Contract : CE 10 and 11 Data Sheet Common to Air Cooled ECS

Chillers at all Stations Data Sheet

DATA SHEET FOR AIR COOLED SCROLL CHILLERS

Unit Type Air cooled scroll type


Reference Code / Standard ARI 550/590(latest), ASME sec VIII Div 1, ANSI B 31.5
Certification AHRI / Eurovent
Tag No To Be Marked On Chiller With Black Letter.
Tag No
SS Tag To Be Firmly Attached
Unit Capacity As per BOQ
Evaporator water flow rate LPS 2 gpm/ton minimum
Total Quantity 2 NosAs per BOQ
COP @ ARI Conditions 3.0
Maximum iKW @ ARI 1.16
Maximum NPLV (kW/TR) 0.83
Refrigerant R – 410A
Noise Criteria 80 dB at 1m distance
Differential Pressure Switch One for Chiller
Vibration Isolators Spring Type Vibration Isolator.
1. Compressor
2. Chiller
Unit Consisting Of 3. Air cooled Condenser
4. Microprocessor Based Control Panel
5. Soft starter
Welded wire-mesh guards must be mounted on the exterior
Unit Protection of the unit. This prevents unauthorized access, yet provides free air
flow. (Factory-mounted)
Compressor
Type Scroll Compressor
Test Pressure 25 Bar (G) (Hydro) or as per manufacturer standard
Working Pressure 17.57 Bar (G) (Max) or as per manufacturer standard
Housing As per manufactures standard
Rotor As per manufactures standard
Anti Friction Type Cylindrical & Ball Bearings for Axial & Radial loads
Bearings
as per service life as per DMRC specifications.
Shaft Seal N/A
Refrigerants’ Valves Isolation Valves as per manufactures specifications to be provided.
Capacity Control Stepped capacity control
No of Refrigerant Circuits 2
Oil Filter 3 micron absolute oil filters with isolation valve.
Condenser
Air cooled, either Unimetal construction or epoxy coated ( post coated
Type dipped condenser coil at factory) cooper tubes with aluminium fins to
avoid galvanic corrosion

1
Contract : CE 10 and 11 Data Sheet Common to Air Cooled ECS
Chillers at all Stations Data Sheet

High efficiency (EFF-1), direct drive, 6 pole, 3 phase, insulation class


Condenser fans “F”, current protected, Totally Enclosed Air-Over (TEAO), rigid
mounted, with double sealed, permanently lubricated, ball bearings
Air Inlet Temp. 35 °C
Chiller
Type DX, Shell & Tube
Water
Inlet Temp. 15 °C

Outlet Temp 8 °C

Fouling Factor 0.000088 Sq.Mtr.° C / W


Pressure drop 10 ft (max)
Test Pressure (pneumatic) As per manufacturer’s quality procedures
Tube
Material Copper Or Copper Alloy (19 mm OD, 22 Gauge)
Test Pressure (pneumatic) 15.75 Bar
Control Panel
Microprocessor panel in IP55 panel, Programmable, BMS interfaced
Type
(MODBUS)
Chilled water temp 0C Entering And Leaving Temperature Status
Ambient Temp Ambient Air Temperature Status
Oil Pressure Measuring Device To be provided
Compressor No. of Running Compressor
Starter Type Soft starter
Panel
Material M.S Heavy Gauge / G.I.
Door Control Interlock
Paint Anti Corrosive – Powder Coating Duly Treated For Corrosion
IP Rating IP55 (Drain Rain tight)
System Protection
Low Suction Pressure System Shut Down
High Discharge Pressure System Shut Down
Freeze Protection System Shut Down
Motor Protector/Mechanical High System Shut Down
Low Evaporator Temperature System Shut Down
Low Ambient Temp Chiller Shut Down
Low Leaving Chilled Liquid
Chiller Shut Down
Temp
Under Voltage Safety Unit Shut Down
Compressor Failure Alarm And Tripping
Anti Recycle Tripping

2
Contract : CE 10 and 11 Data Sheet Common to Air Cooled ECS
Chillers at all Stations Data Sheet

Winding Temp. Sensor Tripping

Notes:

1. Chillers shall be as per DMRC specifications. Any deviations to the specifications should be pointed
out at tendering stage.
2. Chiller Motor starter shall be Soft starter without transient type.
3. Above data is not by way of limitation. Whatever is required for making the unit complete to meet the
intent of specifications shall be deemed to have been included in the scope of work.
4. Flexible Connections at chiller shall be provided.
5. Over current, phase reversal, single phasing protections and KW meter shall be provided.
6. Refrigerant sensor shall be installed.
7. Performance rating.
8. The unit shall be selected for the lowest operating power consumption and noise level. Computer
selected capacity rating and power consumption with operating points clearly indicated, shall be
submitted with the tender as per technical data specified in the tender on full and partial load and shall
be verified at the time of testing and commissioning of the installation. The gear losses should be
included in the IKW/TR figures indicated by the bidders. As energy conservation is today’s theme, it
is expected from each bidder to offer highly energy efficient machines. Necessary credit of
preference will be given on this account. Power consumption shall be computed from measurements
of incoming voltage and input current.
9. Capacity and power consumption shall be computed from the measurements of incoming voltage,
input current, temperature (inlet & outlet) and water flow rate. Necessary provision shall be kept for
providing flow meter and transducers required for computing capacity.
10. The supplier has to confirm that the IKW/TR data for the chilling unit submitted by him has been
selected at the specified operating parameters and at constant condenser entering water temperature.
11. Also the machine shall be rated for actual capacity at specified conditions.
12. Only ARI / Eurovent certified chilling machine shall be acceptable and the computer performance
sheet. duly certified as per ARI / Eurovent shall be submitted along with the technical submittal.