 Drive Set Change

Press the “Fn” (Function) and “Δ” keys simultaneously.


Press “P” (Program) key to conform.
 Factory Reset (In Drive – 1)
1. P9 = 30 (Allow for factory reset)
2. P976 = 1 (Factory Reset)
After that you find the run-up message.
 Access Authorization:
3. P0003 = 1 Standard
P0003 = 2 Advanced
P0003 = 3 Expert,
 Commissioning (In Drive – 2)
4. P10 = 0
5. P2000 = 1500 RPM (Max. Speed of motor)
6. P10 = 1
 Define the external Power Unit
7. P51820 = Rated armature supply voltage
 Adjust the rated unit currents
8. P50076 (0) = (Motor Armature Current / Drive Armature Current) x 100
9. P50076 (1) = (Motor Field Current / Drive Field Current) x 100
 Adjust to the actual unit supply voltage
10. P50078 (0) = Rated value for armature supply voltage (400)
11. P50078 (1) = Rated value for field supply voltage (400)
 Enter the motor data
12. P50100 (0) = rated armature current (4.0)
13. P50101 (0) = rated armature voltage (440)
14. P50102 (0) = rated excitation current (0.5)
15. P50108 (0) = maximum operating speed (1500)
 Data for field
16. Control of the field
P50082 = 0 Internal field is not used
P50082 = 1 the field is activated with the line contactor
P50082 = 2 Automatic switching in of the standstill field set
P50082 = 3 Field current permanently switched on
P50082 = 4 Field with Auxiliaries ON signal activated
17. Field weakening
P50081 = 0 No speed dependent
P50081 = 1 Field weakening operation by means of internal closed loop EMF
control
 Data for actual speed value acquisition
18. P50083 = 1 Operation with analog tachometer
P50083 = 2 Operation with incremental encoder
P50083 = 3 Operation without tachometer
P50083 = 4 freely wired actual value
P50083 = 5 Operation with incremental encoder and SMC30
 Complete quick commissioning
19. P3900 = 3
Now you can start the motor with humming sound.
 Execute optimization runs
20. P50051 = 24 optimization of closed loop field current control
21. P50051 = 25 optimization of closed loop armature current control
22. P50051 = 26 optimization of speed control
23. P50051 = 27 optimization of closed loop emf control
24. P50051 = 28 plotting the friction characteristics
Now you can start the motor with reduced humming sound.