Delhi Metro Contract CP Kukreja AssociatesAHU common HK Station ECS System

BADD4(A) PHASE-IIContract CE for all the stations Data SheetECS Data Sheets
10 and CE-11
A

Schedule of Air Handling Units

Data Sheet for Air Handling Unit (North and South)

S Tag No. Capacity Total Cooling Motor Coil Area Served


No. M3/sec Pressure Capacity KW Entering
Pascal’s KW Condition
DB WB 
 °C °C
1 AHU-001 35 1500 1024 2x45 31.1 21.60 Platform &
Concourse
North
2 AHU-002 35 1500 1024 2x45 31.1 21.60 Platform &
Concourse
North
3 AHU-003 35 1500 1024 2x45 31.1 21.60 Concourse &
Platform South
4 AHU-004 35 1500 1024 2x45 31.1 21.60 Concourse &
Platform South

Notes

1) Air Handling Units shall be as per specifications, data sheets and drawings.
2) All accessories as per data sheets shall be provided
3) Pressures and Motor ratings are approximate. Vendors shall do their own calculations &
offer the equipments as required.
4) Each centrifugal fan shall be provided with access panel and drain plug.

1
Delhi Metro Contract CP Kukreja AssociatesAHU common HK Station ECS System
BADD4(A) PHASE-IIContract CE for all the stations Data SheetECS Data Sheets
10 and CE-11
A

AHU Capacity
As per chart given above.approval given BOQ
(ECS North and South)
Unit Performance ARI – 430, Coil Performance ARI – 410,
Fan AMCA-210 ASHRAE / Eurovent and Unit Performance ,coil
Reference Code / Standard
performance mustshall be certified with Eurovent StandardAHRI
EN:1886
Flow Rate As per chart given aboveBOQ
Total Quantity As per chart given above BOQ
Noise Criteria Refer to Specification (85 dBA at 1 m distance in plant room)
Tag No To Be Marked On AHU With Black Letter.
Tag No
SS Tag To Be Firmly Attached
Thermal Break Profile As per mfg. Standard
Construction Sectionalized / Modular Double Skin Type 60MM thick
Casing
Out side As per specifications1.2mm/or as per Manufacturer Standard
Inside As per specifications 1.0 mm or as per Manufacturer Standard
Insulation As per specifications 60 MM thick
Height of the unit As dictated by plant room layout – refer to drawings
1. Fan Section
Number of Sections 2. Coil Section
(functional – not necessarily 3. Filter Section
physical) 4. Mixing box Section
5. Any other section if required
Access Door Access door to be provided in fan section & mixing box.
Damper
Type Non Fire Rated Parallel Blade (Refer the Data Sheet For Damper)
Inlet One at the suction side (MD)
Outlet One at the discharge of each fan Motor Operated Damper (MOD)
Modular Frame Aluminum Alloy
Base Frame GSS Confirming To BS EN 10142 1991
Drain
Pan Stainless Steel (18G) with Insulation
Insulation Polyurethane Foam / Polyethylene foam
Thickness And Density 12 mm Thick Density 38-40 kg/m3
Connection 40 mm Connection On One Side
Fan Section
Fan
Centrifugal - Backward Curved Aerofoil Construction statically and
Type
Dynamically Balanced
Characteristics Non Over Loading

2
Delhi Metro Contract CP Kukreja AssociatesAHU common HK Station ECS System
BADD4(A) PHASE-IIContract CE for all the stations Data SheetECS Data Sheets
10 and CE-11
A

Number Two per AHU


Total Pressure As Aboveper BOQ
Blade As per specifications
Fan Section
Fan
Shaft As per specifications
Outlet Velocity 12.710 m/s (Max) or as per manufacturer standard.
Housing As per manufacturers standard
Hub As per manufacturers standard
Mounting As per Mfg. Std.
Bearings – Shaft As per Mfg. Std.
Connection Flame Proof Flexible Connection
Vibration Isolator Spring Isolators
Accessories With access door, drain plug spring vibration isolator
Drive
Arrangement Belt Drive
Belt Type V Groove Anti Skid
Minimum Four+1 (Each of 50% capacity to be provided) F Class
No Of Belts
Insulation
Motor
Type TEFC Induction Motor IP-55 Protected, EFF-1 Class
As Per IEC 34 – 1, IEC 72 – 1, BS – 3979, BS – 4999, BS – 5000,
Reference Code / Standard

Electric Supply Three Phase, 415 V, 50 Hz, AC Supply


RPM 1440 (Max)
Mounting Slide Rails
Coil Section

Coil

Valve 2-Port Motorized Valve Each/coil

Entering Water Temperature 8 °C

Leaving Water Temperature 15 °C


Velocity Air 2.8 5 m/s/or as per manufacturers standard
Air Entering Temp As per sheet enclosed
Air Leaving Temp As per sheet enclosed
Test Pressure 23 kg/cm2 (Hydro) or as per manufacturer Standard

3
Delhi Metro Contract CP Kukreja AssociatesAHU common HK Station ECS System
BADD4(A) PHASE-IIContract CE for all the stations Data SheetECS Data Sheets
10 and CE-11
A

No of Rows 68 ROWS deep (Or to suit duty)


Tube Copper, 27 Gauge, 12.5 mm OD
Coil Mounting GSS Confirming To BS EN 10142 1991
5 per 10 mm,Minimum 8 to 10 FPI 38 Gauge Aluminum Maximum
Fins
10 FPI
Type Of Fins Sinusoidal Wave Pattern
Fin Bonding to Tubes Mechanical Expansion / Hydraulic Expansion
Filter Section
Filter
Frame GI with epoxy painting, mMade up of SS 304 material
Type Panel Type .
Media Non flammable , Non toxic, Low smoke synthetic resign media
confirming to NFPA, UL, EN-779 .
Sealing of Media By means of epoxy (CIBA make).
Efficiency 90% down to 10 micron particle size.

1) Air Handling Units shall be as per specifications, data sheets and drawings.
2) All accessories as per data sheets shall be provided
3) Pressures and Motor ratings are approximate. Vendors shall do their own calculations &
offer the equipments as required.
4) Each centrifugal fan shall be provided with access panel and drain plug.
5) AHU’s Shall be fitted with UVC emitters minimum 20 Tubes