Professional Documents
Culture Documents
MICRO SERIES
YORK STELLAR DEH MICRO SERIES
Table of Contents
DESCRIPTION............................................................................................................................................3
TYPICAL UNIT CONFIGURATION ..................................................................................................................3
FEATURES.............................................................................................................................................4
OPTIONS AVAILABLE .............................................................................................................................4
SELECTION METHOD: ............................................................................................................................5
PIN NUMBER GUIDELINES......................................................................................................................5
PRODUCT DATA ....................................................................................................................................6
COOLING PERFORMANCE DATA .............................................................................................................7
FAN PERFORMANCE DATA................................................................................................................... 17
SOUND RATING DATA ......................................................................................................................... 18
ELECTRICAL DATA ............................................................................................................................... 18
DIMENSIONAL DATA (DEH 036-048)..................................................................................................... 19
DIMENSIONAL DATA (DEH 060-072)..................................................................................................... 20
TYPICAL WIRING DIAGRAM.................................................................................................................. 21
GUIDE SPECIFICATION............................................................................................................................. 22
DESCRIPTION ...................................................................................................................................... 22
REFRIGERANT R-410a .......................................................................................................................... 22
MAINTENANCE ....................................................................................................................................... 23
EVERY MONTH.................................................................................................................................... 23
EVERY THREE MONTHS ....................................................................................................................... 23
EVERY SIX MONTHS............................................................................................................................. 23
EVERY TWELVE MONTHS ..................................................................................................................... 23
TEH-36-72-0921 2
YORK STELLAR DEH MICRO SERIES
DESCRIPTION
Models DEH 036, 048, 060, 072 (3, 4, 5, 6 Nominal Tons).
YORK STELLAR Units are single package energy efficient high ambient rooftops air conditioner. All Models have single refrigera nt circuits for efficient part
load operation. STELLAR units are designed for roof top slab mounted at ground level or on steel platform installation above floor or roof. A wide range of
factory mounted options and field installed accessories make the STELLAR units suitable for almost e very application.
YORK STELLAR units are designed to operate satisfactorily in wide range of ambient temperatures from 131°F (55°C) down to 50°F (10°C) as standard.
YORK STELLAR packaged air conditioners are rated in accordance with AHRI 340/360.
• Powder paint finish that meets ASTM B 117, 750 hour salt spray standard.
• Single stage cooling provided by single independent refrigeration circuits with expansion valves, filter drier, high and low pressure switches.
• High efficiency compressors.
• Side air discharge configuration.
• Direct drive arrangement.
• Totally Enclosed Air over (TEAO) Evaporator fan motors with Class B Insulation.
• Totally Enclosed Air over (TEAO) Condenser fan motors with Class B/F Insulation.
• Fresh air intake panel.
• Copper tubes / Aluminum fins Evaporator coils.
• Micro-Channel Aluminum alloy Condenser coils.
• 2 inch disposable filter with easy access.
• Rigging holes in base rails for overhead lifting. Single point power connection.
• Complete factory package-tested, charged and wired.
TEH-36-72-0921 3
YORK STELLAR DEH MICRO SERIES
OPTIONS AVAILABLE
FEATURES
• Heresite Coated Evaporator Coils (factory installed):
Stellar units are self-contained and assembled on full perimeter base rails
Coating is applied by spray for maximum corrosion
with rigging holes in the four corners for overhead rigging. Every unit is
protection.
completely piped, wired, charged and tested at the factory to simplify the
field installation and to provide years of dependable operation. All models
• Techno Coating and E-Coating Condenser Coils (factory
are suitable for horizontal duct connections.
installed).
The power supply can be routed into the control box through a gland in
the wiring panel on the front of the unit.
• Copper Tube and Copper Fin Evaporator Coils (factory
Compressors type of an advanced design ensuring high Energy installed).
Efficiency Ratio, less noise, less vibration and outstanding
endurance.Internal pressure relief valve, internal compressor motor • Filter Options: Standard units are shipped, installed with 2”
protection. Every refrigerant circuit includes an expansion valve, liquid line throw away filters. 2” washable aluminum filters.
filter-drier, a discharge line high pressure switch and low pressure switch
to protect all system components. • Fresh Air Dampers: Manual or motorized.
Each supply air blower is equipped with a direct motor drive to meet the • Electric Heaters: All electric heat models (heater fac-
exact requirements of the application. All evaporator blower motors are tory/field installed only) are wired for a single power source
TEAO with Class B insulation. and include a bank of nickel chromium elements to be
mounted at the discharge of the supply air blower to
A fixed outdoor air intake connection that is designed for 25% fresh air is provide a high velocity and uniform distribution of air across
available as standard. Fresh air dampers are optional for field / factory the heating elements. Every element is fully protected
installation. against excessive current and temperature by high
temperature thermal cut-out (HTIC).
Condenser fans are propeller type of heavy duty construction,
dynamically balanced and suitable for operate up to 80°C ambient. Fans • Main Disconnect Switch (factory installed): Suitably sized in
are driven by TEAO motors with Class B/F insulation. accordance with the applicable electrical codes.
The fan blade pitch Angle is designed for maximum airflow and minimum
noise. • Thermostat (field installed): For Single stage cooling only
and a single stage heating.
The evaporator and microchannel coils are constructed of seamless
internally enhanced copper tubes and aluminum tubes which are • Smoke Detectors for supply air & return air (factory
mechanically bonded to aluminum fins. Heat Exchangers are tested to a installed): The smoke detectors stop operation of the unit
minimum pressure of 445/236 psig High/Low. by interrupting power to the control board if smokes
detected within the air compartment.
A GI painted drain pan with side condensate removal ensures zero water
retention and no corrosion that ensures indoor air quality (IAQ).
All units have long lasting powder paint cabinets with a robust 40 microns
thick paint coating that meets ASTM-B-117 standards and suitable for
750 hour salt spray test, ensuring excellent resistance to corrosion in the
harshest conditions. The cabinet of all Stellar is internally lined by 13mm
Elastomeric insulation that minimize heat gain and improves IAQ.
TEH-36-72-0921 4
YORK STELLAR DEH MICRO SERIES
SELECTION METHOD:
Step 2 For the sensible capacity read the value at the Intersection of the
The following steps illustrate the selection of a DEH Package Unit for a
same row (as the WB in step1) and the 80° DB column on the right. The
Total Capacity requirement of 46MBh and an Airflow of 1,600 cfm. The
Sensible capacity for the unit in this example is 36.5 MBh.
unit operating
Parameters are;
Refer “Fan Performance Data” on page 17 to Check the motor size .
Entering Air Temperature: 80/67°F (DB/WB)
Ambient Temperature: 95°F
Fan External Static Pressure: 0.6 inch wg.
E = Energy Efficient
(SASO Compliant) Field Installed Options
1 = No option installed
2 = 5 Kw Electric Heater
3 = 9 Kw Electric Heater
Product Identifier 4 = Fresh Air Damper
H = High Ambient Operation
Motor Option
A = Standard motor
Power Supply
5 = 230V /1Ph / 60Hz
TEH-36-72-0921 5
YORK STELLAR DEH MICRO SERIES
PRODUCT DATA
Compressor Power Input Hp (KW) 3.3 (2.4) 4.6 (3.4) 5.6 (4.2) 6.5 (4.8)
Area ft² m² 5.8 (0.5) 5.8 (0.5) 10.5 (0.97) 10.5 (0.97)
Area ft² m² 15.5 (1.4) 15.5 (1.4) 21.6 (2) 24.4 (2.3)
Fan Qty 1 1 1 1
Blower Fan & Motor
Motor Type EMC, Class B insulation, Totally Enclosed Air Over
Motor Size std Hp (KW) 0.5 (0.37) 0.75 (0.55) 1.0 (0.75) 1.0 (0.75)
Quantity # 1 1 1 1
Condenser Fan &
Motor Type Class B Insulation, Totally Enclosed Air Over Class F Insulation, Totally Enclosed Air Over
Motor
Motor size Hp (KW) 0.75 (0.55) 0.75 (0.55) 0.75 (0.55) 0.75 (0.55)
Quantity # 1 1 1 1
Type R-410a
Refrigerant No of Circuits # 1 1 1 1
Charge lbs kgs 5.8 (2.6) 4.5 (2) 6.6 (3) 9.9 (4.5)
Weights Basic Unit lbs kgs 904 (410) 973 (441) 1395 (633) 1197 (543)
TEH-36-72-0921 6
YORK STELLAR DEH MICRO SERIES
TEH-36-72-0921 7
YORK STELLAR DEH MICRO SERIES
TEH-36-72-0921 8
YORK STELLAR DEH MICRO SERIES
TEH-36-72-0921 9
YORK STELLAR DEH MICRO SERIES
TEH-36-72-0921 10
YORK STELLAR DEH MICRO SERIES
TEH-36-72-0921 11
YORK STELLAR DEH MICRO SERIES
TEH-36-72-0921 12
YORK STELLAR DEH MICRO SERIES
TEH-36-72-0921 13
YORK STELLAR DEH MICRO SERIES
TEH-36-72-0921 14
YORK STELLAR DEH MICRO SERIES
TEH-36-72-0921 15
YORK STELLAR DEH MICRO SERIES
TEH-36-72-0921 16
YORK STELLAR DEH MICRO SERIES
TEH-36-72-0921 17
YORK STELLAR DEH MICRO SERIES
ELECTRICAL DATA
Condenser Blower Heater Heater Heater Minimum Circuit Maximum Fuse/
Compressor
Unit Model Voltage Qty Motor Qty Motor Sizes Stages Current Amperes Breaker Size
RLA Each LRA Each FLA Each STD kW # Amperes STD Amps STD Amps
18.6 79 1 1.6 1 4.3 - - - 29 45
DEH036 230/1/60
18.6 79 1 1.6 1 4.3 5kW 1 21.74 33 50
24.3 117 1 1.6 1 6.1 - - - 38 60
DEH048 230/1/60
24.3 117 1 1.6 1 6.1 5kW 1 21.74 38 60
29.3 134 1 5.1 1 6.5 - - - 48 75
DEH060 230/1/60
29.3 134 1 5.1 1 6.5 5kW 1 21.74 48 75
34.3 178 1 5.1 1 6.5 - - - 55 85
DEH072 230/1/60 34.3 178 1 5.1 1 6.5 5kW 1 21.74 55 85
34.3 178 1 5.1 1 6.5 9kW 1 40 58 95
TEH-36-72-0921 18
YORK STELLAR DEH MICRO SERIES
TEH-36-72-0921 19
YORK STELLAR DEH MICRO SERIES
TEH-36-72-0921 20
YORK STELLAR DEH MICRO SERIES
TEH-36-72-0921 21
YORK STELLAR DEH MICRO SERIES
Each unit shall have single condenser fans / motors. The outdoor fans REFRIGERANT R-410a
shall be of direct driven propeller type, discharge air vertically and shall be
dynamically balanced for smooth operation. The outdoor fan motors shall R-410a refrigerant is highly efficient heat transfer capability and
be TEAO with class B insulation. Motors shall have permanently environment friendly having zero Ozone Depletion Potentail (ODP).
lubricated bearings and shall have external overload protection. This product is coming with holding refrigerant charge from the factory.
Refrigerant charge must be checked before startup to assure design
REFRIGERANT COMPONENTS performance.
Compressors
Coils
TEH-36-72-0921 22
YORK STELLAR DEH MICRO SERIES
MAINTENANCE
The DEH Stellar Packaged Air Conditioners are premium quality machines with very low maintenance requirements.
Compressors used in Packaged Units are charged with the correct amount of refrigerant and lubricating oil. Unless there is a l eak in the system, no topping
up is generally required.
EVERY MONTH
• Remove the filters and blow compressed air over them to get rid of loose dust. Visually inspect the filter conditions, replac e them with new
ones of same sizes if required.
• DEH Packaged Air Conditioners are provided with a specially designed drain pan, for proper maintenance check and clean blockages at
drain connections if any.
• The condenser coils should be cleaned by spraying water over it at low pressure or with a brush while ensuring that the fins a re not damaged.
• Check all electrical connections and tighten them if required.
• Clean all accessible electrical panels of dirt and dust. Before cleaning the control panels , ENSURE that the electrical power to the unit is
switched off.
TEH-36-72-0921 23
YORK STELLAR DEH MICRO SERIES
Whether you’re at home, in a car, or in an office or workplace, chances are there’s a Johnson
Controls product or service nearby, helping to make your environment more comfortable, safe and
sustainable.
Johnson Controls creates smart environments that improve the places where people spend most of
their time – their homes, workplaces and vehicles. We anticipate consumer needs, and then
integrate technologies, products and services to make life better and easier.
For Johnson Controls, sustain ability matters at every level and through our products, service
operations and community involvement, we promote the efficient use of resources to benefit all
people and the world. Our triple bottom line of sustain ability that is, economic prosperity,
environmental stewardship and social responsibility impacts each and every aspect of our business.
York products are now a premier brand manufactured by Johnson Controls. The acquisition of York,
gives us a unique insight into designing HVAC products that match your exact requirements. We
provide solutions for today's most critical concerns - energy efficiency, refrigerant alternatives and
indoor air quality.
Johnson Controls has a wide range of York products for residential, light commercial and
commercial applications. Our offering includes package & split air conditioners and heat pumps. In
addition, Johnson Controls offers chillers, air handling units, ventilation equipment and controls for
larger projects.