SINAMICS G 120 AC DRIVE

COMMISSIONING
BY B.PANDU RANGA RAO
FACTORY SETTING
STEP 1:

 P 0010 = 0 :READY
1: QUICK COMMISSIONING
2: POWER UNIT COMMISSIONING
3: MOTOR COMMISSIONING
5: TECHNOLOGICAL APPLICATION UNITS.
29: ONLY SIEMENS INTERNAL
30 : PARAMETER RESET.
39 : ONLY SIEMENS INTERNAL.
49 : ONLY SIEMENS INT V/F LINEAR.
 P0970=1

THEN ALL THE PARAMETERS WILL RESET.


STEP 2:
 P0010=1
 P1300(CONTROL MODE) : V/F LINEAR =0

 P0100: FOR 50 HZ=0


FOR 60 HZ=1

 P304(MOTOR VOLTAGE): SPECIFICATION ON NAME PLATE OF MOTOR.

 P305(MOTOR CURRENT):SPECIFICATION ON NAME PLATE OF MOTOR.

 P307(MOTOR POWER):SPECIFICATION ON NAME PLATE OF MOTOR.


 P311(MOTOR RPM): SPECIFICATION ON NAME PLATE OF
MOTOR.

 P308(POWER FACTOR):SPECIFICATION ON NAME PLATE OF


MOTOR.

 P309(RATED MOTOR EFFICIENCY):SPECIFICATION ON NAME


PLATE OF MOTOR.

 P310(RATED MOTOR FREQUENCY):SPECIFICATION ON NAME


PLATE OF MOTOR.

 P311(RATED MOTOR SPEED):SPECIFICATION ON NAME PLATE OF


MOTOR.
P1900(MOTOR ID) : OFF = 0
STILL ROTATION = 1

STILL =2
ROTATION =3

P15(MACRO PARAMETER) : DEFAULT VALUE=12

P1080(MINIMUM SPEED) :0

P1082(MAXIMUM SPEED) :

P2000(REFERENCE SPEED) :
P1120(RAMP UP) :10sec (Default)

P1121(RAMP DOWN) :10sec (Default)

P3900(END OF QUICK COMMISSIONING):0=NO QUICK


COMMISSIONING
1=MOTOR CALCULATION AND RESET
ALL PARA METERS.
2= MOTOR CALCULATION AND
RESET ALL THE I/0 SETTING TO THE
FACTORY SETTING.
3=ONLY MOTOR CALCULATION
OPERATING MOTOR BY USING ANALOG INPUTS WITH HELP OF
POTENTIOMETER.
 P756(INPUT RANGE): 0 TO 10 V = 0

 P1070(MAIN SET POINT)=r755

DIGITAL INPUTS

 P840(START/STOP):5 DI 0=r722.0

 P848(EMERGENCY):6DI 1= r722.1

 P2103(ACKNOWLEDGE FAULTS):8DI 2=r722.2

 P1082(MAXIMUM SPEED):1500 RPM.


FIXED SET POINT
OPERATING MOTOR BY USING DIGITAL INPUTS WITH HELP OF
TERMINAL STRIP .
 P1070(MAIN SET POINT)=r1024

 P1020(Fixed speed set point selection Bit 0)=r722.0

 P1021(Fixed speed set point selection Bit 1)= r722.1

 P1022(Fixed speed set point selection Bit 2)=r722.2


 P1082(MAXIMUM SPEED):1500 RPM.

 P1113(SETPOINT INVERSION):0

 P1001(FIXED FREQUENCY 1):ANY


VALUE NOT EXCEED RPM OF
THE MOTOR GIVEN ON NAME PLATE.

 P1002(FIXED FREQUENCY 2): ANY VALUE NOT EXCEED RPM OF


THE MOTOR GIVEN ON NAME PLATE.
 P1003(FIXED FREQUENCY 3): ANY VALUE NOT EXCEED RPM OF
THE MOTOR GIVEN ON NAME PLATE.
MOTORPOTENTIOMETER:
 P840 (START/STOP ) : r722.0

 P1035 (MOTORIZED POTENTIOMETER RAISE): r722.1

 P1036 (MOTORIZED POTENTIOMETER LOW): r722.2

 P1070 (MAIN SETPOINT) : r1050

 P848 (EMERGENCY) : 1(ALLWAYS ON BIT)