• Verify the start command wiring is correct (24VDC to terminal 5 on the drive, and
0V from CIP to terminal 28).
P3900= Select 1 Motor calculation and reset all non quick commissioning parameters.
Once the display starts alternating between P3900 and A0541, start the blower by
toggling the blower switch to hand.
The VFD blower will do a motor test for 5-10 Min, and when the A0541 goes away that
is the indication that the quick commissioning has finished.
Siemens VFD Setup
After the quick commissioning is completed, we must assign the terminal Digital outputs:
To change this parameter, we must set P0003 to 1 (expert).
After we have verified the configuration and the functionality of the drive, we must set
P0003 back to 1.