Delhi Metro Contract Mott MacDonaldAir Cooled Chiller Station ECS

CEDD 3, Phase-IIIContract CE 10 Pumps, common for all stations Data Sheet


and CE-11

DATA SHEET FOR CHILLED WATER PUMP (Primary)


FOR AIR COOLED CHILLER

Type End Suction Chilled water primary pumps


Reference Code / Standards ISO : 9906 / IS 9079
Tag No To Be Marked On Pump With Black Letter.
Tag No
SS Tag To Be Firmly Attached
Total Number Two (One Working + One Stand By) As per BOQ
Service Continuous Duty
Capacity LPS 7.85 As per BOQ
Operating Head KPa 250 As per requirement
Operating Pressure 6 Kg / cm2
Noise Criteria 85 dbA at 1 mt.
Number Of Stages Single Stage
Impeller
Material Bronze
Casing Material Cast Iron ASTM AI59 43000
Balancing Statically and Dynamically Balanced
Neck Ring Bronze
Lock Nut Bronze
Logging Ring Brass
Pump Speed (nominal) 1450 RPM (Maximum)
Shaft
Seal Mechanical Type
Bearing Drive End Roller Bearing
Bearing Non – Drive End Ball Bearing
Material EN-8 / High tensile stainless steel strength
Sleeve Renewable Sleeve
Mounting Shaft Key And Positive Locking Device
Packing Graphited Cotton
Stuffing Box Cast Iron / Mild Steel
Connection
Suction Flange Type Horizontal
Discharge Flange Type Vertical
Flange Drilled to as per BS Standard, Suitable for ANSI 125
Flexible Yes – On Both Suction And Discharge
Drive Arrangement Direct – With Flexible Coupling And Coupling Guard
Direction Of Rotation Anti Clock Wise / Clock Wise From Driving End

1
Delhi Metro Contract Mott MacDonaldAir Cooled Chiller Station ECS
CEDD 3, Phase-IIIContract CE 10 Pumps, common for all stations Data Sheet
and CE-11

Motor
Type TEFC Induction Motor ( IP – 55 ), EFF-1
Design As Per IEC 34 – 1, IEC 72 – 1, BS – 4999
RPM 1450 (Max)
Power Supply Three Phase, 415 V, 50 Hz, AC Power Supply
Vibration Isolation Inertia Base, Spring Isolation
Mounting Arrangement Suitable Base Frame For Floor Mounting
Lifting Arrangement Lifting Eye At Suitable Location And Number
Paint Epoxy Paint, After Surface Treatment For Corrosion

Notes
1. Pumps shall be provided with common base frame, inertia base, spring vibration isolation pads,
suction & discharge pressure gauges with isolation valves, test and / or air vent cocks, gland drain
& other accessories as required.
2. Pumps starters shall be star delta air break type
3. Pump head given is approximate and vendor shall do their own calculations and offer the pumps
accordingly.
4. Pump motor shall be EFF-1, non overloading up to out off conditions riding over complete curve.