• Available in nine sizes with inner diameter • Aerodynamically designed guide vanes in the
from ø630 to ø2240 mm. hub-casing wich eliminates swirl and turbu-
• Capacity of 1,5 to 200 m³/s. lence.
• System pressure of up to 4 200 Pa/stage. At • Anti rust protection designed to withstand
higher system pressures two or more fans acid and salt environments
are mounted in series. • Silencers with mineral wool as sound absorb-
• 1-5 fan units per fanstation. ing material.
Ventilation
• Heavy duty design with fully welded flanges. • For high efficient noise reduction, the silenc-
• Low sound levels. ers are provided with a centre core which
• Low energy consumption. efficiently also reduces the high frequency
• Available with ISO classified high quality mo- sound.
tors from 10 to 500 kW. • Silencers are also a safe protection against
• Delivered with different types of starters as splinter if a fan should burst.
well as automatic air flow control system. • The inlet bell is bell-shaped and pressure
• Lubrication of the engine bearings is done turned and has a protection grille of spidernet
from outside the casing. model.
• Thermistors are mounted directly onto the • The duct adapter is designed to connect the
motor windings for sensing the heat of the flexible ducting to the fan station.
winding. • The support frame supports the station and is
• Impellers with aerodynamically designed and adapted for the number of fan units in each
individually adjustable blades. fan station.
• Statically and dynamically balanced impeller.
• Precise hub-casing design (small gap be- Standard
tween the casing and the blade tip). CE mark according to European standards.
Options
• Starters • Vibration monitor.
-Direct starters • Air flow measuring devices.
-Dahlander starters (for two-speed motors) • Support frame for roof mounting on 20” con-
-Frequency converters. tainer.
GIA evaluates and recommends which of the
three types will be most suitable. Other options and dimensions on request.
2010-05-19
The manufacturer reserves the right to make modifications without prior notice.
MNS
MNS 201002
Technical data
1-stage
3-stage
4-stage
Dimensions (mm)
L1 L2 L3 L4 L5 L6 L7 D1 D2
AVH63 3 398 4 448 5 498 6 548 1 198 1 050 1 150 871 904
Ventilation
AVH71 3 504 4 704 5 904 7 104 1 154 1 200 1 150 955 980
AVH90 4 084 5 464 6 844 8 224 1 354 1 380 1 350 1 172 1 155
AVH100 4 189 5 574 6 959 8 344 1 404 1 385 1 400 1 275 1 255
AVH125 6 000 7 600 9 200 10 800 2 250 1 600 2 150 1 543 1 578
AVH140 6 000 7 600 9 200 10 800 2 250 1 600 2 150 1 728 1 815
AVH160 7 200 9 000 10 800 12 600 2 750 1 800 2 650 1 941 1 985
AVH180 7 303 9 203 11 103 13 003 2 753 1 900 2 650 2 144 2 229
AVH224 8 470 10 570 12 670 14 770 3 250 2 100 3 120 2 595 2 590
Weight (kg)
Fan unit Silencer GS Silencer GSC Inlet bell Duct adapter
(depending on motor)
Type Inner diameter Nominal power The casings are treated with anti-rust protection,
AVH63 ø 630 mm 9-25 kW
a 60 µm acrylic primer and a 100 µm acrylic top
layer.
AVH71 ø 710 mm 11-37 kW
AVH90 ø 900 mm 37-90 kW
Bearings, SKF with “auto-lubricators system 24”
AVH100 ø 1 000 mm 45-110 kW on the outside of the casing.
AVH125 ø 1 250 mm 45-160 kW
AVH140 ø 1 400 mm 45-160 kW
Capacity
Pressure from fan station (kPa)
approx. Flow rate
1-stage 2-stage 3-stage 4-stage
AVH63 1,3 - 2,2 2,5 - 4,5 4,0 - 6,5 5,0 - 7,5 3 - 9 m³/s
AVH71 1,3 - 2,3 2,6 - 4,6 4,1 - 6,6 5,2 - 8,5 4 - 13 m³/s
AVH90 3,5 - 4,3 7,0 - 8,6 10,1 - 12,5 12,8 - 16,0 8 - 22 m³/s
AVH100 3,8 - 4,4 7,3 - 8,7 10,3 - 12,6 12,9 - 16,2 10 - 24 m³/s
AVH125 1,5 - 2,6 2,9 - 5,1 4,5 - 7,7 6,0 - 9,5 14 - 42 m³/s
AVH140 1,2 - 2,2 2,3 - 4,3 3,5 - 6,4 4,6 - 9,5 20 - 48 m³/s
AVH160 1,3 - 2,2 2,5 - 4,3 3,8 - 6,4 5,1 - 8,5 22 - 70 m³/s
AVH180 1,5 - 3,5 3,0 - 7,0 5,0 - 10,3 --------- 40 - 120 m³/s
AVH224 1,0 - 2,0 1,5 - 4,0 2,0 - 5,7 --------- - 200 m³/s
Impellers
Quality control
Type Speed (rpm) Hub Blades
GIA works according to the quality system ISO
AVH63 9001 and the fans are delivered with CE marking
ø 380 mm
AVH71 affixed.
3 000 / 3 600
AVH90 Before delivery every fan is tested (capacity,
ø 560 mm 8 pcs
AVH100 vibration etc.) and accompanied with a testreport.
AVH125 Allowed vibrations <2 mm/s.
AVH140 ø 800 mm
Ventilation
1 500 / 1 780
AVH160
10 pcs
AVH180
ø 1 000 mm
AVH224 1 000 / 1 200 10/12 pcs