You are on page 1of 2

Delhi Metro Contract CP Kukreja AssociatesCommon for INA Station ECS System

BADD4(A) PHASE-IIContract CE10 Cooling Towers at all Stations Data SheetECS Data Sheets
and CE 11

DATA SHEET FOR COOLING TOWER

Counter Flow, Vertical Discharge Mechanical DraftInduced Draft,


Type Counter Flow/Cross Flow Type with Vertical Discharge, CTI
CERTIFIED
Reference Code / Standard CTI – ATC 105 – 1990STD 201-1991
Tag No To Be Marked On Cooling tower With Black Letter.
Tag No
SS Tag To Be Firmly Attached
Total Number 3 No.As per BOQ
Heat Rejection Capacity 1670 KW As per BOQ
Fluid Water
Condenser Inlet Temp. 36.4 °C
Condenser Outlet Temp. 32.2 °C
Designed WBT 29 °C
Noise Criteria 85 dBA at 1 m
Water Flow Rate 101 LPSas per BOQ
Fiber Reinforced Plastic, with a sturdy Structural Hot Dipped Galvanized
Construction Material
Frame
Total Water Loss 1 % Max (combined drift and evaporative losses).
Water Basin – Material Fiber Reinforced Plastic
Connections
Size As per manufactures standard
Inlet And Outlet As per manufactures standard (Flanged) To BS
Regular Arrangement Suitable For Level Switch Controller And Ball
Make Up
Valve With Quick Fill Arrangement
Drain And Overflow With Valve Arrangement In Drain
Fan
Type Aerofoil Design, Statically and Dynamically Balanced
Static As per manufactures standard
Number of fans Minimum Two Numbers
Blade / Hub Cast Aluminum Alloy
Shaft EN-8
Heavy Duty ,Roller BearingSelf Aligned Grease Packed Bearing with
Bearing
moisture proof seals and integral slinger collars.
Guard 16 SWG Wire Mesh With Frame
Drive Arrangement Speed reduction gears or V Type BeltsThrough gear box
Motor
TEFC – Two speed Induction Motor (IP– 55), With Weather Protection,
Type
EFF-1 Class with service factor of 1.15
As Per IEC 34 – 1, IEC 72 – 1, BS – 3979, BS – 4999, BS – 5000,
Design
Power Connection Three Phase, 415 V, 50 Hz, AC Supply
RPM 1400 (Max) (Two speed)
Nozzles Design As per mfg. Design
Nozzles Material Poly Propylene / HDPE
Cells PVC Honeycomb Block / PVC Fill Block Formed By Continuous

Page 1 of 2
Delhi Metro Contract CP Kukreja AssociatesCommon for INA Station ECS System
BADD4(A) PHASE-IIContract CE10 Cooling Towers at all Stations Data SheetECS Data Sheets
and CE 11

ProcessesAs per manufacturers Standard


Number Of Cells Two Cell
Mounting Legs And Ladder With Hand Rails Minimum 300 mm Wide,
Accessories
Duly Treated For Corrosion, Inspection window
Header / Fittings Galvanized Steel / PVC / HDPE
Base Frame and ladder GSS/MS Hot Dipped Galvanized
Paint on base frame and ladder Hot dipped Galvanized(minimum 750 GSM)
Thickness Casing as per CTI standard and Basin-5mm 4mm (Minimum)
Height of cooling tower As per manufactures standard

Note: 1) Cooling towers shall conform to DMRC specifications.

2) Local push buttons for C.T. motors shall be provided.

3)All hardware used for fixing of cooling tower shall be of SS 316

4) Level switch shall be provided for each cooling tower

Page 2 of 2