Contract : CE 10 and 11 Data Sheet Common to Air Cooled ECS
Chillers at all Stations Data Sheet
2
Contract : CE 10 and 11 Data Sheet Common to Air Cooled ECS
Chillers at all Stations Data Sheet
Notes:
1. Chillers shall be as per DMRC specifications. Any deviations to the specifications should be pointed
out at tendering stage.
2. Chiller Motor starter shall be Soft starter without transient type.
3. Above data is not by way of limitation. Whatever is required for making the unit complete to meet the
intent of specifications shall be deemed to have been included in the scope of work.
4. Flexible Connections at chiller shall be provided.
5. Over current, phase reversal, single phasing protections and KW meter shall be provided.
6. Refrigerant sensor shall be installed.
7. Performance rating.
8. The unit shall be selected for the lowest operating power consumption and noise level. Computer
selected capacity rating and power consumption with operating points clearly indicated, shall be
submitted with the tender as per technical data specified in the tender on full and partial load and shall
be verified at the time of testing and commissioning of the installation. The gear losses should be
included in the IKW/TR figures indicated by the bidders. As energy conservation is today’s theme, it
is expected from each bidder to offer highly energy efficient machines. Necessary credit of
preference will be given on this account. Power consumption shall be computed from measurements
of incoming voltage and input current.
9. Capacity and power consumption shall be computed from the measurements of incoming voltage,
input current, temperature (inlet & outlet) and water flow rate. Necessary provision shall be kept for
providing flow meter and transducers required for computing capacity.
10. The supplier has to confirm that the IKW/TR data for the chilling unit submitted by him has been
selected at the specified operating parameters and at constant condenser entering water temperature.
11. Also the machine shall be rated for actual capacity at specified conditions.
12. Only ARI / Eurovent certified chilling machine shall be acceptable and the computer performance
sheet. duly certified as per ARI / Eurovent shall be submitted along with the technical submittal.