You are on page 1of 28

TECHNICAL BULLETIN

ISSUED BY C V BALAKRISHNAN, DIVISIONAL H.Q., CHENNAI


ISSUE NO. 003/AS03 DATE: 3-02-2003 CIRCULATION TO: ACPD, SPD, PAD, PAD DEALERS, CASD

AIR HANDLING UNITS


• Guide specifications
• Technical data
• Dimensional details

SUPERSEDES ISSUE No. 001/AS01.


Please REPLACE with this issue.

Air Handling Units


Revision A Double Skin AHU Horizontal Floor Mounted
Revision A Double Skin AHU Vertical Floor Mounted
Revision A Double Skin AHU Ceiling Suspended
Revision A Single Skin AHU Horizontal Floor mounted

This bulletin contains updated and final guide


specifications and technical data for the Revision A series
of AHUs (Standard catalogued products - Fan, Coil and
Pre Filter only).

The guide specifications and technical data enclosed


herewith are for the following products:

 Revision A Double Skin Horizontal, Floor Mounted,


draw through unit

 Revision A Double Skin Vertical, Floor Mounted,


draw through unit

 Revision A Double Skin, Ceiling Suspended, draw


through unit (Direct Driven)

 Revision A Double Skin, Ceiling Suspended, draw


through unit (Belt Driven)

 Revision A Single Skin, Horizontal Floor Mounted,


draw through unit.
Double Skin, Horizontal Floor Mounted Draw Through Unit
Guide Specifications
Casing
Rigid framework, comprising of externally chamfered extruded aluminum anodised profiles, with
fibre glass corner joints.

• Double skin sandwiched panels :


Inner Skin : 24 g plain galvanized sheet confirming to IS 277.
Outer Skin : 24 g pre-painted galvanised sheet.

• Panels are 25-mm thick, pressure injected with polyurethane foam, using CFC-free R-141b
blowing agent. High and uniform PUF density of 40 Kg/m3 provide better thermal insulation “K”
factor (not exceeding 0.02 Watt / MC) and sound attenuation properties.

• Fan and motor are mounted on aluminium extruded slide rail base frame. It is isolated from main
casing by using vibration isolators. To arrest vibration, fan outlet is connected to the AHU casing
using fire and moisture resistant canvas.

• Hinged service door in fan section provides easy access to fan and motor. View port is provided
on fan door panel to help to monitor fan and motor status. Marine lamp provides easy visibility.
Door limit switch automatically trips the fan when the door is opened.

• Wider drain pan with differential slope assures quick and complete water drainage ensuring
high Indoor Air Quality (IAQ). Drain Pan is 100 mm deep and fabricated from 0.8 mm thick,
corrosion resistant SS-304 stainless steel. The drain pan is insulated for thermal protection with
10 mm thick closed cell elastomeric insulation to avoid surface condensation. AHUs with stack
coils have intermediate stainless steel drain pan to collect the condensate of top coil.

• AHU is supplied with factory fitted GI, powder coated, opposed blade volume control damper to
facilitate field balancing.

• Aluminium die cast powder coated hinges provide adequate strength to the door. Nylon handles
can be operated from both inside and outside the casing and are user friendly.

Cooling Coils
Free flow fin configuration formed by mild ripples and die formed channels provide excellent heat
transfer capability with low air side pressure drop. Mechanical expansion of copper tube with
aluminium fins assures tight bonding providing optimum heat transfer. Coils are complete with
copper headers. Coils are self draining and vented type. Design working pressure is 250 psig
at 300 °F.

2
Double Skin, Horizontal Floor Mounted Draw Through Unit

Fans
Fans are imported, AMCA certified, energy efficient, with double inlet, double width, forward curved
impeller. All wheels are statically and dynamically balanced. The scroll and impeller are made of
galvanised steel sheet. The fan is V - belt driven through a 3 phase, 415V±6%, 50 Hz AC, squirrel
cage, TEFC induction, 4 Pole, IP55, Class ‘F’ motor.

Pre-Filters
Pre-filters are pleated to provide more filtration area. The filter media are of the synthetic non-
woven type, supported with aluminium and HDPE mesh and generally conforming to EU-3 of EN-
779 specifications. The filter efficiency is 90% down to 10 micron. Filters are provided with handles
for easy removal and are washable.

Base Channel
Entire unit is completely supported by a full-perimeter base rail channel. The base rail is constructed
of 2.0 mm thick galvanized sheet steel and has intermediate cross member for unit support.

Factory Test
Each coil is factory tested and checked for leaks at 325 Psig (pneumatic) under water. Each
assembled AHU is run tested at works before despatch.

Performance Standards
Generally in
accordance to
• Fans - AMCA 210
• Coils - ARI 410
• Motors - IS-325
• Filter - BS-6540 / ASHRAE 52 - 76

Nomenclature
e.g. DHW4 – 035

e.g. D H W 4 - 035

Double skin

Horizontal Floor
Mounted
Chilled Water Coils (X-Direct Expansion Coils)

4 RD Cooling Coils (6 - 6 RD Cooling Coils)

3,500 CMH

3
4
Technical Data

AHU Overall Dimension Standard Coil Size Fan and Motor Details 40 mm 50 mm Pre Filter
(Fan, Coil, Pre Filter) TSP TSP (50 mm thick)

AHU Model Length Width Height FL FH Coil Coil Air Quantity at Fan Model Fan Opening Outlet Motor Motor
Area In/Out 500 FPM CFV Velocity Power Power Area Face Size Qty.
size Velocity
mm mm mm mm mm Sq. Mt inch CFM CMH Kruger W-mm * H-mm m/s KW KW Sq. Mt M/S W-mm * H-mm Nos.

DHW4 - 035 1671 997 757 660 572 0.377 1 2031 3453 FDA 250 - SM 322 * 322 9.25 1.1 1.5 0.400 2.40 400 * 500 2
DHW4 - 040 1810 1099 896 762 572 0.435 1 2344 3984 FDA 280 - SM 360 * 360 8.54 1.1 1.5 0.540 2.05 500 * 600 1
400 * 600 1
DHW4 - 050 1810 1099 896 762 699 0.532 1 1/4 2865 4870 FDA 280 - SM 360 * 360 10.44 1.5 2.2 0.540 2.51 500 * 600 1
400 * 600 1
DHW4 - 060 1949 1251 1174 914 762 0.697 1 1/2 3750 6375 FDA 355 - SM 452 * 452 8.67 2.2 2.2 0.900 1.97 500 * 500 2
500 * 400 2
DHW4 - 080 1949 1251 1174 914 953 0.871 1 1/2 4688 7969 FDA 355 - SM 452 * 452 10.83 2.2 3.7 0.900 2.46 500 * 500 2
500 * 400 2
DHW4 - 100 1810 1810 1174 1422 762 1.084 1 1/2 5833 9917 FDA 450 - CM 568 * 568 8.54 2.2 3.7 1.440 1.91 600 * 500 1
Double Skin, Horizontal Floor Mounted Draw Through Unit

600 * 400 1
500 * 500 2
500 * 400 2
DHW4 - 120 1810 1810 1174 1422 953 1.355 2 7292 12396 FDA 450 - CM 568 * 568 10.67 3.7 3.7 1.440 2.39 600 * 500 1
600 * 400 1
500 * 500 2
500 * 400 2
DHW4 - 140 1949 1949 1313 1575 953 1.500 2 8073 13724 FDA 500 - CM 638 * 638 9.37 3.7 5.5 1.700 2.24 600 * 500 4
500 * 500 2
DHW4 - 160 1949 1949 1313 1575 1080 1.700 2 9149 15554 FDA 500 - CM 638 * 638 10.61 3.7 5.5 1.700 2.54 600 * 500 4
500 * 500 2
DHW4 - 180 2227 2088 1473 1727 1143 1.974 2 10625 18063 FDA 560 - CM 714 * 714 9.84 5.5 5.5 2.160 2.32 600 * 600 6
DHW4 - 200 2227 2088 1473 1727 1270 2.194 2 11806 20069 FDA 560 - CM 714 * 714 10.94 5.5 5.5 2.160 2.58 600 * 600 6
DHW4 - 220 2227 2366 1600 1981 1207 2.390 2 1/2 12865 21870 FDA 630 - CM 800 * 800 9.49 5.5 7.5 2.730 2.23 600 * 500 1
600 * 400 2
500 * 500 3
500 * 400 6
DHW4 - 230 2227 2366 1600 1981 1270 2.516 2 1/2 13542 23021 FDA 630 - CM 800 * 800 9.99 5.5 7.5 2.730 2.34 600 * 500 1
600 * 400 2
500 * 500 3
500 * 400 6
Technical Data

AHU Overall Dimension Standard Coil Size Fan and Motor Details 40 mm 50 mm Pre Filter
(Fan, Coil, Pre Filter) TSP TSP (50 mm thick)

AHU Model Length Width Height FL FH Coil Coil Air Quantity at Fan Model Fan Opening Outlet Motor Motor
Area In/Out 500 FPM CFV Velocity Power Power Area Face Size Qty.
size Velocity
mm mm mm mm mm Sq. Mt inch CFM CMH Kruger W-mm * H-mm m/s KW KW Sq. Mt M/S W-mm * H-mm Nos.

DHW4 - 250 2227 2366 1600 1981 1397 2.768 2 1/2 14896 25323 FDA 630 - CM 800 * 800 10.99 7.5 7.5 2.730 2.58 600 * 500 1
600 * 400 2
500 * 500 3
500 * 400 6
DHW4 - 270 2366 2546 1727 2184 1334 2.913 2 1/2 15677 26651 FDA 710 - CM 898 * 898 9.18 7.5 7.5 3.360 2.20 600 * 500 8
600 * 400 4
DHW4 - 290 2366 2546 1727 2184 1461 3.190 2 1/2 17170 29189 FDA 710 - CM 898 * 898 10.05 7.5 9.3 3.360 2.41 600 * 500 8
600 * 400 4
DHW4 - 300 2366 2546 1727 2184 1524 3.329 2 1/2 17917 30458 FDA 710 - CM 898 * 898 10.49 7.5 9.3 3.360 2.52 600 * 500 8
600 * 400 4

DHW4 - 320 2546 2685 2096 2337 1524 3.561 2 1/2 19167 32583 FDA 800 - TM 1006 * 1006 8.94 7.5 9.3 4.500 2.01 500 * 600 15

DHW4 - 350 2546 2685 2096 2337 1651 3.858 2 20764 35299 FDA 800 - TM 1006 * 1006 9.69 9.3 11.0 4.500 2.18 500 * 600 15

DHW4 - 370 2546 2685 2096 2337 1715 4.006 2 21563 36656 FDA 800 - TM 1006 * 1006 10.06 9.3 11.0 4.500 2.26 500 * 600 15

DHW4 - 400 2546 2685 2096 2337 1842 4.303 2 23160 39372 FDA 800 - TM 1006 * 1006 10.81 9.3 11.0 4.500 2.43 500 * 600 15

DHW4 - 420 2824 2963 2350 2591 1778 4.606 2 1/2 24792 42146 FDA 900 - TM 1130 * 1130 9.17 11.0 15.0 5.400 2.17 600 * 600 4
500 * 600 6
600 * 400 4
500 * 400 6

DHW4 - 450 2824 2963 2350 2591 1905 4.935 2 1/2 26563 45156 FDA 900 - TM 1130 * 1130 9.82 11.0 15.0 5.400 2.32 600 * 600 4
500 * 600 6
600 * 400 4
500 * 400 6

DHW4 - 470 2824 2963 2350 2591 1969 5.100 2 1/2 27448 46661 FDA 900 - TM 1130 * 1130 10.15 11.0 15.0 5.400 2.40 600 * 600 4
500 * 600 6
600 * 400 4
500 * 400 6

5
Double Skin, Horizontal Floor Mounted Draw Through Unit
6
Technical Data

AHU Overall Dimension Standard Coil Size Fan and Motor Details 40 mm 50 mm Pre Filter
(Fan, Coil, Pre Filter) TSP TSP (50 mm thick)

AHU Model Length Width Height FL FH Coil Coil Air Quantity at Fan Model Fan Opening Outlet Motor Motor
Area In/Out 500 FPM CFV Velocity Power Power Area Face Size Qty.
size Velocity
mm mm mm mm mm Sq. Mt inch CFM CMH Kruger W-mm * H-mm m/s KW KW Sq. Mt M/S W-mm * H-mm Nos.

DHW4 - 500 2824 2963 2350 2591 2096 5.429 2 1/2 29219 49672 FDA 900 - TM 1130 * 1130 10.81 15.0 15.0 5.400 2.56 600 * 600 4
500 * 600 6
600 * 400 4
500 * 400 6

DHW4 - 520 2963 3241 2540 2896 1969 5.700 2 1/2 30677 52151 FDA 1000 - TM 1266 * 1266 9.04 15.0 15.0 6.600 2.19 600 * 600 10
600 * 500 10

DHW4 - 540 2963 3241 2540 2896 2032 5.884 2 1/2 31667 53833 FDA 1000 - TM 1266 * 1266 9.33 15.0 15.0 6.600 2.27 600 * 600 10
600 * 500 10
Double Skin, Horizontal Floor Mounted Draw Through Unit

DHW4 - 570 2963 3241 2540 2896 2159 6.252 2 1/2 33646 57198 FDA 1000 - TM 1266 * 1266 9.91 15.0 18.5 6.600 2.41 600 * 600 10
600 * 500 10

DHW4 - 600 2963 3241 2540 2896 2286 6.619 2 1/2 35625 60563 FDA 1000 - TM 1266 * 1266 10.50 15.0 18.5 6.600 2.55 600 * 600 10
600 * 500 10

Note :

# Panel Thickness : 25 mm

# Drain Nozzle Connection: 1 1/4 inch BSP.

# Standard Options:
a) Coil, Fins / inch = 12
b) Row deep = 2,4,6
c) Water circuit = B, C, D
d) Fan Discharge: Top Horizontal, Bottom Horizontal, Upblast.
e) For DX Coils: No. of circuits and tubes per circuit need to be informed.

Dimensions and specifications are subject to change without prior notice.


Double Skin, Vertical Floor Mounted Draw Through Unit
Guide Specifications
Casing
Rigid framework, comprising of externally chamfered extruded aluminum anodised profiles, with
fibre glass corner joints.

• Double skin sandwiched panels :


Inner Skin : 24 g plain galvanized sheet confirming to IS 277.
Outer Skin : 24 g pre-painted galvanised sheet.

• Panels are 25-mm thick, pressure injected with polyurethane foam, using CFC-free R-141b
blowing agent. High and uniform PUF density of 40 Kg/m3 provide better thermal insulation “K”
factor (not exceeding 0.02 Watt / MC) and sound attenuation properties.

• Fan and motor are mounted on aluminium extruded slide rail base frame. It is isolated from main
casing by using vibration isolators. To arrest vibration, fan outlet is connected to the AHU casing
using fire and moisture resistant canvas (for larger units more than 6000 cfm).

• Service door in front of fan section with quarter turn latches provides easy access to fan and
motor.

• Wider drain pan with “V Shaped” design assures quick and complete water drainage ensuring
high Indoor Air Quality (IAQ). Drain Pan is 100 mm deep and fabricated from 0.8 mm thick,
corrosion resistant SS-304 stainless steel. The drain pan is mounted on 25-mm thick PUF
insulated bottom panel and is insulated for thermal protection with 6-mm thick closed cell
elastomeric insulation to avoid surface condensation.

Cooling Coils
Free flow fin configuration formed by mild ripples and die formed channels provide excellent heat
transfer capability with low air side pressure drop. Mechanical expansion of copper tube with
aluminium fins assures tight bonding providing optimum heat transfer. Coils are complete with
copper headers. Coils are self draining and vented type. Design working pressure is 250 psig at
300oF.

Fans
Fans are imported, AMCA certified, energy efficient, with double inlet, double width, forward curved
impeller. All wheels are statically and dynamically balanced. The scroll and impeller are made of
galvanised steel sheet. The fan is V - belt driven through a 3 phase, 415V±6%, 50 Hz AC, squirrel
cage, TEFC induction, 4 Pole, IP55, Class ‘F’ motor.

7
Double Skin, Vertical Floor Mounted Draw Through Unit

Pre-Filters
Pre-filters are pleated to provide more filtration area. The filter media are of the synthetic non-
woven type, supported with aluminium and HDPE mesh and generally conforming to EU-3 of EN-
779 specifications. The filter efficiency is 90 % down to 10 micron. Filters are provided with handles
for easy removal and are washable.

Base Channel
Entire unit is completely supported by a full-perimeter base rail channel. The base rail is constructed
of 2.0-mm thick galvanized sheet.

Factory Test
Each coil is factory tested and checked for leaks at 325 Psig (pneumatic) under water. Each
assembled AHU is run tested at works before despatch.

Performance Standards
Generally in
accordance to
• Fans - AMCA 210
• Coils - ARI 410
• Motors - IS-325
• Filter - BS-6540 / ASHRAE 52 - 76

Nomenclature
e.g. DVW4 – 035

e.g. D V W 4 - 035

Double skin

Vertical Floor Mounted

Chilled Water Coils (X-Direct Expansion Coils)

4 RD Cooling Coils (6-6 RD Cooling Coils)

3,500 CMH

8
Technical Data

AHU Overall Dimension Standard Coil Size Fan and Motor Details 12 mm 20 mm Pre Filter
(Fan, Coil, Pre Filter) ESP ESP (50 mm thick)

AHU Model Length Width Height FL FH Coil Coil Air Quantity at Fan Model Fan Opening Outlet Motor Motor
Area In/Out 500 FPM CFV Velocity Power Power Area Face Size Qty.
size Velocity
mm mm mm mm mm Sq. Mt inch CFM CMH Kruger W-mm * H-mm m/s KW KW Sq. Mt M/S W-mm * H-mm Nos.

DVW4 - 035 785 1040 1321 762 508 0.387 1 2083 3542 KAT 10-10 SL 331 * 289 10.28 0.75 1.1 0.400 2.46 400 * 500 2
1
DVW4 - 050 835 1396 1387 1118 508 0.568 1 /4 3056 5194 KAT 12-12 SL 395 * 341 10.71 1.1 1.5 0.600 2.40 600 * 500 2

DVW4 - 070 885 1599 1532 1321 572 0.755 11/4 4063 6906 KAT 15-15 SL 471 * 404 10.08 1.5 2.2 0.840 2.28 500 * 600 2
400 * 600 1

DVW4 - 100 1035 1776 1861 1473 762 1.123 11/2 6042 10271 KAT 18-18 SL 557 * 478 10.72 2.2 3.7 1.200 2.38 500 * 400 6

DVW4 - 140 885 2233 1904 1930 762 1.471 2 7917 13458 KAT 15-15 S2L 471 * 404 9.82 3.7 3.7 1.600 2.34 500 * 400 8

DVW4 - 170 1035 2741 2021 2438 762 1.858 2 10000 17000 KAT 18-13 S2L 430 * 478 11.49 3.7 5.5 1.920 2.46 600 * 400 8

DVW4 - 200 1035 2945 2059 2642 826 2.181 2 11736 19951 KAT 18-18 S2L 557 * 478 10.41 5.5 5.5 2.160 2.57 600 * 400 4
500 * 400 6

DVW4 - 250 1085 2945 2288 2642 1016 2.684 21/2 14444 24556 FDA 450-C2M 568 * 568 10.57 5.5 7.5 2.700 2.53 600 * 500 4
500 * 500 6

Note :
# Panel Thickness : 25 mm
# S2: Twin Blower System.
# Drain nozzle connection: 1 1/4 inch BSP
# Standard Options:
a) Coil, Fins/inch: 12
b) Row deep: 4&6
c) Fan discharge: Upblast only

Dimensions and specifications are subject to change without prior notice.

9
Double Skin, Vertical Floor Mounted Draw Through Unit
Double Skin, Ceiling Suspended Draw Through Unit
(Direct Driven)
Guide Specifications
Casing
Rigid framework, comprising of externally chamfered extruded aluminum anodised profiles, with
fibre glass corner joints.

• Double skin sandwiched panels :


Inner Skin : 24 g plain galvanized sheet confirming to IS 277.
Outer Skin : 24 g pre-painted galvanised sheet.

• Panels are 25-mm thick, pressure injected with polyurethane foam, using CFC-free R-141b
blowing agent. High and uniform PUF density of 40 Kg/m3 provide better thermal insulation “K”
factor (not exceeding 0.02 Watt / MC ) and sound attenuation properties.

• Fan are mounted on aluminium extruded slide rail base frame.

• Service door at bottom of fan section with quarter turn latches provides easy access to fan and
motor.

• Wider drain pan with “V Shaped” design assures quick and complete water drainage ensuring
high Indoor Air Quality ( IAQ ). Drain Pan is 70 mm deep and fabricated from 0.8 mm thick,
corrosion resistant SS-304 stainless steel. The drain pan is mounted on 25-mm thick PUF
insulated bottom panel and is insulated for thermal protection with 6-mm thick closed cell
elastomeric insulation to avoid surface condensation.

Cooling Coils
Free flow fin configuration formed by mild ripples and die formed channels provide excellent heat
transfer capability with low air side pressure drop. Mechanical expansion of copper tube with
aluminium fins assures tight bonding providing optimum heat transfer. Coils are complete with
copper headers. Coils are self draining and vented type. Design working pressure is 250 psig at
300oF.

Fans
Fans are imported, AMCA certified, energy efficient, with double inlet, double width, forward curved
impeller. All wheels are statically and dynamically balanced. The scroll and impeller are made of
galvanised steel sheet. The fans are direct driven through an imported single phase, 220 V, 50 Hz
AC, 3 speed squirrel cage, induction, IP21, Class ‘F’ motor.

10
Double Skin, Ceiling Suspended Draw Through Unit (Direct Driven)

Pre-Filters
Pre-filters are pleated to provide more filtration area. The filter media are of the synthetic
non-woven type, supported with aluminium and HDPE mesh and generally conforming to EU-3 of
EN-779 specifications. The filter efficiency is 90 % down to 10 micron. Filters are provided with
handles for easy removal and are washable.

Factory Test
Each coil is factory tested and checked for leaks at 325 Psig (pneumatic) under water. Each
assembled AHU is run tested at works before despatch.

Performance Standards
Generally in
accordance to
• Fans - AMCA 210
• Coils - ARI 410
• Filter - BS-6540 / ASHRAE 52 - 76

Nomenclature
e.g. DCW4 – 035 - D

e.g. D C W 4 - 035 - D

Double skin

Ceiling Suspended

Chilled Water Coils (X-Direct Expansion Coils)

4 RD Cooling Coils (6-6 RD Cooling Coils)

3,500 CMH

Direct Driven

11
12
Technical Data

AHU Overall Dimension Standard Coil Size Fan and Motor Details Pre Filter
(Fan, Coil, Pre Filter) (50 mm thick)

AHU Model Length Width Height FL FH Coil Coil Air Quantity at Fan Model Qty. Fan Opening Outlet Motor
Area In/Out 500 FPM CFV Velocity Power Area Face Size Qty.
size Velocity
mm mm mm mm mm Sq. Mt inch CFM CMH Kruger Nos. W-mm * H-mm m/s KW Sq. Mt M/S W-mm * H-mm Nos.

DCW4-035-D 986 1237 565 965 381 0.368 1 1979 3365 KDD10-10 SL 1 331 * 289 9.77 0.55 0.400 2.34 500 * 400 2

DCW4-050-D 986 1745 565 1473 381 0.561 11/4 3021 5135 KDD10-08 SL 2 265 * 289 9.31 0.55 0.600 2.38 500 * 400 3

DCW4-070-D 986 2202 565 1930 381 0.735 11/2 3958 6729 KDD 10-10 SL 2 331 * 289 9.77 0.55 0.800 2.34 500 * 400 4

Note :
# Motor KW is based on 12 MM ESP
# Motor : Single Phase Direct Mounted on Blower
# Motor speed: 1150, 1250, 1350 RPM.
# Rated air flow is at highest speed.
Double Skin, Ceiling Suspended Draw Through Unit (Direct Driven)

# Panel Thickness : 25 mm
# Drain Nozzle Connection : 1 inch BSP
# Standard Option
a) Coil Fins/ inch : 12
b) Row deep : 4 or 6
c) Fan discharge : Bottom Horizontal only

Dimensions and specifications are subject to change without prior notice.


Double Skin, Ceiling Suspended Draw Through Unit
(Belt Driven)
Guide Specifications
Casing
Rigid framework, comprising of externally chamfered extruded aluminum anodised profiles, with
fibre glass corner joints.

• Double skin sandwiched panels :


Inner Skin : 24 g plain galvanized sheet confirming to IS 277.
Outer Skin : 24 g pre-painted galvanised sheet.

• Panels are 25-mm thick, pressure injected with polyurethane foam, using CFC-free R-141b
blowing agent. High and uniform PUF density of 40 Kg/m3 provide better thermal insulation “K”
factor (not exceeding 0.02 Watt / MC ) and sound attenuation properties.

• Fan and motor are mounted on aluminium extruded slide rail base frame.

• Service door at bottom of fan section with quarter turn latches provides easy access to fan and
motor.

• Wider drain pan with “V Shaped” design assures quick and complete water drainage ensuring
high Indoor Air Quality ( IAQ ). Drain Pan is 70 mm deep and fabricated from 0.8 mm thick,
corrosion resistant SS-304 stainless steel. The drain pan is mounted on 25-mm thick PUF
insulated bottom panel and is insulated for thermal protection with 6-mm thick closed cell
elastomeric insulation to avoid surface condensation.

Cooling Coils
Free flow fin configuration formed by mild ripples and die formed channels provide excellent heat
transfer capability with low air side pressure drop. Mechanical expansion of copper tube with
aluminium fins assures tight bonding providing optimum heat transfer. Coils are complete with
copper headers. Coils are self draining and vented type. Design working pressure is 250 psig at
300oF.

Fans
Fans are imported, AMCA certified, energy efficient, with double inlet, double width, forward curved
impeller. All wheels are statically and dynamically balanced. The scroll and impeller are made of
galvanised steel sheet. The fan is V - belt driven through a 3 phase, 415V±6%, 50 Hz AC, squirrel
cage, TEFC induction, 4 pole, IP55, Class ‘F’ motor.

13
Double Skin, Ceiling Suspended Draw Through Unit (Belt Driven)

Pre-Filters
Pre-filters are pleated to provide more filtration area. The filter media are of the synthetic non-
woven type, supported with aluminium and HDPE mesh and generally conforming to EU-3 of EN-
779 specifications. The filter efficiency is 90% down to 10 micron. Filters are provided with handles
for easy removal and are washable.

Factory Test
Each coil is factory tested and checked for leaks at 325 Psig (pneumatic) under water. Each
assembled AHU is run tested at works before despatch.

Performance Standards
Generally in
accordance to

• Fans - AMCA 210


• Coils - ARI 410
• Motors - IS-325
• Filter - BS-6540 / ASHRAE 52 - 76

Nomenclature
e.g. DCW4 – 035 - B

e.g. D C W 4 - 035 - B

Double skin

Ceiling Suspended

Chilled Water Coils (X-Direct Expansion Coils)

4 RD Cooling Coils (6-6 RD Cooling Coils)

3,500 CMH

Belt Driven

14
Technical Data

AHU Overall Dimension Standard Coil Size Fan and Motor Details 12 mm 20 mm Pre Filter
(Fan, Coil, Pre Filter) ESP ESP (50 mm thick)

AHU Model Length Width Height FL FH Coil Coil Air Quantity at Fan Model Qty. Fan Opening Outlet Motor Motor
Area In/Out 500 FPM CFV Velocity Power Power Area Face Size Qty.
size Velocity
mm mm mm mm mm Sq. Mt inch CFM CMH Kruger Nos. W-mm*H-mm m/s KW KW Sq. Mt M/S W-mm * H-mm Nos.

DCW4-035-B 1284 1237 565 965 381 0.368 1 1979 3365 KAT 10-10 SL 1 331 * 289 9.77 0.75 1.1 0.400 2.34 500 * 400 2
DCW4-050-B 1284 1745 565 1473 381 0.561 1 3021 5135 KAT 10-8 S2L 2 265 * 289 9.31 1.1 1.5 0.600 2.38 500 * 400 3
DCW4-070-B 1284 2202 565 1930 381 0.735 11/2 3958 6729 KAT10-10 S2L 2 331 * 289 9.77 1.5 2.2 0.800 2.34 500 * 400 4
DCW4-100-B 1460 2024 819 1727 635 1.097 11/2 5903 10035 KAT 12-12 S2L 2 395 * 341 10.35 2.2 3.7 1.080 2.58 500 * 600 2
400 * 600 2

Note :

# Panel Thickness : 25 mm
# S 2 : Twin Blower System

# Drain Nozzle Connection : 1 inch BSP

# Standard option

a) Coil Fins/inch : 12

b) Row deep : 4 or 6

c) Fan discharge : Bottom horizontal only.

# Units with twin fans also use single motor.

Dimensions and specifications are subject to change without prior notice.

15
Double Skin, Ceiling Suspended Draw Through Unit (Belt Driven)
Single Skin, Horizontal Floor Mounted Draw Through Unit
Guide Specifications
Casing
Rigid framework, comprising of aluminum anodised / galvanized sheet steel profiles, with fibre
glass corner joints.

• Single skin panels :


SKIN : 18 g plain galvanized sheet confirming to IS 277.

• Fan and motor are mounted on aluminium extruded slide rail base frame. It is isolated from
main casing by using vibration isolators. To arrest vibration, fan outlet is connected to the AHU
casing using fire and moisture resistant canvas.

• Hinged service door in fan section provides easy access to fan and motor.

• The insulation of the fan section is to be carried out at site with 25mm thick fibre glass rigid
board stuck to the panels by using stick pins and covered with fibre glass cloth.

• Wider drain pan with differential slope assures quick and complete water drainage ensuring
high Indoor Air Quality ( IAQ ). Drain Pan is 100 mm deep and fabricated from 0.8 mm thick,
plain galvanized sheet steel. The drain pan is insulated for thermal protection with 10 mm thick
closed cell elastomeric insulation and to avoid surface condensation. AHUs with stack coils
have intermediate galvanized sheet steel drain pan to collect the condensate of top coil.

Cooling Coils
Free flow fin configuration formed by mild ripples and die formed channels provide excellent heat
transfer capability with low air side pressure drop. Mechanical expansion of copper tube with
aluminium fins assures tight bonding providing optimum heat transfer. Coils are complete with
copper headers. Coils are self draining and vented type. Design working pressure is 250 psig at
300 °F.

Fans
Fans are energy efficient, with double inlet , double width , forward curved impeller. All wheels are
statically and dynamically balanced. The scroll and impeller are made of galvanised steel sheet.
The fan is V - belt driven through a 3 phase, 415v ± 6%, 50 Hz AC, squirrel cage, TEFC induction,
4 pole, IP55, Class ‘F’ 4 Pole motor.

Pre-Filters
Pre-filters are pleated to provide more filtration area. The filter media are of the synthetic non-
woven type, supported with aluminium and HDPE mesh and generally conforming to EU-3 of EN-
779 specifications. The filter efficiency is 90 % down to 10 micron. Filters are provided with handles
for easy removal and are washable.

16
Single Skin, Horizontal Floor Mounted Draw Through Unit

Base Channel
Entire unit is completely supported by a full-perimeter base rail channel. The base rail is constructed
of 2.0 mm thick galvanized sheet steel and has intermediate cross member for the unit support.

Factory Test
Each coil is factory tested and checked for leaks at 325 Psig (pneumatic) under water. Each
assembled AHU is run tested at works before despatch.

Performance Standards
Generally in
accordance to
• Coils - ARI 410
• Motors - IS-325
• Filter - BS-6540 / ASHRAE 52 - 76

Nomenclature
e.g. SHW4 - 035

e.g. S H W 4 - 035

Single skin

Horizontal Floor
Mounted
Chilled Water Coils (X-Direct Expansion Coils)

4 RD Cooling Coils (6-6 RD Cooling Coils)

3,500 CMH

17
18
Technical Data

AHU Overall Dimension Standard Coil Size Fan and Motor Details 40 mm 50 mm Pre Filter
(Fan, Coil, Pre Filter) TSP TSP (50 mm thick)

AHU Model Length Width Height FL FH Coil Coil Air Quantity at Fan Model Fan Opening Outlet Motor Motor
Area In/Out 500 FPM CFV Velocity Power Power Area Face Size Qty.
size Velocity

mm mm mm mm mm Sq. Mt inch CFM CMH BSL W-mm * H-mm m/s KW KW Sq. Mt M/S W-mm * H-mm Nos.

SHW4-035 1651 997 757 660 572 0.377 1 2031 3453 AT 10 - 10 333 * 289 9.97 1.1 1.5 0.400 2.40 400 * 500 2
SHW4-040 1790 1099 896 762 572 0.435 1 2344 3984 AT 12 - 12 396 * 341 8.20 1.1 1.5 0.540 2.05 500 * 600 1
400 * 600 1
SHW4-050 1790 1099 896 762 699 0.532 1 1/4 2865 4870 AT 12 - 12 396 * 341 10.02 1.5 1.5 0.540 2.51 500 * 600 1
400 * 600 1
SHW4-060 1929 1251 1174 914 762 0.697 1 1/2 3750 6375 AT 15 - 15 472 * 401 9.36 2.2 2.2 0.900 1.97 500 * 500 2
500 * 400 2
SHW4-080 1929 1251 1174 914 953 0.871 1 1/2 4688 7969 AT 15 - 15 472 * 401 11.70 2.2 3.7 0.900 2.46 500 * 500 2
Single Skin, Horizontal Floor Mounted Draw Through Unit

500 * 400 2
SHW4-100 1790 1810 1174 1422 762 1.084 1 1/2 5833 9917 AT 18 - 18 556 * 479 10.34 2.2 3.7 1.440 1.91 600 * 500 1
600 * 400 1
500 * 500 2
500 * 400 2
SHW4-120 1790 1810 1174 1422 953 1.355 2 7292 12396 AT 18 - 18 556 * 479 12.93 3.7 3.7 1.440 2.39 600 * 500 1
600 * 400 1
500 * 500 2
500 * 400 2
SHW4-140 1929 1949 1313 1575 953 1.500 2 8073 13724 AT 20 - 20 629 * 627 9.67 3.7 3.7 1.700 2.24 600 * 500 4
500 * 500 2
SHW4-160 1929 1949 1313 1575 1080 1.700 2 9149 15554 AT 20 - 20 629 * 627 10.96 3.7 5.5 1.700 2.54 600 * 500 4
500 * 500 2
SHW4 - 180 2207 2088 1473 1727 1143 1.974 2 10625 18063 AT 22 - 22 692 * 690 10.51 5.5 5.5 2.160 2.32 600 * 600 6
SHW4 - 200 2207 2088 1473 1727 1270 2.194 2 11806 20069 AT 22 - 22 692 * 690 11.68 5.5 7.5 2.160 2.58 600 * 600 6
SHW4 - 220 2207 2366 1600 1981 1207 2.390 2 1/2 12865 21870 AT 25 - 25 794 * 792 9.66 5.5 7.5 2.730 2.23 600 * 500 1
600 * 400 2
500 * 500 3
500 * 400 6
Technical Data

AHU Overall Dimension Standard Coil Size Fan and Motor Details 40 mm 50 mm Pre Filter
(Fan, Coil, Pre Filter) TSP TSP (50 mm thick)

AHU Model Length Width Height FL FH Coil Coil Air Quantity at Fan Model Fan Opening Outlet Motor Motor
Area In/Out 500 FPM CFV Velocity Power Power Area Face Size Qty.
size Velocity

mm mm mm mm mm Sq. Mt inch CFM CMH BSL W-mm * H-mm m/s KW KW Sq. Mt M/S W-mm * H-mm Nos.

SHW4 - 230 2207 2366 1600 1981 1270 2.516 2 1/2 13542 23021 AT 25 - 25 794 * 792 10.17 5.5 7.5 2.730 2.34 600 * 500 1
600 * 400 2
500 * 500 3
500 * 400 6
SHW4 - 250 2207 2366 1600 1981 1397 2.768 2 1/2 14896 25323 AT 25 - 25 794 * 792 11.19 7.5 7.5 2.730 2.58 600 * 500 1
600 * 400 2
500 * 500 3
500 * 400 6
SHW4 - 270 2346 2546 1727 2184 1334 2.913 2 1/2 15677 26651 AT 28 - 28 870 * 868 9.80 7.5 7.5 3.360 2.20 600 * 500 8
600 * 400 4
SHW4 - 290 2346 2546 1727 2184 1461 3.190 2 1/2 17170 29189 AT 28 - 28 870 * 868 10.74 7.5 7.5 3.360 2.41 600 * 500 8
600 * 400 4
SHW4 - 300 2346 2546 1727 2184 1524 3.329 2 1/2 17917 30458 AT 28 - 28 870 * 868 11.20 7.5 9.3 3.360 2.52 600 * 500 8
600 * 400 4
SHW4 - 320 2526 2685 2096 2337 1524 3.561 2 1/2 19167 32583 AT 30 - 30 933 * 932 10.41 7.5 9.3 4.500 2.01 500 * 600 15
SHW4 - 350 2526 2685 2096 2337 1651 3.858 2 20764 35299 AT 30 - 30 933 * 932 11.28 9.3 11.0 4.500 2.18 500 * 600 15
SHW4 - 370 2526 2685 2096 2337 1715 4.006 2 21563 36656 AT 30 - 30 933 * 932 11.71 9.3 11.0 4.500 2.26 500 * 600 15
SHW4 - 400 2526 2685 2096 2337 1842 4.303 2 23160 39372 AT 30 - 30 933 * 932 12.58 11.0 11.0 4.500 2.43 500 * 600 15
SHW4 - 420 2804 2963 2350 2591 1778 4.606 2 1/2 24792 42146 AT 36 - 30 933 * 1089 11.52 11.0 15.0 5.400 2.17 600 * 600 4
500 * 600 6
600 * 400 4
500 * 400 6
Single Skin, Horizontal Floor Mounted Draw Through Unit

19
20
Technical Data

AHU Overall Dimension Standard Coil Size Fan and Motor Details 40 mm 50 mm Pre Filter
(Fan, Coil, Pre Filter) TSP TSP (50 mm thick)

AHU Model Length Width Height FL FH Coil Coil Air Quantity at Fan Model Fan Opening Outlet Motor Motor
Area In/Out 500 FPM CFV Velocity Power Power Area Face Size Qty.
size Velocity

mm mm mm mm mm Sq. Mt inch CFM CMH BSL W-mm * H-mm m/s KW KW Sq. Mt M/S W-mm * H-mm Nos.

SHW4 - 450 2804 2963 2350 2591 1905 4.935 2 1/2 26563 45156 AT 36 - 30 933 * 1089 12.35 11.0 15.0 5.400 2.32 600 * 600 4
500 * 600 6
600 * 400 4
500 * 400 6
SHW4 - 470 2804 2963 2350 2591 1969 5.100 2 1/2 27448 46661 AT 36 - 30 933 * 1089 12.76 15.0 15.0 5.400 2.40 600 * 600 4
500 * 600 6
600 * 400 4
500 * 400 6
Single Skin, Horizontal Floor Mounted Draw Through Unit

SHW4 - 500 2804 2963 2350 2591 2096 5.429 2 1/2 29219 49672 AT 36 - 30 933 * 1089 13.58 15.0 18.5 5.400 2.56 600 * 600 4
500 * 600 6
600 * 400 4
500 * 400 6

Note :

# Face Velocity Over Coil : 2.54 m / s (500 FPM)


# Standard Options
1. Fan Discharge:
Top horizontal, bottom horizontal, upblast
2. Coil row deep= 4 or 6
Coil Fin/Inch : 12,
Coil water circuit : B,C,D.
3. For DX coils, number of refrigerant circuits and tubes per circuit need to be informed.

Dimensions and specifications are subject to change without prior notice.


Coil Details for Horizontal Floor Mounted Double Skin / Single Skin
Air Handling Units Revision ‘A’ - Standard Models
AHU Model Nomenclature Standard Coil Size (YDW / YDX)

Double Skin Single Skin FL TH Split Area Sq.Ft. Cu Header OD

DHW - 035 SHW - 035 26 18 - 4.1 1 1/8”

DHW - 040 SHW - 040 30 18 - 4.7 1 1/8”


DHW - 050 SHW - 050 30 22 - 5.7 1 3/8”

DHW - 060 SHW - 060 36 24 - 7.5 1 5/8”


DHW - 080 SHW - 080 36 30 - 9.4 1 5/8”

DHW - 100 SHW - 100 56 24 - 11.7 1 5/8”


DHW - 120 SHW - 120 56 30 - 14.6 2 1/8”

DHW - 140 SHW - 140 62 30 - 16.1 2 1/8”


DHW - 160 SHW - 160 62 34 - 18.3 2 1/8”

DHW - 180 SHW - 180 68 36 - 21.3 2 1/8”


DHW - 200 SHW - 200 68 40 - 23.6 2 1/8”

DHW - 220 SHW - 220 78 38 - 25.7 2 5/8”


DHW - 230 SHW - 230 78 40 - 27.1 2 5/8”
DHW - 250 SHW - 250 78 44 - 29.8 2 5/8”

DHW - 270 SHW - 270 86 42 - 31.4 2 5/8”


DHW - 290 SHW - 290 86 46 - 34.3 2 5/8”
DHW - 300 SHW - 300 86 48 - 35.8 2 5/8”

DHW - 320 SHW - 320 92 48 - 38.3 2 5/8”


DHW - 350 SHW - 350 92 52 26 + 26 41.5 2 1/8”
DHW - 370 SHW - 370 92 54 28 + 26 43.1 2 1/8”
DHW - 400 SHW - 400 92 58 30 + 28 46.3 2 1/8”

DHW - 420 SHW - 420 102 56 28 + 28 49.6 2 5/8”


DHW - 450 SHW - 450 102 60 30 + 30 53.1 2 5/8”
DHW - 470 SHW - 470 102 62 32 + 30 54.9 2 5/8”
DHW - 500 SHW - 500 102 66 34 + 32 58.4 2 5/8”

DHW - 520 114 62 32 + 30 61.4 2 5/8”


DHW - 540 114 64 32 + 32 63.3 2 5/8”
DHW - 570 114 68 34 + 34 67.3 2 5/8”
DHW - 600 114 72 36 + 36 71.3 2 5/8”

 Copper Headers
 Top & Bottom flange should be of 25 mm
 Coil Mounting Holes Pitch :
 End Plate : 63.5 mm (2.5”)
 Top & Bottom Flange : 50.8 mm (2.0”)
 DX Coils: Each coil is complete with refrigerant distributor

21
½” YDW / YDX Coils: Nomenclature
1) YDW Water Cooling Coils:
YDW 12 A 4 H C 24 R 94 L

½” Drainable water
Fins per Inch, 12 FPI
Fin Matl., A: Aluminium
Rows Deep (RD), 2, 4, 6, 8
Air Flow, H: Horizontal
Circuiting (Tubes per Circuit), B=4, C=6, D=8
Tubes High (TH), 12 to 48
Hand, R: Right, L: Left
Finned Length (FL), 26” to 114”
L: Loose
Note: Field to specify: (a) Circuit type: B. C. D; (b) Hand-off connection: LHS, RHS

2) YDX Direct Cooling Coils:


YDX 12 A 4 24 R 94 L 0156 40 8 09

½” Direct Exp.
Fins per Inch, 12 FPI
Fin Matl., A: Aluminium
Rows Deep (RD), 2, 4, 6, 8
Tubes High (TH), 12 to 48
Hand, R: Right, L: Left
Finned Length (FL), 26” to 114”
L: Loose
Total Coil Load in MBH,
1 MBH = 1000 BTU/HR
Suction Temp., Deg. F
Tubes per Circuit, B=4, C=6, D=8
No. of Circuits
Note: Field to specify (a) Tube per circuit; (b) Hand-off connection: LHS, RHS

22
½” YDW / YDX Coils: Specifications

Tubes : Plain Copper, ½” OD, 27 G Thick

Fins : Plain Corrugated Aluminium, 0.14 mm Thick

End plates : G.P., 120 gsm, 16 G Thick, with embossed Tube Holes

Top / Bottom Plates : G.P., 120 gsm, 18 G Thick

Inlet / Outlet Header : Copper, 0.048” Thick

Header Connection Ext. Pipe : ERW IS: 1239 (Heavy)

Fin Spacing : 12 fins per inch (standard)

Tube pitch (Vertical) : 1.25”

Rows Deep : 2, 4, 6, 8

Tube High : As indicated for each model

Finned Length : As indicated for each model

Air Vent : Brass, ¼” NPTI (mounted on Inlet header)

Drain : Brass, ¼” NPTI (mounted on Outlet header)

Connection side : LH / RH viewing from Air Entry Side

Packing : 8 mm thick thermocole on finned surface (both sides)


Wooden planks for Header protection
Edge Board angles on all edges
Wrapping in stretch film.
Note:
1. DX coil is provided with a distributor.
2. Coil data plate is mounted on Flange of Top Plate.
3. For special applications, non-standard coils with copper tube of thickness of 0.5 mm and
aluminium fin thickness of 0.2 mm can be supplied at an extra cost and lead time.

23
AHU Ordering Format - DHW & SHW Series
Enclosure : ____________________ Dated : ________________

123456789012345678901234567890121234567890123 123456789012345678901234567890121234567890123456
123456789012345678901234567890121234567890123
123456789012345678901234567890121234567890123 123456789012345678901234567890121234567890123456
123456789012345678901234567890121234567890123456
Customer : 123456789012345678901234567890121234567890123
123456789012345678901234567890121234567890123 Project : 123456789012345678901234567890121234567890123456
123456789012345678901234567890121234567890123456
123456789012345678901234567890121234567890123
1234567890123456789012345678901 123456789012345678901234567890121234567890123456
12345678901234567890123456789012
1234567890123456789012345678901
1234567890123456789012345678901 12345678901234567890123456789012
12345678901234567890123456789012
1234567890123456789012345678901 12345678901234567890123456789012
AHU Tag No. : 1234567890123456789012345678901 Date Required : 12345678901234567890123456789012
1234567890123456789012345678901
12345678901234567 12345678901234567890123456789012
General Data

12345678901234567
12345678901234567
Model : 12345678901234567
12345678901234567
Fully Assembled Yes
12345678901234567
12345678901234567 To Be Sent As : TC Reqd :
12345678901234567
Quantity : 12345678901234567 Knocked Down No
12345678901234567
12345678901234567
Yes Excise Full Required
Factory Inspection Factory Supervisor For
Required : No Duty: Nil ( CT-3 ) Assembly At Site : Not Required

Orientation : Upblast / Top Horizontal / Bottom Horizontal Left


Details
Fan

Fan Section Access Door :


Static Pressure : 40 mm 50 mm Right

Type : Chilled Water DX Circuit : B / C / D


Coil Details

Additional information for DX Coil Only


12345678901234567 1234567890123456 12345678901234567 Left
12345678901234567 1234567890123456 12345678901234567 Coil
12345678901234567
12345678901234567 No. Of 1234567890123456
1234567890123456 Suction 12345678901234567
12345678901234567
12345678901234567 1234567890123456 12345678901234567 Connection:
12345678901234567 1234567890123456
1234567890123456 Temp. ( oF) 12345678901234567
TPC : 12345678901234567 Circuits : 12345678901234567
1234567890123456789012345678901212345678901234567890123456789
Right
123456789012345678
1234567890123456789012345678901212345678901234567890123456789
1234567890123456789012345678901212345678901234567890123456789 123456789012345678
123456789012345678
1234567890123456789012345678901212345678901234567890123456789 123456789012345678
Coil Nomenclature As Per 1234567890123456789012345678901212345678901234567890123456789
1234567890123456789012345678901212345678901234567890123456789 Qty / AHU : 123456789012345678
123456789012345678
1234567890123456789012345678901212345678901234567890123456789 123456789012345678
1234567890123456789012345678901212345678901234567890123456789 123456789012345678
York Format : 1234567890123456789012345678901212345678901234567890123456789
1234567890123456789012345678901212345678901234567890123456789 123456789012345678
123456789012345678
1234567890123456789012345678901212345678901234567890123456789 Qty / AHU : 123456789012345678
1234567890123456789012345678901212345678901234567890123456789 123456789012345678

Additional Information / Special Notes : (Pl. Specify)


Remarks

1. Please fill up date where required and Mark  or Circle for selected options
Notes

2. When quantity is more than One, please use separate sheets for ordering when AHU data are not identical.

3. Coil connection / Access door positions etc. may be determined viewed from the air entry side.

Upblast Top Horizontal Bottom Horizondal

24
AHU Ordering Format - DVW & DCW Series
Enclosure : ____________________ Dated : ________________

1234567890123456789012345678901212345678901234 123456789012345678901234567890121234567890123456
1234567890123456789012345678901212345678901234 123456789012345678901234567890121234567890123456
1234567890123456789012345678901212345678901234
1234567890123456789012345678901212345678901234 123456789012345678901234567890121234567890123456
123456789012345678901234567890121234567890123456
1234567890123456789012345678901212345678901234 123456789012345678901234567890121234567890123456
Customer : 1234567890123456789012345678901212345678901234
1234567890123456789012345678901 Project :
1234567890123456789012345678901212345678901234 123456789012345678901234567890121234567890123456
123456789012345678901234567890121234567890123456
12345678901234567890123456789012
General Data

1234567890123456789012345678901
1234567890123456789012345678901 12345678901234567890123456789012
12345678901234567890123456789012
1234567890123456789012345678901 12345678901234567890123456789012
1234567890123456789012345678901
AHU Tag No. : 123456789012345678901234567890121234567890123 Date Required : 12345678901234567890123456789012
1234567890123456789012345678901
123456789012345678901234567890121234567890123
12345678901234567
12345678901234567890123456789012
12345678901234567
123456789012345678901234567890121234567890123 12345678901234567
123456789012345678901234567890121234567890123 12345678901234567
Model : 123456789012345678901234567890121234567890123
123456789012345678901234567890121234567890123
Quantity : 12345678901234567 TC Reqd :
12345678901234567
Yes / No
123456789012345678901234567890121234567890123
Factory Inspection Required : Yes / No Excise Duty : Full Nil ( CT-3 )

Static Pressure : DVW Series : 32 mm 40 mm


Details
Fan

External Static Pressure : DCW - B Series : 12 mm 20 mm

Type : Chilled Water DX

Additional information for DX Coil Only Left


Coil Details

123456789012345 1234567890123456 1234567890123456 Coil


123456789012345 1234567890123456 1234567890123456
123456789012345
123456789012345 No. Of 1234567890123456
1234567890123456 Suction 1234567890123456
1234567890123456 Connection:
TPC : 123456789012345 1234567890123456 1234567890123456 Right
1234567890123451234567890123456789012345678901212345678901234567890123456789
Circuits : 1234567890123456 1234567890123456
1234567890123451234567890123456789012345678901212345678901234567890123456789
1234567890123456 Temp. ( oF) 1234567890123456 123456789012345678
123456789012345678
1234567890123456789012345678901212345678901234567890123456789 123456789012345678
1234567890123456789012345678901212345678901234567890123456789 Qty / AHU : 123456789012345678
1234567890123456789012345678901212345678901234567890123456789 123456789012345678
1234567890123456789012345678901212345678901234567890123456789
Coil Nomenciature As Per 1234567890123456789012345678901212345678901234567890123456789 123456789012345678
123456789012345678
1234567890123456789012345678901212345678901234567890123456789
1234567890123456789012345678901212345678901234567890123456789 123456789012345678
York Format : 1234567890123456789012345678901212345678901234567890123456789 Qty / AHU : 123456789012345678
123456789012345678
1234567890123456789012345678901212345678901234567890123456789 123456789012345678
1234567890123456789012345678901212345678901234567890123456789 123456789012345678
Additional Information / Special Notes : (Pl. Specify)
Remarks

1. Please fill up date where required and Mark  or Circle for selected options

2. When quantity is more than One, please use separate sheets for ordering when AHU data are not identical.
Notes

3. Coil connection / Access door positions etc. may be determined viewed from the air entry side.

25
Field Feedback Card
Return to : Manufacturing Unit - Bharuch
Product: Air Handing Unit

AHU Model:

Unit Sr. No. :

Customer Name : Location :

Date :

Observation Comments Details of Defects

Quality of Packing OK / Damaged

Receipt of Documents

- Packing List Yes / No

- Panel Arrangement Drawing Yes / No

Condition Of Parts :

- Aluminium Extrusion OK / Damaged

- Puf Panels OK / Damaged

- Hardware OK / Damaged

- Drain Pan OK / Damaged

- Fabricated Frames OK / Damaged

- Coil OK / Damaged

- Blower OK / Damaged

- Motor OK / Damaged

- Drive Set OK / Damaged

- Filters OK / Damaged

- Dampers OK / Damaged

Remarks :

Checked by

For Factory Use :

- Date of Receipt : - Action By :

- Comments :

26
Field Commissioning Report
Return to : Manufacturing Unit - Bharuch
Product: Air Handing Unit

AHU Model:

Unit Sr. No. :

Customer Name : Location :

Date :

Observation Comments Details of Defects

Performance Checks :

- Assembly OK /

- Installation OK /

- Commissioning OK /

- Air Quantity ( CMH / CFM )

- Static Pressure ( Pa / mm )

- Blower ( RPM )

- Motor Current ( Amps )

- Noise Level ( dba )

- Vibration OK /

- Air balancing, If done at site Yes / No

- Change in Pulley Size at site Yes / No

- Others, if any

- Commissioning Date

- Commissioning By

Remarks :

Note: Warranty will be valid only after receipt of this card at the factory.

For Factory Use :


- Date of Receipt : - Action By :
- Comments :

27