Ventilation

High Pressure Fans


SwedVent UNDERGROUND VENTILATION SYSTEM

High Pressure Fans


High pressure fans designed especially for delivering air through ducts with extensive length
in mining and tunnelling. Together with GIA SwedVent ducting and GIA SwedVent calcula-
tions, a complete ventilation system is offered.
Technical features

• Available in nine sizes with inner diameter • Aerodynamically designed guide vanes in the
from ø630 to ø2240 mm. hub-casing wich eliminates swirl and turbu-
• Capacity of 1,5 to 200 m³/s. lence.
• System pressure of up to 4 200 Pa/stage. At • Anti rust protection designed to withstand
higher system pressures two or more fans acid and salt environments
are mounted in series. • Silencers with mineral wool as sound absorb-
• 1-5 fan units per fanstation. ing material.

Ventilation
• Heavy duty design with fully welded flanges. • For high efficient noise reduction, the silenc-
• Low sound levels. ers are provided with a centre core which
• Low energy consumption. efficiently also reduces the high frequency
• Available with ISO classified high quality mo- sound.
tors from 10 to 500 kW. • Silencers are also a safe protection against
• Delivered with different types of starters as splinter if a fan should burst.
well as automatic air flow control system. • The inlet bell is bell-shaped and pressure
• Lubrication of the engine bearings is done turned and has a protection grille of spidernet
from outside the casing. model.
• Thermistors are mounted directly onto the • The duct adapter is designed to connect the
motor windings for sensing the heat of the flexible ducting to the fan station.
winding. • The support frame supports the station and is
• Impellers with aerodynamically designed and adapted for the number of fan units in each
individually adjustable blades. fan station.
• Statically and dynamically balanced impeller.
• Precise hub-casing design (small gap be- Standard
tween the casing and the blade tip). CE mark according to European standards.

Options
• Starters • Vibration monitor.
-Direct starters • Air flow measuring devices.
-Dahlander starters (for two-speed motors) • Support frame for roof mounting on 20” con-
-Frequency converters. tainer.
GIA evaluates and recommends which of the
three types will be most suitable. Other options and dimensions on request.

2010-05-19
The manufacturer reserves the right to make modifications without prior notice.
MNS
MNS 201002
Technical data

1-stage

High Pressure Fans


2-stage

3-stage

4-stage

Dimensions (mm)
L1 L2 L3 L4 L5 L6 L7 D1 D2
AVH63 3 398 4 448 5 498 6 548 1 198 1 050 1 150 871 904

Ventilation
AVH71 3 504 4 704 5 904 7 104 1 154 1 200 1 150 955 980
AVH90 4 084 5 464 6 844 8 224 1 354 1 380 1 350 1 172 1 155
AVH100 4 189 5 574 6 959 8 344 1 404 1 385 1 400 1 275 1 255
AVH125 6 000 7 600 9 200 10 800 2 250 1 600 2 150 1 543 1 578
AVH140 6 000 7 600 9 200 10 800 2 250 1 600 2 150 1 728 1 815
AVH160 7 200 9 000 10 800 12 600 2 750 1 800 2 650 1 941 1 985
AVH180 7 303 9 203 11 103 13 003 2 753 1 900 2 650 2 144 2 229
AVH224 8 470 10 570 12 670 14 770 3 250 2 100 3 120 2 595 2 590

Weight (kg)
Fan unit Silencer GS Silencer GSC Inlet bell Duct adapter
(depending on motor)

AVH63 approx. 360 kg 93 114 14 15


AVH71 112 133 14 21
AVH90 approx. 1 000 kg 148 177 17 26
AVH100 187 215 20 28
AVH125 approx. 1 500 kg 315 370 43 46
AVH140 approx.1 460 kg 330 385 52 43
AVH160 approx. 2 100 kg 476 540 61 58
AVH180 approx. 3 550 kg 585 652 70 55
AVH224 approx. 5 800 kg 1 474 ---- 67 69
Silencer GS = without centre core (inner baffle)
Silencer GSC = with centre core (inner baffle)
Functional data

Type Inner diameter Nominal power The casings are treated with anti-rust protection,
AVH63 ø 630 mm 9-25 kW
a 60 µm acrylic primer and a 100 µm acrylic top
layer.
AVH71 ø 710 mm 11-37 kW
AVH90 ø 900 mm 37-90 kW
Bearings, SKF with “auto-lubricators system 24”
AVH100 ø 1 000 mm 45-110 kW on the outside of the casing.
AVH125 ø 1 250 mm 45-160 kW
AVH140 ø 1 400 mm 45-160 kW

High Pressure Fans


AVH160 ø 1 600 mm 75-315 kW
AVH180 ø 1 800 mm 132-500 kW
AVH224 ø 2 240 mm 132-500 kW

Capacity
Pressure from fan station (kPa)
approx. Flow rate
1-stage 2-stage 3-stage 4-stage
AVH63 1,3 - 2,2 2,5 - 4,5 4,0 - 6,5 5,0 - 7,5 3 - 9 m³/s
AVH71 1,3 - 2,3 2,6 - 4,6 4,1 - 6,6 5,2 - 8,5 4 - 13 m³/s
AVH90 3,5 - 4,3 7,0 - 8,6 10,1 - 12,5 12,8 - 16,0 8 - 22 m³/s
AVH100 3,8 - 4,4 7,3 - 8,7 10,3 - 12,6 12,9 - 16,2 10 - 24 m³/s
AVH125 1,5 - 2,6 2,9 - 5,1 4,5 - 7,7 6,0 - 9,5 14 - 42 m³/s
AVH140 1,2 - 2,2 2,3 - 4,3 3,5 - 6,4 4,6 - 9,5 20 - 48 m³/s
AVH160 1,3 - 2,2 2,5 - 4,3 3,8 - 6,4 5,1 - 8,5 22 - 70 m³/s
AVH180 1,5 - 3,5 3,0 - 7,0 5,0 - 10,3 --------- 40 - 120 m³/s
AVH224 1,0 - 2,0 1,5 - 4,0 2,0 - 5,7 --------- - 200 m³/s

Impellers
Quality control
Type Speed (rpm) Hub Blades
GIA works according to the quality system ISO
AVH63 9001 and the fans are delivered with CE marking
ø 380 mm
AVH71 affixed.
3 000 / 3 600
AVH90 Before delivery every fan is tested (capacity,
ø 560 mm 8 pcs
AVH100 vibration etc.) and accompanied with a testreport.
AVH125 Allowed vibrations <2 mm/s.
AVH140 ø 800 mm

Ventilation
1 500 / 1 780
AVH160
10 pcs
AVH180
ø 1 000 mm
AVH224 1 000 / 1 200 10/12 pcs

In combination with

Flexible ducting TCV Underground Control System


Manufactured from PVC-coated polyester fabrics A complete solution for
in four qualities. • Tracking
Titan Aerolite • Communication
FR-RSX FRA-RSX FR-RSX FRA-RSX
• Ventilation

Available in diameters from ø300 - ø3000 mm in


unit length from 10 m up to 150 m.
There are three types of coupling, steel clamps,
zip-joints and velcro.
Repair sleeves are available in length of 1, 3 and
5 metres.

Contact us for further information.

GIA Industri AB Phone +46 (0)240 797 00


Box 59 Fax +46 (0)240 797 25
SE-772 22 Grängesberg Email: info@gia.se
Sweden Web: www.gia.se