System
SVC MANUAL(Exploded View)
MODEL : AH Series

CAUTION
Before Servicing the unit, read the safety precautions in General SVC manual.
Only for authorized service personnel.
1. Specification
Indoor
AHNW096A0 AHNW126A0 AHNW146A0 AHNW166A0
Indoor Units
(H09SNE) (H12SNE) (H14SNE) (H16SNE)
Combination Outdoor Units AHUW096A0 AHUW126A0 AHUW146A0 AHUW166A0
Nominal Power Input W 135 205 205 205
Nominal Running Current without Electric Heater A 0.59 0.89 0.89 0.89
Operation Range Cooling(Fan coil unit) °C 6 ~ 30 6 ~ 30 6 ~ 30 6 ~ 30
(Min.~Max.) Cooling(Under floor) °C 16 ~ 30 16 ~ 30 16 ~ 30 16 ~ 30
Leaving Water Heating(Fan coil unit or Radiator) °C 15~55℃ ( * * 20~55℃)
Temperature Heating(Under floor) °C 15~55℃ ( * * 20~55℃)
Pump Type - Canned type for hot water circulation
Steps of Speed EA 2 (In Max. / Med. / Min., Min. step is not used)
Power Input W 135 205 205 205
Water Flowrate Limit LPM At least 12 At least 12 At least 12 At least 12
Heat Exchanger Type - Brazed Plate HEX Brazed Plate HEX Brazed Plate HEX Brazed Plate HEX
Number of Plate EA 46 60 60 60
Quantity EA 1 1 1 1
Expansion Vessel Volume liter 8 8 8 8
Water Pressure(Max.) bar 3 3 3 3
Water Pressure(Pre) bar 1 1 1 1
Strainer Mesh Size mm 1x1 1x1 1x1 1x1
Material - Stainless Steel Stainless Steel Stainless Steel Stainless Steel
Electric Heater Type - Sheath Sheath Sheath Sheath
Number of Heating Coil EA 2 2 2 2
Capacity Combination kW 2+2 3+3 3+3 3+3
Operation - Automatic Automatic Automatic Automatic
Heating Steps Step 2 2 2 2
Power Supply Ø / V / Hz 1 / 240 / 50 1 / 240 / 50 1 / 240 / 50 1 / 240 / 50
Rated Current A 16.7 25 25 25
Maximum Current(MCA) A 21 32 32 32
Water Circuit Safety Valve bar 3 3 3 3
Entering Side Diameter inch Male PT 1 Male PT 1 Male PT 1 Male PT 1
Leaving Side Diameter inch Male PT 1 Male PT 1 Male PT 1 Male PT 1
Manometer - O O O O
Drain Valve / Fill Valve - O O O O
Shut Off Valve - O O O O
Air Vent - O O O O
Refrigerant Circuit Gas Side Diameter mm(inch) 15.88 (5/8) 15.88 (5/8) 15.88 (5/8) 15.88 (5/8)
Liquid Side Diameter mm(inch) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8)
Dimensions Unit(W x H x D) mm 850 x 490 x 315 850 x 490 x 315 850 x 490 x 315 850 x 490 x 315
Packed Unit(W x H x D) mm 1082 x 563 x 375 1082 x 563 x 375 1082 x 563 x 375 1082 x 563 x 375
Weight Unit kg 52 54.5 54.5 54.5
(Without water) Packed Unit kg 57 61.5 61.5 61.5
*Sanitary Water Tank Type - Indirect heating(+ Electric heater)
(Field Supply) Heater Capacity kW Max. 3
Power Supply Ø / V / Hz 1 / 230 / 50
Power Supply Type - Separated power source
Thermal Protector Range °C Max. 90
Relay Contactor - Needed
ELB A 40
Sensor Adaptor Diameter mm(inch) 12.7 (1/2)
Accessory Kit - LG Supply
Note : 1. The specification may be subject to change without prior notice for purpose of improvement.
2. * : This information is given as a guideline about the connection of sanitary water tank
3. ** : This specification is data when electric heater is not used.

Copyright ©2010 LG Electronics. Inc. All right reserved. -2-


LGE Internal Use Only
Only for training and service purposes
AHNW09606A0 AHNW09A06A0 AHNW09806A0
Indoor Units
(NH09SNG) (NH09SNK) (NH09SNP)
Combination Outdoor Units AHUW096AN AHUW096AN AHUW096AN
Nominal Power Input W 135 135 135
Nominal Running Current without Electric Heater A 0.59 0.59 0.59~
Operation Range Cooling(Fan coil unit) °C 6~30 6~30 6~30
(Min.~Max.) Cooling(Under floor) °C 16~30 16~30 16~30
Leaving Water Heating(Fan coil unit or Radiator) °C 15~55℃ ( * * 20~55℃)
Temperature Heating(Under floor) °C 15~55℃ ( * * 20~55℃)
Pump Type - Canned type for hot water circulation
Steps of Speed EA 2 (In Max. / Med. / Min., Min. step is not used)
Power Input W 135 135 135
Water Flowrate Limit LPM At least 12 At least 12 At least 12
Heat Exchanger Type - Brazed Plate HEX Brazed Plate HEX Brazed Plate HEX
Number of Plate EA 46 46 46
Quantity EA 1 1 1
Expansion Vessel Volume liter 8 8 8
Water Pressure(Max.) bar 3 3 3
Water Pressure(Pre) bar 1 1 1
Strainer Mesh Size mm 1x1 1x1 1x1
Material - Stainless Steel Stainless Steel Stainless Steel
Electric Heater Type - Sheath Sheath Sheath
Number of Heating Coil EA 2 3 3
Capacity Combination kW 3+3 2+2+2 2+2+2
Operation - Automatic Automatic Automatic
Heating Steps Step 2 2 2
Power Supply Ø / V / Hz 1/230/50 3/220/50 3/380-415/50
Rated Current A 27 16 9
Maximum Current(MCA) A 30 17 10
Water Circuit Safety Valve bar 3 3 3
Entering Side Diameter inch Male PT 1 Male PT 1 Male PT 1
Leaving Side Diameter inch Male PT 1 Male PT 1 Male PT 1
Manometer - 0 0 0
Drain Valve / Fill Valve - 0 0 0
Shut Off Valve - 0 0 0
Air Vent - 0 0 0
Refrigerant Circuit Gas Side Diameter mm(inch) 15.88 (5/8) 15.88 (5/8) 15.88 (5/8)
Liquid Side Diameter mm(inch) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8)
Dimensions Unit(W x H x D) mm 850 x 490 x 315 850 x 490 x 315 850 x 490 x 315
Packed Unit(W x H x D) mm 1082 x 563 x 375 1082 x 563 x 375 1082 x 563 x 375
Weight Unit kg 52 52 52
(Without water) Packed Unit kg 57 57 57
*Sanitary Water Tank Type - Indirect heating(+ Electric heater)
(Field Supply) Heater Capacity kW Max. 3
Power Supply Ø / V / Hz 1 / 230 / 50
Power Supply Type - Separated power source
Thermal Protector Range °C Max. 90
Relay Contactor - Needed
ELB A 40
Sensor Adaptor Diameter mm(inch) 12.7 (1/2)
Accessory Kit - LG Supply
MCCB A 32
Note : 1. The specification may be subject to change without prior notice for purpose of improvement.
2. * : This information is given as a guideline about the connection of sanitary water tank
3. ** : This specification is data when electric heater is not used.

Copyright ©2010 LG Electronics. Inc. All right reserved. -3-


LGE Internal Use Only
Only for training and service purposes
Indoor Units AHNW09604A1 AHNW09606A1 AHNW09A06A1 AHNW09806A1

Combination Outdoor Units AHUW096A1


Nominal Power Input W 135
Nominal Running Current without Electric Heater A 0.59
Operation Range Cooling(Fan coil unit) °C 6 ~ 30
(Min.~Max.) Cooling(Under floor) °C 16 ~ 30
Leaving Water Heating(Fan coil unit or Radiator) °C 15~55℃ ( * * 20~55℃)
Temperature Heating(Under floor) °C 15~55℃ ( * * 20~55℃)
Pump Type - Canned type for hot water circulation
Steps of Speed EA 2(In Max. / Med. / Min., Min. step is not used)
Power Input W 135
Water Flowrate Limit LPM At least 12
Heat Exchanger Type - Brazed Plate HEX
Number of Plate EA 54
Quantity EA 1
Expansion Vessel Volume liter 8
Water Pressure(Max.) bar 3
Water Pressure(Pre) bar 1
Strainer Mesh Size mm 1X1
Material - Stainless steel
Electric Heater Type - Sheath Sheath Sheath Sheath
Number of Heating Coil EA 2 2 3 3
Capacity Combination kW 2+2 3+3 2+2+2 2+2+2
Operation - Automatic Automatic Automatic Automatic
Heating Steps Step 2 2 2 2
Power Supply Ø / V / Hz 1/240/50 1/240/50 3/220/50 3/380~415/50
Rated Current A 16.7 26 16 9
Maximum Current(MCA) A 21 33 20 12
Water Circuit Safety Valve bar 3
Entering Side Diameter inch Male PT 1
Leaving Side Diameter inch Male PT 1
Manometer - O
Drain Valve / Fill Valve - O
Shut Off Valve - O
Air Vent - O
Refrigerant Circuit Gas Side Diameter mm(inch) 15.88 (5/8)
Liquid Side Diameter mm(inch) 9.52 (3/8)
Dimensions Unit(W x H x D) mm 850 X 490 X 315
Packed Unit(W x H x D) mm 1082 X 563 X 375
Weight Unit kg 48 48 52 52
(Without water) Packed Unit kg 55 55 59 59
*Sanitary Water Tank Type - Indirect heating(+Electric heater)
(Field Supply) Heater Capacity kW Max. 3
Power Supply Ø / V / Hz 1/230/50
Power Supply Type - Separated Power Source
Thermal Protector Range °C Max. 90
Relay Contactor - Needed
ELB A 40
Sensor Adaptor Diameter mm(inch) 12.7 (1/2)
Accessory Kit - LG Supply
MCCB A 32
Note : 1. The specification may be subject to change without prior notice 2. * : This information is given as a guideline about the connection of
for purpose of improvement. sanitary water tank

Copyright ©2010 LG Electronics. Inc. All right reserved. -4-


LGE Internal Use Only
Only for training and service purposes
Indoor Units AHNW16606A1 AHNW16A06A1 AHNW16806A1

Combination Outdoor Units AHUW128A1 / AHUW148A1 / AHUW168A1


Nominal Power Input W 205 205 205
Nominal Running Current without Electric Heater A 0.89 0.89 0.89
Operation Range Cooling(Fan coil unit) °C 6 ~ 30 6 ~ 30 6 ~ 30
(Min.~Max.) Cooling(Under floor) °C 16 ~ 30 16 ~ 30 16 ~ 30
Leaving Water Heating(Fan coil unit or Radiator) °C 15~55℃ ( * * 20~55℃)
Temperature Heating(Under floor) °C 15~55℃ ( * * 20~55℃)
Pump Type - Canned type for hot water circulation
Steps of Speed EA 2(In Max. / Med. / Min., Min. step is not used)
Power Input W 205 205 205
Water Flowrate Limit LPM At least 15 At least 15 At least 15
Heat Exchanger Type - Brazed Plate HEX
Number of Plate EA 76 76 76
Quantity EA 1 1 1
Expansion Vessel Volume liter 8 8 8
Water Pressure(Max.) bar 3 3 3
Water Pressure(Pre) bar 1 1 1
Strainer Mesh Size mm 1X1 1X1 1X1
Material - Stainless steel Stainless steel Stainless steel
Electric Heater Type - Sheath Sheath Sheath
Number of Heating Coil EA 2 3 3
Capacity Combination kW 3+3 2+2+2 2+2+2
Operation - Automatic Automatic Automatic
Heating Steps Step 2 2 2
Power Supply Ø / V / Hz 1/240/50 3/220/50 3/380~415/50
Rated Current A 25 16 9
Maximum Current(MCA) A 32 20 12
Water Circuit Safety Valve bar 3 3 3
Entering Side Diameter inch Male PT 1 Male PT 1 Male PT 1
Leaving Side Diameter inch Male PT 1 Male PT 1 Male PT 1
Manometer - O O O
Drain Valve / Fill Valve - O O O
Shut Off Valve - O O O
Air Vent - O O O
Refrigerant Circuit Gas Side Diameter mm(inch) 15.88 (5/8) 15.88 (5/8) 15.88 (5/8)
Liquid Side Diameter mm(inch) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8)
Dimensions Unit(W x H x D) mm 850 X 490 X 315 850 X 490 X 315 850 X 490 X 315
Packed Unit(W x H x D) mm 1082 X 563 X 375 1082 X 563 X 375 1082 X 563 X 375
Weight Unit kg 52 52 52
(Without water) Packed Unit kg 59 59 59
*Sanitary Water Tank Type - Indirect heating(+Electric heater)
(Field Supply) Heater Capacity kW Max. 3
Power Supply Ø / V / Hz 1/230/50
Power Supply Type - Separated Power Source
Thermal Protector Range °C Max. 90
Relay Contactor - Needed
ELB A 40
Sensor Adaptor Diameter mm(inch) 12.7 (1/2)
Accessory Kit - LG Supply
MCCB A
Note : 1. The specification may be subject to change without prior notice 2. * : This information is given as a guideline about the connection of
for purpose of improvement. sanitary water tank

Copyright ©2010 LG Electronics. Inc. All right reserved. -5-


LGE Internal Use Only
Only for training and service purposes
Outdoor
Outdoor Units AHUW096A0(H09SNE) AHUW126A0(H12SNE) AHUW146A0(H14SNE) AHUW166A0(H16SNE)
Combination Indoor Units AHNW096A0 AHNW126A0 AHNW146A0 AHNW166A0
Power Supply Ø / V / Hz 1/220-240/50 1/220-240/50 1/220-240/50 1/220-240/50
Maximum Running Cooling A 24 32 32 32
Current Heating A 24 32 32 32
Wiring Connections For Power Supply
(Included Earth) Number of wires 3 3 3 3
For Connection with
Indoor Unit (Included Earth) Number of wires 4 4 4 4
* Capacity Cooling(Under floor) kW 8.60 14.0 14.0 14.0
Heating(Under floor) kW 9.00 12.0 14.0 16.0
* Power Input Cooling(Under floor) kW 2.70 4.40 4.40 4.40
Heating(Under floor) kW 2.20 2.67 3.17 3.80
* EER Cooling(Under floor) W/W 3.19 3.18 3.18 3.18
* COP Heating(Under floor) W/W 4.10 4.50 4.42 4.20
** Capacity Cooling(Fan coil unit) kW 5.83 9.50 9.50 9.50
Heating(Fan coil unit or Radiator) kW 7.49 9.99 11.7 13.3
** Power Input Cooling(Fan coil unit) kW 2.24 3.65 3.65 3.65
Heating(Fan coil unit or Radiator) kW 2.30 2.79 3.41 4.01
** EER Cooling(Fan coil unit) W/W 2.60 2.60 2.60 2.60
** COP Heating(Fan coil unit or Radiator) W/W 3.26 3.58 3.43 3.32
Operation Range(Min.~Max.) Cooling °C DB 5~48 5~48 5~48 5~48
Outdoor Temperature Heating °C DB -20~30 -20~30 -20~30 -20~30
Compressor Type - Hermetic Motor Hermetic Motor Hermetic Motor Hermetic Motor
Model - 5KD240XAE21 5JD420XAD22 5JD420XAD22 5JD420XAD22
Quantity EA 1 1 1 1
Displacement cm3/Rev. 24 42.4 42.4 42.4
Capacity kW 7.28 13.4 (at 57.5Hz) 13.4 (at 57.5Hz) 13.4 (at 57.5Hz)
Compressor Motor Type - Brushless Brushless Brushless Brushless
Quantity EA 1 1 1 1
Rated Output W 1,700 3,000 3,000 3,000
Refrigerant Type - R410A R410A R410A R410A
Charge g(oz) 1,900(67.02) 3,000(105.8) 3,000(105.8) 3,000(105.8)
Control - Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Refrigerant Oil Type - FV50S FV50S FV50S FV50S
Charged Volume cc 900 1300 1300 1300
Heat Exchanger Quantity EA 1 2 2 2
Rows EA 2 2 2 2
Columns EA 36 32 32 32
FPI Fins/inch 18 17 17 17
Fan Type - Propeller Propeller Propeller Propeller
Quantity EA 1 2 2 2
Air Flow Rate CMM(l/s) 58(967) 60(1,000) 60(1,000) 60(1,000)
Fan Motor Model - SIC-72FW-F1124-3 SIC-72FW-F1124-3 SIC-72FW-F1124-3 SIC-72FW-F1124-3
Quantity EA 1 2 2 2
Output W 124 124 124 124
Sound Pressure Cooling dB(A)+3 51 55 55 55
Level Heating dB(A)+3 53 57 57 57
Liquid Piping Type - Flare Flare Flare Flare
Connection Outer Diameter mm(inch) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8)
Gas Piping Type - Flare Flare Flare Flare
Connection Outer Diameter mm(inch) 15.88(5/8) 15.88(5/8) 15.88(5/8) 15.88(5/8)
Piping Length Minimum m 3 3 3 3
(Outdoor Unit ~ Standard m 7.5 7.5 7.5 7.5
Indoor Unit) Maximum m 50 50 50 50
Height Difference
Maximum m 30 30 30 30
(Outdoor Unit ~ Indoor Unit)
Additional Refrigerant Charge g/m 30 60 60 60
Dimensions Unit(W x H x D) mm 870 x 800 x 320 950 x 1,355 x 330 950 x 1,355 x 330 950 x 1,355 x 330
Packed Unit(W x H x D) mm 1,022 x 870 x 437 1,140 x 1462 x 461 1,140 x 1462 x 461 1,140 x 1462 x 461
Weight Unit kg 56 105 105 105
Packed Unit kg 61 116 116 116
Note :
1. Capacities and power inputs are based on the following conditions:
* : Cooling conditions - Indoor Water Temperature 23°C/18°C; Outdoor Air Temperature 35°CDB
Heating conditions - Indoor Water Temperature 30°C/35°C; Outdoor Air Temperature 7°CDB/6°CWB
Standard piping length 7.5m
** : Cooling conditions - Indoor Water Temperature 12°C/7°C; Outdoor Air Temperature 35°CDB
Heating conditions - Indoor Water Temperature 40°C/45°C; Outdoor Air Temperature 7°CDB/6°CWB
Standard piping length 7.5m
2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.

Copyright ©2010 LG Electronics. Inc. All right reserved. -6-


LGE Internal Use Only
Only for training and service purposes
Outdoor Units AHUW096AN (UH09SNG)
Combination Indoor Units AHNW09606A0/ AHNW09A06A0/ AHNW09806A0
Power Supply Ø / V / Hz 1/220-240/50
Maximum Running Cooling A 24
Current Heating A 24
Wiring Connections For Power Supply
Number of wires 3
(Included Earth)
For Connection with
Number of wires 4
Indoor Unit (Included Earth)
* Capacity Cooling(Under floor) kW 8.60
Heating(Under floor) kW 9.00
* Power Input Cooling(Under floor) kW 2.70
Heating(Under floor) kW 2.22
* EER Cooling(Under floor) W/W 3.19
* COP Heating(Under floor) W/W 4.05
** Capacity Cooling(Fan coil unit) kW 5.83
Heating(Fan coil unit or Radiator) kW 7.49
** Power Input Cooling(Fan coil unit) kW 2.24
Heating(Fan coil unit or Radiator) kW 2.30
** EER Cooling(Fan coil unit) W/W 2.60
** COP Heating(Fan coil unit or Radiator) W/W 3.26
Operation Range(Min.~Max.) Cooling °C DB 5 ~ 48
Outdoor Temperature Heating °C DB -20 ~ 30
Compressor Type - Hermetic Motor
Model - 5KD240XAE21
Quantity EA 1
Displacement cm3/Rev. 24
Capacity kW 7.28
Compressor Motor Type - Brushless
Quantity EA 1
Rated Output W 1,700
Refrigerant Type - R410A
Charge g(oz) 1,900(67.02)
Control - Electronic Expansion Valve
Refrigerant Oil Type - FV50S
Charged Volume cc 900
Heat Exchanger Quantity EA 1
Rows EA 2
Columns EA 36
FPI Fins/inch 18
Fan Type - Propeller
Quantity EA 1
Air Flow Rate CMM(l/s) 58(967)
Fan Motor Model - SIC-72FW-F1124-3
Quantity EA 1
Output W 124
Sound Pressure Cooling dB(A)+3 51
Level Heating dB(A)+3 53
Liquid Piping Type - Flare
Connection Outer Diameter mm(inch) 9.52(3/8)
Gas Piping Type - Flare
Connection Outer Diameter mm(inch) 15.88(5/8)
Piping Length Minimum m 3
(Outdoor Unit ~ Standard m 7.5
Indoor Unit) Maximum m 50
Height Difference
Maximum m 30
(Outdoor Unit ~ Indoor Unit)
Additional Refrigerant Charge g/m 30
Dimensions Unit(W x H x D) mm 870 x 800 x 320
Packed Unit(W x H x D) mm 1,022 x 870 x 437
Weight Unit kg 56
Packed Unit kg 61
Note :
1. Capacities and power inputs are based on the following conditions:
* : Cooling conditions - Indoor Water Temperature 23°C/18°C; Outdoor Air Temperature 35°CDB
Heating conditions - Indoor Water Temperature 30°C/35°C; Outdoor Air Temperature 7°CDB/6°CWB
Standard piping length 7.5m
** : Cooling conditions - Indoor Water Temperature 12°C/7°C; Outdoor Air Temperature 35°CDB
Heating conditions - Indoor Water Temperature 40°C/45°C; Outdoor Air Temperature 7°CDB/6°CWB
Standard piping length 7.5m
2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.

Copyright ©2010 LG Electronics. Inc. All right reserved. -7-


LGE Internal Use Only
Only for training and service purposes
Outdoor Units AHUW096A1 AHUW128A1
(HU091 U41) (HU123 U31)
Power Supply Ø / V / Hz 1 / 220-240 / 50 3/380-415/50
Maximum Running Cooling A 24 32
Current Heating A 24 32
Wiring Connections For Power Supply
Number of wires 3 5
(Included Earth)
For Connection with
Number of wires 4 4
Indoor Unit (Included Earth)
* Capacity Cooling(A35/W18) kW 8.90 14.6
Heating(A7W35) kW 9.00 12.0
* Power Input Cooling(A35/W18) kW 2.70 4.02
Heating(A7W35) kW 2.19 2.67
* EER Cooling(A35/W18) W/W 3.19 3.60
COP Heating(A7W35) W/W 4.10 4.49
Heating(A2W35) W/W 3.15 3.37
Heating(A10W35) W/W 4.50 4.37
Heating(A-7W35) W/W 2.72 2.63
Operation Range(Min.~Max.) Cooling °C DB 5~48 5~48
Outdoor Temperature Heating °C DB -20~30 -20~30
Compressor Type - Hermetic Motor Hermetic Motor
Model - GJT240DAA GPT425DAA
Quantity EA 1 1
Displacement cm3/Rev. 24 42.4
Capacity kW 7.28 12.05 (at 60Hz)
Compressor Motor Type - Brushless Brushless
Quantity EA 1 1
Rated Output W 1,700 4,000
Refrigerant Type - R410A R410A
Charge g(oz) 1,900(67.0) 2,980(105.1)
Control - Electronic Expansion Valve Electronic Expansion Valve
Refrigerant Oil Type - FV50S FV50S
Charged Volume cc 900 1,300
Heat Exchanger Quantity EA 1 2
Rows EA 2 2
Columns EA 36 32
FPI Fins/inch 18 17
Fan Type - Propeller Propeller
Quantity EA 1 2
Air Flow Rate CMM(l/s) 58(967) 60(1,000)
Fan Motor Model - SIC-72FW-F1124-3 SIC-72FW-F1124-3
Quantity EA 1 2
Output W 124 124
Sound Pressure Cooling dB(A)±3 52 54
Level Heating dB(A)±3 52 53
Liquid Piping Type - Flare Flare
Connection Outer Diameter mm(inch) 9.52(3/8) 9.52(3/8)
Gas Piping Type - Flare Flare
Connection Outer Diameter mm(inch) 15.88(5/8) 15.88(5/8)
Piping Length Minimum m 3 3
(Outdoor Unit ~ Standard m 7.5 7.5
Indoor Unit) Maximum m 50 50
Height Difference
Maximum m 30 30
(Outdoor Unit ~ Indoor Unit)
Additional Refrigerant Charge g/m 30 50
Dimensions Unit(W x H x D) mm 950 x 833 x 400 950 x 1,380 x 330
Packed Unit(W x H x D) mm 1,140 x 900 x 461 1,140 x 1,462 x 461
Weight Unit kg 64 105
Packed Unit kg 69 116

Note :
1. Capacities and power inputs are based on the following conditions:
* : Cooling conditions - Indoor Water Temperature 23°C/18°C; Outdoor Air Temperature 35°CDB/24°CWB
Heating conditions - Indoor Water Temperature 30°C/35°C; Outdoor Air Temperature 7°CDB/6°CWB
Standard piping length 7.5m
2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.

Copyright ©2010 LG Electronics. Inc. All right reserved. -8-


LGE Internal Use Only
Only for training and service purposes
Outdoor Units AHUW148A1 AHUW168A1
(HU143 U31) (HU163 U31)
Power Supply Ø / V / Hz 3/380-415/50 3/380-415/50
Maximum Running Cooling A 32 32
Current Heating A 32 32
Wiring Connections For Power Supply
Number of wires 5 5
(Included Earth)
For Connection with
Number of wires 4 4
Indoor Unit (Included Earth)
* Capacity Cooling(A35/W18) kW 15.5 16.8
Heating(A7W35) kW 14.5 16.0
* Power Input Cooling(A35/W18) kW 4.65 5.09
Heating(A7W35) kW 3.38 3.81
* EER Cooling(A35/W18) W/W 3.33 3.33
COP Heating(A7W35) W/W 4.29 4.20
Heating(A2W35) W/W 3.33 3.20
Heating(A10W35) W/W 4.21 4.16
Heating(A-7W35) W/W 2.77 2.63
Operation Range(Min.~Max.) Cooling °C DB 5~48 5~48
Outdoor Temperature Heating °C DB -20~30 -20~30
Compressor Type - Hermetic Motor Hermetic Motor
Model - GPT425DAA GPT425DAA
Quantity EA 1 1
Displacement cm /Rev.
3
42.4 42.4
Capacity kW 12.05 (at 60Hz) 12.05 (at 60Hz)
Compressor Motor Type - Brushless Brushless
Quantity EA 1 1
Rated Output W 4,000 4,000
Refrigerant Type - R410A R410A
Charge g(oz) 2,980(105.1) 2,980(105.1)
Control - Electronic Expansion Valve Electronic Expansion Valve
Refrigerant Oil Type - FV50S FV50S
Charged Volume cc 1,300 1,300
Heat Exchanger Quantity EA 2 2
Rows EA 2 2
Columns EA 32 32
FPI Fins/inch 17 17
Fan Type - Propeller Propeller
Quantity EA 2 2
Air Flow Rate CMM(l/s) 60(1,000) 60(1,000)
Fan Motor Model - SIC-72FW-F1124-3 SIC-72FW-F1124-3
Quantity EA 2 2
Output W 124 124
Sound Pressure Cooling dB(A)±3 54 54
Level Heating dB(A)±3 53 53
Liquid Piping Type - Flare Flare
Connection Outer Diameter mm(inch) 9.52(3/8) 9.52(3/8)
Gas Piping Type - Flare Flare
Connection Outer Diameter mm(inch) 15.88(5/8) 15.88(5/8)
Piping Length Minimum m 3 3
(Outdoor Unit ~ Standard m 7.5 7.5
Indoor Unit) Maximum m 50 50
Height Difference
Maximum m 30 30
(Outdoor Unit ~ Indoor Unit)
Additional Refrigerant Charge g/m 50 50
Dimensions Unit(W x H x D) mm 950 x 1,380 x 330 950 x 1,380 x 330
Packed Unit(W x H x D) mm 1,140 x 1,462 x 461 1,140 x 1,462 x 461
Weight Unit kg 105 105
Packed Unit kg 116 116

Note :
1. Capacities and power inputs are based on the following conditions:
* : Cooling conditions - Indoor Water Temperature 23°C/18°C; Outdoor Air Temperature 35°CDB/24°CWB
Heating conditions - Indoor Water Temperature 30°C/35°C; Outdoor Air Temperature 7°CDB/6°CWB
Standard piping length 7.5m
2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.

Copyright ©2010 LG Electronics. Inc. All right reserved. -9-


LGE Internal Use Only
Only for training and service purposes
2. Function Table
Indoor
AHNW096A0 AHNW126A0 AHNW146A0 AHNW166A0
Category Function
(H09SNE) (H12SNE) (H14SNE) (H16SNE)
Installation Drain pump - - - -
E.S.P. control - - - -
Electric heater(operation) O O O O
High ceiling operation - - - -
Reliability Hot start - - - -
Self diagnosis O O O O
Soft dry operation - - - -
Convenience Auto changeover - - - -
Auto cleaning - - - -
Auto operation(artificial intelligence) - - - -
Auto restart operation O O O O
Child lock O O O O
Forced operation - - - -
Group control - - - -
Sleep mode - - - -
Timer(on/off) O O O O
Timer(weekly) O O O O
Two thermistor control - - - -
Individual control Standard wired remote controller(control panel) O O O O
Deluxe wired remote controller - - - -
Simple wired remote controller - - - -
Wired remote controller(for hotel use) - - - -
Wireless remote controller(simple) - - - -
Wireless LCD remote control - - - -
CAC network function General central controller (Non LGAP) - - - -
Dry contact PQDSA PQDSA PQDSA PQDSA
Network Soluation(LGAP) O O O O
PDI(power distribution indicator) - - - -
PI 485 - - - -
Special function kit Zone control - - - -
CTIE - - - -
Electro thermostat - - - -
Others Remote room temperature sensor (TH8) PQRSTA0 PQRSTA0 PQRSTA0 PQRSTA0
AWHP Anti-Condensation on floor (cooling) O O O O
Water Pump ON / OFF Control O O O O
Flow Switch Control O O O O
Thermostat Interface (230V AC) O O O O
Thermostat Interface (24V AC) O O O O
Sanitary Tank Heating O O O O
Solar-Thermal Interface with Sanitary Tank O O O O
PHEX Anti-Freezing Control O O O O
Water Pump Forced Operation O O O O
Autosetting according to Ambient Temperature O O O O
Silent Operation O O O O
Anti-overheating of Water Pipe O O O O
Emergency Operation O O O O

Notes
O : Applied, X : Not applied, – : No relation
* TH8 : Refer to 'Chapter 8. Piping Diagram' of 'Part 2. Indoor Unit (Hydro kit)'
* Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate
package.

Copyright ©2010 LG Electronics. Inc. All right reserved. - 10 -


LGE Internal Use Only
Only for training and service purposes
AHNW09606A0 AHNW09A06A0 AHNW09806A0
Category Function
(NH09SNG) (NH09SNK) (NH09SNP)
Installation Drain pump - - -
E.S.P. control - - -
Electric heater(operation) O O O
High ceiling operation - - -
Reliability Hot start - - -
Self diagnosis O O O
Soft dry operation - - -
Convenience Auto changeover - - -
Auto cleaning - - -
Auto operation(artificial intelligence) - - -
Auto restart operation O O O
Child lock O O O
Forced operation - - -
Group control - - -
Sleep mode - - -
Timer(on/off) O O O
Timer(weekly) O O O
Two thermistor control - - -
Individual control Standard wired remote controller(control panel) O O O
Deluxe wired remote controller - - -
Simple wired remote controller - - -
Wired remote controller(for hotel use) - - -
Wireless remote controller(simple) - - -
Wireless LCD remote control - - -
CAC network function General central controller (Non LGAP) - - -
Dry contact PQDSA PQDSA PQDSA
Network Soluation(LGAP) O O O
PDI(power distribution indicator) - - -
PI 485 - - -
Special function kit Zone control - - -
CTIE - - -
Electro thermostat - - -
Others Remote room temperature sensor (TH8) PQRSTA0 PQRSTA0 PQRSTA0
AWHP Anti-Condensation on floor (cooling) O O O
Water Pump ON / OFF Control O O O
Flow Switch Control O O O
Thermostat Interface (230V AC) O O O
Thermostat Interface (24V AC) O O O
Sanitary Tank Heating O O O
Solar-Thermal Interface with Sanitary Tank O O O
PHEX Anti-Freezing Control O O O
Water Pump Forced Operation O O O
Autosetting according to Ambient Temperature O O O
Silent Operation O O O
Anti-overheating of Water Pipe O O O
Emergency Operation O O O

Notes
O : Applied, X : Not applied, – : No relation
* TH8 : Refer to 'Chapter 8. Piping Diagram' of 'Part 2. Indoor Unit (Hydro kit)'
* Accessory: Installed at field, ordered and purchased separately by the corresponding model mane, supplied with separate
package.

Copyright ©2010 LG Electronics. Inc. All right reserved. - 11 -


LGE Internal Use Only
Only for training and service purposes
Category Function AHNW09604A1 AHNW09606A1 AHNW09A06A1 AHNW09806A1

Installation Drain pump - - - -


E.S.P. control - - - -
Electric heater(operation) O O O O
High ceiling operation - - - -
Reliability Hot start - - - -
Self diagnosis O O O O
Soft dry operation - - - -
Convenience Auto changeover - - - -
Auto cleaning - - - -
Auto operation(artificial intelligence) - - - -
Auto restart operation O O O O
Child lock O O O O
Forced operation - - - -
Group control - - - -
Sleep mode - - - -
Timer(on/off) O O O O
Timer(weekly) O O O O
Two thermistor control - - - -
Individual control Standard wired remote controller(control panel) O O O O
Deluxe wired remote controller - - - -
Simple wired remote controller - - - -
Wired remote controller(for hotel use) - - - -
Wireless remote controller(simple) - - - -
Wireless LCD remote control - - - -
CAC network function General central controller (Non LGAP) - - - -
Dry contact PQDSA PQDSA PQDSA PQDSA
Network Soluation(LGAP) O O O O
PDI(power distribution indicator) - - - -
PI 485 - - - -
Special function kit Zone control - - - -
CTIE - - - -
Electro thermostat - - - -
Others Remote room temperature sensor (TH8) PQRSTA0 PQRSTA0 PQRSTA0 PQRSTA0
AWHP Anti-Condensation on floor (cooling) O O O O
Water Pump ON / OFF Control O O O O
Flow Switch Control O O O O
Thermostat Interface (230V AC) O O O O
Thermostat Interface (24V AC) O O O O
Sanitary Tank Heating O O O O
Solar-Thermal Interface with Sanitary Tank O O O O
PHEX Anti-Freezing Control O O O O
Water Pump Forced Operation O O O O
Autosetting according to Ambient Temperature O O O O
Silent Operation O O O O
Anti-overheating of Water Pipe O O O O
Emergency Operation O O O O

Notes
O : Applied, X : Not applied, – : No relation
* TH8 : Refer to 'Chapter 8. Piping Diagram' of 'Part 2. Indoor Unit (Hydro kit)'
* Accessory: Installed at field, ordered and purchased separately by the corresponding model mane, supplied with separate
package.

Copyright ©2010 LG Electronics. Inc. All right reserved. - 12 -


LGE Internal Use Only
Only for training and service purposes
Category Function AHNW09606A1 AHNW09A06A1 AHNW09806A1

Installation Drain pump - - -


E.S.P. control - - -
Electric heater(operation) O O O
High ceiling operation - - -
Reliability Hot start - - -
Self diagnosis O O O
Soft dry operation - - -
Convenience Auto changeover - - -
Auto cleaning - - -
Auto operation(artificial intelligence) - - -
Auto restart operation O O O
Child lock O O O
Forced operation - - -
Group control - - -
Sleep mode - - -
Timer(on/off) O O O
Timer(weekly) O O O
Two thermistor control - - -
Individual control Standard wired remote controller(control panel) O O O
Deluxe wired remote controller - - -
Simple wired remote controller - - -
Wired remote controller(for hotel use) - - -
Wireless remote controller(simple) - - -
Wireless LCD remote control - - -
CAC network function General central controller (Non LGAP) - - -
Dry contact PQDSA PQDSA PQDSA
Network Soluation(LGAP) O O O
PDI(power distribution indicator) - - -
PI 485 - - -
Special function kit Zone control - - -
CTIE - - -
Electro thermostat - - -
Others Remote room temperature sensor (TH8) PQRSTA0 PQRSTA0 PQRSTA0
AWHP Anti-Condensation on floor (cooling) O O O
Water Pump ON / OFF Control O O O
Flow Switch Control O O O
Thermostat Interface (230V AC) O O O
Thermostat Interface (24V AC) O O O
Sanitary Tank Heating O O O
Solar-Thermal Interface with Sanitary Tank O O O
PHEX Anti-Freezing Control O O O
Water Pump Forced Operation O O O
Autosetting according to Ambient Temperature O O O
Silent Operation O O O
Anti-overheating of Water Pipe O O O
Emergency Operation O O O

Notes
O : Applied, X : Not applied, – : No relation
* TH8 : Refer to 'Chapter 8. Piping Diagram' of 'Part 2. Indoor Unit (Hydro kit)'
* Accessory: Installed at field, ordered and purchased separately by the corresponding model mane, supplied with separate
package.

Copyright ©2010 LG Electronics. Inc. All right reserved. - 13 -


LGE Internal Use Only
Only for training and service purposes
Outdoor
AHUW096A0 AHUW096AN AHUW126A0 AHUW146A0 AHUW166A0
Category Function
(H09SNE) (UH09SNG) (H12SNE) (H14SNE) (H16SNE)
Reliability Defrost / Deicing O O O O O
High pressure switch O O O O O
Low pressure switch O O O O O
Phase protection - - - - -
Restart delay (3-minutes) O O O O O
Self diagnosis O O O O O
Soft start - - - - -
Test function - - - - -
Convenience Auto operation(Artificial intelligence) - - - - -
Auto restart operation - - - - -
CAC network function Network soluation(LGAP) O O O O O
PDI(Power Distribution Indicator) - - - - -
PI485 PMNFP14A0 PMNFP14A0 PMNFP14A0 PMNFP14A0 PMNFP14A0
Special function kit Low ambient operation - - - - -
Others Thermistor - - - - -
AWHP Sanitary Tank Heating O O O O O
Silent Operation O O O O O
Emergency Operation O O O O O

Category Function AHUW096A1 AHUW128A1 AHUW148A1 AHUW168A1

Reliability Defrost / Deicing O O O O


High pressure switch O O O O
Low pressure switch O O O O
Phase protection - - - -
Restart delay (3-minutes) O O O O
Self diagnosis O O O O
Soft start - - - -
Test function - - - -
Convenience Auto operation(Artificial intelligence) - - - -
Auto restart operation - - - -
CAC network function Network soluation(LGAP) O O O O
PDI(Power Distribution Indicator) - - - -
PI485 PMNFP14A0 PMNFP14A0 PMNFP14A0 PMNFP14A0
Special function kit Low ambient operation - - - -
Others Thermistor - - - -
AWHP Sanitary Tank Heating O O O O
Silent Operation O O O O
Emergency Operation O O O O

Notes
O : Applied, X : Not applied, – : No relation
* Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate
package.

Copyright ©2010 LG Electronics. Inc. All right reserved. - 14 -


LGE Internal Use Only
Only for training and service purposes
3. Pump Hydraulic Performance
Model : AHNW096A0 (H09SNE), AHNW09606A0 (NH09SNG), AHNW09A06A0 (NH09SNK),
AHNW09806A0 (NH09SNP)
8.0
7.5
7.0
6.5
6.0
aulic Head Loss(mH2O)

5.5
5.0
4.5
4.0
3.5
3.0
2.5
2.0
Med.
1.5
Max.
1.0
12
0.5
0.0
0 10 20 30 40 50 60 70 80 90 100 110
Water Flowrate(l/min)
Model : AHNW126A0 (H12SNE), AHNW146A0 (H14SNE), AHNW166A0 (H16SNE)
8.0
7.5
7.0
6.5
6.0
5.5
Hydraulic Head Loss(mH2O)

5.0
4.5
Max.
4.0
3.5
Med.
3.0
2.5
2.0
1.5
1.0 12

0.5
0.0
0 10 20 30 40 50 60 70 80 90 100 110
Water Flowrate(l/min)

★ Max. : high speed setting


Med. : low speed setting

Warning : Selecting a water flowrate outside the curves can cause damage to or malfunction of the unit.
: Operation cutoff range

Copyright ©2010 LG Electronics. Inc. All right reserved. - 15 -


LGE Internal Use Only
Only for training and service purposes
Model : AHNW16606A1(HN1616), AHNW16A06A1(HN1626), AHNW16806A1(HN1636)
8.0
7.5
7.0
6.5
6.0
5.5
Hydraulic Head Loss(mH2O)

5.0
4.5
Max.
4.0
3.5
Med.
3.0
2.5
2.0
1.5
15
1.0
0.5
0.0
0 10 20 30 40 50 60 70 80 90 100 110
Water Flowrate(l/min)

★ Max. : high speed setting


Med. : low speed setting

Warning : Selecting a water flowrate outside the curves can cause damage to or malfunction of the unit.
: Operation cutoff range

Copyright ©2010 LG Electronics. Inc. All right reserved. - 16 -


LGE Internal Use Only
Only for training and service purposes
Only for training and service purposes
Solar
Thermal
4. Piping Diagrams

Componets

Copyright ©2010 LG Electronics. Inc. All right reserved.


- 17 -
Fan
Coil
Unit

Underfloor
Heating

Radiator
Sanitary water tan Solar thermal syst
k is installed em is connected
(Sanitary water tan (Solar thermal kit i
Basic installation k kit is necessary) s necessary)
(
(IDU + ODU))

LGE Internal Use Only


Category Symbol Meaning PCB Connector Remarks
Refrigerant temperature sensor
TH1 CN_PIPE/OUT
(Gas side) - Meaning is expressed based on Cooling
Refrigerant temperature sensor mode.
TH2 CN_PIPE
(Liquid side)
TH3 Entering Water temperature sensor
- TH3, TH4, and TH5 are connected at 6 pin
TH4 Interim Water temperature sensor CN_TH3
type connector CN_TH3.
TH5 Leaving Water temperature sensor
F/S Flow Switch CN_FLOW1
Indoor Unit
- Heating capacity is divided into two level :
partial capacity by E/HEAT(A) and full
capacity by E/HEAT(A) + E/HEAT(B).
CN_E/HEAT(A)
E/HT Electric Heater - Operating power(230V AC 50Hz) of
CN_E/HEAT(B) E/HEAT(A) and E/HEAT(B) are supplied by
external power source via relay connector
and ELB.
Internal Water Pump - Operating power(230V AC 50Hz) of internal
W_PUMP1 CN_W/PUMP(A)
water pump is supplied by the connector.
EXP/TANK Expansion Tank (no connector) - Absorb volume change of heated water,
TH8 Remote Air temperature sensor CN_ROOM - Optional accessory (sold separately)
- Model : PQRSTA0
CTR/PNL Control Panel (or ‘Remote Controller’) CN_REMO - Pre built-in at indoor unit
- 3rd party accessory and Field installation
(sold separately)
2WAY V/V_1 To control water flow for Fan Coil Unit CN_2WAY(A) - 2wire NO or NC type 2way valve is
supported.
- 3rd party accessory and Field installation
W/TANK (sold separately)
Sanitary Water Tank (no connector)
- Generating and storing sanitary hot water by
AWHP or built-in electric heater-
- 3rd party accessory and Field installation
B/HT Electric Heater CN_B/HEAT(A) (usually built-in at W/TANK)
- Supplying additional water heating capacity.
Water
- Flow control for water which is leaving from
Heating - 3rd party accessory and Field installation
indoor unit. CN_3WAY(A)
3WAY V/V_1 - Flow direction switching between under- (sold separately)
floor and water tank - SPDT type 3way valve is supported.
Water to be heated by Indoor unit and B/HT (no connector) - Field installation
CITY WATER
of W/TANK
SHOWER Water supplied to end-user (no connector) - Field installation
TH6 W/TANK water temperature sensor - TH6 and TH7 are connected at 4 pin type connector
CN_TH4
TH7 Solar-heated water temperature sensor CN_TH4.
- TH6 is a part of sanitary water tank kit. (Model:PHLTA)
- TH7 is a part of solar thermal kit (Model:PHLLA)
- Flow control for water which is heated and
- 3rd party accessory and Field installation
3WAY V/V_2 circulated by SOLAR THERMAL SYSTEM. CN_3WAY(B) (sold separately)
- Flow direction switching between SOLAR
THERMAL SYSTEM and W/TANK - SPDT type 3way valve is supported.

- 3rd party accessory and Field installation


Solar (sold separately)
W_PUMP/2 External Water Pump CN_W/PUMP(B) - If water pump of SOLAR THERMAL SYSTEM
Heating
is incapable of circulation,external water pump
can be used.
- This system can include following compo-
nents : Solar panel, Sensors, Thermostats,
SOLAR THER- Interim heat exchanger, Water pump, etc. - 3rd party accessory and Field installation
(no connector) (sold separately)
MAL SYSTEM - To utilized hot water heated by SOLAR
THERMAL SYSTEM, end-user must buy LG
AWHP Solar-Kit.

Copyright ©2010 LG Electronics. Inc. All right reserved. - 18 -


LGE Internal Use Only
Only for training and service purposes
5. Wiring Diagrams
Indoor Unit
Model : AHNW096A0, AHNW126A0, AHNW146A0, AHNW166A0

Copyright ©2010 LG Electronics. Inc. All right reserved. - 19 -


LGE Internal Use Only
Only for training and service purposes
Indoor Unit
Model : AHNW09606A0, AHNW16606A1, AHNW09604A1, AHNW09606A1

Copyright ©2010 LG Electronics. Inc. All right reserved. - 20 -


LGE Internal Use Only
Only for training and service purposes
Indoor Unit
Model : AHNW09A06A0, AHNW09806A0 , AHNW09A06A1, AHNW09806A1,AHNW16A06A1,AHNW16806A1

Copyright ©2010 LG Electronics. Inc. All right reserved. - 21 -


LGE Internal Use Only
Only for training and service purposes
Outdoor Unit : AH-W126A0, AH-W146A0, AH-W166A0

Copyright ©2010 LG Electronics. Inc. All right reserved. - 22 -


LGE Internal Use Only
Only for training and service purposes
Outdoor Unit : AH-W096A0

Copyright ©2010 LG Electronics. Inc. All right reserved. - 23 -


LGE Internal Use Only
Only for training and service purposes
Outdoor Unit : AHUW096AN

Copyright ©2010 LG Electronics. Inc. All right reserved. - 24 -


LGE Internal Use Only
Only for training and service purposes
Outdoor Unit : AHUW096A1

Copyright ©2010 LG Electronics. Inc. All right reserved. - 25 -


LGE Internal Use Only
Only for training and service purposes
Outdoor Unit : AHUW128A1, AHUW148A1, AHUW168A1

Copyright ©2010 LG Electronics. Inc. All right reserved. - 26 -


LGE Internal Use Only
Only for training and service purposes
POWER SOURCE AND MAIN POWER DISTRIBUTION INFORMATION
1~
• TOTAL CAPACITY OF POWER SOURCE CAPACITY SHOULD BE ENOUGH TO 230V
OPERATE SYSTEM INCLUDING INDOOR UNIT, OUTDOOR UNIT, ELECTRIC HEATERS, 50Hz
Indoor Unit
WATER PUMP, ETC. IF POWER SOURCE CAPACITY IS NOT ENOUGH, FREQUENT CUT-
OFF OF MAIN POWER BY CIRCUIT BREAKER IS EXPECTED.

• MAIN POWER DITRIBUTION SHOULD HAVE AT LEAST FOUR OUTGOING BRANCHED


LIKE DIAGRAM. EACH BRANCHES SHOULD EQUIP FUSE AND OVERLOAD
PROTECTOR(OR CIRCUIT BREAKER) TO PREVENT POTENTIAL ELECTRIC ACCIDENT.

• DIAMETER OF CONNECTING WIRE SHOULD BE CHOOSEN CAREFULLY TO PREVENT


BURN-OUT BY MAXIMUM CURRENT.
NOTES

WATER TANK
n IMPORTANT REMARKS
Store or Generate Hot

Only for training and service purposes


Water • This diagram is valid for wiring LG AWHP
system and related accessories.
E/HT SENSOR
3WAY 3WAY WATER
VALVE(B) VALVE(A) PUMP(B) 2P

Flow control Select water- Circulate


for Solar- heating or Solar-heated ELB or
heated fluid floor-heating fluid MCCB
2P

Copyright ©2010 LG Electronics. Inc. All right reserved.


M/C 2P n SYMBOLS
2P
2P
6. External Wiring Diagram

3P 2P FACTORY WIRING
3P 2P
R/C FIELD WIRING
2P
ACCESSORY (supplied by LG Electronics)
3rd PARTY ACCESSORY
3P (supplied by 3rd party company)
WATER E/HT ELB E/HT
MAIN POWER DISTRIBUTION
PUMP
T/B T/B T/B (A) T/S T/B ELB ELECTRIC LEAKAGE BREAKER

- 27 -
T/B TERMINAL BLOCK
M/C M/C

THERMAL SWITCH
CN_3WAY(B) CN_3WAY(A) CN_W/PUMP(B) CN_W/PUMP(A) CN_E/HEAT(B) CN_E/HEAT(A) CN_B/HEAT(A) CN_TH4
E/HT ELECTRIC HEATER
CENTRAL T/S
CONTROLLER WARNIG (READ DIRECTION
CAREFULLY TO PREVENT POTENTIAL
2P ACCIDENTS)
(including 3P
PI485 Gateway)

n 3rd PARTY ACCESORY INSTALLATION


CN_THMO1 CN_THMO2 CN_SOLAR
OUTDOOR UNIT PCB (INSIDE INDOOR UNIT) • To install 3rd party accessory correctly,
please refer to installation manual presented
by related manufacturer.

INDOOR UNIT
THERMOSTAT AND THERMO SWITCH INFORMATION n ACCESSORY INSTALLATION
Model : AHNW096A0, AHNW126A0, AHNW146A0, AHNW166A0, AHNW09606A0

3P or 4P 3P or 4P 3P • NEVER USE THERMOSTAT1 AND THERMOSTAT2 AT THE SAME TIME. IF USED, • To install accessory correctly, please refer to
FIRE ACCIDENT CAN BE OCCURRED BY ELECTRIC SHORT INSIDE PCB. installation manual presented by LG
Electronics
• HEATING ONLY THERMOSTAT : USE 3 PIN CONNECTION
THERMO- THERMO- THERMAL HEATING AND COOLING THERMOSTAT : USE 4 PIN CONNECTION
STAT1 STAT2 SWITCH CONNECTION INFORMATION : SEE PRODUCT INSTALLATION MANUAL(BY LG
ELECTRONICS) AND THERMOSTAT INSTALLATION MANUAL(BY MANUFACTURER).

230V AC 24V AC 230V AC • THERMAL SWITCH SHOULD BE NORMAL OPEN. IT SHOULD BE CLOSED AT
USER’S DESIGNED OPERATION TEMPERATURE. IF NOT, HEATING BY SOLAR
THERMAL SYSTEM CAN BE DEGRADED.

LGE Internal Use Only


Indoor Unit
Model : AHNW09A06A0, AHNW09806A0

MCCB

M/C
380V
220V
50Hz

50Hz
3~

3~
or

MCCB

M/C
3

M/C
230V
50Hz

M/C
1~

Copyright ©2010 LG Electronics. Inc. All right reserved. - 28 -


LGE Internal Use Only
Only for training and service purposes
Wiring Diagram : Indoor and Outdoor Unit(Including Field wiring)
(Indoor : Electric Heater 1Ø, Outdoor : 1Ø)

M/C
50Hz
230V
1~

Copyright ©2010 LG Electronics. Inc. All right reserved. - 29 -


LGE Internal Use Only
Only for training and service purposes
Wiring Diagram : Indoor and Outdoor Unit(Including Field wiring)
(Indoor : Electric Heater 3Ø, Outdoor : 1Ø)

MCCB

M/C
380V
220V
50Hz

50Hz
3~

3~
or

MCCB

M/C
3

M/C
230V
50Hz

M/C
1~

Copyright ©2010 LG Electronics. Inc. All right reserved. - 30 -


LGE Internal Use Only
Only for training and service purposes
Wiring Diagram : Indoor and Outdoor Unit(Including Field wiring)
(Indoor : Electric Heater 3Ø 220V, Outdoor : 3Ø)

MCCB

M/C
220V
50Hz
3~

MCCB

M/C
3
220V
50Hz
1~

M/C
380V
50Hz
3~

M/C

Copyright ©2010 LG Electronics. Inc. All right reserved. - 31 -


LGE Internal Use Only
Only for training and service purposes
Wiring Diagram : Indoor and Outdoor Unit(Including Field wiring)
(Indoor : Electric Heater 3Ø 380-415V, Outdoor : 3Ø)

MCCB

M/C

M/C
220V
50Hz
1~

MCCB
3

M/C

M/C
380V
50Hz
3~

Copyright ©2010 LG Electronics. Inc. All right reserved. - 32 -


LGE Internal Use Only
Only for training and service purposes
7. Exploded View
Indoor Unit
137211

Model : AHNW096A0
AHNW126A0
AHNW146A0
AHNW166A0
733010
AHNW09606A0

552000

135511

268711E 268711B
148391

135500
269300
340090

263230G
752140 349001
263230B

552207
263230C 165020

566001
266007

152141
W6640C
235042
W6640B
261704
W52240

267110 158580
130411

265020

148382

Note) * Please ensure GCSC since the replacement parts may be changed depending upon the buyer's request.
Please check the correct parts in View RPL(Replacement Part List) on GCSC.
(GCSC Website http://biz.Lgservice.com,)

Copyright ©2010 LG Electronics. Inc. All right reserved. - 33 -


LGE Internal Use Only
Only for training and service purposes
Indoor Unit
137211

Model : AHNW09A06A0
AHNW09806A0

733010

552000

249951

268711E 268711B
148391

135500

340090

263230G
752140 349001
263230B

552207
263230C 269300A 165020
269300B
261704

152141
W6640C
566001A 235042
266007

566001B W52240

W6640B

267110 158580
130411

265020

148382

Copyright ©2010 LG Electronics. Inc. All right reserved. - 34 -


LGE Internal Use Only
Only for training and service purposes
Indoor Unit

Model : AHNW16A06A1,AHNW16806A1,AHNW09A06A1,AHNW09806A1

249951

733010
137211
268711E 268711B

552000
263230G
263230B 752140

135500 340090
263230C 148391
349001
261704
566001A 165020
269300A
269300B

W6640C
552207
235042

566001A 566001B 753000


W52240

152141
W6640B
130411 158580

267110
265020
148382

Copyright ©2010 LG Electronics. Inc. All right reserved. - 35 -


LGE Internal Use Only
Only for training and service purposes
Indoor Unit

Model : AHNW16606A1, AHNW09604A1, AHNW09606A1

135510

733010
137211
268711E 268711B

552000

263230G
263230B 752140

340090
263230C 148391
135500
269300

165020
349001

552207

235042
566001
266007

W52240
W6640C

W6640B
130411 158580 152141
261704

267110
148382

Copyright ©2010 LG Electronics. Inc. All right reserved. - 36 -


LGE Internal Use Only
Only for training and service purposes
435300
137213B

137213A

554031

435511

Only for training and service purposes


435512
Outdoor Unit : AW-H096A0

549610 268711F
W4810

Copyright ©2010 LG Electronics. Inc. All right reserved.


546810 552113
PIPE-OUT/AIR 552115
567480E 567480D
SUCTION /
649950

- 37 -
DISCHARGE
437211

349480 566000A

W6200

435301 561410
559010 35211A
566000B 552116
447910

661400
554160
552202
550140
437210
552203A
W6631
552203B
Comp. wire

430411

LGE Internal Use Only


352150
Outdoor Unit : AHUW096AN

661400
552116

552203A
552203B
W49810
435511
137213A

649950
552115
552113

550140 Comp. wire


561410

W6631
552202

553000A
PIPE-OUT/AIR
567480D
435300

W6200

35211A
566000

548490
268711F

554160
DISCHARGE
567480E
SUCTION /

430411
352150
549610

553000B
137213B

554031

546810
W4810

447910
559010
435512

437210
349480

435301
437211

Note) * Please ensure GCSC since the replacement parts may be changed depending upon the buyer's request.
Please check the correct parts in View RPL(Replacement Part List) on GCSC.
(GCSC Website http://biz.Lgservice.com,)

Copyright ©2010 LG Electronics. Inc. All right reserved. - 38 -


LGE Internal Use Only
Only for training and service purposes
Outdoor Unit : AHUW096A1

237205

135500
437212

W6631
548490
435300

561410

550140
554160
552117
137213A

552560
552202
552116

566000
661400
552113

152503
552203A
55211E
552112

430410
263230A

263230C
263230B
554031

148000

552203B

435513
(M-PIPE)
CN-TH4
(PIPE2/DIS1)
(AIR/PIPE1)
W6200

CN-TH1

CN-TH2

W6640

447910
649950

268711
549610

137213B
346810

237202

437211
559010

349480
435512

435301

Note) * Please ensure GCSC since the replacement parts may be changed depending upon the buyer's request.
Please check the correct parts in View RPL(Replacement Part List) on GCSC.
(GCSC Website http://biz.Lgservice.com,)

Copyright ©2010 LG Electronics. Inc. All right reserved. - 39 -


LGE Internal Use Only
Only for training and service purposes
Outdoor Unit : AW-H126A0, AW-H146A0, AW-H166A0
437212

Comp. wire
W52102

W6631
566000B

548490
435300

554160
566000A
552117
661400

561410
237204

552116
55211G
552111

649950
552115

430411
552202

W49810
268711

W6640B
554031

552203B
552203A
PIPE-OUT AIR
567480D

435513
W6640A

SUCTION-DISCHARGE
554031

567480E
W6200

268711F

447910
546810
546810

237202

137213
549610

559010

437211
349480
559010

435512

349480
435301

435301

Note) * Please ensure GCSC since the replacement parts may be changed depending upon the buyer's request.
Please check the correct parts in View RPL(Replacement Part List) on GCSC.
(GCSC Website http://biz.Lgservice.com,)

Copyright ©2010 LG Electronics. Inc. All right reserved. - 40 -


LGE Internal Use Only
Only for training and service purposes
Outdoor Unit : AHUW128A1, AHUW148A1, AHUW168A1

237205

135500
437212

548490
W52102
566000B
435300

552116

554160
W6631

552117
552200
661400

566000A
237204

561410
W52240
55211G
552111

649950
552115

430410
552202

152503
268711C

W6640B
554031A

552203B
PIPE-OUT AIR

552203A
263230B

435513
148000
W6640A

SUCTION-DISCHARGE
554031B

263230C
W6200

268711B
263230A
MIDDLE

447910
546810
546810

237202

137213
549610

559010

437211
349480
559010

435512

349480
435301

435301

Note) * Please ensure GCSC since the replacement parts may be changed depending upon the buyer's request.
Please check the correct parts in View RPL(Replacement Part List) on GCSC.
(GCSC Website http://biz.Lgservice.com,)

Copyright ©2010 LG Electronics. Inc. All right reserved. - 41 -


LGE Internal Use Only
Only for training and service purposes
P/NO : MFL57946203 September , 2011