You are on page 1of 14

Job Name Pepsi

Mark for AHU-1 (Dye y Man Fill)


Date November 22, 2022

Unit Parameters

Aero Outdoor Air Handler

Unit Size: Size 21

Insulation: R-13 Double Wall Sealed Panel

Exterior Finish: Painted Exterior Panels

Interior Finish: 304 Stainless Steel Interior Panels

Level II Thermal Break

6 inch tall Base Rail

Mixing Box

Shipping Split After


Damper: Left Side Premium Parallel
Louver Rear
Damper: Rear Premium Opposed
Door Right Side
Bag/Cartridge Filter

Bag/Cartridge Filter 6 - 12 IN. Side Loading


Qty (6) 24in. x 24in.
Pre Filter : 2In. Flat Filter
Qty (6) 24in. x 24in.
Door Right Side
Coil Connection Housing

Double Wall
24in. deep
Chilled Water Coil

304 Stainless Steel Drain Pan Left Side


UVC Factory Installed and wired for 115 volt
Chilled Water 20.31 sq.ft 6 Row 12 FPI Full Circuit
Coil Connection Left Side
5/8 in. Tube Diameter
0.035 in. Tube Wall Thickness
AL fins 304 Stainless Steel Casing
Non-Ferrous Header
No Coating
Cooling Performance Ratings
Altitude, ft 0 EWT, °F 42.00
Face Vel., fpm 486.9 LWT, °F 52.40
Site Airflow, CFM 9890 Rise, °F 10.4
Std. Airflow, CFM 9890 EADB, °F 86.80
Total Clg. Cap, MBH 697.30 EAWB, °F 71.90
Sen. Clg. Cap, MBH 401.40 LADB, °F 49.20
Flow Rate, gpm 134.0 LAWB, °F 49.10

SUBJECT TO CHANGE WITHOUT NOTICE


6.26
Job Name Pepsi
Mark for AHU-1 (Dye y Man Fill)
Date November 22, 2022

Fluid PD, ft wg 13.3 Air Friction, in wg 1.02


Fluid Vel., ft/s 4.8
Note: Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-
Heating Coils Certification Program which is based on AHRI Standard 410. Certified
units may be found in AHRI Directory (www.ahridirectory.org).
Door Right Side
Hot Water Coil

Standard Drain Pan Left Side


Hot Water 20.31 sq.ft 1 Row 12 FPI Half Circuit
Coil Connection Left Side
5/8 in. Tube Diameter
AL fins Galv. Casing
Steel Header
No Coating
Heating Performance Ratings
Altitude, ft 0 Fluid Vel., ft/s 1.8
Face Vel., fpm 486.9 EWT, °F 113.00
Site Airflow, CFM 9890 LWT, °F 96.3
Std. Airflow, CFM 9890 Drop, °F 16.7
Heating Cap., MBH 208.60 EAT, °F 47.00
Flow Rate, gpm 25.0 LAT, °F 66.50
Fluid PD, ft wg 0.7 Air Friction, in wg 0.13
Note:

* Ent. Fluid Temp. is outside the scope of AHRI Std. 410

* Coil is outside of the scope of AHRI certification, but is rated in accordance with AHRI
Standard 410.
Door Right Side
Bag/Cartridge Filter

Bag/Cartridge Filter 15 - 30 IN. Side Loading


Qty (6) 24in. x 24in.
Door Right Side
Plenum

Shipping Split After


Length 24 inches
304 Stainless Steel Drain Pan Right Side
Door Right Side
Viewport Right Side
Draw-Thru Supply Fan

Rear Inlet
Fan Sled
Plenum Fan B PFMV01273Q
1643 fanRPM Class II
Field Supplied Discharge

SUBJECT TO CHANGE WITHOUT NOTICE


6.26
Job Name Pepsi
Mark for AHU-1 (Dye y Man Fill)
Date November 22, 2022

Right Side Fan Motor Location


Spring Fan Isolation
Motor
15 HP High Efficiency TEFC 400 3Ph 50Hz 1500 RPM
Belt Drive
1.2 Service Factor
Fixed Pitch Drive
1 or more belts
Door Right Side
Viewport Right Side
Marine Light Right Side
Door Left Side
Performance Ratings
Site Airflow, CFM 9890 Htg. Coil Static, in wg 0.13
Altitude, ft 0 Other Losses, in wg 0.00
Std. Airflow, CFM 9890 Accessories Static, in wg 1.99
Upstream Ext. Static, in wg 0.70 Total Static, in wg 5.34
DownStream Ext. Static, in wg 1.50 Calculated Fan Speed, rpm 1643
Clg. Coil Static, in wg 1.02 Calculated Fan BHP 12.5
Acoustic Data:
Freq. Disch. Inlet Casing 1000 hz 90 90 84
63 hz 85 85 81 2000 hz 86 86 80
125 hz 84 84 79 4000 hz 81 81 75
250 hz 88 88 82 8000 hz 80 80 75
500 hz 91 91 87
Coil Connection Curb

14.0in Curb Height


Unit Curb

14.0in Curb Height


Configuration Notes

A piped connection is within 1.2 inches of coil connection housing


inside wall. Verify that ample space is available for all components
contained in the coil connection housing.
Drain is located inside Coil Connection Housing. Ensure this is
correct.
Drain is located inside Coil Connection Housing. Ensure this is
correct.
An Outdoor Plenum fan may not discharge through the roof of the
unit.
If a bottom connection is required, use a Discharge Plenum Section.
Discharge duct(s) must be gasketed and screwed directly to the
discharge panel of the unit.
Weights and Dimensions

(LxWxH in ft in) 21' 10" x 8' 9" x 6' 2" **

SUBJECT TO CHANGE WITHOUT NOTICE


6.26
Job Name Pepsi
Mark for AHU-1 (Dye y Man Fill)
Date November 22, 2022

Operating 6983 LB **
Weights and Dimensions are approximate. Weights include base unit weight, coils (wet & dry), fans and
fan motors, and other components, but does not include filters, drives and skids. Approximate dimensions are
provided primarily for shipping purposes. Shipping skids are not included.
All filter media efficiency ratings are for the filter media only.

SUBJECT TO CHANGE WITHOUT NOTICE


6.26
Project Name: Pepsi
Mark For: AHU-1 (Dye y Man Fill)
Supply Fan Curve

You might also like