Professional Documents
Culture Documents
Excitation System
Publication 9449300990
® Revision -
NCPA
Lodi Energy Center
System P/N: 9449300100
® Basler Electric
12570 State Route 143
Highland IL 62249-1074 USA
www.basler.com, info@basler.com
Phone +1 618-654-2341 Fax +1 618-654-2351
Manual P/N: 9449300990
I
Description Publication Tab
Installation Guidelines for Seismic Applications 2190A88 30
Layout Drawings, Unit 1 9449300400 31
Outline Drawings, Unit 1 9449300920 32
Wiring Diagrams, Unit 1 9449300950 33
Interconnection Diagrams, Unit 1 9449300960 34
Schematic Diagrams, Unit 1 9449300910 35
Layout Drawings, Unit 2 9449300401 36
Outline Drawings, Unit 2 9449300921 37
Wiring Diagrams, Unit 2 9449300951 38
Interconnection Diagrams, Unit 2 9449300961 39
Schematic Diagrams, Unit 2 9449300911 40
Operating Power
Operating power for the regulator and excitation system depends upon the type of system and can be supplied by
any of the following sources:
• An appropriate step-down power potential transformer (PPT) connected to the output terminals of the ac
generator
• A shaft-driven permanent magnet generator (PMG), usually an integral part of a brushless excitation system
• A separate motor-generator set
• A reliable station source, usually 480 Vac or higher
HARDWARE
The excitation control system is an integrated unit composed of sections of low-voltage, metal-enclosed
switchgear along with the generator field and any rotating exciter. (As an option, the low-voltage sections may be
attached to a high-voltage cubicle containing the excitation power transformer.) The system has three major
sections: incoming line, power amplifier, and control.
Control Section
The control cubicle typically contains a set of a set of SIM, ECM, and FCIM modules for each channel and the
control relays required to operate the system. Auxiliary control transformers for the system are also located within
the control cubicle.
With the exception of the control cubicle, most of the ECS2100 system is similar to previous analog or digital
excitation equipment produced by Basler Electric.
Protection Functions
The digital regulator module can be programmed to utilize the following protective functions:
• Overvoltage (OVP)
• Volts per Hertz (HXP)
• Overexcitation (OXP)
• Loss of Field of Underexcitation (LOF)
• Loss of Sensing (LOS)
The digital protection pickup settings must be coordinated with the pickup settings of both the respective digital
limiters and any additional external system backup protective relays that may be utilized.
Field Temperature Monitor
The exciter and/or generator field temperature can be accurately calculated and displayed by means of this
function. The temperature is calculated based upon the known field resistance at a known temperature (usually
25°C). The measured resistance is obtained from dividing the measured field voltage by the measured field
current. The temperature is then determined based upon the temperature coefficient of the winding material
(usually copper).
Transient Event Recorder and Data Logger
The digital excitation control system can be programmed to capture a single event of up to eight channels of
signals to a data base. Each channel can contain up to 9,600 points of data in intervals as short as 1 millisecond.
In addition, the system can record a time/date stamped list of events to a data logger function. Up to 1,000 events
can be recorded. An event may include:
• Pickup and/or operation of any limiter
• Pickup and/or operation of any protective feature
• Excursion of PT and CT signals outside of a preset range
• Field temperature
• Field resistance to ground
• Power supply failure on any card
CAUTION
Generator startup and shutdown procedures must allow for the loss of fan motor
torque and higher motor current at reduces voltage. The cooling fans are single-
phase and have a starting switch that is speed operated. When the frequency
decreases, the fan speed decreases and the starting switch will cut back in,
resulting in motor overload.
CONTROL RELAYS
Some control interface relays operate from 125 Vdc. This power is usually provided from two sources: the station
battery and the excitation source (41A device), rectified to 125 Vdc. These sources are auctioneered with diodes
to permit the higher of the two sources to supply the control circuit. Once the unit is online, any loss of the station
battery will enable the unit to remain online.
The station battery is typically disconnected by a two-pole circuit breaker. If the station battery voltage is 250 Vdc,
a dc-to-dc converter is furnished to supply 125 Vdc for interface relay control power.
SETTINGS
Verifying the suitability of the excitation control equipment settings is the sole responsibility of the user. The
following discussion is intended only as a guide in helping to determine the settings. The settings must be
configured so that the excitation system will operate as an integrated pat of the user's specific power system and
be consistent with the user's operating methods. User-specific schematic diagrams should be reviewed to identify
the settings that apply to a particular application.
The relay control software contains time delayed relays whose delay times require setting. One such timer is the
41ATD relay, whose time delay prevents undesirable operation during the transient that follows the closing of the
41A device. Typically, this time delay is set for five seconds. Another timer is used by the 31TD relay, which
serves to automatically stop a field flash sequence. The amount of time required to flash the generator field will
depend on both the parameters of the generator field and the power available from the station battery (or other
source). Some fields can be flashed in less than five seconds, while others may require more than 15 seconds to
flash. The 31TD is typically set at 10 seconds, although the factory test setting is normally five seconds.
NOTE
The 31TD is not provided in excitation systems where there is no field flashing
circuit.
The time delayed 86ETD relay allows the field current to decay before the 41A device is opened during a unit
shutdown. The amount of time required to de-excite the generator field will depend on the type of excitation power
amplifier converter, ceiling voltage, and generator field time constant. Typically, the 86ETD delay is set at five
seconds, while the factory test setting is three seconds.
When the 41A device is open, the various adjusters go to a preset (pre-position) level. Typically, this level is set
so that when the 41A is first closed, the generator voltage (at no load) goes to about 80 to 90% of rated and the
balance meter is at zero. The second preset on the dc adjuster is sometimes set so that when the overexcitation
protection trips the regulator back to the manual or dc mode, the field current goes to about 80% of the rated, full-
load value.
DIGITAL SETTINGS
All settings for regulation and limiter gains, limiting and protection pickups, and time delays are normally set to
typical values at the factory. These settings are programmed into the FLASH memory of the ECS2100 system.
SAFETY
WARNING!
Bodily injury could result if contact is made with components in this apparatus
which carry either line voltage or are subject to abnormally high voltages. The
circuit diagrams, provided as part of a system’s documentation package, will
disclose hazardous areas.
As with all electrical equipment, appropriate safety measures should be taken whenever dealing with the
excitation equipment. High voltage is present within the excitation cubicles; their magnitudes depend upon the
particular system. Opening the sources, e.g., disconnecting device 41, does not completely disconnect the high
voltages. As long as the machine is still physically connected to the system, there is a possibility that a safety
hazard exists.
Every precaution must be taken when working at the excitation control switchgear to ensure that all high voltages
are isolated and avoided by test personnel. In addition to the machine terminal voltage (460 Vac or greater) at the
excitation transformer, there may be other sources of power entering the cubicles. These sources may include the
user-supplied 125/250 Vdc and/or 120/240 Vac used to feed certain devices. A good rule to follow is to assume
that all connections are live and dangerous until proven otherwise and to completely avoid all body contact with
any of these voltages.
One other cautionary note concerns the generator field ground detector. Because the ground detector input
supply is usually 120 Vac, both the ac bus and dc (100 Vdc) might be back-fed from this device. Therefore, it too
must be disconnected when servicing the excitation control equipment.
MAINTENANCE
No maintenance of the equipment is required other than the periodic inspection and removal of accumulated dust.
SPARE PARTS
A reasonable stock of spare parts will minimize downtime in the event of a equipment malfunction. When ordering
spare parts, specify the equipment part number (listed on the equipment nameplate) and the individual part
numbers (listed in the equipment subassembly documentation).
GLOSSARY
Terms commonly used in ECS2100 documentation are defined in the following paragraphs.
BCM. Bridge Control Module. Up to 16 BCMs can be controlled by one FCIM.
Bridge. A configuration of thyristors (SCRs) that convert ac current into dc current.
ccTool. Controller Configuration Tool. A Windows (2000, XP, or Vista) based application that connects to an
ECM, FCIM, or BCM card for user-programming of the card functions. Presents table or block diagram
representations of the controller program and operation.
CM. Conduction Monitor card. Provides current level information on each SCR or bridge.
ECM. Exciter Control Module. Contains the excitation control, limiting, protection, and communication software
(but is not considered a part of the DFC.
Publication: 9410100990
Revision: — 06/07
INTRODUCTION
This manual provides information concerning the handling, installation, and maintenance of generator and
motor excitation control equipment manufactured by Basler Electric. This publication (9410400990)
supersedes publication 99-1484.
• General Information
• Equipment Handling
• Installation
• Maintenance
• Maintenance Schedule
WARNING!
To avoid personal injury or equipment damage, only qualified personnel should
perform the procedures in this manual.
Printed in USA
CONFIDENTIAL INFORMATION
of Basler Electric, Highland Illinois, USA. It is loaned for confidential use, subject
to return on request, and with the mutual understanding that it will not be used in
any manner detrimental to the interest of Basler Electric.
It is not the intention of this manual to cover all details and variations in equipment, nor does this manual
provide data for every possible contingency regarding installation or operation. The availability and design
of all features and options are subject to modification without notice. Should further information be
required, contact Basler Electric.
BASLER ELECTRIC
ROUTE 143, BOX 269
HIGHLAND IL 62249 USA
http://www.basler.com, info@basler.com
PHONE +1 618.654.2341 FAX +1 618.654.2351
ii Introduction 9410100990 Rev -
CONTENTS
SECTION 1 • GENERAL INFORMATION................................................................................................. 1-1
SYSTEM IDENTIFICATION
Each excitation control system manufactured by Basler Electric is assigned a model, part, and serial
number. The system part number must accompany any correspondence concerning the excitation
system. When ordering parts from Basler Electric, be sure to specify the Basler part number, quantity,
description, and system part number. The system part number can be found in the instruction manual as
well as on the front panel of the system enclosure. An identification nameplate is affixed to the front of
each enclosure.
INSTRUCTION MANUAL
An instruction manual is supplied with every excitation system and should be referred to for information
relating to the individual system requirements. The instruction manual contains important information and
should be kept in a safe place for future reference. Typical instruction manual content includes:
• System specifications
• A functional description
• General operating instructions
• A list of system components
• System drawings
• Publications relevant to devices installed in the system.
SAFETY
WARNING!
Some components of the excitation system carry voltage at hazardous levels.
Contact with these voltages can result in personal injury or death.
Only personnel who are thoroughly trained and who understand the hazards
associated with working on excitation systems should carry out inspection and
maintenance procedures. Plant personnel should become familiar with the
schematic diagrams, wiring diagrams, and instruction manual associated with
this equipment.
Care must be exercised to comply with safety practices as well as local, state,
and federal regulations for this class of equipment.
CAUTION
Failure to inspect, clean, and maintain the excitation control system can reduce
the life expectancy of the equipment or impair its operation.
As with all electrical equipment, appropriate safety measures should be taken whenever dealing with the
excitation equipment. High voltage is present within the excitation cubicles; the magnitude of the voltage
depends upon the particular system. Removing the voltage sources does not completely disconnect the
high voltages. As long as the machine is still physically connected to the system, there is a possibility that
a safety hazard exists.
Every precaution must be taken when working with the excitation control equipment to ensure that all high
voltages are isolated and avoided by personnel. In addition to the three-phase ac excitation source
9410100990 Rev - General Information 1-1
voltage, there may be other sources of power entering the cubicles. These sources can include 125/250
Vdc control power, 120/240 Vac station power, and 480 Vac used to supply certain devices. The field
voltage is also present at the field ground detector. Due to capacitors in the shaft suppression network,
there may be voltage present even when the field circuit breaker is open. A good rule to follow is to
assume that all connections are live and dangerous until proven otherwise.
Before performing maintenance on the current transformer (CT) circuits, place a short-circuit across the
secondary connections of the CT at the shorting-type terminal block.
On some DECS and ECS2100 systems, the ground detector (ground fault relay) is powered by a
separate source. Both the ac power bus and dc field bus might be backfed from this device with 120 Vdc.
Therefore, it too must be disconnected when the excitation control equipment is serviced.
STORAGE
Equipment that will not be installed immediately should be stored according to the following guidelines.
NOTE
Outdoor storage of the equipment is unacceptable. Do not leave the equipment
outdoors exposed to the weather. All equipment should be protected from
damage and vandalism.
Guidelines for moving the equipment into and out of storage is provided in the
paragraphs under Moving Equipment Sections.
All equipment should be stored in an environmentally controlled building or shelter. The environment’s
relative humidity must be below 40%.
If flooding is a concern, all equipment should be elevated on blocks or supports to prevent damage from
water. To determine a safe elevation (height), the purchaser must rely on past experience and site
conditions.
Following an initial inspection, prepare the equipment for storage by taking the following precautions:
• Restore all protective packing
• Identify, label, and secure any shipped-loose components
• Cover all openings to prevent the ingress of dust and insects
• Store all cartons/crates containing draw-out equipment flat to prevent strain and distortion of the
assemblies
CAUTION
Use care when applying heat near cardboard and packing material. Keep heaters
far enough away so that these materials do not become overheated.
Spontaneous combustion (fire) could result from continued heat buildup.
Conduit Openings
Holes or conduit knockouts are not supplied on standard systems. The installing contractor has the
convenience of locating the conduit openings as required during installation. Holes may be punched or
cut as the conditions at the jobsite dictate. Use adequately sized tools to cut or punch holes.
Current Transformers
The standard practice for installing current transformers is to be sure the side of a toroid type CT marked
with a dot or “H1” is facing toward the source. Bar-type current transformers have a polarity mark (dot or
H1). Secondary circuits also have polarity marks such as lead markings “X1”, “X2”, etc. Pay close
attention to the polarity indications on the drawings and CTs when installing them. Also, ensure that the
CT is installed on the correct phase as indicated on the interconnection diagram. Be sure to remove all
jumpers or shorting bars on the CTs before operating the system. Never open-circuit a CT while current is
flowing in the circuit. To perform maintenance on a live CT circuit, always short the CT secondary before
disconnecting any circuit wires. A shorting type terminal board may be provided for this purpose.
Otherwise, use a jumper wire. Bar type CTs are usually provided with a shorting “link” mounted on the CT
terminals.
Control Power
Control power should be connected as shown on the system drawings. Note the current and voltage
requirements listed on the drawings. Batteries should be tested frequently and properly maintained. One
of the most frequently reported causes of system failures and malfunctions is poorly or improperly
maintained control system batteries. Follow all of the battery manufacturer’s recommended maintenance
practices. It is recommended that circuit overcurrent devices be installed as closely as possible to the
supply source. Disconnect devices are also recommended on the control sources to the system.
Grounding
Make sure that all secondary wiring is connected to the system ground bus as indicated on the drawings.
The ground bus should be connected to the system ground with as direct a connection as possible and
should not be run in metal conduit unless the conduit is adequately bonded to the circuit. The grounding
conductor should be sized to carry the maximum short-circuit current available. A permanent low-
resistance ground is essential for adequate safety and protection.
DOCUMENTATION
The importance of good recordkeeping cannot be overstressed. Installation details should be recorded
and securely filed for future used. The following list gives some examples of useful information that may
be recorded or filed during equipment installation.
• Record the dielectric test results and insulation resistances.
• Create a detailed point-to-point installation interconnection diagram.
• Retain all instruction manuals and equipment drawings.
• Record all pertinent system variables obtained during startup and testing. These system variables
can include current, voltage, kilowatt, power factor, and temperature readings.
• Post all normal operating and emergency operating procedures.
MAINTENANCE GUIDELINES
Observing the following maintenance fundamentals and following the maintenance schedule of Section 5
will promote equipment reliability and longevity.
Keep It Clean
Dirt, dust, and corrosives are prime enemies of electrical equipment. Excessive dust buildup hinders
system cooling and causes higher operating temperatures. If possible, prevent dust and dirt from
accumulating on the equipment. Otherwise, frequent cleaning will need to be performed. During regularly
scheduled shutdown for maintenance, the system should be vacuumed thoroughly (except for printed
circuit boards). Do not use compressed air to clean electrical equipment. All filters should be inspected
and replaced/cleaned according to the maintenance schedule as required by the conditions in the plant
environment.
Keep It Cool
Another prime enemy of electrical equipment is excessive heat. Do not allow vent openings to be blocked
or restricted. Ensure that the ambient temperature of the cubicles is less than 40°C (104°F) unless
otherwise indicated on system drawings. If equipped, check the heater and air conditioner power source
and operation. Check for clogged air filters and proper cooling fan operation. Maintain proper blower
motor lubrication.
Keep It Dry
Moisture can cause equipment failure or erroneous operation. Dripping pipes, condensation, and other
moisture sources should be eliminated. Anti-condensation heaters should be checked often and may be
added if not originally equipped.
Eliminate Vibration
Vibration tends to move or loosen electrical connections. Determine the cause of vibration and eliminate
as much vibration as possible. Keep cubicle doors securely fastened and tighten any loose mounting
hardware. Be alert to changing conditions; changing vibration patterns are usually the advance warning of
an impending failure.
Contactor
Inspect and maintain the contactor according to the contactor instruction manual. Observe the following
maintenance notes.
Before the contactor is placed in service or following maintenance, operate the contactor slowly, by hand
two or three times without power to check operation and alignment of the moving parts. If the contactor
operates satisfactorily, then close and open it two or three additional times using the operator magnet, but
with the main power circuit de-energized.
NOTE
Do not exceed operation frequencies indicated in contactor instruction manual.
If the contactor has been operated under heavy fault conditions, it should be inspected at the first
opportunity after it has been de-energized.
Inspect and maintain the contacts according to the contactor instruction manual. Badly pitted, burned, or
worn contacts should be replaced.
Examine the arc horns and arc chute walls for excessive arc erosion. Check the arc chute walls and grid
plates for excessive metal deposits and cracks. Clean dust and other foreign mater from the arc chute
chamber.
Check the general condition of connectors, shunts, and other current carrying parts. Inspect and clean the
insulators and supports.
Fuses
Inspect the fuses, fuse holders, and fuse contact surfaces for signs of overheating, as evidenced by
distorted and discolored metal. There may be discoloration of copper and copper alloy surfaces. This is
the result of oxidation and does not indicate overheating.
WARNING!
Expected trigger voltages are between 750 and 4,250 Vdc, depending on the
DXCB module settings.
With both leads of the DXCB module disconnected from the field circuit, apply a dc voltage across the
module. Start at a low value of voltage and increase the voltage to within 100 Vdc of the expected trigger
voltage. Then, slowly increase the voltage until the trigger is reached and record the trigger level,
verifying that the trigger value is within the expected tolerance. When the DXCB module is triggered, it will
apply a short-circuit across the applied dc voltage. Ideally, a power source with at least 50 Adc short-
circuit output would provide the required current to turn on the conduction monitor and cause LED D2 to
light.
Cooling Fans
Cooling fan maintenance includes inspection and cleaning of the motor, fan blades, fan shutter, and fan
shutter switch.
Motors and Motor Control Equipment
Inspect the fan motor for excessive vibration and noise. Excessive vibration can be caused by loose
mounting hardware, improper shaft alignment, or a bent shaft. Excessive noise can be caused by worn
bearings or a binding rotor.
Keep the motor and motor control equipment clean. In dirty operating environments, clean out dirt
quarterly or semiannually, depending on site conditions. Check operation of the contactors and relays.
Moving parts should operate without excessive friction. Look for loose pins, bolts, and bearings. A dirty
9410100990 Rev - Maintenance 4-3
control should be wiped or blown clean. Check contacts for pitting and signs of overheating (such as
discoloration of metal or charred insulation). Make sure contact pressure is adequate (consult the
manufacturer’s specifications) and is the same on all poles. Inspect, clean, and check overload relays for
proper setting. In general, maintenance requirements for these relays include checking that:
• The rating or trip setting takes into account ambient temperature as well as the higher inrush currents
of modern, energy-efficient motors
• Contacts are clean and free from oxidation
• The relay will operate dependably when needed
To ensure reliable operation, test and calibrate the relays every three years.
Fan Blades
Ensure that the fan motor power supply is disconnected and padlocked prior to working on the fan blade
assembly.
Inspect the fan blade assembly for excessive vibration. If excessive vibration is observed, check for loose
mounting hardware, improper shaft alignment, or a bent shaft.
The fan blades should be inspected and cleaned annually.
Fan Shutter Switch
Verify that the switch functions when the fan is operating.
Check for vane damage and cracks.
The fan shutter switch should be cleaned annually.
Line Filter
Check all line filter fuses. If open fuses are found, check for a short-circuit and replace capacitors. Check
the line filter capacitors for leaks or bulging cases. Contact Basler Electric if leaking or bulging capacitors
are discovered.
If dirty, clean all line filter resistors. Check the resistors for damage from overheating.
Inspect all line filter wires and terminations for damage due to overheating.
Protective Relays
Protective relays should be tested annually. Inspect, maintain, and calibrate each relay according to the
device instruction manual.
Circuit Breaker
The circuit breaker should be periodically cleaned using a vacuum cleaner and/or lint-free cloth. Unless
otherwise indicated, never use compressed air since dirt or foreign objects can be driven into undesired
areas. Never use a wire brush to clean any part of the circuit breaker.
Power Supplies
If equipped, verify power supply cooling fan operation.
Check for short-circuits if power supply fuses are blown.
Heaters
Check operation of the thermostat and heater circuits. Inspect the surface areas around the heaters for
evidence of overheating.
Control Relays
Visually inspect the control relays for burn marks and check the control relays for proper operation.
Equipment Enclosure
Inspect the equipment enclosures for openings into the interior. Seal all openings with the appropriate
material/weather stripping. Check the cable and bus entry areas, the enclosure roof, and access panels
(doors). Check the rain flashing on top of any air conditioner duct openings.
Inspect the enclosure for signs of corrosion. Clean the exterior of the enclosures and touch up scratches
and abrasions using primer and touchup paint.
Inspect and replace vent filters as required. in a dusty environment, filters should be inspected several
times during the year to ensure sufficient ventilation for the equipment.
Lubricate the door locks and hinges.
WARNING!
Disconnect all power to the air conditioner before starting maintenance.
Check the rain flashing on top of any air conditioner duct openings.
Semiannually
Quarterly
Annually
Startup
12.5
17.5
27.5
2.5
7.5
10
15
20
22
25
5
Maintenance Item
AC Isolation Transducers T D T T T T T T T T T T T
Air Conditioner T I D Inspect and maintain according to instruction manual.
Air Filters I/C/D
Analog I/O Circuit Boards T D T T T T T T T T T T T
Bridge Control Module (BCM) T D T T T T T T T T T T T
Bridge Isolation Transducers T D T T T T T T T T T T T
Bus Connections I/O I I I I I I
Cable Terminations I/O I I I I I I
Circuit Breaker T I/D Inspect and maintain according to instruction manual.
Conduction Monitors V V V V V V V V V V V V
Contactor, AC T I/D C
Contactor, DC T I/D C
Control Fuses I/F I/F
Control Relays V V V V V V V V V V V V
Corrosion/Condensation I I
Crowbar Module T T T T T T T T T T T T
DC Isolation Transducers T D T T T T T T T T T T T
De-Excitation Module T T T T T T T T T T T T
Digital Controller (DECS) T D Inspect and maintain according to instruction manual.
Digital I/O Circuit Boards T D T T T T T T T T T T T
Dustiness I I D
Exciter Control Module (ECM) T D T T T T T T T T T T T
Fan/Blower Motors T T C C
Fan Blade Assemblies I I
Fan Shutter Switch I I C C
Fiber Optic Connections I I
Field Flashing Contactor T I
Field Flashing Circuit T I
Firing Control Module (FCIM) T D T T T T T T T T T T T
Firing Module (IFM) T D Inspect and maintain according to instruction manual.
Ground Detector Module T T C C
Semiannually
Quarterly
Annually
Startup
12.5
17.5
27.5
2.5
7.5
10
15
20
22
25
5
Maintenance Item
Insulators and Supports I/D I/D
Line Filter Capacitors I I C C
Line Filter Fuses I/F I/F
Line Filter Resistors I I
MOV Fuses I/F I/F
MOVs I I C C C C C C C C C C C
PanelMate T C C
Power Converter (Drawer) T/I/D D R R R R R
Power Converter (Fixed) T/I/D D R R R R R
Power Supplies T C C C
Protective Relays T T Inspect and maintain according to instruction manual.
Ribbon Cable Connections I I
Sensor Input Module (SIM) T D T T T T T T T T T T T
Shaft Suppression Capacitors I I C C
Shaft Suppression Resistor I I
Space Heater Circuit T D T T T T T T T T T T T
Temperature, Ambient I I
Voltraps I I
Wiring I I
Wiring Connections I I
Revised 11-09-06 1
INSTRUCTIONS FOR SINGLE OR DUAL CHANNEL INSTALLATION I.L. 6D34315E
entering the cubicles, such as the customer 1- D-C 0-200 Millivolt Source (to accurately
125/250 VDC and/or 120/240 VAC used to feed set the transducers this should be accurate
certain devices. The field voltage is also present at to within 0.1%)
the ground detector power source. A good rule to 1- D-C 0- to approx 500Vdc @1 amp (to
follow is to assume that all connections are live accurately set the transducers this should
and dangerous until proven otherwise and to avoid be accurate to within 0.1%) (Voltage out-
completely all body contact with any of these put should be higher than the excitation
voltages. system ceiling voltage, i.e. more than 1.25
times rated RMS voltage to the bridge,
One other cautionary note refers to the Generator from a PMG or a station service
Field Ground Detector. Because the Ground transformer.)
Detector input supply is usually a separate 110
VAC, both the AC power bus and DC field bus [An excitation or relay test box may be substituted
might be backfed from this device with 120 VDC. for the above 4 items.]
Therefore it too must be disconnected when
servicing the excitation control equipment. 1- 0-200 ohm, 1W Variable Resistor
1- 0-1 Mega ohm, 2W Variable Resistor
1- 1 kilo ohm, ¼ W Resistor
TEST EQUIPMENT REQUIRED
Revised 11-09-06 2
INSTRUCTIONS FOR SINGLE OR DUAL CHANNEL INSTALLATION I.L. 6D34315E
AIOM Analog Input / Output Module. Several components in an ECS2100 Unit are
Provides the interface for analog identified by device function numbers defined by
signals into and out of the system. ANSI/IEEE C37.2-1979.
31 = separate excitation device, a device that
DIOM Digital Input / Output Module. connects a circuit to a source of separate
Provides the interface for 125 VDC excitation during the starting sequence; or one that
control signals into and out of the energizes the excitation and ignition circuits of a
power rectifier.
system.
41 = field circuit breaker or contractor, a
device that functions to apply or remove the field
BCM Bridge Control Module generates excitation of a machine. In the following sections
the thyristor firing pulses this device is referred to as 41A because it is
utilized on the AC power input of the regulator or
ECM Exciter Control Module contains static exciter.
the excitation control, limiting, 43 = manual transfer or selector device, a
protection, and communication manually operated device that transfers the control
software. circuits in order to modify the plan of operation of
the switching equipment or of some of the
devices.
FCIM Firing Circuit Interface Module
determines when the firing pulses 86 = lockout relay, a hand or electrically reset
auxiliary relay that is operated upon the
should occur. Provides the occurrence of abnormal conditions to maintain
interface from ac line and dc field associated equipment or devices inoperative until
signals from the IT cards to the it is reset.
ECM. 90 = regulating device, a device that functions to
regulate a quantity, or quantities, such as voltage,
current, power, speed, frequency, temperature, and
SIM Sensor Input Module. Provides the load, at a certain value or between limits for
interface from PT and CT signals machines, tie lines, or other apparatus.
and the AIOM and DIOM signals
to and from the ECM.
Revised 11-09-06 3
INSTRUCTIONS FOR SINGLE OR DUAL CHANNEL INSTALLATION I.L. 6D34315E
Revised 11-09-06 4
INSTRUCTIONS FOR SINGLE OR DUAL CHANNEL INSTALLATION I.L. 6D34315E
Revised 11-09-06 5
INSTRUCTIONS FOR SINGLE OR DUAL CHANNEL INSTALLATION I.L. 6D34315E
Revised 11-09-06 6
INSTRUCTIONS FOR SINGLE OR DUAL CHANNEL INSTALLATION I.L. 6D34315E
(ALXD). Check in the FCIM card that the 15. Check on PanelMate display that field voltage
output “FVAB_OUTPUT” of the reads correctly on all screens.
“F_TO_VAB” block is 0(±40) counts. If not
adjust the “FVAB_OFFSET” so that the 16. Lift the leads from the output current shunt
output “FVAB_OUTPUT” is 0(±40) counts. and connect a millivolt source to the wires
Set the ac line transducer input (Pins J19, J20) going to the field current transducer (DCXD).
to a DC voltage equal to the RMS value of the Set the dc input equal to the shunt millivolt
line-to-line voltage applied to the converter level corresponding to the field current at ten
bridge(s). Check that “FVAB_OUTPUT” is per cent full load. Check in the ECM that the
1100(±80) counts. If not adjust the constant FCIM_INP block's output
input “CONST1_IN1 in the "CONST1" block “FCIN_GEN_FLD_CUR” is 0.100(±0.0009).
until the “FVAB_OUTPUT” of the If not, adjust the “FCIN_IG_OFFSET” so that
"F_TO_VAB" block is 1100(±80) counts. the output “FCIN_GEN_FLD_CUR” is at
0.100(±0.0009).
10. Pull the appropriate fuse, and short the
connections to the phase BC line transducer 17. Set the dc input equal to the shunt millivolts
(ALXD). Check in the FCIM card that the when the field current is at full load. Check
output “FVBC_OUTPUT” of the that the output of the FCIM_INP block
“F_TO_VBC” block is 0(±40) counts. If not “FCIN_GEN_FLD_CUR” is 1.000(±0.0009).
adjust the “FVBC_OFFSET” so that the If not adjust “FCIN_IG_SCALE” so that the
output “FVBC_OUTPUT” is 0(±40) counts. output “FCIN_GEN_FLD_CUR” is
Set the ac line transducer input (Pins J21, J22) 1.000(±0.001). Recheck at ten percent and
to a DC voltage equal to the RMS value of the repeat as needed.
line-to-line voltage going to the converter 18. Run transfer curve with input millivolts set to
bridge(s). Check that “FVBC_OUTPUT” of simulate 50, 100, and 200 percent of full load
the "F_TO_VBC block is 1100(±80) counts. If field current. The expected results should be
not adjust the constant input “CONST1_IN1 linear.
in the "CONST1" block and re-check step 10.
19. Check on PanelMate display that the field
11. Ensure all connection are re-established and current reads correctly on all screens.
replace all fuses removed.
20. Ensure all connection are re-established and
12. With the appropriate fuse pulled short the replace all fuses removed.
connection to the field voltage transducer
(Pins J21, J22 of DCXD). Check in the ECM 21. If analog inputs are used, check that load
that the FCIM_INP block’s output resistors are present if a 4-20 ma source is
“FCIN_GEN_FLD_VLT” is 0.000(±0.0009). used. Check in the “ALOGDIG” block that
If not, adjust “FCIN_VG_OFFSET” so that AD_OFFSET_3”, “AD_GAIN_3” are
the output “FCIN_GEN_FLD_VLT” is properly set for channel 1, per the order
0.000(±0.0009). drawings and customers transducer. (If a
ground detector is used, Channel 3 typically
13. Set the dc input equal to the field voltage at measures leakage to ground, and can be set up
full load. (Typically, full load field current later with the ground detector. Check in the
times field resistance at 75 deg. C). Check that “ALOGDIG” block that "AD_OFFSET_4",
the output of the FCIM_INP block “AD_GAIN_4” are properly set for channel 2,
“FCIN_GEN_FLD_VLT” is at per the order drawings and customers
1.000(±0.0009). If not, adjust the value of transducer.
“FCIN_VG_SCALE” so that the output
“FCIN_GEN_FLD_VLT” is 1.000(±0.0009). 22. If RTD inputs are used, check in the
“ALOGDIG” block that “AD_OFFSET_1”,
14. Run transfer curve with input voltage set to “AD_GAIN_1”, “AD_OFFSET_2”,
simulate 50, 100, 150 percent of full load field “AD_GAIN_2”, “AD_RTD_KSCALE”,
voltage (if possible). The expected results “AD_RTD_RZ”, and “AD_RTD_RZ” are
should be linear. properly set. Connect test resistance in place
of RTD. For a 100 ohm input, the output of
“ALOGDIG” should read 0.0 degrees Celsius.
For a 110 ohm input, the output of
“ALOGDIG” should read 25.9 degrees
Revised 11-09-06 7
INSTRUCTIONS FOR SINGLE OR DUAL CHANNEL INSTALLATION I.L. 6D34315E
Celsius. If output goes to a remote meter, secondary voltage when the generator output
inject signals and check for correct operation is at its rated value. Connect to the metering
of remote meter PT switches a three-phase ac voltage with the
23. If analog outputs are used, check in the same magnitude and phase sequence as the PT
“DIGALOG” block that offsets and scales are secondary voltage when the generator output
properly set, per the order drawings. If output is at its rated value. Check that the unit can be
goes to a remote meter, inject signals and transferred between automatic and manual.
check for correct operation of remote meter Check “AUTO” and “MAN” lights.
5. Check Loss of sensing. Check that the unit
transfers from ‘AUTO’ to ‘MANUAL’ when
Checkout of relays, breakers, and control the regulator and (if used) metering PT’s
switches (F) voltage falls below a selectable value.
Normally the unit is started up in the ‘AUTO’
1. Check the operation of all relays, contactors, mode. Since the PT voltage is initially low, the
cooling fans, circuit breakers, adjusters and controls are defaulted by the loss of sensing
the various control switches located both at function to the “MANUAL’ mode. When the
the excitation switchgear and at the station PT voltage crosses the selectable level in a
operator’s control board. Operation of all these predetermined time the unit transfers back to
devices must be in complete agreement with the ‘AUTO’ mode.
the job contract schematic. The check should
first be made using the local PanelMate, then If metering PT’s are used the unit transfers
control room switches, and then distributed from one set of PT’s to the other when only
control system screens. For dual channel one set of PT’s is low. Transfer to manual
systems, this portion of the procedure should occurs when both sets of PT inputs go low.
be performed first with the Main Channel in This can be simulated (tested) in two ways:
control, and then with Redundant Channel in
control, repeating all the steps. The following The first test simulates a blown fuse by
are checks for the more typically used disconnecting a single PT input. The second
components. simulates a high resistance fuse/connection by
lowering the PT inputs.
2. Check operation of “LOCAL/REMOTE”
transfer. With “LOCAL/REMOTE” in 6. Check correct operation of field flash circuitry
“LOCAL”, the controls in the PanelMate while disconnected from field. Set 31TD per
mounted on the excitation switchgear are customer’s requirements (typically 10
active. With “LOCAL/REMOTE” in seconds). Check 31, 31X contacts in alarm
“REMOTE”, the switches mounted in the and annunciator circuits. Check that field flash
control room are active and the PanelMate is turned off when field current builds up, or
screen switches on the logic cubicle are when regulator pt voltage is applied.
inactive. Steps 3 to 9 should be done in 7. Check operation of the automatic adjuster.
“LOCAL” and then repeated in “REMOTE”. Verify travel range and preposition meet
Check any local and remote lights. customer’s operational practices. With the
3. Check 41A-CS CLOSE command, 41A 41A device tripped, the adjuster output is at
device, 41AX relays and interlocks. When the the ACVLTADJ block preposition value
local 41CS is switched to TRIP position, the (“ACADJ_PP_1”), and cannot be moved
86 device operates immediately, initiating under normal operation. With the 41A device
phase back. The 41A device trips about 5 closed, the adjuster output can be moved.
seconds later (after software timer times out). The range can be easily verified. With the
Upon customer emergency trip, the 41A adjuster at minimum apply a PT signal until
device operates immediately. Check red and the ac error signal reads zero. (Balance meter
green lights. Check alarm and annunciate can be used if dc error is kept at zero.) This is
contacts associated with 41A, 41AX, and 86. the minimum setting of the adjuster.
4. Check mode select. Connect to the regulator Alternately with the adjuster at maximum
PT switches a three-phase ac voltage with the apply a PT signal until again the ac error
same magnitude and phase sequence as the PT signal reads zero. Both of these settings
(“ACADJ_MAX”, “ACADJ_MIN”) are
Revised 11-09-06 8
INSTRUCTIONS FOR SINGLE OR DUAL CHANNEL INSTALLATION I.L. 6D34315E
selectable with the ccTool software. The travel Converter Bridges with Generator Not
time is settable using “ACADJ_SLEW” Running (G)
8. Check operation of the manual adjuster. 1. In the following steps, the bridge operation
Verify travel range and preposition meets under control of the “SLC2_BASE” signal in
customer’s operational practices. With the the “REG_SLCT2” block will be checked.
41A device tripped, the adjuster output is at Three-phase, 60 Hz power for this test may be
the MANADJ block preposition value taken from the excitation transformer
(“MANADJ_PP_1”), and cannot be moved secondary if the transformer can be energized
under normal operation. With the 41A device with its rated primary voltage at the time the
closed, the adjuster output can be moved. main unit transformer is being tested. If a
The range can be easily verified. With the separate supply source must be used, it should
adjuster at minimum, vary a simulated shunt be sized to provide sufficient static exciter
mV signal until dc error reads zero. (Balance load to give the exciter a reasonable
meter can be used if ac error is kept at zero.) operational test. The test supply can be either a
This is the minimum setting of the adjuster. closed three-phase delta or a three-phase wye.
Alternately with the adjuster at maximum Do not use an open-delta three-phase supply
apply a simulated shunt mV signal until again for this test. Check phase sequence of the
the dc error signal reads zero. Both of these supply voltage used to be in agreement with
settings (“MANADJ_MAX”, the contract schematic. The three-phase test
“MANADJ_MIN”) are selectable with the voltage should be connected at the input to the
ccTool software. The travel time is settable 41A device.
using “MANADJ_SLEW”.
9. Check operation of the var control adjuster.
Verify travel range and preposition meet
customer operational practices. With the 41A
device tripped, the adjuster output is at the IF THE EXCITATION TRANSFORMER IS
VARCONTR block preposition value NOT USED AND A SEPARATE SOURCE IS
(“VRC_PP_1”), and cannot be moved under CONNECTED TO THE 41A DEVICE, THE
normal operation. With the 41A device closed, EXCITATION TRANSFORMER SEC-
the adjuster output can be moved. The range ONDARY CONNECTIONS TO THE 41A
can be easily verified. With the adjuster at DEVICE MUST BE DISCONNECTED AND
minimum, apply PT and CT signals and adjust TAGGED AND TAPED. DO NOT
simulated vars until the var balance signal ENERGIZE THE EXCITATION
reads zero. This is the minimum setting of the TRANSFORMER SECONDARY WITH THE
adjuster. Alternately with the adjuster at SEPARATE TEST SOURCE. STARTING
maximum apply PT and CT signals and adjust RESISTORS ALONE MAY BE USED AS A
simulated vars until again the var balance LOAD FOR THIS TEST. IT IS
signal reads zero. Both of these settings PREFERABLE THAT A HIGHER
(“VRC_MAX”, “VRC_MIN”) are selectable CURRENT LOAD (PREFERABLY
with the ccTool software. The travel time is INDUCTIVE) BE USED.
settable using “VRC_SLEW”.
10. If used, check operation of 64-switch and field
ground fault detector. Check that ground fault
detector is disabled during field flash.
IF THE ROTOR FIELD IS TO BE USED AS
11. If used, check operation of cooling fans and PART OF THE LOAD, AN ADDITIONAL
associated controls. LOAD RESISTOR SHOULD BE ADDED IN
12. Repeat steps 3 through 11 above for SERIES WITH THE GENERATOR OR
“REMOTE”. EXCITER FIELD. THIS RESISTOR MUST
13. Check any other control features per job BE SIZED TO PREVENT ANY DAMAGE TO
schematic. THE EXCITER OR GENERATOR ROTOR
AND PREVENT OVERLOADING THE
Check Exciter Power firing Control and TEST POWER SUPPLY WHEN THE UNIT
IS NOT ROTATING, SINCE CURRENTS
Revised 11-09-06 9
INSTRUCTIONS FOR SINGLE OR DUAL CHANNEL INSTALLATION I.L. 6D34315E
Revised 11-09-06 10
INSTRUCTIONS FOR SINGLE OR DUAL CHANNEL INSTALLATION I.L. 6D34315E
Revised 11-09-06 11
INSTRUCTIONS FOR SINGLE OR DUAL CHANNEL INSTALLATION I.L. 6D34315E
3. Check balance meter. With 41A open, disable signals to simulate 0 pf overexcited (generator
followers. Disable any var or power factor lagging vars). For droop compensation,
controller. Set “RCOMP_XC” and ACREG_V2 should become more negative by
“RCOMP_RC” to zero in “REAC_COMP” the amount of droop compensation. For rise
block. Set “LDR_XC” and “LDR_RC” to zero compensation, ACREG_V2 should become
in “LINEDROP” block if used. Set simulated more positive by the amount of droop
PT intelligence and CT intelligence to compensation.
correspond to rated values, and simulated field 8. If used, check setup of var controls (software
current to represent full load field current. block “VARCONTR”). With var control off,
Check output of “POWERTRN#00” block set PT and CT signals to simulate rated load
reads correct MW and MVARS. Close 41A. unity power factor. Use var control raise/lower
Set auto and manual adjuster outputs to 1.0. switches to set “VRC_V2” to zero. Turn on
Check that output of “AUTO_MXR” as seen var control. Reduce PT signal to below
at the “REG_SLCT2” (SLC2_ACR) and VRC_VMIN. Check adjuster position. Change
“MAN_MXR” (SLC2_DCR) both read zero. CT signal to simulate generator overexcited
Check that balance meter reads zero. Raise (approximately 0.8 lagging power factor).
auto adjuster and check that balance meter Verify ac adjuster output remains unchanged.
goes negative. Raise manual adjuster and Return PT signal to rated voltage. Verify that
check that balance meter returns to zero. output of ac adjuster decreases. Change CT
4. Check manual adjuster followers. With unit in signal to simulate generator overexcited
auto, and followers disabled, lower PT (approximately 0.8 lagging power factor).
intelligence to 98 percent of rated. Enable Verify that output of ac adjuster increases.
followers. Check that the manual adjuster 9. If used, check setup of power factor controls
(MANADJ_REF) output increases and the (software block “PFCONTR”). With pf
balance meter heads toward zero. Adjuster control off, set PT and CT signals to simulate
output stops moving when minimum is rated load unity power factor. Use pf control
reached or when balance meter gets near zero raise/lower switches to set “PFC_V2” to zero.
(within bandwidth of manual follower). Turn on PF control. Reduce pt signal to below
5. Check automatic adjuster followers. With unit VRC_VMIN. Check adjuster position. Change
in manual, and followers disabled, return PT CT signal to simulate generator overexcited
intelligence to 100 percent of rated. Use auto (approximately 0.8 lagging power factor).
adjuster switch to return balance meter to zero. Verify ac adjuster output remains unchanged.
Set simulated field current to 90 percent of full Return PT signal to rated voltage. Verify that
load. Enable followers. Check that the output of ac adjuster decreases. Change CT
automatic adjuster output (ACADJ_REF) signal to simulate generator overexcited
increases and the balance meter heads toward (approximately 0.8 lagging power factor).
zero (may cross over and go positive). Verify that output of ac adjuster increases.
Adjuster output stops moving when minimum 10. For dual channel systems, set simulated PT
is reached or when balance meter gets near and CT intelligence to correspond to rated
zero (within bandwidth of automatic values, and simulated field current to represent
follower). full load. With the Main Channel in control,
6. Return “RCOMP_XC” and “RCOMP_RC” to verify that the Trackers are enabled in the
original value in “REAC_COMP” block. Set PanelMate page dedicated to the transfer of
PT and CT signals to simulate 0 pf channel control. Also verify in the same page
overexcited (generator lagging vars). For that the Tracker window reads 0 + 0.1. If this
droop compensation ACREG_V2 should value is not within limits, recalibrate the
become more negative by the amount of droop analog output dedicated to pass the firing
compensation. For rise compensation signal from one channel to the other (usually
ACREG_V2 should become more positive by AD01). Check that the Redundant Tracker in
the amount of droop compensation. the page dedicated to the Redundant channel
7. If line-drop compensation is used, return reads the same value as the Tracker in the
“LDR_XCL” and “LDR_RCL” to original general control page. The Main Tracker in the
value in “LINEDROP” block. Set PT and CT page dedicated to the Main channel usually
will read a different value.
Revised 11-09-06 12
INSTRUCTIONS FOR SINGLE OR DUAL CHANNEL INSTALLATION I.L. 6D34315E
11. Disable the Trackers in the PanelMate page pickup. Turn off mV input; wait for inverse
for transfer control. Go to the "Output timer to time down. Suddenly apply mV
Control" page for the Main channel and raise source and measure time until OEL times out
the adjuster reference. Observe that the and record. Check that this timing is consistent
with the A, B, and C settings and timing is
Tracker reading goes negative. Enable the coordinated with generator thermal capability
Tracker and verify the Tracker value returns to (ANSI C57.xx). “OEL00_F2” turns true after
near zero. inverse timer times out. Remove mV source.
12. Switch to Redundant Channel in Control and 5. Set mV source to be 30 percent over limiter
repeat the above step but raise the adjuster pickup. Turn off mV input; wait for inverse
reference in the Redundant channel page. timer to time down. Suddenly apply mV
source and measure time until limiter and
Checkout of Limiters and Protective Functions protective functions time out and record.
(I) Check that this timing is consistent with the A,
The following are the more commonly used B, and C settings and the timing is coordinated
limiter and protective features and a typical with generator thermal capability.
method for checking each. The event recorder 6. Check correct operation of flags to transfer
feature in ccTool may be used to check short time channels, disable followers, and generate unit
delays in the following section as needed. For dual trip per site specific requirements.
channel systems, it is advisable to perform the 7. If used, check Temperature Recalibration.
calibration of each block at the same time with
both channels to obtain the closest possible 8. If used, check Pressure Recalibration.
results. 9. "INST_CUR" block. Check Instantaneous
Note: If desired, after each pickup point has been Limiter. Check any relays, lights, or
verified, the operation of each limiter can be seen annunciators associated with
by looking at the bridge output voltage. The firing INSTANTANEOUS Current Limiter.
circuit must be brought to a reasonable level (100) 10. Set system to simulate 52 breaker open. Raise
prior to the implementation of the above pickup mV input until Inst. Limiter “INS_F1” picks
signal test. The firing signal can be adjusted with up, and record this as off-line limiter pickup.
the auto/man adjusters. The tracking circuit 11. Raise mV input until Inst. Limiter “INS_F3”
(adjuster followers) should be disabled to prevent picks up, and record this as off-line protection
them from interfering with the operation of the pickup. Remove mV source.
limiters during the test.
12. Set mV source to be 4 percent over off-line
1. "OEL_P" block. Check Overexcitation protection pickup "INS_SP4". Suddenly apply
(Maximum) Excitation Limiter (OEL {MXL} mV source and measure time until INST_CUR
Time Delay). Check any relays, lights, or timers time out and record.
annunciator associated with the OEL (MXL). 13. Set system to simulate 52 breaker closed.
Raise mV input until Inst. Limiter “INS_F1”
Note: When the step change is done any picks up, and record this as on-line limiter
instability of the signal source will cause pickup.
false operation of the pickup point and vary
the timing. The signal can be monitored 14. Raise mV input until Inst. Limiter “INS_F3”
with the data logging function. picks up, and record this as on-line protection
pickup. Remove mV source.
2. Check that the recal inputs are not effecting
the output. Raise mV input until OEL picks up 15. Set mV source to be 4 percent over the on-line
“OEL00_F1”, and record this as limiter protection pickup “INS_SP3”. Suddenly apply
pickup. OEL output remains at “OEL00_OFF” mV source and measure time until all Inst_cur
while OEL is timing. timers time out and record. Check that this is
coordinated with generator thermal capability.
3. Raise mV input until OEL picks up
“OEL00_F3”, and record this as protection 16. "HXL_P" block. Check Volts/Hertz Limiter
pickup. (HXL). Check any relays, lights, or
annunciators associated with the HXL.
4. Set mV source to be 4 percent over limiter
Revised 11-09-06 13
INSTRUCTIONS FOR SINGLE OR DUAL CHANNEL INSTALLATION I.L. 6D34315E
17. Raise PT intelligence until "HXL_F1" picks 27. "UEL_P" block. Check Under Excitation
up and record this as limiter pickup. Raise PT (Capability curve) Limiter (UEL). Check any
intelligence until "HXL_F3" picks up and relays, lights, or annunciators associated with
record this as protection pickup. the UEL.
18. Reduce PT intelligence fifteen percent. Sud-
denly increase PT signal to 4 percent over 28. Check that the recal inputs are not affecting
limiter pickup. Measure time until HXL times the output. Set PT intelligence at rated value,
out. Check that this timing is consistent per set balance meter to zero, and CT intelligence
settings and timing is coordinated with to 0.5 amp at zero power factor lead. Simulate
generator volts/thermal capability (ANSI 52 breaker closed. UEL output should be
C37.xx). “HXL_F2” turns true after inverse negative and equal to “UEL_OFF”. Raise CT
timer times out. signal until UEL picks up and record. Increase
CT signal until "UEL_F2" picks up and
19. Reduce PT intelligence ten percent. Suddenly record.
increase PT signal to 10 percent over limiter
pickup. Measure time until HXL times out. 29. Reduce CT signal to 0.5 amp. Increase CT
Check that this timing is consistent per signal to five percent above "MEL_F2" pick
settings and timing is coordinated with up and measure time until "UEL_P" timers
generator volts/thermal capability. “HXL_F2” time out and record.
turns true after inverse timer times out. 30. Shift phase angle 60 degrees to simulate 26
20. "OVL_P" block. Check Overvoltage Limiter degrees (.9 pf.) under excited. Raise CT signal
(OVL). Check any relays, lights, or until UEL picks up again and record.
annunciators associated with the OVL. Typically this will be more than CT signal at
full load unity p.f. Check that this is
21. Raise PT intelligence until "OVL_F1" picks coordinated with any loss of field protection.
up and record and record this as limiter
pickup. Raise PT intelligence until "OVL_F3" 31. If used, check Temperature Recalibration.
picks up and record this as protection pickup. 32. If used, check Pressure Recalibration.
22. Reduce PT intelligence ten percent. Suddenly 33. Check Loss of Sensing. Check all relays plus
increase pt signal to 4 percent over limiter any lights and annunciators associated with
pickup. Measure time until OVL times out. L.O.S. Disconnect one phase to simulate failed
Check that this timing is consistent per fuse.
settings and timing is coordinated with
generator voltage capability. 34. Check any other limiter and protective
features.
23. "MEL_P" block. Check Minimum
Excitation Limiter (MEL). Check any relays, 35. Make all limiter and protective equipment
lights, or annunciators associated with the settings per customer specified values (settings
MEL. are customer’s responsibility).
24. Set PT intelligence at rated value, set balance
meter to zero and CT intelligence to 0.5 amp
at zero power factor lead. Simulate 52 breaker Test Monitoring Functions (J)
closed. MEL output should be negative and
equal to “MEL_OFF”. Raise CT signal until Test the operation of all protective circuits, using
MEL picks up and record value. Increase CT simulated intelligence where required. Refer to
signal until "MEL_F2" picks up and record. contract schematic diagrams.
25. Reduce CT signal to 0.5 amp. Increase CT 1. Check generator ground detectors and all
signal to five percent above "MEL_F2" pick associated relays, lights and annunciators.
up and measure time until MEL_P timers Typical setup is as follows (using ccTool to access
times out and record. FLDGND block in ECM):
26. Shift phase angle 60 degrees to simulate 26
degrees (.9 pf.) under excited. Raise CT signal a. Disconnect pin 5 from the field.
until MEL picks up again and record value. b. Apply 120 volts AC, 60 Hz to pins 6 and
Typically this will be more than CT signal at 7. Leave resistor off of the pin 10 and 12.
full load unity p.f. Check that this is Check that there is no voltage across pins
coordinated with any loss of field protection. 1 and 2. Verify that output "AD00_IN_A"
Revised 11-09-06 14
INSTRUCTIONS FOR SINGLE OR DUAL CHANNEL INSTALLATION I.L. 6D34315E
Revised 11-09-06 15
INSTRUCTIONS FOR SINGLE OR DUAL CHANNEL INSTALLATION I.L. 6D34315E
Revised 11-09-06 16
INSTRUCTIONS FOR SINGLE OR DUAL CHANNEL INSTALLATION I.L. 6D34315E
5. Holding the machine at rated speed and rated that the Tracker value is close to zero (+0.1).
no-load voltage on its terminals, check the Transfer to Redundant channel and repeat
three-phase intelligence voltage at the steps 8 through 11. At customer request, the
regulator input panel terminals 7-8-9 to be unit can be switched to Redundant channel in
approximately 120 volts line-to-line and to control with 41A device open, and the
have phase sequence 7-8-9. Actual value generator field flashed again and the steps in
should agree with regulator PT ratio on site this section repeated.
specific schematics. If they disagree determine
reason before proceeding. Check Excitation Control Off-Line (N)
6. Check that the output of the terminal voltage Note: The off-line instantaneous limiter has to be
transducers reads 1.00, (in both channels for a set high enough not to impact the bump test,
dual channel system). If not adjust scale i.e., to the on-line value for a rotating
factors in the “SIGIN” block in each channel exciter. The reason is that positive voltage
to make it so. bumps with a rotating exciter can cause the
limiter to effectively reduce the generator
7. Check that “SLC2_V4” reads between 1.0 and ceiling voltage and make the response look
1.15. (A precise value should be based on the like that of an over or critically dampened
generator saturation curve and be equal the regulator. See figure #5.
actual field current at no load divide by the
airgap field current at rated voltage read from The Preliminary Setup should be as follows:
the saturation curve.) If not, adjust 1. Stability and damping adjustments of the
SLC2_KFC to make it so. For a dual channel regulating system are usually made with the
system, change SLC2_KFC in the Redundant synchronous machine off line (except for
channel to the adjusted value. synchronous condensers that must be
8. Verify the operability of the Manual regulator connected to the system to operate). If settings
(unit is in AUTO) in both the RAISE and the have been determined by stability studies,
LOWER direction by moving the Manual those values should be set before doing the
voltage adjuster to cause the regulator balance bump test.
meter to indicate on first one side of meter 2. With ccTool, set up an Event Recorder block
zero and then the other side of zero. This in the ECM to measure the bump input signal,
action of the voltage adjuster should not affect terminal voltage, firing command, and field
the machine terminal voltage. current during the off line bump tests. Set
9. Move the voltage adjuster in the LOWER event to trigger on input of the bump signal.
direction. This action should reduce the Other inputs may be recorded as desired.
machine terminal voltage. The balance meter 3. With the generator operating at rated speed
should return to near zero. Move the voltage and off line, adjust the terminal voltage to the
adjuster in the RAISE direction, causing the rated value by means of the auto adjuster.
machine terminal voltage to return to normal.
Adjust “ACADJ_SLEW” as needed for 4. Connect a low voltage variable DC source to
smooth voltage control by the operator. an analog input point of an AIO card. (A
source can be made by connecting a 5W or
10. Transfer unit to manual and move the manual more potentiometer, 1k to 10K, across the
adjuster in the LOWER direction. This action +24 to -24 volt power supply to the BCM in a
should reduce the machine terminal voltage. manner suitable to feed a plus or minus test
The balance meter should return to near zero. voltage signal into the analog input.) The
Move the voltage adjuster in the RAISE analog input should be scaled so that 1.00 volt
direction, causing the machine terminal in yields 0.0100 change in the appropriate
voltage to return to normal. Adjust ALOGDIG output. Thus a DC voltage of
“MANADJ_SLEW” as needed for smooth approximately one volt will simulate a
voltage control by the operator. machine voltage change of 1%. Make a rapid
11. Return unit to auto. change in the machine voltage setting by
changing this test voltage signal (starting with
12. For a dual channel system, verify the Tracker 1% change in terminal voltage in the direction
and the Transfer Possible is enabled. Check to reduce voltage). Gradually increase bumps
Revised 11-09-06 17
INSTRUCTIONS FOR SINGLE OR DUAL CHANNEL INSTALLATION I.L. 6D34315E
to 5% voltage change first in the LOWER the power grid. Load unit to about 10 percent
direction and then in the RAISE direction for rated MW load (higher if required by turbine
various damping adjustments. By observing conditions).
the response action on the recorder charts, 2. With the generator connected to the power
optimum damping adjustments may be made. system (line breaker 52 closed) and the
See Figure 5 for suggested optimum response machine at unity power factor, check that the
conditions. Care should be taken that the unit phase angle between the current and voltage
is not under damped when off line so as to intelligence using the event recorder. At unity
avoid oscillations when the unit is on line. power factor the Phase B line current should
lag the phase AB line-to-line voltage by
approximately 150 degrees. If needed, adjust
“POWERTRAN#00_PHASE” (in both
channels for a dual channel system) to make
THE INSTALLATION ENGINEER SHOULD “PTRAN_MVAR” read 0.00 at unity power
BE VERY CAREFUL IN RUNNING THESE factor. (This compensates for phase shifts
TESTS TO AVOID SUBJECTING THE between the regulator PTs and CTs from the
MACHINE TO TERMINAL VOLTAGES ideal 150 degrees phase shift.)
GREATER THAN ITS RATING.
3. Re-enable all reactive compensation functions.
Check with the customer to be sure of the
required setting. For satisfactory parallel
operation of the regulator-controlled machine
with the system, there should be a 4% to 6%
reactance between the machine terminals and
the system. This reactance can be in the unit
transformer, or the regulator can be biased by
the droop compensator, set for 4% to 6%
reactive droop to accomplish the same effect.
4. Using auto control, raise excitation slightly;
i.e.; set the generator to supply vars to the
system. Verify that for droop compensation
the adjuster reference moves slightly more
than the terminal voltage increase. Verify that
for rise compensation the adjuster reference
moves slightly less than the terminal voltage
increase.
5. After checking the regulator balance meter is
near zero, transfer from the auto to manual
regulator control. Carefully operate the manual
regulator adjuster slightly in both the LOWER
direction and the RAISE direction, and
observe that the machine reactive loading is
Fig. 5 Generator Output Responses decreased in response to lowering the adjuster,
and is increased in response to raising the
Check polarity and phase angle of Machine CT manual regulator. Transfer unit back to
and PT signals to be correct (O) automatic.
1. The unit is now ready to be synchronized with 6. For a dual channel system, verify Tracker is
the power grid. Before closing the generator reading close to zero and transfer from Main
(52) breaker, set up an Event Recorder block channel control to Redundant channel control.
in the ECM, using ccTool, to measure The oscillations in voltage should be very
regulator PT inputs, CT inputs and terminal small. Repeat previous step. Transfer unit
voltage. If metering PTs are used they should back to Main channel in control.
also be recorded. Synchronize the unit with
Revised 11-09-06 18
INSTRUCTIONS FOR SINGLE OR DUAL CHANNEL INSTALLATION I.L. 6D34315E
Revised 11-09-06 19
INSTRUCTIONS FOR SINGLE OR DUAL CHANNEL INSTALLATION I.L. 6D34315E
Revised 11-09-06 20
INSTRUCTIONS FOR SINGLE OR DUAL CHANNEL INSTALLATION I.L. 6D34315E
Note: To "find" software blocks, inputs, or outputs in ccTool, use the hotkey F3
TABLE 1
Revised 11-09-06 21
INSTRUCTIONS FOR SINGLE OR DUAL CHANNEL INSTALLATION I.L. 6D34315E
TABLE 2
TABLE 3
Revised 11-09-06 22
IL ECSM009B
What is ccTool?
The Controller Configuration Tool (ccTool) is a sophisticated tool for configuring, monitoring, maintaining,
and debugging a programmable controller. Typically, ccTool is used at installation to configure the controller
and, thereafter, is used to monitor operations and, as needed, fine tune input values.
ccTool provides a full range of options for viewing, editing, and saving configuration information, and
includes security levels to ensure that only authorized users can change the configuration information.
Page 2 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/whatisccTool.h 9/26/03
Model for Programming a Controller Page 1 of 1
The ccTool model for programming a controller provides an easy-to-use application program on a PC to
define configuration information for the blocks of code within the controller. The ccTool application is first
used to define all configuration information in a file on the PC. Once the controller is in a Resolved state,
ccTool is used to download the information to the Random Access Memory (RAM) of the controller. You then
use ccTool to fine tune configuration values as needed within RAM. Because information in RAM is lost in
the event of a power cycle, you save the configuration information from RAM to permanent Flash memory
after you have tested and are satisfied with the configuration. At power-up, the configuration comes from
Flash and overwrites the RAM values.
Page 3 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/model.htm 9/26/03
Blocks and Block Connections Page 1 of 1
The controller contains blocks of code that control specific functions. A block can have any number of inputs
and outputs. An input can be a constant or a connection to another block.
For example, the following illustration shows the ACVLTADJ and AUTO_REG blocks of the ECM as they
might be displayed in the ccTool Diagram window. Some of the inputs, such as the K1 through KC inputs of
the AUTO_REG block, are constants. The REF output of the ACVLTADJ block provides the input for the
ACADJ_REF input of the AUTO_REG block, and the connection line is shown. (Connection lines can be
made invisible in the Diagram window, in which case the output name is shown outside the input line as
illustrated below for AUTO_REG block inputs such as PSS2_OUT and TEST. See Diagram Window
Contents for more information on the contents of the Diagram window).
The controller defines the blocks and their inputs. Using ccTool, you define:
l Interrupt blocks have an execution strategy. Some interrupt blocks have a fixed execution strategy,
meaning that the controller assigns the strategy and you cannot change it.
l Mainline blocks either execute or do not execute. They do not have an execution strategy. Some
mainline blocks are fixed, meaning you cannot turn off the execution. Some controllers do not have
mainline blocks.
Page 4 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/blocks.htm 9/26/03
Execution Strategy Page 1 of 1
Execution Strategy
The execution strategy defines when a block executes in relation to all other blocks, the time slots in which
the execution takes place, and the the executions per cycle.
Page 5 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/execstrategy.ht
...m9/26/03
File, RAM, and Flash Configurations Page 1 of 1
l Configuration File - You use the configuration file to define new configurations before putting them in
operation. When you are ready to put the configuration into operation, you download from the
configuration file to the RAM of the controller. If the controller is not in the Resolved state when you try
to download, ccTool asks if you want to set the state to Resolved. Your security level is also checked
at the time of download. Any level user can edit the configuration file, but only users with the
appropriate security level can download the information to RAM.
l RAM - This is the configuration information that will be executed. After you download from the
configuration file, the controller state will be Resolved. You set the state to Execute Blocks to begin
executing the new RAM values. You then monitor and fine tune the configuration as needed.
l Flash memory - Flash memory is the permanent memory of the controller. Unlike RAM, Flash memory
is not lost if the power goes off. Therefore, you save from RAM to Flash in order to retain information
in the event of a power outage or re-cycle. At power-up, the Flash configuration replaces the RAM
configuration. You cannot directly edit any information in Flash memory.
Page 6 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Files%20Ram...% 9/26/03
Controller States Page 1 of 1
Controller States
The following table describes the controller states that are tracked within ccTool.
State Description
Unknown This state indicates there is no response from the controller or the response
cannot be understood. It can result from losing the connection to the controller
or an error in the controller. You cannot set this state. Once in this state, the
problem with the controller or the connection must be fixed before operation
can continue.
Boot Use this state only when you need to download new firmware into the
controller. You can set this state, or ccTool goes into this state automatically if it
gets a response from the controller saying that it is in boot state.
Unresolved This state indicates an user error in the configuration information. To change
the state, you must correct the configuration error.
Resolved This state indicates that the configuration information is valid and ready to
execute but is not executing yet. You can set this state to have ccTool re-check
the resolution.
Initialized This state sets block outputs and internal states of the block sto known values.
Executing This state indicates that the blocks are executing in RAM. After ccTool shows
Blocks the state as Resolved, you can set this state.
Executing This state is set by the controller and cannot be set within ccTool. You can
Application change parameter values while in this state but you cannot change the state.
Page 7 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Controller%20
...S 9/26/03
Security Page 1 of 1
Security
ccTool security levels apply to the RAM configuration. You can edit any information in the File Configuration
regardless of your security level. Your security level is checked when you download from the File
Configuration to RAM, or when you directly edit RAM.
l View Only allows you to view all information in RAM but not save any changes.
l Change Configuration allows adding and removing blocks, purchasing blocks, and changing the
type of input.
The View Only level does not require a password. All other security levels are password protected.
You are logged into ccTool as a View Only user. If you know the associated password, you can change your
security level after you connect to a controller. The Connect command allows you to change your level after
the connection is made, and you can later use the Set Security Level command as needed. Users at a
higher level can change the password for their security level or a lower level. If you forget your password,
call Cutler-Hammer and give them the Controller ID. They can then give you a new password.
Page 8 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Security.htm 9/26/03
Running ccTool Page 1 of 1
Running ccTool
1. Click the Start menu, and then point to Programs, Cutler-Hammer, ccTool. Click on ccTool.
You are logged in as a View Only user. If authorized, you can choose Set Security Level from the File menu
to change your security level.
The ccTool window appears. You can now use the Connect command to connect to a controller.
Page 9 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Running%20CC 9/26/03
The ccTool Windows Page 1 of 1
When you start ccTool, the main ccTool window contains pull down menus and a gray working area in which
other windows are displayed after you connect to a controller. Depending upon how the window was setup
when you lasted used ccTool, it may also contain:
You can toggle the display of the toolbar, connection bar, and status bar using commands in the View menu.
After you connect to a controller, you can display one or more of the following windows in the working area of
the main window:
l The Diagram window displays and allows you to manipulate a graphical representation of a
configuration.
l The Application Configuration window displays the configuration information in a table.
l The Execution Strategy window displays the execution strategy in a table.
l The Mainline Execution window displays a table showing whether or not each mainline block will
execute.
You may also have custom monitor windows setup for you by Cutler-Hammer.
The window in which you are currently working is referred to as the active window. The active window has a
blue header.
Page 10 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/ccTool%20Win 9/26/03
Menu and Command Button Layout Page 1 of 1
l Pull-down menus that include all commands related to the active window
l A toolbar that includes icons for the most frequently used commands
l Pop-up menus that appear over an object when you right-click on the object. These menus are called
shortcut menus. They include the most frequently used commands for that type of object.
When you start ccTool, the menu bar and tool bar appear as follows:
After you connect to a controller, additional menus appear and the tool bar icons related to working with a
controller become active.
Page 11 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Menus%20La...y 9/26/03
Toolbar Icons Page 1 of 1
Toolbar Icons
Close: Closes the connection to the controller or, if you are working in offline mode, closes the
configuration file.
Preferences: Defines your personal settings for how certain features of ccTool operate.
Toggle Connection Bar: Displays or removes a window that lists your current connections.
Alarms: Displays the Alarms window. The icon flashes with a red border, as shown here, if there are
active unacknowledged alarms. The icon flashes with a yellow border if there are one or more active alarms
that have been acknowledged but not cleared. The icon does not flash and has no color if there are no active
alarms.
Configuration Differences: Displays a list of all differences between the configurations. A flashing
icon indicates at least one difference has been detected. However, some differences will not be detected
until the command has been invoked.
Page 12 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/toolbar.htm 9/26/03
Getting Help Page 1 of 1
Getting Help
l Tool Help - Choose Tool Help from the Help menu to display the Help you are now using. This Help
explains how ccTool works.
l Block Help - Choose Block Help from the Help menu to display Help on the blocks within each
controller. This Help describes and provides a diagram of each block. From a block diagram, it also
allows you to find the block in ccTool.
l Context Sensitive Help - Most dialogs contain a Help button. Click the Help button to go directly to
the Help topic for that command.
l Status Bar - The status bar at the bottom of the ccTool window displays a brief description of the
block, input, or output as you work with objects in windows.
l Tool Tips - Position the cursor over a toolbar icon to display the command name.
Page 13 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Help.htm 9/26/03
Connecting to a Controller Page 1 of 1
Connecting to a Controller
The topics in this section are designed to teach you the basics of connnecting.
Page 14 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Connect%20O
...v 9/26/03
Set Connection Preferences Page 1 of 1
You can set the windows that appear when you connect to a controller.
To do so:
1. Click the Preferences icon in the toolbar, or choose Preferences from the File menu.
2. Under Initial Windows, check the windows you want to display when you connect to a controller.
3. Click OK.
Page 15 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Configure%20
...- 9/26/03
Connect Page 1 of 1
1. Click the Connect icon in the toolbar , or choose Connect from the File menu.
Note: If you are already connected to a controller, the Connect menu item changes to Connect Using.
Choose Connect Using, and then choose COM Port Connect.
2. Enter the Port, Baud Rate, and Address, and then click OK. If the address is not in the list, you can
type it.
The command ends and the windows you checked in the Preferences dialog appear.
Page 16 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Configure%20
...- 9/26/03
Assigning Blocks in the Diagram Window Page 1 of 1
The topics in this section are designed to teach you the basics of adding a block and defining input
assignments. Before performing these tasks, look at the Block Help for the block you plan to add. These
topics use the example of adding the DA1 block to the FCIM file configuration.
These topics also focus on using the Diagram window. Note that you also can add blocks and assign inputs
in the Application Configuration window. The Diagram window is used here because it provides a more
visual interface than the Application Configuration window.
For general information on using the Diagram window, see Using the Diagram Window.
Page 17 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Using%20Con
...f 9/26/03
Setting Up the Diagram Window Page 1 of 1
At this point, you want to set up the Diagram window to display the File Configuration and allow editing. You
want to display the File Configuration because you always add and configure a block in the File
Configuration rather than RAM. This allows you to define the configuration before putting it into operation. In
order to allow editing in the Diagram window, you must turn on Dynamic Edit Mode.
1. If the Diagram window is not displayed, choose it from the Window, New Window menu.
2. If the current configuration is not File Configuration, choose File Configuration from the drop-down
list in the toolbar.
3. Click the Toggle Dynamic Edit icon to enable Dynamic Edit Mode.
Page 18 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Setting%20Di...a 9/26/03
Adding a block Page 1 of 3
Adding a Block
Now that you have the Diagram window setup, you want to add a block. You use the Add Block command to
add a block and, optionally, define the execution strategy and inputs. The steps below illustrate adding the
DA1 block of the FCIM controller, defining its execution strategy, and assigning all of its inputs.
To add a block:
2. In the Add Block dialog, select the block to add, check the Configure the Added Blocks option, and
then click Next.
3. In the Configure Blocks dialog, leave both Execution Strategy and Input Assignments checked.
Click Next. (Note that Execution Strategy will be gray if the block is fixed. In that case, skip the next
step.)
Page 19 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Add%20Block
.... 9/26/03
Adding a block Page 2 of 3
The Input Assignment dialog appears for the first block input. The default assignment type
(From Output or Constant) for this input is selected. In the example below, the first input for the
DA1 is DA1_IN1, and the default assignment type is From Output.
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Add%20Block
.... 9/26/03
Adding a block Page 3 of 3
¡ To change the assignment type, click the Constant or From Output radio button.
¡ For a Constant value, type a value and click the radio button that identifies the type of value as
Decimal, Hexadecimal, etc.
¡ For a From Output value, select the block and output from the drop-down lists.
¡ Click Next when you are done.
For the DA1_IN1 input shown in the example above, you want to change the assignment type
to Constant and enter a value. (You will later draw a connection in the Diagram window to
change the type back to From Output).
If there are any potential problems with this assignment, a confirmation dialog asks you to
verify making the assignment. Click Yes to continue, or No to return to the Input Assignment
dialog.
6. The Input Assignment dialog repeats for each input. Assign each input a value as explained in the
previous step. For DA1, assign all remaining inputs constant values.
After you have assigned all inputs, the Configure Blocks dialog is again displayed.
7. In this Configure Blocks example, all block inputs have been assigned and so you can click Finish to
end the command. If all inputs had not been assigned, the unassigned block(s) would be listed in the
dialog and you could either make the assignments or end the command without making assignments.
The block is added. The new block is not displayed in the Diagram window automatically. You display it in
the Diagram window as described in the next topic.
Page 21 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Add%20Block
.... 9/26/03
Displaying and Positioning a Block Page 1 of 1
Now that you have added a block, you want to display it in the Diagram window. You use the Block List to
display the block. The Block List is a window that lists all blocks in the configuration and indicates whether
they are currently displayed (visible) or not displayed (invisible). You use the Block List to control which
blocks are displayed in the Diagram window.
1. In the toolbar of the Diagram window, click the Toggle Block List icon to display the Block List.
2. In the Diagram window, pan to the area where you want to display the block you added. You can use
the scroll bars to do this or the Pan or Zoom commands.
3. In the Block List, first click any visible blocks that you want to make invisible. Then, click the block you
added to make it visible.
The block is placed in the center of the Diagram window, and is blinking.
4. To move the block, position the cursor over the block, and then hold down the left button and drag the
block to the desired location. Release the mouse button when the block is at the desired location.
For example, you could place the DA1 block close to the F_TO_VAB block because the IN1 input of DA1 will
connect to the F_V_TAB output.
Page 22 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Make%20Bloc
...k 9/26/03
Drawing a Connection Line Page 1 of 2
Now that you have displayed the block you added in the Diagram window, you want to change some of its
input assignments. You can change input assignments (or assign unassigned inputs) in the Diagram window
by either drawing a connection line or entering the assignment values in a dialog box. In the steps below,
you will draw a connection line and make it orthogonal. In the next topic, you will enter assignment values.
1. Position the cursor over the input line for which you want to draw a connection. The input can be
unassigned, a constant that you want to change to a connection, or a connection that you want to
change to a different output. The cursor must be positioned exactly over the input line. The cursor
changes to when it is correctly positioned.
2. Hold down the left button and drag to draw a line representing the connection. The cursor changes to
.
3. Release the button over the output to which you want to connect. The output line is highlighted.
If there are any potential problems with this assignment, a confirmation dialog asks you to
verify making the assignment. Click Yes to make the assignment, or No to cancel it.
The connection line is drawn. For example, you could change the IN1 input of DA1 from a constant to a
connection by drawing a connection line between the IN1 input of DA1 and OUTPUT of F_V_VAB as follows:
1. If you want to add one point, position the cursor over the line at the place you want to add the point. If
you want to add multiple evenly spaced points, position the cursor anywhere over the line.
3. Choose Add Point(s), and then choose the number of points from the submenu.
If you chose to add 1 point, it is added at the location you clicked. If you choose to enter multiple
points, they are evenly placed along the line (or along the line segment if you previously added points
and re-shaped the line to have multiple segments).
4. To re-shape the line, hold down the left mouse button over a point, and then drag.
5. You can repeat these steps as needed to continue to add points and re-shape the line.
For example, you could re-shape the connection line you drew above as follows:
Page 23 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Draw%20Con...n 9/26/03
Drawing a Connection Line Page 2 of 2
Page 24 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Draw%20Con...n 9/26/03
Entering Assignment Values Page 1 of 1
In addition to assigning input in the Diagram window by drawing connection lines, you can assign input by
entering the values in a dialog box. You can use this method to assign inputs that are constants or
connections.
1. Position the cursor over the input to assign or edit, click the right mouse button, and then choose
Assignment from the shortcut menu.
3. Click OK.
If there are any potential problems with this assignment, a confirmation dialog asks you to
verify making the assignment. Click Yes to continue, or No to return to the Assign Block Input
dialog.
Page 25 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Enter%20Assi...g 9/26/03
To download to RAM Page 1 of 1
Downloading to RAM
After you define your new File Configuration, you download it to RAM. Downloading to RAM sends the whole
configuration to the controller and overwrites all values now in RAM. Be sure you want to do this before
proceeding. Some notes about downloading:
l If you added or removed a block in the File Configuration, or changed the type of an input, you must
have a security level of Change Configurations to download to RAM. If you only changed input values
in the File Configuration, you only need to have the Tune Configuration security level to download to
RAM.
l All blocks in the File Configuration must be completely configured before downloading. If one or more
blocks are not completely configured, the Download To RAM command allows you to configure them
as this point.
l The controller must be in the Resolved state. If it is not, the Download To RAM command asks if you
want to change the state to Resolve.
l The configuration you download is not automatically put into execution. After downloading, you
change the state from Resolved to Executing Blocks as part of verifying the RAM configuration.
To download to RAM:
2. If one or more blocks in the File Configuration are not completely configured, a dialog asks if you want
to configure the blocks. Click Yes to have operation proceed as described for Add a Block. Click No to
cancel the download.
3. If the controller state is not Resolved, a dialog asks if you want to change the state to Resolved. Click
Yes to change the state to Resolved, or No to cancel the download.
4. A dialog warns you that the current values in RAM will be overwritten and asks if you want to
continue. Click Yes to proceed, or No to cancel the download.
Page 26 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Download.htm 9/26/03
Verfiying the RAM Configuration Page 1 of 1
After downloading to RAM, you put the new RAM values into execution, and then monitor and fine tune the
values as needed to verify that they are correct.
1. Click the Set State icon in the Diagram window toolbar, or choose Set State from the
Configurations menu.
2. Click the Executing Blocks radio button, and then click OK.
3. In the Diagram window toolbar, select RAM Configuration from the drop-down list.
4. Click the Show/Hide RAM Values icon in the Diagram window toolbar to display the actual RAM
values.
5. Monitor the RAM values to ensure that they are correct. If necessary, you can change an input value
but cannot change the input type.
Page 27 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Verifying%20...R 9/26/03
Saving to Flash and File Page 1 of 1
When you are done fine-tuning your RAM Configuration, you save it to Flash. To create a backup copy of the
fine-tuned configuration, you then upload RAM or Flash to the File Configuration.
l To save the RAM Configuration to Flash, choose Save RAM to Flash from the Configurations menu. A
dialog asks you to confirm that you want to overwrite everything in Flash.
l To upload to the File Configuration, choose Upload RAM to File or Upload Flash to File from the
Configurations menu. A dialog asks you to confirm that you want to overwrite everything in the File
Configuration. After you upload, use Save or Save As to save the file configuration to disk.
Page 28 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Saving.htm 9/26/03
Diagram Window - overview Page 1 of 1
The topics in this section describe the content and features of the Diagram window.
l Window Content
l Diagram Toolbar Commands
l Selecting and Moving Blocks
l Moving Connection Points and Line Segments
l Shortcut Menus
l Navigating in the Diagram
For examples of specific tasks you perform in the Diagram window, see Assigning Blocks in the Diagram
Window.
Page 29 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Diagram-over...v 9/26/03
Diagram Window - content Page 1 of 2
Window Content
The Diagram window displays and allows you to manipulate a graphical representation of a configuration. It
is particularly useful for viewing and fine tuning assignments. In addition to providing a full range of menu
commands for assigning blocks, you can manipulate the graphical representation to:
For example, you could display only the following portion of a configuration in the window:
Block information is shown in the Diagram window (except when you are displaying the actual RAM values)
Page 30 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Diagram-conte
...n 9/26/03
Diagram Window - content Page 2 of 2
as follows:
l Inputs are shown on the left of the block and outputs on the right of the block. The input and output
names (or abbreviated names) are shown inside the block.
l Constant values are shown within brackets, such as for the K1 through KC inputs of the AUTO_REG
block.
l Connections can be made visible or invisible. When visible, the connection line is shown as illustrated
above for the connection between the REF output of the ACVLTADJ block and the ACADJ_REF input
of the AUTO_REG block. When invisible, the output name appears next to the input line, as illustrated
above for AUTO_REG inputs such as PSS2_OUT.
l When an output has multiple connections, the number of connections is shown on the output line.
l Pink lines in the diagram indicate that the line is not orthogonal. You can add points to make the line
orthogonal.
To edit any information in the Diagram window, you must use the toolbar to enable Dynamic Edit.
Page 31 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Diagram-conte
...n 9/26/03
Diagram Window - toolbar Page 1 of 2
The Diagram window extends the toolbar along the top of the ccTool window to include the following
Diagram toolbar.
The Diagram window has two viewing modes: Pan Mode and Rectangle Select Mode. The shape of the
cursor when it is not positioned over a block or connection line indicates the current mode: indicates Pan
Mode, indicates Rectangle Select Mode.
When Dynamic Edit is off, Pan Mode is always in effect. Dragging the cursor anywhere in the diagram (either
on an object or outside an object) pans the diagram.
When Dynamic Edit is on, you can use either Pan Mode or Rectangle Select Mode. In Pan Mode, dragging
the cursor when not on a block or connection line pans the diagram. In Rectangle Select Mode, dragging the
cursor when not on a block or connection line draws a rectangle and selects the objects in the rectangle.
Note that connection points are not selected unless the entire connection is within the box.
Zoom to Fit
Zooms out until the diagram fits into the current window. If the diagram is too large or the window is too
small, the diagram is zoomed to the smallest possible setting for the window size.
Zoom to Box
Zooms in to an area that you specify by drawing a rectangle.
Page 32 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Diagram-toolb
...a 9/26/03
Diagram Window - toolbar Page 2 of 2
Shows the current configuration. In offline mode, only the File Configuration is available. When connected to
a controller, you can choose either File, RAM or Flash configurations.
Page 33 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Diagram-toolb
...a 9/26/03
Diagram Window - Moving Blocks Page 1 of 1
When Dynamic Edit is on, you can select and move blocks.
In either Pan Mode or Rectangle Select Mode, you can select and move blocks as follows:
l To move multiple blocks, hold down the Ctrl Key and select each block, and then downclick within the
extents of the selected blocks and drag to move them.
In Rectangle Select Mode, you can also select and move blocks as follows:
1. Position the cursor outside of the blocks and drag to draw a selection box around the blocks.
2. Downclick within the extents of the selection box and drag to move the selected blocks.
Any connection lines to the blocks are automatically adjusted as you move the blocks. You do not need to
select the connection lines.
Page 34 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Diagram-Bloc...k 9/26/03
Diagram Window - Moving Connection Page 1 of 1
You can draw connection lines and add points to the lines as described in Drawing a Connection.
After you add points to a line, you can dynamically re-shape the line by dragging points or line segments.
You can only drag line segments that are vertical or horizontal, and are not the starting or ending line
segment. The shape of the cursor indicates the type of movement allowed:
Cursor Meaning
You are over a connection point or a segment of the connection
line that cannot be moved.
You are over a connection point that can be moved
You are over a horizontal segment of the connection that cannot
be moved
You are over a vertical segment of the connection that cannot be
moved.
You are over a horizontal segment that can be moved.
Movement will be restricted to the perpendicular direction of the
segment.
You are over a vertical segment that can be moved. Movement
will be restricted to the perpendicular direction of the segment.
Page 35 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Diagram-Conn
...e 9/26/03
Diagram Window - Shortcut Page 1 of 2
Shortcut Menus
Different shortcut menus are displayed depending on where you right-click in the Diagram window. The
shortcut menus are illustrated below. For information on the commands in these menus, see the Command
Reference.
l Right-click on an input line to display the following menu. (You must click on the line, not the input
value or connection line).
l Right-click on an output line to display the following menu. (You must click on the line, not the input
value or connection line).
Page 36 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Diagram-Short
...c 9/26/03
Diagram Window - Shortcut Page 2 of 2
l When Dynamic Edit is enabled, right-click on a connection line to display the following menu. (When
Dynamic Edit is not enabled, the first menu shown above is displayed when you right-click on a
connection line).
Page 37 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Diagram-Short
...c 9/26/03
Diagram Window - Navigate Page 1 of 1
You can dynamically navigate through the diagram using the scroll bars, or by dragging the cursor when
in Pan Mode.
You can pan to specific information in the diagram using the following commands:
l Use the Find command in the View menu or shortcut menu to scroll to a specific block, input, or
output.
l For inputs or outputs that are connections, use Pan to Connection in the shortcut menu to pan to the
connecting input or output. Pan to Connection is only available if the connection line is displayed. Use
Display Connections in the shortcut menu to display connection lines.
You can also use the Find in Window command in the block, input, or output shortcut menu to locate a block,
input, or output in another window.
Page 38 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Diagram-Navi...g 9/26/03
Using the Application Configuration Window Page 1 of 1
The topics in this section describe the content and features of the Application Configuration window.
l Window Content
l Mouse Interaction
l Setting Up the Table
l Navigating in the Table
l Edit Mode
Page 39 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/ACT-overview
... 9/26/03
Application Window Content Page 1 of 1
Window Content
The Application Configuration window displays the configuration information in a table. It is particularly useful
when you want to compare File, RAM, and Flash values. You can manipulate the table to:
The following Application Configuration window illustration shows all block inputs and outputs for the DA1
and F_TO_VAB blocks, and only the block name for other blocks. It also includes only some of the available
columns of information.
In the table:
l In the Type column, inputs are shown in the standard font and outputs are shown in Italics.
l A white background in a cell indicates that you can edit that value. You cannot edit values in gray
cells.
l Red values indicate a difference from the corresponding value in the column you established as the
reference column. In this example, the File Input is the reference column.
Page 40 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/ACT-window...
% 9/26/03
Application Window Mouse Interaction Page 1 of 2
Mouse Interaction
Selection (Left-click)
Selection in the Application Configuration window is used to identify the RAM values for the Refresh
Selected RAM Values command and the Update Selected RAM Values preference.
l To select a single RAM value, left-click or use the arrow keys to move the cursor to the row of a RAM
value.
l To select or de-select multiple RAM values, hold down the Ctrl key while you left-click.
Note: Unless you hold down the Ctrl key, the previously selected RAM value is de-selected
and will not be updated when you move the cursor to another row in the table.
l Double-click a block name or block type in the first or second column of the table to expand or
collapse the block input information.
l Double-click an input value in the RAM Input or File Input column to display the Assign Block Input
dialog.
l Double-click the RAM Input column header to display a dialog that allows you to change the name
assigned to the RAM file. By default, the RAM file is assigned the name of the configuration file when
you download the File Configuration to RAM.
Right-Click
Different shortcut menus are displayed depending on where you right-click in the Application Configuration
table. The shortcut menus are illustrated below. For information on the commands in these menus, see the
Command Reference.
Note: When you first display the Application Configuration Window, or any ccTool window that contains a
table of information, you must left-click in a cell of the table before you can right-click to display the shortcut
menu.
Page 41 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/ACT-mouse%...2 9/26/03
Application Window Mouse Interaction Page 2 of 2
l Right-click in a column header to display the following list of column names. Check an item in this list
to display the column, or uncheck an item to hide the column.
Page 42 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/ACT-mouse%...2 9/26/03
Application - Setting up the Table Page 1 of 1
This section summarizes the View menu commands you can use to set up the display of the Application
Configuration table. For more information on one of the commands, click the corresponding link.
l Use Set Properties to turn on or off the display of columns in the table. You also can access the
command by double-clicking a column header.
l Use Set Reference Column when you want to highlight any differences in values between the File,
RAM, and Flash configurations. This command sets the reference column to be either the File Input,
RAM Input, or Flash Input column. After the reference column is set, values in the other columns that
differ from the reference value are displayed in red.
l Use Expand All to display the block inputs for all blocks, or Collapse All to display only the block
names. (To expand or collapse an individual block, double-click the block name or block type in the
first or second column of the table.)
l Use Display Engineering Units to display input values in the unit of measure defined for the value.
Page 43 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/ACT-setup.ht...
m 9/26/03
Application - Navigating the Table Page 1 of 1
You can scroll through the Application Configuration table using the scroll bars, or using the keyboard
scrolling keys such as the arrow keys and paging keys.
You can scroll to specific information in the table using the following commands.
l Use the Find in the View menu command to scroll to a specific block, input, or output.
l Use the Find Config Differences and Find Next Difference commands to scroll through the table,
looking at each row in which there is a difference between the File, RAM, and/or Flash data. Choose
the Find Config Differences command from the View to establish the start point for the search. You
can then press F7 (or choose Find Next Difference from the Edit menu) to scroll to the next difference.
Continue to press F7 to scroll to each difference. After you have scrolled through all differences from
the start point you established, a dialog informs you that the search is complete.
Tip You only need to use the Find Config Differences command if you want a dialog to display
after you have viewed all differences. You can press F7 without having used Find Config
Differences to scroll through the differences without being notified when you have viewed all
differences.
l For inputs or outputs that are connections, use Pan to Connection to scroll to the connection, or to
any other instance of that output value in the table. Choose the command from the shortcut menu
after you right-click anywhere in the row of a block output that is a connection, or after you right-click
over the output value in the File Input, Flash Input, or RAM Input cell of a block input row.
In addition to using the commands above to locate information in this window, you can use the Find in
Window command to locate a block, input, or output in another ccTool window.
Page 44 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/ACT-navigate.
...h 9/26/03
Application - Edit Mode Page 1 of 1
Edit Mode
Edit Mode provides a quick way of editing RAM Configuration constant values in the Application
Configuration window.
Note: Use of Edit Mode is not recommended for most situations because Edit Mode does not update RAM
values and other windows dynamically. Always exit Edit Mode before going to other windows. The other
windows and RAM values are updated when you exit Edit Mode.
1. To turn on Edit Mode, check it in the Edit menu or the shortcut menu.
The cells of all constant values in the RAM Input column turn yellow.
2. You can now edit any of the RAM constant values by clicking the value, and then typing a new value.
3. To exit Edit Mode, uncheck it in the Edit menu or the shortcut menu.
Tip After you click a RAM Input value to initially position the cursor, you can use the up and down arrow keys
to move the cursor to other RAM Input values and edit them.
Page 45 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/ACT-edit.htm 9/26/03
Execution Strategy Window Page 1 of 1
The Execution Strategy Window presents a matrix. The time slots of the cycles are listed along the top of the
matrix. The blocks are listed down the side, followed by the time it takes each block to execute. The cells
within the matrix represent the time slots in which each block will execute. A number in a cell indicates the
percentage of the total time.
You can:
If all cells for a block are blank, nothing has been assigned. You can doubleclick a cell to assign the
executions per cycle.
Page 46 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Window%20-...% 9/26/03
Mainline Execution Window Page 1 of 1
The Mainline Execution window displays a table showing whether or not each mainline block will execute.
You can:
In the table:
l An X indicates that the block will execute. A dash indicates it will not.
l A white background in a cell indicates that you can edit that value. You cannot edit values in gray
cells. If all cells for a block are gray, the block is fixed and you cannot change the execution status.
l Red values indicate a difference from the reference column.
l Click in a white cell with an X to turn off execution of the block. A dialog asks you to confirm that you
want to clear the execution.
l Click in a white cell with a dash (-) to turn on execution of the block.
To hide or show one of the columns in the table, uncheck or check File Assignments, Flash Assignments, or
RAM Assignments in the View menu.
To set a reference column, use the Reference Column command in the View menu.
Page 47 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Window%20-...% 9/26/03
Setting Up Security Page 1 of 1
Setting Up Security
Page 48 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Security-Intro.
...h 9/26/03
Setting Your Security Level Page 1 of 1
Use the Set Security Level command to change your current security level. You must enter the associated
password to change to a security level that is higher than your current level.
2. Select a security level and, if the level is higher than your current level, enter the associated
password. The security levels are:
¡ View Only allows you to view all information in RAM but not save any changes.
¡ Tune Configuration allows changing input assignments.
¡ Change Configuration allows adding and removing blocks, purchasing blocks, and changing
the type of input.
3. Click OK.
Page 49 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Security-settin...g 9/26/03
Changing Passwords Page 1 of 2
Use the Set Security Passwords command to change the password of one or more security levels for any or
all connected controllers. You can change the password of your current security level or a lower security
level. You can also set the Exciter Name for the selected controllers. Controllers with the same Exciter Name
and passwords do not require you to enter the password each time you connect.
Note: Be careful when changing passwords because the old password cannot be recovered after you set a
new one. Also, passwords are not user-specific. The same password applies to all users of the security level:
Page 50 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Security-pass.w
.. 9/26/03
Setting Up Printing Page 1 of 1
Setting up Printing
You can print the contents of any of the ccTool windows. ccTool uses the standard Windows Print, Print
Preview, and Printer Setup commands. It also includes a Page Setup command that allows you to define the
page layout and scale for printing and, in case of the Diagram window, the size of the diagram.
This section explains how to use Page Setup command. The topics covered are:
After using Page Setup, use the Print Preview command before actually printing. Print Preview allows you to
verify that the print results will be as you expect.
Page 51 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Pages-SetupPr...i 9/26/03
Setting Up Pages in Diagram Page 1 of 1
Use the Page Setup command in the Diagram window to define any of the following:
l The diagram size. You may need to change the diagram size even if you do not plan on printing the
diagram. For example, when you make more blocks in a diagram visible, you may need to increase
the diagram size in order to have more space to place the blocks.
l The page size and orientation. You can also turn on the display of page breaks in the Diagram
window.
1. If you want to change the diagram size, display either the RAM or File configuration. The diagram size
is defined and saved by configuration type and cannot be directly edited for the Flash configuration.
(You can download to Flash to update the Flash diagram size).
Any changes you made to the Page Size, Diagram Size, or Print Scale settings are put into effect:
Notes:
l If you will be printing the diagram, it is typically most effective to use the Page Size option to define
the page size and turn on page breaks, and use the Diagram Size option to define the size as a
number of pages. This allows you to see how the diagram will be printed as you work with it.
l Depending on your printer, the page margins on the printed diagram may be slightly different than
page margins shown in ccTool. Do a print preview before printing to verify the page margins that will
be used on the printed pages.
l When you print, the entire diagram size is printed unless you set a print range in the Print dialog. If the
diagram size is much larger than the actual space used, blank pages will be printed. To avoid this,
you can use the Autosize or Minimum Size option in the Diagram Size tab.
Page 52 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/PagesDiagram.
... 9/26/03
Page Size Page 1 of 1
Page Size
This option assists in the layout of the diagram. Use it to define the size and orientation of the pages in the
diagram, and to turn on the display of page breaks in the Diagram window. The page size you define here is
used by the Pages option of the Diagram Size tab. It is not necessarily the page size that will be used by the
printer.
Changes you made to the Page Size settings apply to all configurations (File, RAM, and Flash). They remain
in effect for this ccTool session and, if you use the Save command, are saved for all configurations.
l To define the page size, choose a standard engineering drawing size from the drop-down list, or type
the Width and Height.
l To change the orientation of the page, select Portrait or Landscape.
l To display the page breaks in the Diagram window, check Show Page Breaks.
After you define the page size, you can click Diagram Size or Print Scale to change those settings, or can
click OK to end the Page Setup command.
Page 53 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/PagesDiagram...- 9/26/03
Diagram Size Page 1 of 1
Diagram Size
Use this option to change the size of the diagram for the RAM or File configuration. You can set the size to
be a number of pages or a defined height and width. Changing the diagram size does not change the
physical location of blocks on the diagram. Blocks remain in the same position relative to the upper left
corner of the diagram.
When you change the diagram size, the new size applies only to the current RAM or File configuration. The
new size is automatically saved when you change the RAM configuration. It is saved for the File
configuration if you save the configuration.
l Select the Pages option to define the diagram size as a number of pages. This option uses the page
size defined in the Page Size tab. You can type the number of pages across and down, or click
Autosize to set the size to the minimum number of pages required to accommodate all of the blocks
currently visible in the diagram.
l Select the Custom Size option to define the size by height and width. You can choose a standard
engineering drawing size from the drop-down list, type the size, or click Minimum Size to set the size
to the minimum size required to accommodate all of the blocks currently visible in the diagram.
After you define the diagram size, you can click Page Size or Print Scale to change those settings, or can
click OK to end the Page Setup command.
Page 54 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/PagesDiagram...- 9/26/03
Print Scale Page 1 of 1
Print Scale
Use the Print Scale option when you want to change the scale of the diagram for printing or print previewing.
The scale is changed only for printing; the actual document scale remains the same.
Changes you make to the Print Scale settings apply only to the active window. They remain in effect for the
window only during this session of ccTool.
l To scale the document up or down to fit on a certain number of printed pages, check Fit to Pages and
type the number of pages to print across and high. When Fit to Pages is checked, it uses the Scale
Percentage shown in the dialog as the maximum scale allowed. Therefore, if you are using Fit to
Pages to scale down the diagram, you can leave the Scale Percentage at 100% because scaling
down will result in a Scale Percentage of less than 100%. If you are using Fit to Pages to scale up a
document, you must increase the Scale Percentage shown in the dialog because Fit to Pages will
scale the document up to the highest possible scale for the number of pages without exceeding the
Scale Percentage shown in the dialog. For example, if you define the Scale Percentage as 200%, Fit
to Pages will scale the document up as high as possible to fit on the number of pages specified
without exceeding 200%.
l To scale a diagram up or down without specifying the number of printed pages, define a Scale
percentage and do not check Fit to Pages.
After you define the scale, you can click Page Size or Diagram Size to change those settings, or can click
OK to end the Page Setup command.
Page 55 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/PagesDiagram...- 9/26/03
Setting Up Pages in Grid Based Windows Page 1 of 2
Use the Page Setup command in any of the following ccTool windows to define the page layout and scale for
printing: Application Configuration, Execution Strategy, Mainline Execution, Memory, and Execution Time.
The Page Setup command is the same in all of these windows.
Changes you make to the default Page Setup settings apply only to the active window. The changes remain
in effect for the window only during this session of ccTool.
2. In the Header and Footer lists, you can define the header and footer that appear on each printed
page. You type text and/or formatting codes to define the content of the header and footer.
3. In the Margins panel, you can change the current page margins and the placement of the header and
footer.
4. In the Print Options panel, you can check the Black & White option to have the grid and text print in
black on a white background rather than printing in the colors shown in the window. None of the other
options are used. Grid lines are always printed even if not checked here, and columns and rows are
printed as they appear in the window.
l Top to Bottom (the default) prints all pages for the first set of columns that fit across a
page, then all pages for the next set of columns, etc.
l Left to Right prints all pages for the first set of rows that fit across a page, then all pages
for the next set of rows, etc.
Page 56 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/PagesGridWin
...s 9/26/03
Setting Up Pages in Grid Based Windows Page 2 of 2
6. In the Center panel, you can select one or both of the following options to center the document on the
page when the document does not extend to the full width or length of the page as defined by the
page margins:
l Center Horizontally is useful when the column breaks in the grid result in the document
not extending to the full-page width. It centers the document horizontally so that the left
and right margins increase to be equal size.
l Center Vertically is useful when the document is less than one full page length. It
centers the document vertically so that the top and bottom margins are equal size.
7. In the Scale panel, you can change the scale of the document for printing as follows:
l To scale the document up or down to fit on a certain number of printed pages, check Fit
to Pages and type the number of pages to print across and high. When Fit to Pages is
checked, it uses the Scale Percentage shown in the dialog as the maximum scale
allowed. Therefore, if you are using Fit to Pages to scale down the diagram, you can
leave the Scale Percentage at 100% because scaling down will result in a Scale
Percentage of less than 100%. If you are using Fit to Pages to scale up a document, you
must increase the Scale Percentage shown in the dialog because Fit to Pages will scale
the document up to the highest possible scale for the number of pages without
exceeding the Scale Percentage shown in the dialog. For example, if you define the
Scale Percentage as 200%, Fit to Pages will scale the document up as high as possible
to fit on the number of pages specified without exceeding 200%.
l To scale a document up or down without specifying the number of printed pages, define
a Scale percentage and do not check Fit to Pages.
8. When you are done defining the page setup, click OK.
Printing now uses the page setup you defined. Use Print Preview before printing to verify that the page
layout is as you expected.
Page 57 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/PagesGridWin
...s 9/26/03
Specifying Headers and Footers Page 1 of 1
You specify the header and footer in the Page Setup dialog by typing text and formatting codes. You can
enter the codes in upper or lower case.
Headers and footers are centered unless you specify &L or &R, and are in Courier font unless you specify a
different font name with the &"fontname" code. Some examples follow.
Page 58 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/PagesGridWin
...s 9/26/03
Using the Connection Bar Page 1 of 2
The Connection Bar is particularly useful when you are connected to multiple controllers. With a user
interface that is similar to the Windows Explorer, it presents a hierarchy of the controllers to which you are
connected, files you have open for offline editing, and the windows open for each controller and file. You can
use it to easily navigate between windows when you are connected to multiple controllers and/or have
multiple files open. The Connection Bar is updated automatically as you open or close controller
connections, files, or windows.
When you access ccTool, the Connection Bar appears automatically if it was displayed the last time you
used ccTool. The bar appears in the same place as last displayed.
1. If the Connection Bar is not displayed, click the Toggle Connection Bar icon in the toolbar .
The Connection Bar is displayed. For example, the content is as illustrated below if you
connected to the ECM and FICM controllers, bridge connected through FICM to Bridge 0, and
opened a configuration file named FV4YST16.ccf. The windows open for each connection and
file are listed under the connection or file. The active window is highlighted in the list.
2. You can:
3. To turn off display of the Connection Bar, click the Toggle Connection Bar icon in the toolbar .
Page 59 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Connection_W
... 9/26/03
Using the Connection Bar Page 2 of 2
You can also move or re-size the Connection Bar as described in the next topic.
Page 60 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Connection_W
... 9/26/03
Moving and Re-sizing the Connection Bar Page 1 of 1
The first time you display the Connection Bar, it appears docked to the left side of the main ccTool window.
Docked means that the window holds a fixed position on the left or right side of the main ccTool window.
1. Double-click the header of the Connection Bar to undock it. The window header turns blue to indicate
that the window is undocked.
2. You can now move or re-size the window as you would any other window. Specifically, to move the
window, position the cursor in the window header, and then hold down the left mouse button and drag
the window. To re-size the window, position the cursor over one of the window edges until the cursor
changes to a double-sided arrow, and then hold down the left mouse button and drag the window
edge.
3. To re-dock the window to the same side of the main ccTool window as it was previously docked,
double-click the window header. To dock it to the opposite side of the main ccTool window, move the
window until it is flush against that edge of the ccTool window.
Page 61 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Connection_W
... 9/26/03
Working with Alarms Page 1 of 1
The controller activates an alarm to alert you to a condition that requires your attention.
The topics in this section describe how to work with alarms. The topics are:
Page 62 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Alarms-Intro.h
...t 9/26/03
Setting the Auto-Refresh Preference Page 1 of 1
The Auto-Refresh preference for Alarms controls how often the controller checks for alarms in order to
refresh the Alarms icon and Alarms window. When the controller finds that an alarm has been activated
since the last auto-refresh interval, it refreshes the Alarms icon to show the flashing red border . If the
Alarms window is displayed, it also adds the alarm to the window.
The default auto-refresh interval for alarms is 5 seconds. To change the auto-refresh interval:
1. Click the Preferences icon in the toolbar, or choose Preferences from the File menu.
Note: Only uncheck Alarms for temporary situations such as communications being very slow
when you are using a remote connection. When Alarms is unchecked, you are not notified of
any new alarms.
4. Click OK.
Page 63 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Alarms-AutoR
...e 9/26/03
Acknowleding Alarms Page 1 of 2
Acknowledging Alarms
When an alarm goes off, the Alarms icon in the toolbar flashes with a red border . You then use the
Alarms command to acknowledge the alarm. Acknowledging an alarm just indicates that you have viewed
the message. The alarm continues to be listed in the Alarms window until it is cleared and removed.
After you acknowledge all alarms in the Alarms window, the Alarms icon border changes from flashing red to
flashing yellow . Flashing yellow indicates that all alarms have been acknowledged but are not yet
cleared and removed. If another alarm goes off, the icon border again flashes in red.
To acknowledge alarms:
1. In the toolbar, click the Alarms icon when it is flashes with a red border .
The Alarms window lists the alarms. The text "Alarm" in the column next to the alarm
description indicates that the alarm has not yet been acknowledged. For example, the following
window contains alarms that are activated if the FCIM loses communication with Bridge 0.
l If the alarms are grouped into categories by type, as in the illustration above, you can
acknowledge all alarms of one type. To do so, right-click on the row of one of the alarms
of the type, and then choose Acknowledge All Alarms of this Type from the shortcut
menu.
Page 64 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Alarms-Ackno
...w9/26/03
Acknowleding Alarms Page 2 of 2
When you acknowledge an alarm, the text "Acknowledged" replaces the text "Alarm" in the
column next to the Alarm description.
3. When you are done acknowledging alarms, you can do one of the following:
Page 65 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Alarms-Ackno
...w9/26/03
Clearing and Removing Alarms Page 1 of 1
After you acknowledge alarms in the Alarms window, you can clear or remove them from the Alarms window
as follows.
Clearing Alarms
Alarms are normally cleared automatically by the controller when the condition that caused the
alarm no longer exists. There may be alarms, however, that require that you clear the alarm.
You can manually clear a single alarm or all alarms of the same type:
l To clear a single alarm, right-click on the row of the alarm, and then choose Clear
Alarm from the shortcut menu. A dialog asks you to confirm clearing the alarm.
l If the alarms are grouped into categories by type, you can clear all alarms of one type.
To do so, right-click on the row of one of the alarms of the type, and then choose Clear
All Alarms of this Type from the shortcut menu. A dialog asks you to confirm clearing
the group of alarms.
When you clear an alarm, the text "Cleared" appears in the column next to the Acknowledged
column.
Removing Alarms
Alarms must be acknowledged and cleared before you can remove them from the Alarms
window. To remove them, click the Remove All Cleared, Acknowledged Alarms button. The
alarms are removed from the window.
Page 66 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Alarms-Cleari...n 9/26/03
Other Commands in the Alarms Window Page 1 of 1
In addition to the commands used to acknowledge alarms, and clear and remove them, the Alarms window
contains the following commands.
Refresh
Click the Refresh button in the Alarms window to update the window with all alarms that have
been activated since the last auto-refresh.
The controller writes a log of all alarms. This is particularly useful because there may be alarms
that go off and are cleared so quickly that ccTool never detects the alarm. To view the alarm
history, click the Upload to Database button in the Alarms window. If you previously uploaded
the history, the command uploads only the new information to ensure that there are no
duplicates in the database.
The Clear History command clears the controller log; it does not clear the database if you
uploaded the log to a database. Be sure to upload the history to a database before using this
command to ensure that the information is not lost.
You can list the description of all alarms for the controller in the Alarms window. To do so,
check Show All Alarms. Uncheck Show All Alarms to return to the standard Alarms window
display.
Page 67 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Alarms-Other....h 9/26/03
Working with Events and Data Loggers Page 1 of 1
The topics in this section describe how to work with Data Loggers and Event Recorders.
Page 68 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Graph_overvie
...w9/26/03
What are Data Loggers and Event Recorders? Page 1 of 1
You setup a Data Logger when you need to monitor specific outputs. A Data Logger is a special function
block that takes samples of data. You specify the inputs to this block as the outputs from other blocks that
you want to monitor. You also specify the time interval at which you want the Data Logger to sample the
data. Once a Data Logger is setup and put into execution, it is always recording data. You choose when to
upload and view the data.
Note: The Data Logger writes the sampled data to a buffer. When the buffer is full, the Data
Logger begins to overwrite the existing data from the top of the buffer. You can look at the
Total Size and Data Size columns in the View Events and Data Loggers command to
determine whether the buffer is full. To clear the buffer, you can set the state from Executing to
Resolved, and then back to Executing. The buffer is cleared when the state changes to
Executing or when you change an input while in the Executing state. Before clearing the buffer,
use the Events and Data Loggers command to upload the data to the PC.
You setup an Event Recorder when you want to capture the data related to a single event. An Event
Recorder is a special function block that records the output values related to an event. You specify the inputs
to this block as the trigger that sets off the event and the outputs that you want to record. You enable the
Event Recorder when you want the controller to start monitoring for an occurrence of the trigger. When the
trigger occurs, the Event Recorder records the event and automatically displays a dialog in ccTool to allow
you to upload and view the data at that point. (The Event Recorder does not have any of the buffer overwrite
concerns that were noted above for the Data Logger).
There are two types of triggers: LOGIC and FLOAT. For the LOGIC type, you define whether a TRUE or
FALSE value for a specific output triggers the event. For the FLOAT type, the event is triggered if the value
of a specific output falls outside a minimum and maximum value that you define. The Event Recorder saves
both pre-trigger and post-trigger data. You specify a time interval for sampling the data and how many
samples you want taken at each interval for pre-trigger and total samples.
Page 69 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Graph-WhatA...r 9/26/03
Positioning Channels Page 1 of 2
You view Data Loggers and Event Recorders in a Graph window. You can set the default display
characteristics for this window using the Preferences command. The Preferences command also includes a
feature named Changes in graph window are saved in preferences. This feature is an efficient way to set
preferences when you are not yet familiar with all of the graph display options, or want to refine settings in
the Graph window before saving them as your preferences. When this feature is checked, the last graph
display settings you define in a Graph window before closing it are saved as your preferences.
Note: Changes you make in Preferences apply only to subsequent Graph windows that you open. Choose
the command before opening any Graph windows if you want changes to apply to those windows.
1. Click the Preferences icon in the toolbar, or choose Preferences from the File menu.
3. For all of the options except Default Wave Height and Default Vertical Scale:
l Change the default settings shown in the dialog as needed. For an explanation of each
option, see Setting Graph Display Options.
l Check Changes in graph window are saved in preferences to update your
preferences automatically with changes to the settings that you make using the related
commands in the Graph window.
4. Change the Default Wave Height and Default Vertical Scale as needed:
The Default Wave Height defines the default height for the waves in the channels, in pixels. It is used
by the Default Vertical Scale settings to determine how to display the channels by default. The two
options for setting vertical scale are:
Page 70 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Graph_Prefere
...n 9/26/03
Positioning Channels Page 2 of 2
These preferences do not have direct command equivalents in the Graph window. You set the
defaults in the Preferences command for all channels. In the Graph window, you adjust the default
vertical scale as needed for individual channels.
Your preferences are set. They will be used the next time you open a Graph window.
Page 71 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Graph_Prefere
...n 9/26/03
Uploading the Data Page 1 of 2
You upload the data recorded by an Event Recorder or a Data Logger in order to view the data or save it in a
file.
1. For an Event Recorder, the View Events and Data Loggers dialog displays automatically when the
event occurs. For a Data Logger or a previously recorded (and not yet reset) Event Recorder, choose
Events and Data Loggers from the View menu to display the dialog.
The dialog displays the following information for each Event Recorder or Data Logger:
Getting Data means the controller Getting Data means the controller
is in the process of collecting data. is in the process of collecting data.
You must cancel from this You must cancel from this command
command and wait until the data is and wait until the data is collected
collected before proceeding. before proceeding.
2. Select the Data Logger or Event Recorder for which you want to upload data, and then click Get Data.
The following illustration assumes you selected the DATA_LOGGER block. The options in the
dialog are the same for all Data Loggers and Event Recorders.
Page 72 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Graph-Upload.
... 9/26/03
Uploading the Data Page 2 of 2
Page 73 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Graph-Upload.
... 9/26/03
Using the Graph Window Page 1 of 1
The Graph window is displayed after you choose the view option in the View Events and Data Loggers
command, and after you open a previously saved file using the Open Event Graph or Import Graph Data
command. The topics in this section describe how to use the window.
l Window Basics
l Setting and Moving the Cursors
l Setting Channel Properties
l Managing the Display
Page 74 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Graph-UsingG
...r 9/26/03
Window Basics Page 1 of 3
Window Basics
The Graph window is modeled on an oscilloscope. It presents a graph of the data recorded by a Data Logger
or Event Recorder and allows you to compare and analyze the data as you would on a physical oscilloscope.
The window is the same for a Data Logger or Event Recorder, except that a few additional options are
available for an Event Recorder.
The graph charts the recorded data as a function of time, where the x-axis represents time and the y-axis
represents the data values. Each output being monitored appears as a channel on the graph. You set and
move two graph cursors to view and compare values.
You can display the name of each channel or, as illustrated above, only the number of the channel. An arrow
along the left of the graph shows the zero point of each channel. If the zero point is not currently displayed,
the arrow points up or down towards the zero point.
You can dynamically set and move the graph cursors and channels, as well as control the graph display
using commands in the window and in the menus.
Note: This documentation uses the term graph cursor to refer to the cursors you set in the graph, and the
term mouse cursor to refer to the cursor you move on the screen as you move the mouse.
Above the graph is a dashed line that represents an overview of the data. The dashed line represents all of
the data in the graph, and the symbols on it represent the position of the Graph window, graph cursors, and
(for the Event Recorder) the trigger point within all of the data. You cannot interact in the Overview.
Page 75 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Graph-Basics....h 9/26/03
Window Basics Page 2 of 3
Cursors Panel
The top right section of the window displays the Cursors panel.
You can set the graph cursors by selecting the channels from these drop-down lists. You can set the channel
properties by clicking the button next to the drop-down list. As you set and move the graph cursors, the
X, Y, dX, and dY values are displayed here.
The middle right section of the window contains the following controls:
You can set the vertical scale and/or position of a channel, or the horizontal scale of all channels.
Channel List
The lower right section of the window lists the channels and their current vertical scale. A checkmark next to
a channel indicates that the channel is currently displayed in the graph.
Page 76 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Graph-Basics....h 9/26/03
Window Basics Page 3 of 3
l Uncheck a channel to turn off its display in the graph, or check it to turn on its display.
l Click a channel to select it. You select a channel in order to set its vertical scale or position. You can
only select a channel that has a checkmark.
l Double-click a channel to set its properties.
Page 77 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Graph-Basics....h 9/26/03
Setting and Moving the Cursors Page 1 of 1
When the Graph window is first displayed, the two graph cursors are not displayed. You set the channels for
the graph cursors to initially position them. You can then move the cursors along the same channels or move
them to different channels as needed to view and compare data.
Before setting or moving the graph cursors, check Snap to Data Points in the Cursors menu if you want the
cursors to snap to the closest data point as you set and move them.
To initially set the channel for a graph cursor or later set a different channel, you can either:
l Select the channel from the CURSOR 1 or CURSOR 2 Channel drop-down list in the top right of the
window.
If the graph cursor was not previously set, it is placed at the zero point location of the channel
you selected. If the graph cursor was previously set on a different channel, it is moved to the
selected channel at the same X-axis location.
l Use the shortcut menu to define the channel and location for the graph cursor. To do this:
1. Position the mouse cursor on the channel at the location you want to place the graph
cursor.
2. When the mouse cursor changes to , right-click to display the shortcut menu.
3. Choose the Set Cursor 1 or Set Cursor 2 command.
The graph cursor is set on the channel, and positioned at the location you right-clicked.
Note: The shortcut menu only contains the Set Cursor commands if you right-click while the
mouse cursor is the cursor. A right-click while the mouse cursor is still the cursor
displays the shortcut menu but the menu does not contain the Set Cursors command.
After you initially set the channel for a graph cursor, you also can dynamically move the cursor to a different
channel. To do this, position the mouse cursor directly over the of the graph cursor, and then drag the to
the desired channel. x x
To move a graph cursor to a different position on the current channel, you can:
l Dynamically move the graph cursor along the channel. To do this, position the mouse cursor
anywhere along the vertical line that runs though the graph cursor, and then drag the vertical line.
l Use the shortcut menu to define a new position on the channel. To do this, right-click at the location
you want to position the graph cursor (you do not have to right-click directly over the channel), and
then choose Position Cursor 1 or Position Cursor 2 from the shortcut menu.
l Position the graph cursor at the center of the window. To do this, choose Position Cursor 1 or Position
Cursor 2 from the Cursors menu.
Page 78 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Graph-SetCurs
... 9/26/03
Setting Channel Properties Page 1 of 1
As you work with channels in the graph, you may want to change their vertical scale, re-position them, make
some channels invisible, or change the color or name of the channel. A channel's vertical scale, position,
visibility, color, and name are called the channel properties. There are a number of ways you can change the
channel properties:
l You can dynamically change the position of a channel in the graph by dragging the channel in the
graph.
l You can check or uncheck the first column in the Channel List to set a channel's visibility.
l You can use the Channel Properties command to change any of the properties of a channel.
l You can select a channel, and then change its position or scale.
Page 79 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Graph_SetCha
...n 9/26/03
Using the Channel Properties Command Page 1 of 1
You use the Channel Properties command to change a channel's color, visibility, scale, and/or position
l The Channel Name controls the name shown in the Channel List and graph. The
default channel name is the name of the output. To change the channel name, type a
new name.
l Color controls the color of the channel in the graph and Channel List. To change the
channel color, click the color button and then choose a new color.
l Visibility controls whether the channel is displayed in the graph. Check this option to
display the channel in the graph, or uncheck it to turn off display of the channel in the
graph.
l Vertical Scale is the number of counts per grid division. The default scale is determined
by your preferences. To change the vertical scale, select or type a new scale in the
drop-down list. If you type a scale that is out of range for the sample of data, an error
dialog displays the valid range.
l Vertical Position is the distance from the top of the graph, in pixels, of the zero point of
the channel. To change the position of the channel in the graph, type a new distance in
pixels.
The Graph window is updated to show the changes you made to the channel properties.
Page 80 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Graph-UseCha
...n 9/26/03
Changing the Scale or Position of the Selected Channel Page 1 of 1
You can select a channel and then change its vertical scale and/or position in the graph. This method of
changing a channel's position is particularly useful when you want to align the zero points of two channels.
Rather than dynamically aligning the two channels in the graph, you can select and then type the same zero
point location for each channel.
The current vertical scale and position of the selected channel appear in the Selected Channel
area of the window.
The vertical scale is the number of counts per grid division. The position is the distance from
the top of the graph, in pixels, of the zero point of the selected channel.
2. To change the vertical scale, select or type a new scale in the drop-down list. If you type a scale that
is out of range for the sample of data, an error dialog displays the valid range.
3. To change the position, type a new value in the Position box to move the zero point to that position, or
click the arrows next to the box to move the channel up or down one pixel at a time.
Page 81 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Graph-VerSca...l 9/26/03
Managing the Display Page 1 of 1
The topics in this section describe how to manage the display in the Graph window.
Page 82 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Graph-Manag...e 9/26/03
Scrolling the Graph Page 1 of 1
You can scroll the graph dynamically using the scroll bars, or you can use the following commands:
l Go to Cursor 1 scrolls the graph to display graph cursor 1 in the center of the window.
l Go to Cursor 2 scrolls the graph to display graph cursor 2 in the center of the window.
l (For Event Recorders only) Go to Trigger Pt scrolls the graph to display the trigger point in the center
of the window.
You can choose these commands from the Cursors menu or the shortcut menu.
Page 83 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Graph_Scroll....h 9/26/03
Setting Horizontal Scale Page 1 of 1
The horizontal scale of the graph is the time interval per grid division. You use the controls in the middle right
area of the Graph window to change the horizontal scale.
You can select a new horizontal scale value from the drop-down list, or you can click AutoFit to set the
horizontal scale so that the entire width of the drawing is displayed in the window.
Page 84 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Graph-HorSca...l 9/26/03
Setting Display Options Page 1 of 2
You can set general graph display options using commands in the View, Cursors, and Grid menus. The
options you can set are described below. You set the defaults for these options using the Preferences
command. The options are listed here in the order that they appear in the Preferences command, in order to
allow you to reference this section as you use the Preferences command to define the defaults for these
options.
Note: Of the display options described here, only TINT time is saved with the file. If you
change any other settings, the change applies only to the current window.
The graph display options that you can set in the View, Cursors, and Grid menus are:
l None displays only the data points (and automatically checks the Display Data Points option):
Page 85 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Graph-SetOpti
...o 9/26/03
Setting Display Options Page 2 of 2
Page 86 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Graph-SetOpti
...o 9/26/03
Changing the Graph Height Page 1 of 1
You may need to increase or decrease the height of the graph as you change the vertical scale of channels,
make them visible or invisible, and/or move them around on the graph. For example, if you increase the
wave height of channels by changing their vertical scale, the channels may overlap. You may need to
increase the graph size in order to have enough room to re-position the channels so that they no longer
overlap.
The Grid Height determines the height of the graph. Space is added or removed from the bottom of the
graph as you increase or decrease the grid height. The height is defined in pixels.
2. Type a height for the grid in pixels, and then choose OK.
The height of the grid/graph is adjusted to add or remove space from the bottom of the graph.
Page 87 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/Graph-Chang...
eH 9/26/03
Assign Block Input Page 1 of 2
You can assign or change the input values of block inputs that are displayed in the Diagram or Application
Configuration window. In the File Configuration, you can assign unassigned values, change existing values,
and/or change the assignment type. In the RAM configuration, you can change existing values but not
change the assignment type unless the Controller is in the Resolve State or a lower state.
1. Display the input you want to assign in the Diagram or Application Configuration window.
2. Choose the Assign Block Input command as follows:
l In the Diagram Window, right-click the input in the diagram, and then choose
Assignment from the shortcut menu.
l In the Application Configuration window, double-click the input in the table. You can also
right-click the input, and then choose either File Assignment or RAM Assignment from
the shortcut menu.
The Assign Block Input dialog appears for the input you specified. For example, the following
illustration assumes you specified the DA1_PAGE input of the DA1 block in the File
Configuration.
In this dialog:
l The From Output and Constant radio buttons are only active if you are editing the File
Configuration. In the File Configuration, you can use these buttons to change the
assignment type. In the RAM Configuration, you cannot change the assignment type
unless the Controller is in the Resolve State or a lower state.
l For a Constant value, the Eng Units radio button is only active if Engineering Units are
defined for this input.
l The Update RAM Values checkbox is only active if you are editing the RAM
Configuration in the Executing State. When Update RAM Values is checked, all RAM
values are read in order to update any changes that may propagated through the
system. When Update RAM Values is unchecked, the input you edit is updated
immediately but any affected values are not updated until the next auto-refresh interval.
You are given the choice of whether or not to update values immediately because
updating them immediately may take some time if you have a large configuration and/or
Page 88 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/H-AssignInput
.... 9/26/03
Assign Block Input Page 2 of 2
a slow connection.
l To change the assignment type in the File Configuration, click the Constant or From
Output radio button.
l For a Constant value, type a value and click the radio button that identifies the type of
value as Decimal, Hexadecimal, etc.
l For a From Output value, select the block and output from the drop-down lists.
4. If you are editing the RAM Configuration in the Executing State and want to update all affected RAM
values immediately, check Update RAM Values.
5. Click OK.
If there are any potential problems with this assignment, a confirmation dialog asks you to
verify making the assignment. Click Yes to continue, or No to return to the Assign Block Input
dialog.
Tip In the Diagram window, you can also assign input by drawing a connection.
Related Topics:
l Configure Block
Page 89 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/H-AssignInput
.... 9/26/03
Open Configuration Page 1 of 1
Open Configuration
To do so:
ccTool displays the standard Open dialog. The Look In folder is set to the folder you defined
for Configuration Files in your Directory Preferences. Files of Types is set to Configuration
Files (ccf).
ccTool opens the selected configuration file and displays it in the windows you defined as your Initial
Windows in your General Preferences.
Tips
l To open a file that you have used recently, choose the filename from the list at the bottom of the File
menu.
l You also can use this command to open Event Recorder or Data Logger files. To do so, change the
Look In folder to the folder than contains the file, and change the Files of Type to either Event
Recorder Files or Data Logger Files. The Event Recorder or Data Logger file will be opened in the
Graph window.
Related Topics:
Page 90 of 90
mk:@MSITStore:C:\Program%20Files\Cutler-Hammer\ccTool\ToolHelp.chm::/HF-OpenConfi
... 9/26/03
PanelMate Power Series
Online Operation
User’s Guide
&XWOHU+DPPHU
173 Heatherdown Drive
Westerville, OH 43086-6166
The information contained in this manual is the property of Cutler-Hammer, Inc. Information in this
manual is subject to change without notice and does not represent a commitment on the part of
Cutler-Hammer, Inc.
Any Cutler-Hammer software described in this manual is furnished under a license agreement. The
software may be used or copied only in accordance with the terms of the agreement. It is against the
law to copy the software on any medium except as specifically allowed in the agreement. No part of
this manual may be reproduced or transmitted in any form or by any means, electronic, mechanical,
photocopying, recording or otherwise, without prior written permission of Cutler-Hammer, Inc.
TRADEMARKS
AcceleratI/On is a trademark of Cutler-Hammer, Inc.
TouchPanel is a trademark of Cutler-Hammer, Inc.
PowerBlink is a trademark of Cutler-Hammer, Inc.
PowerAnimation is a trademark of Cutler-Hammer, Inc.
PowerGraphics is a trademark of Cutler-Hammer, Inc.
PanelMate is a registered trademark of Cutler-Hammer, Inc.
Microsoft and Windows are registered trademarks of Microsoft Corporation.
Modbus is a trademark of Schneider Automation Inc.
Remote I/O, DH-485, Data Highway, and Data Highway Plus are trademarks of Allen-Bradley
Company, Inc.
GEnius I/O is a trademark of GE Fanuc Automation North America, Inc.
DCS-NET is a trademark of Reliance Electric Company.
Commercial names of products from other manufacturers or developers that appear in this manual are
registered or unregistered trademarks of those respective manufacturers or developers, which have
expressed neither approval nor disapproval of Cutler-Hammer products.
P/N 01-00394-00
Table of Contents i
Table of Contents
Preface ..............................................................................................................................................I
About This Manual.....................................................................................................................II
Purpose ...................................................................................................................................II
What’s Inside..........................................................................................................................II
Support Services....................................................................................................................... III
Chapter 1: Power-Up Sequence ...................................................................................................... 1
Power-Up Sequence.................................................................................................................... 2
Execute Normal Power-Up Diagnostics ................................................................................... 2
Determine if the Unit Should Enter the Transfer Mode ........................................................... 3
Check for Executive Firmware ................................................................................................ 3
Check User Configuration Compatibility with Executive Firmware ......................................... 3
Check for Presence of Installed Drivers ................................................................................... 4
Determine Power-Up Mode ..................................................................................................... 4
Run Mode Operation............................................................................................................... 6
Chapter 2: Online Page Layout ...................................................................................................... 7
Online Page Layout .................................................................................................................... 8
Page Number and Page Title ................................................................................................... 9
Pages In Alarm ....................................................................................................................... 9
Alarm Window ....................................................................................................................... 9
Refresh Graphics ........................................................................................................................ 9
Conditional Visibility ............................................................................................................... 10
Default Control Buttons............................................................................................................ 11
Get Page ............................................................................................................................... 13
PLC Page Selection ............................................................................................................... 13
Host Display Window............................................................................................................ 13
Directory............................................................................................................................... 14
Chapter 3: Operator Input............................................................................................................ 15
Operator Input .......................................................................................................................... 16
One-Touch Selection of Variable-Sized Templates ................................................................ 16
Two-Touch Selection of Variable-Sized Templates................................................................ 16
Selecting a Template............................................................................................................. 16
Control Button Operation...................................................................................................... 16
Chapter 4: Alarms......................................................................................................................... 19
Alarms ..................................................................................................................................... 20
Alarm Summary Page ........................................................................................................... 21
View or Acknowledge Alarms............................................................................................... 21
Chapter 5: Password Protection.................................................................................................... 23
Password Protection.................................................................................................................. 24
Lost Password Recovery........................................................................................................ 25
ii Online Operation User’s Guide
Preface
Welcome to Cutler-Hammer’s Online Operation User’s Guide. This chapter describes the contents of
this manual and provides information on Support Services.
II Online Operation User’s Guide
Purpose
This manual focuses on describing the features of the PanelMate Power Series unit when in Run
Mode.
What’s Inside
This manual is organized in the following way:
Preface
Chapter 1: Power-Up Sequence
Chapter 2: Online Page Layout
Chapter 3: Operator Input
Chapter 4: Alarms
Chapter 5: Password Protection
Chapter 6: Setup Page
Chapter 7: Fault Relay
Chapter 8: Maintenance Template
Chapter 9: Errors
Appendix A: Online Problems
Appendix B: Momentary Pushbutton Operation
Preface III
Support Services
It is Cutler-Hammer’s goal to ensure your greatest possible satisfaction with the operation of our
products. We are dedicated to providing fast, friendly, and accurate assistance. That is why we offer
you so many ways to get the support you need. Whether it’s by phone, fax, modem, or mail, you can
access Cutler-Hammer support information 24 hours a day, seven days a week. Our wide range of
services include:
Power-Up Sequence
1
In this chapter, you will learn:
• The sequence of events during power-up
2 Online Operation User’s Guide
Power-Up Sequence
On power-up, the PanelMate unit performs the following sequence of operations:
• Execute normal power-up diagnostics
• Determine if the unit should enter the Transfer Mode
• Check for Executive Firmware
• Check User Configuration compatibility with Executive Firmware
• Check for presence of installed drivers
• Determine Power-up Mode
Recovery Mode
In the unlikely event of the Executive Firmware getting corrupted in the PanelMate unit, the
PanelMate unit will power up to the Recovery Mode.
Recovery Mode is indicated by the Recover Mode prompt located in the lower right corner of the
screen. During normal operation, the Recovery Mode prompt is replaced by the Serial Mode prompt
or the Network Mode prompt.
You must re-download your executive firmware to resume operating.
Alternate Mode
Alternate Mode is feature that allows you to load two small configurations in the PanelMate unit and
toggle between the two configurations. If you enter Alternate Mode, a banner will appear on the
screen to state that you are in Alternate Mode and then the Alternate Offline Mode screen will be
displayed. Once in Alternate Mode, the PanelMate unit will stay in Alternate Mode until power is
cycled. Once power is cycled, the PanelMate unit will return to the operating mode it was in before
the unit entered the Alternate Mode.
Offline Mode
Initialization to the Offline Mode will display a screen which allows the following selections: Execute
Diagnostics, Enter Serial Transfer Mode, Enter Network Transfer Mode, Display
System/Configuration Information, Enter Run Mode, and Calibrate Touchscreen. The diagnostic tests
and calibration are explained in the Execute Diagnostics section in the PanelMate Power Series
Hardware Installation Guide. Refer to the PanelMate Transfer topic for more information on serial
transfer and network transfer modes.
Chapter 1: Power-Up Sequence 5
Run Mode
The following message will be displayed:
Please wait .... entering Run Mode
At this point in the initialization, the integrity of the Executive Firmware and integrity of the User
Configuration have been verified. The proper driver is also known to be installed. The PanelMate unit
will display the Loading Status Screen while performing the initialization procedure outlined below.
The time to complete the initialization depends upon the complexity of the configuration. The
complexity of the user configuration is determined by the density of the pages, number of alarm
conditions, and the number of control bits which must be initialized in the PLC(s).
The Loading Status Screen displays the name, date, and time of the configuration being loaded, the
component that is currently being loaded, the percentage of the configuration that has been loaded,
and the percentage of the usable free memory remaining (based on the largest contiguous block).
2
In this chapter, you will learn:
• About the online page layout
• How to refresh graphics
• What is conditional visibility
• The different default control buttons
8 Online Operation User’s Guide
Pages In Alarm
The second line will show only the pages in alarm. The PanelMate unit will use the First-In-First-Out
(FIFO) method to show only the most recent 10 pages in alarm. If no pages are in alarm, then no
page numbers will be displayed.
Alarm Window
This area will show the alarms you have received. The Alarm Window will display 4 alarms. If there
are more than 4 alarms, the PanelMate unit will use the First-In-First-Out (FIFO) method to show
only the latest alarms received. If there are no alarms, then the Alarm Window will be blank.
Note that if you have a touchscreen unit, control buttons will be displayed as boxes instead of arrows.
Refresh Graphics
To refresh templates, variable-sized templates, and graphics that appear on the online PanelMate unit
screen, the Refresh Affected Graphics Online field must be selected for the item you are configuring.
When the Refresh Affected Graphics Online field is selected, templates, variable-sized templates, and
graphics that lie within the area of the item being updated will be refreshed to properly reflect the
layering of objects on the page when the item is updated.
For example, the following template and object are displayed on the online PanelMate unit screen.
If the Readout Template is updated and the Refresh Affected Graphic Online field is not selected, the
screen will appear as shown below.
10 Online Operation User’s Guide
If the Readout Template is updated and the Refresh Affected Graphic Online field is selected, the
screen will appear as shown below.
Conditional Visibility
All templates, variable-sized templates, symbols, and text objects can be visible at all times or only
visible based on a condition. When creating a template, variable-sized template, symbol, or text
object, you have the following options:
• If the Enable Conditional Visibility field is not selected for the template, variable-sized template,
symbol, or text object you are configuring, the item will be visible at all times and all updating of
the item will be activated when in Run Mode.
• If the Enable Conditional Visibility field is selected and the Visibility Expression evaluates to be
true for the template, variable-sized template, symbol, or text object you are configuring, the item
will be displayed and all updating of the item will be activated when in Run Mode.
• If the Enable Conditional Visibility field is selected and the Visibility Expression evaluates to be
false for the template, variable-sized template, symbol, or text object you are configuring, the
item will not be displayed and all updating of the item will be deactivated when in Run Mode.
When templates, variable-sized templates, symbols, or text objects are activated or deactivated as a
result of the Visibility Expression changing, the item is drawn or erased accordingly. If you want the
layering of objects to be maintained, you must select the Refresh Affected Graphics Online field for
the item you are configuring. Refer to the Refresh Graphics topic for more information.
Note the following Conditional Visibility items:
• It is not recommended to use the Conditional Visibility feature on a Variable-Sized Control
Button on a PanelMate touchpanel unit.
• It is not recommended to use the Conditional Visibility feature on a Variable-Sized Control
Button on a PanelMate touchscreen unit or PanelMate PC unit that does not have the Direct
Select field enabled on the System Parameters – General Tab dialog box.
Chapter 2: Online Page Layout 11
The Silence Alarm Horn control button will always appear even if there are not any alarms.
Refer to the Fault Relay topic for more information about the fault relay. Note that the Enable Fault
Relay control button only appears for communications errors and alarms.
Refer to the View or Acknowledge Alarms topic for more information about viewing or
acknowledging alarms.
Refer to the Get Page topic for more information about getting a page.
Note that the default control buttons displayed on a PanelMate Power Series 1500 unit are Reset PLC
Comm, View or Acknowledge Alarms, and Get Page control buttons. The Enable Fault Relay control
button will be replaced by the Reset PLC Comm control button because the PanelMate Power Series
1500 does not support an external Fault Relay.
When you press the Get Page control button on a touchpanel unit, the following control buttons will
appear.
12 Online Operation User’s Guide
Refer to the Alarm Summary Page topic for more information about the getting the alarm page.
Refer to the Directory topic for more information about the directory.
When you press the Get Page control button on a touchscreen unit, one of the following touchscreen
keypads will appear to allow numeric entries.
Press the Switch to Two Column Keypad template or the Switch to Three Column Keypad
template on the Setup Page to switch between keypads. Refer to the Switch to Two Column Keypad or
Switch to Three Column Keypad section in the Setup Page topic for more information.
Press the More Buttons control button and the following control buttons will appear.
Refer to the Maintenance Template topic for more information about the Maintenance Template.
Note that the Maintenance Template control button only appears if a Maintenance Template is
allowed on the page.
Chapter 2: Online Page Layout 13
Refer to the Change Online Labels topic for more information about the System Online Labels. Note
that the Change Online Labels control button only appears if any of the system online labels have
been changed and the user can toggle between the standard and user-defined labels.
Refer to the Host Display Window topic for more information about the Host Display Window. Note
that the Host Display Window control button only appears if selected in the System Parameters -
General Tab dialog box.
Refer to the Setup Page topic for more information about the Setup Page.
Get Page
The first page to appear when entering Run Mode will be Page 0, unless you have defined a different
start-up page when editing the Startup Page Number field in the Systems Parameters - General Tab
dialog box. From the default control button selections, select any other page by performing the
following tasks:
1. Press the Get Page control button. The control button labels will change. Press the Directory
control button to access a page title directory.
2. On the numeric keypad, press the number of the page you wish to select. (Note that if you are
entering a single-digit page number, the number must be preceded by a zero, e.g., 01.) The new
page will appear immediately. If you press the number for the page you are already on, the page
is not re-drawn. Press the CANCEL key to remain on the current page and return the control
buttons to their default labels.
Directory
A directory of the page titles is automatically created by the PanelMate unit as you configure your
system. If you need to refer to this list of page titles while in Run Mode, press the Get Page control
button from the default control button selections. The control button labels will immediately change.
Press Directory control button to view the directory.
To exit from the directory, press any page number or the CANCEL key.
Some online units may have up to 100 pages available for configuration.
Chapter 3: Operator Input 15
Operator Input
3
In this chapter, you will learn:
• The options for operator input
16 Online Operation User’s Guide
Operator Input
Operator input may be one-touch (optional) or two-touch depending upon your equipment and your
configuration.
Selecting a Template
Before any change can be made to a template, that template must be selected. To select a template,
press the TouchPanel to move the white box cursor to the location of the template on the screen.
If the template requires control button input, the corresponding control button labels appear when the
template is selected. Press the appropriate control button.
If the wrong template is selected before the control button is pressed, simply use the selection keypad
to make the right choice. If no selection is wanted, press the CANCEL key.
When the control button is pressed, the PanelMate unit sends the appropriate command to the PLC or
changes the page.
If a template requires numeric keypad input, the Change Value control button will appear when the
template is selected. The control button labels will immediately change to read Clear and Enter New
Value. Use the numeric keys to write the value onto the screen, then press the Enter New Value
control button to transmit the value to the PLC. If the wrong number is written before the control
button is pressed, simply press the Clear control button and try again. If no selection is wanted, press
the CANCEL key.
When variable-sized templates or graphics are used, a given template cell area may contain more than
one control point. When the membrane is initially touched, the first control point that lies within the
indicated template cell area is selected, and is identified by its flashing control indicator. If this is not
the desired control point, a subsequent pressing of the same membrane will step to the next variable-
sized template in a top-to-bottom, left-to-right search pattern within the cell area. The selection
process will cycle and recycle through all the variable-sized templates with controls lying within the
selected cell area.
18 Online Operation User’s Guide
Chapter 4: Alarms 19
Alarms
4
In this chapter you will learn:
• The features of an alarm
• About the Alarm Summary Page
• How to view or acknowledge alarms
20 Online Operation User’s Guide
Alarms
The alarm conditions that you designate in the PanelMate unit’s template editors are constantly
monitored. When an alarm condition occurs, an alarm message is automatically configured by the
PanelMate unit and printed in the 4-line alarm window. The same message will also go to a printer if
you have configured a printer in the PLC Name and Port Table dialog box.
Alarm conditions can be selected for audible alarming. The Alarm Horn can be silenced two different
ways. The Alarm Horn can be silenced by pressing the Silence Alarm Horn control button from the
default control button selection. The Alarm Horn can also be silenced remotely by setting a bit in the
PLC. See Systems Parameters - Remote Tab topic in the Configuration Editor’s User Guide for
more information on configuring the Remote Silence Alarm Bit. The PanelMate unit can also set a bit
in the PLC when the Silence Alarm Horn control button is pressed. This can allow one operator to
silence all Alarm Horns on all the PanelMate units on a network.
The alarm message always includes:
• the device name or alarm device name
• the nature of the alarm (high alarm, low alarm, or the alarm condition label)
• the time of the event being reported
• the page the device is displayed on in the PanelMate unit
Additionally, the following attributes also apply to alarm messages, depending on the condition being
reported:
New alarms If you have a grayscale PanelMate unit, the alarms are displayed as
no intensity text on high intensity background. If you have a color
PanelMate unit, the alarms are displayed as white text on a red
background.
Acknowledged If you have a grayscale PanelMate unit, the alarms are displayed as
no intensity text on a medium intensity background. If you have a
color PanelMate unit, the alarms are displayed as yellow text on a
black background. The abbreviation “Ackd” will appear in the
message in front of the time.
Cleared, not acknowledged If you have a grayscale PanelMate unit, the alarms are displayed as
high intensity text on a no intensity background. If you have a color
PanelMate unit, the alarms are displayed as red text on a white
background. The abbreviation “Clrd” will appear in the message in
front of the time.
Cleared and Acknowledged The message will disappear from the screen. The message that gets
sent to the printer will include the abbreviation “Clrd” in front of the
time.
The four most recent alarm messages appear in the alarm window of the current page.
Chapter 4: Alarms 21
Password Protection
5
In this chapter you will learn:
• About password protection
24 Online Operation User’s Guide
Password Protection
Passwords can be used to restrict access to certain functionality when the PanelMate unit is in the
Run Mode. The PanelMate unit supports multiple levels of password protection. A great deal of
flexibility is provided so it is important to define an implementation scheme before configuring your
passwords. There are three levels of protection: Password A, Password B, and the Keyswitch.
Passwords A and B are configured in the System Parameters - Password Tab dialog box.
(Passwords can be enabled or disabled to permit or prohibit change during online operation.) A
security keyswitch can be attached to a removable terminal block to provide another level of
protection.
Although you may enter a password of up to 8 characters in the System Parameters – Password Tab
dialog box, the allowable range for passwords in Run Mode is 0 to 65535.
PanelMate Power Series 1500 does not support the security keyswitch.
Note that leading zeroes are not supported when configuring Password A and Password B in the
System Parameters - Password Tab dialog box.
Passwords can be used in the following areas in the Run Mode and must be enabled for entry each
time they are selected.
Templates with Numeric Entry selected:
Readout Template
Variable-Sized Readout Template
Bar Template
Variable-Sized Bar Template
Table Template
Enter Offline Mode
Maintenance Template
Set Date and Time
The following combinations of Password Protection are available:
• None
• Keyswitch Only
• Keyswitch and Password A
• Keyswitch and Password B
• Keyswitch and Password A or B
• Password A Only
• Password B Only
• Password A or B
Password protection can also be invoked to protect access on a Page-by-Page basis. Once a Page
Password is logged-in, then access to a page remains active until it is logged-out. While logged-in,
the operator can change pages and return to this page until logged-out. Password A and B can be
logged-out manually or a user-defined time period can expire which will log-out all passwords. If the
time-out occurs, the operator retains access to the current page.
Chapter 5: Password Protection 25
Page Passwords are accessed in the Setup Page. This page is accessed from the default page by
selecting the Get Page, More Buttons and Setup Page control buttons. The letters K, A, and B will
appear to the left of the time of day clock on the top line of each page to indicate when the Keyswitch,
Password A, and Password B are enabled for entry. The status of the passwords and security
keyswitch, when used as Page Passwords, may be transmitted to a PLC by setting the appropriate
address in the System Parameters - Password Tab dialog box. This feature can be useful when
implementing the Page Protection concept when a Page Change is sent from a PLC.
The security keyswitch is an option which may be ordered as a spare part from the Cutler-Hammer
Customer Service Department. The terminals on the PanelMate unit require contact closure to enable
entry. Multiple key switches, PLC relay contact outputs, and hard contact outputs from other devices,
such a magnetic strip badge readers, may be used in combination to create the contact closure signal.
Note that a security keyswitch cannot be connected to the PanelMate Power Series 1500.
Passwords A and B are downloaded within the User Configuration to the PanelMate unit. These
values may be used at system start-up or they may be defined to overwrite current passwords which
reside in the system.
Password Protection can be implemented in many ways. Examples of usage are defined below:
• Offline Mode protected with Keyswitch and Password A
• Set Date and Time protected with Keyswitch and Password B
• Page 9, the machine parameter page, protected with Keyswitch
• Reset Part Counter Readout Template protected with Password A
• Operating Temperature Setpoint Readout Template protected with Password B
Setup Page
6
In this chapter you will learn:
• The features available on the setup page
28 Online Operation User’s Guide
Setup Page
The Setup Page is accessed from the default control buttons. The Setup Page provides selection of the
following features while the online unit remains in the Run Mode.
To access a feature, select a template then press the Execute control button.
Note that if you have a PanelMate Power Series 1500, the Setup Page will display a Reset PLC
Comm control button instead of an Enable Fault Relay control button. The Reset PLC Comm
control button will reset communication errors if the reason for the error no longer exists.
Cleaning Mode
This selection will allow you to clean your touchscreen.
The Cleaning Mode template will only appear in the Setup Page if you have a touchscreen unit.
Calibrate Touchscreen
This selection will allow you to calibrate your touchscreen.
The Calibrate Touchscreen template will only appear in the Setup Page if you have a touchscreen
unit.
Adjust Contrast
This selection will allow you to adjust the contrast.
The Adjust Contrast template will only appear in the Setup Page if you have a dual-scan or grayscale
LCD display.
For more information about the two column or three column keypads, refer to the Default Control
Buttons topic.
30 Online Operation User’s Guide
Chapter 7: Fault Relay 31
Fault Relay
7
In this chapter, you will learn:
• About the fault relay
32 Online Operation User’s Guide
Fault Relay
The fault relay is a relay contact output with normally open and normally closed contacts. At power
up, the PanelMate unit performs system diagnostics. If diagnostics are passed, the fault relay is
energized (enabled). The unit begins communications to PLCs. Four events can cause the fault relay
to de-energize: online system error, communication error, alarm (if this feature is selected), and loss
of power.
Note that the PanelMate Power Series 1500 does not support an external Fault Relay.
Warning
If blank templates appear on the screen, a communication error has occurred. The operator should not
attempt to perform control with blank templates as this may cause control buttons to be buffered in
the PanelMate unit. Buffered control buttons may be sent in rapid succession when the
communication error clears and may result in undesirable control system operation.
The System Parameters – Communications Tab dialog box permits the selection of setting all
referenced control button bits to zero (or one for Variable-Sized Control Buttons configured as
Normally Closed, Momentary) when the Enable Fault Relay control button is pressed or when a
Remote Enable Fault Relay Bit reference is triggered by the PLC. To reset all control button bits, the
Bit Zero After Comm Fault field in the System Parameters – Communication Tab dialog box must
be selected. To configure a Remote Enable Fault Relay Bit, the Remote Enable Fault Relay Bit field
must be configured in the System Parameters – Remote Tab dialog box. Refer to the System
Parameters – Communications Tab dialog box or the System Parameters – Remote Tab dialog
box in the Configuration Editor User’s Guide for more information.
Chapter 7: Fault Relay 33
The data at the time of a communication failure will remain on the current page. All data from other
PLCs which are communicating correctly will be displayed as usual. If the communication error
continues to exist and you select a different page, then no data from the PLC with errors will be
shown on the newly selected page. For example, if the page contains a readout template, no numerical
data from the PLC with the communication errors will be shown. Once the communication problem is
corrected and the Enable Fault Relay control button is pressed or the Remote Enable Fault Relay Bit
reference is triggered by the PLC, the fault relay will be energized and the page will be re-drawn. Any
references to a PLC which are not communicating will not be re-drawn until valid communications
have resumed. If the communication error still exists, the fault relay will be de-energized and a
communication error message will be displayed on the bottom line of the screen.
Note that pressing the Enable Fault Relay control button or triggering the Remote Enable Fault
Relay Bit reference may still cause invalid information to be displayed. For example, if an expression
for a bar template value contains a reference to a PLC which is communicating and also to a PLC
which is not communicating, the bar will be updated on the screen even though invalid data may
appear on the screen.
When communications have been re-established, the relay remains de-energized until the operator
presses the Enable Fault Relay control button or a Remote Enable Fault Relay Bit reference is
triggered by a PLC.
Maintenance Template
8
In this chapter, you will learn:
• About the Maintenance Template
36 Online Operation User’s Guide
Maintenance Template
In order to use the Maintenance Template online, you must configure the Allow on Page selection in
the New Configuration Page dialog box or in the Page Properties dialog box within the
Configuration Editor.
It is important to note that when in Run Mode, do not place Maintenance Templates in an area of the
screen where invisible templates are located. If an invisible template becomes visible, it will draw on
top of the Maintenance Template. The Maintenance Template will not be able to be selected for de-
activation until the object obscuring that template becomes invisible. It is recommended that on pages
which use the template visibility and allow Maintenance Template selection, an area of the page be
reserved for placement of the Maintenance Template.
To access the Maintenance Template online, you must press the Get Page control button from the
default control buttons online, press the More Buttons control button (More on a touchscreen unit),
and then press the Maintenance Template control button. The Maintenance Template selection
cursor will appear in the upper left corner. You can place the Maintenance Template on any cell
including cells already occupied by a fixed template or another Maintenance Template. You cannot
place a Maintenance Template on top of a variable-sized template.
Note that the Maintenance Template will not appear on your page until you press the Activate control
button. (The default PLC Name will appear in the Maintenance Template.) If you press the
Deactivate control button, the Maintenance Template will be removed from your page.
Once the Maintenance Template is activated, press the CANCEL key and re-select the Maintenance
Template. The Deactivate and Modify Template control buttons will appear.
Note that when selecting a template cell to place a Maintenance Template, static values will be
displayed in the template’s value fields if the PanelMate unit is not communicating to the PLC.
Start Monitor
This control button label will toggle between Start Monitor and Stop Monitor. With this control
button, it is possible to freeze a value for prolonged observation.
When you press the Start Monitor control button and the Enable Writes field in the New
Configuration Page dialog box is configured on the page and the Maintenance Template is
configured with a valid reference, the Change Value control button will also appear.
Note that if the double high font is redefined, the Maintenance Template will be blank for numeric
and hex display formats unless the characters have been redefined. If the characters have been
redefined, then the redefined characters will be displayed.
Deactivate
This control button will delete the Maintenance Template from the page.
Chapter 8: Maintenance Template 37
Change Value
This control button will be displayed only if the Enable Writes field in the New Configuration dialog
box or the Page Properties dialog box was configured for the page. This control button will change
the display and open a data entry field to permit the operator to enter a value. If Password Protection
has been configured in the New Configuration dialog box or the Page Properties dialog box for the
pages that contain Maintenance Templates, the operator will be prompted before data entry is
permitted.
Modify Template
This control button is used to change the configuration of the Maintenance Template. This control
button will change the display and call three control buttons. The control buttons are Change PLC
Name, Change PLC Ref, and Data Format. The operator may change one or all of the three entry
variables (name, reference, format). When the Maintenance Template is configured with a valid
reference, the Start Monitor control button will appear. Once you are satisfied with the changes, you
must press the Start Monitor control button. This will advise the PanelMate unit to check the name,
reference, and format to determine if they are valid, and if valid, begin to read that information.
If the reference is invalid, an error will be displayed on the error line on the bottom of the page and
the reference will be cleared.
Keypad Touchscreen
Hot Keys Hot Keys Description
Cursor Right >> Move the entry cursor one character right.
Cursor Left << Move the entry cursor one character left.
Delete DEL Delete the character at the current cursor position.
Space SPACE Place a blank space at the current cursor position.
Clear CLEAR Clear the entire entry field.
Select SEL Enters the mode to select alpha character strings.
Upon entering the Change PLC Reference mode, the Hot Key labeled “Clear” will be displayed.
Selecting the Previous button will change the Hot Key to Space, while selecting the Next button will
change the Hot Key to Select.
Upon entering the Select mode, the first of a list of alpha characters for the currently selected PLC
Name will be displayed in the data entry field. Selecting the Next button will move deeper into the
alpha character list while selecting Previous button would take you back to Clear. Once in the Select
mode, the Previous and Next keys will scroll through the alpha character strings that are required to
address the PLC brand associated with the PLC Name currently selected. Once the correct character
string is displayed, you may press the Select Hot Key to lock in that character. Alternately, you may
press a numeric key which will lock in the alpha key and enter a number. Pressing the numeric key
will reduce the number of keystrokes and permit faster entry. Do not press the Accept button until the
entire address is entered or an error may occur.
The operator uses a combination of Hot Key entry and numeric entry to enter the address for the PLC.
The Hot Key may also be used to edit an existing address without requiring complete re-entry of the
address. Refer to the Maintenance Template Examples for more information.
Chapter 8: Maintenance Template 39
Data Format
The register can be formatted to display in one of the following selections: NUM, BITS, or HEX.
• If NUM is selected, the data will display in a numeric format. The PanelMate unit will
automatically type cast information based upon the memory area of the PLC which is read. This
means it will manage integer, BCD, and binary data types and display them as numbers. Numeric
entries will be converted to the correct data type and sent to the PLC if the Enable Writes field is
configured in the New Configuration Page dialog box or in the Page Properties dialog box.
• If BITS is selected, the data is entered and will be displayed in a binary bit pattern for the register
selected. If the PLC word contains 16 bits, then the display will show two 8 bit bytes. The
sequence is high byte above low byte and high bit to the left, low bit to the right. The bit values
will not be manipulated to any data format. The operator accepts responsibility for entering a
legal bit combination. (For example, writing 1111 to a BCD digit is an illegal value.)
• If HEX is selected, the data is entered and will be displayed in hexadecimal format (0-9 and A-F)
of the bit pattern for the register selected.
Sixteen bit values are displayed in four-digit HEX representation.
Example: 0023 HEX is written to the PLC as 0000 0000 0010 0011.
It is not converted to 35 decimal or 0000 0000 0100 0101 in binary.
Only NUM types are converted to the numeric value based upon the memory areas of the PLC
referenced.
The figure below shows an example of a 16-bit word in a Maintenance Template with the Bits format
selected.
The Maintenance Template does not support 32-bit registers (i.e., #S32, #U32, #BIN6, #BIN8,
#BCD8, #BCD6, and #FP).
The Maintenance Template does not support unsoliciteds.
Chapter 9: Errors 41
Errors
9
In this chapter, you will learn:
• About Remote I/O errors
• About errors during Run Mode
• About communication errors
• About system errors
• About error codes
42 Online Operation User’s Guide
Communication Errors
The PanelMate unit can interface with a single PLC or with multiple PLCs. It provides predictable
fault responses with the occurrence of communication errors which indicate a breakdown in
communication between the PanelMate unit and a PLC. It is the Control System Designer’s
responsibility to define how the operator should respond to an error.
The PanelMate unit provides two indications when a communication error occurs: an error message is
written to the bottom of the screen and the fault relay is de-energized. The fault relay is provided for
both local annunciation to an operator and to send hardwired feedback to a PLC.
Once a communication error occurs, the operator should first note the page status. The data is a
snapshot in time of the last valid communication. The next action is to try to clear the error by
pressing the Enable Fault Relay control button or triggering the Remote Enable Fault Relay Bit
reference. This energizes the fault relay and attempts to restart communications. If the condition
causing the error no longer exists, the screen is updated with dynamic information. If the error
remains, the fault relay is de-energized again and the communication error message is written to the
screen. If values could not be read due to the lack of communications, then templates will be
displayed as blank.
Chapter 9: Errors 43
Warning
If blank templates appear on the screen, it means that communications have not been re-established.
The operator should not attempt to perform control with blank templates because the actual state of
the machine or process cannot be determined. If the operator continues to press control buttons, data
may be sent faster than the communication link which is in error can handle them. The PanelMate
unit will buffer the control requests until communications have re-established. This may result in
control bits being sent to a PLC in rapid succession which may cause undesirable operation of the
control system.
Communication errors can be cleared by pressing the Enable Fault Relay control button, triggering
the Remote Enable Fault Relay Bit reference, or changing pages, provided the reason for the error no
longer exists. Integrity of the communication link to the PLC (or host) is monitored by ensuring that
proper responses are received for each transmission that the PanelMate unit makes, according to the
specific protocol in use.
Communication problems can include:
• Broken or incorrect cabling to the PLC
• PLC or interface card failure
• Incorrect setting of PLC interface card switches
• Removal of a PLC from the active network
• Attempt to access a non-existent PLC address
• Attempt to write to a protected PLC address
• Too much traffic on a PLC network
The PanelMate unit will try to re-transmit a request several times before reporting that a
communications error has occurred. Unlike Systems Errors, Communication Errors do not halt the
system. The PanelMate unit continues to re-transmit requests indefinitely, even after an error has
been reported.
The frequency of the re-transmission gradually decreases to five minutes if requests continue to fail
over a prolonged period of time. This feature effectively prevents failing requests from conflicting
with other communications.
Refer to the Error Codes topic for a list of error codes and their descriptions.
Local Errors
Local errors are reported on the bottom of the screen as follows:
where
X is an internally generated communication error code which indicates the nature of
the problem. Refer to the Error Codes topic for a list of error codes and their
descriptions.
N is the PLC name in the PLC Name and Port Table
P is the port
O is the operation being performed
R is the reference
44 Online Operation User’s Guide
Remote Errors
Remote errors are reported on the bottom of the screen as follows:
where
X is a generated communication error code from a remote device. Refer to your PLC
user manual for more information on this error code.
N is the PLC name in the PLC Name and Port Table
P is the port
O is the operation being performed
R is the reference
If you are using Allen-Bradley PLCs for Data Highway or Data Highway Plus, a complete set of error
codes can be found in the Allen-Bradley Publication 1770-6.5.16, November 1991. Take note of the
hexadecimal error code and consult the Allen-Bradley publication. If the remote error code is F0XX
(hex), then the XX represents the Allen-Bradley EXT STS (extended status) error code. The EXT
STS codes are found in the EXT STS Codes for Command Code 0F (hex) table. Other remote error
codes are found in the Remote STS Error Codes table.
When a communication error is reported, the fault relay is de-energized, but the system continues to
operate. Other PLC transmissions will be attempted and processed. Transmissions which have failed
will be re-attempted until normal communication is re-established. Each time the error is detected,
the message will be reprinted at the bottom of the screen (and the relay will be de-energized). The
data at the time of a communication failure will remain on the current page. If a different page is
selected, no data from the PLC with errors will be shown. For example, if the page contains a readout
template, no numerical data from the PLC with the communication errors will be shown. The
numerical area will be blank. All data from other PLCs which are operating correctly, will be
displayed as usual. Once the communications problem is corrected and the Enable Fault Relay
control button is pressed or the Remote Enable Fault Relay Bit reference is triggered by the PLC, the
page will be re-drawn. Any templates or Variable-Sized Templates which reference a PLC which is
not communicating will not be re-drawn until valid communications has resumed.
When the error is corrected, the relay remains de-energized until the operator presses the Enable
Fault Relay control button or the Remote Enable Fault Relay Bit reference is triggered by the PLC,
which appears on the default selections when a communications error occurs. This also clears the
message from the bottom of the screen. (The button label disappears once the button has been
pressed.)
Note that invalid information may still be displayed. For example, if an expression for a Variable-
Sized Bar Template value contains a reference to PLC which is communicating and also contains a
reference to a PLC which is not communicating, the Variable-Sized Bar Template will be updated on
the screen, even though invalid data may be in the data base.
Refer to the Error Codes topic for a list of error codes and their descriptions.
Chapter 9: Errors 45
System Errors
During Run Mode operation, two basic conditions are checked in the PanelMate unit: proper
operation of the CPU and proper operation of the system software.
Proper operation of the microprocessor is monitored by a Watchdog Timer. If a microprocessor error
is detected, the fault relay is de-energized, the screen will display “Watchdog Time-out. Press Cancel
Key to Continue” , and the system is halted.
One possible reason for the Watchdog Time-out error could be related to the power. Check to make
sure that the PanelMate unit is properly installed. If problems still occur, call your local distributor for
more information.
Proper operation of system software is monitored to ensure that all internal processes are active and
functioning normally. If a system software error is detected, the fault relay is de-energized, and the
system is halted.
An error message is displayed at the bottom of the screen:
where
X a system error code which indicates the nature of the problem. Refer to the Error
Codes topic for a list of the error codes and their descriptions.
O is the operation being performed
P is an internal error code. This error code may appear more than one time.
Note that if these error messages appear, please call your local distributor.
46 Online Operation User’s Guide
Error Codes
Error
Number Description Possible Cause
0 Undefined error.
1 Software module not found or
corrupted.
2 Out of memory.
201 Bad or missing communication card.
244-246 Read/write error. Cabling wrong.
RS232/RS422 converter bad or missing.
Excessive noise on communication line.
253 Acknowledge not received from the No communication.
remote device or remote device did PLC busy.
not reply to request in allotted Invalid network ID.
amount of time. Wrong communication parameter.
PanelMate unit may be receiving too many
unsolicited messages.
1000 Internal system error code. Invalid configuration.
Bad PLC Name and Port Table.
1001 Serial port buffer overrun. PLC locked in transmit mode.
PLC transmitting too much data.
1002 Error on input. Wrong communication parameters.
Intermittent hardware failure.
1003 Error on output. Wrong communication parameters.
Intermittent hardware failure.
1100 Device descriptor cannot be Out of memory.
generated.
Module not found.
1101 Device cannot be opened. Missing module.
Serial controller or I/O board bad.
Missing or bad hardware.
Interface board not installed.
1102 Expected data was not received. Communication established. The PanelMate
unit started reading data but timed out.
Error 1102 is usually followed by a 1202 or
1702 error.
Chapter 9: Errors 47
Error
Number Description Possible Cause
Error
Number Description Possible Cause
1156 DH-485 - data link is not active (link Missing or bad cable
time-out) PanelMate unit is not Noise on communication line.
passing token.
1157 DH-485 - application time-out
(destination active but not
responding).
1158 DH-485 - The PanelMate unit has Network communications disrupted. The
not received token from previous cable was disconnected from the PanelMate
node. unit or the previous node has dropped off the
network.
Error 1158 is usually followed by an 1156
error.
1200 Communication active but remote Noise on communication line.
device responded with negative Wrong parity.
acknowledge (NAK).
1201 Communication active but remote Noise on communication line.
device responded with negative Wrong parity.
acknowledge (NAK).
1202 Acknowledge not received from the No communication.
remote device or remote device did PLC is busy.
not reply to request in allotted Invalid network ID.
amount of time. Wrong communication parameter.
The PanelMate unit may be receiving too
many unsolicited messages.
This error is driver dependent.
1203 PanelMate unit cannot set privilege Communication error while trying to set
level in GE PLC (SNP). privilege.
Other device has set privilege.
1250 Could not establish link with Square
D PLC.
1250 Could not synchronize with
Westinghouse PLC.
1250 Reliance AutoMate Gateway not No communication.
configured. PLC is busy.
Invalid network ID.
The PanelMate unit unsuccessfully trying to
reconfigure Reliance gateway module.
Dipswitches configured wrong.
Power loss to gateway module.
Intermittent error.
1250 Channel prematurely closed by GE The PanelMate unit too busy to close channel.
CCM.
Chapter 9: Errors 49
Error
Number Description Possible Cause
1250 Communication to GE with SNP out The PanelMate unit too busy to accept reply.
of sync. Noise or cable problems
1251 Open Channel request was refused GE CCM card is too busy to open channel.
by GE CCM. Noise on communication line to GE.
Wrong parity.
1251 Reliance AutoMate processor not
found in destination slot.
1251 PanelMate unit cannot set privilege Communication error while trying to set
level in GE PLC (SNP). privilege.
Other device has set privilege.
1252 More than one Reliance AutoMate
processor in the rack.
1700 Communications out of sync. Duplicate token, noise, or busy device causes
PanelMate unit to time-out and PLC responds
to previous request.
1701 A reply was received for which there Scan delays too large.
was no request issued.
1702 Acknowledge not received from the No communication.
remote device or remote device did PLC busy.
not reply to request in allotted Invalid network ID.
amount of time. Wrong communication parameter.
The PanelMate unit may be receiving too
many unsolicited messages.
This error is driver dependent.
If using unsolicited messages over Data
Highway or Data Highway Plus, check the
part number of the EPROM on your Allen-
Bradley AcceleratI/O board. The EPROM
needs to be upgraded to revision 06
(P/N 85-00285-06).
1703 Internal system error code.
1705 This interface does not support any
unsolicited requests from a remote
device.
1706 Received an unsolicited command
that is not supported.
1707 The remote device memory type is
not supported.
1708 Cannot write to read only reference.
1750 Siemens follow-on telegrams are not PLC sending too much data.
supported.
50 Online Operation User’s Guide
Error
Number Description Possible Cause
Error
Number Description Possible Cause
Error
Number Description Possible Cause
2502 Invalid reference. Cannot parse. Not enough characters in network address or
PLC reference.
2503 Invalid reference. Cannot parse. Too many characters in network address or
PLC reference.
2525 Network address component out of Configured Network ID or PLC ID out of
range. range.
3000- Internal system error code. Driver corrupted.
3005 Download new executive firmware/ drivers.
3006 Cannot write to unsolicited driver. A reference associated with a name in the
unsolicited device field is being used in a
control button or numeric entry field.
3025 Network address (PLC ID field) is
invalid or out of range.
3050- Internal system error code. Data Baud rate too slow.
3055 buffer corrupted.
4100 Invalid network ID.
4101 Invalid network ID.
4102 Not enough network ID levels
specified.
4103 Too many network ID levels
specified.
4104 Invalid network ID.
Chapter 9: Errors 53
Error
Number Description Possible Cause Possible Solution
101 Internal system error. Out of environment space. Add shell command to
The mode argument is config.sys and increase
invalid. environment size.
Increase the amount of
RAM available or do not run
TSRs, other programs, or
device drivers.
102 Interface card software KT software not properly Install Allen-Bradley
missing or bad path. installed. KT software Standard Driver Software
directory not in the path. (Cat No 6001-FIE) as shown
in the Allen-Bradley
Software User manual.
Add the KT software
directory to path command
in autoexec.bat and reboot
system.
102 Interface card software Configuration software not Reinstall configuration
missing or bad path. properly installed or is software.
corrupt.
103 Interface card software KT software is corrupt. Reinstall Allen-Bradley
bad. Standard Driver Software
(Cat No 6001-F1E) as
shown in the Allen-Bradley
Standard Driver Software
User Manual.
103 Interface card software Configuration software is Reinstall configuration
bad. corrupt. software
104 Not enough memory is Out of low memory (lower Increase the amount of
available to initialize 640K of RAM). RAM available or do not run
interface card. TSRs other programs or
device drivers.
Refer to the DOS manual to
optimize memory usage.
54 Online Operation User’s Guide
Error
Number Description Possible Cause Possible Solution
105 KT card could not be KT card could not be Exit configuration software
initialized. initialized for unknown and run startkt.exe
reasons. command as shown in the
Allen-Bradley Standard
Driver Software User
Manual.
If the card initializes
correctly, the problem is a
shortage of memory.
Increase the amount of
RAM available or do not run
TSRs other programs or
device drivers.
Refer to the DOS manual to
optimize memory usage.
If the card fails to initialize
an error message displays.
See Error Codes in the
Allen-Bradley Standard
Driver Software User
Manual.
106 SD card program error. Configuration software not Reinstall configuration
properly installed or is software.
corrupt.
107 SD card bad port and/or Port address does not match Ensure the dip switch
memory address. the switch settings on settings on interface card
interface card. Port address match the port address
in conflict with other selected.
memory in computer.
Select a different port
address.
108 SD card memory error. SD card memory in conflict Select a different memory
with other memory in setting. Replace and test
computer. SD card may be with a known good interface
defective. card.
109 SD card processor SD card may be defective. Replace and test with a
failure. known good interface card.
10A SD card error. SD card may be defective. Replace and test with a
known good interface card.
10B SD card software Configuration software not Reinstall configuration
module not found. properly installed or is software.
corrupt.
Appendix A: Online Operation Problems 55
A
In this chapter, you will learn:
• Common online problems and solutions
56 Online Operation User’s Guide
B
In this chapter, you will learn:
• About momentary pushbutton precautions
58 Online Operation User’s Guide
3. PanelMate also has a built-in feature designed to correct this potential situation that doesn’t
require any PLC logic. At system boot-up and after a communications fault is reset by the
operator (or remotely by the PLC), the PanelMate can be made to write all momentary control
bits to their normal state. This means that every Normally Open, Momentary control button will
have a zero written to the associated PLC control bit and every Normally Closed, Momentary
control button will have a one written to the associated PLC control bit. This solution is less
desirable than using the fault relay because it requires either a complete restart of the PanelMate
unit after power loss or an operator action before the potential “stuck button” is reset. Also, it is
possible that a cable could become disconnected or severed and this reset would not occur. This
function is enabled by checking the box labeled “Bit Zero After Com Fault” in the System
Parameters–Communications Tab dialog box. This box is left unchecked by default when a
new configuration is created and must be checked by the developer to enable this feature.
Depending on the number of momentary pushbuttons created in the PanelMate configuration, the
resetting of all control bits could noticeably increase the boot-up and communications reset time.
PanelMate offers several features to help increase the intrinsic safety of the control system, but it is up
to the control system developer to determine the best solution to a potential “stuck pushbutton”.
60 Online Operation User’s Guide
Index 61
Index
A E
About This Manual, II Emergency Technical Support, III
Purpose, II Enter Offline Mode, 29
What’s Inside, II Errors During Run Mode, 42
Adjust Contrast, 29 Execute Normal Power-Up Diagnostics, 2
Alarm Summary Page, 21
Alarm Window, 9 F
Alarms, 20
Alternate Mode, 4 Fault Relay, 32
Fault Relay and Alarms, 33
Fault Relay and Communication Errors,
B 32
Bulletin Board Service, IV Fault Relay and Loss of Power, 33
Fault Relay and Online System Errors, 32
C
Calibrate Touchscreen, 29
G
Change Password A or Change Password Get Page, 13
B, 28
Change PLC Name (Maintenance H
Template), 37
Change PLC Ref (Maintenance Host Display Window, 13
Template), 38
Change Value (Maintenance Template), I
37
Check for Executive Firmware, 3 Information Fax-Back Service, III
Check for Presence of Installed Drivers, 4 Interface Card Errors, 53
Check User Configuration Compatibility
with Executive Firmware, 3 L
Cleaning Mode, 29
Communication Errors, 42 Local Errors, 43
Conditional Visibility, 10 Log-in Password A and Log-in Password
Control Button Operation, 16 B, 28
Correspondence Address, IV Log-out Password A and Log-out
Password B, 29
Lost Password Recovery, 25
D
Data Format (Maintenance Template), 40 M
Deactivate (Maintenance Template), 36
Default Control Buttons, 11 Maintenance Template Examples, 39
Determine if the Unit Should Enter the Maintenance Template, 36
Transfer Mode, 3 Modify Template (Maintenance
Determine Power Up Mode, 4 Template), 37
Directory, 14 Momentary Pushbutton Operation, 58
Display System/Configuration
Information, 29
62 Runtime Operation User’s Guide
O
Offline Mode, 4
One-Touch Selection of Variable-Sized
Templates, 16
Online Page Layout, 8
Online Problems, 56
Operator Input, 16
P
Page Number and Page Title, 9
Pages In Alarm, 9
Password Protection, 24
PLC Page Selection, 13
Power Up Sequence, 2
Preface, I
Problems, Online, 56
Product Ordering Service, IV
R
Recovery Mode, 3
Refresh Graphics, 9
Remote Errors, 44
Remote I/O Errors, 42
Run Mode Operation, 6
Run Mode, 5
S
Selecting a Template, 16
Set Date and Time, 28
Setup Page, 28
Software Update Service, IV
Start Monitor (Maintenance Template),
36
Support Services, III
Switch to Two Column Keypad or Switch
to Three Column Keypad, 29
System Errors, 45
T
Technical Support Fax, III
Technical Support, III
Troubleshooting the Online Operation, 56
Two-Touch Selection of Variable-Sized
Templates, 16
V
View or Acknowledge Alarms, 21
Reader Comment Card
Cutler-Hammer strives to provide quality user guides and product manuals. Please take a moment to
fill out this comment card.
Other comments:
Thank you for your comments. Please fax this page to:
Cutler-Hammer Technical Publications Dept.
FAX : 614-882-0289
I.L. 195C492C
ECS2100 PanelMate Screen
INSTRUCTION LEAFLET
This document describes the control of a 2-channel ECS2100 excitation system using the PanelMate operator control
interface. The PanelMate Power Series 1700 is described here with additional information being available in PanelMate
Power Series Online Operation User’s Guide, IL#P/N-01-00394-00.
A 1-channel or 3-channel system would have the same general pages described below. The difference being a 2 or 3
channel system will contain pages giving channel specific data.
Modbus 4.6 RTU protocol is used to implement communication between the PanelMate and the controller that resides in
the ECM. The software in the ECM card has dedicated blocks that direct information sent to or received from the
PanelMate. These blocks are called PMIN for input from the PanelMate and PMOUT for output information directed to
the PanelMate.
PAGE 0
Page 0 is the page that will be visible when the PanelMate is initially
powered. Page 0 is shown in Figure 1. Identified is the address of
each control board that may be addressed via Modbus or by the
ccTool programming software.
To navigate from this point the “Index” button will open the Index
page.
Figure 1
Index
The examples shown are generic in nature and do not represent actual excitation system alarms. The examples of
‘Reduction Furnace Overtemp’ and ‘Inbound Hopper Overweight’ have been cleared by the inputs no longer being
active.
Most alarms must be acknowledged in order to remove them from the alarm page. This is done by pressing the
‘View or Acknowledge Alarms’ on the right of the PanelMate screen. At that time an option to scroll up or down the last
100 alarms allows the operator to acknowledge all alarms or alarms that the operator selects. When alarms are
acknowledged the background of those alarms becomes black and the text becomes yellow with a notation of ACKN in
front of the time stamp.
To view the entire Alarms page, use the ‘Get Page’ feature. When the keypad appears on the right side of the
screen, press ‘Alarms’. The Alarms page will then open displaying the last 100 alarms.
For more information about PanelMate alarm features, refer to PanelMate Power Series Online Operation User’s
Guide, IL#P/N-01-00394-00, page 19.
Output Control
selections on right side of screen. The two selections will allow operator to choose Auto Mode or Manual Mode.
AC Breaker- Indicates the opened or closed status of the AC field breaker.
Figure 7
Indication icons, such as the one shown in Figure 8 give an indication or status of
the regulator system. Any indicator with the arrow in the bottom left corner is also a
control switch. Pressing the AC Breaker indicator, the operator will be given two
command selections which can close or open the AC field breaker
To close the 41A breaker, the operator should press the ‘AC Breaker’ indicator
that is available on either the Output Control page or the Generator Monitor page. When
that is pressed, two selections will appear on the right side of the PanelMate screen.
These control selections are shown in Figure 9. When the operator selects “Close 41A’,
the breaker will close and the field will flash automatically for a pre-determined amount of
time, or until the field is self-sustaining.
Figure 8
Once the breaker has closed and the field has flashed, the ECS2100 will return to
the mode
(Auto or Manual) it was operating in when the 41A was open.
Figure 9
Figure 10
Generator Monitor
Figure 11
Transfer Control
The Transfer Control page would be used
to transfer control of the ECS2100 from one
channel to another.
To transfer channel control, the
PanelMate being used must be in control. It also
must be known if the PanelMate being used is the
‘Local’ or ‘Remote’ PanelMate. The Local/Remote
indicator informs the operator. If the PanelMate
being used is not in control, that function is
available on Remote/Local Control page shown in
Figure 13.
Note that the PanelMate on the door of the
ECS2100 is considered the ‘Local’ PanelMate. Any
other control location is considered ‘Remote’.
Once the PanelMate being used is in
control, the PanelMate Enable Trans control must
indicate “PanelMate Enabled”. That would be
accomplished by pressing the “PanelMate Enable Figure 12
Trans” indicator and selecting “Enable PanelMate
Transfer”. Then press the “Transfer Using PanelMate”
indicator and select the channel to be in control.
Figure 13
Figure 14
PSS
The PSS screen will be available only on systems
that have PSS on the ECS2100 regulator. PSS is enabled
and disabled with the PSS ON/OFF control switch and
indicator on the right side of the screen. The output
indications are along the left of the page are channel specific
PSS output. The indications along center are the normal
operating mode indications.
Figure 16
Figure 17
VAR
The VAR screen will be available only on systems
that have VAR control on the ECS2100 regulator. The gray
button is a toggle button which will turn VAR on and off. The
control indicators along the bottom of the page are the same
control switches available on the Generator Monitor page
(Figure 11) and the Output Control page (Figure 6).
Figure 18
Figure 19
Meter Panel
The meter panel page is the only page that is
found only in the channel specific pages. There are no
control functions, only position indicating meters. All
meters are shown in P.U. (per unit) values.
Figure 20
For additional information such as setting date and time, uploading and downloading programs, alarms,
and passwords refer to PanelMate Power Series Online Operation User’s Guide, IL#P/N-01-00394-00. On rare
occasions a red alarm appears on the bottom of the PanelMate screen referring to alarm #00065. Due to
receiving information from 4 different controllers (ECM/ECR/FCIM/FCIR) there can be some timing issues if
unshielded cables are used for the Modbus communication. If this becomes a problem the cables from the ECM
and ECR to the PanelMate should be exchanged with shielded cables.
View the Alarm Page Any 1. Select ‘Get Page’ on the right of
the screen.
2. On the keypad, press ‘Alarm’
Acknowledge Alarms Alarm Page or Alarm banner that This can be done either on the
is always visible Alarm page or on the Alarm banner.
1. On the right side of the screen,
select ‘View or Acknowledge
Alarms’.
2. To acknowledge all alarms,
select ‘Acknowledge All
Alarms’.
3. To acknowledge selected
alarms, move the cursor up or
down by pressing ‘Scroll Up’ or
‘Scroll Down’.
4. When the cursor is on the
desired alarm, select
‘Acknowledge Alarm’.
Open Field Breaker (41A) Either Output Control 3. Press ‘AC BREAKER’ indicator
Or Generator Monitor at bottom of screen.
4. On right of screen select ‘Trip
41A’.
41A failed to close (M) / (R) Alarm Status A signal to close the 41A 1. Mechanical operation of
device was sent, but 41A device.
confirmation of 41A closure 2. 41A feedback signal to
was not received. DIGIN1_C609.
3. Press ‘Trip 41A’ to reset.
Bridge Alarm (M) / (R) Alarm Status A bridge has an alarm. Refer to Bridge Status
page(s) for details of the
alarm.
DXCB operated (M) / (R) Alarm Status DX module operated due to Investigate. Check AC line
a voltage spike on the field. snubbers or AC voltraps.
This can be a typical
occurrence on some
systems during a normal
shutdown.
Field Flash Failed (M) / (R) Alarm Status 41A device closed but 1. 31 devices.
neither field current nor 2. Field flash voltage
terminal voltage reached supply.
required threshold levels. 3. Some systems require to
be reset after this alarm.
If so, press ‘Trip 41A’.
FLD Current xdcr fail (M) / (R) Alarm Status Channel specified has lost 4. DCXDM(R)
the signal from DCXDM or 5. Power supply
DCXDR. connections to
DCXDM(R).
6. Fuses DCOFU(R)
7. Fiber optic connections
IFG, VFG, IEXFR,
VEXFR.
FLD Voltage xdcr fail (M) / (R) Alarm Status The channel specified has 1. ALXDM(R).
lost signals from ALXDM(R). 2. Fuses ACLFU(R).
3. FIM(R) input from
ALXDM(R).
4. Fiber optic connections
between ALXDM (R)
and FIM (R)
HXL limiting (M) / (R) Limiters & Trips Volts per Hertz limiter is in 1. Check terminal voltage.
control of regulator. 2. Adjust voltage.
HXL timing (M) / (R) Limiters & Trips Volts per Hertz ratio has 1. Check terminal voltage.
exceeded the protection 2. Adjust voltage.
setting and is now in the
timing.
HXL timed out (M) / (R) Limiters & Trips Volts per Hertz ratio has 1. Check terminal voltage.
exceeded the protection 2. Adjust voltage.
setting and has now timed
out. The HXL limiter should
now take control.
HXL trip (M) / (R) Limiters & Trips The HXL Limiter failed to Investigate terminal voltage
reduce the volts per hertz levels previous to trip.
ratio The HXL protection
has tripped the regulator via
the 94E relay.
HXL xfer to Redundant (M) / (R) Limiter & Trips HXL limiter has transferred Terminal voltage.
the system to the redundant
channel in an attempt to
avoid a trip.
Page 12 of 16 November 13, 2006
INST limiting (M) / (R) Limiters & Trips INST Limiter is in control of 1. Check field current.
the regulator. 2. Adjust voltage.
INST trip (M) / (R) Limiters & Trips The INST Limiter failed to Investigate field current
reduce the field current. The levels previous to trip.
INST protection has tripped
the regulator via the 94E
relay.
INST xfer to Redundant (M) / (R) Limiter & Trips INST limiter has transferred Field current.
the system to the redundant
channel in an attempt to
avoid a trip.
LBF trip (M) / (R) Limiters & Trips Both fans in the power 1. 88MPFU and 88RPFU
cubicle have failed and the fuses.
regulator has tripped via the 2. T10 and T11
94E relay. transformers.
3. Fan motors.
LOS transfer to manual (M) / (R ) Limiters & Trips Loss of sensing has 1. PT
detected less than 89% 2. Feedback from PT to PT
terminal voltage and thus SIM card.
has transferred the system
to manual control.
LOS transfer to Redundant (M) / (R ) Limiters & Trips Loss of sensing has 1. PT
detected less than 89% 2. Feedback from PT to PT
terminal voltage and thus SIM card.
has transferred the system
to the redundant channel.
Main Local/Red Remote Local / Remote Two channels under control Follow instruction is TASK
of separate locations. GUIDE for Change
Remote/Local Control.
Main not Ready Transfer Main Channel not ready for 1. PT signal to main
Control service. channel (SIM J1 or J4)
2. Power supply for
channel (PS1 or PS4)
MEL limiting (M) / (R) Limiters & Trips MEL Limiter is in control of Check MW and MVAR
the regulator. operating point.
MEL trip (M) / (R) Limiters & Trips The MEL Limiter failed to Investigate MW and MVAR
correct the under excitation levels previous to trip.
condition. The MEL
protection has tripped the
regulator via the 94E relay.
MEL xfer to Redundant (M) / (R) Limiters & Trips MEL limiter has transferred Check MW and MVAR
the system to the redundant operating point.
channel in an attempt to
avoid a trip.
Met PT fail (M) / (R) Alarm Status The channel specified has 1. Metering PT.
detected a loss of signal 2. Switch SW2.
from the metering PT. 3. Transformers AUPT4-6.
4. SIM(R) input J4.
OEL limiting (M) / (R) Limiters & Trips OEL Limiter is in control of 1. Check field current.
the regulator. 2. Adjust reference point.
Page 13 of 16 November 13, 2006
OEL timed out (M) / (R) Limiters & Trips Field Current remained 1. Check field current.
above the timing threshold 2. Adjust reference point
and the OEL will now begin
limiting.
OEL timing (M) / (R) Limiters & Trips Field Current has reached 1. Check field current.
the timing threshold. The 2. Adjust reference point
OEL timer will delay the
limiting for a predetermined
number of seconds.
OEL xfer to Redundant (M) / (R) Limiters & Trips OEL limiter has transferred Field current.
the system to the redundant
channel in an attempt to
avoid a trip.
OEL trip (M) / (R) Limiters & Trips The OEL Limiter failed to Investigate field current
correct the over excitation levels previous to trip.
condition. The OEL
protection has tripped the
regulator via the 94E relay.
OTT trip (M) / (R) Limiters & Trips The regulator has tripped via Excitation transformer
the 94E relay due to an temperature.
overtemperature condition of
the excitation transformer.
Outside trip (M) / (R) Limiters & Trips Regulator has been tripped 1. PPT overcurrent relay.
from outside sources such 2. Other sources.
as PPT overcurrent relay or
immediate trip signal to the
86 relay.
OVL limiting (M) / (R) Limiters & Trips OVL Limiter is in control of 1. Check terminal voltage.
the regulator. 2. Adjust voltage.
OVL trip (M) / (R) Limiters & Trips The OVL Limiter failed to Investigate generator
reduce the generator voltage before trip.
voltage. The OVL protection
has tripped the regulator via
the 94E relay.
Phase Lock Loop (M) / (R) Alarm Status VAB and VBC are not 1. Fuses ACLFU,
locking on the input AC ACLFUR.
frequency. 2. Fiber optic connections,
V-AB, V-BC, V-ABR, V-
BCR.
PPT Hi-Temp (M) / (R) Alarm Status The channel specified has Excitation transformer
received a hi-temp alarm temperature.
from the excitation
transformer.
PPT Hi-Hi-Temp (M) / (R) Alarm Status The channel specified has Excitation transformer
received a hi-hi-temp alarm temperature.
from the excitation
transformer.
Power Supply 1 (2) (M) / (R) Alarm Status Failure of primary power 1. Power supply 1 (PS1)
supply for channel. for main channel loss.
2. Power supply 2 (PS2)
for redundant channel
loss.
3. Fuses SACFU or
MACFU.
4. Transformer T3.
Red Local/Main Remote Local / Remote Two channels under control Follow instruction is TASK
of separate locations. GUIDE for Change
Remote/Local Control.
Reg. PT fail (M) / (R) Alarm Status The channel specified has 1. Regulator PT.
detected a loss of signal 2. Switch SW1.
from the metering PT. The 3. Transformers AUPT1-3.
regulator will now use the 4. SIM(R) input J1.
metering PT signal if one is
available.
Tracker Disabled Transfer Tracker has been disabled. Regulator should not be
Control The tracker allows the operated without the tracker.
redundant channel to ‘track’ Open the ‘Transfer Control’
the outputs of the main page. Press Tracker Status
channel. and select ENABLE
TRACKER.
Transfer Disabled Transfer The ability to transfer Open the ‘Transfer Control’
Control channels has been disabled. page. Press Transfer Status
and select ENABLE
TRANSFER.
Transformer Trip (M) / (R) Limiter & Trips Contacts on PPT overtemp 1. PPT temperature.
trip device have closed. 2. Digital input from PPT
contacts.
Two Channels not Ready Transfer Neither Main Channel nor See Main not Ready and
Control Redundant Channel are Redundant not ready.
ready for service.
UEL limiting (M) / (R) Limiters & Trips UEL Limiter is in control of Check MW and MVAR
the regulator. operating point.
UEL trip (M) / (R) Limiters & Trips The UEL Limiter failed to Investigate MW and MVAR
correct the under excitation operating levels previous to
condition. The UEL trip.
protection has tripped the
regulator via the 94E relay.
Purpose
The MDA is used to connect multiple exciter control modules (ECMs) to a single PanelMate or Modbus™ PLC. Only
one PanelMate or PLC can be connected to the MDA, as it would be the master for the Modbus communication. Up to
three ECMs can be connected to the MDA; the ECMs are Modbus slaves.
Application
For local PanelMate connection, up to three ECMs can be connected at jacks J2, J3, and J4 with standard Ethernet
cable (RJ-45 terminals 568A category 5 patch cord). The circuit card of the 4A36840G01 MDA takes care of the
conversion from two-wire communication of the ECM to the four-wire communication to the PanelMate. Next, connect
J1 to the local PanelMate with standard Cat-5 Ethernet patch cable.
For a remote PanelMate or Modbus PLC, connect the remote MDA to three ECMs with the Cat-5 Ethernet cable. This
MDA will be mounted in the exciter cubicle. To connect the remote Modbus device, use J5 with twisted, shielded
cable. Pin 1 is positive, pin 2 is negative, and pin 3 is used for the shield connection. In the control room, a second
MDA will be required to land the twisted pair at J5. Then use J1 to connect the remote PanelMate to the network with
a standard Ethernet patch cord.
Drawings
INSTRUCTION MANUAL
FOR
TIME OVERCURRENT RELAY
BE1-51
BE1-51
OVERCURRENT RELAY
R
Style No. V3E Z1P B2C1F POWER
Serial No. H12345678 R U
2 ELEMENT FUNCTION
TAP A B C D E F G H I J
T HIGH 2.25 3.00 4.50 5.25 6.75 7.50 9.00 9.75 11.25 12.00
LOW 0.75 1.00 1.50 1.75 2.25 2.50 3.00 3.25 3.75 4.00
P0048-48
Publication: 9137200997
Revision: D 08/07
INTRODUCTION
This instruction manual provides information about the operation and installation of the BE1-51 Time
Overcurrent Relay. To accomplish this, the following information is provided:
WARNING!
To avoid personal injury or equipment damage, only qualified personnel should
perform the procedures in this manual.
NOTE
Be sure that the relay is hard-wired to earth ground with no smaller than 12 AWG
copper wire attached to the ground terminal on the rear of the unit case. When
the relay is configured in a system with other devices, it is recommended to use a
separate lead to the ground bus from each unit.
Printed in USA
August 2007
CONFIDENTIAL INFORMATION
of Basler Electric, Highland Illinois, USA. It is loaned for confidential use, subject
to return on request, and with the mutual understanding that it will not be used in
any manner detrimental to the interest of Basler Electric.
It is not the intention of this manual to cover all details and variations in equipment, nor does this manual
provide data for every possible contingency regarding installation or operation. The availability and design
of all features and options are subject to modification without notice. Should further information be
required, contact Basler Electric.
BASLER ELECTRIC
ROUTE 143, BOX 269
HIGHLAND IL 62249 USA
http://www.basler.com, info@basler.com
PHONE +1 618.654.2341 FAX +1 618.654.2351
ii BE1-51 Introduction 9137200997 Rev D
REVISION HISTORY
The following information provides a historical summary of the changes made to the BE1-51 instruction
manual (9137200997). Revisions are listed in reverse chronological order.
Manual
Revision and Date Change
D, 08/07 • Updated Output Contacts ratings in Section 1.
• Moved content of Section 6, Maintenance to Section 4.
• Updated front panel illustrations to show laser graphics.
• Moved content of Section 7, Manual Change Information to manual
introduction.
• Added manual part number and revision to all footers.
• Updated cover drawings.
• Moved Time Overcurrent Characteristic Curves from Section 1 to new
Appendix A.
• Updated power supply burden data in Section 1.
• Updated Target Indicator description in Section 3.
C, 01/98 • Changed paragraph styles to new manual design.
• Added Note 3 to Figure 1-1.
• Corrected inductive output specification from 0.1 to 0.3 A.
• Changed TOC specification.
• Added instantaneous response time with graph 1-1.
• Deleted specification reference to field selectable switch in Type S
power supply.
• Corrected weight in kilograms for all case styles.
• Replaced Figure 1-49 with correct curve.
• Corrected Figure 1-51.
• Added multiturn potentiometer description to controls in Table 2-1.
• Corrected Range 9 entries in Table 2-2.
• Changed “Element D” in Table 2-4 to “Element N”.
• Deleted Figure 3-1.
• Revised the power supply functional description to accommodate new
wide range power supplies.
• Corrected Figures 4-2, 4-3, and 4-4.
• Deleted Figure 4-5.
B, 09/93 • Added Figures 4-4 and 4-6 through 4-9.
• Restructured Section 5, Operational Test.
• Corrected minor typographical errors.
A, 02/93 • Added characteristic curves for integrating algorithm, Figures 1-39
through 1-70.
• Changed Figure 1-2.
• Corrected minor discrepancies.
—, 07/92 • Initial release
Figures
Figure 1-1. Style Number Identification Chart ........................................................................................... 1-4
Figure 1-2. Typical Instantaneous Response Time................................................................................... 1-5
Tables
Table 1-1. Power Supply Specifications.................................................................................................... 1-6
STANDARD FEATURES
Time Overcurrent Functions
Time overcurrent elements pick up over a range of 0.1 to 0.8 amperes, 0.3 to 2.4 amperes, 0.5 to 4.0
amperes, 1.5 to 12.0 amperes, 0.1 to 2.4 amperes, or 0.5 to 12.0 amperes and provide an adjustable time
delay that is proportional to the overcurrent. Time delay is initiated when the sensed current exceeds the
pickup point. When the current drops below the pickup point, the timing circuit is reset immediately. At
reset, the output contacts, if operated, are restored to normal.
Adjustment of the overcurrent pickup point is provided by controls on the relay front panel. Time delay is a
function of the characteristic curve that has been selected. Time delay is settable from 00 to 99 on the
TIME DIAL thumbwheel switch located on the front panel. Curve type is selected either as an option or, in
some models, is switch selectable.
Sixty-nine characteristic curves and three timing options are available. They are:
Characteristic curves:
• Seven inverse time
• Nine I2t
• Seven inverse time with extended timing range
• Nine I2t with extended timing range
• Five British Standard 142 (E curves)
• Seven integrating inverse time
• Nine integrating I2t
• Seven integrating inverse time with extended timing range
• Nine integrating I2t with extended timing range
Timing option Z1 (switch selectable - 16 position) B and C curves:
• Seven inverse time
• Nine I2t
Timing option Z1 with option 2-D or 2-E (switch selectable - 16 position) B and C curves:
• Seven inverse time with extended timing range
• Nine I2t with extended timing range
Timing option Z2 (switch selectable - 16 position) B and E (British Standard 142) curves:
• Seven inverse time
• One I2t
• Five British Standard (BS) 142 (E curves)
Timing option Z2 with option 2-D or 2-E (switch selectable - 16 position) B and E (BS142) curves:
• Seven inverse time with extended timing range
• One I2t with extended timing range
• Five British Standard 142 (E curves)
Timing option Z3 (switch selectable - 16 position) integrating B and C curves:
• Seven integrating inverse time
• Nine integrating I2t
Timing option Z3 with option 2-D or 2-E (switch selectable - 16 position) integrating extended B and C
curves:
• Seven integrating inverse time with extended timing range
• Nine integrating I2t with extended timing range
Non-Integrating Timing
Timing options Z1 and Z2 and the characteristic curves available with those options use non-integrating
timing. Non-integrating timing is accomplished by timing at a gate that is not solely dependent on the
magnitude of the applied multiple of pickup current. The time-out value is calculated based on the type of
time curve characteristic selected, time dial setting, and the magnitude of the applied multiple of pickup
current. The time-out value is continuously updated during the timing cycle. When pickup is exceeded, a
timer is initiated. When the timer elapsed time exceeds the calculated time-out value, a time trip output
signal is generated.
This type of non-integrating time delay characteristic exhibits a dynamic characteristic that is immediately
responsive to changes of the applied multiple of pickup current.
Integrating Timing
Timing option Z3 and the characteristic curves available for that option uses integrating timing. Integrating
timing is accomplished by summing time increments that are based on the magnitude of the applied
multiple of pickup current, the time curve characteristic selected, and the time dial value. These time
increments are summed until a predetermined value is exceeded, then a time trip output signal is
generated.
This type of integrating time delay characteristic simulates the operating characteristics of an
electromechanical overcurrent relay.
Built-In Test
A built-in test (BIT) switch mounted on the Logic Board provides diagnostic troubleshooting and
calibration.
OPTIONS
Timing
An extended timing option multiplies by approximately 5.7, the standard time delays. The resulting curves
are shown following the standard curves in Appendix A - e.g., Figure A-1 is timing type B1 and Figure A-2
is the timing type B1 with extended timing range.
When timing option Z1, Z2, or Z3 is specified, a printed circuit board mounted selector switch allows a
choice of up to sixteen different time overcurrent functions. Timing option Z1 or Z3 may be further
specified as standard or extended time, depending upon option 2 selection.
Neutral Defeat
When neutral defeat is specified, a front panel switch allows neutral current sensing to be disabled. This
function permits the user to energize desired circuits and not trip because of imbalanced current in the
neutral circuit. After the circuits are balanced, the neutral defeat function can be switched off and neutral
current sensing protection is provided.
Power Supply
Five power supply options are available. They are:
• 24 Vdc
• 48 Vdc
• 125 Vdc and 100/125 Vac
• 48 Vdc or 125 Vdc and 100/125 Vac
• 250 Vdc and 240 Vac
Targets
Single-phase relays have two function targets that indicate when the time delay or instantaneous
element(s) have operated. On multiple phase relays, additional targets indicate which phase or neutral
element(s) operated.
Function targets may be specified as either internally operated or current operated by a minimum of 0.2
amperes through the output trip circuit. When current operated, the output circuit must be limited to 30
amperes for 0.2 seconds, 7 amperes for 2 minutes, and 3 amperes continuously.
Outputs
Optional normally opened, normally closed, or SPDT auxiliary output contacts may be selected. Contacts
actuate when the output relay is energized. Internally operated front panel mounted targets, and front
panel targets operated by the dc current in the output circuit are available for the time overcurrent and
instantaneous overcurrent functions. Optional front panel mounted PUSH-TO-ENERGIZE-OUTPUT
pushbuttons allow direct actuation of each output relay for external circuit testing.
Instantaneous Outputs
One or two instantaneous overcurrent outputs are optionally available. Each is adjustable up to 40 times
the time overcurrent pickup point. When the sensed current exceeds the instantaneous overcurrent
pickup point, an output relay is energized. An independent front panel control (INST 1 or INST 2) adjusts
the pickup point for each optional output. If more than one phase is applied to the relay, the instantaneous
pickup point will be the same for all phases. If neutral current is sensed, a front panel INST 1 (NEUTRAL)
provides adjustment of the neutral pickup point. Instantaneous overcurrent elements are not voltage
controlled.
Packaging
Each relay is mounted in a drawout cradle and enclosed in a standard utility style case with either semi-
flush or projection mounting (depending upon case style selected). Circuit components are accessed by
removing the individual printed circuit boards from the relay cradle. Use an extender card (Basler Electric
part number: 9165500199) to test and troubleshoot the relay. An available test plug (Basler Electric part
number: 10095 or G.E. part number 12XLA12A1) allows the relay to be tested in place without disturbing
external control circuit wiring.
H - Three-Phase-and-Neutral sensing
3 - Sensing input range of 1.5 to 12.0 amperes for phase and 0.5 to 4.0 amperes for neutral
E - Normally open outputs
Z1 - Switch selectable time curves
P - Operating power derived from 125 Vdc or 120 Vac
B - Current operated targets
2 - Two instantaneous elements
C - Push-to-energize outputs
1 - Normally open auxiliary timed output relay
F - Semi-flush mounting
Instantaneous Response
Figure 1-2 shows the typical response for the instantaneous pickup element.
Output Circuits
Resistive Ratings
120 Vac: Make, break, and carry 7 Aac continuously
250 Vdc: Make and carry 30 Adc for 0.2 s, carry 7 Adc continuously, and break 0.3 Adc
500 Vdc: Make and carry 15 Adc for 0.2 s, carry 7 Adc continuously, and break 0.3 Adc
Inductive Ratings
120 Vac, 125 Vdc, 250 Vdc: Break 0.3 A (L/R = 0.04)
Target Indicators
Function targets may be specified as either internally operated or current operated by a minimum of 0.2
amperes through the output trip circuit. When current operated, the output circuit must be limited to 30
amperes for 0.2 seconds, 7 amperes for 2 minutes, and 3 amperes continuously.
Power Supply
Power for the internal circuitry may be derived from a variety of ac or dc external power sources as
indicated in Table 1-1.
Input Voltage
Type Burden at Nominal
Nominal Range
∗ Type R power supply may require 14 Vdc to begin operation. Once operating, the voltage may be
reduced to 12 Vdc.
Isolation
In accordance with IEC 255-5 and ANSI/IEEE C37.90, one-minute dielectric (high potential) tests as
follows:
All circuits to ground: 2,121 Vdc
Input to output circuits: 1,500 Vac or 2,121 Vdc
UL Recognized
UL recognized per Standard 508, UL File No. E97033. Note: Output contacts are not UL recognized for
voltages greater than 250 volts and input power supply voltages greater than 150 volts.
GOST-R
Gost-R certified No. POCC US.ME05.B03391; complies with the relevant standards of Gosstandart of
Russia. Issued by accredited certification body POCC RU.0001.11ME05.
Operating Temperature
The operating temperature range is from -40°C (-40°F) to +70°C (+158°F).
Storage Temperature
The storage temperature range is from -65°C (-85°F) to +100°C (+212°F).
Shock
In standard tests, the relay has withstood 15 g in each of three mutually perpendicular planes without
structural damage or degradation of performance.
Vibration
In standard tests, the relay has withstood 2 g in each of three mutually perpendicular planes, swept over
the range of 10 to 500 Hz for six sweeps, 15 minutes each sweep without structural damage or
degradation of performance.
Weight
Single-Phase: 13.0 lbs. (5.90 kg)
Two-Phase and Neutral: 14.0 lbs. (6.35 kg)
Three-Phase: 14.0 lbs. (6.35 kg)
Three-Phase and Neutral: 14.4 lbs. (6.53 kg)
Case Size
S1 (Refer to Section 4 for case dimensions.)
Figures
Figure 2-1. Location of Controls and Indicators ........................................................................................ 2-1
Tables
Table 2-1. Controls and Indicators ............................................................................................................ 2-2
Table 2-2. Sensing Input Ranges .............................................................................................................. 2-3
Table 2-3. Target Installation Configurations ............................................................................................ 2-4
O P Q R S
M BE1-51 E
OVERCURRENT RELAY
Style No. V3E Z1P B2C1F POWER
F
R
2 ELEMENT FUNCTION H
TAP A B C D E F G H I J
HIGH 2.25 3.00 4.50 5.25 6.75 7.50 9.00 9.75 11.25 12.00
K T
LOW 0.75 1.00 1.50 1.75 2.25 2.50 3.00 3.25 3.75 4.00
I
P0048-49
∗ For relays with sensing input ranges 1 or 9, connect the system wiring to the current sensing
terminals for the desired range (HIGH or LOW).
X X
K X X X
X X X X
X X X X
G X X X X X X
X X X X X X X
X X X X X
H X X X X X X X
X X X X X X X X
X X X X X
X X X X X X X
X X X X X X X
Figures
Figure 3-1. Functional Block Diagram ....................................................................................................... 3-1
Current Sensing
All relay models (except three-phase-and-neutral units) have two sensing ranges for each phase. Each
high/low sensing range has its own set of input terminal connections.
• Five ampere CTs have: LOW (0.5 A to 4.0 A) and HIGH (1.5 A to 12.0 A).
• One ampere CTs have: LOW (0.1 A to 0.8 A) and HIGH (0.3 A to 2.4 A).
Three-phase-and-neutral sensing units, however, have one of four possible combinations of input sensing
ranges with one range for neutral and one range for the phases.
• Five ampere CTs have: 0.5 A to 4.0 A and 1.5 A to 12.0 A.
• One ampere CTs have: 0.1 A to 0.8 A and 0.3 A to 2.4 A.
Neutral Defeat
Front panel mounted switch allows neutral current sensing to be disabled. When the switch is set to ON,
a current imbalance in the neutral circuit will not trip the output contacts.
Multiplexor
The multiplexor sequentially switches a voltage representing each of the sensed input currents to the
analog-to-digital converter and level detector.
Auxiliary Outputs
In addition to the output relays, an auxiliary relay, having the same or a different contact configuration,
may be specified. Both the output and the auxiliary relays will remain energized for the duration of the
overcurrent condition.
Push-to-Energize Pushbuttons
If either option 2-C or 2-E is present, each individual output relay can be directly energized for test
purposes by the actuation of a front panel PUSH-TO-ENERGIZE OUTPUT pushbutton. The pushbutton is
actuated by the insertion of a thin, non-conducting rod through an access hole in the front panel.
Target Indicators
Target indicators are optional components selected when a relay is ordered. The electronically latched
and reset targets consist of red LED indicators located on the relay front panel. A latched target is reset
by operating the target reset switch on the front panel. If relay operating power is lost, any illuminated
(latched) targets are extinguished. When relay operating power is restored, the previously latched targets
are restored to their latched state.
A relay can be equipped with either internally operated targets or current operated targets.
Internally Operated Targets
The relay trip outputs are directly applied to drive the appropriate target indicator. Each indicator is
illuminated regardless of the current level in the trip circuit.
Current Operated Targets
A current operated target is triggered by closure of the corresponding output contact and the presence of
at least 200 milliamperes of current flowing in the trip circuit.
Note that the front panel function targets (TIMED, INST 1, etc.) may be either internally or current
operated. Phase and neutral indicators are current operated only if the instantaneous options are not
included and if current operated targets are specified.
9137200997 Rev D BE1-51 Functional Description 3-3
NOTE
Prior to August 2007, BE1-51 target indicators consisted of magnetically latched,
disc indicators. These mechanically latched target indicators have been replaced
by the electronically latched LED targets in use today.
Figures
Figure 4-1. Outline Dimensions, Side View, Semi-Flush Mounted, Double-Ended Case......................... 4-2
Figure 4-2. Outline Dimensions, Side View, Projection Mounted, Double-Ended Case ........................... 4-3
Figure 4-3. Outline Dimensions, Front View, Case Cover ........................................................................ 4-4
Figure 4-4. Panel Cutting and Drilling Dimensions, Semi-Flush Mounting, Double-Ended Case............. 4-5
Figure 4-5. Panel Drilling Dimensions, Projection Mounting, Double-Ended Case .................................. 4-6
Figure 4-6. Typical External Connections, Current Operated Targets, DC Powered ............................... 4-7
Figure 4-7. Typical Sensing External Connections, Sensing Input Type G or K....................................... 4-8
Figure 4-8. Typical Sensing External Connections, Sensing Input Type I or X ........................................ 4-8
Figure 4-9. Typical Sensing External Connections, Sensing Input Type H or V....................................... 4-9
Figure 4-10. Typical Internal Diagram, Sensing Input Type K ................................................................ 4-10
Figure 4-11. Typical Internal Diagram, Sensing Input Type I or X .......................................................... 4-11
Figure 4-12. Typical Internal Diagram, Sensing Input Type G ................................................................ 4-12
Figure 4-13. Typical Internal Diagram, Sensing Input Type H or V......................................................... 4-13
CAUTION
When the connection plugs are removed, the relay is disconnected from the
operating circuit and will not provide system protection. Always be sure that
external operating (monitored) conditions are stable before removing a relay for
inspection, test, or service.
NOTE
Be sure that the relay is hard-wired to earth ground with no smaller than 12 AWG
copper wire attached to the ground terminal on the rear of the case. When the
relay is configured in a system with other devices, it is recommended to use a
separate lead to the ground bus from each device.
MOUNTING
Because the relay is of solid-state design, it does not have to be mounted vertically. Any convenient
mounting angle may be chosen. Refer to Figures 4-1 through 4-5 for relay outline dimensions and panel
drilling diagrams.
Figure 4-1. Outline Dimensions, Side View, Semi-Flush Mounted, Double-Ended Case
STORAGE
This protective relay contains aluminum electrolytic capacitors which generally have a life expectancy in
excess of 10 years at storage temperatures less than 40°C (104°F). Typically, the life expectancy of a
capacitor is cut in half for every 10°C rise in temperature. Storage life can be extended if, at one year
intervals, power is applied to the relay for a period of 30 minutes.
Figures
Figure 5-1. Test Setup for Sensing Input Type K (Single-Phase Sensing) ............................................... 5-2
Figure 5-2. Test Setup for Sensing Input Type G (Three-Phase Sensing) ............................................... 5-2
Figure 5-3. Test Setup for Sensing Input Type H or V (Three-Phase with Neutral Sensing).................... 5-3
Figure 5-4. Test Setup for Sensing Input Type I or X (Two-Phase with Neutral Sensing)........................ 5-3
OPERATIONAL TEST
Preliminary Instructions
Perform the following steps before going on to any testing.
Step 1. Connect the relay test setup in accordance with Figures 5-1 through 5-4, depending upon the
sensing input type for your relay (see Figure 1-1, Style Number Identification Chart).
(a) Sensing Input Type K (Single-Phase Sensing). Refer to Figure 5-1.
NOTE
For relays having the above sensing, only the front panel LOW range current
sense terminal(s) should be connected for a complete check of the relay.
NOTE
For relays having the above sensing, only the from panel LOW range current
sense terminal(s) should be connected for a complete check of the relay.
For all three-phase relays, the test signals must connect to both the current and
voltage terminals for the same phase.
(c) Sensing Input Type H or V (Three-Phase with Neutral Sensing). Refer to Figure 5-3.
Ensure that the timed output terminals 1 and 10 are connected. Also, verify that either A,
B, or C current sense terminals are connected initially (N terminals will be connected later
in the test).
Figure 5-1. Test Setup for Sensing Input Type K (Single-Phase Sensing)
Figure 5-2. Test Setup for Sensing Input Type G (Three-Phase Sensing)
Figure 5-4. Test Setup for Sensing Input Type I or X (Two-Phase with Neutral Sensing)
NOTE
During this test, disregard any indication on the test setup timer.
NOTE
For relays having three-phase sensing (Sensing Input Type G or V), only a single
input phase needs to be connected, since this is sufficient for a complete test of
the Time Delay. For relays that include neutral sensing (Sensing Input Type H, I,
V, or X) this test includes reconnecting the Test Output to the Neutral Sensing
terminals for testing the Timed Output during neutral sensing.
NOTE
Due to delays inherent in the test equipment, the time delay for the following test
may appear to exceed these limits.
Step 9. On the appropriate time overcurrent curve chart (Figures A-1 through A-69), locate the line
representing 5 times the tap value (from Step 5) where it intersects the particular curve
representing the front panel TIME DIAL setting of 20 (from Step 4). The resulting time delay
value in seconds should be within ±5% of the timer reading [from Step 7(2)].
Step 10. Adjust the front panel TIME DIAL to 40, 60, and 99, each time repeating Steps 6 through 9.
NOTE
For relays having two-phase-and-neutral, three-phase, or three-phase-and-
neutral sensing (Sensing Input Types G, H, I, V, or X) it is not necessary to
repeat this test for the remaining phases.
For relays having two-phase-and-neutral, or three-phase-and-neutral sensing
(Sensing Input Types H, I, V, or X) perform Steps 11 through 20.
For relays having single-phase or three-phase sensing (Sensing Input Types G
or K) with instantaneous overcurrent option 1-1 or 1-2, proceed to the
instantaneous overcurrent test.
Step 11. Remove the power and reconnect the test output to the neutral current sensing input of the
relay as shown in Figures 5-3 and 5-4 (terminals 17 and 18).
Step 12. Set the front panel TAP (NEUTRAL) selector to B.
Step 13. Rotate the front panel CAL (NEUTRAL) control fully CW.
Step 14. Rotate the front panel TIME DIAL (NEUTRAL) to 20.
Step 15. Ensure that all relay targets have been reset.
Step 16. Adjust the test set for an overcurrent threshold of precisely 5 times the front panel TAP
(NEUTRAL) selector B setting as measured by the ammeter.
Step 17. Apply input current to the relay and initiate the test setup timer.
RESULTS: Observe that the appropriate front panel TIMING (NEUTRAL) indicator illuminates.
Step 18. When the time delay ends, the timed output relay is energized.
RESULTS: (1) The front panel TIMING (NEUTRAL) indicator extinguishes.
(2) The test setup timer stops. (Record count for use in Step 20.)
(3) If target Type A or B is present:
(a) Front panel FUNCTION-TIME target (if present) trips.
(b) Appropriate front panel ELEMENT target A, B, or C (if present) trips.
Step 19. Remove input current and (if present) reset the relay front panel targets.
Step 20. On the appropriate time overcurrent curve chart (Figures A-1 through A-69), locate the line
representing 5 times the tap value (from Step 5) where it intersects the particular curve
representing the front panel TIME DIAL (NEUTRAL) setting of 20 (from Step 14). The resulting
time delay value in seconds should be within ±5% of the timer reading [from step 18(2)].
NOTE
For relays having three-phase sensing (Sensing Input Types G or V), only a
single input phase is connected since this is sufficient for a complete test of the
instantaneous overcurrent sensing and output.
For relays that include neutral sensing (Sensing Input Types H, I, V, or X), this
test includes reconnecting the test output to the neutral sensing terminals for
testing the instantaneous 1 output during neutral sensing.
Step 12. For the neutral sensing, connect the relay as shown in Figures 5-3 and 5-4, then repeat Steps 2
through 11, substituting the following:
(a) The front panel TAP (NEUTRAL) selector instead of the front panel TAP selector (Step 3).
(b) The front panel INST 1 (NEUTRAL) control instead of the front panel INST 1 control
(Step 4).
Step 13. Reconnect the test setup to the INST 2 output terminals (11 and 12) as shown in Figure 5-1,
then repeat Steps 4 through 11, substituting the following:
(a) Front panel INST 2 control instead of the front panel INST 1 control (Step 3).
(b) Front panel FUNCTION-INST 2 target instead of the front panel INST 1 target (Step 4).
(c) Instantaneous 2 output relay instead of the instantaneous 1 output relay (Step 2).
NOTE
Selection of one of the specific overcurrent pickup points provided by the front
panel TAP selector (and with the front panel TAP CAL control fully CW) will
permit a pickup point within ±5% of the selector value without having to connect
the relay to a test setup to verify the setting. If present, the front panel TAP
(NEUTRAL) selector and the front panel CAL (NEUTRAL) control provide this
function for the neutral overcurrent pickup point
However, if the desired pickup point falls between these front panel TAP selector
settings, or if the instantaneous overcurrent option 1-1 or 1-2 is present, the relay
should be connected to a test setup for a precise setting, then the following steps
should be performed.
Step 1. Connect the test setup to the relay according to the sensing input type present in the relay as
follows:
(a) Sensing Input Type K: Refer to Figure 5-1. Because the relay front panel TIMING indicator
provides the needed pickup indication, do not connect the test setup to the output
terminals. The current sense terminals for the desired range (HIGH or LOW), however,
should be connected to the relay.
(b) Sensing Input Types I or X: Refer to Figure 5-4. Because the relay front panel TIMING
indicator provides the needed pickup indication, do not connect the test setup to the output
terminals. The front panel TAP selector is ganged and the adjustment of one input phase
automatically aligns the other, thus, only one set of current sense terminals need be
connected. For adjustment of the front panel TAP (NEUTRAL) selector, the relay is
reconnected for neutral sensing by this procedure.
(c) Sensing Input Type G: Refer to Figure 5-2. Because the relay front panel TIMING indicator
provides the needed pickup indication, do not connect the test setup to the output
terminals. The desired range terminals (HIGH or LOW), however, should be connected to
the relay. The front panel TAP selector is ganged and the adjustment of one input phase
automatically aligns the others, thus, only one set of current sense terminals need be
connected.
NOTE
For relays with two-phase-and-neutral or three-phase-and-neutral sensing
(Sensing Input Types I or V), perform Steps 10 through 15. Otherwise, the time
overcurrent pickup point calibration ends here (unless instantaneous 1 or 2
overcurrent calibration is to be performed later in these procedures).
Step 10. Reconnect the test set output to the neutral sense terminals. See Figures 5-3 or 5-4.
Step 11. Adjust the current to the desired time overcurrent pickup point for the relay.
Step 12. Set the front panel TAP (NEUTRAL) selector to the closest setting above the desired pickup
point.
Step 13. Rotate the front panel CAL (NEUTRAL) control fully CW.
Step 14. Slowly adjust the front panel CAL (NEUTRAL) control CCW until the front panel TIMING
(NEUTRAL) indicator just illuminates to establish the desired time overcurrent pickup point for
neutral sensing.
Step 15. Remove input current.
NOTE
Pickup point calibration ends here.
Time Overcurrent Curve Selection (Timing Type Z1, Z2, and Z3 Only)
Step 1. Remove the relay cradle front cover to gain access to the logic board time overcurrent
characteristic curve selector.
Step 2. Remove the Phillips screws from both sides of the unit and remove the front panel. See Figure
2-1 for the location of the logic board and curve selector.
Step 3. Select the desired curve. See Table A-2 for the desired curve and selector position.
Step 4. Re-install the front panel and the front cover.
NOTE
If Timing Type Z1, Z2, or Z3 is installed, refer to time overcurrent curve selection
to obtain the desired set of time overcurrent curves (see Figures A-1 through A-
69). Then proceed to Step 1, following.
If Timing Type Z1, Z2, or Z3 is not installed, determine the timing type from the
model and style number for a specific relay. Then select the appropriate timing
curve (see Figures A-1 through A-69). Proceed to the following, Step 1.
Step 1. Referring to the appropriate time overcurrent characteristic curve, select the desired time delay
on the front panel TIME DIAL for the anticipated input overcurrent difference (multiples-of-
pickup current) from the selected time overcurrent pickup point as follows:
(Selected Pickup Point) - (Anticipated Input Overcurrent) = Overcurrent Difference from Pickup
Step 2. Set the front panel TIME DIAL as follows:
(a) On the appropriate curve, plot upward from the multiples-of-pickup-current value until the
horizontal line opposite the desired time delay (time-in-seconds) is reached. The setting
curve nearest the plot point should then be entered on the front panel TIME DIAL.
(b) Using Figure 1-6 as an example, if the overcurrent is expected to be 4 times the pickup
point value and time delay of 4 seconds is desired, plot upward from the point 4 on the
multiples-of-pickup-current axis until the point 4 from the time-in-seconds axis is
crossed. The curve for a setting of 52 crosses the plot point and should be entered on the
front panel TIME DIAL.
(c) For a lesser overcurrent difference from the pickup point, the time delay will be greater, so
that for a multiple of 3 times the pickup current, the time delay for the previous front panel
setting of 52 will be 5.8 seconds.
NOTE
Because the lower limit for this pickup is determined by the front panel TAP
selector setting and the front panel TAP (CAL) control position, ensure that these
adjustments have been performed as in the paragraph TAP and TAP
(NEUTRAL) Selector Setting.
CAUTION
Steps 3 through 8 provide the application of overcurrent for short periods to allow
adjustment while avoiding overheating of the input sensing transformers. To
avoid damaging the relay, do not attempt to apply a constant high level of input
current for adjustment of the front panel INST 1, INST 1 (NEUTRAL), or INST 2
controls.
Step 3. Set the front panel INST 1 control to a position approximating the desired instantaneous 1
overcurrent pickup point for the relay.
Step 4. Apply current to the relay.
Step 5. Rapidly increase the overcurrent input to the relay until the instantaneous output relay just
energizes. Note the overcurrent threshold reading on the ammeter.
Step 6. Remove input current.
Step 7. Reset the INST TARGET (if present).
Step 8. If the overcurrent threshold reading from Step 5 was too high or low, adjust the front panel
INST 1 control CCW to lower (or CW to raise) the instantaneous 1 overcurrent pickup point.
Repeat Steps 4 through 8. If the overcurrent threshold reading from Step 5 was NOT too high
or low, proceed to Step 9.
NOTE
For relays with two-phase-and-neutral or three-phase-and-neutral sensing
(Sensing Input Types I or X), perform Steps 9 through 14.
Step 9. Reconnect the output to the neutral current sense terminals. See Figures 5-3 or 5-4.
Step 10. Set the front panel INST 1 (NEUTRAL) control to a position approximating the desired neutral
instantaneous 1 overcurrent pickup point for the relay.
Step 11. Apply current to the relay.
Step 12. Rapidly increase the overcurrent input to the relay until the instantaneous output relay just
energizes. Note the test set overcurrent threshold reading on the ammeter.
Step 13. Remove the input current.
Step 14. Reset the INST TARGET (if present).
Step 15. If the overcurrent threshold reading from Step 13 was too high or low, adjust the front panel
INST 1 (NEUTRAL) control CCW to lower (or CW to raise) the Neutral Instantaneous 1
Overcurrent Pickup Point. Repeat Steps 9 through 14. If NOT, proceed to the next test.
Figures
Figure A-1. Timing Type B1, Short Inverse ...............................................................................................A-3
Figure A-2. Timing Type B1, Short Inverse with Extended Timing Range................................................A-3
Figure A-3. Timing Type B2, Long Inverse................................................................................................A-4
Figure A-4. Timing Type B2, Long Inverse with Extended Timing Range ................................................A-4
Figure A-5. Timing Type B3, Definite Time ...............................................................................................A-5
Figure A-6. Timing Type B3, Definite Time with Extended Timing Range ................................................A-5
Figure A-7. Timing Type B4, Moderately Inverse......................................................................................A-6
Figure A-8. Timing Type B4, Moderately Inverse with Extended Timing Range ......................................A-6
Figure A-9. Timing Type B5, Inverse.........................................................................................................A-7
Figure A-10. Timing Type B5, Inverse with Extended Timing Range .......................................................A-7
Figure A-11. Timing Type B6, Very Inverse ..............................................................................................A-8
Figure A-12. Timing Type B6, Very Inverse with Extended Timing Range ...............................................A-8
Figure A-13. Timing Type B7, Extremely Inverse......................................................................................A-9
Figure A-14. Timing Type B7, Extremely Inverse with Extended Timing Range ......................................A-9
Figure A-15. Timing Type B8, I2t .............................................................................................................A-10
Figure A-16. Timing Type B8, I2t with Extended Timing Range ..............................................................A-10
Figure A-17. Timing Type C1, I2t with Limit #1 ........................................................................................A-11
Figure A-18. Timing Type C1, I2t with Limit #1 and Extended Timing Range .........................................A-11
Figure A-19. Timing Type C2, I2t with Limit #2 ........................................................................................A-12
Figure A-20. Timing Type C2, I2t with Limit #2 and Extended Timing Range .........................................A-12
Figure A-21. Timing Type C3, I2t with Limit #3 ........................................................................................A-13
Figure A-22. Timing Type C3, I2t with Limit #3 and Extended Timing Range .........................................A-13
Figure A-23. Timing Type C4, I2t with Limit #4 ........................................................................................A-14
Figure A-24. Timing Type C4, I2t with Limit #4 and Extended Timing Range .........................................A-14
Figure A-25. Timing Type C5, I2t with Limit #5 ........................................................................................A-15
Figure A-26. Timing Type C5, I2t with Limit #5 and Extended Timing Range .........................................A-15
Figure A-27. Timing Type C6, I2t with Limit #6 ........................................................................................A-16
Figure A-28. Timing Type C6, I2t with Limit #6 and Extended Timing Range .........................................A-16
Figure A-29. Timing Type C7, I2t with Limit #7 ........................................................................................A-17
Figure A-30. Timing Type C7, I2t with Limit #7 and Extended Timing Range .........................................A-17
Figure A-31. Timing Type C8, I2t with Limit #8 ........................................................................................A-18
Figure A-32. Timing Type C8, I2t with Limit #8 and Extended Timing Range .........................................A-18
Figure A-33. Timing Type E2, BS 142 Long Inverse...............................................................................A-19
Figure A-34. Timing Type E4, BS 142 Inverse (1.3 Sec) ........................................................................A-19
Figure A-35. Timing Type E5, BS 142 Inverse (2.9 Sec) ........................................................................A-20
Figure A-36. Timing Type E6, BS 142 Very Inverse ...............................................................................A-20
Figure A-37. Timing Type E7, BS 142 Extremely Inverse.......................................................................A-21
Figure A-38. Timing Type B1, Short Inverse with Integrated Algorithm ..................................................A-22
Figure A-39. Timing Type B1, Short Inverse with Integrated Algorithm and Extended Timing...............A-22
Figure A-40. Timing Type B2, Long Inverse with Integrated Algorithm...................................................A-23
Figure A-41. Timing Type B2, Long Inverse with Integrated Algorithm and Extended Timing ...............A-23
Figure A-42. Timing Type B3, Definite Time with Integrated Algorithm ..................................................A-24
Figure A-43. Timing Type B3, Definite Time with Integrated Algorithm and Extended Timing ...............A-24
Figure A-44. Timing Type B4, Moderately Inverse with Integrated Algorithm.........................................A-25
Figure A-45. Timing Type B4, Moderately Inverse with Integrated Algorithm and Extended Timing .....A-25
Figure A-46. Timing Type B5, Inverse with Integrated Algorithm............................................................A-26
Figure A-47. Timing Type B5, Inverse with Integrated Algorithm and Extended Timing ........................A-26
Figure A-48. Timing Type B6, Very Inverse with Integrated Algorithm ...................................................A-27
Figure A-49. Timing Type B6, Very Inverse with Integrated Algorithm and Extended Timing ................A-27
9137200997 Rev D BE1-51 Time Overcurrent Characteristic Curves i
Figure A-50. Timing Type B7, Extremely Inverse with Integrated Algorithm...........................................A-28
Figure A-51. Timing Type B7, Extremely Inverse with Integrated Algorithm and Extended Timing .......A-28
Figure A-52. Timing Type B8, I2t with Integrated Algorithm ....................................................................A-29
Figure A-53. Timing Type B8, I2t with Integrated Algorithm and Extended Timing .................................A-29
Figure A-54. Timing Type C1, I2t Limit #1 with Integrated Algorithm ......................................................A-30
Figure A-55. Timing Type C1, I2t Limit #1 with Integrated Algorithm ......................................................A-30
Figure A-56. Timing Type C2, I2t Limit #2 with Integrated Algorithm ......................................................A-31
Figure A-57. Timing Type C2, I2t Limit #2 with Integrated Algorithm and Extended Timing ...................A-31
Figure A-58. Timing Type C3, I2t Limit #3 with Integrated Algorithm ......................................................A-32
Figure A-59. Timing Type C3, I2t Limit #3 with Integrated Algorithm and Extended Timing ...................A-32
Figure A-60. Timing Type C4, I2t Limit #4 with Integrated Algorithm ......................................................A-33
Figure A-61. Timing Type C4, I2t Limit #4 with Integrated Algorithm and Extended Timing ...................A-33
Figure A-62. Timing Type C5, I2t Limit #5 with Integrated Algorithm ......................................................A-34
Figure A-63. Timing Type C5, I2t Limit #5 with Integrated Algorithm and Extended Timing ...................A-34
Figure A-64. Timing Type C6, I2t Limit #6 with Integrated Algorithm ......................................................A-35
Figure A-65. Timing Type C6, I2t Limit #6 with Integrated Algorithm and Extended Timing ...................A-35
Figure A-66. Timing Type C7, I2t Limit #7 with Integrated Algorithm ......................................................A-36
Figure A-67. Timing Type C7, I2t Limit #7 with Integrated Algorithm and Extended Timing ...................A-36
Figure A-68. Timing Type C8, I2t Limit #8 with Integrated Algorithm ......................................................A-37
Figure A-69. Timing Type C8, I2t Limit #8 with Integrated Algorithm and Extended Timing ...................A-37
Tables
Table A-1. Timing Choices with Available Curves.....................................................................................A-1
Table A-2. Timing Curve Selection Table..................................................................................................A-2
1.5 1.5
Figure A-1. Timing Type B1, Short Inverse Figure A-2. Timing Type B1, Short Inverse
with Extended Timing Range
P0049-05
Figure A-3. Timing Type B2, Long Inverse Figure A-4. Timing Type B2, Long Inverse
with Extended Timing Range
Figure A-5. Timing Type B3, Definite Time Figure A-6. Timing Type B3, Definite Time
with Extended Timing Range
P0049-09
Figure A-7. Timing Type B4, Moderately Inverse Figure A-8. Timing Type B4, Moderately Inverse
with Extended Timing Range
P0049-11
Figure A-9. Timing Type B5, Inverse Figure A-10. Timing Type B5, Inverse
with Extended Timing Range
Figure A-11. Timing Type B6, Very Inverse Figure A-12. Timing Type B6, Very Inverse with
Extended Timing Range
Figure A-13. Timing Type B7, Extremely Inverse Figure A-14. Timing Type B7, Extremely Inverse
with Extended Timing Range
Figure A-15. Timing Type B8, I2t Figure A-16. Timing Type B8, I2t
with Extended Timing Range
Figure A-17. Timing Type C1, I2t with Limit #1 Figure A-18. Timing Type C1, I2t with Limit #1
and Extended Timing Range
Figure A-19. Timing Type C2, I2t with Limit #2 Figure A-20. Timing Type C2, I2t with Limit #2
and Extended Timing Range
P0049-23
Figure A-21. Timing Type C3, I2t with Limit #3 Figure A-22. Timing Type C3, I2t with Limit #3
and Extended Timing Range
Figure A-23. Timing Type C4, I2t with Limit #4 Figure A-24. Timing Type C4, I2t with Limit #4
and Extended Timing Range
Figure A-25. Timing Type C5, I2t with Limit #5 Figure A-26. Timing Type C5, I2t with Limit #5
and Extended Timing Range
Figure A-27. Timing Type C6, I2t with Limit #6 Figure A-28. Timing Type C6, I2t with Limit #6
and Extended Timing Range
Figure A-29. Timing Type C7, I2t with Limit #7 Figure A-30. Timing Type C7, I2t with Limit #7
and Extended Timing Range
P0049-33
Figure A-31. Timing Type C8, I2t with Limit #8 Figure A-32. Timing Type C8, I2t with Limit #8
and Extended Timing Range
Figure A-33. Timing Type E2, BS 142 Figure A-34. Timing Type E4,
Long Inverse BS 142 Inverse (1.3 Sec)
Figure A-35. Timing Type E5, Figure A-36. Timing Type E6,
BS 142 Inverse (2.9 Sec) BS 142 Very Inverse
Figure A-38. Timing Type B1, Short Inverse Figure A-39. Timing Type B1, Short Inverse with
with Integrated Algorithm Integrated Algorithm and Extended Timing
P0049-42
Figure A-40. Timing Type B2, Long Inverse Figure A-41. Timing Type B2, Long Inverse with
with Integrated Algorithm Integrated Algorithm and Extended Timing
Figure A-42. Timing Type B3, Definite Time Figure A-43. Timing Type B3, Definite Time with
with Integrated Algorithm Integrated Algorithm and Extended Timing
Figure A-44. Timing Type B4, Moderately Figure A-45. Timing Type B4, Moderately
Inverse with Integrated Algorithm. Inverse with Integrated Algorithm
and Extended Timing
Figure A-46. Timing Type B5, Inverse with Figure A-47. Timing Type B5, Inverse with
Integrated Algorithm Integrated Algorithm and Extended Timing
Figure A-48. Timing Type B6, Very Inverse Figure A-49. Timing Type B6, Very Inverse with
with Integrated Algorithm Integrated Algorithm and Extended Timing
Figure A-50. Timing Type B7, Extremely Inverse Figure A-51. Timing Type B7, Extremely Inverse
with Integrated Algorithm with Integrated Algorithm
and Extended Timing
P0049-54
Figure A-52. Timing Type B8, I2t Figure A-53. Timing Type B8, I2t with Integrated
with Integrated Algorithm Algorithm and Extended Timing
Figure A-54. Timing Type C1, I2t Limit #1 Figure A-55. Timing Type C1, I2t Limit #1
with Integrated Algorithm with Integrated Algorithm
Figure A-56. Timing Type C2, I2t Limit #2 Figure A-57. Timing Type C2, I2t Limit #2 with
with Integrated Algorithm Integrated Algorithm and Extended Timing
Figure A-58. Timing Type C3, I2t Limit #3 Figure A-59. Timing Type C3, I2t Limit #3 with
with Integrated Algorithm Integrated Algorithm and Extended Timing
P0049-62
Figure A-60. Timing Type C4, I2t Limit #4 Figure A-61. Timing Type C4, I2t Limit #4 with
with Integrated Algorithm Integrated Algorithm and Extended Timing
Figure A-62. Timing Type C5, I2t Limit #5 Figure A-63. Timing Type C5, I2t Limit #5 with
with Integrated Algorithm Integrated Algorithm and Extended Timing
Figure A-64. Timing Type C6, I2t Limit #6 Figure A-65. Timing Type C6, I2t Limit #6 with
with Integrated Algorithm Integrated Algorithm and Extended Timing
Figure A-66. Timing Type C7, I2t Limit #7 Figure A-67. Timing Type C7, I2t Limit #7 with
with Integrated Algorithm Integrated Algorithm and Extended Timing
Figure A-68. Timing Type C8, I2t Limit #8 Figure A-69. Timing Type C8, I2t Limit #8 with
with Integrated Algorithm Integrated Algorithm and Extended Timing
–125 vdc to ground. If there are other sources or Note: The 125 above is used as a nominal figure
loads connected to the field circuit, they will cause for ground detector source output voltage. The 30
misoperation of the ground detector. Care must be above is used as a nominal figure for current
taken to remove any other ground detectors from limiting resistance in the ground detector source.
the field circuit. Actual voltage and for current limiting resistance
can be set in FLDGND software block.
This field ground detection scheme can be used
with either a rotating exciter field or a generator For the min. resistance calculation, it is assumed
field. For brushless excitation systems where the ground occurs at the (+) terminal of the
grounding brushes are connected to the field machine field, and the voltage is supplied solely
occasionally, other discrete relay controls can be from the 125 V d-c supply of the ground detector
added to the control software and additional source. For the maximum resistance calculation, it
contacts from a DIOM can be used to lower the is assumed the ground occurs at the (-) terminal of
grounding brushes at the desired interval. Note: the machine field, and the voltage is supplied
this system does not contain a brush contact from the 125 V ground detector source supply in
verifier feature as in some other ground detection series with the D-C voltage applied across the
schemes. entire machine field. The possibility for a ground
to occur at a point in the excitation system where
The ground detector is continuously monitoring the machine field voltage to ground can nullify the
the leakage current to ground and computing an 125 V d-c from the ground detector source does
equivalent ground resistance range. (It acts much not exist. This is because the ground detector’s
like having a 125 vdc meggar continuously source voltage is always adds to any machine field
connected to the field) The magnitude of the voltage to ground.
ground current is dependent upon both the ohmic
value of the ground resistance and where the The ground detector scheme monitors the leakage
ground occurs in the excitation system. Depending current to ground by measuring the voltage drop
on where the ground occurs, the amount of across an internal shunt resistor. In the lower
leakage current will vary with the field voltage. voltage ground detector source a 500 ohm resistor
Therefore the actual ground resistance will fall is used. So an output voltage of 1 volt dc between
within a defined range for any particular value of pins 1 & 2 of the ground detector source would
leakage current. The following equations may be correspond to 2 milliamps of leakage current to
employed to determine the minimum and ground. In the higher voltage ground detector
maximum resistance values that can be expected source a 200 ohm resistor id used. So an output
for a given leakage current. voltage of 1 volt dc between pins 1 & 2 of the
ground detector source would correspond to 5
Min. resistance (kΩ) = (125 / IG) -30 milliamps of leakage current to ground.
Max. resistance (kΩ) = ((VF+ 125)/ IG) -30 EXAMPLE: FOR A MACHINE OPERATING
WITH A FIELD VOLTAGE OF 325 V D-C
Where (VF), WITH A MEASURED LEAKAGE
CURRENT OF 2.5 MA (lG), THE
VF = DC voltage across machine field. (volts) FOLLOWING RESISTANCE VALUES ARE
OBTAINED:
IG = Measured leakage ground current.(ma)
Note: If a ground occurs near the (-) terminal of The resistors R6, R7, zener diode Z1, and
the machine field, and the field voltage is high capacitor C1 serve to provide protection of the
enough to cause the leakage current to exceed Analog Input Output Module against voltage
4.17 ma, the calculated min. resistance will be transients coming in from the machine field
negative. connection.
Ground Detector Source Hardware For the lower voltage ground detector source
(G01), a resistor RT is supplied which may be
The ground detector source operates from a 1 used to check the setup of the ground detector.
phase, 120 V, 50-60 Hz supply. The diode bridge Normally this resistor is disconnected from the
DB1 rectifies A-C power from T1. The nominally output of the ground detector source. Before using
125 V d-c rectified signal is supplied to the output RT, the field needs to be disconnected from the
pins through current limiting resistors R1, R2,R3, ground detector source by opening 64FU. After 64
and sensing resistor R4 when relay 64G is FU has been opened, RT is unplugged from TB-
energized. For the lower voltage ground detector 13, 14,15 and then plugged into TB-10, 11,12.
source (G01) the output pins are TB-4 and TB-5 , The display should then read approximately one
where TB-4 is connected to ground and TB-5 is megaohm. After taking the reading RT should be
connected to the field “+” bus. For the higher replaced in TB-13, 14,15 before closing 64FU.
voltage ground detector source (G02) the output
pins are TB-4 and TB-6 , where TB4 is connected INSTALLATION
to ground and TB-6 is connected to the field “+” When shipped, the equipment will have its
bus. Current limiting resistors R1, R2, and, R3 Ground Detector Source physically installed and
serve to limit the current to about 4.2 ma if the connected. If replacement is necessary, open
output terminals are shorted together. Sensing GDFU (EXFU), and 64FU before removing the
resistor R4 serves to develop a voltage Ground Detector Source. Carefully label and
proportional to leakage current. That voltage, document each of the connections to the Ground
representing leakage current, is sent to an Analog Detector Source in order to properly reconnect to
Input Output Module. Should a ground develop, a a new board.
ground current will flow from the grounded
machine shaft through the field winding, through
All possible contingencies which may arise during installation, operation or maintenance, and all
details and variations of this equipment do not purport to be covered by these instructions. If further
information is desired by purchaser regarding this particular installation, operation or maintenance
of this equipment, the local ABB Power T&D Company Inc. representative should be contacted.
Printed in U.S.A .
41-751N Type SG Auxiliary Relay
2
Type SG Auxiliary Relay 41-751N
Sub 4 Sub 5
629A337 1D2102
Figure 1: Internal Schematic for Type SG Relay in Front Figure 2: Internal Connections for Closed Type SG
Connected Case. Relay.
Sub 4 Sub 5
57D390 57D389
Figure 3: Internal Connections for 2-Make and 2-Break Figure 4: Internal Connections for Open Type SG Relay
contact Open Type SG Relay. with Reversible Contacts.
3
41-751N Type SG Auxiliary Relay
Sub 5
182A904
Figure 5: Outline and Drilling plan for t he Closed Type SG Auxiliary Relay with 5/8 inch terminal studs.
Sub 3
182A903
Figure 6: Outline and Drilling plan for the Semi-Flush Case for the Type SG Relay with 5/8 inch terminal studs.
4
Type SG Auxiliary Relay 41-751N
Sub 12
31D890
Figure 7: Outline and Drilling plan for the Open Type SG Auxiliary Relay with Reversible Contacts.
Sub 5
18D5332
Figure 8: Outline and Drilling plan for the 2-Make and 2-Break Contact Open Type SG Relay.
5
41-751N Type SG Auxiliary Relay
6
Type SG Auxiliary Relay 41-751N
7
41-751N Type SG Auxiliary Relay
*Sub 3
629A331
Figure 9: Outline and Drilling Plan for t he Type SG Relay in Front Connected with dust cover.
Physical Properties:
RS232: 3-wire interface to RJ11/12 Connector (TXD, RXD, Common), DTE/DCE Jumpers
RS485: Wago terminal strip (TXD/RXD-, TXD/RXD+, Common) and dual RJ12/RJ11 connectors
Power: 2.1mm center positive "Barrel" connector, Terminals, (9-35Vdc), switching regulator
LEDs: For RS232 & RS485: Power (Yellow), TXD (Red), RXD (Green)
Bias: 910 / 2.2K Ohm pull-up and pull-down resistors (jumper selectable)
Termination: 120 Ohm (jumper selectable)
Special: Robust transient protection and isolation, Loop-back test jumper
Specifications:
Temp./Humidity: -40C to +85C (-40F to +185F) operating temp., 10-90% relative humidity, non-condensing
Isolation Voltage 3KV for 1-Sec. peak for opto-isolators and onboard DC-DC converter
Input Voltage Range: 9-35Vdc (Switching regulator)
Power: Under 1/2 Watt (typical) + external load
Physical Size: PCB size: 3.25" X 3.00" X 0.9" with connectors: 3.50" X 3.25 X 0.9" (built-in #6 standoffs)
RS485 Distance: 4000ft. (1250 meters) minimum, with up to 32 unit loads
Speed/Format: Up to 115.2Kbps data rate, with any combination of bits (start, data, parity, stop, etc.)
Operation: 2-wire, half-duplex, RS485 data, using twisted 24AWG wire (100-120 Ohm impedance)
NOTE: Industrial/robust applications, can be used with outdoor wiring (signs, camera PTZ, etc.)
I.L. 8651C66C
Revised 11/13/2006
ECS2100 Exciter Control Module
INSTRUCTION LEAFLET
SAFETY
DRAWINGS
DANGER:
The following drawings are referenced within this BODILY INJURY COULD RESULT IF
document. CONTACT IS MADE WITH COMPONENTS
ECM Card Assembly .........................8651C66 IN THIS APPARATUS WHICH CARRY
EITHER LINE VOLTAGE OR ARE
SUBJECT TO ABNORMALLY HIGH
PURPOSE VOLTAGES. REFERENCES TO THE
CIRCUIT DIAGRAMS, NOTABLY WITHIN
The purpose of the Exciter Control Module OTHER DOCUMENTATION WILL
(ECM) is to serve as the primary control board for DISCLOSE HAZARDOUS AREAS.
the ECS2100 excitation system. The ECM
contains a 32-bit digital signal processor that As with all electrical equipment, appropriate
implements all of the regulator, limiter, safety measures should be taken whenever dealing
protection, and system control functions. The with the excitation equipment. High voltage is
ECM also utilizes a 32-bit microcontroller that present within the excitation cubicles; their
supervises communication with other boards in magnitudes depend upon the particular system.
the system as well as with the user over several Opening the sources (e.g., disconnect device 41)
different communication media (RS-232, RS-485, does not completely disconnect the high voltages.
Ethernet 10baseT, Ethernet AUI, modem). All As long as the machine is still physically
user settings and the firmware are stored in non- connected to the system, there is a possibility that
volatile flash memory and may be easily upgraded a safety hazard exists.
in the field using a laptop computer and the
proprietary ccTool software. Up to 3 ECMs may Every precaution must be taken when working at
be installed in a system to provide fully redundant the excitation control switchgear to ensure that all
control with supervision. high voltages are isolated and avoided by test
personnel. In addition to the machine terminal
This document contains a description of the voltage (460 Vac or greater) at the excitation
functions of the ECM, along with a description of transformer, there may be other sources of power
inputs and outputs. There is also a brief entering the cubicles, such as the customer
description of the installation of the ECM. 125/250 Vdc and/or 120/240 Vac used to feed
Maintenance and warranty information is certain devices. A good rule to follow is to assume
provided as well. that all connections are live and dangerous until
proven otherwise and to avoid completely all body
contact with any of these voltages.
One other cautionary note refers to the Generator status of the ECM; normally blinks in a
Field Ground Detector. Because the Ground regular counting pattern at a one second
Detector input supply is usually 120 Vac, both the rate.
AC bus and DC (100 Vdc) might be backfed from 1 RS232 Port, DB9 port (J22) used for
this device. Therefore it too must be disconnected interface to ccTool via Modbus RTU.
when servicing the excitation control equipment. 1 Internal 33.6 kbaud Modem RJ11 jack
(J15) used for remote interface to ccTool
via Modbus RTU.
GLOSSARY
2 RS485 Port, RJ45 port (J17, J18) used for
ECM Exciter Control Module. Contains interface to Panelmate, other operator
the excitation control, limiting, interface devices, distributed control or
protection, and communication SCADA systems via Modbus RTU.
software (but is not considered a 1 RS485 Port RJ45 ganged ports (J19, J20)
part of the Digital Firing Control). used for connection between multiple
ECMs in two or three channel system.
1 Ethernet Port RJ45 port (J16) pused for
OPERATION/APPLICATION interface to distributed control or SCADA
systems; either 10baseT or AUI port (J21)
The Exciter Control Module is a dual processor port may be used to interface with any
controller card that serves as the primary control Ethernet media.
board for the ECS2100 excitation system. The 6 Ethernet Status LEDs used to indicate
ECM contains a 32-bit digital signal processor communication status on the Ethernet
that implements all of the regulator, limiter, port; Collision, Link, Transmit, Receive,
protection, and system control functions. The Jabber, and Polarity indications are
ECM also utilizes a 32-bit microcontroller that provided.
supervises communication with other boards in 1 Serial Interface to SIM used to gather CT
the system as well as with the user over several and PT data from the SIM card as well as
different communication media (RS-232, RS-485, to interface with the DIOM and AIOM
Ethernet 10baseT, Ethernet AUI, modem). All boards via the SIM FPGA.
user settings and the firmware are stored in non-
volatile flash memory and may be easily upgraded 1 Serial Interface to FCIM used for bi-
in the field using a laptop computer and the directional communication with the FCIM
proprietary ccTool software. Up to 3 ECMs may and the BCM via the FCIM of various
be installed in a system to provide fully redundant firing control data.
control with supervision. 2 24Vdc power supply inputs. Either or
both supplies will provide the power,
ECM I/O and Hardware implementing the redundant power supply
philosophy of the ECS2100 system.
The following list of hardware resources and
inputs and outputs of the ECM is included as an
aid in understanding its functionality. INSTALLATION
Refer to the distribution medium discussion under The user application consists of invoking and
CODE Firmware. For more information of the interconnecting blocks. The interconnections are
upload/download process refer to the ccTool implemented through software patching within the
User’s Manual. firmware and governed by table entries within the
USER FLASH RAM
CODE Firmware
Using ccTool, the user may upload or download
the operating firmware which creates all the NORMAL ECM OPERATION
features and functions of the ECM. The ECM is
shipped with the latest operating firmware at the The ECM will operate independently of any user
time of production. New firmware will be intervention. However, aspects of operation may
distributed on computer medium, principally a 3- be observed, monitored, or controlled through the
1/2 inch floppy disk or on a Compact Disk CD- use of the ccTool program, visually through the 8
ROM. The file containing the released code will ECM LEDs, or through information
have the extension, .RHX. communicated with the ECM and displayed either
on a local Panelmate™ , located at the excitation
Application/User Program control cubicles, or on the control room display.
. Each system is designed by Customer Order
Engineering (COE), based on an adaptation of a Creating or Adjusting User Programs
standard base design to best serve the customer's Programs are created, modified, and adjusted
job requirements. using the ccTool program. The function of many
of the blocks within the user’s program are
The COE personnel install customized software governed by constant inputs. The constants may
according to the specific requirements of the be modified dynamically during on-line operation.
order. A series of standardized and pre-tested Thus gains, scale factors, and time constants may
application programs are initially used by COE. be adjusted to improve operation.
Adjustments then are made to satisfy individual
site-specific customer requirements. The software Providing Over-riding Control
is installed in the ECM module during production Using the ccTool program, a user may force
assembly and test. The program is also provided values or states within his Block Diagram
on computer data media that is shipped along with program. This is generally done for the sake of
the other documentation of the system. debugging or to temporarily compensate for
operational problems.
The application block diagram program is loaded
into the ECM through the Windows™ application Monitoring Alarms
program, ccTool. The ccTool also allows copying Using the ccTool program, the user may monitor
and/or modification of the provided program and respond to alarms, trips, and other system
stored within the ECM in its Flash RAM. exceptions. The ALARM descriptions are stored
within the ECM as part of the operating firmware.
Modification of the original user application Thus, when a new exception type is added, its
program likely will be the most frequent description is immediately available for display by
upload/download event over the life of the ECM the ccTool while the user is monitoring.
and the associated excitation equipment. Changes
may be as simple as gain adjustments or more
involved changes in the block structure.
Environment
SPARE PARTS Ambient temperature range of -20°C to 50°C
A reasonable stock of spare parts will minimize Relative humidity of 0 to 95% non-condensing
down-time, in the event of a malfunction in this
Page 1 of 8
INSTRUCTIONS FOR Firing Control Interface Module I.L. 8651C67C
One other cautionary note refers to the Generator and firing angle command from the
Field Ground Detector. Because the Ground ECM and determines when to fire
Detector input supply is usually 120 VAC, both the each SCR.
AC bus and DC (100 VDC) might be backfed from Flash A type of Random Access Memory
this device. Therefore it too must be disconnected (RAM) that retains memory contents
when servicing the excitation control equipment. without power, and not relying on a
battery.
GLOSSARY FO Fan Out card. Provides transceiver
BCM Bridge Control Module. Up to 16 capability beyond the three built into
BCMs can be controlled by one the FCIM as Standard.
FCIM. FPGA Field Programmable Gate Array. An
Bridge A configuration of thyristors that integrated circuit that implements
convert AC current to DC current. complex logic functions within a
ccTool Controller Configuration Tool, a PC single package.
based Windows (95, 98, or NT) IT Isolation Transducer card. Isolates
application program which connects two analog signals for digital input
to an ECM, FCIM, or BCM card for to FCIM or BCM and other
user programming of the card modules.
functions. Presents Table or Block PLL Phase Locked Loop. A closed-loop
Diagram representations of the circuit scheme to automatically lock
controller program and operation. the frequency and phase of an
CM Conduction Monitor card. Provides oscillator, so that it produces a
current level information on each precise firing angle necessary to
SCR or bridge. maintain the desired level of a
COE Customer Order Engineering, converter output parameter under
provides all the engineering control.
information for a customer job- QSPI Queued Serial Peripheral Interface,
specific design, including the provides a high speed means to
application firmware required to communicate with the ECM. The
operate the FCIM. QSPI is built into the architecture of
DCE Data Communications Equipment the FCIM controller (MC68HC16).
(part of the RS232 standard). The RS232 A standard physical link protocol for
FCIM is DCE configured. serial communication. Almost every
DFC Digital Firing Control (subset of the PC provides a port using this
digital excitation control system). communication connection.
DTE Data Terminal Equipment (part of SCR Silicon Controlled Rectifier. A
the RS232 standard). The PC variable-conduction rectifier with
running ccTool is DTE configured. delayed forward turn-on gating. Also
ECM Exciter Control Module. Contains referred to in the industry as a
the excitation control, limiting, thyristor.
protection, and communication VCO Voltage Controlled Oscillator. A
software (but is not considered a part circuit that provides a variable
of the Digital Firing Control). frequency output proportional to a
FCIM Firing Control Interface Module. voltage input.
Processes the AC source waveforms
Page 2 of 8
INSTRUCTIONS FOR Firing Control Interface Module I.L. 8651C67C
The FCIM is provided the operational set point data The software implemented control scheme is also
to operate as an excitation control system by the viewable as a block diagram or as tables using the
Exciter Control Module (ECM) via the high-speed ccTool.
QSPI interface built into the architecture of the
68HC16 processor within the FCIM. FCIM I/O and Hardware
The following list of hardware resources and inputs
Using isolated VAB and VBC power line input signals and outputs of the FCIM is included as an aid in
(obtained from an IT module), a software understanding its functionality.
implemented Phase Locked Loop (PLL) within the
FCIM processor creates an internal timing signal # of FCIM Hardware Resource
which is used to establish SCR firing signals. These 2 10 bit A/D converters based upon built-in
are time and pattern synchronized correctly to the 68HC16 processor converters. The input is
source AC line. Firing signals, interspersed with scaled for -10V to +10V, unadjusted.
data signals, are transmitted to up to 16 paralleled 4 12 bit D/A outputs based upon MP7680.
bridges, each controlled by a BCM. This The output is scaled for –10VDC to
information is sent over fiber-optic cables, using a +10VDC unadjusted.
custom logical and physical communication
protocol implemented by a Field Programmable 4 DC Logical Inputs. For each of the four
Gate Array (FPGA). inputs from universal AC/DC inputs from
DIOM, TRUE if the input is high.
The FCIM, BCM, and ECM replaces previous 6 VCO counter inputs. These are optical
designs which used various control relays and cable inputs driving 16 bit counters within
timers to control the excitation system. To the a custom FPGA. An external IT card
maximum extent possible discrete relays, timers, provides a variable frequency input
and associated wiring are eliminated, and their proportional to a scaled and measured
function is implemented in the software of the voltage. These inputs are processed by the
FCIM, BCM, and ECM. Discrete relays are used custom FPGA and sent to the processor at
when the power requirements of the devices being fixed intervals, representing an isolated
operated (e.g., the 41A device) necessitate them or digitization of the signals being measured.
when an application requires dry contacts. 12 Status LEDs, consisting of 4 RED, 4
AMBER, and 4 GREEN. The LEDs are
Data communication is bi-directional between the accessed via the DR” Block Function.
FCIM and the BCM(s), and between the FCIM and 4 Relay Control output contacts (For
the ECM. The ECM receives all significant example, power cubicle fans ON/OFF)
operating data of the FCIM and the BCM(s).
1 RS232 Port based upon the SCI interface
built into the 68HC16.
The FCIM consolidates alarm and other information
from all the bridges and provides it to a Windows™
application program, Controller Configuration Tool
Page 3 of 8
INSTRUCTIONS FOR Firing Control Interface Module I.L. 8651C67C
Page 4 of 8
INSTRUCTIONS FOR Firing Control Interface Module I.L. 8651C67C
Jumpers PROGRAMMING
For jumper placement refer to the Block Diagram
Program Modifications Onsite
8651C67. Jumpers are placed for two functions on Using the ccTool, modifications of FLASH stored
the FCIM, for RS-232 mode (ECM or ccTool code can be made at the customer’s facility or
connection) and for F memory configuration. remotely (ccTool supports modem connection) to
the site. This capability permits the firmware as well
Communication Jumpers as the startup, running, and shutdown sequence
Jumpers JMP10, JMP11 are used to establish
logic to be changed on site. Three specific classes of
whether RS232 communication comes through J20 stored data can be changed:
or from the ECM to which the FCIM is connected.
FCIM startup will typically proceed with the
• Download/Upload BOOT firmware
communication connection directly to the FCIM.
• Download/Upload CODE firmware
• Download/Upload Application (Tables)
Flash Memory Jumpers
The FLASH memory jumpers seldom need to be
These functions will be useful during initial startup
changed. The primary occasion requiring a FLASH
as well as in later maintenance situations.
jumper change is for downloading a new firmware
BOOT program. When new BOOT code is
downloaded, the jumpers must be moved to re- BOOT Firmware
The BOOT firmware is code that controls the FCIM
locate the new code at the memory location which is
power-up, communications, and upload/download
executed at power-up.
process. Since the BOOT bank of FLASH memory
controls the download process, downloading new
The location of banks of BOOT, CODE, and
BOOT code requires the use of the existing BOOT
TABLES FLASH RAM memory may be changed
code with a subsequent interchanging of the location
with jumpers, JMP1 through JMP9. For the most
of the old CODE and BOOT banks (with the power
part, the default jumper location will suffice. For
off). It will be necessary to invoke the new BOOT
more information consult the ccTool User’s
bank at the next power-on of the FCIM. This is an
Manual.
infrequent event, as BOOT code is relatively simple
and not likely to change.
Connection of ccTool
In order to perform a setup, the user must connect a
Refer to the distribution medium discussion under
personal computer running the Windows™
CODE Firmware. For more information of the
application program ccTool to the FCIM via
upload/download process refer to the ccTool User’s
connector J20. Use a standard through wired RS232
Manual.
cable with DCE 9 pin on the end connecting to the
FCIM and DTE 9 or 25 pin at the other end to
match the RS232 port on the PC. After assuring the CODE Firmware
communication source jumper is properly installed Using ccTool, the user may upload or download the
and the FCIM is energized, invoke ccTool. operating firmware which creates all the features
and functions of the FCIM. The FCIM is shipped
with the latest operating firmware at the time of
production. New firmware will be distributed on
computer medium, principally a 3-1/2 inch floppy
disk or on a Compact Disk CD-ROM. The file
containing the released code will have the
extension, .RHX.
Page 5 of 8
INSTRUCTIONS FOR Firing Control Interface Module I.L. 8651C67C
Page 6 of 8
INSTRUCTIONS FOR Firing Control Interface Module I.L. 8651C67C
Watchdog Timer
The watchdog timer is a hardware function within
the module processor which will reset the system if
software doesn’t periodically send a signal into the
timer. If the watchdog timer resets the system, the
Page 7 of 8
INSTRUCTIONS FOR Firing Control Interface Module I.L. 8651C67C
MAINTENANCE QSPI
This equipment contains solid state components High-speed communication with the ECM module
which require little maintenance. The removal of is by means of the Queued Serial Peripheral
accumulated dust occasionally will be sufficient. Interface (QSPI) which is an integral part of the
Maintenance for non-solid-state components is FCIM processor. Bi-directional data interchanges
required only as specifically defined. occur at intervals of 1.024 milliseconds. The ECM
initiates a QSPI interchange every millisecond, and
it will consequently never miss a sample.
SPARE PARTS
A reasonable stock of spare parts will minimize PLL Firing Control
down-time, in the event of a malfunction in this The PLL, Phase Locked Loop, (with ranges of 15
equipment. When ordering spare parts, care should Hz to 90 Hz for static systems, and 60 to 480 Hz for
be taken to specify the style numbers (or other brushless and rotating exciters) requires two phases
identification) which are printed on the nameplate, of three-phase voltage power input signals. These
located on this apparatus. are provided by an IT Card via fiber optic links to
connectors U41, U42.
For the FCIM, it is recommended that the user stock
at least one FCIM board, fuses, and plastic-housed Active Current Balance
0.010-inch jumpers. Active current balancing algorithms (so-called
“Skip Firing “) may be provided on each BCM. The
FCIM will enable, freeze or disable each BCM’s
SPECIFICATIONS AND PERFORMANCE implementation of the balance. BCM’s will report
Power Supply Requirements back their “fair share” current to the FCIM. The
+24VDC ±10%, with nominal current of 0.14 ADC FCIM then makes this information available to the
ECM.
External Serial Communication
The RS232 communication occurs at a fixed rate of Redundancy
38.4 KBaud through J20, a 9-pin sub-miniature “D” A State Select line is available on FCIMs for the
connector, configured as DCE. Since PCs are purpose of controlling which one of two FCIM
typically configured as DTE, a standard “through” redundant fiber networks is to be used to control the
RS232 cable may be used. All parameters for this BCMs. A third FCIM (termed the “supervisory”
communication are fixed by the FCIM firmware, FCIM) monitors the operation of the two redundant
requiring no user setup or intervention. Some choice FCIMs, detecting the failure conditions that require
is provided by the ccTool for the logical protocol, a switch over to the second FCIM, using the State
but the physical protocol is fixed. Select Line.
Page 8 of 8
I.L. 8651C65C
Revised 11/13/06
ECS2100 Sensor Input Module
INSTRUCTION LEAFLET
As long as the machine is still physically
DRAWINGS connected to the system, there is a possibility that
The following drawings are referenced within this a safety hazard exists.
document.
SIM Card Assembly...........................8651C65 Every precaution must be taken when working at
the excitation control switchgear to ensure that all
high voltages are isolated and avoided by test
PURPOSE personnel. In addition to the machine terminal
The purpose of the Sensor Input Module (SIM) is voltage (460 Vac or greater) at the excitation
to provide the means to interface the AC generator transformer, there may be other sources of power
metering and regulator PT and CT signals to the entering the cubicles, such as the customer
digital excitation control system. Each SIM has 125/250 Vdc and/or 120/240 Vac used to feed
the capability to sense twelve analog inputs (24 certain devices. A good rule to follow is to assume
Vac nominal, 40Vdc peak). Utilizing the ccTool that all connections are live and dangerous until
software, the analog input data can be connected proven otherwise and to avoid completely all body
to any control software block input in the ECM. contact with any of these voltages.
FPGA Field Programmable Gate Array. the location of connectors and LED indicators.
An integrated circuit that
implements complex logic
functions within a single package. VERIFICATION OF CALIBRATION
SIM Sensor Input Module. Provides the There are no user adjustments on the SIM Card. If
interface from PT and CT signals necessary, adjustments may be made digitally
and the AIOM and DIOM to the within the user's program. Each of the modules
ECM. that use the SIM for input operates on the basis of
a user program viewable as a block diagram using
OPERATION/APPLICATION the ccTool program. The ccTool provides
The Sensor Input Module provides the means to individual adjustment of gain and offset for each
isolate the AC generator metering and regulator input. Using a precision voltage source,
PT and CT signals from the digital electronics. multimeter, and ccTool, the user may verify the
The PT and CT secondary inputs (24 Vac accuracy of the inputs across the full range by
nominal, 40Vdc peak) are sampled simultaneously plotting the analog input versus the digital values
every 400 microseconds by stereo sigma delta displayed in ccTool.
analog-to-digital converters with 16-bit resolution.
Six of these high-speed, high-resolution A-to-Ds
are used in parallel to provide 12 input channels. LIMITS OF WARRANTY
Fiber optic cable connections for Digital Input / The warranty of this apparatus may be
Output Modules (DIOM) and Analog Input / invalidated, unless the following described
Output Modules (AIOM) are also located on the procedures are followed. Apparatus which
SIM. Serial communications to these cards are malfunctions should be replaced with new
routed through the SIM FPGA. This FPGA is used units obtained from the factory.
to link all analog and digital inputs and outputs, Malfunctioning items should be returned to the
including the PTs and CTs, to the ECM. factory for repair after authorization is
received from the local sales and service office
Utilizing the ccTool software, the analog input or the factory. This is particularly true of
data can be connected to any control software electronic printed circuit boards which require
block input in the ECM. These inputs are typically careful handling by skilled personnel and for
connected to phase locked loops or system test which field repair or modifications should not
inputs. be attempted.
For the SIM, it is recommended that the user stock Relative humidity of 0 to 95% non-condensing
at least one SIM board.
MAINTENANCE Environment
Ambient temperature range of -20°C to 50°C
This equipment contains solid state components
which require little maintenance. The removal of Relative humidity of 0 to 95% non-condensing
accumulated dust occasionally will be sufficient.
One other cautionary note refers to the Generator FCIM Firing Control Interface Module.
Field Ground Detector. Because the Ground Processes the AC source waveforms
Detector input supply is usually 120 Vac, both the and firing angle command from the
AC bus and DC (100 Vdc) might be backfed from ECM and determines when to fire
this device. Therefore it too must be disconnected each SCR.
when servicing the excitation control equipment. Flash A type of Random Access Memory
(RAM) that retains memory contents
without power, and not relying on a
GLOSSARY battery.
FO Fan Out card. Provides transceiver
BCM Bridge Control Module. Up to 16 capability beyond the three built into
BCMs can be controlled by one the FCIM as Standard.
FCIM. FPGA Field Programmable Gate Array. An
Bridge A configuration of thyristors that integrated circuit that implements
convert AC current to DC current. complex logic functions within a
ccTool Controller Configuration Tool, a PC single package.
based Windows (95, 98, or NT) IT Isolation Transducer card. Isolates
application program which connects two analog signals for digital input
to an ECM, FCIM, or BCM card for to FCIM or BCM and other
user programming of the card modules.
functions. Presents Table or Block PLL Phase Locked Loop. A closed-loop
Diagram representations of the circuit scheme to automatically lock
controller program and operation. the frequency and phase of an
CM Conduction Monitor card. Provides oscillator, so that it produces a
current level information on each precise firing angle necessary to
SCR or bridge. maintain the desired level of a
COE Customer Order Engineering, converter output parameter under
provides all the engineering control.
information for a customer job- QSPI Queued Serial Peripheral Interface,
specific design, including the provides a high speed means to
application firmware required to communicate with the ECM. The
operate the FCIM. QSPI is built into the architecture of
DCE Data Communications Equipment the FCIM controller (MC68HC16).
(part of the RS232 standard). The RS232 A standard physical link protocol for
FCIM is DCE configured. serial communication. Almost every
DFC Digital Firing Control (subset of the PC provides a port using this
digital excitation control system). communication connection.
DTE Data Terminal Equipment (part of SCR Silicon Controlled Rectifier. A
the RS232 standard). The PC variable-conduction rectifier with
running ccTool is DTE configured. delayed forward turn-on gating. Also
ECM Exciter Control Module. Contains referred to as a thyristor.
the excitation control, limiting, VCO Voltage Controlled Oscillator. A
protection, and communication circuit that provides a variable
software (but is not considered a part frequency output proportional to a
of the Digital Firing Control). voltage input.
Page 2 of 9
INSTRUCTIONS FOR Bridge Control Module I.L. 8651C70C
Page 3 of 9
INSTRUCTIONS FOR Bridge Control Module I.L. 8651C70C
2 + 24Vdc power supply inputs. Either or the purpose of monitoring and adjusting for the
both supplies will provide the power, specific job application. Refer to the BCM Block
implementing the redundant power supply Diagram (8651C70) for the location of connectors
philosophy of the ECS2100 system. The and jumpers.
digital logic as well as the SCR firing pulse
circuits use the positive supply voltage. BCM Board Connection
2 -24Vdc power supply inputs. Either or both Power and signal connections must be provided to
supplies will provide the power, the BCM. Signals are both optical and electrical.
implementing the redundant power supply Refer to Block Diagram 8651C70 and the job-
philosophy of the ECS2100 system. The specific schematics. All electrical power to the
negative supply voltage is used only by the BCM is provided through the redundant ±24Vdc
SCR firing pulse circuits. connectors, J3 and J4.
2 Optical Transmit Interface from fiber
communication channels with the FCIMs. Optical connections are made by inserting the fiber
The second input allows for redundancy of cables and connectors provided into the main optical
FCIMs. channel receptacles, U41, U42, at the bottom edge
of the board. For redundant (two-channel) systems,
2 Optical Receive Interface to fiber a second optical channel is provided through U43,
communication channels to FCIMs. The U44. Dual fiber cable assemblies are provided for
second output allows for redundancy of the these connections in various lengths, depending on
FCIMs. the specific design.
6 High Energy "Picket Fence" SCR pulse
circuits. Signals received via fiber optic U45 through U48 are four fiber optic receivers that
cable from the FCIM results in the use single fiber cable assemblies to receive signals
appropriate pattern of picket pulses to SCR from two Isolation Transducer modules (2 channels
gates. per module). One of the modules typically obtains
6 Bi-Polar Conduction Sensor inputs. Enable the I+ and I- bridge currents from the two bridge
the assessment of actual firing pattern of shunts.
SCRs for fault detection and metering of
the total and individual device currents. Digital and analog electrical inputs and outputs are
Conduction signals also used for detection provided as shown in the Block Diagram 8651C70A
of failed devices. drawing. In general, it is difficult to establish within
1 4 position dip switch to set the Bridges’ this document the precise use of each of the digital
address, 0 – 15. and analog I/O points. Refer to the drawings for
7 RTD (Resistance Temperature Device) each job-specific system, supplied as physical
drawings and as part of the HTML, dynamic on-
inputs, for measuring the ambient and the
line, HELP. But, above all, carefully document of
six heat sink temperatures..
the original connections is essential any time the
BCM is removed.
INSTALLATION
When shipped the equipment will have its BCM(s) RTDs
physically installed and connected. If replacement is The temperature of each of the SCRs and the
necessary, carefully label and document each of the ambient temperature are measuerd using Resistance
connections to the BCM, in order to properly Temperature Devices. No calibration is required.
reconnect to a new board. Even for the original The device cables plug into J10, J12, J13, J16, J18,
startup (as well as when replacing the BCM), the J20, and J22.
user will be required to interface with the BCM for
Page 4 of 9
INSTRUCTIONS FOR Bridge Control Module I.L. 8651C70C
Page 5 of 9
INSTRUCTIONS FOR Bridge Control Module I.L. 8651C70C
Page 6 of 9
INSTRUCTIONS FOR Bridge Control Module I.L. 8651C70C
Page 7 of 9
INSTRUCTIONS FOR Bridge Control Module I.L. 8651C70C
Communication Tests with the ccTool For the BCM, it is recommended that the user stock
The ccTool provides communication test functions. at least one BCM board and plastic-housed 0.010-
Repetitive test write followed by read actions are inch jumpers.
carried out through the FCIM to each of the BCMs,
or directly to a BCM. By invoking the
communication tests, operation of several SPECIFICATIONS AND PERFORMANCE
subsystems can be verified, including processors
and fiber optic channels. Power Supply Requirements
+24Vdc ±10%, with nominal current of 0.25 ADC
Page 8 of 9
INSTRUCTIONS FOR Bridge Control Module I.L. 8651C70C
Bridge Communication
The bridge communication to the Bridge Control
Modules is performed over a fiber optic link. Three
fiber optic channels are built into the FCIM. An
electrical connector is provided to interface with a
Fan Out Card, providing 13 additional full duplex
fiber channels.
Redundancy
A State Select line is available on FCIMs for the
purpose of controlling which one of two FCIM
redundant fiber networks is to be used to control the
BCMs. A third FCIM (termed the “supervisory”
FCIM) monitors the operation of the two redundant
FCIMs, detecting the failure conditions that require
a switch over to the second FCIM, using the State
Select Line. Each BCM has a State Select input
connector J9.
Environment
Ambient temperature range of -20° to 50°C
Page 9 of 9
I.L. 4D01737B
Instructions for ECS2100 Three Phase Power Drawer - Draw Out Design
Full Converter (Inverter) Power Amplifier Drawer
The apparatus described herein is part of a system. A necessary complement to this amplifier is the circuit
The specific system is described in a separate that provides the firing pulses to the thyristors.
instruction leaflet located near the front of this Operation of the firing circuits is explained in the
instruction book. The system instructions should be Digital Firing Control Instruction Leaflet. The phase
thoroughly read and understood before proceeding lock loop used to create the firing reference is
with this leaflet. All "DANGER" and "CAUTION" generated on the FCIM and the firing signals are sent
notes included in the instructions for the system will to the BCM. On the BCM, gate pulse amplifiers apply
apply to the apparatus herein described. a picket fence signal to the Thyristor gates. The picket
fence signal is adjustable on the BCM by software
DRAWINGS settings appropriate for the application. In order to get
Typical Schematic (1100A) 4D01737A. the maximum range of output voltage, the gate circuits
Output Waveforms Inverter 662A221. of the thyristors must be pulsed at the proper time and
Mechanical Layout Power Drawer 4D01727A. in the proper sequence. During flashing, all of the
Mechanical Layout Power Drawer 4D01727D. bridges may be fired in unison and at a very high rate
Rear View of Power Drawer 4D01747C to cause the thyristor control bridge to act like a diode
bridge.
PURPOSE AND APPLICATION
FULL CONVERTER (Inverter)
The ECS2100 power converter is a switching type AC
to DC converter that uses silicon-controlled rectifiers During normal operation, the pulses must be 120
(thyristors) as the control element. It is used to supply electrical degrees apart between each thyristor in the
the excitation to the field of an electric machine. It is positive legs and 120 degrees apart between those in
an inverting type bridge and has thyristors in all legs the negative legs. In addition, the pulses between the
of the three-phase full wave bridge and thus is capable positive and negative legs must be 180 degrees apart.
of driving the output voltage both positive and Since there is a 180-degree shift between the positive
negative. Although voltage can reverse, the amplifier and negative thyristor pulses and a 120-degree shift
can only output positive current as the current can between each pulse in the positive or negative legs,
never reverse through a thyristor. See the typical there is no pulse occurring in a negative leg when a
electrical drawing 4D01737A. positive leg is pulsed. This would mean that there
would be no return path for the current. To provide the
The amplifier is constructed as a draw out drawer necessary return path, each thyristor is pulsed twice
assembly with contacts at the rear for both power and per cycle. The first pulse is the main pulse and
control disconnects. Many drawers may be paralleled determines what point in the cycle the thyristor will
to handle higher currents. The input voltage rating of conduct. The second pulse occurs 60 degrees later and
the drawer is typically limited to 600 Vac or less and is used to give a return path for the current when the
is based on creepage and clearance and the PIV of the amplifier is first turned on. To vary the output voltage
thyristors. The application environment must be from maximum positive to maximum negative, the
considered in both the voltage and current the rating. pulses must be varied 180 degrees (160 degrees
The rating chart is used as a guideline including margin).
DESCRIPTION AND OPERATION The inverter power amplifier has the capability of
reversing the load voltage while maintaining
Phase rotation and actual phasing of the three phase conventional current flow. This characteristic is useful
supply to the power disconnects must be AC1, AC2, in forcing the circuit current to zero by transferring the
AC3 as marked. This is necessary to insure that the magnetic energy from the load to the line.
gate pulses that fire the SCRs will be timed correctly.
Page 1 of 4
Instruction for Power Drawer I.L. 4D01737B
Note that if the gates are pulsed at zero delay with in the BCM on reception of the firing signal. Jumpers
respect to positive voltage on the anodes of the on the BCM select the required gate current and as
thyristors, current will flow when the supply voltage is stated earlier, each thyristor is fired twice per cycle.
positive and power will flow to the field. If the gates The rise time and duration of the pulses is very fast
are pulsed at 90 degrees delay, current will flow and a current probe and fast oscilloscope should be
during half the time the supply voltage is positive and used for accurate representation of the current
during half the time the supply voltage is negative. waveform.
The net result is zero average load voltage and zero
average power flow to the field. If the gates are pulsed A BCM, IT, and Power Supply are mounted on the
at more than 90 degrees delay, current will flow when front of each Power Drawer (see drawings 4D01737A
the supply voltage is negative longer than when it is and 4D01737D). The IT is used to measure the
positive and there will be power flow from the field to positive and negative shunt current. Software in the
the supply. A delay of 90 degrees to 180 degrees is a BCM uses the firing signal received from the FCIM,
transient condition and power will flow only until the the Conduction Monitor inputs and the IT to develop
field current is zero. measurements of the average peak current in each
thyristor. These currents, as well as the average shunt
Refer to drawing 662A221 showing output currents can be are gathered by the FCIM and are
waveforms. Note that these waveforms are drawn available via Modbus. They can also be viewed at the
assuming perfect sine waves at the input to the output of the CSL block in the BCM.
amplifier and do not show commutation effects. In
actual practice, the firing of the thyristors into a load CONDUCTION MONITORS
distorts the supply sine wave hence the output
waveforms will be distorted since they are made up of The Conduction Monitors are used to verify that each
parts of the supply sine wave. The following shows thyristor is conducting. The conduction monitors
typical field voltage: detect 30 amps or greater in both directions and are
placed in the ac input to the bridge (see the back view
of the bridge drawing 4D01747C). The conduction
monitor software (CSL block) in the BCM reads the
status of the conduction monitors and will detect when
a thyristor is not conducting. A thyristor may not be
conducting if the gate lead is open, or if a fuse is
blown. The following shows the output of a single
bridge into an inductive load with a missing pulse:
Page 2 of 4
Instruction for Power Drawer I.L. 4D01737B
If both the positive and negative thyristor in one phase will display this number. Use ccTool to verify this
are open, or when there is a blown fuse, the number.
conduction monitor software in the BCM will detect
the condition. The Alarm log in the FCIM should be REMOVING THE DRAWOUT UNIT
read, and from the information presented one can
deduce if a fuse is blown, or if thyristors are not The unit may be removed while the machine is under
conducting. load. Determine that the remaining drawers have
sufficient capacity to carry the load before removing a
drawer.
2. Slide the drawer out to the end of the rails till the
stops hit.
Page 3 of 4
Instruction for Power Drawer I.L. 4D01737B
Page 4 of 4
Highland, Illinois USA (618) 654-2341
Highland, Illinois USA (618) 654-2341
FOR
DE-EXCITATION/CROWBAR (DXCB) MODULE
STYLE 2D80367 G01, G02, G03, G12, G13, G23
Drawings
The following drawings are provided with this publication:
Outline drawing, 2D80367920
Block diagram, 2D80367001
Connection diagram, 2D80371
Operating Power
Operating power for the current sensor board circuitry is received via the control circuit board. Components on the
current sensor board reduce the 24 Vdc applied to the control circuit board down to an appropriate level.
LED D9
LED D9, located on the control circuit board, lights to confirm that the current sensor board is connected to the
control circuit board via the ribbon cable.
Thyristor Firing
Two optically-isolated logic inputs are available to control firing of the thyristor. Logic input J2 accepts a 24 Vdc
firing input at terminals FP24 (+) and FN24 (–). Logic input J1 accepts a 125 Vdc firing input at terminals FP125
(+) and FN125 (–). When thyristor firing is initiated by logic input J1 or J2, a train of pulses fire the thyristor for as
long as the logic commands firing. The initial high intensity of the firing pulse train decreases after approximately
200 milliseconds. If a power supply failure occurs, capacitors provide enough energy to fire the thyristors for 500
milliseconds. A gate pulse transformer isolates the control firing circuitry from the thyristor gate.
Pushbutton Controls
The control circuit board has two pushbutton controls: Test and Reset.
The Test pushbutton is used to simulate current flow through the thyristor. Jumper J7 must be in the E (enable)
position to allow this test.
The Reset pushbutton resets the CSRD signal when the control circuit board is in Manual Reset mode. Manual
Reset mode is enabled by placing jumper J6 in the M (manual) position.
Operating Power
The control circuit board accepts 24 Vdc operating power at terminals P24 (+), N24 (–), and COM at J4. These
terminals are protected by diodes against reverse polarity. Components on the control circuit board reduce the
Jumper J5
Jumper J5 is used to make the gate to cathode connection on the thyristor.
PARALLELING
Logic firing and BOD firing are paralleled so that either or both can fire the thyristor required. (BOD firing alone or
logic firing alone may be utilized in some applications.)
As shown in Figure 2, control circuit boards can be paralleled using ribbon cable connections to J10 and J11.
(Wire to the primary unit and connect to the followers with ribbon cable.) This feature is provided for redundancy
and to increase the rating for certain types of operation.
Parallel operation should be broken up into two categories: control firing and self firing.
Control Firing
Parallel operation via control firing is not a concern since the firing pulses are synchronized.
Self Firing
For de-excitation or crowbar applications, a resistor is required when DXCB modules are paralleled, either Rc or
Rd.
NOTE
For de-excitation operation via self firing, the excitation system must have a
breaker that will support the required voltage. For parallel operation without
separate discharge resistors in series with each thyristor, the voltage across the
parallel thyristor may disappear before self firing occurs.
SPECIFICATIONS
Power Connections
For DXCB module terminals CX and CB, use cables or bus bars from the generator field circuit. These terminals
are 0.375-16 UNC. Terminal CB is current in—anode side of the thyristor. Terminal DX is current out—cathode
side of the thyristor.
Logic Power
125 Vdc logic power is applied to pins 1 (+) and 3 (–) of connector DXTBP. The mating plug is Phoenix
MSTB2.5-ST-S.08.
Control Firing
Thyristor firing can be externally initiated through the application of either a 125 Vdc or 24 Vdc control firing input.
125 Vdc Control Firing
A 125 Vdc control firing input is applied to terminals FP125 (+) and FN125 (–) of connector J1. The mating plug is
Phoenix MSTB2.5-ST-5.08.
24 Vdc Control Firing
A 24 Vdc control firing input is applied to terminals FP24 (+) and FN24 (–) of connector J2. The mating plug is
Phoenix MSTB2.5-ST-5.08.
Physical Ratings
Dimensions: See drawing 2D80367920
Weight: 21.4 kg (47.2 lb)
Maximum Temperature: 55C (131F) at full rating
Humidity: 0 to 95% relative humidity, non-condensing
MAINTENANCE
The DXCB module requires no maintenance other than periodic inspection and removal of accumulated dust.
There are three transformers (T1, T2, and T3) that attenuate the PT signals from 120 Vac to 20 Vac. Jumpers
J7, J8, J10 (on the primary side), J4, J5, J6 (on the secondary side) are used to make a delta-delta
configuration. Each of the transformers can be used in a single-phase sensing configuration by removing the
appropriate primary and secondary jumpers. The 120 Vac PT signals are connected into the board at J19 and
the 20 Vac output signals connect at J1, J2, and J3. In a typical application, a one-to-one cable is used to
connect:
• From J1 of this card to the main channel SIM
• From J2 of this card to the redundant channel SIM
• From J3 of this card to the supervisor channel SIM
Transformers T4, T5, and T6 are used for current sensing. The primary side (J16) of the transformers is
typically connected across a 0.3 ohm precision sensing resistor. The sensing resistor is in series with the CT
secondary and rated currents are typically 4 Aac, rms. When using three CTs, jumpers J14 and J15 are used
to configure the secondary in a wye configuration. Three-phase sensing, single-phase sensing, and sensing
any two CT currents is supported.
Using a separate transformer card for the main, redundant, and supervisor channels will eliminate single
point failure in the transformer card.
Figure 1. PT Connections
INSTRUCTIONS FOR ECS2100 ISOLATION CARD IL25A4501A
Figure 2. CT Connections
I.L. 8651C64C
Revised 11/13/06
ECS2100 Isolation Transducer
INSTRUCTION LEAFLET
DRAWINGS As with all electrical equipment, appropriate
The following drawings are referenced within this safety measures should be taken whenever dealing
document. with the excitation equipment. High voltage is
IT Card Assembly ..............................8651C64 present within the excitation cubicles; their
FCIM Card Assembly ........................8651C67 magnitudes depend upon the particular system.
Opening the sources (e.g., disconnect device 41)
does not completely disconnect the high voltages.
PURPOSE As long as the machine is still physically
The purpose of the Isolation Transducer (IT) is to connected to the system, there is a possibility that
provide a highly isolated version of the input a safety hazard exists.
signal in a form convenient for reception by the
module using the signal. The output of the Every precaution must be taken when working at
Isolation Transducer is a pulsed fiber optic light the excitation control switchgear to ensure that all
signal with a frequency proportional to the input high voltages are isolated and avoided by test
voltage. The Isolation Transducer has two isolated personnel. In addition to the machine terminal
sections, each electrically isolated from the other voltage (460 Vac or greater) at the excitation
and with the output electrically isolated from the transformer, there may be other sources of power
input. The Isolation Transducer is specifically entering the cubicles, such as the customer
targeted at pairs of signals associated with the 125/250 Vdc and/or 120/240 Vac used to feed
power portions of a generator or exciter system. certain devices. A good rule to follow is to assume
The FCIM and BCM are ECS2100 modules that all connections are live and dangerous until
capable of using the IT for highly isolated input. proven otherwise and to avoid completely all body
contact with any of these voltages.
GLOSSARY
The accuracy of the transducer frequency is
BCM Bridge Control Module. Up to 16 ±4KHz = ±1.6% of Full Scale. No adjustment is
BCMs can be controlled by one provided within the Isolation Transducer. If
FCIM. necessary, adjustments may be made digitally
DFC Digital Firing Control (subset of within the user's program. Each of the modules
the digital excitation control which use the IT for input operates on the basis of
system). a user program viewable as a block diagram using
the ccTool program. The ccTool provides user
ECM Exciter Control Module. Contains adjustment for each specific input.
the excitation control, limiting,
protection, and communication The reception is based upon functions built into
software (but is not considered a the fiber optic FPGA. Due to the free running
part of the Digital Firing Control). characteristic of the VCOs, the average accuracy
FCIM Firing Control Interface Module. of the digital data is very good. The incoming
Processes the AC source frequency is counted over a known fixed time
waveforms and firing angle interval. Since the VCO is free-running, any pulse
command from the ECM and which is missed during one interval will still fall
determines when to fire each SCR. within the next interval. Thus quantization errors
FO Fan Out card. Provides transceiver are averaged out.
capability beyond the three built
into the FCIM as Standard. The advantage of a VCO translation is that the
FPGA Field Programmable Gate Array. isolation is provided by non-conducting optical
An integrated circuit that fiber.
implements complex logic
functions within a single package.
IT Isolation Transducer card. Isolates INSTALLATION
two analog signals for digital input
to FCIM or BCM and other When shipped the equipment will have its IT(s)
modules. physically installed and connected. If replacement
VCO Voltage Controlled Oscillator. A is necessary, carefully label and document each of
circuit that provides a variable the connections to the IT(s) in order to properly
frequency output proportional to a reconnect to a new board.
voltage input.
Refer to the IT Block Diagram (8651C64) for the
location of connectors, fuses, and jumpers.
OPERATION/APPLICATION
The Isolation Transducer has an input voltage
range of 100mV to 2000V. VERIFICATION OF CALIBRATION
The Isolation Transducer has two isolated Voltage
Controlled Oscillator (VCO) channels. Each There are no user adjustments on the IT Card.
channel creates an output frequency, which is However, the IT card may be tested for three
proportional to the input voltage for that channel. different voltage input ranges as a verification of
The transfer function for each channel is: accuracy. The factory verifies calibration for three
range conditions:
Fout= 750KHz +250KHz * Vin/Vrange
Revised 11/13/06
Page 2 of 5
INSTRUCTIONS FOR Isolation Transducer I.L. 8651C64C
LIMITS OF WARRANTY
SPECIFICATIONS AND PERFORMANCE
The warranty of this apparatus may be
invalidated, unless the following described Power Supply Requirements
procedures are followed. Apparatus which +24Vdc ±10%, with nominal current of 0.25 ADC
malfunctions should be replaced with new
units obtained from the factory. Environment
Malfunctioning items should be returned to the Ambient temperature range of -20°C to 50°C
factory for repair after authorization is
received from the local sales and service office Relative humidity of 0 to 95% non-condensing
or the factory. This is particularly true of
electronic printed circuit boards which require
careful handling by skilled personnel and for
which field repair or modifications should not
be attempted.
MAINTENANCE
Revised 11/13/06
Page 3 of 5
INSTRUCTIONS FOR Isolation Transducer I.L. 8651C64C
IT Calibration
Verification
Chart
Input Voltage Jumper Output Freq.
Configuration (KHz)
Max Input *200Mv
PLUS MINUS CH. 1 CH. 2 PLUS MINUS
23mV 23mV J15-J3& J17-J5& 778 720
J16-J4 J18-J6
45mV 45mV " " 800 692
68mV 68mV " " 834.8 664
90mV 90mV " " 860 636
112mV 112mV " " 890 608
135mV 135mV " " 920 580
151mV 151mV " " 950 552
186mV 186mV " " 974 523
200mV 200mV " " 1000 500
Max Input 200V
PLUS MINUS CH. 1 CH. 2 PLUS MINUS
50V 50V J15-J7& J17-J9& 778 725
J16-J8 J18-J10
100V 100V " " 800 700
200V 200V " " 850 650
300V 300V " " 900 600
400V 400V " " 950 550
500V 500V " " 1000 500
Max Input 500V
PLUS MINUS CH. 1 CH. 2 PLUS MINUS
200V 200V J15-J11 J17-J13 800 700
&J16-J2 &J18-J1
400V 400V " " 850 650
600V 600V " " 900 600
800V 800V " " 950 550
1000V 1000V " " 1000 500
• 100Mv or 200Mv scales selected by J27-28, J29-30 for the chart divide the input in mV by 2 for
100Mv scale.
Revised 11/13/06
Page 4 of 5
INSTRUCTIONS FOR Isolation Transducer I.L.8651C64
Revised 11/13/06
Page 5 of 5
Cutler-Hammer I.B. 2C12060H05
Double-wide Fixed
Breakers will be addressed in a general manner in this THE WARNINGS AND CAUTIONS INCLUDED AS
manual. Specific trip unit details and time-current char- PART OF THE PROCEDURAL STEPS IN THIS MAN-
acteristic curves are covered in separate documents UAL ARE FOR PERSONNEL SAFETY AND PROTEC-
specific to the trip units. TION OF EQUIPMENT FROM DAMAGE. AN EXAM-
PLE OF A TYPICAL WARNING LABEL HEADING IS
Magnum DS circuit breaker accessory items are dis- SHOWN ABOVE TO FAMILIARIZE PERSONNEL
cussed briefly in this manual. Field installation instruc- WITH THE STYLE OF PRESENTATION. THIS WILL
tions for such items, however, are covered in individual HELP TO INSURE THAT PERSONNEL ARE ALERT
instruction leaflets specific to the accessory. This infor- TO WARNINGS. IN ADDITION, CAUTIONS ARE ALL
mation is also available from the Cutler-Hammer web- UPPER CASE AND BOLDFACE.
site at www.cutler-hammer.com
All possible contingencies which may arise during installation operation or maintenance, and all details and variations
of this equipment do not purport to be covered by these instructions. If further information is desired by purchaser
regarding his particular installation, operation or maintenance of particular equipment, contact the local Cutler-
Hammer Inc. representative.
Effective 7/02
Page iv I.B. 2C12060H05
TABLE OF CONTENTS
3-1 Introduction........................................................................................................................................................11
3-2 Basic Circuit Breaker Assembly ........................................................................................................................15
3-3 Pole Units ..........................................................................................................................................................15
3-3.1 Primary Moving Contacts .....................................................................................................................15
3-3.2 Primary Stationary Contacts.................................................................................................................16
3-4 Operating Mechanism .......................................................................................................................................17
3-4.1 Manual Operation .................................................................................................................................17
3-4.2 Electrical Operation ..............................................................................................................................18
3-4.3 Anti-Pump Feature ...............................................................................................................................18
3-5 Arc Chambers ...................................................................................................................................................18
3-5.1 Arc Chute .............................................................................................................................................18
3-6 Electronic Tripping System................................................................................................................................19
3-6.1 Microprocessor-based Trip Unit ...........................................................................................................19
3-6.2 Rating Plug ...........................................................................................................................................21
3-6.3 Current Sensors ...................................................................................................................................21
3-6.4 Trip Actuator .........................................................................................................................................22
3-6.5 Mechanical Trip Flag ............................................................................................................................22
3-6.6 Making Current Release.......................................................................................................................22
3-6.7 High Instantaneous Trip Option............................................................................................................22
3-6.8 Voltage Taps ........................................................................................................................................22
3-7 Secondary Contacts and Connection Diagrams ...............................................................................................23
3-7.1 Connection Diagrams ...........................................................................................................................24
Effective7/02
I.B. 2C12060H05 Page v
PAGE
SECTION 7: TROUBLESHOOTING
7-1 Introduction........................................................................................................................................................49
Effective 7/02
Page vi I.B. 2C12060H05
FIGURES
1-1 Magnum DS Family of Low Voltage Power Fixed and Drawout Circuit Breakers (800-5000 Amperes) ..1
1-2 Typical Magnum Nameplate ....................................................................................................................2
1-3 Sample Designation Example ..................................................................................................................3
3-1 Typical Drawout Circuit Breaker Features (Front and Rear Views) ........................................................11
3-2 Typical Fixed Circuit Breaker Features (Front and Rear Views) ............................................................12
3-3 Typical Double-wide Standard Frame Circuit Breaker Features (Front and Rear Views) ......................13
3-4 Typical Magnum DS Drawout Circuit Breaker Front Cover ....................................................................14
3-5 Typical Magnum Construction (Right Side View)....................................................................................15
3-6 Features of Magnum Moving Conductor Assembly ................................................................................15
3-7 Narrow Frame (8-finger) Moving Conductor Assembly ..........................................................................16
3-8 Standard Frame (12-finger) Moving Conductor Assembly......................................................................16
3-9 Parital Cross-Sectional View (Shown in Closed Position) ......................................................................16
3-10 Electrically Operated Drawout Circuit Breaker with Front Cover Removed ............................................17
3-11 Circuit Breaker Closing Springs Being Manually Charged......................................................................18
3-12 Electrical Motor Operator to Charge Closing Spring ..............................................................................18
3-13 Cross Section of Conductor and Arc Control System ............................................................................19
3-14 Integral Arc Runner as Viewed From Top of Arc Chamber
(Arc Chute Removed and Circuit Breaker Closed) ................................................................................19
3-15 Magnum Arc Plate Assembly ..................................................................................................................19
3-16 Pictorial Diagram of Typical Current Sensing, Processing and Tripping System....................................20
3-17 Digitrip RMS 1150 Programmable Trip Unit Installed in Magnum DS Circuit Breaker............................21
3-18 Hand Held Tester ....................................................................................................................................21
3-19 Replaceable Current Sensors Shown with Bottom Adapters and Cover Plate Removed ......................22
3-20 Line Side Voltage Tap for 1150 Trip Unit ................................................................................................23
3-21 Top View Secondary Connectors............................................................................................................23
3-22 Secondary Connector Protective Hood ..................................................................................................23
3-23 Cassette Mounted Secondary Wiring ......................................................................................................24
3-24 AMP Secondary Wiring Removal Tool.....................................................................................................24
3-25 Digitrip Connection Diagrams .................................................................................................................25
thru
3-30 Digitrip Connection Diagrams .................................................................................................................30
3-31 Through-the-Window Electrical Accessories ...........................................................................................31
3-32 Shunt Trip with Cutoff Switch...................................................................................................................31
3-33 Shunt Trip Switch Installed ......................................................................................................................31
3-34 Spring Release with Optional Latch Check Switch ..................................................................................32
3-35 Undervoltage Release Device .................................................................................................................32
Effective7/02
I.B. 2C12060H05 Page vii
6-1 Top Rear View of Circuit Breaker with One Arc Chute Removed............................................................45
6-2 Bottom View of Arc Chute........................................................................................................................45
6-3 Primary Contacts with Circuit Breaker Open (Not Used for Contact Wear Inspection) ...........................46
6-4 Contact Inspection Area with Circuit Breaker Open.................................................................................46
6-5 Use of Contact Wear Indicator with Circuit Breaker Closed ....................................................................47
6-6 Trip Unit Rating Plug Location .................................................................................................................47
6-7 Current Sensor Cover in Place Over Sensors .........................................................................................48
6-8 One Current Sensor Shown Removed and Disconnected.......................................................................48
Effective 7/02
Page viii I.B. 2C12060H05
TABLES
Effective7/02
I.B. 2C12060H05 Page 1
Double-wide Fixed
Figure 1-1 Family of Magnum Low Voltage Power Fixed and Drawout Circuit Breakers (800-5000 Amperes)
Effective 7/02
Page 2 I.B. 2C12060H05
Effective7/02
I.B. 2C12060H05 Page 3
Effective 7/02
Page 4 I.B. 2C12060H05
SECTION 2: RECEIVING, HANDLING AND On drawout circuit breakers shipped without a cassette,
INSTALLATION two shipping clamps hook into the breaker side plates
and are held to the pallet with 4 lag screws (Figure 2-1).
2-1 GENERAL INFORMATION Remove the lag screws and clamps. Save the screws
and clamps for future shipment of the breaker. On
Magnum DS Power Circuit Breakers, when supplied as empty cassettes, remove the 4 or 5 lag screws and/or
part of an assembly, may be shipped already installed in machine screws which pass through the floorpan of the
their respective breaker compartments. Receiving and cassette holding it to the wooden pallet. On drawout
handling of this equipment is addressed in an assembly breakers shipped in a cassette, first remove the breaker
instruction manual supplied with the assembled equip- from the cassette using the levering mechanism and
ment. This instruction manual applies to only the circuit drawout rails. After the breaker is removed the machine
breakers.
screws passing through the floorpan can be removed.
2-2 SUGGESTED TOOLS
Every effort is made to ensure that Magnum DS circuit 2-3.1 STORING CIRCUIT BREAKER
breakers arrive at their destination undamaged and
ready for installation. Care should be exercised, howev- If it is necessary to store a circuit breaker before instal-
er, to protect the breakers from impact at all times. Do lation, do so in its original shipping container. Keep the
not remove protective packaging until the breakers are circuit breaker in a clean dry place. Ensure there is
ready for inspection, testing and/or installation. ample air circulation and heat, if necessary, to prevent
condensation. It is very important that the circuit break-
When ready to inspect and install the Magnum DS cir- er not be exposed to dirt or moisture.
cuit breaker, carefully remove the banding straps and lift
off the cardboard box. Remove any additional packing NOTICE
material and internally packed documentation. The cir-
cuit breaker and/or cassette are mounted to a wooden A circuit breaker that has been stored for any
shipping pallet. length of time should be operated a minimum of
five times before it is placed in service.
Effective 7/02
I.B. 2C12060H05 Page 5
Effective 7/02
Page 6 I.B. 2C12060H05
Molded Rail
Supports
Extension Rail
Cutout
Figure 2-3 Rear View Showing Current Sensor Rating Figure 2-4 One Side of Drawout Circuit Breaker
Through Viewing Window Properly Seated on Extension Rail
Effective 7/02
I.B. 2C12060H05 Page 7
! CAUTION
Cell For:
Pin Locations
1 2 3 4 5 6 7 8
MDN-408, 412, 416 X X
DO NOT DISABLE REJECTION INTERLOCKS. X
MDN-508, 512, 516 X X
DOING SO AND USING A LOWER CAPACITY CIR-
MDN-608, 612, 616 X X X X
CUIT BREAKER IN AN INCOMPATIBLE CASSETTE
COULD RESULT IN AN ELECTRICAL FAULT WHICH MDS-408, 412, 416 X X
5
1
6
2
7
3
! CAUTION
4
8 MAKE CERTAIN THAT THE CIRCUIT BREAKER IS
FULLY INSERTED INTO ITS COMPARTMENT
BEFORE ANY ATTEMPT IS MADE TO LEVER THE
CIRCUIT BREAKER. ATTEMPTING TO LEVER THE
CIRCUIT BREAKER IN BEFORE IT IS FULLY POSI-
TIONED INSIDE ITS COMPARTMENT CAN RESULT
Figure 2-5 Cassette Rejection Interlock Pin IN DAMAGE TO BOTH THE CIRCUIT BREAKER AND
Positioning/Installation THE COMPARTMENT.
Effective 7/02
Page 8 I.B. 2C12060H05
Compartment Secondary
Front Door Connection Not Made Rear of
Compartment
Circuit
Breaker Primary
Side View Connections
Not Made
Circuit Breaker
Out of Compartment
On Extension Rails ■ No Electrical Connections Made
■ Breaker On Extension Rails
■ Remove or Inspection Position
Secondary
Connection
Not Made
Rear of
Compartment
Compartment
Front Door
Circuit
Breaker Primary
Side View Connections
Not Made
Circuit
Breaker Primary
Side View Connections
Not Made
Effective 7/02
I.B. 2C12060H05 Page 9
Secondary
Connection Made
Rear of
Compartment
Compartment
Front Door
Circuit
Breaker Primary
Side View Connections
Made
Effective 7/02
Page 10 I.B. 2C12060H05
CONNECT
TEST
DISCONNECT
Mounting
Foot
Figure 2-11 Levering Position Indication
Figure 2-12 Typical Fixed Magnum Circuit Breaker
NOTICE
2-7 FIXED CIRCUIT BREAKER
The Magnum DS fixed type circuit breaker differs from Refer to the circuit breaker weights in Table 2.1 to
the drawout version in that it has no levering device, pri- ensure that the panel on which a fixed circuit break-
mary disconnects and secondary disconnects (Figure 2- er is to be mounted is capable of supporting the
12). In addition, a fixed circuit breaker does not have a weight.
standard feature to hold the breaker in a trip-free posi-
tion. To ensure the proper sequence of operation 2-8 CIRCUIT BREAKER OPERATION
between two or more circuit breakers, an optional key
interlock is mounted through the front panel (Figure 3-4). Circuit breakers should be operated manually and/or
electrically before they are put into service. This can be
Circuit breaker terminals have holes for making bolted done during the installation process or some later date
horizontal primary bus connections. Adapters are avail- prior to start-up. To check circuit breaker operation, fol-
able for making vertical primary bus connections. low the operational procedures outlined in Section 3 for
Secondary connections can be made through standard both manually operated and electrically operated circuit
terminal blocks or a special connector compatible with breakers.
the drawout circuit breaker’s type secondary connector.
Both secondary connection devices are mounted at the
top front of the circuit breaker.
Effective 7/02
I.B. 2C12060H05 Page 11
SECTION 3: CIRCUIT BREAKER mon for the two frame sizes that cover all continuous
DESCRIPTION AND OPERATION current ratings through 5000 amperes.
3 2 1
12 10
11
5
7
6
10
Figure 3-1 Typical Drawout Circuit Breaker Features (Front and Rear Views)
Effective 7/02
Page 12 I.B. 2C12060H05
1
6 Fixed Primary Terminal (with optional Vertical Adapter)
7 Arc Chamber
4 8 Sensor Rating Viewing Window
9 Mounting Foot
10 Circuit Breaker Nameplate
2
3 1
10
9
4
Figure 3-2 Typical Fixed Circuit Breaker Features (Front and Rear Views)
Effective 7/02
I.B. 2C12060H05 Page 13
2
1
9 4
9
6
Figure 3-3 Typical Double-wide Standard Frame Fixed Circuit Breaker Features (Front and Rear Views)
Effective 7/02
Page 14 I.B. 2C12060H05
1 2
CLOSED (Red)
5
(Green)
OPEN
(Yellow)
6
CHARGED
3 (White)
DISCHARGED
4
8
PUSH ON (Green)
14
9 PUSH OFF
7 (Red)
15 10
CONNECT
13 11 TEST
DISCONNECT
12
Red = Connect
Yellow = Test
Green = Disconnect
1 Trip Flag (Pop Out Indicator) 7 Manual “OFF” Button (Push) 12 Color Coded-Breaker
Position Indicator
2 Three Accessory Windows 8 Manual “ON” Button (Push)
13 Nameplate
3 Trip Unit 9 Manual Charge Handle
14 Trip Unit Test Port
4 Rating Plug 10 Optional Operation Counter
15 Trip Unit Cover with Two
5 Contact Status (Open-Close) 11 Padlockable Levering Device Access
Mounting Screws (Mounting
Door for Drawout Breaker
6 Spring Status (Charged-Discharged) Screws will Accept Customer
Supplied Lead Security Meter
Seals
Effective 7/02
I.B. 2C12060H05 Page 15
3-2 BASIC CIRCUIT BREAKER ASSEMBLY provide for pole unit isolation and insulation from one
another. Each pole unit has one primary contact
Magnum DS circuit breakers use a rigid frame housing assembly, which consists of a moving portion and a
construction of engineered thermoset composite resins. fixed portion. The exact design configuration depends
This construction provides high strength structural prop- upon the breaker’s frame size. Circuit breakers with
erties, excellent dielectric characteristics and resistance frame sizes of 4000 amperes and higher use two pole
to arc tracking. units and arc chute assemblies connected mechanically
and electrically in parallel to form one phase.
The 3-piece construction approach provides support
while isolating and insulating power conductors (Figure 3-3.1 PRIMARY MOVING CONTACTS
3-5):
Depending upon the frame size, each primary moving
(1)
1 A 2-piece engineered thermoset composite resin contact assembly is comprised of multiple individual
case encloses current paths and arc chambers. The copper contact fingers connected to the load conductor
chambers act to channel arc gases up and out of the cir- through flexible braided connectors (Figure 3-6). Two
cuit breaker during interruption. flexible connectors are used to connect each finger to
the load conductor. The number of fingers used
(2)
2 The operating mechanism sits on the front of the depends upon the circuit breaker’s continuous and
case and is electrically isolated and insulated from cur- short-circuit current ratings (Figures 3-7 and 3-8). On
rent contact structures. It is covered by an insulating some ratings fingers are removed and replaced with
front cover. spacers.
3-3 POLE UNITS The single contact finger performs both the main and
arcing contact functions on different parts of the same
A current carrying pole unit is individually enclosed and finger (Figure 3-6). A highly conductive alloy pad is part
rigidly supported by the case. The individual chambers of the contact finger and functions as the moving main
contact, and is called the “Heel.” The tip of the same
contact finger functions as the moving arcing contact,
and is called the “Toe.”
Figure 3-5 Typical Magnum Construction (Right Side Figure 3-6 Features of Magnum Moving Conductor
View) Assembly
Effective 7/02
Page 16 I.B. 2C12060H05
“Toe”
(Arcing Contact)
“Heel”
(Main Contact)
“Toe”
(Arcing Contact)
“Heel”
(Main Contact)
Figure 3-7 Narrow Frame (8-finger) Moving Conductor Figure 3-8 Standard Frame (12-finger) Moving
Assembly Conductor Assembly
yyyy
ÀÀÀÀ
@@@@
,,,,
3-3.2 PRIMARY STATIONARY CONTACTS
Breaker
,,,
yyy
,,
yy ,
y
yyyyy
,,,,,
The primary stationary contact is a combination of two
items (Figure 3-9). One is a conductive pad mounted Front
on the line conductor which functions as the stationary
,,,
yyy
,,y
yy,y
,
main contact. The other is an arc runner, also connect-
ed to the line conductor. The integral arc runner serves Arc Chute
yyy
,,,
,,
yy ,
y,
y
a dual purpose:
Integral
Arc Runner
• Fixed arcing contact
,,,
yyy
,,
yy yy
,,
,
y
Moving Contact Arcing
• Part of the arc chute Fingers Contact (Toe)
Line
,,,,
yyyy,,
yy
Conductor
Current
Flow
,,,,
yyyy,,
yy
Moving Contact
Springs Stationary
Main Contact
Moving Main
,,,,
yyyy
,
y
xxxxxxxx Contact (Heel)
x x
x x
xxxxxxxx
,,,,
yyyy
y,
Current
Flow
xxxxxxxx
x x
x x
xxxxxxxx
Breaker
Bottom
Effective 7/02
I.B. 2C12060H05 Page 17
3-4 OPERATING MECHANISM “OFF” buttons respectively located on the front of the cir-
cuit breaker (Figure 3-4). Performing either operation is
The Magnum DS operating mechanism is based on the accomplished by pressing and releasing the appropriate
proven cam and spring design of the DSII power circuit button. Access to these pushbuttons can be limited by
breaker. It is easily accessed by removing four cover the use of an optional, padlockable cover. In addition,
screws and the front cover (Figure 3-10). The mecha- complete access to the “ON” button can be prevented
nism is a two-step stored energy mechanism. Potential with an optional prevent close cover. The status of the
energy is stored to close the circuit breaker. Sufficient springs and the primary contacts are always indicated in
energy to open the circuit breaker remains available an indicator window just above the pushbuttons.
after a closing operation.
Electrically operated optional devices are available to
3-4.1 MANUAL OPERATION automatically close or trip a manually operated circuit
breaker. An electrical spring release is available to close
On manually operated circuit breakers, the closing spring a manually operated circuit breaker. Two optional
can only be charged manually. To manually charge the devices, a shunt trip and an undervoltage release, are
spring, insert one finger in the recess behind the charging available to automatically trip (open) a manually operated
handle and pull out. This permits a gloved hand to grasp circuit breaker. All of these UL listed optional devices can
the handle and begin charging (Figure 3-11). It takes be installed easily in the field. For more details on these
from 5 to 7 downward strokes on the charging handle to devices, refer to paragraph 3-8 in this manual.
complete the manual charging process. It is possible to
manually recharge the spring immediately after closing An electrical operator which is used to charge the closing
the circuit breaker and before it has been tripped open. spring automatically can be added to a manually operat-
ed circuit breaker in the field (Figure 3-12). Manually
Standard manually operated circuit breakers are closed operated circuit breakers are pre-wired to accept this
and opened by hand using the Manual “ON” and Manual addition.
1
1 Secondary Wiring Points
2
2 Field Installable Accessories
(3 maximum)
3 Trip Unit
Figure 3-10 Electrically Operated Drawout Circuit Breaker with Front Cover Removed
Effective 7/02
Page 18 I.B. 2C12060H05
Electrical Motor
Operator
Figure 3-11 Circuit Breaker Closing Springs Being Figure 3-12 Electrical Motor Operator to Charge
Manually Charged Closing Spring
3-4.2 ELECTRICAL OPERATION closing, a Latch Check Switch (LCS) option is available
(see paragraph 3-8.1) which will block the application of
For electrically operated circuit breakers, the springs are the electrical close command until the breaker is ready
normally charged through the use of an electrical operator to close.
(Figure 3-12). The springs can, however, be charged
manually as just described in the previous paragraph 3-5 ARC CHAMBERS
(Figure 3-11).
The Magnum DS circuit breaker utilizes arc chambers to
Like the manually operated circuit breaker in the previous insulate and isolate individual poles from one another,
paragraph, electrically operated circuit breakers can also from the rest of the circuit breaker, and from operating
be manually closed and opened through the use of the personnel (Figure 3-1). Arc chambers are molded and
front mounted Manual “ON” and Manual “OFF” buttons. integral parts of the circuit breaker frame. Enclosed
within each arc chamber is an arc chute which mounts
An electrically operated circuit breaker from the factory is over each set of primary contacts.
also equipped as standard with a spring release to close
the circuit breaker electrically. An optional shunt trip and After the main contacts part, any remaining current is
undervoltage release are also available to trip (open) an driven to the arcing contacts (Figure 3-13). Magnetic
electrically operated circuit breaker. Refer to paragraph action draws the arc to the arc chute. As the arcing
3-8 for more details on both standard and optional contacts separate, the moving arcing contacts discharge
devices. into the arc chute plates while the integral arc runner
also helps to draw the arc into the arc chute (Figure 3-
3-4.3 ANTI-PUMP FEATURE 14).
The Magnum circuit breaker has both mechanical and 3-5.1 ARC CHUTE
electrical anti-pump features. If the circuit breaker is
closed on a fault condition (and trips open while the The Magnum DS arc chute mounts down over the arc-
CLOSE signal is maintained), using either the mechani- ing contact. Alternating V-shaped arc chute plates
cal pushbutton or the electrical close coil, it will not attract the arc and interrupt it. The top arc plate, which
make subsequent attempt to close until the close com- is a part of the arc chute itself, also helps to attract the
mand is removed and reapplied. Note that if the close arc away from the moving arcing contact and up into the
signal is applied prematurely (before the breaker is com- arc chute’s V-shaped plates (Figure 3-15).
pletely charged and latched), the close command will be Arc chute components are assembled in an insulating
ignored until it is removed and reapplied. For electrical
Effective 7/02
I.B. 2C12060H05 Page 19
Models 220 and 520 are plug compatible and inter- Top Plate for
,,
yy
yyy
,,, ,
y
changeable in the field. Circuit breakers with these trip Arcing Contact
units can be upgraded to Models 520M and/or 520MC in
Figure 3-15 Magnum Arc Plate Assembly
,,
yy
,,,
yyy
,,
yy
,,,
yyyy
,
yy
,,,
y
,
y
Top Arc
Plate
,,
yy ,,
yy
Integral
Arc Runner Integral
Arc Runner
,,,,
yyyy
,
yy,
Current
Flow
,,,,
yyyy
xxxxxxxx
x x
x x
xxxxxxxx
,,,,
yyyy
,y
Current
Flow
Figure 3-13 Cross Section of Conductor and Arc Figure 3-14 Integral Arc Runner Viewed From Top of Arc
Control System Chamber (Arc Chute Removed, Circuit Breaker Closed)
Effective 7/02
Page 20 I.B. 2C12060H05
Cutler-Hammer
Rating
Toroidal Plug
Current
Sensor
Trip
Trip Unit Actuator
A 01 02 03 Typical Magnum DS
B
Circuit Breaker
C
N A B C Sensors
G
Figure 3-16 Pictorial Diagram of Typical Current Sensing, Processing and Tripping System
the field; however additional wiring (for power supply
and communications) may be required to take full
advantage of the additional features. Contact Cutler- Table 3.1 Magnum Digitrip Trip Units
Hammer for upgrading to Model 1150.
Functions 220 520 520M➄ 520MC➄ 1150➄
The electronic trip units are self-powered. When the cir- LSIG Protection Yes ➀ Yes Yes Yes Yes
cuit breaker is closed, no external power is required to
operate their protective systems. Current signal levels Disable (I) No Yes Yes Yes Yes
and the control power are derived from the current sen- GF Protection No Yes Yes Yes Yes
sors integrally mounted in the circuit breaker. GF Alarm No No Yes Yes Yes
Display No No Yes ➁ Yes ➁ Yes ➂
A functional local test of a major portion of the trip unit’s
electronic circuitry and the circuit breaker’s mechanical Programmable No No No No Yes
tripping action can be verified through the trip unit’s test Metering No No Yes ➃ Yes ➃ Yes
receptacle (Figure 3-17). This is accomplished using a Power and
Digitrip (DS Type) Test Kit which provides a secondary Energy Values No No No No Yes
injection test that simulates the current sensors. A Power Quality No No No No Yes
small hand held Magnum functional Test Kit can also be
used to check circuitry and mechanical tripping func- Communication No No No Yes Yes
tions (Figure 3-18). ➀ Long and Instantaneous only.
➁ One-line, (four characters per line) LCD display.
When the circuit breaker is shipped from the factory, the
➂ Three-line, (eight characters per line) LED display.
trip unit’s protective functions are normally set at mini-
➃ Phase, neutral, ground, and high load current only.
mum values. For specific overload tripping characteris-
tics and time/current curves to coordinate with a load or ➄ Available control voltages are 24/48Vdc, 120Vac and 240Vac
system, refer to the trip unit instruction book.
Effective 7/02
I.B. 2C12060H05 Page 21
Effective 7/02
Page 22 I.B. 2C12060H05
Effective 7/02
I.B. 2C12060H05 Page 23
3-6.8 VOLTAGE TAPS (Figure 3-21). The wiring points are finger safe with
no more than two wires per terminal.
On circuit breakers with Digitrip 1150 trip units potential
taps are required to monitor the three phase voltages. Up to two secondary contact plug-in connectors (AMP),
Voltage taps may be placed on either the line (top) or each with 30 secondary points, are mounted on the top
load (bottom) terminals of the breaker at the factory. rear portion of the circuit breaker . The plug-in connec-
Figure 3-20 illustrates line-side voltage taps. tors are protected by a molded hood (Figure 3-22).
How many connectors are mounted depends upon a
3-7 SECONDARY CONTACTS AND CONNECTION number of considerations, such as whether the circuit
DIAGRAMS breaker is electrically or manually operated and how
many features are required. When the front cover of the
A maximum of sixty secondary wiring connection points circuit breaker is removed, the top of each plug-in con-
are available on the standard frame circuit breaker (48 nector is exposed. A label on each connector identifies
on narrow frame), each dedicated to a specific function the wiring points.
Protective Hood
Effective 7/02
Page 24 I.B. 2C12060H05
Drawout type circuit breakers: Compatible secondary Closed Hinged Covers Terminal Blocks
plug-in connectors are mounted on the top front portion with Testing Holes
of the drawout cassette (Figure 3-23). These connec-
tors match and plug into the circuit breaker mounted
connectors. Contact points are wired from the cas-
sette’s plug-in connectors to cassette mounted terminal
blocks. The terminal blocks are also mounted on the
top front portion of the cassette. The secondary termi-
nals have finger-proof hinged covers with small holes for
probe testing.
Effective 7/02
Effective 7/02
I.B. 2C12060H05
SEE NOTE 13
NOTES: 6. TO PROVIDE SELECTED TIME DELAYS FOR SHORT TIME AND/OR GROUND TIME FUNCTIONS FOR TESTING OR NON-
1. 4 WIRE CRIMP CONNECTION ZONE INTERLOCKING APPLICATIONS, A JUMPER FROM B-8 TO B-9 IS REQUIRED.
2. 3 WIRE CRIMP IF HIGH INST TRIP MODULE IS SUPPLIED. 7. ON THREE POLE BREAKERS ONLY, HAVING GROUND FAULT FUNCTIONALITY, A JUMPER INSTALLED FROM B-6 TO B-7
3. WIRE CONNECTION USED WITH DIGITRIP 520M/520MC GROUND ALARM POWER SUPPLY MODULE WILL “HANG UNCON- WILL ENABLE SOURCE GROUND FAULT SENSING AND DISABLE RESIDUAL GROUND FAULT SENSING. INPUTS B-4 AND B-5
Figure 3-25 Connection Diagram for Narrow and Standard Frame with Digitrip 220/520/520M/520MC
NECTED” IF DIGITRIP 220 OR 520 IS SUPPLIED. WILL BE REASSIGNED FOR SOURCE GROUND SENSOR INPUTS.
4. ALL AUX SWITCHES SHOWN WITH BREAKER IN OPEN POSITION AND WITH SPRING NOT CHARGED AND WITH TRIP UNIT 8. THIS LEAD SUPPLIED ON G62 STYLE HIGH INSTANTANEOUS TRIP MODULE ONLY.
IN “NON-TRIPPED” STATE (OTS SWITCHES). 9. MOTOR OPERATOR SWITCH SHOWN WITH BREAKER CLOSING SPRING DISCHARGED.
5. THE SPRING RELEASE ACCESSORY CONSISTS OF A “SR” COIL AND A P.C. BOARD. THE PRINTED CIRCUIT BOARD PRO- 10. ON 4-POLE BREAKERS, THE NEUTRAL CURRENT SENSOR IS THE SAME STYLE AND WIRED THE SAME AS THE PHASE
VIDES A .20 SECOND PULSE FOR THE CLOSING OPERATION. VOLTAGE MUST BE REMOVED AND THEN REAPPLIED FOR SENSORS AND IS LOCATED WITHIN THE BREAKER FRAME. THE SECONDARY CONTACTS B-4, B-5, ARE NOT WIRED OUT.
SUBSEQUENT OPERATION. 11. SECOND SHUNT TRIP MAY BE INSTALLED (USING A-7, A-8 CONTACTS) IN PLACE OF UVR. THIRD AUX SWITCH NOT
AVAILABLE WITH SECOND SHUNT TRIP.
AN OPTIONAL LATCH CHECK SWITCH (LCS) ACCESSORY MAY BE CONNECTED TO THE SPRING RELEASE. THE (CLOSED) 12. ONLY ONE LATCH CHECK SWITCH MAY BE INSTALLED. USE OF CUSTOMER ACCESSIBLE LATCH CHECK SWITCH (B-29,
LCS DELAYS THE SPRING RELEASE PULSE UNTIL THE BREAKER MECHANISM IS READY TO CLOSE (CHARGED AND B-30) IN SERIES WITH SPRING RELEASE DEFEATS ANTI-PUMP FUNCTION AND IS NOT RECOMMENDED. SEE NOTE 3 FOR
RESET). (THIS WILL INSURE THAT THE LATCH WILL ALWAYS BE IN THE PROPER STATE BEFORE THE SPRING RELEASE SPRING RELEASE LATCH CHECK SWITCH.
PULSE IS INITIATED). IF VOLTAGE IS MAINTAINED TO THE SPRING RELEASE, THE CLOSING PULSE WILL OCCUR WHEN 13. THIS AUX. SWITCH ASSEMBLY NOT AVAILABLE IN NARROW FRAME. MAXIMUM OF TWO AUX SWITCHES (4A/4B)
THE MECHANISM IS CHARGED AND RESET (LCS OPEN). VOLTAGE MUST BE REMOVED AND REAPPLIED TO THE SPRING INSTALLED IN NARROW FRAME.
RELEASE FOR SUBSEQUENT OPERATION.
Page 25
Page 26
Figure 3-26 Connection Diagram for Standard Frame with Digitrip 1150
5. ON THREE POLE BREAKERS ONLY, HAVING GROUND FAULT FUNCTIONALITY, A JUMPER INSTALLED FROM B-6 TO B-7
NOTES: WILL ENABLE SOURCE GROUND FAULT SENSING AND DISABLE RESIDUAL GROUND FAULT SENSING. INPUTS B-4 AND
1. 3 WIRE CRIMP IF HIGH INST TRIP MODULE IS SUPPLIED. B-5 WILL BE REASSIGNED FOR SOURCE GROUND SENSOR INPUTS.
2. ALL AUX SWITCHES SHOWN WITH BREAKER IN OPEN POSITION AND WITH SPRING NOT CHARGED AND WITH TRIP UNIT 6. NORMALLY OPENED CONTACT PROGRAMMED AS RELAY A. VIA DIGITRIP FRONT PANEL. (ALARM CONTACT).
IN “NON-TRIPPED” STATE (OTS SWITCHES). 7. NORMALLY CLOSED CONTACT PROGRAMMED AS RELAY B. VIA DIGITRIP FRONT PANEL. (BLOCK CLOSE CONTACT)
3. THE SPRING RELEASE ACCESSORY CONSISTS OF A “SR” COIL AND A P.C. BOARD. THE PRINTED CIRCUIT BOARD PRO- 8. NORMALLY OPEN CONTACT PROGRAMMED AS RELAY C. VIA DIGITRIP FRONT PANEL. (LATCHING CONTACT)
VIDES A .20 SECOND PULSE FOR THE CLOSING OPERATION. VOLTAGE MUST BE REMOVED AND THEN REAPPLIED FOR 9. THIS LEAD SUPPLIED ON G62 STYLE HIGH INSTANTANEOUS TRIP MODULE ONLY.
SUBSEQUENT OPERATION. 10. MOTOR OPERATOR SWITCH SHOWN WITH BREAKER CLOSING SPRING DISCHARGED.
11. ON 4-POLE BREAKERS, THE NEUTRAL CURRENT SENSOR IS THE SAME STYLE AND WIRED THE SAME AS THE
AN OPTIONAL LATCH CHECK SWITCH (LCS) ACCESSORY MAY BE CONNECTED TO THE SPRING RELEASE. THE (CLOSED) PHASE SENSORS AND IS LOCATED WITHIN THE BREAKER FRAME. THE SECONDARY CONTACTS B-4, B-5, ARE NOT
LCS DELAYS THE SPRING RELEASE PULSE UNTIL THE BREAKER MECHANISM IS READY TO CLOSE (CHARGED AND WIRED OUT.
RESET). (THIS WILL INSURE THAT THE LATCH WILL ALWAYS BE IN THE PROPER STATE BEFORE THE SPRING RELEASE 12. FOUR POINT SOCKET USED HERE.
PULSE IS INITIATED). IF VOLTAGE IS MAINTAINED TO THE SPRING RELEASE, THE CLOSING PULSE WILL OCCUR WHEN 13. SECOND SHUNT TRIP MAY BE INSTALLED (USING A-7, A-8 CONTACTS) IN PLACE OF UVR. THIRD AUX SWITCH NOT
THE MECHANISM IS CHARGED AND RESET (LCS OPEN). VOLTAGE MUST BE REMOVED AND REAPPLIED TO THE SPRING AVAILABLE WITH SECOND SHUNT TRIP.
RELEASE FOR SUBSEQUENT OPERATION. 14. ONLY ONE LATCH CHECK SWITCH MAY BE INSTALLED. USE OF CUSTOMER ACCESSIBLE LATCH CHECK SWITCH (B-
4. TO PROVIDE SELECTED TIME DELAYS FOR SHORT TIME AND/OR GROUND TIME FUNCTIONS FOR TESTING OR NON- 29, B-30) IN SERIES WITH SPRING RELEASE DEFEATS ANTI-PUMP FUNCTION AND IS NOT RECOMMENDED. SEE NOTE 3
ZONE INTERLOCKING APPLICATIONS, A JUMPER FROM B-8 TO B-9 IS REQUIRED. FOR SPRING RELEASE LATCH CHECK SWITCH.
Effective 7/02
I.B. 2C12060H05
Effective 7/02
I.B. 2C12060H05
NOTES:
1. 4 WIRE CRIMP CONNECTION
2. 3 WIRE CRIMP IF HIGH INST TRIP MODULE IS SUPPLIED. 6. TO PROVIDE SELECTED TIME DELAYS FOR SHORT TIME AND/OR GROUND TIME FUNCTIONS FOR TESTING OR NON-
3. WIRE CONNECTION USED WITH DIGITRIP 520M/520MC GROUND ALARM POWER SUPPLY MODULE WILL “HANG UNCON- ZONE INTERLOCKING APPLICATIONS, A JUMPER FROM B-8 TO B-9 IS REQUIRED.
NECTED” IF DIGITRIP 220 OR 520 IS SUPPLIED. 7. ON THREE POLE BREAKERS ONLY, HAVING GROUND FAULT FUNCTIONALITY, A JUMPER INSTALLED FROM B-6 TO B-7
4. ALL AUX SWITCHES SHOWN WITH BREAKER IN OPEN POSITION AND WITH SPRING NOT CHARGED AND WITH TRIP UNIT WILL ENABLE SOURCE GROUND FAULT SENSING AND DISABLE RESIDUAL GROUND FAULT SENSING. INPUTS B-4 AND B-
IN “NON-TRIPPED” STATE (OTS SWITCHES). 5 WILL BE REASSIGNED FOR SOURCE GROUND SENSOR INPUTS.
5. THE SPRING RELEASE ACCESSORY CONSISTS OF A “SR” COIL AND A P.C. BOARD. THE PRINTED CIRCUIT BOARD PRO- 8. THIS LEAD SUPPLIED ON G62 STYLE HIGH INSTANTANEOUS TRIP MODULE ONLY.
VIDES A .20 SECOND PULSE FOR THE CLOSING OPERATION. VOLTAGE MUST BE REMOVED AND THEN REAPPLIED FOR 9. MOTOR OPERATOR SWITCH SHOWN WITH BREAKER CLOSING SPRING DISCHARGED.
SUBSEQUENT OPERATION. 10. ON 4-POLE BREAKERS, THE NEUTRAL CURRENT SENSOR IS THE SAME STYLE AND WIRED THE SAME AS THE PHASE
SENSORS AND IS LOCATED WITHIN THE BREAKER FRAME. THE SECONDARY CONTACTS B-4, B-5, ARE NOT WIRED OUT.
AN OPTIONAL LATCH CHECK SWITCH (LCS) ACCESSORY MAY BE CONNECTED TO THE SPRING RELEASE. THE (CLOSED) 11. SECOND SHUNT TRIP MAY BE INSTALLED (USING A-7, A-8 CONTACTS) IN PLACE OF UVR. THIRD AUX SWITCH NOT
LCS DELAYS THE SPRING RELEASE PULSE UNTIL THE BREAKER MECHANISM IS READY TO CLOSE (CHARGED AND AVAILABLE WITH SECOND SHUNT TRIP.
RESET). (THIS WILL INSURE THAT THE LATCH WILL ALWAYS BE IN THE PROPER STATE BEFORE THE SPRING RELEASE 12. ONLY ONE LATCH CHECK SWITCH MAY BE INSTALLED. USE OF CUSTOMER ACCESSIBLE LATCH CHECK SWITCH (B-
PULSE IS INITIATED). IF VOLTAGE IS MAINTAINED TO THE SPRING RELEASE, THE CLOSING PULSE WILL OCCUR WHEN 29, B-30) IN SERIES WITH SPRING RELEASE DEFEATS ANTI-PUMP FUNCTION AND IS NOT RECOMMENDED. SEE NOTE 3
THE MECHANISM IS CHARGED AND RESET (LCS OPEN). VOLTAGE MUST BE REMOVED AND REAPPLIED TO THE SPRING FOR SPRING RELEASE LATCH CHECK SWITCH.
Figure 3-27 Connection Diagram for Double-wide Frame with Digitrip 520/520M/520MC with ABCABC Configuration
RELEASE FOR SUBSEQUENT OPERATION.
Page 27
LINE N1 N2 LA1 LA2 LB1 LB2 LC1 LC2
Page 28
NOTES: 6. TO PROVIDE SELECTED TIME DELAYS FOR SHORT TIME AND/OR GROUND TIME FUNCTIONS FOR TESTING OR NON-
1. 4 WIRE CRIMP CONNECTION ZONE INTERLOCKING APPLICATIONS, A JUMPER FROM B-8 TO B-9 IS REQUIRED.
2. 3 WIRE CRIMP IF HIGH INST TRIP MODULE IS SUPPLIED. 7. ON THREE POLE BREAKERS ONLY, HAVING GROUND FAULT FUNCTIONALITY, A JUMPER INSTALLED FROM B-6 TO B-
3. WIRE CONNECTION USED WITH DIGITRIP 520M/520MC GROUND ALARM POWER SUPPLY MODULE WILL “HANG 7 WILL ENABLE SOURCE GROUND FAULT SENSING AND DISABLE RESIDUAL GROUND FAULT SENSING. INPUTS B-4
UNCONNECTED” IF DIGITRIP 220 OR 520 IS SUPPLIED. AND B-5 WILL BE REASSIGNED FOR SOURCE GROUND SENSOR INPUTS.
4. ALL AUX SWITCHES SHOWN WITH BREAKER IN OPEN POSITION AND WITH SPRING NOT CHARGED AND WITH TRIP 8. THIS LEAD SUPPLIED ON G62 STYLE HIGH INSTANTANEOUS TRIP MODULE ONLY.
UNIT IN “NON-TRIPPED” STATE (OTS SWITCHES). 9. MOTOR OPERATOR SWITCH SHOWN WITH BREAKER CLOSING SPRING DISCHARGED.
5. THE SPRING RELEASE ACCESSORY CONSISTS OF A “SR” COIL AND A P.C. BOARD. THE PRINTED CIRCUIT BOARD 10. ON 4-POLE BREAKERS, THE NEUTRAL CURRENT SENSOR IS THE SAME STYLE AND WIRED THE SAME AS THE
PROVIDES A .20 SECOND PULSE FOR THE CLOSING OPERATION. VOLTAGE MUST BE REMOVED AND THEN REAPPLIED PHASE SENSORS AND IS LOCATED WITHIN THE BREAKER FRAME. THE SECONDARY CONTACTS B-4, B-5, ARE NOT
FOR SUBSEQUENT OPERATION. WIRED OUT.
11. SECOND SHUNT TRIP MAY BE INSTALLED (USING A-7, A-8 CONTACTS) IN PLACE OF UVR. THIRD AUX SWITCH NOT
AN OPTIONAL LATCH CHECK SWITCH (LCS) ACCESSORY MAY BE CONNECTED TO THE SPRING RELEASE. THE (CLOSED) AVAILABLE WITH SECOND SHUNT TRIP.
LCS DELAYS THE SPRING RELEASE PULSE UNTIL THE BREAKER MECHANISM IS READY TO CLOSE (CHARGED AND 12. ONLY ONE LATCH CHECK SWITCH MAY BE INSTALLED. USE OF CUSTOMER ACCESSIBLE LATCH CHECK SWITCH (B-
RESET). (THIS WILL INSURE THAT THE LATCH WILL ALWAYS BE IN THE PROPER STATE BEFORE THE SPRING RELEASE 29, B-30) IN SERIES WITH SPRING RELEASE DEFEATS ANTI-PUMP FUNCTION AND IS NOT RECOMMENDED. SEE NOTE 3
PULSE IS INITIATED). IF VOLTAGE IS MAINTAINED TO THE SPRING RELEASE, THE CLOSING PULSE WILL OCCUR WHEN FOR SPRING RELEASE LATCH CHECK SWITCH.
THE MECHANISM IS CHARGED AND RESET (LCS OPEN). VOLTAGE MUST BE REMOVED AND REAPPLIED TO THE SPRING
RELEASE FOR SUBSEQUENT OPERATION.
Figure 3-28 Connection Diagram for Double-wide Frame with Digitrip 520/520M/520MC with AABBCC Configuration
Effective 7/02
I.B. 2C12060H05
Effective 7/02
I.B. 2C12060H05
NOTES 4. TO PROVIDE SELECTED TIME DELAYS FOR SHORT TIME AND/OR GROUND TIME FUNCTIONS FOR TESTING OR NON-
1. ON THREE POLE BREAKERS ONLY (NOT EIGHT PHYSICAL POLES), HAVING GROUND FAULT FUNCTIONALITY, A ZONE INTERLOCKING APPLICATIONS, A JUMPER FROM B-8 TO B-9 IS REQUIRED.
JUMPER INSTALLED FROM B-6 TO B-7 WILL ENABLE SOURCE GROUND FAULT SENSING AND DISABLE RESIDUAL 5. 3 WIRE CRIMP IF HIGH INST TRIP MODULE IS SUPPLIED.
GROUND FAULT SENSING. INPUTS B-4 AND B-5 WILL BE REASSIGNED FOR SOURCE GROUND SENSOR INPUTS. 6. NORMALLY OPENED CONTACT PROGRAMMED AS RELAY A. VIA DIGITRIP FRONT PANEL. (ALARM CONTACT).
2. ALL AUX SWITCHES SHOWN WITH BREAKER IN OPEN POSITION AND WITH SPRING NOT CHARGED AND WITH TRIP 7. NORMALLY CLOSED CONTACT PROGRAMMED AS RELAY B. VIA DIGITRIP FRONT PANEL. (BLOCK CLOSE CONTACT)
UNIT IN “NON-TRIPPED” STATE (OTS SWITCHES). 8. NORMALLY OPEN CONTACT PROGRAMMED AS RELAY C. VIA DIGITRIP FRONT PANEL. (LATCHING CONTACT)
Figure 3-29 Connection Diagram for Double-wide Frame with Digitrip 1150 with ABCABC Configuration
3. THE SPRING RELEASE ACCESSORY CONSISTS OF A “SR” COIL AND A P.C. BOARD. THE PRINTED CIRCUIT BOARD PRO- 9. ON 4-POLE BREAKERS (ACTUALLY 8 PHYSICAL POLES), THE NEUTRAL CURRENT SENSOR IS THE SAME STYLE AND
VIDES A .20 SECOND PULSE FOR THE CLOSING OPERATION. VOLTAGE MUST BE REMOVED AND THEN REAPPLIED FOR WIRED THE SAME AS THE PHASE SENSORS AND IS LOCATED WITHIN THE BREAKER FRAME. THE SECONDARY CON-
SUBSEQUENT OPERATION. TACTS B-4, B-5, ARE NOT WIRED OUT.
10. MOTOR OPERATOR SWITCH SHOWN WITH BREAKER CLOSING SPRING DISCHARGED.
AN OPTIONAL LATCH CHECK SWITCH (LCS) ACCESSORY MAY BE CONNECTED TO THE SPRING RELEASE. THE (CLOSED) 11. FOUR POINT SOCKET USED HERE.
LCS DELAYS THE SPRING RELEASE PULSE UNTIL THE BREAKER MECHANISM IS READY TO CLOSE (CHARGED AND 12. SECOND SHUNT TRIP MAY BE INSTALLED (USING A-7, A-8 CONTACTS) IN PLACE OF UVR. THIRD AUX SWITCH NOT
RESET). (THIS WILL INSURE THAT THE LATCH WILL ALWAYS BE IN THE PROPER STATE BEFORE THE SPRING RELEASE AVAILABLE WITH SECOND SHUNT TRIP.
PULSE IS INITIATED). IF VOLTAGE IS MAINTAINED TO THE SPRING RELEASE, THE CLOSING PULSE WILL OCCUR WHEN 13. ONLY ONE LATCH CHECK SWITCH MAY BE INSTALLED. USE OF CUSTOMER ACCESSIBLE LATCH CHECK SWITCH (B-
THE MECHANISM IS CHARGED AND RESET (LCS OPEN). VOLTAGE MUST BE REMOVED AND REAPPLIED TO THE SPRING 29, B-30) IN SERIES WITH SPRING RELEASE DEFEATS ANTI-PUMP FUNCTION AND IS NOT RECOMMENDED. SEE NOTE 3
RELEASE FOR SUBSEQUENT OPERATION. FOR SPRING RELEASE LATCH CHECK SWITCH.
Page 29
LINE N1 N2 LA1 LA2 LB1 LB2 LC1 LC2
Page 30
NOTES 4. TO PROVIDE SELECTED TIME DELAYS FOR SHORT TIME AND/OR GROUND TIME FUNCTIONS FOR TESTING OR NON-
1. ON THREE POLE BREAKERS ONLY (NOT EIGHT PHYSICAL POLES), HAVING GROUND FAULT FUNCTIONALITY, A ZONE INTERLOCKING APPLICATIONS, A JUMPER FROM B-8 TO B-9 IS REQUIRED.
JUMPER INSTALLED FROM B-6 TO B-7 WILL ENABLE SOURCE GROUND FAULT SENSING AND DISABLE RESIDUAL 5. 3 WIRE CRIMP IF HIGH INST TRIP MODULE IS SUPPLIED.
GROUND FAULT SENSING. INPUTS B-4 AND B-5 WILL BE REASSIGNED FOR SOURCE GROUND SENSOR INPUTS. 6. NORMALLY OPENED CONTACT PROGRAMMED AS RELAY A. VIA DIGITRIP FRONT PANEL. (ALARM CONTACT).
2. ALL AUX SWITCHES SHOWN WITH BREAKER IN OPEN POSITION AND WITH SPRING NOT CHARGED AND WITH TRIP 7. NORMALLY CLOSED CONTACT PROGRAMMED AS RELAY B. VIA DIGITRIP FRONT PANEL. (BLOCK CLOSE CONTACT)
UNIT IN “NON-TRIPPED” STATE (OTS SWITCHES). 8. NORMALLY OPEN CONTACT PROGRAMMED AS RELAY C. VIA DIGITRIP FRONT PANEL. (LATCHING CONTACT)
Figure 3-30 Connection Diagram for Double-wide Frame with Digitrip 1150 with AABBCC Configuration
3. THE SPRING RELEASE ACCESSORY CONSISTS OF A “SR” COIL AND A P.C. BOARD. THE PRINTED CIRCUIT BOARD PRO- 9. ON 4-POLE BREAKERS (ACTUALLY 8 PHYSICAL POLES), THE NEUTRAL CURRENT SENSOR IS THE SAME STYLE AND
VIDES A .20 SECOND PULSE FOR THE CLOSING OPERATION. VOLTAGE MUST BE REMOVED AND THEN REAPPLIED FOR WIRED THE SAME AS THE PHASE SENSORS AND IS LOCATED WITHIN THE BREAKER FRAME. THE SECONDARY CON-
SUBSEQUENT OPERATION. TACTS B-4, B-5, ARE NOT WIRED OUT.
10. MOTOR OPERATOR SWITCH SHOWN WITH BREAKER CLOSING SPRING DISCHARGED.
AN OPTIONAL LATCH CHECK SWITCH (LCS) ACCESSORY MAY BE CONNECTED TO THE SPRING RELEASE. THE (CLOSED) 11. FOUR POINT SOCKET USED HERE.
LCS DELAYS THE SPRING RELEASE PULSE UNTIL THE BREAKER MECHANISM IS READY TO CLOSE (CHARGED AND 12. SECOND SHUNT TRIP MAY BE INSTALLED (USING A-7, A-8 CONTACTS) IN PLACE OF UVR. THIRD AUX SWITCH NOT
RESET). (THIS WILL INSURE THAT THE LATCH WILL ALWAYS BE IN THE PROPER STATE BEFORE THE SPRING RELEASE AVAILABLE WITH SECOND SHUNT TRIP.
PULSE IS INITIATED). IF VOLTAGE IS MAINTAINED TO THE SPRING RELEASE, THE CLOSING PULSE WILL OCCUR WHEN 13. ONLY ONE LATCH CHECK SWITCH MAY BE INSTALLED. USE OF CUSTOMER ACCESSIBLE LATCH CHECK SWITCH (B-
THE MECHANISM IS CHARGED AND RESET (LCS OPEN). VOLTAGE MUST BE REMOVED AND REAPPLIED TO THE SPRING 29, B-30) IN SERIES WITH SPRING RELEASE DEFEATS ANTI-PUMP FUNCTION AND IS NOT RECOMMENDED. SEE NOTE 3
RELEASE FOR SUBSEQUENT OPERATION. FOR SPRING RELEASE LATCH CHECK SWITCH.
Effective 7/02
I.B. 2C12060H05
I.B. 2C12060H05 Page 31
Shunt Trip - The shunt trip is an optional device on cir- Figure 3-32 Shunt Trip with Cutoff Switch
cuit breakers (Figures 3-32 and 3-33). It opens the cir-
cuit breaker instantaneously when its coil is energized
by a voltage input (Table 3.3). A total of two shunt trips
can be mounted on a Magnum DS circuit breaker.
Effective 7/02
Page 32 I.B. 2C12060H05
Spring Release - The spring release is an optional Undervoltage Release - The undervoltage release is
device (Figure 3-34). It remotely closes the circuit an optional device on both manually and electrically
breaker when the coil is energized by a voltage input operated circuit breakers (Figure 3-35). It opens the cir-
(Table 3.4). The closing spring must be fully charged cuit breaker when its supply voltage falls to between 35-
and the trip latch reset (not held in the tripped position) 60% of rated voltage. If the release is not energized to
for the SR to operate. If these two conditions are not 85% of its supply voltage, the circuit breaker cannot be
met the close signal will be ignored until it is removed closed electrically or manually (Table 3.5).
and re-applied.
Auxiliary Switch - An auxiliary switch is an optional
An optional Latch Check Switch (LCS) can also be device providing remote electrical indication if the circuit
installed to delay application of power to the Spring breaker is open or closed (Figure 3-37). Up to 3 auxil-
Release coil until the circuit breaker is “ready to close”. iary switches can be mounted in the circuit breaker.
The LCS will not permit energization of the Spring Each switch has 2 normally open (“a”) and 2 normally
Release until the breaker is fully charged and the trip closed (“b”) contacts for a total of 12 available contacts
latch is reset. Two versions of the LCS are available. (Table 3.6).
One version is wired internally to the Shunt Trip coil
control circuit. On the other version the LCS switch
contacts are brought out through the secondary con-
tacts for integration into external control schemes. Note
that placing the (externally accessible) LCS directly in
series with the ST coil is not recommended as this will
override the “anti-pump” feature of the electrical charg-
ing/closing system.
Effective 7/02
I.B. 2C12060H05 Page 33
Mechanical
Figure 3-37 Auxiliary Switch (2A/2B) Trip Indicator
Effective 7/02
Page 34 I.B. 2C12060H05
Effective 7/02
I.B. 2C12060H05 Page 35
Operations
Counter
“OFF”
Key Lock
Figure 3-41 Cover Mounted Key Lock and Operations Figure 3-42 Cassette Mounted Key Lock
Counter
3-8.3 MECHANICAL ACCESSORIES Cassette Lock - A cassette mounted lock can be used
in conjunction with different interlocking schemes (such
There are eight optional mechanical type accessories: as main-tie-main) (Figure 3-42). The lock holds the cir-
cuit breaker trip-free in the conected position, preventing
• Operations Counter it from being closed.
• Off Key Lock Up to three lock cylinders can be installed on one cas-
• Cassette Lock sette. Cutler-Hammer supplies the lock provisions only.
• Pushbutton Cover The customer is responsible for the locks, which can be
• Prevent Close Cover Kirk or Castell.
• Cassette Safety Shutters
• Cassette Cell Switch
Pushbutton Cover - A padlockable cover is available to
• Door Escutcheon
limit access to the “ON” and “OFF” pushbuttons (Figure
• Waterproof Cover
3-43). It can be installed with either or both pushbutton
• Mechanical Interlock
covers in place.
Operations Counter - The operations counter is a
mechanical device used to provide a record of the num-
ber of circuit operations. It is mounted in the lower right
portion of the circuit breaker and can be viewed through
the front cover (Figure 3-41).
Off Key Lock - The off key lock secures the circuit
breaker in the “OFF” position. It is mounted in the lower
right portion of the circuit breaker and can be viewed
through the front cover (Figure 3-41). The customer
supplies the key lock. The provisions available are for
Kirk, Castell or Ronis.
Effective 7/02
Page 36 I.B. 2C12060H05
Prevent Close Cover - Complete access to the “ON” Door Escutcheon - The door escutcheon is a molded
pushbutton can be prevented by adding the prevent frame used to seal the space between the circuit break-
close cover to the pushbutton cover. er and the compartment door cutout. It is supplied with
a mounting gasket (Figure 3-48).
Cassette Safety Shutters - Automatically operated
insulating type safety shutters are available for use with
the drawout cassette. When the drawout circuit breaker
is levered from the CONNECT position, the shutters
automatically close to cover the fixed primary contacts
(Figure 3-44). When the circuit breaker is levered into
the cassette, the shutters automatically open permitting
primary connections to be made (Figure 3-45).
Effective 7/02
I.B. 2C12060H05 Page 37
Effective 7/02
Page38 I.B. 2C12060H05
SECTION 4: DRAWOUT CIRCUIT supplies vertical stab/terminals only (Figure 4-5). The
BREAKER AND CASSETTE basic cassette omits the copper stab/terminals so that
these pieces can be integrated with vertical bus bars
4-1 GENERAL provided by the switchgear builder (Figure 4-6). The
universal cassette provides a set of flat pad terminals on
Section 3 discussed topics and features common to all the rear of the cassette that can be adapted to vertical,
Magnum DS circuit breakers, no matter what the mount- horizontal or front connection (Figures 4-7). Mounting
ing configuration. In this section, features unique to the locations for cell (TOC) switches, safety shutters,
drawout configuration not covered elsewhere, including mechanical interlocks and key interlocks are provided
the drawout cassette, are covered. Drawings and on the cassette. Note that the narrow frame cassette
dimensions associated with all circuit breakers, drawout uses the IEC cell switches and shutter assemblies.
cassettes and any appropriate primary bus connections
can be found in a separate document entitled
Engineering Data 2C12062H01. The installation and 4-2 DRAWOUT CIRCUIT BREAKER DIMENSIONS
levering of a drawout circuit breaker were discussed in
Section 2. If necessary, review that information, since it The Magnum DS drawout circuit breaker connects to the
will not be repeated here. fixed primary stabs of the drawout cassette through the pri-
mary finger clusters attached to the rear of the circuit
4-1.1 DRAWOUT CASSETTE breaker. Two different frame sizes cover all Magnum DS
circuit breakers from an overall dimensional standpoint.
A drawout circuit breaker is used in combination with a Circuit breaker drawings can be found in Engineering
fixed drawout cassette (Figures 4-1 and 4-3); the dra- Data 2C12062H01.
wout circuit breaker is equipped with automatic primary
disconnects (Figure 4-2). The cassette provides all of 4-3 DRAWOUT CASSETTE DIMENSIONS
the necessary interfaces to the drawout circuit breaker
including automatic primary and secondary connections. Cassette drawings provide all the dimensional informa-
For the narrow frame circuit breaker a single cassette tion required for all mounting configurations and can
style using horizontal stabs and horizontal customer bus also be found in Engineering Data 2C12062H01.
bar terminals is available (Figure 4-4). For the standard Review carefully for a specific installation.
and double-wide circuit breakers three cassette styles,
all with vertical stabs, are available: basic, standard, and
universal. The standard cassette
Effective 7/02
I.B. 2C12060H05 Page 39
4 5
1 2
Effective 7/02
Page 40 I.B. 2C12060H05
Effective 7/02
I.B. 2C12060H05 Page 41
Effective 7/02
Page 42 I.B. 2C12060H05
5-1 GENERAL
Effective 7/02
I.B. 2C12060H05 Page 43
Effective 7/02
Page44 I.B. 2C12060H05
After the first inspection, inspect at least once a year. If Eaton Cutler-Hammer recommends that the following
these recommended inspections show no maintenance functional tests be performed on Magnum circuit break-
requirements, the period may be extended to a more ers as part of any maintenance procedure. The circuit
economical point. Conversely, if the recommended breaker should be removed from service and Cutler-
inspection shows, for instance, a heavy accumulation of Hammer notified if the circuit breaker fails to perform any
dirt or other foreign matter that might cause mechanical, of these tests successfully. Please be prepared to pro-
insulation or other electrical damage, the inspection and vide the number of operations the circuit breaker has to
maintenance interval should be decreased. date as well as the following nameplate information:
❶ G.O.#: It: Seq: ❸ Code:
6-4 WHAT TO INSPECT ❷ Cust. P.O.: ❹ Date of Manufacture
➎ Cat#:
What to inspect and to what extent is dictated by the
nature of the maintenance function. Routine inspec-
tions require one type of observation. Inspections fol-
lowing a known high level fault require more detailed
inspections.
Effective 7/02
I.B. 2C12060H05 Page 45
Charge the breaker mechanism springs either using the Since the arc chutes are removed, this is an ideal time
charging handle or the motor operator. Close the break- to inspect primary contacts for wear using the circuit
er by applying rated voltage to the spring release acces- breaker’s contact wear indicators. The details associat-
sory and verify closing by noting the state of the indicat- ed with primary contact inspection are presented in the
ing flag. Charge the breaker mechanism springs either next paragraph.
using the charging handle or the motor operator. If
using the motor operator, disconnect power to it to pre-
vent automatic recharging. Open the breaker by apply-
Arc Chute Baffled
ing rated voltage to the shunt trip accessory. Close the
breaker using the spring release accessory. Is the Removed Cover
breaker closed? Open the breaker using the shunt trip
accessory. Is the breaker open? Repeat this entire
described test procedure three times.
Arc Chamber
Trip Unit Overload Functional Test
This test uses the Digitrip 1150 self test function, the
Digitrip Test Kit or the handheld Magnum Functional
Test Kit. Review test kit instructions for the trip unit.
Instruction leaflet 5720B55, section 1.2 or 1.3 applies for
instantaneous test procedures or paragragraph 5.2.1
“1150 Self Testing, Trip Mode” in the trip unit instruction
leaflet 70C1036.
Effective 7/02
yy
,,
z
Page 46 I.B. 2C12060H05
|
{{
Arcing Integral
Contact Arc
(Toe) Runner
Stationary
Main Contact
Moving Main
Contact
(Side View)
Figure 6-3 Primary Contacts with Circuit Breaker Open Figure 6-4 Contact Inspection Area with Circuit Breaker
(Not Used for Contact Wear Inspection) Open
NOTICE
With the arc chutes removed, visually inspect each pri- ! WARNING
mary contact structure for signs of wear and/or damage.
The primary contacts with the circuit breaker open can ARC CHUTES MUST ALWAYS BE SECURED PROP-
be viewed by looking directly down into the arc chamber ERLY IN PLACE BEFORE A CIRCUIT BREAKER IS
(Figure 6-3 and 6-4). INSTALLED IN A CIRCUIT BREAKER COMPART-
MENT. FAILURE TO DO THIS COULD RESULTS IN
A contact wear indicator is provided for each primary EQUIPMENT DAMAGE, BODILY INJURY OR EVEN
contact and indicates whether or not the contact should DEATH.
be replaced. Inspection of the contacts using the con-
tact wear indicators is conducted only with the circuit Once the inspection is complete, be sure the arc chutes
breaker closed (Figures 6-5). are properly replaced as previously described in para-
graph 6-4.1.
Effective 7/02
I.B. 2C12060H05 Page 47
Side-to-Side Side-to-Side
Ledge Ledge
Contact Wear
Contact Wear Inspection Area
Inspection Area (Ledge Now Becoming
(Ledge Not Visible Visible Under
Under Contacts) Contacts)
Figure 6-5 Use of Contact Wear Indicator with Circuit Breaker Closed
6-5 CIRCUIT BREAKER MODIFICATIONS AND To remove the rating plug from the trip unit, open the
CHANGES small rating plug door located on the right side of the trip
unit (Figure 6-6). The trip unit’s battery cavity is also
The topics discussed here will relate to those actions located behind this door. Use a 1/8” wide screwdriver to
that can be taken in the field to change, update, main- remove the M4 screw holding the rating plug in position.
tain or repair a Magnum DS circuit breaker. This infor- Pull the door to release the rating plug from the trip unit.
mation does not, however, include most accessory
devices. Their installation is covered by separate
instruction leaflets dedicated to the individual devices.
The tasks described here do not, under ordinary circum-
stances, require any assistance beyond the appropriate
instructional material. If further assistance is required,
however, contact your Cutler-Hammer representative.
NOTICE
If a rating plug is not installed in the trip unit, the
trip unit will trip when energized. Also remember
that the trip unit’s rating plug and the circuit break-
er’s current sensors must have matching ratings.
Effective 7/02
Page 48 I.B. 2C12060H05
To install a new rating plug, insert the rating plug into f the circuit breaker is a drawout configuration, the lower
the cavity where the other rating plug was removed. primary disconnect finger clusters and the vertical adap-
Make sure the three pins on the rating plug are aligned tors must first be removed from frame sizes up to
with the sockets in the cavity. The rating plug should fit 3000/3200A. On the 3000/3200A frame, both the upper
with a slight insertion force. and lower primary disconnects and vertical adaptors
must be removed. Each primary disconnect finger clus-
ter is removed by loosening the two hex-head bolts with
! CAUTION a 10 mm wrench. These bolts do not have to be com-
pletely removed to slide the primary disconnects off of
the terminals. Remove the vertical adaptors next from
TO PREVENT DAMAGE TO THE RATING PLUG, DO the circuit breaker terminals by removing the two or
NOT FORCE IT INTO THE MOUNTING CAVITY. three 10 mm bolts holding them in place (Figure 6-8).
Use the same 1/8” screwdriver to tighten the M4 screw The current sensors are removed by pulling them off of
and secure the rating plug in the trip unit. The maxi- the terminals and unplugging the wiring plugs from the
mum torque on the mounting screw is 15 in-oz. Close sensors (Figure 6-8).
the rating plug door.
Install new current sensors by connecting the wiring
6-5.2 CURRENT SENSOR REPLACEMENT plugs to the sensors and sliding the sensors over the
terminals. Reinstall the cover over the sensors and
secure in place with the screws previously removed.
NOTICE
Reinstall the previously removed vertical adaptors to the
terminals using the removed hardware and 40 ft-lb of
Remember that the trip unit’s rating plug and the tightening torque. Make sure the vertical adaptors are
circuit breaker’s current sensors must have match- square to the rear housing. Slip the primary discon-
ing ratings. nects on to the vertical adaptors. Make sure the primary
disconnects are fully inserted on to the vertical adaptors.
The three current sensors are installed at the rear of the Tighten the two retention bolts to 40 in-oz of torque.
circuit breaker on the lower terminals. A cover with sen- Properly engaged and secured retention bolts should
sor rating viewing windows covers the sensors and is engage the slots or holes in the vertical adaptors.
held in place with screws (Figure 6-7). Remove the
cover by removing the screws.
Vertical
Adaptor
Effective 7/02
I.B. 2C12060H05 Page 49
SECTION 7: TROUBLESHOOTING
7-1 INTRODUCTION
Circuit breaker opens Undervoltage release Check and correct the UVR
(fault trip indicator button operates; voltage too low supply voltage (85-110% rated
is not out) or zero voltage)
Effective 7/02
Page 50 I.B. 2C12060H05
Table 7.1 Circuit Breaker Troubleshooting Guide (continued from previous page)
Circuit breaker makes Closing spring not fully Charge spring manually; check
no attempt to close with charged (check SPRING voltage to electrical operator;
either local (manual) or CHARGED indicator) replace electrical operator if
remote controls; springs faulty
do not discharge
If equipped with undervoltage Unplug undervoltage release
release, undervoltage release from mounting deck and retry
is not energized or is faulty closing operation; if OK, check
voltage supply to undervoltage
release (>85%); replace under-
voltage release if faulty
Effective 7/02
I.B. 2C12060H05 Page 51
Table 7.1 Circuit Breaker Troubleshooting Guide (continued from previous page)
Symptom Probable Cause Corrective Actions
Circuit breaker cannot Spring release (closing) coil Check power supply voltage;
be closed remotely (can supply voltage low or spring replace spring release if faulty
be closed locally) release faulty
Circuit breaker cannot Opening and/or closing Check reason for lock
be closed locally (but pushbuttons locked
can be closed remotely)
Circuit breaker does not Charging motor supply voltage Check charging motor electrical
recharge electrically but absent or too low (<85%) circuit voltage (check under
will recharge manually load)
Drawout circuit breaker Circuit breaker will not fully Circuit breaker ratings do not
will not lever-in enter cell (cell rejection correspond to the cassette
code plate) requirements
Effective 7/02
Page 52 I.B. 2C12060H05
8-1 GENERAL
Effective 7/02
I.B. 2C12060H05
Cutler-Hammer
Pittsburgh, Pennsylvania U.S.A.
Effective 7/02(ISI)
Style 2C12060H05
Printed in U.S.A.
150 W S in g le O150W�Single�Output�Switching�Power�Supply
u tput Switching Power Sup pl y aSs--115500 sseer irei es s
����������
�����������������������������������
������������������������������������������������
������������������������������
���������������������������
����������������������������������
����������������
SPECIFICATION
MODEL AS150-5
S-150-5 AS150-7.5
S-150-7.5 AS150-9
S-150-9 AS150-12
S-150-12 AS150-13.5
S-150-13.5 AS150-15
S-150-15 AS150-24
S-150-24 AS150-27
S-150-27 AS150-48
S-150-48
DC�VOLTAGE 5V 7.5V 9V 12V 13.5V 15V 24V 27V 48V
RATED�CURRENT 30A 20A 16.7A 12.5A 11.2A 10A 6.5A 5.6A 3.2A
CURRENT�RANGE 0�~�30A 0�~�20A 0�~�16.7A 0�~�12.5A 0�~�11.2A 0�~�10A 0�~�6.5A 0�~�5.6A 0�~�3.2A
RATED�POWER 150W 150W 150.3W 150W 151.2W 150W 156W 151.2W 153.6W
RIPPLE�&�NOISE�(max.) Note.2 150mVp-p 150mVp-p 180mVp-p 180mVp-p 180mVp-p 180mVp-p 240mVp-p 240mVp-p 240mVp-p
OUTPUT VOLTAGE ADJ.�RANGE 4.5�~�5.5V 6�~�8.3V 8�~�10.4V 10.6�~�13.2V 12�~�15V 13.5�~�16.5V 21�~�28V 24�~�30V 43�~�53V
VOLTAGE�TOLERANCE Note.3 2.0% 1.0% 1.0% 1.0% 1.0% 1.0% 1.0% 1.0% 1.0%
LINE�REGULATION 0.5% 0.5% 0.3% 0.3% 0.3% 0.3% 0.2% 0.2% 0.2%
LOAD�REGULATION 0.5% 0.5% 0.3% 0.3% 0.3% 0.3% 0.2% 0.2% 0.2%
SETUP,�RISE�TIME 100ms,�50ms�at�full�load
HOLD�TIME (Typ.) 28ms�at�full�load
VOLTAGE�RANGE 88�~�132VAC/176�~�264VAC�selected�by�switch����������248�~�370VDC
FREQUENCY RANGE 47�~�63Hz
EFFICIENCY (Typ.) 78% 80% 80% 82% 83% 84% 85% 86% 87%
INPUT
AC�CURRENT (Typ.) 3.2A/115VAC����������1.6A/230VAC
INRUSH�CURRENT (Typ.) COLD�START 35A
LEAKAGE�CURRENT <3.5mA /�240VAC
105�~�150% rated�output�power
OVER�LOAD
Protection�type�:�Shut�down�o/p�voltage,�re-power�on�to�recover
PROTECTION
5.75�~�6.75V 8.63�~�10.13V 10.35�~�12.2V 13.8�~�16.2V 15.53�~�18.2V 17.25�~�20.3V 30�~�34.8V 31.1�~�36.45V 55.2�~�64.8V
OVER�VOLTAGE
Protection�type�:�Shut�down�o/p�voltage,�re-power�on�to�recover
WORKING�TEMP. -10�~�+60 (Refer�to�output�load�derating�curve)
WORKING�HUMIDITY 20�~�90%�RH�non-condensing
ENVIRONMENT STORAGE�TEMP.,�HUMIDITY -20�~�+85 ,�10�~�95%�RH
TEMP.�COEFFICIENT 0.03%/ (0�~�50
VIBRATION 10�~�500Hz,�2G�10min./1cycle,�60min.�each�along�X, Y,�Z�axes
SAFETY STANDARDS UL1012,�UL60950-1, TUV�EN60950-1 Approved
WITHSTAND�VOLTAGE I/P-O/P:3KVAC�����I/P-FG:1.5KVAC�����O/P-FG:0.5KVAC
SAFETY & ISOLATION�RESISTANCE I/P-O/P,�I/P-FG,�O/P-FG:100M�Ohms/500VDC
EMC EMI�CONDUCTION�&�RADIATION Compliance�to��EN55022�(CISPR22)�Class�B
(Note�4) Compliance�to EN61000-3-2,-3
HARMONIC�CURRENT
EMS�IMMUNITY Compliance�to�EN61000-4-2,3,4,5,6,8,11;�ENV50204,�EN55024,�Light�industry�level,��criteria A
MTBF 286.7K�hrs�min.������MIL-HDBK-217F�(25 )
OTHERS DIMENSION 199*110*50mm�(L*W*H)
PACKING 0.8Kg;�16pcs/13.8Kg/0.95CUFT
����������������������������������������������������������������������������������������� �����������������������
NOTE
����������������������������������������������������������������������������������������������������������������������������������������
������������������������������������������������������������������������������
���������������������������������������������������������������������������������������������������������������������� �����������������������������������
���������������
File�Name:S-150-SPEC���2005-09-13
300 Myles Standish Blvd., Taunton, MA 02780
WWW.ASTRODYNE.COM Ph: 1-800-823-8082 Fax: 508-823-8181
150 W S in g le O150W�Single�Output�Switching�Power�Supply
u tput Switching Power Sup pl y aSs--115500 sseer irei es s
Mechanical�Specification Case�No.�906�����Unit:mm
192
5 172
100
6
12
3.5
1
2
9.5
4
110
97
5
8.2
6
5-M3
7
37
199
6 190.5
6.5
12
16.5
3.5
24.5
3.5
20
50
25
3-
M3
20 159
Terminal�Pin.�No Assignment
Pin�No. Assignment Pin�No. Assignment
1 AC/L 4,5 DC�OUTPUT -V
2 AC/N 6,7 DC�OUTPUT +V
3 FG
Derating�Curve Static�Characteristics�(24V)
Ta=25
32 350
100
OUTPUT�RIPPLE�(mVp-p)
2 28 300
OUTPUT�VOLTAGE�(V)
80
24 250
1
1 S-150-5~12�CONVECTION
60 2 S-150-15~48�CONVECTION 20 200
S-150-5~12�FORCED AIR
LOAD�(%)
16 150
40
12 100
20
8 50
AMBIENT�TEMPERATURE�( ) INPUT�VOLTAGE�(V)�60Hz
File�Name:S-150-SPEC���2005-09-13
300 Myles Standish Blvd., Taunton, MA 02780
WWW.ASTRODYNE.COM Ph: 1-800-823-8082 Fax: 508-823-8181
PFC500/PDC500 Series Data Sheet
Features
• RoHS lead solder exemption compliant
• Power Factor Correction meets EN61000-3-2 (AC input
versions)
• Fully-regulated outputs
• Remote sense
• Logic level Inhibit
• Current Share, Power Fail, and Power Good Signals
• Overtemperature, overvoltage, and overcurrent protected
• Available with metric or SAE mountings
• Input transient & ESD compliance to
EN61000-4-2/-3/-4/-5
• Fan output voltage and optional fan
• Optional isolation diodes for parallel or redundant
operation
• DC input versions (36-75VDC)
Description
The PFC500/PDC500 products of the PerFormanCe Power Series combine high performance midrange power with
high power density (4.4 watts/in3) and high reliability to meet the requirements of communications, commercial, and
industrial systems.
Providing tightly regulated DC power, the PFC500/PDC500 delivers full output performance with only 300 Linear Feet
per Minute (LFM) forced-air cooling (factory-installed fan optional). Main channel current sharing is provided for
redundant applications, and AC input units can be paralleled with DC input versions. Units are available with SAE
mountings or optional metric mountings.
The PFC500/PDC500 product line is approved to the latest international regulatory standards, and displays the CE
Mark.
Environmental Specifications
PARAMETER CONDITIONS/DESCRIPTION MIN NOM MAX UNITS
Altitude Operating. 10k ASL Ft.
Non-Operating. 40k ASL Ft.
Operating Temperature At 100% load 0 50 °C
Derate linearly above 50°C by 2.5% per °C. At 50% load 0 70 °C
Storage Temperature -55 85 °C
Forced Air Cooling Forced air cooling of 300 LFM (400 LFM for PDC500) is required if the internal
fan is not specified Cooling air velocity is measured at the output exiting window
(2.5” x 5”). Airflow direction is from the input section to the output section.
Temperature Coefficient 0°C to 70°C (after 15 minute warm-up). ±0.02 ±0.05 %/°C
Relative Humidity Non-Condensing. 5 95 %RH
Shock Operating: 10±3mSec, 3 axis, Half Sine. 20 G
Non-operating: 10±3mSec, 3 axis, Half Sine. 40
Vibration Operating: 5-32Hz 0.02 in (DA)
32-2000Hz Sinusoidal 1 GPK
Non-operating: 6.15 GRMS
Options
DESCRIPTION NOTES SIZE IMPACT
Isolation Diodes Add “D” as a suffix to the model number to order factory installed isolation diodes N/A
for parallel or redundant operation. For 24V models with the “D” option, external caps
are required to meet the 1% noise/ripple spec. Power Good has a pull-up
resistor of 475 on the 24V models. See Application Note #P1 for details.
Fan Add “F” as a suffix to the model number to order integral fan. 10.50" x 5.00" x 2.50"
Fan provides the required 300 LFM (400 LFM for PDC500) of forced air cooling, (266.7mm x 127.0mm x 63.5mm)
or otherwise provided by the end user.
Metric Mounting Add “M” as a suffix to the model number to order chassis with
N/A
M4 x 0.7 mounting inserts.
SUGGESTED AIRFLOW *
DC+ or
DC- or
Input and Output Connections: 6-32 Screw Terminal on 0.375" (9.5mm) centers
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical
components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of
the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the
date manufactured. Specifications are subject to change without notice.
Features:
DC Power Supplies
• Cost-effective power source
• Universal input 90-264 Vac
• 2-year warranty
• Compact (4.25” x 2.50” x 1.25”; meets
1U applications)
• Overload and overvoltage protection
• Conducted EMI exceeds FCC Class B and
CISPR 22 Class B (Commercial models) and
CISPR 11 Class B (Medical models)
• Commercial UL/CSA/IEC60950-1, EN60950 approvals
• Medical UL/EN/IEC60601-1, CSA22.2 No. 601,
• RoHS compliant models available (G suffix)
• marked to LVD
SPECIFICATIONS
Ac Input Temperature Coefficient
90-264 Vac, 47-63 Hz single phase.. 0.03%/°C typical on all outputs.
Input Current Output Noise
Maximum input current at 120 Vac, 60 Hz with full rated output load: 1.5 A 0.5% rms, 1% pk-pk, 20 MHz bandwidth, differential mode. Measured with noise
probe directly across output terminals of the power supply.
Hold-Up Time
15 ms minimum from loss of ac input at full load, nominal line (115 Vac). Transient Response
500 μs typical response time for return to within 0.5% of final value for a 50% load
Output Power
step change. ∆i/∆t<0.2 A/μs. Maximum voltage deviation is 3.5%. Startup/shut-
50 W continuous, 60 W peak. Peak ratings are for 60 s maximum duration,
down overshoot less than 3%.
10% duty cycle. During peak load condition, output regulation may exceed
total regulation limits. Voltage Adjustment
Built-in potentiometer adjusts V1 ±5%.
Output Regulation
To maintain specified regulation on multi-output models, output #1 load EMI/EMC Compliance
power must be at least 1/5th of, and not greater than 5 times output #2 load All models include built-in EMI filtering to meet the following emissions require-
power. ments:
Overload Protection EMI SPECIFICATIONS COMPLIANCE LEVEL
Fully protected against short circuit and output overload. Short circuit pro-
tection is cycling type power limit on outputs 1 & 2; foldback type on output Conducted Emissions GLC EN55022 Class B; FCC Class B
3. Recovery after fault is automatic. See output ratings chart for additional Conducted Emissions GLM EN55011 Class B; FCC Class B
notes or conditions. Static Discharge EN61000-4-2, 6 kV contact, 8 kV air
Efficiency RF Field Susceptibility EN61000-4-3, 3 V/meter
70-85% at full rated load, nominal input voltage, depending on model and Fast Transients/Bursts EN61000-4-4, 2 kV, 5 kHz
load distribution. Surge Susceptibility EN61000-4-5, 1 kV diff., 2 kV com.
Minimum Load Commercial Leakage Current
Operating without minimum load will not degrade reliability, but regula- 160 μA 254 Vac @ 60 Hz input (with no deviations).
tion may be affected. Multiple output models require 20% minimum load
on V1 for proper regulation. Single models require 5% minimum load when Commercial Safety
a transient load greater than 30% is applied or removed, but will operate All GLC models are approved to UL1950, CSA22.2 No.
without load. 234 Level 3, IEC950 and EN60950.
All specifications are typical at nominal input, full load at 25OC unless otherwise stated
Commercial Medical Minimum Total
Model Model Output No. Output Current Load (B) OVP Setpoint Noise P-P Regulation (A)
GLC50A GLM50A 1 +5.05 V 4A 0.8 A 6.2 ± 0.6 V 50 mV 2%
2 +12 V 2.5 A 120 mV +10%,-5%
3 -12 V 0.2 A 120 mV 3%
GLC50B GLM50B 1 +5.05 V 4A 0.8 A 6.2 ± 0.6 V 50 mV 2%
2 +15 V 2.5 A 150 mV +10%,-5%
3 -15 V 0.2 A 150 mV 3%
GLC50D GLM50 D 1 +5.05 V 4A 0.8 A 6.2 ± 0.6 V 50 mV 2%
2 +24 V 1.5 A 240 mV +10%,-5%
3 -12 V 0.2 A 120 mV 3%
GLC50G GLM50G 1 +3.3 V 4A 0.8 A 4.2 ± 0.6 V 33 mV 2%
2 +12 V 2.5 A 120 mV +10%-5%
3 -12 V 0.2 A 120 mV 3%
GLC50-3.3 GLM50-3.3 1 3.3 V 8A 0.2 4.2 ± 0.6 V 66 mV 2%
GLC50-5 GLM50-5 1 5.1 V 8A 0.4 6.2 ± 0.6 V 75 mV 2%
GLC50-12 GLM50-12 1 12 V 4.2 A 0.2 14 ± 1.1 V 120 mV 2%
GLC50-15 GLM50-15 1 15 V 3.3 A 0.16 18.5 ± 1.5 V 150 mV 2%
GLC50-24 GLM50-24 1 24 V 2.1 A 0.1 28 ± 2.5 V 240 mV 2%
GLC50-28 GLM50-28 1 28 V 1.8 A 0.09 34.5 ± 2.8 V 280 mV 2%
GLC50-48 GLM50-48 1 48 V 1.1 A 0.05 54 ± 3.0 V 480 mV 2%
Notes:
A. Total regulation is defined as the maximum deviation from the nominal voltage for all steady-state conditions of initial voltage setting, input line voltage and output load.
B. To maintain specified regulation on multi-output models, output #1 load power must be at least 1/5th of, and not greater than 5 times output #2 load power.
C. Add “G” suffix to model number for RoHS compliant model.
GLC50 MECHANICAL SPECIFICATIONS
SL Power Electronics Corp, 6050 King Drive, Bldg. A, Ventura, CA 93003, USA. Phone:(805) 486 4565 Fax:(805) 487 8911 www.slpower.com. Rev. 1/07.
Data Sheet © 2007 SL Power Electronics Corp. The information and specifications contained in this data sheet are believed to be correct at time of publication.
However, Condor accepts no responsibility for consequences arising from reproduction errors or inaccuracies. Specifications are subject to change without notice.
TYPE CMP HIGH VOLTAGE FILTER CAPACITORS
GENERAL DESCRIPTION
SPECIFICATIONS
IMPREGNATION: Type CMP capacitors are impregnated and filled with silicone oil and hermetically sealed.
TERMINAL: All metallized hermetic terminals are used to insure perfect seals. Terminals meet L5
requirements of MIL-I-10 specifications. For voltages > 30kV, a single bushing with a
threaded ground stud is employed to assure safety and stability.
DIELECTRIC: Polyester Resin film and the finest grade Kraft Paper impregnated with silicone oil.
BRACKETS: Footed Mounting Brackets are available and are not included with the capacitor.
MOUNTING POSITION: All type CMP capacitors will operate satisfactorily mounted in any position.
TEST VOLTAGE: For capacitors rated ≤20kV, 200% rated voltage applied terminal-to-terminal for one minute
at room temperature. For rated voltages between 20 kV and 50 kV, 150% rated voltage for
two minutes at room temperature. For terminal to case, rating is same above plus 1 kV. Test
voltage shall be applied and discharged through a resistance of at least 1 Ω/rated volt to
maximum of 5 kΩ.
FLASHOVER: For rated voltages ≤5kV, capacitor terminal will with stand 125 %rated voltage at a pressure
of 12 kPa, (1.7 psia or 0.12 bar), equivalent to 50,000 feet altitude. For rated voltage of ≥6
kV, terminals will with stand 125% rated voltage at a pressure of 68kPa (10 psia), equivalent
to 10,000 feet altitude.
APPLICATION NOTES
SIZE: The case sizes listed below are not necessarily the smallest possible for a given capacitor. If a
custom size and shape are required by your application, CCC will be pleased to work with you to
optimize to your needs. CCC stocks a wide range of can sizes in several styles. If the revised design
employs a stock can, no cost penalty should be incurred. If a custom can is required, cost depends
heavily on quantity.
IMPREGNANT: CMP capacitors are premium products impregnated with silicone dielectric fluid, which is about ten
times more expensive than high grade mineral oil. The use of mineral oil in CMP designs results in
substantial cost reductions, at the expense of operating temperature range and flammability. Should
your design allow the use of mineral oil impregnated, CCC will be pleased to quote on mineral oil
impregnated design.
CONTAINER: At the highest voltages, the large ceramic terminals required become a substantial portion of material
costs. Capacitor cost can be reduced by either specifying only one terminal (with the other grounded
to the case) or one terminal rated for the full voltage with the other rated for a much lower voltage
(for example, when one terminal will be connected to neutral). While CMP capacitors can be
fabricated to any voltage level, above 50kV, CCC’s BAM capacitors tend to be much more cost
effective. These capacitors are fabricated in an insulating tubular container with the terminal at each
end. The case, therefore, becomes the insulation between the terminals. For further detail, see
CCC’s BAM catalog.
WINDING DESIGN: Capacitors can be constructed in a range of winding designs (e.g., extended foil, tab constructions,
etc.) and can be fabricated from a wide range of dielectric materials including polypropylene,
polyester (“Mylar”), polycarbonate, etc. with varying layers and configurations of paper. Each
combination of construction and material has its advantages and disadvantages. Your successful
application of any high technology capacitor depends on matching the capacitor design to your
requirements. Using its computerized design programs, CCC will work with you to determine your
requirements and customize the design gives the greatest current carrying capability and lowest ESR
at the expense of a somewhat higher inductance than can be achieved with tab design. The
inductance and ESR in tab designs depends on the number of tabs. Increasing the number of tabs in
a winding increases the time required in manufacture, and, therefore, the cost to the customer. Mylar
is a good general-purpose dielectric with a relatively high dielectric constant which results in a
smaller capacitor than polypropylene; however, polypropylene has much better high frequency
characteristics. The proper use of fluid-impregnated paper layers is important in capacitors which
see frequent and wide swings in voltage (ac, pulse discharge, etc.), as it provides a medium with
greater tolerance to electron injection in highly stressed regions of the capacitor.
Chicago Condenser Corporation Manufactures a wide variety of impregnated plastic film and paper dielectric
capacitors in many styles, including metal cans, non-conducting cases, “wrap-and-fill” with axial leads, and capacitor bypass
feedthroughs. Some MIL Spec product lines (e.g., CP53 “bathtubs” and CQ72) are available. During our sixty years in
business, we count many of the world’s largest corporations among our customers in the fields of lasers, military electronics,
scientific apparatus, etc. While CCC has standard product line, such as that represented in this catalog, it manufactures
essentially all products to order, typically with eight to ten weeks delivery. As a result of this semi-custom manufacture,
product characteristics can be customized through alterations in winding type, winding materials, etc. to optimize the product
for the user’s application. For this reason, CCC maintains expert engineering staff ready to help customers determine their
needs. The brief applications information on the next page introduces some of the relevant criteria.
Many of the products in this catalog can store lethal voltages and energies. Utmost care should be exercised in the use of
these products to assure that voltage or power source is disconnected and that the capacitor is discharged, grounded, and
shorted before servicing equipment into which a capacitor has been installed. Installation should comply with all federal,
state, and local electrical code requirements.
• FEATURES
Post Glover Smoothwound resistors are available in through-bolt or flat bar
mounting arrangements. This makes Post Glover Smoothwound Resistors directly
interchangeable with most major brands. Individual coils can be manufactured
with either fixed or adjustable taps.
• APPLICATION
Our Smoothwound Resistor is the best you can buy for applications where high
resistance and low currents are the main criteria. This resistor is especially well
suited for use in;
• Dynamic braking with low duty cycle or small motors,
• Low voltage neutral grounding,
• Elevator controls.
SIZE = 2 through 6
L ID
OD
* These are typical ratings only. Other ratings are possible for special case, including using a 1.5” diameter core.
Please contact the factory for additional assistance.
FEATURES
• CSA Performance Certifled at 16A.
GENERAL
The T498A,B Electric Heat Thermostats provide line voltage
control of electric heating equipment. A snap action switch
makes heating circuit on temperature fall.
Contents
General ............................................................................... 1
Features .............................................................................. 1
Specifications ...................................................................... 2
Ordering Information ........................................................... 2
Installation ........................................................................... 3
Setting and Checkout .......................................................... 4
Security Features ................................................................ 4
Calibration ........................................................................... 5
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number, or specify:
1. Order Number. 3. Accessories, if desired.
2. Switching. 4. Order additional system components and system accessories
separately.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Logistics
Honeywell Inc., 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 (612) 951-1000
In Canada—Honeywell Limited/Honeywell Limitée, 155 Gordon Baker Road, North York, Ontario M2H 2C9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
95C-10686—3 2
T498A,B ELECTRIC HEAT THERMOSTATS
OFF 3-9/32
(83)
12 o’clock position. This will prevent accidental damage
to the dial stop during mounting.
4-17/32
2-3/32
(53) 5 Using a screwdriver, secure the thermostat to the outlet
(116) box by tightening the two mounting screws. Handle the
thermostat with care; excessive pressure can damage
the control knob or sensing element.
1/2 (13)
CAUTION
15/16
2-29/32 (72)
(24)
1. Disconnect power supply before making wiring
M6089A
connections to prevent electrical shock or
Fig. 1. Nominal dimensions in in. (mm). equipment damage.
2. All wiring must comply with applicable codes and
RECYCLING NOTICE 3
ordinances.
Thermostats are designed to be used with a
If this control is replacing a control that contains separate limit control in the appliance.
mercury in a sealed tube, do not place your old
control in the trash. 6 Using wire connectors approved for No. 12 wires, make
line voltage wiring connections directly to the leadwires
Contact your local waste management authority for installed on the thermostat.
instructions regarding recycling and the proper
disposal of any control containing mercury in a
sealed tube. CAUTION
If connecting with aluminum conductors, use
If you have any questions, call Honeywell Inc. at approved CO/ALR solderless wire connectors to avoid
1-800-468-1502. fire hazard.
INSTALLATION L2
T498A 2
WARNING 1 3
Location ELECTRIC
HEATER
Install a vertical outlet box that is used to mount the T498, four
to five feet (1.5m) above the floor on an inside wall where the 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
thermostat will be subjected to average room temperature. PROTECTION AS REQUIRED.
Check the old insulation for cracks, nicks, or fraying and apply
approved electrical tape where necessary to achieve adequate
insulation, or replace the wires using approved methods.
3 95C-10686—3
T498A,B ELECTRIC HEAT THERMOSTATS
L2 2
T498B
1 3 6
L1 L1 L2
(HOT) RED WIRE
5
T1 T2
50 60
4
70
40
ELECTRIC
HEATER OFF
80
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
RANGE STOP
SECURITY FEATURES HOLES
Locking Cover
1 Remove cover by swinging up from the bottom edge of
the thermostat.
2 Insert the Tinnerman Speed Nut® (included) into the
slot on the lower back of thermostat base. See Fig. 4.
3 Insert the Allen screw into the Speed Nut until the
screw head is flush with the lower edge of the
thermostat base.
4 Replace the thermostat cover and lock by removing the M7238
Allen screw until screw body protrudes through the
cover hole.
5 To unlock the cover, insert the Allen screw into the
thermostat base until the screw body clears the cover. Fig. 5. Range stop installation.
95C-10686—3 4
T498A,B ELECTRIC HEAT THERMOSTATS
CALIBRATION
The T498 Thermostats are calibrated at the factory using
precise instruments under closely controlled conditions.
Recalibration should not be necessary. Allow the thermostat
to operate for several hours before checking calibration. 50 60
Temperature deviations of 2°F (1°C) are normal. If the
70
40
thermostat is mounted in a suitable location and still appears
out of calibration, check calibration using the procedures that OFF
follow.
80
Check Calibration
1 Remove the thermostat cover and set it aside for
°F
several minutes. Radiant heat from your hands will
affect the thermometer reading.
50
2 Turn the setting dial clockwise until the switch makes 60
70
(clicking sound) and the heating equipment and fan 80
90
start.
3 No recalibration is necessary if the thermostat switch
makes with the thermostat setting at the same
temperature as indicated on the thermostat cover
thermometer.
4 If the thermostat setting differs from the thermometer, APPLY NEW INSERT DECAL
record the temperature difference and recalibrate as M7237
instructed in the Recalibration Procedure section.
5 95C-10686—3
This page left intentionally blank.