV referring to typical 150 kV and 400 kV
Hence, the perfect shielding angle at critical interception is
given as

20 25 20 25
Shieldwire heit:lht(m) Shield wire height (m )
where h« (m) and hp (m) are defmed in Fig. 2 and CI is given 40 40

in Table III. By considering also the neighboring effects on ~ [,s'= : : : - - - -


~20 ~~20
30

the shield wire interception radius of the phase conductor ~


~_ ~,~~ ::::
[25], [28], equation (10) becomes I': [.':[ '>.'.~:~
-;

-'-~. ~ ~'-~".~ ::::!i~' ··· I':


v

>., _.:~~~ ~:.~3.t.


~ '10 hpIh",-O .7S,I . -SkA I~ "' · 10 -,
~-20
a..
- Eled rogeoll19lnc rrode ls
- - IEEE Std 1243
...
' ...
Fsl
16j
~-20
a..
~~O~~~I;':~~
- -IEEEStd1243
<,,
' -,
-30 _ • • Slahstica lmodal "', 2 -30 - · · Stallst ical rrode l ' .

W W ~ ~ 45 20 W ~ ~ ~

Shield wire height (m) Shield wire height (m)

Fig. 3. Perfect shielding angle as a function of shield wire height.

Authorized licensed use limited to: Stantec Inc. HQ. Downloaded on May 12,2023 at 06:15:27 UTC from IEEE Xplore. Restrictions apply.
lines of the Hellenic transmission system. In Table IV, the TABLE VI
EFFECTIVE SHIELDING ANGLE OF TYPICAL 150kV AND 400 kV OVERHEAD
calculated values of ap correspond to line geometries at the LINES OF THE HELLENICTRANSMISSION SYSTEM
tower and average height along the line; the basic line Lightningattachmentmodel 150kV 400kV
parameters are given in Table V. All models yield greater ap Wagner & Hileman 3 21 13
at average transmission line height than at the tower as a Young et al. 4 34 26
result of the sag of the shield wire and phase conductor; this Armstrong & Whitehead 5 17 12
Brown & Whitehead 6 16 11
also indicates that ap varies along the length of the line. The
Love 7 24 18
electrogeometric models yield generally negative ap values, Whitehead 8 23 18
which deviate considerably from the actual shielding angles Anderson fill and IEEE WG 12 18 6
of the studied transmission lines. However, in practice an IEEE Std 1243 2 18 9
effective shielding of transmission lines is realized based on Eriksson 13 7 15
Rizk 15 30 29
an acceptable shielding failure flashover rate, SFFOR. For a Petrovet al. 19 24 25
given line geometry SFFOR (flashovers/1 OOlan/year), Ait-Amar & Berger 21 24 12
normally used together with backflashover rate to estimate Mikropoulos & Tsovilis 25 19 15
the expected outage rate of a transmission line, is given as
From Tables IV and VI it can be deduced that the effective
L VSF shielding angle shows less variability than perfect shielding
SFFOR = O.2Ng f W(I)j(I)dI (13) angle among models . It is important to note that for SFFOR =
r.
0.05 flashovers/lOOkm/year the electrogeometric models, in
where Ng (flashes/kmvyear) is the ground flash density,JtI) is agreement with the other models, yield positive shielding
the probability density function of the stroke current angles agreeing with the actual shielding angles (Table V).
amplitude distribution, W (m) is the shielding failure width The applicability of a lightning attachment model in perfect
and I MSF (kA) is the maximum shielding failure current. For a shielding angle calculations can be evaluated based on the
design value of SFFOR = 0.05 flashovers/lOOkm/year, shielding performance of transmission lines; this is illustrated
commonly used in shielding design and by assuming Ng = 5 in Fig. 4. Lines with actual shielding angles greater than the
flashes/kmvyear, the effective shielding angles for the studied corresponding calculated perfect shielding angle should
overhead lines are listed in Table VI. These calculations refer experience shielding failures, whereas lines with actual
to average line height, employ the JtI) distribution suggested shielding angles smaller than the corresponding calculated
in [30] and values for Ie and I MSF found according to [2] and perfect shielding angle should show superior shielding
[31], respectively, and consider the variation of W with the performance. The shielding performance of the lines is
lightning attachment model used for shielding analysis . generally underestimated for Eriksson's model [13] (Fig. 4a)
and for the electrogeometric models [5] and [6], whereas
TABLEIV
PERFECT SHIELDING ANGLE OF TYPICAL 150kV AND 400 kV OVERHEAD overestimated for Rizk 's [15] (Fig. 4b) and Young et al. [4]
LINES OF THE HELLENIC TRANSMISSION SYSTEM models . The IEEE Std [2] (Fig . 4c), electrogeometric models
150kV 400kV [3], [7] and [8] as well as the statistical model [25] (Fig. 4d)
Tower
Average
Tower
Average yield generally consistent results with respect to shielding
Liahtninz attachmentmodel heizht height performance of transmission lines, whereas inconsistency
Wagner & Hileman 3 -12 -I -12 -4
Young et al. 4 16 23 12 18 have been found for the generic models [19] and [21].
Armstrong& Whitehead 5 -35 -21 -15 -7
50
Brown & Whitehead 6 -36 -23 -18 -10 (a) Eriksson [13)

Love 7 -14 -3 -3 4
Whitehead 8 -16 -5 -5 3
Anderson [J 1l and IEEE WG 12 -32 -18 -31 -22
IEEE Std 1243 2 -24 -10 -22 -9
Eriksson 13 6 2 15 14
Rizk 15 15 17 21 22
Petrovet al. 19 12 12 18 18 ." -rc
Ait-Amar & Berger 21 5 6 7 7 50
Mikronoulos & Tsovilis 25 0 7 3 8 40 (c) IEEE SId 1243(2 )

TABLEV

...
PARAMETERS OF TYPICAL 150kV AND 400 kV OVERHEAD LINES OF THE "
HELLENIC TRANSMISSION SYSTEM '
Shield Upper phase Shielding Shieldingangle
Operating
voltage
t, wire conductor angle at at average
(kA) height height tower height
(kV) (Deg)
(m) (m) (Deg)
150 4 33.0 27.8 31 23 Fig. 4. Perfect shielding angle versus actual shielding angle. Empty and solid
400 8 45.1 36.5 19 16 points depict lines showing superior shielding performance [5] and
Sag of shIeldWIre and phase conductor. 5.5 m and 8.6 m, respectIvely experiencingshieldingfailures [32], respectively.

Authorized licensed use limited to: Stantec Inc. HQ. Downloaded on May 12,2023 at 06:15:27 UTC from IEEE Xplore. Restrictions apply.
Finally, it must be mentioned that in the present analysis [10] T. Suzuki, K. Miyake and T. Shindo, "Discharge path model in model
test of lightning strokes to tall mast," IEEE Trans. Power App. Syst.,
subsequent strokes possessing current magnitudes bigger than vol. PAS-I00, no. 7, pp. 3553-3562, Jul. 1981.
minimum current causing flashover of insulation have not [11] 1. G. Anderson, "Transmission Line Reference Book - 345 kV and
been considered in determining SFFOR of transmission lines. Above," Second Edition, 1982, chapter 12, Electric Power Research
Institute, Palo Alto, California.
[12] IEEE Working Group, "A Simplified method for estimating lightning
performance of transmission lines," IEEE Trans. Power App. Syst.,
IV. CONCLUSIONS
vol. PAS-I04, no. 4, pp. 919-932, Apr. 1985.
General relationships for the estimation of the perfect [13] A. J. Eriksson, "An improved electrogeometric model for transmission
line shielding analysis," IEEE Trans. Power Del., vol. PWRD-2, no. 3,
shielding angle of transmission lines have been derived by pp. 871-886, Apr. 1987.
performing shielding analysis on the basis of several lightning [14] P. Chowdhuri and A. K. Kotapalli, "Significant parameters in
attachment models. There is a great variability in perfect estimating the striking distance of lightning strokes to overhead lines,"
IEEE Trans. Power Del., vol. 4, no. 3, pp.1970-1981, Jul. 1989.
shielding angle among lightning attachment models. The [15] F. A. M. Rizk, "Modeling of transmission line exposure to direct
effect of the transmission line height is much more lightning strokes," IEEE Trans. Power Del.,vol. 5, no. 4, pp. 1983-
pronounced for the electrogeometric models; the latter, thus 1997, Oct. 1990.
[16] L. Dellera and E. Garbagnati, "Lightning stroke simulation by means of
also IEEE Standard 1243:1997, generally yield smaller the leader progression model," IEEE Trans. Power Del., vol. 5, no. 4,
perfect shielding angles, even negative ones for relatively pp. 2009-2029, Oct. 1990.
high transmission lines contrary to the generic, Eriksson's [17] F. A. M. Rizk, "Modeling of lightning incidence to tall structures,"
IEEE Trans. Power Del., vol. 9, no. 1, pp. 162-193, Jan. 1994.
and statistical model yielding positive perfect shielding [18] N. I. Petrov and R. T. Waters, "Determination of the striking distance
angles. The effective shielding angle calculated by assuming of lightning to earthed structures," Proc. Roy. Soc., London A, vol. 450,
an acceptable shielding failure flashover rate is less variable pp. 589-601, 1995.
[19] N. I. Petrov, G. Petrova and R. T. Waters, "Determination of attractive
among lightning attachment models. These fmdings are area and collection volume of earthed structures," in Proc. 25th Int.
demonstrated through an application to typical 150 kV and Conf. Lightning Protection, Rhodes, Greece, 2000, pp. 374-379.
400 kV overhead lines of the Hellenic transmission system. [20] F. D'Alessandro and 1. R. Gumley, "A collection volume method for
the placement of air terminals for the protection of structures against
The applicability of lightning attachment models in perfect lightning," Elsevier J. Electrostat., vol. 50, pp. 279-302, 2001.
shielding angle calculations has been evaluated based on the [21] S. Ait-Amar and G. Berger, "Lightning protection modelling:
shielding performance of transmission lines reported in Applications to revisited electrogeometrical model," in Proc. 17th Int.
Conf. Gas Discharges and their Application, Cardiff, U.K., 2008, pp.
literature. Consistent results have been derived for the 517-520.
statistical model and some electrogeometric models, as well [22] R. T. Waters, "Lightning phenomena and protection systems," in
as for the IEEE Standard 1243:1997. Advances in High Voltage Engineering, ser. Inst. Elect. Eng. Power
Energy, M. Haddad and D. Warne, Eds. London U.K.: Inst. Elect. Eng.
2004, vol. 40, pp. 107-114.
[23] P. N. Mikropoulos and Th. E. Tsovilis, "Interception radius and
ACKNOWLEDGEMENTS shielding against lightning," 29 th Int. Conf. Lightning Protection,
Uppsala, Sweden, 2008, paper 4-10, pp. 1-11.
Th. E. Tsovilis wishes to thank the Research Committee of [24] P. N. Mikropoulos and Th. E. Tsovilis, "Interception probability and
Aristotle University of Thessaloniki for the support provided shielding against lightning," IEEE Trans. Power Del., vol. 24, no. 2,
by a merit scholarship. pp. 863-873, Apr. 2009.
[25] P. N. Mikropoulos and Th. E. Tsovilis, "Interception probability and
neighboring effects: Implications in shielding design against lightning,"
REFERENCES IEEE Trans. Power Del., submitted.
[26] P. N. Mikropoulos and Th. E. Tsovilis, "Experimental investigation of
[1] R. H. Golde, Lightning Protection. London U.K.: Academic Press, the Franklin rod protection zone," in Proc. 15th Int. Symp. High Voltage
1977, vol. 2, pp. 545-564. Eng., Ljubljana, Slovenia, 2007, paper 461, pp.1-5.
[2] IEEE Guide for improving the Lightning performance of Transmission [27] P. N. Mikropoulos and Th. E. Tsovilis, "Striking distance and
Lines, IEEE Std. 1243-1997, Dec. 1997. interception probability," IEEE Trans. Power Del., vol. 23, no. 3, pp.
[3] C. F. Wagner and A. R. Hileman, "The lightning stroke-II," AlEE 1571-1580, Jul. 2008.
Trans. PA&S, pp. 622-642, Oct. 1961. [28] P. N. Mikropoulos, Th. E. Tsovilis and T. Ananiadis, "The effect of an
[4] F. S. Young, 1. M. Clayton and A. R. Hileman, "Shielding of earthed object on the interception radius of the Franklin rod: An
transmission lines," IEEE Trans. Power App. Syst., vol. S82, no. 4, pp. experimental investigation," Med Power'08, Thessaloniki, Greece,
132-154, 1963. 2008, paper No. 77, pp. 1-6.
[5] H. R. Amstrong and E. R. Whitehead, "Field and analytical studies of [29] A. R. Hileman, "Shielding of transmission lines," Insulation
transmission line shielding," IEEE Trans. Power App. Syst., vol. 87, pp. Coordination for Power Systems, CRC Press, Taylor & Francis Group,
270-281, Jan. 1968. New York, 1999, pp. 244-254.
[6] G. W. Brown and E. R. Whitehead, "Field and analytical studies of [30] Lightning and Insulator Subcommittee of the T&D Committee,
transmission line shielding-II," IEEE Trans. Power App. Syst., vol. 88, "Parameters of Lightning Strokes: A Review," IEEE Trans. Power
pp. 617-626, May 1969. Del., vol. 20, no. 1, pp. 346-358, Jan. 2005.
[7] E. R. Love, "Improvements in lightning stroke modeling and [31] P. N. Mikropoulos and Th. E. Tsovilis, "Lightning attachment models
applications to design of EHV and UHV transmission lines," M.Sc. and maximum shielding failure current: Application to transmission
thesis, Univ. Colorado, Denver, CO, 1973. lines," in Proc. Power Tech, Bucharest, Romania, 2009, accepted.
[8] E. R. Whitehead, "CIGRE survey of the lightning performance ofEHV [32] IEEE Working Group, "Estimating lightning performance of
transmission lines," Electra, vol. 33, pp. 63-89, 1974. transmission Lines II - updates to analytical models," IEEE Trans.
[9] A. M. Mousa and K. D. Srivastava, "Modelling of power lines in Power Del., vol. 8, no. 3, pp. 1254-1267, Jul. 1993.
lightning incidence calculations," IEEE Trans. Power Del., vol. 5, no.l,
pp.303-310,Jan.1981.

Authorized licensed use limited to: Stantec Inc. HQ. Downloaded on May 12,2023 at 06:15:27 UTC from IEEE Xplore. Restrictions apply.

You might also like