Compressor 4FES-3Y-40S
Capacity steps 100%
Cooling capacity 9.40 kW
Cooling capacity * 9.43 kW
Evaporator capacity 9.40 kW
Power input 1.71 kW
Current (400V) 4.49 A
Voltage range 380-420V
Condenser capacity 11.10 kW
COP/EER 5.51
COP/EER * 5.53
Mass flow 239 kg/h
Operating mode Standard
Discharge gas temp. w/o cooling 33.9 °C
Tentative Data.
Discharge gas temperature at least 20K (36°F) above condensing temperature
Consider national standards for the use of flammable refrigerants.
*According to EN12900 (20°C suction gas temp., 0K liquid subcooling)
Legend
additional cooling
M1: motor 1
M2: motor 2
BITZER Software v6.17.9 rev2773 10/24/2022 / All data subject to change. 1/1
Result
Compressor 4FES-3Y-40S
Capacity steps 100%
Cooling capacity 8.78 kW
Cooling capacity * 8.84 kW
Evaporator capacity 8.78 kW
Power input 1.89 kW
Current (400V) 4.64 A
Voltage range 380-420V
Condenser capacity 10.66 kW
COP/EER 4.66
COP/EER * 4.69
Mass flow 234 kg/h
Operating mode Standard
Discharge gas temp. w/o cooling 38.8 °C
Tentative Data.
Discharge gas temperature at least 20K (36°F) above condensing temperature
Consider national standards for the use of flammable refrigerants.
*According to EN12900 (20°C suction gas temp., 0K liquid subcooling)
Legend
additional cooling
M1: motor 1
M2: motor 2
BITZER Software v6.17.9 rev2773 10/24/2022 / All data subject to change. 1/1
Result
Compressor 4FES-3Y-40S
Capacity steps 100%
Cooling capacity 8.16 kW
Cooling capacity * 8.25 kW
Evaporator capacity 8.16 kW
Power input 2.05 kW
Current (400V) 4.79 A
Voltage range 380-420V
Condenser capacity 10.21 kW
COP/EER 3.98
COP/EER * 4.02
Mass flow 230 kg/h
Operating mode Standard
Discharge gas temp. w/o cooling 43.6 °C
Tentative Data.
Discharge gas temperature at least 20K (36°F) above condensing temperature
Consider national standards for the use of flammable refrigerants.
*According to EN12900 (20°C suction gas temp., 0K liquid subcooling)
Legend
additional cooling
M1: motor 1
M2: motor 2
BITZER Software v6.17.9 rev2773 10/24/2022 / All data subject to change. 1/1
Result
Compressor 4FES-3Y-40S
Capacity steps 100%
Cooling capacity 7.53 kW
Cooling capacity * 7.66 kW
Evaporator capacity 7.53 kW
Power input 2.20 kW
Current (400V) 4.94 A
Voltage range 380-420V
Condenser capacity 9.73 kW
COP/EER 3.42
COP/EER * 3.48
Mass flow 224 kg/h
Operating mode Standard
Discharge gas temp. w/o cooling 48.6 °C
Tentative Data.
Discharge gas temperature at least 20K (36°F) above condensing temperature
Consider national standards for the use of flammable refrigerants.
*According to EN12900 (20°C suction gas temp., 0K liquid subcooling)
Legend
additional cooling
M1: motor 1
M2: motor 2
BITZER Software v6.17.9 rev2773 10/24/2022 / All data subject to change. 1/1
Result
Compressor 4FES-3Y-40S
Capacity steps 100%
Cooling capacity 6.89 kW
Cooling capacity * 7.06 kW
Evaporator capacity 6.89 kW
Power input 2.34 kW
Current (400V) 5.08 A
Voltage range 380-420V
Condenser capacity 9.23 kW
COP/EER 2.95
COP/EER * 3.02
Mass flow 218 kg/h
Operating mode Standard
Discharge gas temp. w/o cooling 53.6 °C
Tentative Data.
Discharge gas temperature at least 20K (36°F) above condensing temperature
Consider national standards for the use of flammable refrigerants.
*According to EN12900 (20°C suction gas temp., 0K liquid subcooling)
Legend
additional cooling
M1: motor 1
M2: motor 2
BITZER Software v6.17.9 rev2773 10/24/2022 / All data subject to change. 1/1
Result
Compressor 4FES-3Y-40S
Capacity steps 100%
Cooling capacity 6.25 kW
Cooling capacity * 6.47 kW
Evaporator capacity 6.25 kW
Power input 2.46 kW
Current (400V) 5.21 A
Voltage range 380-420V
Condenser capacity 8.71 kW
COP/EER 2.54
COP/EER * 2.63
Mass flow 212 kg/h
Operating mode Standard
Discharge gas temp. w/o cooling 58.7 °C
Tentative Data.
Discharge gas temperature at least 20K (36°F) above condensing temperature
Consider national standards for the use of flammable refrigerants.
*According to EN12900 (20°C suction gas temp., 0K liquid subcooling)
Legend
additional cooling
M1: motor 1
M2: motor 2