Professional Documents
Culture Documents
Monitoring types
The inverter monitors its temperature using the following monitoring types:
Paramete
r Description
You define how the inverter responds if there is a risk of thermal overload
using this parameter. The details are described below.
The inverter responds depending on the control mode that has been set:
Once the overload condition has been removed, the inverter re-enables the output current or speed.
If the measure cannot prevent an inverter thermal overload, then the inverter switches off the motor with fault F30024.
The inverter immediately switches off the motor with fault F30024.
We recommend this setting for drives with square-law torque characteristic, e.g. fans.
1. If you operate the inverter with increased pulse frequency setpoint p1800, then the inverter reduces
its pulse frequency starting at p1800.
In spite of the temporarily reduced pulse frequency, the base load output current remains unchanged at the value that is
assigned to p1800.
Figure: Derating characteristic and base load output current for overload
Once the overload condition has been removed, the inverter increases the pulse frequency back to the pulse frequency
setpoint p1800.
2. If it is not possible to temporarily reduce the pulse frequency, or the risk of thermal overload cannot
be prevented, then stage 2 follows:
o - In vector control, the inverter reduces its output current.
o - In U/f control, the inverter reduces the speed.
Once the overload condition has been removed, the inverter re-enables the output current or speed.
If both measures cannot prevent a power unit thermal overload, then the inverter switches off the motor with fault
F30024.
If you operate the inverter with increased pulse frequency, then the inverter reduces its pulse frequency starting at the
pulse frequency setpoint p1800.
In spite of the temporarily reduced pulse frequency, the maximum output current remains unchanged at the value that
is assigned to the pulse frequency setpoint. Also see p0290 = 2.
Once the overload condition has been removed, the inverter increases the pulse frequency back to the pulse
frequency setpoint p1800.
If it is not possible to temporarily reduce the pulse frequency, or the measure cannot prevent a power unit thermal
overload, then the inverter switches off the motor with fault F30024.
1. If you operate the inverter with increased pulse frequency setpoint p1800, then the inverter reduces
its pulse frequency starting at p1800.
Once the overload condition has been removed, the inverter increases the pulse frequency back to the pulse frequency
setpoint p1800.
2. If it is not possible to temporarily reduce the pulse frequency, or the risk of inverter thermal
overload cannot be prevented, then stage 2 follows:
o - In vector control, the inverter reduces the output current.
o - In U/f control, the inverter reduces the speed.
Once the overload condition has been removed, the inverter re-enables the output current or speed.
If both measures cannot prevent a power unit thermal overload, then the inverter switches off the motor with fault
F30024.
We recommend this setting for drives with high starting torque, e.g. horizontal conveyors or extruders.
If you operate the inverter with increased pulse frequency, then the inverter reduces its pulse frequency starting at the
pulse frequency setpoint p1800.
Once the overload condition has been removed, the inverter increases the pulse frequency back to the pulse
frequency setpoint p1800.
If it is not possible to temporarily reduce the pulse frequency, or the measure cannot prevent a power unit thermal
overload, then the inverter switches off the motor with fault F30024.