SUB: VFD PARAMETER SETTING (ANALOG INPUT + FIXED FREQUENCY) VFD MODEL: SIEMENS MM420 IO WIRING DESCRIPTION DESCRIPTION

REMARKS SL NO: TERMINALS 1 3 ANALOG INPUT (0-10VDC) AUTO MODE SPEED REFERENCE SOURCE 2 4 COMMON 3 12 ANALOG OUTPUT (+) SPEED FEEDBACK (0-20mA) 4 13 ANALOG OUTPUT (-) NPN 5 9 INTERNAL 0V SUPPLY (SINK) 6 6 VFD ENABLE/DISABLE CMD. AUTO MODE VFD ENABLE/DISABLE JOG RIGHT SELECTION IN HAND HAND MODE VFD RUN IN PRESET SPEED 7 5 MODE SELECTION -1 RELAY NO 8 10 ENABLED WHEN DRIVE FAULT ACTIVE OUTPUT COM 9 11 VFD PARAMETER SETTING DESCRIPTION SETTING UNIT IN kW & 50Hz SELECTION 0 MOTOR POWER (kW) * MOTOR FREQUENCY (Hz) 50 MOTOR VOLTAGE (V) * CURRENT RATING (A) * MOTOR SPEED (RPM) * OVERLOAD FACTOR 150 2 CONTROL FROM - VFD TERMINALS 2 ANALOG SETPOINT FOR SPEED CONTROL 0 MINIMUM FREQUENCY 50 MAXIMUM FREQUNECY ACCELERATION TIME (S) 30 DECELERATION TIME (S) 10 0 NO QUICK COMMISSIONING - REQUIRED TO SET VFD 0 READY (SETTINGS COMPLETED) 1 QUICK COMMISSIONING 30 FACTORY RESET AFTER P0970 = 1 1 STANDARD USER 2 EXTENDED USER - REQUIRED TO MAKE SETTINGS 3 EXPERT USER - UNLOCK ALL PARAMENTERS NPN MODE SELECTED - TERMINAL 9 0 10 TERMINAL 5 - JOG RIGHT: HAND MODE RUN 1 TERMINAL 6 - ENABLE VFD: AUTO MODE RUN 52.3 RELAY OUTPUT: CONFIGURED FOR DRIVE FAULT 50 JOG FREQUENCY: HAND MODE RUN FREQUENCY

SL NO: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

PARAMETER P0100 P0307 P0310 P0304 P0305 P0311 P0640 P0700 P1000 P1080 P1082 P1120 P1121 P3900 P0010

16 17 18 19 20 21

P0003 P0725 P0701 P0702 P0731 P1058

NOTE: * TO BE SET ACCORDING TO MOTOR NAMEPLATE RATING. CURRENTLY SET AT DRIVE RATINGS *DIP SWITCH SEETTING TO BE DONE FOR 50Hz FOR FACTORY RESET: P0010 = 30 P0970 = 1 10 SEC REQUIRED FOR RESET.