sadia VG FANCOIL SALA 1 ou 2

Munters ICA--090

Prepared for :
Date : 27/set/07

,
Prepared by : ANTONIO FABIO
Reference No. : Quote
System Flow Diagram

Altitude 0 ft

FAN COIL SALA 1 OU 2


A B C D E F
SCFM 3,530 20,000 23,530 23,530 23,530 23,530
°F 96 50 57 57 37 40
gr/lb 1.9 35.0 30.0 30.0 29.3 29.3
A27147

Release 4.4.9
sadia VG FANCOIL SALA 1 ou 2
ICA--090
Altitude 0 ft

System Configuration Data

System Level Configuration Items:

Model No. ICA-090

Internal Material Stainless Steel

External Material Galvalume

Wall Thickness 2.5 inch

Roof Flat - Indoor locations

Length Limit NONE

Access/Removal side * From the LEFT looking in the direction of air flow

Floor Drains No Floor Drains

Entering Air Connection Open

Leaving Air Connection End Discharge

System Power 460/3/60

System FLA 33.8

Component Options:

Component View Plenum Other


Name Port Light
Mixing Box No No RA Connection on Non-Access Side

Med. Eff Filter No No Side Loading

Cooling Coil No No None

Fan No No None

Access Section No No None

* See the system drawing for further details on component access and removal.
A27147

Release 4.4.9
sadia VG FANCOIL SALA 1 ou 2
ICA--090
Altitude 0 ft

Equipment Schedule
Air Filter
Media Type Panel
Filter Thickness in 2.0
Filter Efficiency % 30%
Filter Class UL 1
Face Velocity FPM 370
Initial Resistance ''WC 0.16
Final Resistance ''WC 0.90
Filter Sizes 7 @ 12 in x 24 in, 12 @ 24 in x 24 in

Cooling Coil - Chilled Water with Ethylene Glycol (2 coils - energy and flow values are totals)
Entering Conditions °F / gr/lb 57 / 30.0
Leaving Conditions °F / gr/lb 37 / 29.3
Capacity Btuh 522,594
Air Flow SCFM 23,530
Face Area ft² 2 Coils @ 31.5 each
Face Velocity FPM 373
Air Resistance ''WC 0.47
Water Consumption GPM 108.6
Percent Glycol % 20
Fluid Resistance feet 18.8
Connection Size Sweat 2.5
Rows 10
Tubes .625 dia x .035 thk Copper
Fins 9 FPI, .0075 thk Aluminium
Case GalvanizedSteel

Supply Air Fan


Model 270 DWDI
Type BI-AF - DWDI
Air Flow SCFM 23,530
Entering Conditions °F / gr/lb 37 / 29.3
Leaving Conditions °F / gr/lb 40 / 29.3
Total Pressure ''WC 5.75
External Pressure ''WC 3.68
Fan Speed RPM 1815
Fan Power hp 28.5
Motor Speed RPM 3450
Motor Power hp 30.0
Motor Enclosure TEFC
Motor Class Class B
Housing Construction Welded Steel
Vibration Isolation Spring
A27147

Release 4.4.9
sadia VG FANCOIL SALA 1 ou 2
ICA--090
Altitude 0 ft

Filter Specifications

Filter

COARSE FILTERS

1. Air is filtered through filters of 25% to 30% minimum efficiency with 90% to 92% arrestance minimum as rated by
ASHRAE Test Standard 52-76. Filters are disposable 2" deep, pleated disposable type with non-woven media held in
place by a welded wire grid. Filters are held in aluminum channels top and bottom with spacers and back-up plates to
minimize bypass. Filter channels are welded and sealed in place to eliminate air bypass.

FINE FILTERS

1. Air is filtered through 12 inch deep pleated disposable filter of efficiency show in the schedule. All filters are
constructed of a non-woven media held in a rigid frame with welded wire support grid. The 12 inch deep filter also contains
contour supports and is held in a specifically designed rigid frame using spring type clamping fasteners. Filter mounting
partitions are welded and sealed in place to eliminate air bypass.

INITIAL DUST SPOT E0 <= 20 % E0 20 => %


EFFICIENCY (E0) Average Average
Type Of Filter Arrestance AM % Efficiency Em% EN 779 EUROVENT 4/5 ASHRAE
----------------------------------------------------------------------------------------------------------------------------------------------------------------
Coarse Filter (Panel) Am < 65 ---------- G1 EU 1 G 60
Coarse Filter (Panel) 65 <= Am < 80 ---------- G2 EU 2 G 70
Coarse Filter (Panel) 80 <= Am < 90 ---------- G3 EU 3 G 85
Coarse Filter (Panel) 90 <= Am - - - ---------- G4 EU 4 G 90
Fine Filter (Bag) -------- 40 <= Em < 60 F5 EU 5 F 45
Fine Filter (Bag) -------- 60 <= Em < 80 F6 EU 6 F 65
Fine Filter (Bag) -------- 80 <= Em < 90 F7 EU 7 F 85
Fine Filter (Bag) -------- 90 <= Em < 95 F8 EU 8 F 95
Fine Filter (Bag) -------- 95 <= Em - - F9 EU 9 F 95
A27147

Release 4.4.9
sadia VG FANCOIL SALA 1 ou 2
ICA--090
Altitude 0 ft

Cooling Coil

Outlet

23,530 SCFM 23,530 SCFM

57 °F 37 °F

30.0 gr/lb 29.3 gr/lb

Inlet

Performance Data:

Air Side Capacity Sensible 513,926 Btuh


Latent 8,668 Btuh
Total 522,594 Btuh

Face Velocity 373 FPM Pressure Loss 0.47 ''WC

Coolant Flow Rate 108.6 GPM Tube Velocity 3.1 FPS


Entering 34 °F Leaving 44 °F
Pressure Loss 18.8 feet

Physical Data:
Dimensions 42.0 in FH 108.0 in FL 63.0 ft²
10 Rows 9.0 fpi 0.625 in Tubes
Copper Tubes 0.625 in Diameter 0.035 in wall
Aluminum Fins 0.0075 in Thick Corrugated Fins
Galvanized Casing
2.5 Conn. Size Circuiting 3/4 Serpentine
(MPT)
A27147

Release 4.4.9
sadia VG FANCOIL SALA 1 ou 2
ICA--090
Altitude 0 ft

Cooling Coil Specifications


CHILLED WATER COOLING COILS

1. Coils shall be sized to provide the full capacity scheduled. Coils shall be arranged to condition the full volume of
process air with bypass or balancing dampers as required. Tube water velocities are 7 fps or less and air face velocities
are 500 fpm or less. Coil circuiting provides for optimum performance with minimum pressure loss. Coil shall be designed
for 250 PSI working pressure and factory tested under water at 300-PSI air pressure.

2. Chilled water coils are fin and tube type, constructed of seamless copper tubes of .625 inch diameter with .035
inch wall thickness and aluminum plate type fins of .0075 inch thickness, mechanically bonded to tubes. Casing and tube
support sheets are 16 gauge galvanized steel formed to provide mounting flanges and structural support for the finned-tube
assembly. Supply and return headers are heavy wall copper pipe with vent and drain connections. Supply and return
connections are brazed in place with sweat connections for piping. Coils conform to ARI standard 410.

3. Chilled water coils shall be equipped with a drain pan for removal of condensate and to collect and remove coolant
in case of leaks. The drain pan is to be constructed of welded 304 SS and bolted in place. Cooling coil drain pans shall
extend the entire length of the coil and shall extend a minimum of 6 inches beyond the air leaving side of the coil. The drain
pan shall be a minimum of 2 inches deep and have a minimum pitch of 1 inch. The drain pan shall be triple sloped to ensure
zero standing water. Drain connection shall extend through unit base. Connection to be 1 inch male NPT.
A27147

Release 4.4.9
sadia VG FANCOIL SALA 1 ou 2
ICA--090
Altitude 0 ft

Supply Air Fan


Description:
Fan: Motor and Drive:
Size: 270 DWDI Motor Power 30.0 hp
Type: DWDI BI-AF Motor Speed 3450 rpm
Fan Speed: 1815 Drive Type Belt Drive
Rotation: CW
Vibration Isolation: Spring

Performance:
Component Initial Final
Mixing Box .20 .20
Med Eff Panel Filter .16 .90
Cooling Coil .47 .47
Supply Fan Diffuser .50 .50
Access Section .00 .00
Total 1.33 2.07

External Static 4.42 3.68


Pressure

Fan Performance @ 37 °F
Design Point
9.0

8.0

7.0
Static Pressure ''WC

6.0

270 DWDI @
5.0 1815 rpm

4.0

3.0

2.0
System
Final
System
1.0 Initial

5000 10000 15000 20000 25000 30000


Air Flow - CFM