Canalis
20 to 1000 A
Prefabricated busbar trunking
Catalogue
2012
Range contents
Index 3
Index of catalogue numbers
Introduction 8
Canalis KDP 57
Presentation 58
Description 62
Catalogue numbers - Dimensions 69
Installation 78
Canalis KBA and KBL industrial luminaires 85
Presentation 86
Description 90
Catalogue numbers - Dimensions 96
Installation 106
Canalis KBB 113
Presentation 114
Description 118
Catalogue numbers - Dimensions 124
Installation 132
Canalis KN 139
Presentation 140
Description 144
Catalogue numbers - Dimensions 150
Installation 168
Canalis KS 175
Presentation 176
Description 180
Catalogue numbers - Dimensions 188
Installation 218
Canalis KS riser 229
Presentation 230
Description 234
Catalogue numbers - Dimensions 236
Installation 246
Canalis KT 253
Presentation 254
Maintenance 267
Maintenance 268
81140 Household NF sockets 159, 207 KBB 40DF4405W Flexible length 40 A, 0.5 m 126
81141 Household Schuko sockets 159, 207 KBB 40DF4420W Flexible length 40 A, 2 m 126
KBB 40ED2202W Straight distribution lengths 40 A, 2 m 124
KBA KBB 40ED22203W Straight distribution lengths 40 A, 2 m 125
KBA 25ABG4W Feed unit 25 A left mounting 97 new 125
KBB 40ED22300W Straight distribution lengths 40 A, 3 m new
KBA 25ED2300W Transport length 25 A, 3 m 96 new KBB 40ED22305W Straight distribution lengths 40 A, 3 m 125
KBA 25ED2302W Straight distribution length 25 A, 3 m 96 new KBB 40ED2300W Transport length 40 A, 3 m 124 new
KBA 25ED2303W Straight distribution length 25 A, 3 m 96 124
KBB 40ED2303W Straight distribution lengths 40 A, 2 m
KBA 25ED2305W Straight distribution length 25 A, 3 m 96 new 124
KBB 40ED4202W Straight distribution lengths 40 A, 2 m
KBA 25ED4202W Straight distribution length 25 A, 2 m 96 new 125
KBB 40ED42203W Straight distribution lengths 40 A, 2 m
KBA 25ED4300W Transport length 25 A, 3 m 96 new KBB 40ED42300W Transport length 40 A, 3 m 125 new
KBA 25ED4302W Straight distribution length 25 A, 3 m 96 new KBB 40ED42305W Straight distribution lengths 40 A, 3 m 125
KBA 25ED4303W Straight distribution length 25 A, 3 m 96 124
KBB 40ED4300W Transport length 40 A, 3 m new
KBA 25ED4305W Straight distribution length 25 A, 3 m 96 new 124
KBB 40ED4303W Straight distribution lengths 40 A, 3 m
KBA 40ABD4W Feed unit 40 A right mounting 97 125
KBB 40ED44203W Straight distribution lengths 40 A, 2 m
KBA 40ABG4W Feed unit 40 A left mounting 97 125
KBB 40ED44300W Transport length 40 A, 3 m new
KBA40ABT4W Center feed unit 40A 97 125
KBB 40ED44305W Straight distribution lengths 40 A, 3 m
KBA 40DF405W Flexible length 40 A, 0.5 m 97 124, 125
KBB 40EDA20W Empty length 2 m
KBA 40DF420W Flexible length 40 A, 2 m 97 98, 126
KBB 40ZFC Pigtail hook
KBA 40ED2203W Straight distribution lengths 40 A, 2 m 96 new 98, 127
KBB 40ZFC5 Open hook
KBA 40ED2300W Transport length 40 A, 3 m 96 new 98, 127
KBB 40ZFC6 Closed ring
KBA 40ED2303W Straight distribution lengths 40 A, 3 m 96 99, 127
KBB 40ZFG1 &DEOHGXFWPP¿[LQJEUDFNHW
KBA 40ED2305W Straight distribution lengths 40 A, 3 m 96 new KBB 40ZFG2 Cable duct support + intermediate 127
KBA 40ED4203W Straight distribution length 40 A, 2 m 96 support
KBB 25ED2300W Transport length 25 A, 3 m 124 new KBC 06DCERFZ RF control tap-off unit with GST18i3 77
KBB 25ED2303W Straight distribution lengths 25 A, 3 m 124 KBC 10DCB20 10 A tap-off units 73, 102, 128
KBB 25ED42300W Transport length 25 A, 3 m 125 new KBC 10DCB40 10 A tap-off units 73, 102, 128
KBB 25ED42305W Straight distribution lengths 25 A, 3 m 125 KBC 10DCC211 10 A tap-off units 73, 102, 128
KBB 25ED4300W Transport length 25 A, 3 m 124 new KBC 10DCC21Z 10 A tap-off units 73, 102, 128
KBZ KFB
71 KFB 25CD253 Cable duct 25 m 99, 127
KBZ 31EFC010 Connection lead 1 m
71 KFB CA81100 Cantilever arm 100 mm 154
KBZ 31EFC030 Connection lead 3 m
71 KFB CA81200 Cantilever arm 200 mm 192, 239, 244
KBZ 31EFC050 Connection lead 5 m
71 KFB CA81300 Cantilever arm 300 mm 198, 204
KBZ 31EFM020 Connection lead 2 m
KBZ 31EFM030 Connection lead 3 m 71 KNA
KBZ 31EFM040 Connection lead 4 m 71 KNA 100AB4 End feed unit 100 A 151
KBZ 31EFM050 Connection lead 5 m 71 KNA 100ABT4 Center feed unit 100 A 151
KBZ 31EFM070 Connection lead 7 m 71 KNA 100DF410 Flexible edgewise lenght 100 A 153
KBZ 31EFM090 Connection lead 9 m 71 KNA 100DL4 Flexible edgewise elbows 100 A 153
KBZ 31EMC010 Connection lead 1 m 71 KNA 100ED4204 Straight length 100 A 150
KBZ 32APFR2 Connector for connection lead 71 KNA 100ED4301 Straight length 100 A 150
KBZ 32APMR2 Connector to be wired 71 KNA 100ED4303 Straight length 100 A 150
KBZ 32DBA12 Splitter block 71 KNA 100ED4306 Straight length 100 A 150
KBZ 32DBA15 Splitter block 71 KNA 100EDF430 Flexible length 160 A 154
KBZ 32ZVP01 Locking device for connecti on lead 71 KNA 160AB4 End feed unit 160 A 151
KNA 160ABT4 Center feed unit 160 A 151
KNB 160ZL40 Tap-off locating device 167 KSA 1000ABG4 End feed unit 1000 A 201, 243
KNB 16CF2 Tap-off unit 16 A, L + N + PE for UTE 160 KSA 1000ABT4 Centre feed box 1000 A 202
fuses KSA 1000AE4 Flange feed unit 1000 A 202, 243
KNB 16CG2 Tap-off unit 16 A L + N + PE for BS fuses 162 203, 242
KSA 1000DLC40 Elbow 1000 A
KNB 16CM2 Tap-off unit 16 A, L + N + PE 156
KSA 1000DLE40 Elbow 1000 A 203, 242
KNB 16CM2H Tap-off unit 16 A, L + N + PE 156
KSA 1000DLF40 Elbow 1000 A 203, 242
KNB 16CN5 Tap-off unit 16 A for DIN fuses 164
KSA 1000DTC40 Tee 1000 A 203
KNB 20CG5 Tap-off unit 20 A for BS fuses 162
KSA 1000ED4081 Riser distribution length 0,8 m 1 tap-off 241
KNB 25CF5 Tap-off unit 25 A for NF fuses 160 outlet 1000 A
KNB 25SD4 Tap-off unit 25 A with isolator for DIN 164 KSA 1000ED4154 Straight distribution length 1.5 m 1000 A 200
fuses Straight distribution length 2 m 1000 A 200
KSA 1000ED4206
KNB 32CM55 Tap-off unit 32 A for modular equipment 156
KSA 1000ED4306 Straight distribution length 3 m 1000 A 200
KNB 32CP Tap-off unit 32 A empty for 2 sockets 159
KSA 1000ED45010 Straight distribution length 5 m 1000 A 200
KNB 32CP11D Tap-off unit 32 A with 2 DIN sockets 158
KSA 1000ET430 Transport length 3 m 1000 A 242
KNB 32CP11F Tap-off unit 32 A with 2 NF sockets 158
KSA 1000ET450 Transport length 5 m 1000 A 242
KNB 32CP15D Tap-off unit 32 A with 1 DIN and 1 IEC 158
KSA 1000ET4A Made to measure length 1000 A 202, 242
socket
KNB 32CP15F Tap-off unit 32 A with 1 NF and 1 IEC 158 KSA 1000ET4AF Fire barrier length 1000 A 202, 241
socket KSA 1000EV4203 Riser distribution length 2 m 3 tap-off 241
KNB 32CP35 Tap-off unit 32 A with 2 IEC sockets 158 outlets 1000 A
KNB 32SG4 Tap-off unit 32 A with isolator for BS 163 KSA 1000EV4254 Riser distribution length 2,5 m 4 tap-off 241
fuses outlets 1000 A
KNB 50SD4 Tap-off unit 50 A with isolator for DIN 164 KSA 1000ZJ4 Jointing device 1000 A 205, 245
fuses 189, 238
KSA 100AB4 End feed unit 1000 A
KNB 50SF4 Tap-off unit 50 A with isolator for NF 161
fuses KSA 100ED4081 Riser distribution length 0.8 m 1 tap-off 236
outlet 100 A
KNB 50SN4 Tap-off unit 50 A with isolator for DIN 164
fuses KSA 100ED4306 Straight distribution length 3 m 100 A 188
KNB 63SM412 Tap-off unit 63 A for modular equipment 157 KSA 100ED45010 Straight distribution length 5 m 100 A 188
KSA 160ED4306 Straight distribution length 3 m 160 A 188 KSA 630ABT4 Centre feed box 630 A 196
KSA 160ED45010 Straight distribution length 5 m 160 A 188 KSA 630AE4 Flange feed unit 630 A 196, 243
KSA 250AB4 End feed unit 250 A 189, 238 KSA 630DLC40 Elbow 630 A 197, 242
KSA 250ABT4 Centre feed box 250 A 190 KSA 630DLE40 Elbow 630 A 197, 242
KSA 250AE4 Flange feed unit 250 A 190, 238 KSA 630DLF40 Elbow 630 A 197, 242
KSA 250DLC40 Elbow 250 A 191, 237 KSA 630DTC40 Tee 630 A 197
KSA 250DLE40 Elbow 250 A 191, 237 KSA 630ED4081 Riser distribution length 0,8 m 1 tap-off 241
outlet 630 A
KSA 250DLF40 Elbow 250 A 191, 237
KSA 630ED4154 Straight distribution length 1.5 m 630 A 194
KSA 250DTC40 Tee 250 A 191
KSA 630ED4206 Straight distribution length 2 m 630 A 194
KSA 250ED4081 Riser distribution length 0.8 m 1 tap-off 236
outlet 250 A KSA 630ED4306 Straight distribution length 3 m 630 A 194
KSA 250ED4156 Straight distribution length 1.5 m 250 A 188 KSA 630ED45010 Straight distribution lenght 5 m 630 A 194
KSA 250ED4208 Straight distribution length 2 m 250 A 188 KSA 630ET430 Transport length 3 m 630 A 242
KSA 250ED4306 Straight distribution length 3 m 250 A 188 KSA 630ET450 Transport length 5 m 630 A 242
KSA 250ED45010 Straight distribution length 5 m 250 A 188 KSA 630ET4A Made to measure length 630 A 196, 242
KSA 250ET4A Made to measure length 250 A 190 KSA 630ET4AF Fire barrier length 630 A 196, 241
KSA 250ET4AF Fire barrier length 250 A 190, 236 KSA 630EV4203 Riser distribution length 2 m 3 tap-off 241
outlets 630 A
KSA 250EV4203 Riser distribution length 2 m 3 tap-off 236
outlets 250 A KSA 630EV4254 Riser distribution length 2,5 m 4 tap-off 241
outlets 630 A
KSA 250EV4254 Riser distribution length 2.5 m 4 tap-off 236
outlets 250 A KSA 630ZJ4 Jointing device 630 A 199, 245
KSA 250FA4 2OG.6$DGDSWHU 193 KSA 80EZ5 Fixing bracket 189
KSA 250ZJ4 Jointing device 250 A 193, 240 KSA 800ED4306 Straight distribution length 3 m 800 A 200
KSA 400AB4 End feed unit 400 A 189, 238 KSA 800ED45010 Straight distribution lenght 5 m 800 A 200
KSA 400ABT4 Centre feed box 400 A 190 KSA 800ET430 Transport length 3 m 800 A 242
KSA 400AE4 Flange feed unit 400 A 190, 238 KSA 800ET450 Transport length 5 m 800 A 242
KSA 400DLC40 Elbow 400 A 191, 237 KSA 800ET4AF Fire barrier length 800 A 241
KSA 400DLE40 Elbow 400 A 191, 237 KSA 800EV4203 Riser distribution length 2 m 3 tap-off 241
191, 237 outlets 800 A
KSA 400DLF40 Elbow 400 A
KSA 800EV4254 Riser distribution length 2,5 m 4 tap-off 241
KSA 400DTC40 Tee 400 A 191
outlets 800 A
KSA 400ED4081 Riser distribution length 0.8 m 1 tap-off 236
KSA 800FA4 2OG.6$DGDSWDWRU 199, 205
outlet 400 A
KSA 400ED4156 Straight distribution length 1.5 m 400 A 188
KSB
KSA 400ED4208 Straight distribution length 2 m 400 A 188
KSB 1000ZB1 Tap-off blanking plate 1000 A IP55 199, 205, 245
KSA 400ED4306 Straight distribution length 3 m 400 A 188
KSB 1000ZB2 6SULQNOHUSURR¿QJDFFHVVRU\ 199, 205, 245
KSA 400ED45010 Straight distribution length 5 m 400 A 188
KSB 1000ZF1 Fixing bracket 1000 A 195, 201
KSA 400ET430 Transport length 3 m 400 A 237
KSB 1000ZFKP1 Vertical pendant kit 1000A 198, 204
KSA 400ET450 Transport length 5 m 400 A 237
KSB 1000ZP1 Feed unit and jointing screws sealing kit 193, 199, 205,
KSA 400ET4A Made to measure length 400 A 190 240, 245
KSA 400ET4AF Fire barrier length 400 A 190, 236 KSB 1000ZP2 Tap-off outlet sealing kit 193, 199, 205,
KSA 400EV4203 Riser distribution length 2 m 3 tap-off 236 240, 245
outlets 400 A KSB 1000ZV1 Bottom support for riser 1000 A 244
KSA 400EV4254 Riser distribution length 2.5 m 4 tap-off 236 KSB 1000ZV2 Floor support 239, 244
outlets 400 A
KSB 1000ZV3 Floor support 239, 244
KSA 400FA4 2OG.6$DGDSWHU 193
KSB 100SE4 Tap-off unit 100 A fuse T00 214, 216
KSA 400ZJ4 Jointing device 400 A 193, 240
KSB 100SE5 Tap-off unit 100 A fuse T00 214, 216
KSA 500ED4306 Straight distribution length 3 m 500 A 194
KSB 100SF4 Tap-off unit 100 A fuse 22x58 213
KSA 500ED45010 Straight distribution length 5 m 500 A 194
KSB 100SF5 Tap-off unit 100 A fuse 22x58 213
KSA 500ET430 Transport length 3 m 500 A 242
KSB 100SM412 Tap-off unit 100 A 12 modules 206
KSA 500ET450 Transport length 5 m 500 A 242
KSB 100SM512 Tap-off unit 100 A 12 modules 206
KSA 500ET4AF Fire barrier length 500 A 241
KSB 160DC4 Tap-off unit 160 A Compact NSX 208
KSA 500EV4203 Riser distribution length2 m 3 tap-off 241
outlets 500 A KSB 160DC5 Tap-off unit 160 A Compact NSX 208
KSA 500EV4254 Riser distribution length 2,5 m 4 tap-off 241 KSB 160SE4 Tap-off unit 160 A fuse T00 214, 216
outlets 500 A
KSB 32SG4 Connector 32 A fuse BS88A1 217 PKY32F723 Industrial sockets 32 A, 200-250 V AC, 159, 207
2P + T, 90 x 100
KSB 400DC4 Tap-off unit 400 A Compact NSX 208
PKY32F725 Industrial sockets 32 A, 200-250 VAC, 159, 207
KSB 400DC4TRE Tap-off unit 400 A Compact NSX TRE 209 3P + N + T, 90 x 100
KSB 400DC5 Tap-off unit 400 A Compact NSX 208 PKY32F733 Industrial sockets 32 A, 380-415 VAC, 159, 207
209 2P + T, 90 x 100
KSB 400DC5TRE Tap-off unit 400 A Compact NSX TRE
214, 216 PKY32F735 Industrial sockets 32 A, 380-415 VAC, 159, 207
KSB 400SE4 Tap-off unit 400 A fuse T2
3P + N + T, 90 x 100
KSB 400SE5 Tap-off unit 400 A fuse T2 214, 216
A new path
for achieving your
electrical installations
Canalis is part of a comprehensive offer
Optimum system Decentralised electrical Decentralised electrical
of products that are perfectly coordinated
performance is ensured distribution with total distribution with total
to meet all medium and low voltage
by coordination between coordination perfectly coordination is the ideal
electrical distribution requirements. the protection circuit VDWLV¿HVDOO\RXU solution for a wide range
breakers and the busbar requirements in terms of of applications including
All of these products have been designed trunking used for safety, continuity of factories, warehouses,
to work together: electrical, mechanical decentralised distribution. service, upgradeability commercial premises and
and communication compatibility. and simplicity. laboratories.
6FKQHLGHU(OHFWULFRIIHUVGLIIHUHQWGLVWULEXWLRQV\VWHPVWR¿W\RXURSHUDWLQJQHHGV
Distribution systems
DD221021.eps
Centralised distribution
b For all continuous processes:
v cement plants
v oil and gas
v petrochemicals
v steel
v paper, etc.
b Centralised distribution offers:
v continuity of service
v combined distribution of power, control and monitoring circuits
v supervision, etc.
Our solutions:
b Prisma Plus and Okken switchboards.
Decentralised distribution
PD202044.eps
Our solutions:
b Prisma Plus switchboards
b Canalis busbar trunking.
Combined distribution
PD202155.eps
Our solutions:
b Prisma Plus and Okken switchboards
b Canalis busbar trunking.
Total coordination of the Schneider Electric system provides maximum safety of life
and property, continuity of service, upgradeability and ease of installation.
Total coordination is made easy by the tables in the “Selection Guide”. They help you
chose the right combination of circuit breakers and busbar trunking.
Product characteristics are checked by calculations and tests carried out in our
laboratories.
A competitive installation.
Simplicity, upgradeability, safety and continuity of service and operation.
Decentralised distribution
DB403456.eps
for small sites
Maximum power available throughout the
installation.
The main busbar trunking distributes the full power of
the source.
&RQWLQXLW\DQGÀH[LELOLW\
The large number of tap-off points makes it easy to
supply new loads.
Anyone can connect and disconnect loads quickly and
safely.
7KHVHDGGLWLRQVRUPRGL¿FDWLRQVDUHFDUULHGRXWZLWKRXW
shutting down the installation.
DB403457.eps
for large sites
The simplicity of decentralised distribution
systems
The distribution system can be designed without
detailed knowledge of load locations. Only the source
and load characteristics are needed.
Trunking is selected in advance with optimum results.
Easy upgrading
&DQDOLVFDQHDVLO\DGDSWWRLQVWDOODWLRQPRGL¿FDWLRQVRU
extensions. Simply move an existing tap-off unit or add
a new one at the desired location.
Total safety
Tap-units can be connected and disconnected without
de-energising the trunking.
Changes can therefore be made safely on live
installations:
b protection against direct contact
b mismatch prevention for tap-off units and automatic
compatibility between the performance levels of
tap-units equipped with circuit breakers and the
prospective short-circuit current at the point of
installation.
Halogen-sensitive applications
b Public buildings (infrastructures, hospitals, schools, etc.).
b %XLOGLQJVZLWKHYDFXDWLRQGLI¿FXOWLHVKLJKULVHVVKLSVHWFDQGVHUYLFHDFWLYLW\
buildings.
b Sensitive processes (production of electronic components, etc.).
Health
&DQDOLVUHGXFHVWKHULVNRIH[SRVXUHWRHOHFWURPDJQHWLF¿HOGV
DD205674_r.eps
$OOHOHFWULFDOFRQGXFWRUVJHQHUDWHPDJQHWLF¿HOGVSURSRUWLRQDOWRWKHGLVWDQFH
between them. The design of Canalis busbar trunking with tightly spaced conductors
LQDPHWDOHQFORVXUHKHOSVWRFRQVLGHUDEO\UHGXFHUDGLDWHGHOHFWURPDJQHWLF¿HOGV
7KHHOHFWURPDJQHWLF¿HOGFKDUDFWHULVWLFVRI&DQDOLVEXVEDUWUXQNLQJDUHZHOOGH¿QHG
and measurements show that they are far below potentially dangerous levels.
<RXZLOO¿QGWKHPDJQHWLFLQGXFWLRQYDOXHVRIRXUSURGXFWVRQWKH³&KDUDFWHULVWLFV´
pages.
Environment
Canalis is fully recyclable
DD205673_r.eps
Example:
34 m of Canalis KS 250 A trunking equipped with 14-pole 25 A feeders.
DD205656.eps
23 kg 1600 Joules
90 kg 2000 Joules
Conception Industrialisation
Recyclage Exploitation
Schneider Electric has employed all its expertise to optimize the energy
consumption of your electricity distribution system.
:LWK&DQDOLV.6UHGXFHWKH&22 impact of your system.
b Losses:
v &DQDOLV.6$N:KP
v 250 A cables: 5.7 kWh / 100 m
v Difference: 2.2 kWh / 100 m, i.e. for one year = 19272 kWh / year / 100 m.
b Discharge of CO2 / 100 m = 19272 x 0.64 (1) kg / kWh = 12.3 tonnes / year / 100 m.
b Saving achieved = 19272 x € 0.084 (2) = € 1619 / year / 100 m.
With Canalis KS, environmental conservation rhymes with energy savings.
)RUPRUHLQIRUPDWLRQWKHHQYLURQPHQWDOSUR¿OHRIWKH&DQDOLVUDQJHLVDYDLODEOHRQ
www.schneider-electric.com.
(1) CO2 emissions per kWh: 0.64 kg CO2 / kWh (source: International Energy Agency).
(2) Industrial cost of 1 kWh = € 0.084 (source: Eurostat, January 2006), for an annual consumption of 2000 MWh,
excluding VAT.
PD202216_r.eps
Run components
Degree of protection IP55
Number of circuits 1
Rating 20 A
Tap-off intervals 1200 - 1350 - 1500 - 2400 - 2700 - 3000 mm
Standard lengths 24 and 192 meters
Finish -
0D[LPXPGLVWDQFHEHWZHHQ¿[LQJSRLQWV 0.7 meter
Tap-off units
PD202225_r.eps
Rating 10 and 16 A
Option
-
-
:KHUHWR¿QGWKHSURGXFWV
Run components page 69
Feed components and end covers page 69
Fixing devices page 70
Tap-off units page 73
Accessories page 72
-
PD202219_r.eps
IP55 IP55
1 1 or 2
25 and 40 A 25 and 40 A
500 - 1000 - 1500 mm 500 and 1000 mm
2 and 3 meters 2 and 3 meters
White RAL 9003 White RAL 9003
3 meters 5 meters
PD202225_r.eps
PD202225_r.eps
10 and 16 A 10 and 16 A
PD202222_r.eps
Run components
Degree of protection IP55 IP55
Polarity 3L + N + PE 3L + N + PE
Rating 40, 63, 100 and 160 A 100, 160, 250, 400, 500, 630,
800 and 1000 A
Tap-off intervals 500 - 1000 - 1500 mm 500/1000 mm on each face
Standard lengths 3 meters 3 and 5 meters
Finish White RAL 9001 White RAL 9001
0D[LPXPGLVWDQFHEHWZHHQ¿[LQJSRLQWV 3 meters 3 and 5 meters
Tap-off units
PD202089-r.eps
PD202080-r.eps
Option
Remote control conductor Yes -
:KHUHWR¿QGWKHSURGXFWV
Run components page 150 page 188
Feed components and end covers page 151 page 189
Fixing devices page 151 page 189
Tap-off units page 156 page 206
Complementary products page 155 page 190
page 152 page 205 (TRE)
PD202343.eps
PD202223_r.eps
IP55 IP55
3L + N + PE 3L + PE ; 3L + N +PE ; 3L + N + oversized PE
100, 250, 400, 500, 630, 800 and 1000 A 800, 1000, 1250, 1350, 1600, 2000, 2500, 3200 and
4000 and 5000 A
500 mm 500 and 1000 mm
'H¿QHGE\WKHÀRRUSLWFK 2 and 4 meters
White RAL 9001 White RAL 9001
'HSHQGLQJRQWKHGLVWDQFHEHWZHHQÀRRUV 3 meters
PD202214-r.eps
PD202314.eps
25 to 400 A 25 to 400 A
- 400 to 1000 A
- -
In a garage
PD202017.eps
Characteristics of the garage:
b area 300 m2 (20 x 15 m)
b loads:
v 3 car lifts
v 1 compressor
v 1 wheel balancing machine
v portable tools
v ÀXRUHVFHQWOLJKWLQJ
DD210512.eps
In a plastics factory
PD202018.eps
)RURI¿FHOLJKWLQJVHH³&DQDOLVLQRI¿FHV´SDJH
DD210515.eps
Canalis products installed:
b for power distribution:
v (1.1$$UXQPORQJWRVXSSO\WKHEDWWHU\FKDUJHUV
v (2.1$$UXQPORQJWRVXSSO\WKHDXWRPDWLFGRRUV Prisma Plus System G electrical distribution switchboard
b for lighting:
v (3.1$UXQPORQJWRVXSSO\WKHOLJKWLQJFLUFXLWV
v (4.%$$UXQV[PORQJ[PORQJDQG[PORQJWRVXSSO\
ith few
(5.%/7[:OXPLQDLUHV Even w oints,
gp
lightin s is
)RURI¿FHOLJKWLQJVHH³&DQDOLVLQRI¿FHV´SDJH C ali
a n
titive.
compe
Canalis in a greenhouse
PD202021.eps
b area 15000 m2 (150 x 100 m)
b loads:
v lighting by 600 W horticultural lamps
v rolling shutters.
DD210517.eps
Canalis in a supermarket
)RUWKHRI¿FHOLJKWLQJVHH³&DQDOLVLQRI¿FHV´SDJH
,QDSDUWLWLRQHGRI¿FHDQRSHQSODQRI¿FH
PD202023.eps
&KDUDFWHULVWLFVRIWKHRI¿FH
b area 1000 m2 (40 x 25 m)
b loads:
v power: supply to power sockets and VDI network
v ÀXRUHVFHQWOLJKWLQJ[:
DD210519.eps
Canalis products installed: Prisma Plus System G electrical distribution switchboard.
b for power distribution:
(1.1$UXQVPORQJLQVWDOOHGDVIHHGHUVWRVXSSO\WKHOLJKWLQJFLUFXLWV
b for lighting:
asy
v (2.'3UXQVPORQJWRVXSSO\WKH[:OXPLQDLUHV s for e
Canali ut
v .%&VLQJOHVZLWFKXQLWVIRUWKHRI¿FHV la y o
V
v .%&WZRZD\VZLWFKXQLWIRUWKHPHHWLQJURRP FDWLRQ
PRGL¿
v 3 timer switch units for the entrance, washrooms and hall.
re
ity whe
Electric ed it.
you n e
WKHDSSOLFDWLRQ(FRQRPLFDODQGHDV\WRLQVWDOOWKH\DUHVHFXUHGWRIDOVHÀRRU
or false ceiling VDI supports.
7KUHHPHWUHORQJÀH[LEOHFRPSRQHQWVDUHDYDLODEOHIRUFKDQJHVLQGLUHFWLRQRUOHYHOV
and detours around large obstacles.
Flexible length.
DD202209.eps
Straight length.
DD205659_r.eps
Description
b /LJKWLQJGLVWULEXWLRQE\&DQDOLV.'3
b 'LVWULEXWLRQRISRZHUVRFNHWVE\&DQDOLV.'3ZLWK
earth-leakage protection located in the distribution
columns.
b All active VDI components are centralised in a patch
bay. 2. RJ45 connectors are pre-installed at regular
intervals (VDI interface points).
Advantages
b 2SHUDWLQJÀH[LELOLW\
b Major reduction in installation time. 1 Prisma Plus (System P) power distribution switchboard.
2 Patch bay (computers + VDI).
5 &DQDOLV.'3OLJKWLQJDQGSRZHUVRFNHWGLVWULEXWLRQ
6 Distribution column (earth-leakage protection + power sockets + VDI).
Fully-decentralised architecture
DD205662_r.eps
DD205661.eps
Description
b Electrical distribution decentralised in relay
enclosures 3 installed in false ceilings and supplied by
&DQDOLV.1
b VDI decentralised in the same enclosure 3
DQGVXSSOLHGE\RSWLFDO¿EUH
Advantages
b *UHDWO\VLPSOL¿HGLQVWDOODWLRQIHZHUFDEOHVDQG
cable trays
1 3ULVPD3OXV6\VWHP*SRZHUGLVWULEXWLRQVZLWFKERDUGIRUWKHHQWLUHÀRRU
b (DV\GLYLVLRQRIRI¿FHVSDFHEHWZHHQDQXPEHURI
users 2 3DWFKED\IRUWKHHQWLUHÀRRU
b WiFi & ToIP ready 3 5HOD\HQFORVXUHGHGLFDWHGWRDJLYHQVHFWRURQWKHÀRRUOLJKWLQJSRZHUDQG
b 0RGL¿FDWLRQRIWKHLQVWDOODWLRQFDQEHFDUULHGRXW active VDI component distribution).
locally, maximising continuity of service
4 &DQDOLV.1
b Major reduction in installation time
b Clear and organised layout 5 &DQDOLV.'3
b Easier maintenance. 6 Distribution column (earth-leakage protection + power sockets + VDI).
Index 3
Introduction 8
Design guide
6LPSOL¿HGGHVLJQJXLGHIRUOLJKWLQJGLVWULEXWLRQ
Lighting-technology review 30
Installation 34
Selection of Canalis busbar trunking 35
Determining the operational current 36
Overload protection 37
Short-circuit protection 39
Check on voltage drop 40
6LPSOL¿HGGHVLJQJXLGHIRUSRZHUGLVWULEXWLRQ
Power distribution via Canalis 42
6LPSOL¿HGGHVLJQJXLGH
Determining the degree of protection 44
Characteristics
Canalis KDP, 20 A 46
Busbar trunking for lighting and power socket distribution 46
Canalis KBA, 25 and 40 A 47
Busbar trunking for lighting and power socket distribution 47
KBL Industrial luminaires 48
Canalis KBB, 25 and 40 A 49
Busbar trunking for lighting and power socket distribution 49
KBC tap-off units, KDP connections 50
Canalis KN, 40 to 160 A 51
Busbar trunking for low-power distribution 51
Canalis KS, 100 to 1000 A 53
Busbar trunking for medium-power distribution 53
DD210496.eps
The table below sums up the essential characteristics of the main types of light
source.
Type of light source Colour Length of Power Luminous
temperature tubes (W) ÀX[/P
(°K) (m)
Incandescent 2800 to 3000 - 75 850
lamps - 150 2100
- 300 4750
- 750 13500
White industrial With starter 4250 to 4500 1.20 40 3200
ÀXRUHVFHQWWXEH 1.50 65 5100
1.50 80 5900
Instant start 4250 to 4500 1.20 40 2900
1.50 65 4800
2.40 105 8000
Mercury vapour With starter 3300 to 4300 - 125 6500
- 250 14000
- 400 24000
- 700 42000
- 1000 60000
WKHWRWDOOXPLQRXVÀX[LVVXI¿FLHQWVHHQH[WSDJH
Incorrect Correct
7RWDOOXPLQRXVÀX[
DD210499.eps
7KHWRWDOOXPLQRXVÀX[UHTXLUHGIRUWKHGHVLUHGLOOXPLQDQFHLQDURRPLVSURYLGHGE\
the equation below:
F7RWDOOXPLQRXVÀX[UHTXLUHGLQOXPHQV
(Lumen: quantity of light per second reaching the working plane).
E: Illuminance (in lux).
(1 lux = 1 lumen/m2).
S: Surface area of room (in m2).
d: Depreciation factor taking into account ageing of light sources and of the room (1.3
to 1.5).
u7KHZDOOVDQGFHLOLQJDEVRUEDSDUWRIWKHÀX[HPLWWHGE\WKHOLJKWVRXUFHV7KH
XWLOLVDWLRQIDFWRULVWKHUDWLREHWZHHQWKHOXPLQRXVÀX[UHDFKLQJWKHZRUNLQJSODQH
and that emitted by the lamps.
b It depends on:
v URRPSURSRUWLRQVDFFRUGLQJWRWKH.LQGH[
v UHÀHFWDQFHIDFWRUVRIWKHZDOOVDQGFHLOLQJ
v ÀX[GLVWULEXWLRQRIWKHOXPLQDLUHV
Selection of light sources taking into account the long daily use and the luminaire
installation height set at 5 metres.
Luminaires in photometric class E are selected (table B, page 31).
Distribution of luminaires
DD210500.eps
that we round to 4
*LYHQDUHÀHFWDQFHIDFWRURIIRUWKHFHLOLQJDQGIRUWKHZDOOVDQGWKHXVH
mercury-vapour lamps:
u = 0.73.
7RWDOOXPLQRXVÀX[
lumens
lumens
of luminaires
The table on page 30 allows you to choose 400 W (24 000 lumens) mercury-vapour
lamps which provide a lighting level of slightly above 250 lux.
Note: LIFKDQJHVLQZRUNVKRSOD\RXWUHTXLUHPRGL¿FDWLRQVLQWKHLOOXPLQDWLRQRQWKHZRUNLQJplane,
Canalis makes it easy to add or remove luminaires.
DD230311.eps
installation times. The busbar trunking:
It is the optimum solution for installations with false
cannot must carry a
FHLOLQJVRUÀRRUV support the number of must support the luminaires
luminaires circuits
.%$DQG.%%EXVEDUWUXQNLQJLVLGHDOZKHUHWKH
building structure cannot support the luminaires.
They offer an IP55 degree of protection which means 7KH¿[LQJGLVWDQFHEHWZHHQFHQWUHVLV
they can be installed in all types of buildings.
>3m y3m
Fixing distance
.%$DQG.%%EXVEDUWUXQNLQJ
DD205692.eps
7KH¿[LQJGLVWDQFHIRU.%$DQG.%%EXVEDUWUXQNLQJGHSHQGVRQWKHQXPEHUDQG
weight of the luminaires, as well as the building structure. The table below indicates
WKHPD[LPXPSHUPLVVLEOHORDGNJEHWZHHQWZR¿[LQJSRLQWVIRUDGHÀHFWLRQRI
,IWKHORDGLVFRQFHQWUDWHGEHWZHHQWZR¿[LQJSRLQWVPHUFXU\YDSRXUODPSV
DSSO\DFRHI¿FLHQWRIWRWKHYDOXHV
Maximum load
(kg)
Type of tap-offs Fixing
busbar distance (m) distance a (m)
trunking
2 2.5 3 3.5 4 4.5 5 5.5 6
.%$ 1 34 22 15 no load
0.5 29 19 13 no load
.%% 1 circuit 60 60 48 35 27 21 17 no load
2 circuits 60 51 41 30 23 18 17 no load
,QGXVWULDOUHÀHFWRUW\SHÀXRUHVFHQWOXPLQDLUHVZLWKRXWSURWHFWLRQJULOO
,QGXVWULDOUHÀHFWRUW\SHÀXRUHVFHQWOXPLQDLUHVZLWKSURWHFWLRQJULOO
'XVWDQGGDPSSURRILQGXVWULDOUHÀHFWRUW\SHÀXRUHVFHQWOXPLQDLUHV
Close together Far apart $FURVV¿[LQJSRLQW
DD205693.eps
Power Unit weight Possible spacing
(W) (kg) (metre)
Without With Dust and
protection gril protection gril damp-proof
KBA KBB KBA KBB KBA KBB
1 x 36 4.20 5.20 3.30 3.00 5.00 3.00 5.00 4.00 6.00
1 x 58 5.30 6.50 4.20 3.00 5.00 3.00 5.00 4.00 6.00
2 x 36 4.90 5.90 5.20 3.00 5.00 3.00 5.00 4.00 6.00
2 x 49 4.90 5.90 5.20 3.00 5.00 3.00 5.00 3.00 5.00
2 x 58 6.30 7.50 5.39 3.00 5.00 3.00 5.00 4.00 6.00
Mercury-vapour luminaires
%HWZHHQWZR¿[LQJSRLQWV 1H[WWRD¿[LQJSRLQW
DD205694.eps
The tables below show the operational current as a function of the type and number
DD205014.eps
Procedure:
b LGHQWLI\WKHW\SHRIOXPLQDLUHHJ[:FRPSHQVDWHGÀXRUHVFHQW
Ph + N distribution b on the corresponding line, select the number (or next highest) of installed
luminaires (e.g. 26 if there are 23 luminaires)
b at the bottom of the table, read the corresponding operational current (e.g. 20 A).
DD205015.eps
,QGXVWULDOUHÀHFWRUW\SHÀXRUHVFHQWOXPLQDLUHV
Type of ballast Power Number of luminaires on the line
(W) Single-phase line Three-phase + N line
Electronic 1 x 36 33 53 66 - - - 99 - - - - -
1 x 58 25 40 50 62 - - 75 - - - - -
2 x 36 21 33 42 52 67 - 63 99 - - - -
3Ph + N balanced distribution
2 x 49 20 32 40 50 64 80 80 96 120 - - -
2 x 58 13 20 26 32 41 52 39 60 78 96 - -
Ferro-magnetic 1 x 36 22 35 44 55 - - 66 105 - - - -
1 x 58 14 22 28 35 45 - 42 66 84 - - -
2 x 36 11 17 22 27 35 44 33 51 66 81 - -
2 x 58 7 11 14 17 22 28 21 33 42 51 66 84
Operational current (A) 10 16 20 25 32 40 10 16 20 25 32 40
Mercury-vapour luminaires
Type of ballast Power Number of luminaires on the line
(W) Single-phase line Three-phase + N line
Compensated 250 7 11 14 17 22 21 33 42 51 66
400 4 6 8 10 13 12 18 24 30 39
Non-compensated 250 4 7 9 11 14 12 21 27 33 42
400 3 4 6 7 9 9 12 18 21 27
Operational current (A) 10 16 20 25 (1) 32 16 20 25(1) 32
Type of busbar trunking 20 A KDP 40 A KBA 25 A KBA or 40 A KBA
25 A KBA or KBB or KBB KBB or KBB
(1) For this type of luminaire, for 25 A and higher, select a 40 A KBA or KBB to take into account
the overcurrent during starting.
Tap-off protection
Canalis tap-offs must have overload protection. The tap-off is created using a fused
tap-off unit to protect the cable (C3) and the device against short-circuits.
This protection offers good discrimination during operation (continuity of service,
trouble-shooting, etc.).
For lighting, it may be useful to take advantage of the possibilities for dispensing
with or remotely locating the protection, offered by standard IEC 60-364-4-43
(§ 433 and 434) and summarised in the texts below, drawn from UTE C 15-107.
The tap-off is created using a pre-wired tap-off unit.
The tables below determine, as a function of the type of overload protection (circuit
breaker or fuse):
b the type of busbar trunking required
b the size of supply cables (in mm2) as a function of the installation method, for all
FRQGXFWRUFRQ¿JXUDWLRQV
Protection by gG fuses
Type of busbar Rated XLPE cable PVC cable
trunking current Spaced Touching Spaced Touching
(A) (number of cables) (number of cables)
2 to 5 6 or 2 3 4 or
more more
$.'3 10 1.5 1.5 1.5 1.5 1.5 1.5 1.5
$.%$ 16 1.5 2.5 2.5 2.5 2.5 2.5 4
$.%%
1.5 (1)
20 2.5 2.5 2.5 2.5 4 4 6
1.5 (1)
$.%$ 25 2.5 4 6 4 6 6 6
$.%% 4 (1)
$.%$ 32 4 6 6 6 6 10 10
$.%% 2.5 (1) 4 (1)
(1) Permissible cable cross-sections for single-phase distribution.
DD210530.eps
Canalis
Cable &DQDOLV.1RU.6
Canalis
.'3.%$
RU.%%
% Un
DD205021.eps
% Un
% Un
b Convert into volts the % of the rated voltage (Un) assigned to each circuit.
b Using the tables, check that the trunking and/or cables selected in the previous
pages are compatible with the calculated voltage drops.
Otherwise, it is necessary to increase the size of the cables.
Remarks
b In a mixed circuit, the most economical option is to increase the size of cables and
avoid the use of prefabricated trunking with a higher rated current (Inc).
b For certain loads, it may be necessary to take into account transient voltage drops.
Voltage-drop conversion
Operational Voltage drop in volts for a given %
voltage (V) 0.3 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 6 7 8 9 10
230 0.7 1.2 2.3 3.5 4.6 5.8 6.9 8.1 9.2 10 12 14 16 18 21 23
400 1.2 2 4 6 8 10 12 14 16 18 20 24 28 32 36 40
Except for the most extreme environments, there is no The procedure presented below describes the steps in creating a simple installation.
reason to hesitate. Canalis can be installed For a detailed design study, it is necessary to use the suitable tools, approved by
everywhere. FHUWL¿FDWLRQRUJDQLVDWLRQVDQGLQFRPSOLDQFHZLWKORFDOLQVWDOODWLRQVWDQGDUGV
Ecodial software, published by Schneider Electric, is perfectly suited to the task.
Procedure
1 ,GHQWLI\H[WHUQDOLQÀXHQFHV
2 Layout the Canalis structure in the building according to the load locations.
3 Carry out a power sum.
4 Size the busbar trunking.
,GHQWLI\H[WHUQDOLQÀXHQFHV
The ambient temperature, the presence of dust or condensation, etc. are all factors
LQGH¿QLQJWKHGHJUHHRISURWHFWLRQIRUWKHURRPFRQWDLQLQJWKHHOHFWULFDOLQVWDOODWLRQ
Canalis prefabricated busbar trunking provides an IP55 degree of protection and can
be installed on virtually all sites.
b Examples:
v mechanical workshops: IP32
v warehouses: IP30
v poultry farms: IP35
v greenhouses: IP23
v ...
WUXQNLQJ¿[LQJSRVVLELOLWLHV
b A single distribution line can supply a zone four to six metres long.
b Load protection is located in the tap-off units, as close as possible to the loads.
b A single Canalis feeder can supply a set of loads with different power ratings.
3 - Power sum
Once the busbar trunking has been laid out, calculate the currents drawn by the
Canalis lines.
Calculation of the total operational current drawn by the line
(In) is equal to the sum of the currents drawn by the loads (Ib): In = 6 Ib.
The loads do not all operate at the same time or continuously at full rated load, i.e. it
LVQHFHVVDU\WRFDOFXODWHWKHGLYHUVLW\FRHI¿FLHQW.S): In = 6,E[.S).
'LYHUVLW\FRHI¿FLHQWDVDIXQFWLRQRIWKHQXPEHURIORDGV
Application Number of loads KSFRHI¿FLHQW
DD205295.eps
Lighting, heating - 1
Distribution 2...3 0.9
(Mechanical workshop) 4...5 0.8
6...9 0.7
10...40 0.6
40 or more 0.5
Caution. For industrial installations, remember to allow for changes in types and numbers of
PDFKLQHV6LPLODUWRDVZLWFKERDUGDPDUJLQRILVUHFRPPHQGHG
In = 6 Ib x KS x 1.2.
Voltage-drop criterion
The voltage drop between the head and any other point in the installation must not
exceed the values in the table below:
Installation supplied by a distribution network Lighting Other application
LV public system 3% 5%
High voltage 6% 8%
For Canalis, voltage drops are indicated in V/100 m/A in the “Characteristics”
section.
U = 6,E[.S) x L / 100
([DPSOH³&KDUDFWHULVWLFV´SDJHIRU.1WR$
For a cos M of Canalis KN
40 A 63 A 100 A 160 A
0,7 V/100 m/A 0.376 0.160 0.077 0.063
0,8 V/100 m/A 0.425 0.179 0.084 0.067
0,9 V/100 m/A 0.474 0.196 0.089 0.071
1 V/100 m/A 0,516 0.208 0.088 0.068
6WDQGDUG,(&FDWHJRULVHVDODUJHQXPEHURIH[WHUQDOLQÀXHQFHVWRZKLFK
electrical installations can be subjected, for instance the presence of water, solid
objects, shocks, vibrations and corrosive substances.
7KHLPSRUWDQFHRIWKHVHLQÀXHQFHVGHSHQGVRQWKHLQVWDOODWLRQFRQGLWLRQV
For example, the presence of water can vary from a few drops to total immersion.
Degree of protection IP Standard IEC 60529 (February 2001) indicates the degree of protection provided by
electrical equipment enclosures against accidental direct contact with live parts and
against the ingress of solid foreign objects or water.
This standard does not apply to protection against the risk of explosion or conditions
such as humidity, corrosive gases, fungi or vermin.
The IP code comprises 2 characteristic numerals and may include an additional letter
when the actual protection of persons against direct contact with live parts is better
WKDQWKDWLQGLFDWHGE\WKH¿UVWQXPHUDO
7KH¿UVWQXPHUDOFKDUDFWHULVHVWKHSURWHFWLRQRIWKHHTXLSPHQWDJDLQVWSHQHWUDWLRQ
of solid objects and the protection of people.
The second numeral characterises the protection of the equipment against
penetration of water with harmful effects.
b The degrees of protection indicated in this catalogue are valid for the enclosures
as presented. However, the indicated degree of protection is guaranteed only when
the installation and device mounting are carried out in accordance with professional
standard practice.
Additional letter
Protection of persons against direct contact with live parts.
The additional letter is used only if the actual protection of persons is higher than that
LQGLFDWHGE\WKH¿UVWFKDUDFWHULVWLFQXPHUDORIWKH,3FRGH
If only the protection of persons is of interest, the two characteristic numerals are
replaced by the letter “X”, e.g. IPXXB.
IK codepp
7KH,.FRGHFRPSULVHVFKDUDFWHULVWLFQXPHUDOVHJ,.
Practical guide UTE C 15-103 shows, in the form of tables, the characteristics
required for electrical equipment (including minimum degrees of protection),
according to the locations in which they are installed.
DD210014.eps
DD210006.eps
penetration of solid objects contact with the back of the dripping water
having a diameter greater than hand (accidental contact). 1 (condensation). 1
or equal to 50 mm.
Protected against the Protected against direct Protected against dripping
DD210531.eps
DD210007.eps
penetration of solid objects ¿QJHUFRQWDFW water at an angle of up to
having a diameter greater than 2 15°. 2
or equal to 12.5 mm.
Protected against the Protected against direct Protected against rain at an
DD210532.eps
DD210008.eps
penetration of solid objects contact angle of up to 60°.
having a diameter greater than with a 2.5 mm diameter tool. 3 3
or equal to 2.5 mm.
Protected against the Protected against direct Protected against splashing
DD210017.eps
DD210009.eps
penetration of solid objects contact with a 1 mm diameter water in all directions.
having a diameter greater than wire. 4 4
1 mm.
Dust protected Protected against direct Protected against water jets
DD210018.eps
DD210010.eps
(no harmful deposits). contact with a 1 mm diameter in all directions.
wire. 5 5
Dust tight. Protected against direct Protected against powerful
DD210019.eps
DD210011.eps
contact with a 1 mm diameter jets of water and waves.
wire. 6 6
Protected against the effects
DD210012.eps
of temporary immersion.
7
Protected against the effects
DD210013.eps
of prolonged immersion
XQGHUVSHFL¿HGFRQGLWLRQV 8
Additional letter
Corresponds to protection of persons against direct contact with A With the back of the hand.
live parts.
B :LWKWKH¿QJHU
C With a 2.5 mm diameter tool.
D With a 1.0 mm diameter tool.
00
01 0.20 7.50 0.15
02 10 0.20
03 17.50 0.35
04 25 0.50
05 35 0.70
06 0.50 20 1
07 40 2
08 1.70 30 5
09 5 20 10
10 40 20
DD205708.eps
Conductor characteristics
Phase conductors
Mean resistance at an ambient temperature of 20 °C R20 PȍP 6.80
Mean resistance at Inc and 35 °C R1 PȍP 8.30
Mean reactance at Inc, 35 °C and 50 Hz X1 PȍP 0.02
Mean impedance at Inc, 35 °C and 50 Hz Z1 PȍP 8.30
Protective conductor (PE)
Mean resistance at an ambient temperature of 20 °C PȍP 7.25
Other characteristics
Short-circuit withstand capacity
Rated peak withstand current Ipk kA 3.6
Maximum thermal limit I2t A2s 120 x 103
Rated short-time withstand current (t = 1 s) Icw kA 0.34
Voltage drop
Composite voltage drop (hot state) expressed in V/100 m/A (50 Hz) with the load uniformly
distributed over the run. If the load is concentrated at one end of the run, the voltage drop is
twice the value indicated in the table.
For a power factor of 1 V/100 m/A 0.72
0.9 V/100 m/A 0.65
0.8 V/100 m/A 0.58
0.7 V/100 m/A 0.50
This table is given for three-phases network. The single phase voltage drop is obtained by
dividing the three-phase voltage drop indicated above by 0.866
5DGLDWHGPDJQHWLF¿HOG
5DGLDWHGPDJQHWLF¿HOGVWUHQJWKPHWUHIURPWKHWUXQNLQJ B ȝ7 < 2 x 10-3
Product selection when harmonics are present (for details, see the “Special Applications” section)
Operational current as a function of 3rd-order harmonic content THD y 15 % 20
15 % < THD y 33 % 16
THD > 33 % 14
Permissible current as a function of ambient temperature
Ambient temperature °C < 35 35 40 45 50 55
&°I¿FLHQW. % n/a 1 0.93 0.85 0.76 0.66
or or
3L+N 3L+N
Ue = 230...400 V
RAL 9010 white
Luminaire characteristics
Type of luminaire KBL 258HF 249T5 280T5 258HFE 249T5E
General characteristics
Compliance with standards IEC/EN 60598-1
Degree of protection IP 20 20 20 55 55
Mechanical impacts ,. 07 07 07 10 10
(I¿FLHQF\ (1) K 0.72 0.72 0.85 0.58G + 0.79G +
0.07T 0.06T
Class E E C G G
Operating temperature °C 35 35 25 35 35
(1) G: Class of luminaires in direct lighting
T: Class of luminaires in indirect lighting
3KRWRPHWULFFKDUDFWHULVWLFVRIÀXRUHVFHQWWXEHV
DD210591.eps
DD210592.eps
DD210593.eps
DD210595.eps
Number of circuits 1 2 2 1 2 2
Rated current at an ambient temperature of 35 °C Inc A 25 25 25 40 40 38
Rated insulation voltage Ui V 690 690
Rated operational voltage Ue V 230...400 230...400
Rated impulse voltage Uimp kV 4 4
Rated frequency f Hz 50/60 50/60
Conductor characteristics
Phase conductors
Mean resistance at an ambient temperature of 20 °C R20 PȍP 6.80 2.83
Mean resistance at Inc and 35 °C R1 PȍP 8.30 3.46
Mean reactance at Inc, 35 °C and 50 Hz X1 PȍP 0.02 0.02
Mean impedance at Inc, 35 °C and 50 Hz Z1 PȍP 8.33 3.46
Protective conductor (PE)
Mean resistance at an ambient temperature of 20 °C PȍP 0.80 0.80
Fault loop characteristics
Symmetrical Ph/N Mean resistance R0 ph/N PȍP 27.21 17.28
components at 20 °C Mean reactance X0 ph/N PȍP 0.85 5.25
method
Mean impedance Z0 ph/N PȍP 27.22 18.06
Ph/PE Mean resistance R0 ph/PE PȍP 17.28 13.83
at 20 °C Mean reactance X0 ph/PE PȍP 5.25 0.73
Mean impedance Z0 ph/PE PȍP 18.06 13.85
Impedance At 20 °C Mean Ph/Ph Rb0 ph/ph PȍP 13.61 5.68
method resistance Ph/N Rb0 ph/N PȍP 13.61 5.68
Ph/PE Rb0 ph/PE PȍP 10.26 6.92
For Inc Mean Ph/Ph Rb1 ph/ph PȍP 16.59 6.92
at 35 °C resistance Ph/N Rb1 ph/N PȍP 16.59 6.92
Ph/PE Rb1 ph/PE PȍP 11.77 7.14
For Inc Mean reactance Ph/Ph Xb ph/ph PȍP 0.35 0.90
at 35 °C and Ph/N Xb ph/N PȍP 0.35 0.90
50 Hz
Ph/PE Xb ph/PE PȍP 0.07 1.85
Other characteristics
Short-circuit withstand capacity
Rated peak withstand current Ipk kA 4.40 9.60
Maximum thermal limit I2t A2 s 195 x 103 900 x 103
Rated short-time withstand current (t = 1 s) Icw kA 0.44 0.94
Voltage drop
Composite voltage drop (hot state) expressed in V/100 m/A (50 Hz) with the load uniformly
distributed over the run. If the load is concentrated at one end of the run, the voltage drop is
twice the value indicated in the table.
For a power factor of 1 V/100 m/A 0.72 0.30
0.9 V/100 m/A 0.67 0.28
0.8 V/100 m/A 0.61 0.25
0.7 V/100 m/A 0.55 0.22
5DGLDWHGPDJQHWLF¿HOG
5DGLDWHGPDJQHWLF¿HOGVWUHQJWKPHWUHIURPWKHWUXQNLQJ B ȝ7 < 2 x 10-3 < 2 x 10-3
Product selection when harmonics are present (for details, see the “Special Applications” section)
Operational current as a function of 3rd harmonic content THD y 15 % 25 40
15 % < THD y 33 % 20 32
THD > 33 % 16 28
Permissible current as a function of ambient temperature
Ambient temperature °C < 35 35 40 45 50 55
&°I¿FLHQW. % n/a 1 0.96 0.93 0.89 0.85
Tap-off unit characteristics
6HH.%&WDSRIIXQLWFKDUDFWHULVWLFVRQSDJH
Schneider Electric offers comprehensive software to CanBrass software, from Schneider Electric, has been developed to accompany
help you design Canalis installations and prepare you when designing and preparing quotations for Canalis busbar trunking
quotations. installations.
CanBrass, a comprehensive tool CanBrass software helps you rapidly design the best installation for your project. It
lets you:
CanBrass brings you all the help you need. b easily choose the right products,
b compare the busbar trunking solution with an equivalent cable-based solution,
PD202231_r.eps
The software breaks the project down into quantities for the different product
IXQFWLRQV¿[LQJVVWUDLJKWOHQJWKVHWF
PD202128_r.eps
$IWHUFRQ¿UPLQJWKHEUHDNGRZQRIWKHOLQHWKHXVHUDFFHVVHVWKHFRVWLQJWDEOH
PD202129_r.eps
Breakdown of the line into
catalogue numbers with price
calculations and estimation of
the time required for
installation.
Comparaison of a Canalis
lighting installation and an
equivalent cable-based
solution.
PD202132_r.eps
Index 3
Introduction 8
Design guides and characteristics 29
Presentation
Canalis KDP 58
For lighting and power socket distribution 58
Description
Canalis KDP, 20 A 62
Busbar trunking for lighting and power socket distribution 62
Canalis KDP, KBA and KBB 64
Busbar trunking for lighting and power socket distribution 64
Tap-off units 64
Canalis KDP, 20 A 66
Busbar trunking for lighting and power socket distribution 66
Tap-off units 66
Radio frequency tap-off unit 67
Prefabricated connections 68
Installation
Canalis KDP, 20 A 78
Busbar trunking for lighting and power socket distribution 78
Installation scenario 78
Assembly of trunking components 80
PD202157.eps
PD202161.eps
PD202159.eps
PD202160.eps
DD205717.eps
smoke or toxic gases.
DD202141.eps
PD202162.eps
DD205718.eps
Remarkably compact
7KHFRPSDFWGHVLJQRI&DQDOLV.'3HQVXUHVHDV\
PRXQWLQJLQIDOVHÀRRUVRUFHLOLQJV
DD205719.eps
DD202142.eps
DD205720.eps
,QWKHHYHQWRID¿UHFDEOHDQGFRQGXFWRULQVXODWLRQFRQWDLQLQJKDORJHQVFKORULQH
bromine, etc.) releases dark, toxic and corrosive smoke. The latter can cause panic,
GLI¿FXOWLHVIRUUHVFXHWHDPVLQWR[LFDWLRQDQGVHYHUHGDPDJHWRHOHFWURQLFDQG
computer equipment.
KDP trunking, halogen free, avoids the above risks.
Run components
&DUU\WKHFXUUHQWDQGVXSSO\OLJKWLQJ¿[WXUHV
The run components consist of:
DD210155.eps
$OOWKHLQVXODWLQJDQGSODVWLFPDWHULDOVKDYHLQFUHDVHG¿UHUHWDUGDQWFDSDFLW\
b incandescent-wire test in compliance with IEC 60695-2:
v 960 °C for components in contact with live parts,
v 650 °C for other components.
.'3LVFHUWL¿HGWREHQRQÀDPHSURSDJDWLQJLQFRPSOLDQFHZLWKVWDQGDUG
IEC 60332-3.
The system as a whole complies with standard IEC 60439-2.
$IWHUVWULSSLQJWKH.'3FDEOHWKHFRQQHFWLRQLVPDGHE\PHDQVRIDVFUHZWHUPLQDO
for copper cable with a maximum c.s.a. of 4 mm2.
7KHVHFRPSRQHQWVDUH¿WWHGZLWKD3*FDEOHJODQG7KH\DUHORFNHGLQWKHFORVHG
position by a screw.
7KH\FDQEHXVHGWRVXSSO\WKHUXQIURPHLWKHUVLGHDQGIRUFRQQHFWLQJWZR.'3UXQV
Each feed unit is supplied with an end cover for the opposite end of the run.
The system as a whole complies with standard IEC 60439-2.
DD210154.eps
Uncoiler kit
0DNHVIRUHDV\LQVWDOODWLRQRI.'3WUXQNLQJE\DOORZLQJWKHFDEOHWREHUROOHGRXWfrom
the reel.
It can be used with all standard roller-type uncoilers.
It clips onto the packing spools and can be removed for re-use.
1 Uncoiler kit (8 parts)
2 Packing spools.
3 Cable uncoiler (not supplied).
Fixing systems
7KHVHV\VWHPVDUHXVHGWR¿[.'3LQDFFRUGDQFHZLWKUHFRPPHQGHGLQVWDOODWLRQ
methods.
DD205728.eps
Stripping tool
DD210132.eps
8VHGWRFXWUHPRYHWKHVKHDWKDQGVWULS.'3RUFRQGXFWRUFDEOHV
3UHZLUHG$WDSRIIXQLWZLWK¿[HGSRODULW\
DD205733.eps
Pre-wired with SO5Z1Z1-F 3 x 1.5 mm2 cable, 0.80 m long, pre-stripped on luminaire
end:
b 10 A rating
b ¿[HG/13(SRODULW\
b the various models make it possible to balance 3-phase distribution systems.
7KHFRORXURIWKHORFNDQGWKHFDVLQJHQDEOHUHPRWHLGHQWL¿FDWLRQRIWKHSRODULW\
1 Live-conductor contacts.
2 Protective-conductor contact.
3 Lock.
If prefabricated leads are used, the line must have 16 A protection (see possibilities
RIGLVSHQVLQJZLWKSURWHFWLRQLQWKHVLPSOL¿HGGHVLJQJXLGHIRUOLJKWLQJGLVWULEXWLRQ
in the section on protection against overloads).
)RUFRQQHFWLRQRIOXPLQDLUHVXVLQJDFDEOHRIVSHFL¿FW\SHVL]HDQGOHQJWK
Accessories
DD205737.eps
6SHFL¿FWR.%&'&)WDSRIIXQLWV
1 Additional remote-control contact block
b )RUWDSRIIRIWKHUHPRWHFRQWUROFLUFXLWWRWKHOXPLQDLUH.%%DQG.%$OLQHVZLWK7
option).
b &OLSVRQWR.%&'&%RU&)H[FHSW.%&'&)WDSRIIXQLWV
b Terminals for data cable, max. size 2 X 0.75 mm2.
b Supplied with cable bushing.
DD205784.eps
Other accessories
3 Interlocking device
For all 10 A and 16 A tap-off units.
DD206064.eps
7KHVHXQLWVFDQDOVREHFRQQHFWHGWR.%$DQG.%%EXVEDUWUXQNLQJ
DD210078.eps
)RUZLUHOHVVFRQWURODQGVXSSO\LQJRIOLJKW¿WWLQJVLQSDUWLWLRQHGVLWHV
Used to open and close a lighting circuit controlled by 1 to 32 switches maximum
from the Alvaïs RF range.
b Rating 6 A.
b Phase selection system ensuring balancing on three-phase distributions.
b The two studs are mobile, allowing both L+N+PE and 2L + PE distribution.
b Supplied with cable gland.
If prefabricated connections are used, you need to protect the entire line at 16 A (see
WKHSURWHFWLRQZDLYHUFDVHVVHH³6LPSOL¿HGVWXG\JXLGHIRUOLJKWLQJGLVWULEXWLRQ±
Overload protection”).
7KHVHFRQQHFWRUVFDQDOVREHPRXQWHGRQ.%$DQG.%%EXVEDUWUXQNLQJV
Prefabricated connections
7RVXSSO\VHYHUDOOXPLQDLUHVIURPWKHVDPH.%&WDSRIIXQLWIRUGLVWULEXWLRQLQIDOVH
ceilings.
DD210159.eps
Prefabricated lead
b Male-female extension lead KBZ 31EFMppp.
Cable type SO5Z1Z1-F 3 X 1.5 mm2, available in 2, 3, 4, 5, 7 and 9 metre lengths.
KBZ 31EFMppp
DD210161.eps
KBZ 31EMCppp
DD210160.eps
KBZ 31EFCppp
DD210165.eps
Connectors
b Female connector KBZ 32APFR2.
Spring connection for 2 rigid cables 3 x 1.5 to 2.5 mm2 or 2 stranded cables 3 x 1.5
to 2.5 mm2¿WWHGZLWKIHUUXOHV
KBZ 32APFR2
DD210166.eps
KBZ 32APMR2
DD210162.eps
DD210163.eps
Splitter block
b Splitter block, 2 outlets KBZ 32DBA12.
One male input and two female outputs for connection to a pre-wired luminaire.
Lock
b Lock KBZ 30ZVP01 for extension leads.
Can withstand pulling forces greater than 20 N on the leads.
KBZ 30ZVP01
Run components
DD210087.eps
KDP 20Eppppp
DD210023.eps
KDP20Epp024p KDP20Epp192p
DD210065.eps
DD210027.eps
KDP 20ABG4
7KHHQGFRYHU.'3LVDVSDUHSDUW
of the after-sales service
ref KDP 20AF
Fixing systems
DD206065.eps
KDP ZF10 KDP ZF11 KDP ZF12 KDP ZF13 KDP ZF14
DD206066.eps
Prefabricated connections
Connection leads
DD210138.eps
KBZ 31EMC10
DD210061.eps
KBZ 31EFM0p0
DD210060.eps
Connection accessories
DD210140.eps
DD210064.eps
KBZ 32DBA15
DD210134.eps
DD210059.eps
KBZ 32APMR2
DD210142.eps
KBZ 32ZVP01
Accessories
For tap-off units
DD210085.eps
KBC 16ZLpp
Spare parts
DD210131.eps
KBC 16ZB
Accessories
DD210129.eps
KDP ZF31
DD210058.eps
KDP ZF31
DD210121.eps
DD210051.eps
KBC 10DCS301
DD210126.eps
DD210121.eps
DD210128.eps
L2 + N2 or L3 + N3
DD210126.eps
DD210121.eps
DD210128.eps
L2 + N2 or L3 + N3
Yes (1) 10 KBC 10DCC21Z 0.165
10 A tap-off unit, 3L + N + PE
Type of busbar trunking Polarity Order in Cat. no. Weight
multiples of (kg)
7REHGH¿QHGIRUHDFKDSSOLFDWLRQ 10 KBC 10DCB40 0.065
(dimmer, emergency lighting, etc.)
DD210112.eps
DD210126.eps
DD210121.eps
DD210124.eps
(1) For IP, see Canalis KDP, KBA and KBB Tap-off units description page 64.
DD210151.eps
or
DD205739.eps
DD210126.eps
DD210121.eps
L2 + N
or
L3 + N
DD210153.eps
Single- Balancing on 3 fuse
circuit phases or NF 8.5 x 31.5
KBC 16DCB2p
switching 3-circuit 16 A gG
switching maximum
(not supplied)
DD210145.eps
or
DD205740.eps
DD210123.eps
L1 + L3
or
L2 + L3
Balancing on fuse
3 phases without NF 8.5 x 31.5
KBC 16DCp22
neutral 16 A gG
maximum
(not supplied)
DD210128.eps
2 single-phase fuse
circuits NF 8.5 x 31.5
KBC 16DCp2pp6
16 A gG
maximum
(not supplied)
L3 + N3 None Blue 10 KBC 16DCB216 0.090
DD210149.eps
fuse
NF 8.5 x 31.5
16 A gG
maximum
(not supplied)
DD210144.eps
DD210119.eps
DD210121.eps
DD210143.eps
All types possible NF 8.5 x 31.5
12 A gG
KBC 16DCp40
maximum
(not supplied)
KBC 16DCp40
DD210054.eps
2P + E NF 8.5 x 31.5
DD210120.eps
DD210121.eps
10/16 A, 250 V 16 A gG
maximum
(not supplied)
KBC 16DCPp
DD210055.eps
DD210121.eps
DD210128.eps
L3 + N or
Double-circuit switching 10 KBC 10DDA20 0.085
L1 + L2 or
L1 + L3 or
L2 + L3 or Two-way switching 10 KBC 10DVV20 0.085
L2 + N2 or
L3 + N3
Timer or impulse switch 10 KBC 10DMT20 0.085
KBC 10Dpp20
KBC 10Dpp20
DD210057.eps
DD210121.eps
DD210128.eps
L3 + N or
Double-circuit 0.5 6 KBC 10DDA21Z 0.085
L1 + L2 or
switching (1)
L1 + L3 or
L2 + L3 or Two-way 0.5 6 KBC 10DVV21Z 0.085
L2 + N2 or switching (1)
L3 + N3
Timer or impulse 0.5 6 KBC 10DMT21Z 0.085
switch (1)
KBC 10Dpp21Z
KBC 10Dpp21Z
DD210056.eps
(1) For IP, see KDP, KBA and KBB Tap-off units description page 64.
L2 + N2 or L3 + N3
yes(1) KBC 06DCERFZ 0,300
Single circuit-switching
DD210121.eps
Installation of a line
DD210319_r.eps
DD210320_r.eps
Unload and carry the products inside to an area where
they are not exposed to dust or inclement weather.
DD210321_r.eps
DD210322_r.eps
0RXQW&DQDOLV.'3LQWKHIDOVHFHLOLQJ,QDQHZ
LQVWDOODWLRQLWLVDGYLVHGWRLQVWDOO&DQDOLV.'3EHIRUH
the false ceiling.
DD210323_r.eps
$WWDFK&DQDOLV.'3WRWKHFDEOHWUD\XVLQJWKH¿[LQJV
7KHUHDUHRWKHUW\SHVRI¿[LQJVVSHFL¿FDOO\GHVLJQHG
IRUWKHVWUXFWXUHRQZKLFK&DQDOLV.'3LVLQVWDOOHG
b metal structure,
b wooden structure,
b concrete slab.
<RXZLOODOVR¿QGDUDQJHRIDFFHVVRULHVWRVXSSRUWDOO
the cables associated with your installation.
DD210328_r.eps
Prepare the luminaires.
Connection of the tap-off units to the luminaires and
phase selection are carried out on the ground.
These operations can also be carried out in the
workshop, before delivery to the site.
DD210324_r.eps
8VLQJ.'3FRQQHFWLRQVEHWZHHQWZRDQG¿YH
luminaires can be connected to a single tap-off unit
(bridge or star connection).
DD210327_r.eps
IP55
Busbar trunking for lighting and
Ue = 230...400 V power socket distribution
Assembly of trunking components
DD210330.eps
DD210534.eps
DD210332.eps
DD210334.eps
DD210335.eps
DD210336.eps
DD210337.eps
DD210338.eps
DD210339.eps
DD210340.eps
Mounting on mesh trays
DD210341.eps
IP55
Busbar trunking for lighting and
Ue = 230...400 V power socket distribution
Assembly of trunking components
Solution 1 Solution 1
Pre-wired tap-off unit equipped with female Male/female lead for luminaires equipped with
GST18i3 connector. a GST18i3 connection.
Solution 2 Solution 2
Tap-off unit to be wired plus female lead with Male lead with end stripped for connection to
end stripped. a luminaire.
Solution 3 Solution 3
Tap-off unit to be wired plus female GST18i3 Male plus female connectors to be wired
connector (cable not supplied). (cable not supplied).
Solution 1
Male/female lead for luminaires equipped with
a GST18i3 connection.
Solution 2
Male lead with end stripped for connection to
a luminaire.
Solution 3
Male connector to be wired
(cable not supplied).
Index 3
Introduction 8
Design guides and characteristics 29
Canalis KDP 57
Presentation
Canalis KBA 86
For lighting and power socket distribution 86
Description
Canalis KBA, 25 and 40 A 90
Busbar trunking for lighting and power socket distribution 90
KBL Industrial luminaires 93
)RU&DQDOLV.%$
Canalis KDP, KBA and KBB 94
Busbar trunking for lighting and power socket distribution 94
Tap-off units 94
Installation
Canalis KBA, 25 and 40 A 106
Busbar trunking for lighting and power socket distribution 106
Installation scenario 106
Assembly of trunking components 110
PD202164R.eps
DD205760R.eps
PD202167.eps
PD202439.eps
PD202165.eps
DD202141_r.eps
Ready-to-install 1RWR[LFHPLVVLRQLQFDVHRI¿UH
luminaires $OOFRPSRQHQWVLQWKH.%$UDQJHDUH
&DQDOLV.%/OXPLQDLUHV halogen free.
have been designed for ,QFDVHRI¿UH&DQDOLV.%$GRHVQRWUHOHDVHVPRNHRU
HDV\LQVWDOODWLRQRQ.%$ toxic gases.
trunking.
With just a few catalogue
numbers, you have a
complete range of
luminaires suited to all
types of buildings.
PD202169R.eps
mounting
&DQDOLV.%$FRPSRQHQWV
can be assembled in just
a few clicks.
7KHKLJKGHJUHHRISURWHFWLRQIRU&DQDOLV.%$PHDQVLW
can be installed in all types of buildings.
Run components
Carry current, support and supply the luminaires.
Straight lengths
DD210476_r.eps
Straight lengths constitute the basic structure of the line and are made up of:
1 an all-in-one carrier casing, crimp closed, forming a rigid beam made of sheet
steel, in RAL 9003 white lacquered sheet steel, hot galvanised on both sides. This
casing also acts as the protective earth conductor (PE),
2 a ribbon cable with two or four copper conductors,
3 RQHWZRWKUHHRU¿YHWDSRIIRXWOHWV
4 an electrical jointing unit ensuring automatic and simultaneous connection of all
live conductors,
5 a mechanical joining device made of galvanised sheet steel that makes the
connection of two lengths rigid and resistant to bending.
7KHEXVEDUWUXQNLQJLVQRQÀDPHSURSDJDWLQJDVSHUWKHUHFRPPHQGDWLRQVRI
standard IEC 60332-3. All the insulating and plastic materials are halogen-free and
KDYHHQKDQFHG¿UHZLWKVWDQGFDSDELOLWLHVLQFDQGHVFHQWZLUHWHVWDVSHUVWDQGDUG
IEC 60695-2).
b 960°C for components in contact with live parts.
b 650°C for other components.
DD205805.eps
For changes in direction or levels and detours around
obstacles.
It is mounted in the same way as a straight length.
DD205806.eps
Fixing systems
Busbar trunking
DD205824_r.eps
1 8QLYHUVDO¿[LQJEUDFNHWEUDFNHW
For suspension on a threaded rod, diameter 6 mm.
For horizontal mounting on a beam, pendant, wall,
etc.
2 Cable suspension system
&XWVPRXQWLQJWLPHRIWKH¿[LQJV\VWHPWRRQHWKLUG
of that required for threaded rods.
Enables height adjustment of the trunking.
3 Adjustable, threaded-rod suspension system
For suspension on a threaded rod, diameter 6 mm.
A spring system locks the threaded rod in position
for fast adjustment of the trunking.
DD206072.eps
4 Pigtail hook
For suspension by a chain.
5 Closed ring
For suspension by a steel cable.
Luminaires
Attached to the luminaires before mounting, these
¿[LQJVHQVXUHIDVWDQGGLUHFW¿[LQJWR&DQDOLV.%$
b 6DPHFDWDORJXHQXPEHUVDVWKHEXVEDU¿[LQJV
b Automatic locking of moving part on closing.
b Use with an open hook and/or closed ring enables
suspension.
Cable support
For running adjacent circuits such as emergency
DD210482_r.eps
lighting, low-current circuits, etc.
1 Cable brackets
Clips to trunking for fast mounting. It is possible to
run three cables (diameter 5 to 16 mm) and two
IRL tubes.
2 Cable duct
7KHFDEOHGXFW¿WVRQVXSSRUW.%%=)*ZKLFK
LQWXUQ¿WVRQWRDWKUHDGHGURGVXVSHQVLRQV\VWHP
.%$=)38$QLQWHUPHGLDWHVXSSRUWLVSODFHG
between the duct and the trunking if the distance
between the suspension points exceeds 2 metres.
Each duct is equipped with a connection device.
Options
Empty length (no electric circuit)
DD210483.eps
DD210485_r.eps
,QGXVWULDOÀXRUHVFHQWOXPLQDLUHVDUHGHVLJQHGIRU
industrial buildings of low to medium height.
They are supplied:
b premounted
b SUHZLUHGZLWKD.%&'&%WDSRIIXQLWDQGRQH
metre of SO5Z1Z1-F 3G1.5 cable
b SUHHTXLSSHGZLWKWZR.%$=)8¿[LQJV
,3KLJKLQWHQVLW\ÀXRUHVFHQW
DD210486.eps
luminaires
+LJKLQWHQVLW\LQGXVWULDOÀXRUHVFHQWOXPLQDLUHVDUH
designed for industrial buildings with high ceilings.
They may be equipped exclusively with 80 W T5 tubes
(diameter 16 mm) and an electonic ballast (HF), dual
2 x 80 W version.
3UHZLUHG$WDSRIIXQLWZLWK¿[HGSRODULW\
DD205808_r.eps
Pre-wired with SO5Z1Z1-F 3 x 1.5 mm2 cable, 0.80 m long, pre-stripped on luminaire
end:
b 10 A rating,
b ¿[HG/13(SRODULW\
b the various models make it possible to balance 3-phase distribution systems.
7KHFRORXURIWKHORFNDQGWKHFDVLQJHQDEOHUHPRWHLGHQWL¿FDWLRQRIWKHSRODULW\
1 Live-conductor contacts.
2 Protective-conductor contact.
3 Lock.
If prefabricated leads are used, the line must have 16 A protection (see possibilities
RIGLVSHQVLQJZLWKSURWHFWLRQLQWKHVLPSOL¿HGGHVLJQJXLGHIRUOLJKWLQJGLVWULEXWLRQ
in the section on protection against overloads).
Accessories
DD205811_r.eps
6SHFL¿FWR.%&'&)WDSRIIXQLWV
1 Additional remote-control contact block
b )RUWDSRIIRIWKHUHPRWHFRQWUROFLUFXLWWRWKHOXPLQDLUH.%$DQG.%%OLQHVZLWK7
option).
b &OLSVRQWR.%&'&%RU&)H[FHSW.%&'&)WDSRIIXQLWV
b Terminals for data cable, max. size 2 X 0.75 mm2.
b Supplied with cable bushing.
DD205812_r.eps
Other accessories
3 Interlocking device
For all 10 A and 16 A tap-off units.
DD206073_r.eps
Straight lengths
DD205822.eps
KBA ppEDpppW Type of Trunking Length Number Order in 25 A rating Weight 40 A rating Weight Option (2)
component polarity (m) of multiples Cat. no. (kg) Cat. no. (kg) T
tap-offs of (1)
Straight length 3 0 6 KBA 25ED2300W 2.400 KBA 40ED2300W 2.700 -
DD210095.eps
KBA ppEDp300W
DB403706.eps
KBA ppEDp302W
KBA ppEDp303W
KBA ppEDp305W
KBA ppEDp202W
DB403707.eps
KBA ppEDp203W
Designation Rating Mounting Cable connection Cat. no. Weight Option (1)
(A) Terminals Cable gland (kg) T
(mm2) max. Ø (mm)
Feed unit 25 Left 4 PG 16, Ø 15 KBA 25ABG4W 0.200 -
25 or 40 Left 10 PG 21, Ø 19 KBA 40ABG4W 0.400 b
25 or 40 Central 10 PG 21, Ø 19 KBA 40ABT4W 0.500 b
25 or 40 Right 10 PG 21, Ø 19 KBA 40ABD4W 0.500 b
KBA 25ABG4W (1) b Option T may be combined. Add T at the catalogue number. Ex: KBA 40ABG4TW.
7KHHQGFRYHU.%$LVDVSDUHSDUWRIWKHDIWHUVDOHVVHUYLFHUHIKBA 40AF
DD205831.eps
DB403889.eps
Flexible lengths
DD205815.eps
KBA 40DF4ppW
Designation Mounting Length Cat. no. Weight Option (1)
(m) (kg) T
Flexible length For elbows, changing levels, 0.5 KBA 40DF405W 0.050 b
detours around obstacles, etc. 2 KBA 40DF420W 0.105 b
(1) b Option T may be combined. Add T at the catalogue number. Ex: KBA 40DF405TW.
KBA 40DF405W
DD206074.eps
KBA 40DF420W
DD206075.eps
Fixing systems
%XVEDUWUXQNLQJ¿[LQJV
DD205834.eps
DD205835.eps
DD205837.eps
DD205838.eps
DD210049.eps
DD210104.eps
KBB 40ZFMP
DD210050.eps
KBA 40ZFPU
/XPLQDLUH¿[LQJV
DD205834.eps
DD205816.eps
DD210041.eps
DD210040.eps
DD210589.eps
DD202294.eps
DD210590.eps
DD210029.eps
KBB 40ZFG1 KBA 40ZFG2
DD210111.eps
KBB 40ZFGU
Other accessories
DD210085.eps
KBC 16ZB1
,3LQGXVWULDOOXPLQDLUHVIRU77ÀXRUHVFHQWWXEHVQRWVXSSOLHG
DD210207.eps
Cotes A B
.%/+) 1526 1375
.%/7 1475 1325
DD210208.eps
KBL 280T5
DD210210.eps
DD210121.eps
DD210051.eps
KBC 10DCS301
DD210126.eps
DD210121.eps
DD210128.eps
L2 + N2 or L3 + N3
DD210126.eps
DD210121.eps
DD210128.eps
L2 + N2 or L3 + N3
Yes(1) 10 KBC 10DCC21Z 0.165
10 A tap-off unit, 3L + N + PE
Type of busbar trunking Polarity Order in Cat. no. Weight
multiples of (kg)
7REHGH¿QHGIRUHDFKDSSOLFDWLRQ 10 KBC 10DCB40 0.065
(dimmer, emergency lighting, etc.)
DD210112.eps
DD210126.eps
DD210121.eps
DD210124.eps
(1) For IP, see KDP, KBA and KBB Tap-off units description page 94
DD210151.eps
or
DD205820.eps
DD210126.eps
DD210121.eps
L2 + N
or
L3 + N
DD210153.eps
Single- Balancing on 3 fuse
KBC 16DCB2p circuit phases or NF 8.5 x 31.5
switching 3-circuit 16 A gG
switching maximum
(not supplied)
DD210145.eps
or
DD205821.eps
DD210123.eps
L1 + L3
or
L2 + L3
Balancing on fuse
KBC 16DCp22 3 phases without NF 8.5 x 31.5
neutral 16 A gG
maximum
(not supplied)
DD210126.eps
2 single-phase fuse
KBC 16DCp2pp6 circuits NF 8.5 x 31.5
16 A gG
maximum
(not supplied)
L3 + N3 None Blue 10 KBC 16DCB216 0.090
DD210149.eps
fuse
NF 8.5 x 31.5
16 A gG
maximum
(not supplied)
DD210144.eps
DD210119.eps
DD210121.eps
DD210143.eps
KBC 16DCp40 All types possible NF 8.5 x 31.5
12 A gG
maximum
(not supplied)
KBC 16DCp40
DD210054.eps
2P + E NF 8.5 x 31.5
DD210120.eps
DD210121.eps
10/16 A, 250 V 16 A gG
maximum
(not supplied)
KBC 16DCPp
DD210055.eps
Rear support bracket For securing 16 A single-phase tap-off units to 10 KBC 16ZC1 0.020
KBC 16ZT1 the trunking
DD205823.eps
KBC 16ZC1
Installation of a line
DD210348_r.eps
Unload and carry the products inside to an area where
they are not exposed to dust or inclement weather.
DD210349_r.eps
8QSDFNDQGOD\RXWRQWKHÀRRUWKHWUXQNLQJ
components required to mount the line.
Make sure that the feed unit is on the end closest to the
switchboard.
DD210350_r.eps
DD210644_r.eps
3UHSDUDWLRQRI¿[LQJV
,QWKLVFDWDORJXH\RXZLOO¿QGDQXPEHURI¿[LQJV
suited to different building structures.
<RXZLOODOVR¿QGDUDQJHRIDFFHVVRULHVWRVXSSRUWDOO
the cables associated with your installation.
DD210351_r.eps
DD210645_r.eps
DD210353_r.eps
DD210354_r.eps
3RVLWLRQWKHOLQHVHJPHQWLQWKH¿[LQJEUDFNHWV7KH\
are designed to immediately relieve the installer of the
weight. The busbar trunking is held in place as soon as
WKH.%$OHQJWKVDUHSRVLWLRQHGLQWKHEUDFNHWV
DD210646_r.eps
IP55
Busbar trunking for lighting and
Ue = 230...400 V power socket distribution
RAL 9003 white Installation scenario
DD210356_r.eps
The following segments can be mounted effortlessly,
due to the ease of assembling the mechanical and
electrical connections.
DD210357_r.eps
Tap-off connections
DD210358_r.eps
,QWKLVFDWDORJXH\RXZLOO¿QGUHDG\WRXVHOXPLQDLUHV
They are supplied prewired, equipped with a tap-off
unit with phase-selection.
DD210359_r.eps
DD210647_r.eps
2QFHDJDLQWKH¿[LQJEUDFNHWVDUHGHVLJQHGWR
immediately relieve the installer of the weight. The
luminaire is held in place as soon as the bracket is
placed on the trunking.
DD210361_r.eps
DD210648_r.eps
The brackets lock when clipped closed.
DD205689.eps
DD205696.eps
DD205697.eps
DD205698.eps
DD206077.eps
KBA 40ZFU KBA 40ZFU KBA 40ZFSU KBA 40ZFPU
+ KBB 40ZFC
DD206078.eps
DD205705.eps
DD205700.eps
DD205701.eps
DD205703.eps
DD205704.eps
Index 3
Introduction 8
Design guides and characteristics 29
Canalis KDP 57
Canalis KBA and KBL industrial luminaires 85
Presentation
Canalis KBB 114
For lighting and power socket distribution 114
Description
Canalis KBB, 25 and 40 A 118
Busbar trunking for lighting and power socket distribution 118
Canalis KDP, KBA and KBB 122
Busbar trunking for lighting and power socket distribution 122
Tap-off units 122
Installation
Canalis KBB, 25 and 40 A 132
Busbar trunking for lighting and power socket distribution 132
Installation scenario 132
Assembly of trunking components 136
Canalis KN 139
Canalis KS 175
Canalis KS riser 229
Canalis KT 253
7HFKQLFDOVSHFL¿FDWLRQV
Maintenance 267
Recommendations for special applications 273
Catalogue numbers 309
Canalis worldwide 315
PD202171R.eps
PD202173R.eps
PD202439.eps
PD202172.eps
DD202141_r.eps
1RWR[LFHPLVVLRQLQFDVHRI¿UH
$OOFRPSRQHQWVLQWKH.%%UDQJHDUHhalogen free.
,QFDVHRI¿UH&DQDOLV.%%GRHVQRWUHOHDVHVPRNH
or toxic gases.
PD202174R.eps
DD202169.eps
DD205711.eps
A high degree of Very rigid
protection &DQDOLV.%%RIIHUV¿[LQJ
b IP55 guarantees distances of up to 5
trunking protection metres, including the
against splashes and jointing units.
dust.
b &DQDOLV.%%FRPSOLHV
with sprinkler tests, guaranteering operation under
vertically and horizontally sprayed water for 50
minutes.
7KHKLJKGHJUHHRISURWHFWLRQIRU&DQDOLV.%%
means it can be installed in all types of buildings.
DD205706.eps
Run components
Carry current, support and supply the luminaires.
3DUWLFXODUO\VWURQJ&DQDOLV.%%LVVSHFLDOO\LQWHQGHGIRULQVWDOODWLRQVZLWKODUJH¿[LQJ
distances and/or heavy or numerous luminaires.
Straight lengths
DD210379_r.eps
Straight lengths constitute the basic structure of the line and are made up of:
1 an all-in-one carrier casing, crimp closed, forming a rigid beam made of sheet
steel, in RAL 9003 white lacquered sheet steel, hot galvanised on both sides. This
casing also acts as the protective earth conductor (PE),
2 one or two ribbon cable with two or four copper conductors, making up one or two
independent circuits,
3 three tap-off outlets maxi spaced every metre on the main circuit (front), two
tap-off outlets maxi on the adjacent circuit (rear),
4 an electrical joint unit ensuring automatic and simultaneous connection of all live
conductors,
5 a mechanical joint device in two parts, made of stamped sheet steel, that makes
the connection of two lengths rigid and resistant to bending.
DD206079.eps
Multi-circuit
possibilities
7KHEXVEDUWUXQNLQJLVQRQÀDPHSURSDJDWLQJDVSHUWKHUHFRPPHQGDWLRQVRI
standard IEC 60332-3. All the insulating and plastic materials are halogen-free and
KDYHHQKDQFHG¿UHZLWKVWDQGFDSDELOLWLHVLQFDQGHVFHQWZLUHWHVWDVSHUVWDQGDUG
IEC 60695-2).
b 960°C for components in contact with live parts.
b 650°C for other components.
DD205713_r.eps
They clip on (jointing unit) to the end of the line. Supply from left
Flexible lengths
Flexible length
DD205714.eps
Fixing systems
Busbar trunking
DD206080_r.eps
For attachment of the busbar trunking to the structure
of the building, either directly or via a threaded rod,
chain or steel cable.
b Designed to relieve the installer of the weight of the
busbar trunking once placed in a bracket.
b Automatic locking of moving part on closing
XQORFNLQJUHTXLUHVDPPÀDWVFUHZGULYHU
b 7KHPD[LPXPUHFRPPHQGHG¿[LQJGLVWDQFHLV¿YH
metres.
1 8QLYHUVDO¿[LQJEUDFNHW
For suspension on a threaded rod, diameter 6 mm.
For horizontal mounting on a beam, pendant, wall,
etc.
2 Cable suspension system
&XWVWKHPRXQWLQJWLPHRIWKH¿[LQJV\VWHPWR
one-third of that required for threaded rods.
Enables adjustment of the hight of the trunking.
3 Adjustable threaded-rod suspension system
For suspension on a threaded rod, diameter 6 mm.
A spring system locks the threaded rod in position
DD206081.eps
Luminaires
Attached to the luminaires before mounting, these
¿[LQJVHQVXUHIDVWDQGGLUHFW¿[LQJWR&DQDOLV.%%
b Fixing systems with automatic locking of moving part
on closing.
b To be completed according to the luminaire with
suspension accessories (open hook, closed ring...).
Cable support
For running adjacent circuits such as emergency
DD210386.eps
Cable brackets
Clips to trunking for fast mounting. It is possible to run
three cables (diameter 5 to 16 mm) and two IRL tubes.
DD205676_r.eps
Cable duct
7KHFDEOHGXFW¿WVRQVXSSRUW1ZKLFKLQWXUQ¿WVRQWR
a threaded rod suspension system (2). An intermediate
support is placed between the duct and the trunking if
the distance between the suspension points exceeds
2 metres.
Each duct is equipped with a mechanical joint system.
DD210388.eps
Used to adjust line length to building dimensions (e.g.
WRUHDFKD¿[LQJSRLQW
Two metres long, can be cut on site.
DD202264_r.eps
$VDQRSWLRQDIDFWRU\¿WWHGGHGLFDWHGHDUWKFRQGXFWRU
isolated from the grounding is available. This is known
as a Clean Earth and has a cross-section of 6 mm2.
1 The clean earth is always provided on the main
FLUFXLWRI.%%EXVEDUWUXQNLQJRQWKHIURQWSDQHO
VLGHZLWKODEHODQGWDSRIIVRQ.%%ZLWK
circuits). The symbol, which appears at regular
intervals near to the tap-off outlets, serves as a
reminder of the special nature of this circuit.
2 The electrical jointing unit is supplied with additional
clean earth contacts. Thus, installation of
FRPSRQHQWV¿WWHGZLWKRSWLRQ(GRHVQRWUHTXLUHDQ\
additional assembly operation.
3 The receivers are connected using a standard 16 A
.%&'&%pp ou DCFpp).
4 7KHIHHGER[HVDUH¿WWHGZLWKFOHDQHDUWKODEHOOHG
)et PE (labelled ) terminals.
DD210389_r.eps
)RULQVWDQWDQHRXVFRQQHFWLRQRIOXPLQDLUHVWR.'3EXVEDUWUXQNLQJ
b they can be handled while energised and under live conditions,
b the contacts for live conductors are of the clamp type,
b PE connection occurs before that of the phases and neutral,
b phase-selection system (clip-in contact studs) for balancing of 3-phase distribution
systems,
b selection is visible via a transparent window,
b a coloured lock holds them in the tap-off outlet,
b DOOWKHLQVXODWLQJDQGSODVWLFPDWHULDOVKDYHDKLJK¿UHUHWDUGDQWFDSDFLW\
v incandescent-wire test in compliance with IEC 60695-2-1:
- 960 °C for components in contact with live parts,
- 650 °C for other components.
3UHZLUHG$WDSRIIXQLWZLWK¿[HGSRODULW\
Pre-wired with SO5Z1Z1-F 3 x 1.5 mm2 cable, 0.80 m long, pre-stripped on luminaire
DD205722.eps
end:
b 10 A rating,
b ¿[HG/13(SRODULW\
b the various models make it possible to balance 3-phase distribution systems.
7KHFRORXURIWKHORFNDQGWKHFDVLQJHQDEOHUHPRWHLGHQWL¿FDWLRQRIWKHSRODULW\
1 Live-conductor contacts.
2 Protective-conductor contact.
3 Lock.
b 7REHZLUHGIRUFRQQHFWLRQRIOXPLQDLUHVXVLQJDFDEOHRIVSHFL¿FW\SHVL]HRU
length.
b Fast connection for 3 x 0.75 to 1.5 mm2 cable. If prefabricated leads are used, the
line must have 16 A protection (see possibilities of dispensing with protection in the
VLPSOL¿HGGHVLJQJXLGHIRUOLJKWLQJGLVWULEXWLRQLQWKHVHFWLRQRQSURWHFWLRQDJDLQVW
overloads).
If prefabricated leads are used, the line must have 16 A protection (see possibilities
RIGLVSHQVLQJZLWKSURWHFWLRQLQWKHVLPSOL¿HGGHVLJQJXLGHIRUOLJKWLQJGLVWULEXWLRQ
in the section on protection against overloads).
)RUFRQQHFWLRQRIOXPLQDLUHVXVLQJDFDEOHRIVSHFL¿FW\SHVL]HDQGOHQJWK
FLUFXLWVRIFRQGXFWRU.%%WUXQNLQJ
Identical in design to the tap-off units on the opposite page, but with factory-set
polarity.
Accessories
6SHFL¿FWR.%&'&)WDSRIIXQLWV
DD205725.eps
$GGLWLRQDO¿[LQJRI.%&WDSRIIXQLWVXVLQJWKHUHDUVXSSRUWEUDFNHWPD\EH
necessary, notably if there is a risk of accidental pulling on the cable or if the cable
is very heavy (great length).
Other accessories
3 Interlocking device
For all 10 A and 16 A tap-off units.
A set of three interlocking devices in different colours can be used to mechanically
DD210192.eps
lock out tap-off units when two or three different distribution networks are present
(load, voltage, frequency, etc.).
b An interlocking device is made up of a handle and an interlocking device on each
end. It can be used for a tap-off outlet and the corresponding tap-off unit.
b /DEHOVFDQEHSODFHGRQWKHWDSRIIXQLWVDQGWKHWUXQNLQJIRUUHPRWHLGHQWL¿FDWLRQ
KBB ppEDppppW Type of Length Number Order in 25 A rating Weight 40 A rating Weight Option (1)
busbar trunking (m) of multiples Cat. no. (kg) Cat. no. (kg) T E
tap-offs of (2)
Standard 3 0 6 KBB 25ED2300W 2.400 KBB 40ED2300W 2.700 - -
DD210135.eps
KBB ppEDppp3W
DB403708.eps
KBB ppEDppp2W
KBB 40ABG4W W W
DD210021.eps
DD210069.eps
DB403888.eps
End cover
7KHHQGFRYHU.%%LVDVSDUHSDUWRIWKHDIWHUVDOHVVHUYLFH
DD210048.eps
KBB ppEDpppppW Type of Length Number Order in 25 A rating Weight 40 A rating Weight Option (1)
busbar trunking (m) of multiples Cat. no. (kg) Cat. no. (kg) T E
tap-offs of (3)
Standard 3 0 6 KBB 25ED22300W 4.600 KBB 40ED22300W 5.200 - -
DD210108.eps
KBB ppEDpp203W
DD210048.eps
DD210098.eps
7KHHQGFRYHU.%%LVDVSDUHSDUWRI
DB403889.eps
KBB 40DF4pppW Designation Mounting For trunking Length Cat. no. Weight Option (1)
(m) (kg) T E
Flexible lengths For elbows, 0.5 KBB 40DF405W 0.800 b b
DD210136.eps
changing levels,
detours around 2 KBB 40DF420W 1.900 b b
obstacles, etc.
0.5 KBB 40DF4405W 0.800 b b
DD210109.eps
2 KBB 40DF4420W 1.900 b b
KBB 40DF4pppW
DB403835.eps
Fixing systems
%XVEDUWUXQNLQJ¿[LQJV
Designation Mounting Maximum Order in Cat. no. Weight
DD202178.eps
DB403494.eps
threaded rod, Ø M6
Pigtail hook For suspension by 60 10 KBB 40ZFC 0.020
a chain
Raiser For mounting on 60 10 KBB 40ZFMP 0.040
ZDOORUIDOVHÀRRU
KBB 40ZFC KBB 40ZFSU (1) W option available. (2)0D[LPXQUHFRPPHQGHGGLVWDQFHEHWZHHQ¿[LQJVPHWHUV
KBB 40ZFU KBB 40ZFSU KBB 40ZFPU KBB 40ZFC
DD202211.eps
DD210047.eps
DB403495.eps
DD210046.eps
DD210049.eps
KBB 40ZFMP
DD210050.eps
KBB 40ZFPU
DB403491.eps
DD205776.eps
DD210040.eps
DD210047.eps
DB403492.eps
Accessories DD210041.eps
DD210316.eps
DD202294.eps
DD202261.eps
DD210039.eps
KBB 40ZFGU
Other accessories
DD210085.eps
Cutting pliers To cut steel cable used for cable 1 KBB 40ZFS 0.300
suspension system
KBC 16ZB1
DD210121.eps
DD210051.eps
KBC 10DCS301
DD210126.eps
DD210121.eps
DD210128.eps
L2 + N2 or L3 + N3
DD210126.eps
DD210121.eps
DD210128.eps
L2 + N2 or L3 + N3
Yes (1) 10 KBC 10DCC21Z 0.165
10 A tap-off unit, 3L + N + PE
Type of busbar trunking Polarity Order in Cat. no. Weight
multiples of (kg)
7REHGH¿QHGIRUHDFKDSSOLFDWLRQ 10 KBC 10DCB40 0.065
(dimmer, emergency lighting, etc.)
DD210112.eps
DD210126.eps
DD210121.eps
DD210124.eps
(1) For IP, see KDP, KBA and KBB Tap-off units description page 122.
DD210151.eps
or
DD205780.eps
DD210126.eps
DD210121.eps
L2 + N
or
L3 + N
DD210153.eps
Single- Balancing on 3 fuse
circuit phases or NF 8.5 x 31.5
KBC 16DCB2p
switching 3-circuit 16 A gG
switching maximum
(not supplied)
DD210145.eps
or
DD205781.eps
DD210123.eps
L1 + L3
or
L2 + L3
Balancing on fuse
3 phases without NF 8.5 x 31.5
KBC 16DCp22
neutral 16 A gG
maximum
(not supplied)
DD210128.eps
2 single-phase fuse
circuits NF 8.5 x 31.5
KBC 16DCp2pp6
16 A gG
maximum
(not supplied)
L3 + N3 None Blue 10 KBC 16DCB216 0.090
DD210149.eps
fuse
NF 8.5 x 31.5
16 A gG
maximum
(not supplied)
DD210144.eps
DD210119.eps
DD210121.eps
DD210143.eps
All types possible NF 8.5 x 31.5
12 A gG
KBC 16DCp40
maximum
(not supplied)
KBC 16DCp40
DD210054.eps
2P + E NF 8.5 x 31.5
DD210120.eps
DD210121.eps
10/16 A, 250 V 16 A gG
maximum
(not supplied)
KBC 16DCPp
DD210055.eps
multiples of (kg)
Bus connection device For 16 A single-phase or three-phase tap-off 10 KBC 16ZT1 0.010
units to tap off the remote control circuit of the
trunking to the remote receiver
KBC 16ZT1 Rear support bracket For securing 16 A single-phase tap-off units to 10 KBC 16ZC1 0.020
the trunking
DD205782.eps
KBC 16ZC1
Installation of a line
DD210390_r.eps
no work is going on.
Do not store the busbar trunking outdoors.
8QSDFNDQGOD\RXWRQWKHÀRRUWKHWUXQNLQJ
DD210391_r.eps
FRPSRQHQWVUHTXLUHGWRPRXQWWKH¿UVWOLQH
3UHSDUDWLRQRI¿[LQJV
DD210392_r.eps
DD210649_r.eps
,QWKLVFDWDORJXH\RXZLOO¿QGDQXPEHURI¿[LQJV
suited to different building structures.
<RXZLOODOVR¿QGDUDQJHRIDFFHVVRULHVWRVXSSRUWDOO
the cables associated with your installation.
DD210393_r.eps
DD210650_r.eps
DD210398_r.eps
Assemble two or three lengths (clip together) and lock
with the joint screw.
DD210395_r.eps
/LIWDQGSRVLWLRQWKHOLQHVHJPHQWLQWKH¿[LQJEUDFNHWV
DD210396_r.eps
7RXQORFNWKHEUDFNHWVXVHPPÀDWVFUHZGULYHU
DD210397_r.eps
DD210651_r.eps
DD210398_r.eps
due to the ease of assembling the mechanical and
electrical connections.
Tap-off connections
DD210647_r.eps
,QWKLVFDWDORJXH\RXZLOO¿QGUHDG\WRXVHOXPLQDLUHV
They are supplied prewired, equipped with a tap-off
unit with phase-selection.
DD210401_r.eps
DD210402_r.eps
2QFHDJDLQWKH¿[LQJEUDFNHWVDUHGHVLJQHGWR
immediately relieve the installer of the weight. The
luminaire is held in place as soon as the bracket is
placed on the trunking.
DD210648_r.eps
Connect the tap-off unit to the trunking
&RQQHFWWKHVXSSO\FDEOHWRWKH&DQDOLV.%%IHHGXQLW
then to the switchboard.
DD205783.eps
Version : 2.0
KBB 40ZFU
DD205790.eps
DD205794.eps
DD205800.eps
DD210416.eps
03/10/2011
DD205791.eps
DD205798.eps DD210419.eps
Fixing Canalis KBB in the brackets
KBB 40ZFC
KBB 40ZFU +
DD205792.eps
Mounting the luminaires on the trunking
DD205801.eps
DD205795.eps
KBB 40ZFSU
DD210413.eps
KBB 40ZFPU
137
138 Version : 2.0 03/10/2011 .(
Contents Canalis KN
Index 3
Introduction 8
Design guides and characteristics 29
Canalis KDP 57
Canalis KBA and KBL industrial luminaires 85
Canalis KBB 113
Presentation
Canalis KN 140
For low-power distribution from 40 to 160 A 140
Description
Canalis KN, 40 to 160 A 144
Low-power distribution 144
Installation
Canalis KN, 40 to 160 A 168
Busbar trunking for low-power distribution 168
Installation scenario 168
Assemby of trunking components 172
Canalis KS 175
Canalis KS riser 229
Canalis KT 253
7HFKQLFDOVSHFL¿FDWLRQV
Maintenance 267
Recommendations for special applications 273
Catalogue numbers 309
Canalis worldwide 315
PD202199_r.eps
PD202202_r.eps
b 7KH¿[LQJV\VWHPHQVXUHVWKDW&DQDOLV.1LVZHOO b The tap-off units (with and without isolators) are used to:
secured, whatever the type of building structure. v supply loads from 16 to 63 A
v or protect nearby loads against overloads due to lightning strikes
PD202201_r.eps
DB403667.eps
DD202172.eps
PD202079_r.eps
DD202143_r.eps
DD202144_r.eps
7KHKLJKGHJUHHRISURWHFWLRQIRU&DQDOLV.1PHDQVLWFDQ
be installed in all types of buildings.
b IP55 guarantees trunking protection against splashes,
dust.
b IK08 guarantees the strength of the trunking (resistance
to shocks).
b IPxxD ensures totally safe working conditions for
maintenance personnel.
b &DQDOLV.1FRPSOLHVZLWKsprinkler tests, guaranteeing
operation under vertically and horizontally sprayed water
for 50 minutes.
142 Version : 3.0 03/10/2011 .(
Unmatched upgrading possibilities
Tap-off outlets are positioned every 0.5 metres to
ensure availability of an outgoer as close as possible to
loads throughout the life of the installation.
Tap-off units can be added or removed on live
installations, without interrupting the supply to the other
loads.
DD205761.eps
DD205762.eps
DD202145_r.eps
&DQDOLV.1LVGHVLJQHGIRUORZSRZHUGLVWULEXWLRQ
DD210183.eps
Straight lengths
Carry the current and supply low-power loads.
Straight lengths constitute the basic structure of the line and are made up of:
1 a carrier casing, crimp closed, made of hot-galvanised sheet steel, pre-lacquered RAL 9001 white. This rail also acts as the protective earth
conductor (PE),
2 an insulated mounting casing, supporting the live conductors,
3 four live aluminium conductors, equipped with silver-plated aluminium/copper bimetal contacts at junctions and tap-off points,
4 tap-off outlets with automatic shutters that open and close automatically when tap-off units are installed or removed. They are equipped
with blanking plugs to maintain the degree of protection IP55. There are one or two tap-offs per metre, depending on the version,
5 a mechanical and electrical jointing system(OHFWULFDOFRQQHFWLRQLVYLDÀH[LEOHJULSFRQWDFWVPDGHRIVLOYHUSODWHGFRSSHU7KHV\VWHP
ensures automatic and simultaneous connection of all live conductors and the continuity of the protective earth conductor,
6 three copper bus conductors&DQDOLV.17IRUWKHFRPSOHPHQWDU\RIIHU
DB403673.eps
Feed units
6XSSO\D&DQDOLV.1OLQHYLDDFDEOH
DD205829.eps
DD210186.eps
(posts, pipes). They can be shaped by hand, on site, to
follow any path.
1 Flexible elbow
2 Flexible length
One metre long, these components can be used in
corners to adjust to the lengths of the straight
DD205828.eps
components running along three walls, regardless of
the dimensions of the premises.
3 'ÀH[LEOHOHQJWK
Three metres long, it can be bent in any direction to
avoid major obstacles, particularly useful in false
ceilings.
7KH¿[LQJVDUHVXLWDEOHIRUDOOW\SHVRIPRXQWLQJ
RQFHLOLQJVVXVSHQGHGRQZDOOVHWF5HJDUGLQJ¿[LQJ
installation, some tap-off outlets would not be available.
1 8QLYHUVDO¿[LQJEUDFNHW
)RUHGJHZLVHRUÀDWWUXQNLQJLQVWDOODWLRQ
7KHUHFRPPHQGHG¿[LQJGLVWDQFHLVWKUHHPHWUHVIRU
trunking installed edgewise and 1.5 metres when
LQVWDOOHGÀDW
2 Wall brackets
)RUHGJHZLVHPRXQWLQJRQO\7KHUHFRPPHQGHG¿[LQJ
distance is two metres.
3 6SULQJ¿[LQJEUDFNHW
7KHVHEUDFNHWVDUHXVHGWRVXVSHQGWKH.1OLQHRQ
threaded rods M8 and do not require tools. The bracket
is attached to the treaded rod by the spring mechanism,
without nuts or bolts. Adjustment of the length of the
WKUHDGHGURGLVVLPSOL¿HGDQGWKH.1WUXQNLQJFDQEH
installed three times faster.
They are suitable for all ratings.
4 Pendant Kit
The pendant kit includes:
WKHPRXQWLQJKDUGZDUHUHTXLUHGWRVHFXUHWKH.1
bracket and the cantilever arm to the pendant.
If neccessary, additional cantilever arms can be
ordered.
DD210180.eps
(e.g. lighting), in compliance with installation standards
CEI 60364 and regulations concerning TT, IT and TNS
systems.
2 Power socket
$OOWDSRIIXQLWVDUHPDQXIDFWXUHGLQWKH.1$YHUVLRQ
DD210177.eps
DD210236.eps
(L1, L2 or L3 + N + PE).
Positioned as close as possible to the loads; extension
leads are not required.
devices.
Rated current: 63 A
2 sizes available: 8 or 12 18 mm modules.
They are available with windows and blanking plates
(devices visible and accessible) or with a plain cover
(devices not accessible when energised).
Tap-off units (with and without isolators) equipped with a SPD (Surge Protection Device)
These tap-off units (with and without isolators) are
DD205831.eps
DD210253.eps
household or industrial plugs in a:
b garage,
b maintenance workshop,
b laboratory,
b battery charging room, etc.
Rated courant: 32 A
Capacity: 8 modules in multiple of 18 mm wide
Two versions are available:
b SUHHTXLSSHGZLWK3.RU3UDWL.DSRZHUVRFNHWV
b customisable:
v WZR[PPRSHQLQJVIRU3.W\SHVFUHZ
FRQQHFWLRQVRU3UDWL.DIDVWDQGUHOLDEOHFRQQHFWLRQ
without stripping) industrial or household sockets.
v direct mounting for industrial IEC 16 A 5P or
IEC 32 A 3, 4 or 5P sockets.
v mounting on 65 x 85 mm clip-on adapter plate for
industrial IEC 16 A 3P or 5P and household 10/16 A 2P
+ PE sockets.
DD210172.eps
DD205839.eps
8VHGWRWDSRIIWKH.17EXV
Clips into all tap-offs with isolators and can be used to
control the equipment via a bus (BatiBus...).
Standard lengths
KNA pppED4ppp Polarity Rating Length Number of tap-off Cat. no. Weight
(A) (mm) outlets (kg)
3L + N + PE or 3L + PEN 40 3000 3 KNA 40ED4303 5.60
6 KNA 40ED4306 5.60
63 3000 3 KNA 63ED4303 5.70
6 KNA 63ED4306 5.70
100 3000 3 KNA 100ED4303 6.70
6 KNA 100ED4306 6.70
160 3000 3 KNA 160ED4303 7.30
6 KNA 160ED4306 7.30
KNA pppED4306
DD210213.eps
KNA pppED4303
DD210214.eps
Additional lengths
Polarity Rating Length Number of tap-off Cat. no. Weight
(A) (mm) outlets (kg)
3L + N + PE or 3L + PEN 40 3000 1 KNA 40ED4301 5.50
63 3000 1 KNA 63ED4301 5.60
2000 4 KNA 63ED4204 4.10
100 3000 1 KNA 100ED4301 6.60
2000 4 KNA 100ED4204 4.80
160 2000 4 KNA 160ED4204 5.20
KNA pppED4301
DD210215.eps
KNA pppED4204
DD210216.eps
DD205038.eps
63 A
A 265 340 256
B 165 238 258
C 100 102 98
D 71 112 130
E 92 127 185
KNA pppABT4
Dim. 40 to 100 A 160 A
DD205039.eps
63 A
KNA pppABT4 A 535 685 600
B 335 481 502
C 100 102 98
D 71 112 122
Cable entry E 92 127 243
(3)0D[LPXPUHFRPPHQGHGGLVWDQFHEHWZHHQ¿[LQJVPHWHUV
DD210228.eps
DD210225.eps
KNB 160ZF2
DD210224.eps
DD210223.eps
KNB 160ZF2
DD210226.eps
KNB 160ZFG100
KNB 160ZFPU
KNT pppED4ppp Polarity Rating Length Number of tap-off Cat. no. Weight
(A) (mm) outlets (kg)
3L + N + PE or 3L + PEN 40 3000 3 KNT 40ED4303 5.60
6 KNT 40ED4306 5.60
63 3000 3 KNT 63ED4303 5.70
6 KNT 63ED4306 5.70
2000 4 KNT 63ED4204 4.10
100 3000 3 KNT 100ED4303 6.70
6 KNT 100ED4306 6.70
2000 4 KNT 100ED4204 4.80
KNT pppED4306
DD210213.eps
KNT pppED4303
DD210214.eps
KNT pppED4204
DD210216.eps
Feed units with built-in transmission bus (supplied with end cover)
KNA pppAB4
Dim. 40 à 63 A 100 A
DD210218.eps
DD210219.eps
A 265 340
B 165 238
C 100 102
D 71 112
E 92 127
KNA pppABT4
Dim. 40 à 63 A 100 A
DD210220.eps
(A) (kg)
Flexible elbow, for internal 40 to 63 Left or right KNA 63DL4 1.20
or external 100 Left or right KNA 100DL4 1.30
angle, 80° to 180° 160 Left or right KNA 160DL4 1.50
KNA pppDL4 Flexible length, 1 m 40 to 63 Left or right KNA 63DF410 2.10
for detours around 100 Left or right KNA 100DF410 2.30
obstacles 160 Left or right KNA 160DF410 2.50
KNA pppDL4
DD210230.eps
DD210231.eps
KNA pppDF410
KNA pppDF410
DD210232.eps
(A) (kg)
Flexible elbow, for internal 40 to 63 Left or right KNT 63DL4 1.20
or external 100 Left or right KNT 100DL4 1.30
angle, 80° to 180°
KNT pppDL4 Flexible length, 1 m 40 to 63 Left or right KNT 63DF410 2.10
for detours around 100 Left or right KNT 100DF410 2.30
obstacles
KNA pppDL4
DD210230.eps
DD210231.eps
KNA pppDF410
KNT pppDF410
DD210232.eps
KNA 100EDF430
Designation Rating Direction (edgewise) Cat. no. Weight
(A) (kg)
Flexible length, 3 m 100 Left or right KNA 100EDF430 5.00
Up or down
KNA 100EDF430
DD210233.eps
Fixing system
7UXQNLQJ¿[LQJV\VWHP
Designation Rating Max. load Mounting Order in Cat. no. Weight
DD202216.eps
DD202219.eps
KNB 160ZFKP1
DD202217.eps
KFB CA81100
Spare parts
Designation Rating Order in Cat. no. Weight
DD210234.eps
(A) (kg)
Electrical and 40 to 63 KNT 63ZJ4 0.60
mechanical jointing unit 100 KNT 100ZJ4 0.60
Single-phase IP41 tap-off unit with phase selection, equipped with a C60 circuit breaker
Disconnection by unplugging the tap-off unit
DD210446.eps
(e.g. circuit-breaker
protection)
Rating Circuit Connection Max. size Cable gland Cat. no. Weight
KNB 16CM2p (A) breaker (mm2) (not supplied) (kg)
(supplied) Flexible Rigid
16 C60N, 1P, C60 4 6 Cable clamp KNB 16CM2* 0.34
curve C supplied
C60H, 1P, C60 4 6 Cable clamp KNB 16CM2H* 0.34
curve C supplied
* Adaptatation for transmission bus (KNT) with remote control power socket block KNT 63ZT1
not possible.
KNB 16CM2H KNB 16CM2
DD210238.eps
Cable exit
Centre line of tap-off outlets
(1) Protruding.
(1)
Four-pole tap-off unit (not equipped)
Disconnection by unplugging the tap-off unit
Earthing system Busbar trunking TT - TNS - TNC - IT (2)
DD210237.eps
DD210242.eps
(e.g. circuit-breaker
protection)
Rating Number of Connection Max. size Cable gland (4) Cat. no. Weight
(A) 18 mm (mm2) (not supplied) (kg)
KNB 32CM55 modules Flexible Rigid
32 5 (1) Pre wired 6 10 ISO 32 max. KNB 32CM55 0.60
(1) Supplied with blanking plate (1x5 divisible).
(2) The neutral must be protected or not distributed (3L + PE) for IT system.
(3) Also suitable for tap-off unit 3L + PE (N not distributed).
(4) Maximum diameter for a multipolar cable.
KNB 32CM55
DD202007.eps
Cable exit
Centre line of tap-off
outlets
(5) Protruding.
DD210246.eps
DD210247.eps
(e.g. circuit-breaker
protection)
KNB 63SM4pp Rating Number of Connection Max. size Cable gland (4) Cat. no. Weigh
(A) 18 mm (mm2) (not supplied) (kg)
modules Flexible Rigid
63 8 (1) Tunnel 25 25 ISO 50 max. KNB 63SM48 2.40
terminals
12 (1) Tunnel 25 25 ISO 50 max. KNB 63SM412 2.70
terminals or
1 x 32 + 2 x 25
(1) Supplied with blanking plates (1x5 divisible (8 modules) or 2x5 divisible (12 modules)).
(2) The neutral must be protected or not distributed (3L + PE) for IT system.
(3) Also suitable for tap-off unit 3L + PE (N not distributed).
(4) Maximum diameter for a multipolar cable.
KNB 63SM48
DD202008.eps
DD210248.eps
X = 432.5
KNB 63SM412
DD202008.eps
DD210249.eps
X = 491
Cable exit
Centre line of tap-off outlets
(5) Protruding.
7KHVHWDSRIIXQLWVDUHHTXLSSHGZLWKÀXVKPRXQWHGSRZHUVRFNHWV
DD210241.eps
DD210242.eps
(e.g. circuit-breaker wiring depends
protection) on the sockets
used
KNB 32CPppp
DD210252.eps
7KLVWDSRIIXQLWLVHTXLSSHGZLWKDQDGDSWHUSODWHIRUÀXVKPRXQWHGSRZHUVRFNHWV
DD210241.eps
DD210242.eps
(e.g. circuit-breaker wiring depends
protection) on the sockets
used
KNB 32CP
DD202009.eps
Power sockets
Designation Rated current Rated voltage Number of poles Dimensions Cat. no. Weigh
(A) (V AC) (W x H in mm) (kg)
Industrial sockets 16 200-250 2P + T 65 x 85 PKY16F723 -
3P + N + T 90 x 100 PKY16F725 -
380-415 2P + T 65 x 85 PKY16F733 -
3P + N + T 90 x 100 PKY16F735 -
32 200-250 2P + T 90 x 100 PKY32F723 -
3P + N + T 90 x 100 PKY32F725 -
380-415 2P + T 90 x 100 PKY32F733 -
3P + N + T 90 x 100 PKY32F735 -
Household NF sockets 10 to 16 250 2P + T 65 x 85 81140 -
Household Schuko sockets 10 to 16 250 2P + T 65 x 85 81141 -
Screw-on plate For blanking of unused openings 13137 0.10
For adapting 65 x 85 mm power-socket bases 13136 0.09
DD210255.eps
(e.g. fuse protection)
Rating For fuses Connection Max. size Cable gland Cat. no. Weigh
KNB 16CF2 (A) (not supplied) (mm2) (not supplied) (kg)
Flexible Rigid
16 NF 8,5 x 31,5 Cable clamp 4 6 Cable clamp KNB 16CF2* 0.16
Type gG : 16 A maxi. terminals supplied
Type aM : 16 A maxi.
* Adaptatation for transmission bus (KNT) with remote control power socket block KNT 63ZT1
not possible.
KNB 16CF2
DD202215.eps
Cable exit
Centre line of tap-off outlets
(1) Protruding.
DD210257.eps
Rating For fuses Connection Max. size Cable gland Cat. no. Weigh
(A) (not supplied) (mm2) (not supplied) (kg)
KNB 25CF5 Flexible Rigid
25 NF 10 x 38 Cable clamp 6 10 Cable clamp KNB 25CF5* 0.38
Type gG, 20 A max. terminals supplied
Type aM, 25 A max.
KNB 25CF5
DD202006.eps
Cable exit
Centre line of tap-off outlets
(2) Protruding
DD210470.eps
DD210260.eps
(e.g. fuse protection)
KNB 50SF4
Rating For fuses Connection Max. size Cable gland (2) Cat. no. Weigh
(A) (not supplied) (mm2) (not supplied) (kg)
Flexible Rigid
50 NF 14 x 51 Cable clamp 16 16 ISO 50 max. KNB 50SF4 1.50
Type gG, 50 A max. terminals
Type aM, 50 A max.
KNB 50SF4
DD202008.eps
DD210262.eps
X = 420
Cable exit
Centre line of tap-off outlets
(3) Protruding
DD210255.eps
(e.g. fuse protection)
Rating For fuses Connection Max. size Cable gland Cat. no. Weigh
KNB 16CG2 (A) (not supplied) (mm2) (not supplied) (kg)
Flexible Rigid
16 BS88 A1 Cable clamp 4 6 Cable clamp KNB 16CG2* 0.18
terminals supplied
* Adaptatation for transmission bus (KNT) with remote control power socket block KNT 63ZT1
not possible.
KNB 16CG2
DD210256.eps
Cable exit
Centre line of tap-off outlets
(1) Protruding
DD210257
Rating For fuses Connection Max. size Cable gland (2) Cat. no. Weigh
(A) (not supplied) (mm2) (not supplied) (kg)
KNB 20CG5 Flexible Rigid
20 BS88 A1 Cable clamp 4 6 ISO 32 max. KNB 20CG5* 0.60
terminals
(1) Also suitable for tap-off unit 3L + PE (N not distributed)
(2) Maximum diameter for a multipolar cable.
* Adaptatation for transmission bus (KNT) with remote control power socket block KNT 63ZT1
not possible.
KNB 20CG5
DD210243.eps
Cable exit
Centre line of tap-off outlets
(3) Protruding
DD210470.eps
DD210260.eps
(e.g. fuse protection)
KNB 32SG4
Rating For fuses Connection Max. size Cable gland (2) Cat. no. Weigh
(A) (not supplied) (mm2) (not supplied) (kg)
Flexible Rigid
32 BS88 A1 Cable clamp 10 10 ISO 50 max. KNB 32SG4 1.50
terminals
(1) Also suitable for tap-off unit 3L + PE (N not distributed).
(2) Maximum diameter for a multipolar cable.
KNB 32SG4
DD202008.eps
DD210262.eps
X = 432.5
Cable exit
Centre line of tap-off outlets
(3) Protruding
DD210258.eps
DD210257.eps
(e.g. fuse protection)
Rating For fuses Connection Max. size Cable gland (2) Cat. no. Weigh
(A) (not supplied) (mm2) (not supplied) (kg)
KNB 16CN5 Flexible Rigid
16 Néozed E14 Tunnel terminals 4 6 ISO 32 max. KNB 16CN5* 0.60
(1) Also suitable for tap-off unit 3L + PE (N not distributed).
(2) Maximum diameter for a multipolar cable.
KNB 16CN5
* Adaptatation for transmission bus
DD210243.eps
Cable exit
Centre line of tap-off outlets
(3) Protruding.
load is de-energised.
Earthing system Busbar trunking TT - TNS - TNC IT
arrangement Tap-off unit TT - TNS - TNS IT
Tap-off polarity 3L + N + PE (1) 3L + PE
Tap-off diagram(e.g. fuse
DD210470.eps
DD210260.eps
protection)
KNB ppSp4 Rating For fuses Connection Max. size Cable gland (2) Cat. no. Weigh
(A) (not supplied) (mm2) (not supplied) (kg)
Flexible Rigid
25 Diazed E27 Tunnel terminals 16 16 ISO 50 max. KNB 25SD4 1.50
50 Néozed E18 Tunnel terminals 16 16 ISO 50 max. KNB 50SN4 1.50
Diazed E33 Tunnel terminals 16 16 ISO 50 max. KNB 50SD4 1.50
(1) Also suitable for tap-off unit 3L + PE (N not distributed).
(2) Maximum diameter for a multipolar cable.
KNB ppSp4
DD202008.eps
DD210262.eps
X = 432.5
arrangement
Tap-off polarity 3L + N + PE(1)
Diagram L1 L2 L3 N PE
DD511621.eps
Protection Surge arrester Connection Permissible Max. discharge Cat. no. Weight
type cartridges short-circuit current (kg)
KNB QPF (supplied) Isc (kA) Imax (kA)
Type 2 Fixed Pre-wired 6 10 KNB QPF 1.3
Surge arrester installed: Quick PF10, 3P+N, cat. no. 16618 (Type 2 monoblock surge arrester,
ZLWK¿[HGFDUWULGJHVDQGLQWHJUDWHGGLVFRQQHFWLRQGHYLFHFHUWL¿HG,(&(1
(1) Also suitable for tap-off unit 3L + PE (N not distributed).
DD511619.eps
DD511621.eps
KNB QPRD Protection Surge arrester Connection Permissible Max. discharge Cat. no. Weight
type cartridges short-circuit current (kg)
(supplied) Isc (kA) Imax (kA)
Type 2 Removable Pre-wired 25 40 KNB QPRD 3.40
Surge arrester installed: Quick PRD40r, 3P+N, cat. no. 16294 (Type 2 monoblock surge
DUUHVWHUZLWK¿[HGFDUWULGJHVDQGLQWHJUDWHGGLVFRQQHFWLRQGHYLFHFHUWL¿HG,(&(1
61643-11).
(1) Also suitable for tap-off unit 3L + PE (N not distributed).
DD511620.eps
DD202008.eps
X= 432.5
Accessories
For all tap-off units
Designation Colour Order in Cat. no. Weight
DD210263.eps
multiple of (kg)
Outlet/tap-off unit interlocking White 10 KNB 160ZL10 0.01
device Red 10 KNB 160ZL20 0.01
Yellow 10 KNB 160ZL30 0.01
Blue 10 KNB 160ZL40 0.01
multiple of (kg)
Remote control power socket 1 KNT 63ZT1 0.035
block
Installation of a line
DD210653_r.eps
they are not exposed to dust or inclement weather.
Do not store the busbar trunking outdoors.
8QSDFNDQGOD\RXWRQWKHÀRRUWKHWUXQNLQJ
DD210654_r.eps
FRPSRQHQWVUHTXLUHGWRPRXQWWKH¿UVWOLQH
3UHSDUDWLRQRI¿[LQJV
DD210655_r.eps
&RXQWWKHQXPEHURI¿[LQJVUHTXLUHGWRLQVWDOOWKH
trunking components.
,QWKLVFDWDORJXH\RXZLOO¿QGDQXPEHURI¿[LQJV
suited to different building structures.
DD210657_r.eps
DD210658_r.eps
3RVLWLRQDQGVHFXUHWKH¿[LQJEUDFNHWV
3RVLWLRQWKH&DQDOLV.1WUXQNLQJLQWKH¿[LQJEUDFNHWV
DD210659_r.eps
DD210662_r.eps
changing direction.
,QWKLVFDWDORJXH\RXZLOO¿QGDIXOOUDQJHRI
accessories for running all the adjacent circuits of the
installation.
Tap-off connections
DD210665_r.eps
unit.
,QWKLVFDWDORJXH\RXZLOO¿QGDIXOOUDQJHRIWDSRII
units to cover all protection needs using either circuit
breakers or fuses.
DD210666_r.eps
DD210667_r.eps
,QWKLVFDWDORJXH\RXZLOO¿QGDIXOOUDQJHRISRZHU
socket units with household and industrial sockets that
DUHFRPSDWLEOHZLWKWKHHQWLUH3.VRFNHWUDQJH
&RQQHFWWKHVXSSO\FDEOHWRWKH&DQDOLV.1IHHGXQLW
then to the switchboard.
IP55
Busbar trunking for low-power
Ue = 230...500 V distribution
RAL 9001 white Assemby of trunking components
DD205680.eps
DD205677.eps
KNB 160ZF1
KNB 160ZFPU
Index 3
Introduction 8
Design guides and characteristics 29
Canalis KDP 57
Canalis KBA and KBL industrial luminaires 85
Canalis KBB 113
Canalis KN 139
Presentation
Canalis KS 176
For medium-power distribution from 100 to 1000 A 176
Description
Canalis KS, 100 to 1000 A 180
Medium-power distribution 180
Installation
Canalis KS, 100 to 1000 A 220
Busbar trunking for medium power distribution 220
Installation scenario 220
Assembly of trunking components 224
PD202205_r.eps
PD202208_r.eps
b 7KH¿[LQJV\VWHPHQVXUHVWKDW&DQDOLV.6LVZHOO b The tap-off units (with and without isolators) are used to:
secured, whatever the type of building structure. v supply loads from 25 to 400 A
v or protect nearby loads against overloads due to lightning strikes.
b Protection is ensured with modular or Compact NSX circuit breakers or fuses.
PD202207_r.eps
DB403671.eps
PD202232.eps
or toxic gases.
PD202209_r.eps
DD202143_r.eps
DD202144_r.eps
7KHKLJKGHJUHHRISURWHFWLRQIRU&DQDOLV.6PHDQVLW
can be installed in all types of buildings.
b IP55 guarantees trunking protection against
splashes, and dust.
b IK08 guarantees the strength of the trunking
(resistance to shocks).
b IPxxD ensures totally safe working conditions for
maintenance personnel.
b &DQDOLV.6FRPSOLHVZLWKsprinkler tests,
guaranteering operation under vertically and
horizontally sprayed water for 50 minutes.
&DQDOLV.6LVGHVLJQHGIRUPHGLXPSRZHUGLVWULEXWLRQZLWKKLJKWDSRIIGHQVLWLHVLQLQGXVWULDODQGFRPPHUFLDOEXLOGLQJVIDFWRULHVH[KLELWLRQ
halls, supermarkets, etc.).
The range is available in eight ratings: 100, 160, 250, 400, 500, 630, 800 et 1000 A.
Canalis KS provides an IP55 degree of protection, whatever the installation method. Consequently it can be installed in virtually any type
of building.
Tap-offs are implemented by tap-off units from 25 to 400 A that may be removed in complete safety under energised conditions, from 25 to 400 A.
Busbar trunking rated 100 to 400 A may be equipped with tap-off units up to 250 A.
Busbar trunking with higher ratings may be equipped with the entire range of tap-off units.
All the insulating and plastic materials are halogen-freeDQGKDYHHQKDQFHG¿UHZLWKVWDQGFDSDELOLWLHV
b incandescent wire test as per standard IEC 60695-2 :
v 960 °C for components in contact with live parts
v 650 °C for other components.
Straight lengths
Distribution components
DD205843.eps
These components carry the current and supply loads up to 400 A. They constitute the basic structure of the line and are made up of:
1 a casing, crimp closed, made of hot-galvanised sheet steel, pre-lacquered RAL 9001 white. This casing, shaped and ribbed by roller
burnishing, provides excellent resistance to bending and twisting. Two sizes cover the entire range of ratings: 54 mm wide for the 100, 160, 250
and 400 A ratings and 113 mm wide for the 500, 630, 800 and 1000 A ratings, live conductors made up of four identically sized bars.
2 silver-plated aluminium/copper bimetal laminate for the 100 and 160 A ratings, aluminium equipped with silver-plated aluminium/copper
bimetall laminate contacts electrically welded at junctions and tap-off points for the 250 and 1000 A ratings.
3 a protective conductor (PE) sized u 50 % with respect to the cross-section of phases. It is connected to the casing at each junction.
4 tap-off outlets every meter on both sides of the trunking.
5 a mechanical and electrical jointing system: (OHFWULFDOMRLQWLQJLVHQVXUHGE\DEORFNZLWKÀH[LEOHJULSFRQWDFWVPDGHRIVLOYHUSODWHGFRSSHU
This block equally absorbs the difference in conductor and casing thermal expansion for each length.
For the 100 to 250 A ratings, it ensures automatic and simultaneous jointing of all live conductors and the continuity of the protective earth
conductor, as well as its connection with the casing. For the 400 to 1000 A ratings, electrical jointing is ensured by a quarter-turn locking
mechanism for each conductor.
Special components
DD205844.eps
2 Fire barrier
7KLVW\SHRIOHQJWKLVXVHGWRWUDQVLWD¿UHSURRIZDOO
(e.g. between two rooms in a building).
,WKDVEHHQWHVWHGLQDFHUWL¿HGODERUDWRU\DQG
complies with standard EN 1363-1.
The laboratory report lists the following results:
v thermal insulation: u 120 minutes,
vUHVLVWDQFHWRÀDPHVu 120 minutes,
v stability: u 120 minutes.
DD210267.eps
8VHGWRIHHGD.6OLQHE\FDEOHVRUGLUHFWO\IURPWKH
busbars in a switchboard. They can be mounted at the
end of a line (end feed, left or right) or in the middle
(central feed).
5 End cover
The end cover protects and isolates the ends of the
conductors. It is mounted on the last component.
Supplied with end feet unit and feed unit.
a junction block.
1 Edgewise elbow
One model for turning right or left.
2 Flat elbows
Two models, one for turning up and the other for
turning down.
3 Edgewise tee
To create branches perpendicular to the main line.
Sprinkler kit
To comply with the sprinkler tests (guaranteeing
DD205043.eps
Fixing systems
7KHPD[LPXPUHFRPPHQGHG¿[LQJGLVWDQFHLVWKUHH
DD210273.eps
metres.
1 8QLYHUVDO¿[LQJEUDFNHW
For attachment of the busbar trunking to the
structure of the building, either directly or via a
threaded rod M8, brackets, etc.
Suspension using chains or steel cables is not
advised.
2 Pendant kit
The pendant kit includes:
bDSHUIRUDWHGSHQGDQWXVHGWRVXVSHQGD.6OLQH
from the building structure, an IPN or the ceiling.
Length: 1 meter
Width: 80 mm
b a cantilever arm that supports the cable tray
XQGHUWKH.6OLQH
bWKHPRXQWLQJKDUGZDUHUHTXLUHGWRVHFXUHWKH.6
bracket and the cantilever arm to the pendant.
Tap-off units
DD210275.eps
DD210277.eps
DD210278.eps
up to 100 A are made of plastic:
b Colour: RAL 9001 white for the casing and the grip
zones and transparent green for the cover (design
EDVHGRQ.DHGUDHQFORVXUHV7KH¿[LQJPHFKDQLVPV
are in RAL 7016
b Material: self-extinguishing, halogen free insulating
SODVWLF¿UHUHVLVWDQWDQGYHU\KLJKWHPSHUDWXUH
withstand).
DD210279.eps
DD210280.eps
b Other characteristics: cable gland drilling zone,
stainless steel screws and the door can be lead sealed.
Disconnection principle:
DD210280.eps
DD210282.eps
This tap-off unit can be equipped with most modular
devices (18 mm wide) of the Multi 9 type:
b rated current: 32 A
b capacity: 5 modules
b with a window in front for visual and physical access
to the devices. A transparent cover seals the window.
metering
These tap-off units are used for sub-billing or
monitoring of secondary lines. The values measured by
the TI module of the Compact NSX are transmitted to
the power-monitoring unit that forwards the information
to a central unit via a bus.
(see Special measurement and metering applications)
DD210302.eps
For the supply of portable loads equipped with
household or industrial plugs in a garage, maintenance
workshop, laboratory, battery charging room, etc
For installation on trunking mounted on a wall for better
access.
For easy access, install on trunking mounted at an
appropriate height on the wall.
Flexibility, upgradeability: positioned as close as
possible to the loads, extension leads are not required
Degree of protection: IP55, IK08.
Safety of persons: IPxxB, earth-leakage protection.
Rated current: 32 A
DD210459.eps
IP55
Medium-power distribution
Ue = 230...690 V
RAL 9001 white
DD210287.eps
1 Tap-off unit with fuse holders
This tap-off unit exists in three versions:
b for NF 10 x 38 fuses
b for BS type 88 A1 fuses
b for DIN type Neozed E14 fuses.
DD210288.eps
2a and 2b Tap-off units, with isolator, for fuses
There are two types of tap-off units:
Plastic tap-off units (2a) equipped with fuse holders for:
b NF 50 to 100 A cylindrical fuses
b BS 32 to 80 A screw fuses
b DIN 25 to 63 A screw fuses
b 100 A blade-type fuses.
Sheet-metal tap-off units (2b) equipped with fuse
holders for 160 to 400 A blade-type fuses.
DD205742.eps
pre-equipped with a modular Type 2 surge arrester,
with integrated disconnection device.
on to
nnecti e
For co ne, use th
li .
an old adapaters
l ry
specia mplementa
o
See c .
cts
produ
Standard lengths
KSA pppED4pppp Polarity Rating Length Number of Cat. no. Weight
(A) (mm) tap-off outlets (kg)
3L + N + PE or 3 L + PEN 100 5000 10 KSA 100ED45010 19.20
3000 6 KSA 100ED4306 12.10
160 5000 10 KSA 160ED45010 21.40
3000 6 KSA 160ED4306 13.40
250 5000 10 KSA 250ED45010 25.20
3000 6 KSA 250ED4306 15.70
400 5000 10 KSA 400ED45010 32.85
3000 6 KSA 400ED4306 20.40
KSA pppED45010
DD202179.eps
DD210290.eps
KSA pppED4306
DD210291.eps
Other lengths
Polarity Rating Length Number of Cat. no. Weight
(A) (mm) tap-off outlets (kg)
3L + N + PE or 3 L + PEN 100 to 250 2000 8 KSA 250ED4208 10.85
1500 6 KSA 250ED4156 8.55
400 2000 8 KSA 400ED4208 13.90
1500 6 KSA 400ED4156 10.85
KSA pppED4208
DD210292.eps
KSA pppED4156
DD210293.eps
DD210296.eps
DD210297.eps
KSA pppAB4 KSA 400AB4
DD210642.eps
Cable exit
Fixing system
DD202200.eps
DD210306.eps
Cable exit
KSA pppAE4
KSA pppAE4 Dim. 100 to 250 A 400 A
DD230005.eps
A 243 261
B 261.5 279.5
C 108 117
D 278 318
E 294 334
(A) (kg)
Elbow 100 to 250 Right or left KSA 250DLC40 3.15
Upward KSA 250DLE40 5.00
Downward KSA 250DLF40 5.00
400 Right or left KSA 400DLC40 3.80
Upward KSA 400DLE40 5.60
Downward KSA 400DLF40 5.60
Tee 100 to 250 Perpendicular KSA 250DTC40 4.30
KSA pppDLp40 400 Perpendicular KSA 400DTC40 5.20
DD210311.eps
KSA pppDLC40
DD205748.eps
KSA pppDTC40
DD210312.eps
KSA pppDTC40
Fixing system
DD202193.eps
KSB 400ZFKP1
DD210317.eps
328
KFB CA81200
KSB 1000ZP1
DD202018.eps
Spare parts
Designation Rating Order in Cat. no. Weight
(A) multiples of (kg)
Electrical and mechanical 100 to 250 1 KSA 250ZJ4 1.60
jointing unit KSA 250FA4 1.60
KSB 1000ZP2 400 1 KSA 400ZJ4 2.00
IP55 blanking plate 100 to 400 15 KSB 400ZB1 0.015
6SULQNOHUSURR¿QJ 100 to 400 1 KSB 400ZB2 1
accessory
DD205749.eps
DD205750.eps
KSA 400ZJ4
DD202053.eps
KSB 400ZB2
KSB 400ZB2
DD205044.eps
DD202021.eps
KSA 400ZB1
Adapters
Designation Rating For Cat. no. Weight
DD202054.eps
(A) (kg)
Adapter 100 to 250 &RQQHFWLRQWRROG.6OLQHV KSA 250FA4 1.35
250 &RQQHFWLRQWRROG.6OLQHV KSA 250FA4 1.35
400 &RQQHFWLRQWRROG.6OLQHV KSA 400FA4 2.90
KSA 250FA4
KSA 250FA4 KSA 400FA4
DD202087.eps
DD202088.eps
DD202068.eps
KSA 400FA4
on to
nnecti e
For co ne, use th
li .
an old adapaters
l ry
specia mplementa
o
See c
cts.
produ
Standard lengths
KSA pppED4pppp Polarity Rating Length Number of tap-off Cat. no. Weight
(A) (mm) outlets (kg)
3L + N + PE or 3L + PEN 500 5000 10 KSA 500ED45010 54.50
3000 6 KSA 500ED4306 34.90
630 5000 10 KSA 630ED45010 58.20
3000 6 KSA 630ED4306 36.40
KSA pppED45010
DD210638.eps
DD202023.eps
KSA pppED4306
DD202024.eps
Additional lengths
Polarity Rating Length Number of tap-off Cat. no. Weight
(A) (mm) outlets (kg)
3L + N + PE or 3L + PEN 500 to 630 2000 6 KSA 630ED4206 26.00
1500 4 KSA 630ED4154 20.50
KSA 630D4206
DD202025.eps
KSA 630D4154
DD202026.eps
DD202028.eps
DD202070.eps
KSA 630ABp4
Cable exit
Fixing system
KSB 1000ZF1
DD202297.eps
KSB 1000ZF1
Cable exit
KSA 630AE4
KSA 630AE4
DD202052.eps
(A) (kg)
Elbow 500 to 630 Right or left KSA 630DLC40 13.40
Upward KSA 630DLE40 12.10
Downward KSA 630DLF40 12.10
Tee 500 to 630 Perpendicular KSA 630DTC40 15.80
DD202058.eps
DD202056.eps
KSA 630DLC40
DD202057.eps
KSA 630DTC40
DD202059.eps
KSA 630DTC40
Fixing system
DD202198.eps
DD202199.eps
KSB 1000ZFKP1
DD202197.eps
KFB CA81300
KSB 1000ZP1
DD202018.eps
KSB 1000ZP2
Spare parts
Designation Rating Order in Cat. no. Weight
DD202060.eps
DD202062.eps
KSB 1000ZB1
DD205041.eps
KSA 630ZJ4
DD205042.eps
KSB 1000ZB2
DD202082.eps
Adapters
Designation Rating For Cat. no. Weight
(A) (kg)
Adaptators 500 &RQQHFWLRQWRROG.6$OLQHV KSA 500FA4 3.65
630 &RQQHFWLRQWRROG.6$OLQHV KSA 800FA4 4.00
KSA pppFA4
KSA pppFA4
DD202089.eps
on to
nnecti e
For co ne, use th
li .
an old adapaters
l ry
specia mplementa
o
See c
cts.
produ
KSA pppED45010
DD210638.eps
DD202023.eps
KSA pppED4306
DD202024.eps
Additional lengths
Polarity Rating Length Number of tap-off Cat. no. Weight
(A) (mm) outlets (kg)
3L + N + PE or 3L + PEN 800 to 1000 2000 6 KSA 1000ED4206 38.50
1500 4 KSA 1000ED4154 29.90
KSA 1000ED4206
DD202025.eps
KSA 1000ED4154
DD202026.eps
DD202072.eps
DD202063.eps
Cable exit
Fixing system
KSB 1000ZF1
DD202297.eps
KSB 1000ZF1
Cable exit
KSA 1000AE4
KSA 1000AE4
DD202065.eps
(A) (kg)
Elbow 800 to 1000 Right or left KSA 1000DLC40 19.00
Upward KSA 1000DLE40 16.70
Downward KSA 1000DLF40 16.70
Tee 800 to 1000 Perpendicular KSA 1000DTC40 22.60
DD202058.eps
DD202056.eps
KSA 1000DLC40
DD202057.eps
KSA 1000DTC40
DD202059.eps
KSA 1000DTC40
Fixing system
DD202198.eps
DD202199.eps
KSB 1000ZFKP1
DD202197.eps
KFB CA81300
KSB 1000ZP1
DD202018.eps
KSB 1000ZP2
Spare parts
Designation Rating Order in Cat. no. Weight
DD202060.eps
KSA 1000ZJ4
KSA 1000ZJ4
DD202062.eps
DD202061.eps
KSB 1000ZB1
DD205041.eps
KSB 1000ZB2
DD205042.eps
KSB 1000ZB2
DD202083.eps
Adapters
Designation Rating For Cat. no. Weight
(A) (kg)
Adapter 800 &RQQHFWLRQWRROG.6OLQHV KSA 800FA4 4.00
KSA 800FA4
KSA 800FA4
DD202090.eps
Tap-off units
Disconnection by unplugging the tap-off unit
DD210451.eps
(e.g. circuit-breaker
protection)
KSB 32CM55
Rating Number of Connection Max. size Cable gland (4) Cat. no. Weight
(A) 18 mm (mm2) (not supplied) (kg)
modules (3) Flexible Rigid
32 5 Pre wired 6 10 ISO 32 max. KSB 32CM55 0.60
(1) The neutral must be protected or not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Supplied with blanking plate (1x5 divisible).
(4) Maximum diameter for a multipolar cable.
KSB 32CM55
DD210453.eps
Cable exit
Centre line of tap-off outlets
(5) Protruding.
DD205034.eps
(e.g. circuit-breaker
protection)
KSB 63SMp8, Rating Number of Connection Max. size Cable gland (4) Cat. no. Cat. no. Weight
KSB 100SMp12 (A) 18 mm (mm2) (not supplied) (kg)
modules (3) Flexible Rigid
63 8 Copper cable 16 16 ISO 50 max. KSB 63SM48 KSB 63SM58 2.40
lugs
100 12 Copper cable 35 35 ISO 63 max. KSB 100SM412 KSB 100SM512 5.00
lugs
(1) The neutral must be protected or not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed).
(3) Supplied with blanking plates:(1x5 divisible (8 modules) or 2x5 divisible (12 modules)).
(4) Maximum diameter for a multipolar cable.
DD210455.eps
DD205035.eps
(e.g. circuit-breaker protection) depends on the
sockets used
(1) The neutral must be protected or not distributed (3L+PE) for the IT system.
DD210459.eps
KSB 32CPppp
DD210460.eps
KSB 32CP
Power sockets
Designation Rated current Rated voltage Number of poles Dimensions Cat. no. Weight
(A) (V AC) (W x H in mm) (kg)
Industrial sockets 16 200-250 2P + T 65 x 85 PKY16F723 -
Pratika 3P + N + T 90 x 100 PKY16F725 -
380-415 2P + T 65 x 85 PKY16F733 -
3P + N + T 90 x 100 PKY16F735 -
32 200-250 2P + T 90 x 100 PKY32F723 -
3P + N + T 90 x 100 PKY32F725 -
380-415 2P + T 90 x 100 PKY32F733 -
3P + N + T 90 x 100 PKY32F735 -
Household NF sockets 10 to 16 250 2P + T 65 x 85 81140 -
Household Schuko sockets 10 to 16 250 2P + T 65 x 85 81141 -
Screw-on plate For blanking of unused openings 13137 0.10
For adapting 65 x 85 mm power-socket bases 13136 0.09
DD210451.eps
DD210452.eps
(e.g. circuit-breaker
protection)
KSB pppDCp
Rating Type of circuit Connection Max. size Cable gland (3) Cat. no. Cat. no. Weight
(A) breaker (mm2) (not supplied) (kg)
(not supplied) Flexible Rigid
160 NSX 100 or NSX 160 NSX 70 70 ISO 32 max. KSB 160DC4 KSB 160DC5 9.00
Curve N, H or L with
Rotary handle
LV429338
250 NSX 250 NSX 150 150 ISO 40 max. KSB 250DC4 KSB 250DC5 12.50
Curve N, H or L with
Rotary handle
LV429338
400 NSX 400 NSX 240 240 ISO 50 max. KSB 400DC4 KSB 400DC5 18.00
Curve N, H or L with
Rotary handle
LV432598
(1) The neutral must be protected or not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Maximum diameter by unipolar cable.
KSB 160DCp
DD202008.eps
DD210462.eps
KSB 400DCp
DD210464.eps
DD210451.eps
DD210452.eps
(e.g. circuit-breaker
protection)
KSB pppDCpTRE Rating Type of circuit breaker Connection Max. size Cable gland (3) Cat. no. Cat. no. Weight
(A) (not supplied) (mm2) (not supplied) (kg)
Flexible Rigid
250 NSX 250 Type N, H or L NSX CT block 150 150 ISO 40 max. KSB 250DC4TRE KSB 250DC5TRE 13.50
with Rotary handle
LV429338
400 NSX 400 Type N, H or L NSX CT block 240 240 ISO 50 max. KSB 400DC4TRE KSB 400DC5TRE 19.50
with Rotary handle
LV432598
(1) The neutral must be protected or not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Maximum diameter by unipolar cable.
KSB 250DCpTRE
DD202008.eps
DD202085.eps
KSB 400DCpTRE
DD202086.eps
DD210451.eps
DD210452.eps
(e.g. circuit-breaker
protection)
KSB 160SMp13 Rating Type of circuit breaker Connection Max. size Cable gland (3) Cat. no. Cat. no. Weight
(A) (not supplied) (mm2) (not supplied) (kg)
Flexible Rigid
160 NG160 with
rotary handle 28060 NG 70 70 ISO 32 max. KSB 160SM413 KSB 160SM513 8.50
125 NG125 with
rotary handle 19088
(1) The neutral must be protected or not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Maximum diameter by unipolar cable.
KSB 160SMp13
DD202008.eps
DD202155.eps
X = 625.5
DD230650.eps
DD230651.eps
(e.g. circuit-breaker protection)
KSB160SM424
Rating Number Number of Connection Max. cross- Cable gland (4) Cat. no. Cat. no. Weight
(A) of 9 mm 18 mm (3) section (mm2) (not supplied) (kg)
mod. mod. Flexible Rigid
160 48 24 Lugs 35 50 ISO 50 max. KSB 160SM424 KSB 160SM524 10.69
(1) The neutral must be protected or not distributed (3L + PE) for the IT earthing system.
DD230652.eps
X = 650
KSB160SM424
DD230847_r.eps
DB403860.eps
303
395 177
32 450 230
494 308
Cable outlet
Tap-off outlet axis
DB403569.eps
DB403570.eps
(e.g. circuit-breaker
protection)
KSB pppSDFp Rating Type of Fupact Connection Max. size Cable gland (3) Cat. no. Cat. no. Weight
(A) (not supplied) (mm2) (not supplied) (kg)
Flexible Rigid
250 NG160 with INF 70 150 ISO 32 max. KSB 250SDF4 KSB 250SDF6 12.50
rotary handle 28060
400 NG125 with INF 150 240 ISO 40 max. KSB 400SDF4 KSB 400SDF6 18.00
rotary handle 19088
(1) The neutral must be protected or not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Maximum diameter by unipolar cable.
KSB 250SDF
DD202008.eps
DB403763.eps
KSB 400SDF
DB403764.eps
DD210468.eps
protection)
KSB 32CF5 Rating For fuses Connection Max. size Cable gland (3) Cat. no. Weight
(A) (not supplied) (mm2) (not supplied) (kg)
Flexible Rigid
32 NF 10 x 38 Cable clamp 6 10 ISO 32 max. KSB 32CF5 0.60
Type gG: 25 A max. terminals
Type aM: 32 A max.
(1) The neutral must be not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only if N not
distributed).
(3) Maximum diameter for a multipolar cable.
KSB 32CF5
DD202011.eps
Cable exit
Centre line of tap-off outlets
(4) Protruding.
DD210471.eps
protection)
Rating For fuses Connection Max. size Cable gland (3) Cat. no. Cat. no. Weight
KSB pppSFp (A) (not supplied) (mm2) (not supplied) (kg)
Flexible Rigid
50 NF 14 x 51 Cable clamp 25 25 ISO 50 max. KSB 50SF4 KSB 50SF5 2.40
Type gG, 50 A max. terminals
Type aM, 50 A max.
100 NF 22 x 58 Copper cable lugs 50 50 ISO 63 max. KSB 100SF4 KSB 100SF5 5.00
Type gG, 100 A max.
Type aM, 100 A max.
(1) The neutral must be not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only if N not
distributed).
(3) Maximum diameter for a multipolar cable.
Dim. 50 A 100 A
DD210467.eps
A 356 444
B 153 178
C 167 202
D 309 397
E 103 128
F 202 220
X = 432.5 (KSB 50SFp)
X = 545.5 (KSB 100SFp) Cable exit
Centre line of tap-off outlets (4) Protruding.
DD210470.eps
DD210471.eps
(e.g. fuse protection)
KSB 160SEp
KSB 250SEp
KSB 400SEp
Rating For blade-type Connection Max. size Cable gland Cat. no. Cat. no. Weight
(A) fuses (mm2) (not supplied) (kg)
(not supplied) Flexible Rigid
100 Size 00 Copper cable 35 50 ISO 63 (3) KSB 100SE4 (5) KSB 100SE5 (5) 5.00
Type gG, 100 A max. lugs max.
Type aM, 100 A max.
160 Size 00 Copper cable 70 70 ISO 32 (4) KSB 160SE4 KSB 160SE5 11.00
Type gG, 160 A max. lugs max.
Type aM, 160 A max.
Size 0 Copper cable 70 70 ISO 32 (4) KSB 160SF4 KSB 160SF5 11.00
Type gG, 160 A max. lugs max.
Type aM, 160 A max.
250 Size 1 Copper cable 150 150 ISO 40 (4) KSB 250SE4 KSB 250SE5 20.00
Type gG, 250 A max. lugs max.
Type aM, 250 A max.
400 Size 2 Copper cable 240 240 ISO 50 (4) KSB 400SE4 KSB 400SE5 29.20
Type gG, 400 A max. lugs max.
Type aM, 400 A max.
(1) The neutral must be not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only if N not
distributed).
(3) Maximum diameter for a unipolar cable.
(4) Cable gland for multipolar cable only.
(5) For 100A dimensions, see “Tap-off units with insulators for cylindrical fuses”, page 213, cat.
no. KSB 100SFp.
DD210473.eps
A 450 600
B 257 308
C 300 400
D 395 548
E 207 258
F 032 032
G 032 032
X = 577.5 (KSB 160Spp) H 182 192
X = 777 (KSB 250SEp)
X = 855 (KSB 400SEp) &DEOHH[LWRI.6%6pp Centre line of tap-off outlets
&DEOHH[LWRI.6%6(p (6) Protruding
KSB 400SEp
DD210474.eps
DD210468.eps
protection)
KSB 16CN5 Rating For fuses Connection Max. size Cable gland (3) Cat. no. Weight
(A) (not supplied) (mm2) (not supplied) (kg)
Flexible Rigid
16 Neozed E14 Tunnel terminals 6 10 ISO 32 max. KSB 16CN5 0.60
(1) The neutral must be not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only if N not
distributed).
(3) Maximum diameter for a multipolar cable.
KSB 16CN5
DD202295.eps
DD210471.eps
Rating For fuses Connection Max. size Cable gland (3) Cat. no. Cat. no. Weight
(A) (not supplied) (mm2) (not supplied) (kg)
Flexible Rigid
25 Diazed E27 Tunnel terminals 25 25 ISO 50 max. KSB 25SD4 KSB 25SD5 2.40
50 Neozed E18 Tunnel terminals 25 25 ISO 50 max. KSB 50SN4 KSB 50SN5 2.40
63 Diazed E33 Tunnel terminals 25 25 ISO 63 max. KSB 63SD4 KSB 63SD5 2.40
(1) The neutral must be not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only if N not
distributed).
(3) Maximum diameter for a multipolar cable.
KSB ppSpp
Dim. 25 and 63 A
DD202008.eps
DD205037.eps
50 A
A 356 444
B 153 178
C 167 202
D 309 397
E 103 128
X = 432.5 (KSB 25SDp, KSB 50SNp)
X = 545.5 (KSB 63SDp) Cable exit (4) Protruding
Centre line of tap-off outlets
DD210470.eps
DD210471.eps
protection)
KSB160SEp
KSB 250SEp
Rating For blade-type Connection Max. size Cable gland Cat. no. Cat. no. Weight
(A) fuses (mm2) (not supplied) (kg)
(not supplied) Flexible Rigid
100 Size 00 Copper cable 35 50 ISO 63(3) KSB 100SE4(5) KSB 100SE5(5) 5.00
Type gG, 100 A max. lugs max.
Type aM, 100 A max.
160 Size 00 Copper cable 70 70 ISO 32(4) KSB 160SE4 KSB 160SE5 11.00
Type gG, 160 A max. lugs max.
Type aM, 160 A max.
250 Size 1 Copper cable 150 150 ISO 40(4) KSB 250SE4 KSB 250SE5 20.00
Type gG, 250 A max. lugs max.
Type aM, 250 A max.
400 Size 2 Copper cable 240 240 ISO 50(4) KSB 400SE4 KSB 400SE5 29.20
Type gG, 400 A max. lugs max.
Type aM, 250 A max.
(1) The neutral must be not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only if N not
distributed).
(3) Maximum diameter for a unipolar cable.
(4) Cable gland for multipolar cable only.
(5) For 100A dimensions, see “Tap-off units with insulators for cylindrical fuses”, page 213, cat.
no. KSB 100SFp.
DD210473.eps
A 450 600
B 257 308
C 300 400
D 395 548
E 207 258
F 032 032
G 032 032
X = 577.5 (KSB 160SEp) H 182 192
X = 777 (KSB 250SEp)
X = 855 (KSB 400SEp)
&DEOHH[LWRI.6%6(p Centre line of tap-off outlets
&DEOHH[LWRI.6%6(p (6) Protruding
KSB 400SEp
DD210474.eps
DD210468.eps
protection)
KSB 20CG5
Rating For fuses Connection Max. size (mm2) Cable gland (3) Cat. no. Weight
(A) (not supplied) Flexible Rigid (not supplied) (kg)
20 BS88 A1 Cable clamp terminals 6 10 ISO 32 max. KSB 20CG5 0.60
(1) The neutral must be not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only if N not
distributed).
(3) Maximum diameter for a multipolar cable.
KSB 20CG5
DD202295.eps
Cable exit
Centre line of tap-of foutlets
(4) Protruding .
protection)
Rating For fuses Connection Max. size Cable gland Cat. no. Cat. no. Weight
KSB 160SG4
(A) (not supplied) Flexible or rigid (not supplied) (kg)
32 BS88 A1 Cable clamp terminals 25 ISO 50 max.(3) KSB 32SG4 2.40
DD202014.eps
DD202267.eps
A 356 444
B 153 178
C 167 202
D 309 397
E 103 128
F 202 220
KSB 160SG4
X = 432.5 (KSB 32SG4)
DD202015.eps
arrangement
Tap-off polarity 3L + N + PE (1)
Diagram L1 L2 L3 N PE
DD511621.eps
KSB QPF
Protection Lightning arrester Connection Permissible Max. discharge Cat. no. Weight
type cartridges short-circuit current (kg)
(supplied) Isc (kA) Imax (kA)
Type 2 Fixed Pre-wired 6 10 KSB QPF 1.3
SPD (Surge Protection Device) installed: Quick PF10 SPD, 3P+N, cat. no. 16618 (Type 2
PRQREORFNVXUJHDUUHVWHUZLWK¿[HGFDUWULGJHVDQGLQWHJUDWHGGLVFRQQHFWLRQGHYLFHFHUWL¿HG
IEC 81643-1, EN 61643-11).
(1) Also suitable for tap-off unit 3L + PE (N not distributed).
DD511623.eps
KSB QPRD Protection Surge arrester Connection Permissible Max. discharge Cat. no. Weight
type cartridges short-circuit current (kg)
(supplied) Isc (kA) Imax (kA)
Type 2 Removable Pre-wired 25 40 KSB QPRD 3.40
Surge arrester installed: Quick PRD40r surge arrester, 3P+N, cat. no. 16294 (Type 2 monoblock
VXUJHDUUHVWHUZLWK¿[HGFDUWULGJHVDQGLQWHJUDWHGGLVFRQQHFWLRQGHYLFHFHUWL¿HG,(&
EN 61643-11).
(1) Also suitable for tap-off unit 3L + PE (N not distributed).
DD202008.eps
DD511624.eps
167
202
309 108
X= 432.5 158
357
Accessories
IP55
Busbar trunking for medium power
Ue = 230..0.690 V distribution
RAL 9001 white Installation scenario
Installation of a line
DD210704_r.eps
Unload and carry the products inside to an area where
they are not exposed to dust or inclement weather.
Do not store the busbar trunking outdoors.
DD210705.eps
DD210706_r.eps
DD210707.eps
3UHSDUDWLRQRI¿[LQJV
$VVHPEOHWKH¿[LQJEUDFNHWVUHTXLUHGWRLQVWDOOWKH
trunking components.
6HFXUHWKH¿[LQJEUDFNHWVWRVWHHOEHDPV
,QWKLVFDWDORJXH\RXZLOO¿QGDQXPEHURI¿[LQJV
suited to different building structures.
DD210708.eps
3UHSDUDWLRQRIDOLQHVHJPHQWRQWKHÀRRU
DD210710.eps
DD210711.eps
Fit the cover and interconnect the lengths using the
mechanical and electrical jointing system.
/LIWDQGSRVLWLRQWKHOLQHVHJPHQWLQWKH¿[LQJEUDFNHWV
IP55
Busbar trunking for medium power
Ue = 230..0.690 V distribution
RAL 9001 white Installation scenario
DD210715_r.eps
Assemble the mounted trunking sections.
Tap-off connections
DD210716.eps
DD210719.eps
Wire the modular devices and then clip in the tap-off
unit.
,QWKLVFDWDORJXH\RXZLOO¿QGDIXOOUDQJHRIWDSRII
units to cover all protection needs using either circuit
breakers or fuses.
DD210720.eps
IP55
Busbar trunking for medium power
Ue = 230...690 V distribution
RAL 9001 white Assembly of trunking components
DD210840.eps
400 A
DD210841.eps
500 to 1000 A
DD210842.eps
DD205685.eps
400 A
DD210844.eps
500 to 1000 A
DD205686.eps
500 to 1000
DD210847.eps
DD210848.eps
DD205683.eps
Index 3
Introduction 8
Design guides and characteristics 29
Canalis KDP 57
Canalis KBA and KBL industrial luminaires 85
Canalis KBB 113
Canalis KN 139
Canalis KS 175
Presentation
Canalis KS rising mains 230
Medium-power busbar trunking for multi-storey building from 100 to 1000 A 230
Description
Canalis KS, 100 to 1000 A 234
Rising mains 234
Medium-power busbar trunking for multi-storey buildings 234
Installation
Canalis KS, 100 to 1000 A 246
Busbar trunking for medium power distribution 246
Installation scenario 246
Assembly of trunking components 250
Canalis KT 253
7HFKQLFDOVSHFL¿FDWLRQV
Maintenance 267
Recommendations for special applications 273
Catalogue numbers 309
Canalis worldwide 315
PD202212_r.eps
b 7KH¿[LQJV\VWHPLVPDGHXSRI b The tap-off units (with and without isolators) are used to supply loads from 25 to
v bottom support, 400 A.
v ÀRRUJXLGH b Protection using modular or Compact NSX circuit breakers or fuses.
v ÀRRUVXSSRUWVIRUWKHULVHU
PD202214_r.eps
PD202213.eps
&DQDOLV.6FRPSOLHVZLWKsprinkler tests,
guaranteering operation under vertically and
horizontally sprayed water for 50 minutes.
&DQDOLV.6PDNHVLWIDVWDQGHDV\WRXSJUDGHWKHLQVWDOODWLRQ7KHWDSRIIXQLWVFDQ
be removed and handled under energised conditions.
What is more, a line does not require expansion joints since the expansion of
straight lengths is absorbed automatically by the electrical junctions. This technique
HQVXUHVWKDWWKHWDSRIIRXWOHWVRQDOOÀRRUVUHPDLQDYDLODEOH
Installation is made easy due to the design of the jointing units that facilitate
alignment of the straight lengths.
7KHÀRRUGLVWULEXWLRQ &DQDOLV.6HQKDQFHVWKHFRQWLQXLW\RIVHUYLFHEHFDXVH
components in the no maintenance is required on the line. All sliding jointing contacts are lubricated
&DQDOLV.6UDQJHRIIHU3 for the life of the product.
or 4 tap-off outlets per
ÀRRU, enough to have
reserve outlets for future
upgrades.
General
&DQDOLV.6ULVHUVGLVWULEXWHSRZHUWRHDFKÀRRULQPXOWLOHYHOEXLOGLQJVRI¿FH
DD210675.eps
For more detailed description, see “Canalis 100 to 1000 A for power distribution”, in
the “Description” chapter, page 180.
:KHQLQVWDOOHGYHUWLFDOO\WKH&DQDOLV.6GHJUHHRISURWHFWLRQLV,3
C 8VHFXVWRPOHQJWK¿UHEDUULHUVWREORFN¿UHSURSDJDWLRQEHWZHHQÀRRUV7KH\
DOVRSURYLGHWKHPHDQVWRDGMXVWWRWKHGLVWDQFHEHWZHHQÀRRUV
D 8VHVWDQGDUGVWUDLJKWOHQJWKVRUPHWUHVORQJ/HQJWKVDQG¿UHEDUULHUV
can be combined to provide:
Solution 1IRUDGLVWDQFHRIPPWRPPEHWZHHQÀRRUVWKUHHWDSRII
RXWOHWVZLWK.6$pppEV4203 straight lengths,
Solution 2 IRUDGLVWDQFHRIPPWRPPEHWZHHQÀRRUVIRXUWDSRII
RXWOHWVZLWK.6$pppEV4254 straight lengths,
E Use KSB 1000ZV2¿[LQJVWRJXLGHWKHULVHURQHDFKÀRRU
Solution 1: Solution 2:
DD210676.eps
DD210677.eps
2 &XVWRPOHQJWK¿UHEDUULHUOHQJWKV
,QVWDOOHGDWHDFKÀRRUOHYHOWKHVHOHQJWKVHOLPLQDWHDQ\ULVNRI¿UHSURSDJDWLRQ
IURPRQHÀRRUWRDQRWKHUYLDWKHWUXQNLQJ7KHVH¿UHEDUULHUVKDYHEHHQWHVWHGLQ
DFHUWL¿HGODERUDWRU\DQGFRPSO\ZLWKVWDQGDUG(17KHODERUDWRU\
report lists the following results:
b thermal insulation: u 120 minutes
b UHVLVWDQFHWRÀDPHVu 120 minutes
b stability: u 120 minutes.
Provided in custom lengths, these barriers are used with the straight lengths to
DGMXVWWRWKHH[DFWKHLJKWRIHDFKÀRRU
Feed units
Direct supply
The trunking connects directly to a switchboard via a spreader. In this
FRQ¿JXUDWLRQWKHULVHULVVXSSOLHGWKURXJKDKRUL]RQWDOVHFWLRQPDGHRIOHQJWKV
without tap-off outlets.
Fixing systems
4 Bottom support
7KLVFRPSRQHQWDWWDFKHVWRWKH¿UVWMRLQWLQJXQLWDWWKHEDVHRIWKHULVHUDQGLV
secured to the wall by two brackets. It supports the entire riser (see height
limitations on the previous page).
Note. The foot of the riser is a special jointing unit to which a wall bracket is
installed.
5 Guides
These guides, clipped to the riser, maintain it in the vertical position on each
ÀRRU7KH\QRWEORFNDFFHVVWRWKHWDSRIIRXWOHWV
6 Floor supports
6HFXUHGWRWKHÀRRURUZDOOYLD&DQDOLVPPFDQWLOHYHUDUPVWKH\DWWDFK
WRWKHVLGHVRIDVSHFLDOFRPSRQHQWZLWKRUZLWKRXW¿UHEDUULHU
Tap-off units
6WDQGDUG.6WDSRIIXQLWVDUHXVHGVHH&DWDORJXHSDJH
Accessories
Sprinkler kit
To comply with the sprinkler tests (guaranteeing operation under vertically and
horizontally sprayed water for 50 minutes), each electrical jointing system should be
¿WWHGZLWKDUHLQIRUFHGSURWHFWLRQNLWWKHMRLQWLQJVOHHYH
5LVHUFRPSRQHQWV'LVWULEXWLRQWRÀRRUV
DD202092.eps
KSA pppED4081
DD230022.eps
Fire barriers
Without tap-off outlets
Rating Length Barrier position Cat. no. Weight
(A) Dim. l (mm) Dim. x (mm) (kg/m)
250 900 to 2200 450 to 1750 KSA 250ET4AF 8.40
400 900 to 2200 450 to 1750 KSA 400ET4AF 9.90
KSA pppET4AF
DD230023.eps
Transport lengths
Designation Rating (A) Length Cat. no. Weight
Dim. B (mm) (kg)
Transport length 400 3000 KSA 400ET430 18.80
5000 KSA 400ET450 30.00
KSA 400ET430
DD202095.eps
KSA 400ET450
DD202268.eps
KSA 400ET4A
DD202096.eps
Other changes in direction can be made on special order, please consult us.
KSA 100AB4
DD210296.eps
KSA 250AB4
DD210297.eps
KSA 400AB4
DD202270.eps
Cable exit
KSA pppAE4
Dim. 100 to 250 A 400 A
DD230005.eps
A 243 261
B 261.5 279.5
C 108 117
D 278 318
E 294 334
Bottom support
Designation Rating Max. permissible weight (kg) Cat. no. Weight
(A) (kg)
Bottom support 250 680 KSB 250ZV1 4.50
400 680 KSB 400ZV1 5.00
KSB pppZV1
55 mm y Z y 105 mm
DD205078.eps
Floor guide
Used with the bottom support.
Designation Rating (A) Cat. no. Qty included Weight
(kg)
Floor guide All KSB 1000ZV2 5 0.70
)RUÀRRUVKLJKHUWKDQPHWUHVLWLVDGYLVHGWRXVHWZRJXLGHVSHUÀRRU
KSB 1000ZV2
65 mm y A y 95 mm
DD210643.eps
Floor supports
Designation Rating Max. permissible Mounting Cat. no. Qty included Weight
(A) weight (kg) (kg)
6HWRIÀRRUVXSSRUWV All 440 Floor or cantilever KSB 1000ZV3 1 1.80
arm
Cantilever arm, 200 mm All 220 Wall KFB CA81200 4 0.40
)RUÀRRUVKLJKHUWKDQPHWUHVLWLVDGYLVHGWRXVHDÀRRUJXLGHLQDGGLWLRQWRWKHVXSSRUW
DD202193.eps
Tap-off units
Accessories
Spare parts
DD202018.eps
DD202053.eps
KSB 400ZB1
DD205045.eps
KSB 400ZB2
DD205044.eps
KSB 400ZB2
DD202077.eps
KSA pppED4081
DD230024.eps
Fire barriers
Without tap-off outlets
Rating Length Barrier position Cat. no. Weight
(A) Dim. l (mm) Dim. x (mm) (kg/m)
500 900 to 2340 450 to 1890 KSA 500ET4AF 16.60
630 900 to 2340 450 to 1890 KSA 630ET4AF 18.00
800 900 to 2340 450 to 1890 KSA 800ET4AF 19.50
1000 900 to 2340 450 to 1890 KSA 1000ET4AF 24.20
KSA pppET4AF
DD230025.eps
Transport lengths
Designation Rating (A) Length (mm) Cat. no. Weight
(kg)
Transport length 500 3000 KSA 500ET430 33.10
5000 KSA 500ET450 51.50
630 3000 KSA 630ET430 34.60
5000 KSA 630ET450 55.20
800 3000 KSA 800ET430 41.30
5000 KSA 800ET450 66.20
1000 3000 KSA 1000ET430 53.40
5000 KSA 1000ET450 86.50
.6$(7
DD202099.eps
.6$(7
DD202269.eps
.6$(7$
DD202100.eps
Other changes in direction can be made on special order, please consult us.
DD202063.eps
Cable exit
KSA 630AE4
DD202052.eps
KSA 1000AE4
DD202065.eps
Fixing system
Bottom support
Designation Rating Max. permissible weight (kg) Cat. no. Weight
(A) (kg)
Bottom support 500 to 630 1760 KSB 630ZV1 7.00
800 to 1000 1760 KSB 1000ZV1 7.30
KSB pppZV1
55 mm y Z y 105 mm
DD202097.eps
Floor guide
Used with the bottom support.
Designation Rating (A) Cat. no. Qty included Weight
(kg)
Floor guide All KSB 1000ZV2 5 0.70
)RUÀRRUVKLJKHUWKDQPHWUHVLWLVDGYLVHGWRXVHWZRJXLGHVSHUÀRRU
KSB 1000ZV2
65 mm y A y 95 mm
DD210643.eps
Floor support
Designation Rating Max. Mounting Cat. no. Qty included Weight
(A) permissible (kg)
weight (kg)
6HWRIÀRRUVXSSRUWV All 440 Floor or cantilever KSB 1000ZV3 1 1.80
arm
Cantilever arm, 200 mm All 220 Wall KFB CA81200 4 0.60
)RUÀRRUVKLJKHUWKDQPHWUHVLWLVDGYLVHGWRXVHDÀRRUJXLGHLQDGGLWLRQWRWKHVXSSRUW
DD202193.eps
Accessories
Spare parts
DD202018.eps
DD202062.eps
KSB 1000ZB1
KSB 1000ZB2
DD205041.eps
DD205042.eps
KSB 1000ZB2
DD205043.eps
Installation of a line
DD202460.eps
Unload and carry the products inside the building.
Cover the components with plastic tarpaulins to protect
them from dust and moisture.
Do not store the busbar trunking outdoors.
3ODFHDUXQFRPSRQHQWDQGD¿UHEDUULHURQHDFKVWRUH\
of the building.
For protection, leave the trunking components in their
packaging until ready to install.
DD202462.eps
DD202465.eps
,QVWDOOWKH¿UVWUXQFRPSRQHQWRIWKHULVLQJPDLQ$Q800
mm long straight length equipped with a tap-off outlet
makes it possible to supply loads even before passing
WKURXJKWKH¿UVWÀRRU
DD202466.eps
,QVWDOOD¿UHEDUULHULQWKHÀRRUEHWZHHQHDFKVWRUH\RI
the building.
DD202468.eps
DD202469.eps
Fit the cover and interconnect the components using
the mechanical and electrical jointing system.
DD202470.eps
DD202471.eps
Mount the guide brackets on the wall.
DD202472.eps
3RVLWLRQWKH&DQDOLV.6WUXQNLQJLQWKHJXLGHEUDFNHWV
DD202473.eps
Place the packed tap-off units on each storey of the
building.
DD202474.eps
Switch-on
DD202476_r.eps
IP55
Busbar trunking for medium power
Ue = 230..0.690 V distribution
RAL 9001 white Assembly of trunking components
DD205755.eps
DD210854.eps
Index 3
Introduction 8
Design guides and characteristics 29
Canalis KDP 57
Canalis KBA and KBL industrial luminaires 85
Canalis KBB 113
Canalis KN 139
Canalis KS 175
Canalis KS riser 229
Presentation
Canalis KT busbar trunking 254
For high power feeders and distribution from 800 to 5000 A 254
7HFKQLFDOVSHFL¿FDWLRQV
Maintenance 267
Recommendations for special applications 273
Catalogue numbers 309
Canalis worldwide 315
PD202431_r.eps
PD202317_r.eps
PD202312_r.eps
PD202328.eps
PD202318_r.eps
PD202314_r.eps
PD202300_r.eps
DD202142_r.eps
LQFDVHRI¿UH &DQDOLV.7EXVEDUWUXQNLQJRIIHUVDQIP55 degree of
$OOFRPSRQHQWVLQWKH.7 protection.
range are halogen free ,WLVGHVLJQHGWRSUHYHQWWKHHQWU\RIZDWHUIURP¿UH
and contain no PVCs. In protection sprinklers.
FDVHRI¿UH&DQDOLV.7 This high degree of protection means it can be installed
does not release smoke in all types of buildings and in all positions.
RUWR[LFJDVHV&DQDOLV.7
is also a EDVLF¿UH Excellent contact
barrier. The trunking thus
Excellent contact is ensured by the use of Copral-inside technology.
contributes to containing
The electrical contacts are made of a silver-plated aluminium/copper laminate
D¿UHE\SUHYHQWLQJWKH
(Copral).
SURSDJDWLRQRIÀDPHVIRU
The initial performance level is maintained throughout the entire life of the
two hours.
installation.
PD202241_r.eps
Easy installation
The equipment comes
ready to install.
Easy to connect and test,
the trunking solution cuts
installation time in half
compared to cable
solutions.
In addition, the small size
RI&DQDOLV.7UHGXFHVWKH
space requirements to a
minimum
DD202145_r.eps
An interlocking device assistance, by
prevents mounting errors your side
and makes it impossible
Our staff and tools are
to install or remove an
available to help you in
energised tap-off unit.
choosing and installing
IPxxD ensures totally
&DQDOLV.7EXVEDU
safe working conditions
trunking.
for maintenance
Our specialists and our
personnel because live
production and
parts are not accessible.
distribution centres
guarantee fast service
and quality.
upgrading 7DSRIIXQLWVRIWKH&DQDOLV.6UDQJHDUHWRWDOO\
possibilities FRPSDWLEOHZLWKWKRVHRIWKH&DQDOLV.7UDQJH
b they cover all your needs:
&DQDOLV.7PDNHVLWIDVW
v &DQDOLV.6WDSRIIXQLWV$WR$
and easy to upgrade the
v &DQDOLV.7WDSRIIXQLWV$WR$
installation. Tap-off units
b protection is possible using circuit breakers or fuses.
can be added or removed
on live installations,
without stopping
operations.
Intelligent tap-off units
b They monitor the installation to avoid overloads and ensure continuity of service.
b They can meter the energy consumed for precise management of your electrical
distribution system (cost allocation for each consumer).
Index 3
Introduction 8
Design guides and characteristics 29
Canalis KDP 57
Canalis KBA and KBL industrial luminaires 85
Canalis KBB 113
Canalis KN 139
Canalis KS 175
Canalis KS riser 229
Canalis KT 253
7HFKQLFDOVSHFL¿FDWLRQV
Canalis KDP, 20 A 260
Canalis KBA, 25 and 40 A 261
Canalis KBB, 25 and 40 A 262
Canalis KN, 40 to 160 A 263
Canalis KS, 100 to 1000 A 264
Rising mains 265
Maintenance 267
Recommendations for special applications 273
Catalogue numbers 309
Canalis worldwide 315
Fire resistance:
b Materials resistant to abnormal heat (glow-wire test as per IEC 60695-2).
b Class C2 for the halogen free version.
All plastic components are halogen free.
Straight lengths constitute the basic structure of the line and are made up of:
b a ribbon cable (1ZLWKWKUHHRU¿YHPP2conductors made of tinned copper.
Conductor insulation and sheathing are made of cross-linked polyethylene (XLPE)
b tap-off outlets (2IDFWRU\¿WWHGDWUHJXODULQWHUYDOV&RPSOLDQWZLWKVWDQGDUG
,(&WKH\FDQVXSSO\OXPLQDLUHVXQGHUOLYHFRQGLWLRQVXVLQJ.%$DQG.%%
tap-off units.
Other line components:
b WKH¿[LQJV\VWHP3) used to attach the line to the sides of cable trays, metal
structures or directly to concrete slabs
b 10 A tap-off units (4), pre-wired or not, with phase selection, or 16 A tap-off units
with or without fuses, used to supply luminaires under live conditions
b a range of prefabricated tap-off units for local control of luminaires for single and
double-circuit switching, two-way switching and impulse switches.
Fire resistance:
b 5HVLVWDQWWRÀDPHSURSDJDWLRQLQFRPSOLDQFHZLWKVWDQGDUG,(&SDUW
b Materials resistant to abnormal heat (glow-wire test as per IEC 60695-2).
All plastic components are halogen free.
Straight lengths constitute the basic structure of the line and are made up of:
b a carrier casing (1), crimp closed, made of hot-galvanised sheet steel, pre-
lacquered RAL 9003 white. This casing also serves as the protective earth conductor
(PE)
b a ribbon cable with two or four insulated conductors made of copper, 2.5 mm2 for
25 A and 6 mm2 for 40 A
b tap-off outlets every 0.5, 1 or 1.5 metre, on both sides of the trunking
b an additional twisted cable (2 x 0.75 mm2, remote-control circuit) on request.
b an electrical jointing unit ensuring automatic and simultaneous connection of all
live conductors. The contacts are clamp + spring type and exert no forces on the
plastic parts. The jointing unit is maintenance free
b a mechanical jointing unit ensuring rigid assembly of two components.
The continuity of the protection conductor is ensured automatically. Proper tightening
at the end of the assembly operation is ensured by a captive screw with a notched
base (2). The two components are instantly assembled. Electrical and mechanical
jointing is carried out simultaneously.
Other line components:
b WKH¿[LQJV\VWHP3IRUVXSSRUWLQJRIERWKWUXQNLQJDQGOXPLQDLUHVZLWK¿QDO
automatic locking around the trunking.
7KHPD[LPXPGLVWDQFHEHWZHHQWZR¿[LQJSRLQWVLVWKUHHPHWUHV
The luminaires can be installed at any point on the line (including the jointing units),
b 10 A tap-off units (4), pre-wired or not, with phase selection, or 16 A tap-off units
with or without fuses, used to supply luminaires under live conditions
b the cable-support system (5) for running adjacent circuits such as telephone lines,
emergency lighting, etc.
b ÀH[LEOHOHQJWKVWRFKDQJHGLUHFWLRQRUDYRLGREVWDFOHV
Fire resistance:
b 5HVLVWDQWWRÀDPHSURSDJDWLRQLQFRPSOLDQFHZLWKVWDQGDUG,(&SDUW
b Materials resistant to abnormal heat (glow-wire test as per IEC 60695-2).
All plastic components are halogen free.
Straight lengths constitute the basic structure of the line and are made up of:
b a carrier casing (1), crimp closed, made of hot-galvanised sheet steel, pre-
lacquered RAL 9003 white. This casing also serves as the protective earth conductor
(PE)
b one or two ribbon cables with two or four insulated conductors made of copper, 2.5
mm2 for 25 A and 6 mm2 for 40 A
b tap-off outlets every 0.5 or 1 metre, on both sides of the trunking
b an additional twisted cable (2 x 0.75 mm2, remote-control circuit) on request,
b an electrical jointing unit ensuring automatic and simultaneous connection of all
live conductors. The contacts are clamp + spring type and exert no forces on the
plastic parts. The jointing unit is maintenance free
b a mechanical jointing unit ensuring rigid assembly of two components.
The continuity of the protection conductor is ensured automatically. Proper tightening
at the end of the assembly operation is ensured by a captive screw with a notched
base.
The two components are instantly assembled.
Electrical and mechanical jointing is carried out simultaneously (2).
Other line components:
b WKH¿[LQJV\VWHP3IRUVXSSRUWLQJRIERWKWUXQNLQJDQGOXPLQDLUHVZLWK¿QDO
automatic locking around the trunking.
7KHPD[LPXPGLVWDQFHEHWZHHQWZR¿[LQJSRLQWVLV¿YHPHWUHV
The luminaires can be installed at any point on the line (including the jointing units).
b 10 A tap-off units (4), pre-wired or not, with phase selection, or 16 A tap-off units
with or without fuses, used to supply luminaires under live conditions
b the cable-support system (5) for running adjacent circuits such as telephone lines,
emergency lighting, etc.
b ÀH[LEOHOHQJWKVWRFKDQJHGLUHFWLRQRUDYRLGREVWDFOHV
Fire resistance:
b 5HVLVWDQWWRÀDPHSURSDJDWLRQLQFRPSOLDQFHZLWKVWDQGDUG,(&SDUW
b Materials resistant to abnormal heat (glow-wire test as per IEC 60695-2).
All plastic components are halogen free.
Straight lengths constitute the basic structure of the line and are made up of:
b an enclosure (1), made of sheet steel, galvanised and painted RAL 9001, serving
as the protective conductor (PE)
b four aluminium conductors supported along their entire length by an insulator.
All electrical contacts are made of silver-plated copper
b three additional copper conductors (3 x 2.5 mm2, remote-control circuit) on
request
b tap-off outlets every 0.5 or 1 metre, on one side of the trunking. The tap-off outlets
(2) are equipped with automatic shutters that avoid accidental contact with live parts
b a eletrical jointing unit (3ZLWKÀH[LEOHFRQWDFWVIRUWKHHOHFWULFDOMXQFWLRQEHWZHHQ
two components. These contacts are designed to adapt to the difference in
expansion between the conductors and the enclosure
b an mechanical jointing unit (3) for the mechanical junction between two
components with four captive screws that also ensure the continuity of the protective
conductor. The jointing unit is maintenance free.
Other line components:
b WKH¿[LQJEUDFNHWV4GHVLJQHGIRUVXVSHQVLRQRU¿[LQJWRDZDOOHYHU\PHWUHV
XQOHVVRWKHUZLVHVSHFL¿HG
b the tap-off units (5) with the following characteristics:
v the contact of the protective conductor ensures automatic opening of the shutters
and feeds the tap-off unit
v ZKHQWKHWDSRIIXQLWLVSOXJJHGLQWKHHDUWKLQJFRQWDFWFRQQHFWV¿UVWIROORZHGE\
the phases
v there is no access to live parts when the cover of the tap-off unit is open
QR¿QJHUDFFHVV,3[[%
v tap-off units can be equipped with fuses or modular device,
v trunking and tap-off units can be equipped with colour-coded interlocking devices
to restrict connection to certain tap-off units
b ÀH[LEOHOHQJWKV6) to change direction or avoid obstacles.
Fire resistance:
b Fire barriers as per standard ISO 834 (DIN 4102-part 9) for passages through
partitions.
b 5HVLVWDQWWRÀDPHSURSDJDWLRQLQFRPSOLDQFHZLWKVWDQGDUG,(&SDUW
b Materials resistant to abnormal heat (glow-wire test as per IEC 60695-2).
All plastic components are halogen free.
b The enclosure (1), made of sheet steel, galvanised and pre-lacquered RAL 9001
white.
b 7KHIRXUDOXPLQLXPFRQGXFWRUVDUHPRXQWHGRQ¿EUHJODVVUHLQIRUFHGSRO\HVWHU
insulators. All electrical contacts are made of silver-plated copper.
b The straight lengths have a tap-off unit (2) every metre on both sides.
The tap-off outlets are equipped with automatic shutters that avoid accidental contact
with live parts. The protective conductor is electrically connected to the enclosure at
each jointing unit,
b (OHFWULFDOFRQWDFWEHWZHHQWZRFRPSRQHQWVLVHQVXUHGE\ÀH[LEOHFRQWDFWV
designed to adapt to the difference in expansion between the conductors and the enclosure.
It is possible to check visually that the electrical contact is effective.
The mechanical junction between two components is ensured by four captive screws.
The jointing unit (3) is maintenance free.
b 7KHULJLGLW\RIWKHVWUDLJKWOHQJWKVLVVXI¿FLHQWWKDW¿[LQJSRLQWV4) are required only
every three metres (excepting special conditions).
b Special components (5) are available to change direction or avoid obstacles.
b The tap-off units (6) have the following characteristics:
v connection and disconnection are possible only with the cover open
v the contact of the protective conductor ensures automatic opening of the shutters
and feeds the tap-off unit
v there is no access to live parts when the cover of the tap-off unit is open
QR¿QJHUDFFHVV,3[[%
v ZKHQWKHWDSRIIXQLWLVSOXJJHGLQWKHHDUWKLQJFRQWDFWFRQQHFWV¿UVWIROORZHGE\
the phases
v it is not possible to close the cover before the tap-off unit is mechanically locked on
the trunking
v tap-off units can be equipped with fuses, modular devices or moulded case circuit
breakers.
5LVLQJPDLQVIRUSRZHUGLVWULEXWLRQLQEXLOGLQJVZLWKPRUHWKDQRQHÀRRU
PD202341_r.eps
Fire resistance:
b Fire barriers as per standard ISO 834 (EN 1363-1, EN 1366-3) for passages
through partitions (slabs for exemple).
b 5HVLVWDQWWRÀDPHSURSDJDWLRQLQFRPSOLDQFHZLWKVWDQGDUG,(&SDUW
b Materials resistant to abnormal heat (glow-wire test as per IEC 60695-2).
All plastic components are halogen free.
b The enclosure (1), made of sheet steel, galvanised and pre-lacquered RAL 9001
white.
b 7KHIRXUDOXPLQLXPFRQGXFWRUVDUHPRXQWHGRQ¿EUHJODVVUHLQIRUFHGSRO\HVWHU
insulators. All electrical contacts are made of silver-plated copper.
b The straight lengths have a tap-off unit (2) every 0.5 metre on one side. There are
IRXUWDSRIIXQLWVSHUÀRRUIRUÀRRUKHLJKWVEHWZHHQDQGPHWUHVRUWKUHH
WDSRIIXQLWVSHUÀRRUIRUÀRRUKHLJKWVOHVVWKDQPHWUHV7KHWDSRIIRXWOHWVDUH
equipped with automatic shutters that avoid accidental contact with live parts.
The protective conductor is electrically connected to the enclosure at each jointing
unit.
b (OHFWULFDOFRQWDFWEHWZHHQWZRFRPSRQHQWVLVHQVXUHGE\ÀH[LEOHFRQWDFWV
designed to adapt to the difference in expansion between the conductors and the
enclosure. It is possible to check visually that the electrical contact is effective.
The mechanical junction between two components is ensured by four captive screws.
The jointing unit (3) is maintenance free.
b $¿UHEDUULHU4) can be installed when the riser passes through a slab to avoid any
ULVNRI¿UHSURSDJDWLRQIURPRQHÀRRUWRDQRWKHUYLD&DQDOLV.6WUXQNLQJ
7ZRKRXU¿UHUHVLVWDQFH$LVSURYLGHGLQFRPSOLDQFHZLWKVWDQGDUG,62
b Special components (5) are available to change direction or avoid obstacles.
b The riser can be maintained by a special bottom support (6) or a spring-based
¿[LQJGHYLFHRQHDFKÀRRURIWKHEXLOGLQJGHSHQGLQJRQWKHKHLJKWRIWKHEXLOGLQJ
b The tap-off units (7) have the following characteristics:
v connection and disconnection are possible only with the cover open
v the contact of the protective conductor ensures automatic opening of the shutters
and feeds the tap-off unit
v there is no access to live parts when the cover of the tap-off unit is open
QR¿QJHUDFFHVV,3[[%
v ZKHQWKHWDSRIIXQLWLVSOXJJHGLQWKHHDUWKLQJFRQWDFWFRQQHFWV¿UVWIROORZHGE\
the phases
v it is not possible to close the cover before the tap-off unit is mechanically locked on
the trunking
v tap-off units can be equipped with modular devices or moulded case circuit
breakers.
Index 3
Introduction 8
Design guides andCharacteristics 29
Canalis KDP 57
Canalis KBA and KBL industrial luminaires 85
Canalis KBB 113
Canalis KN 139
Canalis KS 175
Canalis KS riser 229
Canalis KT 253
7HFKQLFDOVSHFL¿FDWLRQV
Maintenance
Maintenance recommendationsfor your installation 268
Feed units
DD205757.eps
They are equipped with anti-shear tunnel terminals for copper cables up to 10 mm2.
As for all screw-type connections, it is advised to check tightness one year after
installation and then at longer intervals.
)RU.%$DQG.%%WUXQNLQJWKHIHHGXQLWVDUHMRLQWHGWRWKH¿UVWUXQFRPSRQHQWRI
the line (see next paragraph). This connection is maintenance free.
Run components
DD205758.eps
)RU&DQDOLV.'3WKHUXQFRPSRQHQWVDUHRQHSLHFHOHQJWKVGUDZQIURPDPHWUH
reel. No joints are required.
)RU&DQDOLV.%$DQG.%%UXQFRPSRQHQWVDUHLQWHUFRQQHFWHGE\HOHFWULFDOMRLQWLQJ
units ensuring automatic and simultaneous connection of all live conductors.
The contacts are clamp + spring type and exert no forces on the plastic parts.
The electrical contacts of the jointing unit and the conductors are made of copper.
Components can be dismantled and reused.
Run components for all types of busbar trunking are maintenance free.
Tap-off units
DD205759.eps
They are the clamp type, made of bronze with tinned beryllium to ensure optimum
mechanical rigidity and contact quality. The contacts do not press or apply any forces
on the plastic parts. They connect to the active line conductors at the tap-off outlets.
The conductors are made of tinned copper.
These components are maintenance free.
)RU&DQDOLV.%$DQG.%%FLUFXLWVVXSSOLHGE\WKH$WDSRIIXQLWVDUHFRQQHFWHG
via tunnel terminals. As for all screw-type connections, it is advised to check
tightness one year after installation and then run checks at longer intervals.
b Luminaire cleaning
During operation, in both industrial and commercial environments, the luminaires
become dirty and illuminance is reduced. Cleaning of luminaires restores the initial
level of illuminance.
*RRGOLJKWLQJFRQWULEXWHVWRWKHSUR¿WDELOLW\RIDQ\EXVLQHVV
v ¿QDQFLDOJDLQVEHFDXVHDWWHQWLRQSDLGWRWKHTXDOLW\RIOLJKWLQJLVSDUWRIDZLGHU
analysis on operating costs and installation maintenance
v productivity gains, because good lighting improves working conditions and quality
control of products or operations
v gains in employee satisfaction, through enhanced comfort and less visual fatigue
and risk of accidents
v environmental gains, because good lighting means less energy consumed and
often fewer lamps to replace and dispose of.
b Tube replacement
7KLVFRQVLVWVRIFKDQJLQJWXEHVDQGVWDUWHUVIRUÀXRUHVFHQWOXPLQDLUHVDQGEXOEVIRU
discharge lamps.
Advantages of Canalis
Because the luminaires are mounted on trunking and supplied by tap-off units, they
can be easily removed for cleaning and changing at ground level, then put back.
It is also possible to have spare units for immediate replacement of luminaires,
followed by cleaning and bulb changing of the removed luminaires that then become
the spare units.
Feed units
DD202298.eps
Run components
DD202299.eps
Tap-off units
DD205764.eps
7UXQNLQJFRQWDFWVDUHÀH[LEOHPDGHRIVLOYHUSODWHGFODPSVSURYLGLQJRSWLPXP
contact quality. The contacts do not press or apply any forces on the plastic parts.
They connect to the live line conductors at the tap-off outlets. Conductors are made
of silver-plated copper at the point of contact.
These components are maintenance free.
The connections for outgoing cables are made to terminals or using lugs.
As for all screw-type connections, it is advised to check tightness one year after
installation and then run checks at longer intervals.
Feed units
DD202301.eps
They are equipped with terminals up to 100 A and lug connectors for higher ratings.
As for all screw-type connections, it is advised to check tightness one year after
installation and then run checks at longer intervals.
7KHIHHGXQLWVDUHMRLQWHGWRWKH¿UVWUXQFRPSRQHQWRIWKHOLQHVHHQH[WSDUDJUDSK
This connection is maintenance free
Run components
DD202302.eps
Tap-off units
DD202303.eps
7UXQNLQJFRQWDFWVDUHÀH[LEOHPDGHRIVLOYHUSODWHGFODPSVSURYLGLQJRSWLPXP
contact quality. The contacts do not press or apply any forces on the plastic parts.
They connect to the live line conductors at the tap-off outlets. Conductors are made
of silver-plated copper at the point of contact.
These components are maintenance free.
The connections for outgoing cables are made to terminals or using lugs.
As for all screw-type connections, it is advised to check tightness one year after
installation and then run checks at longer intervals.
Visual check
Cleaning
It is advised to check annually that trunking is clean and to remove any dust, water,
oil or other conducting substances or objects from sensitive zones such as junctions,
tap-off outlets and tap-off units.
External appearance
Check the external appearance of the trunking to detect:
b signs of shocks, in which case it is necessary to check the degree of protection
to avoid any risk of insulation faults
b anomalies, i.e. incorrect implementation of the trunking (incorrect supports, etc.)
b traces of corrosion (in particular on supports).
Index 3
Introduction 8
Design guides and characteristics 29
Canalis KDP 57
Canalis KBA and KBL industrial luminaires 85
Canalis KBB 113
Canalis KN 139
Canalis KS 175
Canalis KS riser 229
Canalis KT 253
7HFKQLFDOVSHFL¿FDWLRQV
Maintenance 267
Coordination
Preface 285
Advantages of the Schneider Electric system 286
Trunking protection 287
Overload protection 287
Short-circuit protection 289
Circuit breaker/trunking coordination 290
Non-limiting or time-delayed circuit breakers 290
Limiting circuit breakers 291
BTS protection by Compact NSX limiting circuit breakers 292
Selection guides 293
Lighting control with Canalis KNT 296
Self-contained emergency lighting units 297
Lighting with dimming control 299
Lighting controlled by proximity sensors 301
Lighting controlled by a timer or impulse relay 303
Measurements and metering 305
Transparent Ready units 305
TR tap-off unit 307
Where:
b the power dissipated as heat: Pac = 3 x R x Iac² where:
v R= resistance of a conductor
v Iac = conductor rms current
b the dissipated power for 4 conductors: Pdc = 4 x R x Idc² where:
v Idc = direct current.
Selection table
b 1 source
Case of 2 conductors in parallel for the + and 2 conductor in parallel for the – (only
1 circuit in the busbar trunking):
DD210893.eps
b 2 sources
Case of 1 conductor for the + and 1 conductor for the – (2 circuits possible in the
same busbar trunking):
DD210894.eps
8VHZLWKVSHFL¿FVZLWFKJHDU
A quick rise in arcing voltage can be achieved by using series fuses, one fuse on
the + and one fuse on the – of each circuit.
For some current rating and fuse characteristics, the placing of two fuses in series
RQHDFKSRODULW\PD\EHVSHFL¿HGKLJKO\LQGXFWLYHFLUFXLW
In some cases, two fuses must be placed in parallel for each polarity.
$VGH¿QHGLQVWDQGDUGV,(&DQG,(&DQG
Method
Application of an incandescent wire for 30 seconds on the insulating materials in
contact with live parts.
Result criteria
The specimen is considered to have passed the incandescent wire test if:
b LIWKHUHLVQRYLVLEOHÀDPHDQGQRVXVWDLQHGLQFDQGHVFHQFH
b WKHVSHFLPHQ¶VÀDPHVDQGLQFDQGHVFHQFHJRRXWZLWKLQVHFRQGVRIWKH
incandescent wire being removed.
$VGH¿QHGLQVWDQGDUGV,(&DQG,(&SDUW
Method
b $SSOLFDWLRQRIDÀDPHIRUPLQXWHVRQDVWUDLJKWOHQJWKRIEXVEDUWUXQNLQJ
whose centre is located 2.5 metres from the edge of the burner.
Result criteria
The specimen is considered to have passed the test if:
b combustion does not occur
b the maximum extent of the burned part (external and internal) of the busbar
trunking does not go beyond 2.5 metres above the lower edge of the burner.
$VGH¿QHGLQVWDQGDUG(1(1,62',1SDUW
Method
7KH¿UHEDUULHUEXVEDUWUXQNLQJVHFWLRQWREHWHVWHGLVSODFHGLQDQRYHQZKLFK
executes a standardised temperature-time curve.
Result criteria
The specimen is considered to have passed the test if:
b WKHUHDUHQRÀDPHVEHKLQGWKH¿UHEDUULHU
b WKHUHLVQRVPRNHRUJDVEHKLQGWKH¿UHEDUULHUQRWUHTXHVWHGE\WKHVWDQGDUG
can appear as a remark in the test report)
b WKHWHPSHUDWXUHULVHRIWKHFDVLQJEHKLQGWKH¿UHEDUULHUGRHVQRWH[FHHG&
Origin of harmonic currents Harmonic currents are caused by non-linear loads connected to distribution systems,
i.e. by loads that draw current with a waveform different that that of the voltage that
supplies them.
7KHPRVWFRPPRQQRQOLQHDUORDGVDUHHTXLSPHQWLQFOXGLQJUHFWL¿HUVÀXRUHVFHQW
lighting and computer hardware.
,QLQVWDOODWLRQVZLWKDGLVWULEXWHGQHXWUDOQRQOLQHDUORDGVPD\FDXVHVLJQL¿FDQW
overloads in the neutral conductor due to the presence of third-order harmonics.
Harmonic order
DD210679.eps
The order is the ratio
between the harmonic
frequency fn and the
fundamental frequency
(generally the power
frequency, 50 or 60 Hz):
n = fn / f1
%\GH¿QLWLRQWKH
fundamental f1 is order 1
(H1).
Third-order harmonics
(H3) have a frequency of
150 Hz (when f1 = 50 Hz).
Estimating THD (total harmonic The presence of third-order harmonics depends on the applications involved.
distortion) It is necessary to carry out an in-depth study on each non-linear load to determine
the level of H3:
ih3 (%) = 100 x i3 / i1
b i3 = rms current of H3
b i1 = rms current of the fundamental
Assuming that H3 is preponderant among harmonics, the THD is close to the value
of H3 (ih3(%)).
PD202029.eps
Workshops 2I¿FHV
Mix of disturbing loads (computers, 1XPHURXVGLVWXUELQJORDGVFRPSXWHUV
836VÀXRUHVFHQWOLJKWLQJDQG 836VÀXRUHVFHQWOLJKWLQJ
non-disturbing loads (motors, pumps,
heating).
DD210681.eps
trunking
1RFXUUHQWLQWKHQHXWUDO
The conductors are correctly sized.
DD210683.eps
ih1 (50 Hz) and
33 % H3
DD210682.eps
Busbar-trunking selection
THD y 15 % 15 % < THD y 33 % THD > 33 %Busbar trunking Rating (A)
25 20 16 KBA / KBB 25
40 32 25 KBA / KBB 40
KN 40
63 50 40 KN 63
100 80 63 KN 100
KS 100
160 125 100 KS 160
250 200 160 KS 250
400 315 250 KS 400
500 400 315 KS 500
630 500 400 KS 630
800 630 500 KS 800
1000 800 630 KS 1000
Example: for a total rms current of 376 A, (estimation based on power drawn by loads, including
harmonics), the operational current is 400 A.
THD is estimated at 30 %. The appropriate trunking is KS 500 A.
For more information on harmonics See the Cahier Technique publications on the Schneider Electric web site:
www.schneider-electric.com
Foreword Prefabricated electrical trunking components expand and contract due to:
b changes in ambient temperature (e.g. summer and winter)
b FXUUHQWÀRZLQJLQWKHFRQGXFWRUVHJWR,Q
)RUH[DPSOHFRQVLGHUDPHWUHORQJ$&DQDOLV.6OLQHHTXLSSHGZLWKWHQ
160 A tap-off units and installed under the roof of a building where the ambient
temperature varies by more than 30 °C between summer and winter:
b just the change in the ambient temperature results in an expansion of 20 mm for
the conductors and the 10 mm for the casing
b at a constant ambient temperature, the temperature rise in the conductors every
morning when the installation is started (increase in current from 0 to In = 800 A)
results in an expansion of 55 mm for the conductors and 7 mm for the casing.
The lengths of the sheet steel (1) and the aluminium conductors (2) therefore vary as
DIXQFWLRQRIWKHFKDQJHVLQWHPSHUDWXUHDQGWKHLUVSHFL¿FWKHUPDOH[SDQVLRQ
FRHI¿FLHQWV
PD202309_r.eps
For this reason, Canalis components are designed so that these phenomena do not
affect their installation or operation.
DD202282.eps
1 Spring of clamps.
DD202283.eps
2 Copper area.
3 Silver plated copper.
Conclusion: at both the jointing system and the tap-off outlets, sliding contacts can
handle the expansion of the conductors.
These maintenance-free silver-plated contacts are guaranteed for life.
Only the expansion of the sheet steel must be taken into account for Canalis
installation, however the problem is minor because both trials and
calculations show that expansion is only approximately 1 mm for every
three-metre length under extreme operating conditions.
)RUD¿[HGSRLQWFDXVHGE\DEORFNHGHOERZIRUH[DPSOHWKHFDVLQJVFRPSHQVDWH
their expansion by slight lateral movement (0.7 mm maximum) on either side of the
longitudinal axis. This movement has no impact on the contact quality of the jointing
system or on the IP.
5LVLQJPDLQVZLWKVSULQJEDVHG¿[LQJGHYLFHV2)
)RUULVLQJPDLQVZLWKVSULQJEDVHG¿[LQJGHYLFHVRQO\WKHULVHUH[SDQGVERWK
XSZDUGVDQGGRZQZDUGV$WHDFKÀRRUWKHFDVLQJVLGHVQDWXUDOO\WKURXJKWKH¿UH
barriers.
What is a sprinkler?
designed to deliver water when the temperature to which it is subjected exceeds its
calibration value.
The main aim of the installation is to lower the temperature in the accident area by
ZHWWLQJWKHLJQLWHGDQGDGMDFHQWPDWHULDOVE\VSUD\LQJZDWHULQWKHIRUPRI¿QH
droplets.
The transformation of these droplets into water vapour captures a lot of energy from
WKH¿UHDQGH[WLQJXLVKHVLWTXLFNO\0RUHRYHUWKLVLQFUHDVHGYROXPHSUHYHQWVDLU
IURPÀRZLQJWRWKHKHDUWRIWKH¿UH
:KHQD¿UHGHYHORSVDPELHQWWHPSHUDWXUHULVHVWRUHDFKWKHFDOLEUDWLRQYDOXH
:DWHUWKHQOHDYHVWKHVSULQNOHURSHQLQJDQGVWULNHVDGHÀHFWRUWKDWSURMHFWVLWRQWR
WKH¿UHLQDFHUWDLQIRUP*URXQGFRYHUDJHUDQJHVEHWZHHQDQGPðDFFRUGLQJ
to mounting height.
A sprinkler delivers between 60 and 120 l/min according to the hazard class.
On nuisance tripping lasting a few minutes, some hundreds of litres of water are
released. IPx5 approval as per standard
IEC 60529 does not guarantee non ingress of water in the busbar trunking in these
conditions, as the water volumes, test duration and projection distance vary (nozzle
22.5 mm in diameter, at a distance of 2.5-3 m, with a water volume of 12.5l/min for
1min/m² for at least 3 min).
To provide you with all necessary safety guarantees, Schneider Electric has chosen
to go further still than the IP55 test by subjecting its busbar trunking to an extremely
severe “sprinkler” test.
PD202443_r.eps
Chronology
PD202442.eps
In view of the absence of reference standard for sprinkler tests, we have chosen to
apply the following procedure:
b insulation resistance test (1000 V)
b dielectric properties test (2.5 kV, 5 s: IEC 60439-1 & 2)
b water projection
b 5 min break
b insulation resistance test (1000 V)
b dielectric properties test (2.5 kV, 5 s: IEC 60439-1 & 2).
Water projection,
FRQ¿JXUDWLRQVZLWKRUZLWKRXWHQHUJLVDWLRQ
b horizontally installed busbar trunking:
v PLQZDWHUSURMHFWLRQZLWKVSULQNOHUW\SH.:HUW1)ôEDU/PLQ
v PLQZDWHUSURMHFWLRQZLWKVSULQNOHUW\SH.:HUW1)ôEDU/PLQ
b vertically installed busbar trunking:
v PLQZDWHUSURMHFWLRQZLWKVSULQNOHUW\SH.:HUW1)òEDU/PLQ
v PLQZDWHUSURMHFWLRQZLWKVSULQNOHUW\SH.:HUW1)òEDU/PLQ
Canalis KS and sprinkler.
Mounting position
The distance between the sprinkler head and the busbar trunking is 500 mm.
DD205063_r.eps
1 Sprinkler
2 Pressure gauge
3 Closing valve
4 Tap-off unit.
5 Busbar trunking
7HVWFRQ¿JXUDWLRQ
DD205064_r.eps
Test results
%XVEDUWUXQNLQJV.'3.%$.%%.1DQG.6KDYHXQGHUJRQHWKHVSULQNOHUWHVW
This test, if successful, proves that our busbar trunkings can operate during and
immediately after sprinkling of a line by a sprinkler for a period of 50 min.
Canalis is part of a comprehensive offering of Optimum system performance is ensured by coordination between the protection
Schneider Electric products designed to operate circuit breakers and the Canalis prefabricated busbar trunking used for decentralised
together. In particular, this offering covers all low and distribution.
medium voltage electrical distribution components. 'HFHQWUDOLVHGHOHFWULFDOGLVWULEXWLRQZLWKWRWDOFRRUGLQDWLRQSHUIHFWO\VDWLV¿HV
all your requirements in terms of safety, continuity of service, upgradeability
and simplicity.
In the following pages, we will present the advantages of the Schneider Electric
system as well as the selection guide tables that ensure coordination between
circuit breakers and Canalis busbar trunking.
PD202357_SE.eps
Tap-off units b The Canalis tap-off units of the Schneider Electric system satisfy operator
needs in terms of:
v installation upgradeability without production downtime
PD202333_SE.eps
v continuity of service
v safety.
b Switch-disconnectors comply with the IEC 60947-3 standard and are designed
to ensure AC23 load breaking and isolation.
Their protection is guaranteed by coordination with the upstream circuit breakers.
Selection of busbar trunking with The busbar trunking rating can be optimised when the trunking is protected by circuit
respect to protective device ratings breakers rather than fuses.
To take into account busbar trunking thermal overload protection, the various
protection switchgear technologies and the currents under overload conditions
must be considered.
The sizing characteristics for the choice of busbar trunking and overload
protection are:
Example:
DD210602en.EPS
Due to their design, circuit breaker thermal settings are more precise.
Explanations
b Calibration of thermal asymptotes:
v distribution fuses are calibrated to trip for overloads of between 1.25 and 1.6 times
DD210601en.EPS
Example:
a circuit breaker with a nominal rating of 100 A set to 90 A will be used to protect
KSA100 busbar trunking (ln trunking = 100 A) which is used for an ambient
temperature of 50 °C.
Extensive setting range of circuit Circuit breakers equipped with electronic trip units offer an extended range
of settings:
breakers equipped with electronic trip b thermal protection lr adjustable from 0.4 ln to ln
units b short-circuit protection from 2 lr to 10 lr.
Example:
a 250 A circuit breaker (NSX250N equipped with an STR22SE) can easily
be set up for:
- thermal protection from 100 to 250 A
- short-circuit protection from 200 to 2500 A.
Advantages:
DD210603.EPS
b 7KLVHQVXUHVDKLJKGHJUHHRIÀH[LELOLW\ZLWKUHVSHFWWR
v PRGL¿FDWLRQVÀH[LELOLW\H[WHQVLRQVXSJUDGHDELOLW\SURWHFWLYHGHYLFHV
can be easily adapted to the application requiring protection and to the system
earthing arrangement used (protection of life and property)
v maintenance: use of this type of device considerably reduces maintenance
component stocks.
Trunking characteristics Busbar trunking systems must meet all rules stipulated in standards
IEC 60439.1 and 60439.2.
b With respect to short-circuits, BTS sizing is determined by the following
characteristics:
v rated peak withstand current Ipk (kÂ):
this characteristic expresses the instantaneous electrodynamic withstand limits
of the busbar trunking. The peak current value is often the most restrictive
instantaneous characteristic for the protective device
v maximum rms short-time withstand current Icw (kArms/...s):
this characteristic expresses the permissible temperature-rise limit of conductors
over a given period of time (0.1 to 1 s)
v thermal stress in A2s:
this characteristic expresses the instantaneous thermal stress withstand of the BTS.
Normally, if the short-circuit generates fault conditions that are compatible with
WKH¿UVWWZRFKDUDFWHULVWLFVWKLVFRQVWUDLQWLV³DXWRPDWLFDOO\VDWLV¿HG´
Circuit breaker characteristics A circuit breaker must meet the requirements of product construction standards
(IEC 60947-2, etc.) and installation standards (IEC 60364 or applicable country
VWDQGDUGVLHLWVEUHDNLQJFDSDFLW\OFX
PXVWEHJUHDWHUWKDQVKRUWFLUFXLWFXUUHQW
Isc at the point where it is installed.
* installation standard IEC 60364 and the construction standards specify that the breaking
capacity of a circuit breaker is:
- the ultimate breaking capacity, lcu, if it is not coordinated with an upstream protective device
- the breaking capacity enhanced by cascading, if there is coordination with the upstream
protective device.
the protective device must take into account the following requirements:
b circuit-breaker lcu u prospective Isc at point A
b BTS l peak u limited or asymmetrical prospective Isc at point B
b BTS thermal withstand at lcw u thermal stress passing through the BTS.
b The busbar trunking must be capable of withstanding the peak fault current
to which it may be subjected as well as the thermal stress during any time delay:
v the permissible peak current, l peak, of the BTS must be greater than the peak
DD210605en.EPS
Current value of the 1st. peak as a function of rms Isc. 20 < I y 50 2.1
50 < I 2.2
v The short-time withstand current lcw of the BTS must be greater than the current
DD210606en.EPS
,VFÀRZLQJWKURXJKWKHLQVWDOODWLRQIRUWKHGXUDWLRQRIWKHVKRUWFLUFXLW
(duration T = total breaking time, including the time delay if applicable).
,IRQHRIWKHVHFULWHULDLVQRWVDWLV¿HGWKHUDWLQJRIWKHEXVEDUWUXQNLQJWREHXVHG
must be increased.
b In this case, the BTS must withstand the peak current limited by the protective
device and the corresponding thermal stress.
v The current limited (I peak) by the circuit breaker must be less than the peak
current permitted in the BTS.
v The thermal stress limited by the circuit breaker must be less than
the thermal stress permitted in the BTS.
DD210607en.EPS
Busbar trunking ratings can be optimised when circuit breakers rather than fuses are
used for protection.
Limiting capacity The circuit breakers in the Compact NSX range are limiting circuit breakers
with a high current-limiting capacity.
A circuit breaker’s limiting capacity is its ability to let only a limited current IL,
lower than the prospective asymmetrical peak short-circuit current Isc through
in the event of a short-circuit.
The consequence is a considerable reduction in electrodynamic
and thermal stresses in the protected installation.
PB104166_SE_r.eps
DD210612en.EPS
The selection guides below can be used to determine the circuit breaker required
to fully protect the trunking depending on the prospective short-circuit current
of the installation.
In bold, the most appropriate device to the rating of the busbar trunking
KSA trunking
Isc max (kA rms) KSA100 25 kA
Circuit breaker NG125N100
NSX100B/F/N/H/S/L
:LWK&DQDOLV.17OLJKWLQJFRQWUROV\VWHPVFDQSURYLGHDKLJKGHJUHHRIÀH[LELOLW\LQ
WKHFUHDWLRQDQGPRGL¿FDWLRQRIOLJKWLQJ]RQHVDQGOHYHOV
b XVHRI.17WUXQNLQJHTXLSSHGZLWKFRQGXFWRUVIRUSRZHUFLUFXLWVDQG
conductors for remote control.
DD202288.eps
iC60
iC60
OVA58911
OVA58914
OVA58945 HF
iC60
iC60
OVA58911
OVA58914
OVA58945
&DQDOLV.%%KDVVHSDUDWHFLUFXLWVPDGHXSRIRUOLYHFRQGXFWRUV7KLVPDNHV
it possible to easily implement classical three-phase lighting via one circuit and
supply and control self-contained emergency lighting units via the other circuit.
iC60
iC60
(or DALI)
HF
7KHDGGLWLRQDOFDEOHVSURYLGHGZLWK&DQDOLV.%$RSWLRQ7FDQEHXVHGWR
implement 3-phase lighting with dimming control by using the 2 additional conductors
WRFDUU\WKH9VXSSO\LQJWKHOXPLQDLUHVYLD.%&'&p2pp tap-off units
HTXLSSHGZLWKWKH.%&$=7DFFHVVRU\
This application requires the use of luminaires equipped with dimming ballasts.
Lighting with DALI control and emergency lighting in a large store or warehouse
Use of KBB trunking
DB403898.eps
OVA58911
OVA58914
OVA58945
iC60
(or DALI)
iC60
&DQDOLV.%%HTXLSSHGZLWKWZRFRQGXFWRUFLUFXLWVDQGRSWLRQ7DGGLWLRQDO
twisted pair), can be used to implement 3-phase lighting with dimming and self-
contained emergency lighting units.
This application requires the use of luminaires equipped with dimming ballasts.
iC60
Lighting controlled by proximity sensors and emergency lighting in a logistics centre or warehouse
Use of KBB trunking
DB403899.eps
iC60
(or DALI)
iC60
OVA58911
OVA58914
OVA58945
&DQDOLV.%%PDNHVLWSRVVLEOHWRFRQWURODVLQJOHSKDVHOLJKWLQJFLUFXLWE\DSUR[LPLW\
VHQVRU7KHDVVRFLDWHGUHOD\VDUHORFDWHGLQWKHÀRRUVZLWFKERDUG
&DQDOLV.%%WUXQNLQJZLWKFLUFXLWVFDQEHXVHGIRUFRPELQHGLQVWDOODWLRQVZLWK
self-contained emergency lighting units.
/LJKWLQJFRQWUROOHGE\DWLPHURULPSXOVHUHOD\LQWKHKDOOZD\VRIDQRI¿FHEXLOGLQJ
Use of KDP trunking
DB403866.eps
iC60
&DQDOLV.'3WUXQNLQJFDQEHXVHGWRVXSSO\DQGFRQWUROOLJKWLQJYLDDWLPHURU
impulse relay:
b WKHLPSXOVHUHOD\RUWLPHULVLQVWDOOHGLQWKHÀRRUVZLWFKERDUG
b &DQDOLV.'3FDEOHVDUHXVHGIRUDVLQJOHSKDVHOLJKWLQJFLUFXLW
b the other 2 cables are used to connect the pushbuttons.
Lighting controlled by a timer or impulse relay and emergency lighting in a logistics centre or warehouse
Use of KBB trunking
DB403895.eps
iC60
iC60
OVA58911
OVA58914
OVA58945
&DQDOLV.%%FDQEHXVHGWRFRQWUROWKHOLJKWLQJLQDJLYHQ]RQHRIDZDUHKRXVHRU
logistics centre using an impulse relay or timer.
7KHLPSXOVHUHOD\RUWLPHULVLQVWDOOHGLQWKHHOHFWULFDOVZLWFKERDUG&DQDOLV.%%
trunking with 2 circuits can be used to combine zone lighting with self-contained
emergency lighting units.
The Transparent Ready concept Transparent Ready is a simple solution to access information (status,
measurements, etc.) available from your electrical distribution equipment
(transformers, switchboards, busbar trunking).
DD205669.eps
This information can be accessed from any PC connected to your Ethernet network
via a simple Web browser (e.g. Internet Explorer). No other software is required.
Transparent Ready can make your company more competitive by:
b reducing operating costs
b optimising equipment performance
b improving the reliability of the electrical power supply.
DD205666.eps
DD205668_r.eps
DD205671.eps
Customer needs for measurements and In all non-residential buildings, the need for sub-metering exists and is growing
metering under the combined effects of:
b national and supra-national energy regulations
b the need to reduce overheads and production costs
b the allocation of energy expenditures to cost centres
b the outsourcing of operations tasks to specialists.
current transformers, must be installed in the tap-off unit equipped with a mounting
plate and a DIN rail .
Data acquisition in distributed When busbar trunking is located upstream of a secondary trunking line, the
architectures measurement devices should be installed in the tap-off units.
DD205665.eps
Canalis and Transparent Ready When the power-monitoring unit is installed in a tap-off unit, it is often too high for
easy reading of the measurements.
DD205826.eps
7KHQWKH&DQDOLVVROXWLRQLVWRLQVWDOOD.%$OLQH('7SDUDOOHOWRWKHPDLQOLQH
and dedicated to carry the information (as a Modbus network) from the power-
monitoring tap-off unit to the Ethernet TCP/IP network (see “The Transparent Ready
Concept”) and the connections are:
.
DD202287.eps
Index 3
Introduction 8
Design guides and characteristics 29
Canalis KDP 57
Canalis KBA and KBL industrial luminaires 85
Canalis KBB 113
Canalis KN 139
Canalis KS 175
Canalis KS riser 229
Canalis KT 253
7HFKQLFDOVSHFL¿FDWLRQV
Maintenance 267
Recommendations for special applications 273
Catalogue numbers
Replacement table former/new catalogue numbers 310
Canalis worldwide 315
Former cat. numbers New cat. numbers Former cat. numbers New cat. numbers
KBA .%$(/: .%$(':
.%$$$ .%$$%* .%$(/ .%$('
.%$($ .%$(' .%$(/7 .%$('7
.%$($7 .%$('7 .%$(9 .%$('$
.%$($7: .%$('7: .%$(9: .%$('$:
.%$($: .%$(': .%$)$ .%$$)
.%$($ .%$(' .%$6/ .%$$%'
.%$($ .%$(' .%$6/7 .%$$%'7
.%$($7 .%$('7 .%$6/7: .%$$%'7:
.%$($7: .%$('7: .%$6/: .%$$%':
.%$($: .%$(': .%$=$ Cancelled
.%$(% .%$(' .%$=$ Cancelled
.%$(% .%$(' .%$=$ Cancelled
.%$(/ .%$(' .%$=)38 .%$=)38
.%$(/7 .%$('7 .%$=* Cancelled
.%$(/ .%$(' .%$=68 .%$=)68
.%$(/7 .%$('7 .%$=8 .%$=)8
.%$(6 .%$(' .%$=8 .%$=)8
.%$(6 .%$(' .%$=8: .%$=)8:
.%$$$ .%$$%* .%$=8: .%$=)8:
.%$$$6 Cancelled KBB
.%$$$7 .%$$%*7 .%%($ .%%('
.%$$$7: .%$$%*7: .%%($7 .%%('7
.%$$$: .%$$%*: .%%($7: .%%('7:
.%$%7 .%$$%7 .%%($: .%%(':
.%$%7: .%$$%7: .%%($ .%%('
.%$($ .%$(' .%%($7 .%%('7
.%$($7 .%$('7 .%%($7: .%%('7:
.%$($7: .%$('7: .%%($: .%%(':
.%$($: .%$(': .%%($ .%%('
.%$($ .%$(' .%%($7 .%%('7
.%$($7 .%$('7 .%%($7: .%%('7:
.%$($7: .%$('7: .%%($: .%%(':
.%$($: .%$(': .%%($ .%%('
.%$() .%$') .%%($: .%%(':
.%$()7 .%$')7 .%%($7 .%%('7
.%$()7: .%$')7: .%%($7: .%%('7:
.%$(): .%$'): .%%($: .%%(':
.%$() .%$') .%%$$ .%%$%*
.%$()7 .%$')7 .%%$$ .%%$%*
.%$()7: .%$')7: .%%$$7 .%%$%*7
.%$(): .%$'): .%%$$7: .%%$%*7:
.%$(/ .%$(' .%%$$: .%%$%*:
.%$(/7 .%$('7 .%%$$7 .%%$%*7
.%$(/ .%$(' .%%$$7: .%%$%*7:
.%$(/7 .%$('7 .%%$$: .%%$%*:
.%$(/ .%$(' .%%%7: .%%$%7:
.%$(/7 .%$('7 .%%%7: .%%$%7:
.%$(/7: .%$('7: .%%($ .%%('
Former cat. numbers New cat. numbers Former cat. numbers New cat. numbers
KBB (cont.) .%%()7: .%%')7:
.%%($7 .%%('7 .%%(): .%%'):
.%%($7: .%%('7: .%%(9: .%%('$:
.%%($: .%%(': .%%6/ .%%$%'
.%%($ .%%(' .%%6/( .%%$%'(
.%%($7 .%%('7 .%%6/7 .%%$%'7
.%%($7: .%%('7: .%%6/7: .%%$%'7:
.%%($: .%%(': .%%6/( .%%$%'(
.%%($ .%%(' .%%6/7 .%%$%'7
.%%($7 .%%('7 .%%6/7: .%%$%'7:
.%%($7: .%%('7: .%%6/: .%%$%':
.%%($: .%%(': .%%<$ .%%=-
.%%($ .%%(' .%%<$ .%%=-
.%%($7 .%%('7 .%%<$7 .%%=-7
.%%($7: .%%('7: .%%<$7: .%%=-7:
.%%($: .%%(': .%%<$: .%%=-:
.%%($ .%%(' .%%=& .%%=)&
.%%($7 .%%('7 .%%=& .%%=)&
.%%($7: .%%('7: .%%=& .%%=)&
.%%($: .%%(': .%%=)* .%%=)*
.%%($ .%%(' .%%=)38 .%%=)38
.%%($7 .%%('7 .%%=*8 .%%=)*8
.%%($7: .%%('7: .%%=03 .%%=)03
.%%($: .%%(': .%%=6 .%%=)6
.%%($: .%%(': .%%=6 .%%=)6
.%%($ .%%(' .%%=68 .%%=)68
.%%($: .%%(': .%%=8 .%%=)8
.%%($ .%%(' .%%=8: .%%=)8:
.%%($7 .%%('7 .%%=8: .%%=)8:
.%%($7: .%%('7: KBC
.%%($: .%%(': .%&&% .%&'&%
.%%($ .%%(' .%&&% .%&'&%
.%%($7 .%%('7 .%&&& .%&'&&
.%%($7: .%%('7: .%&&&= .%&'&&=
.%%($: .%%(': .%&&6 .%&'&6
.%%() .%%') .%&&6 .%&'&6
.%%()7 .%%')7 .%&&6 .%&'&6
.%%()7: .%%')7: .%&'$ .%&''$
.%%(): .%%'): .%&'$= .%&''$=
.%%() .%%') .%&07 .%&'07
.%%()7 .%%')7 .%&6$= .%&'6$=
.%%()7: .%%')7: .%&99 .%&'99
.%%(): .%%'): .%&99= .%&'99=
.%%() .%%') .%&$= .%&=7
.%%()7 .%%')7 .%&$= .%&=/
.%%()7: .%%')7: .%&$= .%&=/
.%%(): .%%'): .%&&% .%&'&%
.%%() .%%') .%&&% .%&'&%
.%%()7 .%%')7 .%&&% .%&'&%
Former cat. numbers New cat. numbers Former cat. numbers New cat. numbers
KBC (cont.) KFB
.%&&% .%&'&% .)%(, .)%(9',
.%&&% .%&'&% .)%6% .)%69',
.%&&) .%&'&) KNA
.%&&) .%&'&) .1$&' .1%&0
.%&&) .%&'&) .1$&'+ .1%&0+
.%&&) .%&'&) .1$&' .1%&1
.%&&) .%&'&) .1$&) .1%&)
.%&&3 .%&'&3 .1$&* .1%&*
.%&&3 .%&'&3 .1$&3 .1%&3)
.%&=% .%&=% .1$&3' .1%&3'
.%&=& .%&=& .1$&3 .1%&3
KBZ .1$&3 .1%&3)
.%=93 .%==93 .1$&* .1%&*
.%=)& .%=()& .1$&0 .1%&0
.%=)& .%=()& .1$&; .1%&0
.%=)& .%=()& .1$6' .1%6'
.%=)0 .%=()0 .1$$= .1%=/
.%=)0 .%=()0 .1$$= .1%=/
.%=)0 .%=()0 .1$$= .1%=/
.%=)0 .%=()0 .1$$= .1%=/
.%=)0 .%=()0 .1$6) .1%6)
.%=)0 .%=()0 .1$6* .1%6*
.%=0& .%=(0& .1$6- .1%61
.%=%$ .%='%$ .1$60 .1%60
.%=%$ .%='%$ .1$60; .1%60
.%=3)5 .%=$3)5 .1$60 .1%60
.%=305 .%=$305 .1$6; .1%60
KDP .1$6; .1%60
.'3$$ .'3$%* .1$($ .1$('
.'3(% .'3(' .1$(' .1$('
.'3(%; .'3(' .1$$% .1$$%
.'3(% .'3(' .1$%7 .1$$%7
.'3(%; .'3(' .1$($ .1$('
.'3(% .'3(' .1$(' .1$('
.'3(%; .'3(' .1$() .1$')
.'3(% .'3(' .1$/) .1$'/
.'3(( .'3(' .1$<$ .1$=-
.'3(( .'3(' .1$$% .1$$%
.'3(( .'3(' .1$($ .1$('
.'3= .'3=) .1$(' .1$('
.'3= .'3=) .1$(' .1$('
.'3= .'3=) .1$() .1$')
.'3= .'3=) .1$/) .1$'/
.'3= .'3=) .1$<$ .1$=-
.'3= .'3=) .1$=$ .1%=)
.'3= .'3=) .1$=$ .1%=)
.'3= .'3=) .1$=* .1%=)*
.'3= .'3=) .1$') .1$(')
Former cat. numbers New cat. numbers Former cat. numbers New cat. numbers
KNE .6$'% .6%60
.1(<& .1(<& .6$'% .6%60
.1(<& .1(<& .6$($ .6$('
.1(&) .1%&) .6$($ .6$('
.1(<& .1(<& .6$6) .6%6)
.1(<& .1(<& .6$6) .6%6)
.1(<& .1(<& .6$$= Cancelled
.1(<& .1(<& .6$$= Cancelled
.1(<& .1(<& .6$$= .6$$=
.1(<&; .1(<&; .6$+' .6%+'
.1(() .1$') .6$6) .6%6)
.1(/) .1$'/ .6%6)
.1(<% .1(<% .6$6) .6%6)
.1(() .1$') .6%6)
.1(/) .1$'/ .6$69 .6%69
.1(<$ .1(<$ .6%69
.1(<$ .1(<$ .6$69 .6%69
.1(<% .1(<% .6%69
KNT .6$$= Cancelled
.17&0 .1%&0 .6$$= .6%=&
.17&; .1%&0 .6$'% .6%'&
.17$= .17=7 .6$'% .6%'%
.17($ .17(' .6$'% .6%'&
.17(' .17(' .6$'% .6%'%
.17$% .17$% .6$($ .6$('
.17%7 .17$%7 .6$($ .6$('
.17($ .17(' .6$6) .6%6)
.17(' .17(' .6$6) .6%6)
.17(' .17(' .6$6) .6%6)
.17() .17') .6$$% .6$$%
.17/) .17'/ .6$%7 .6$$%7
.17<$ .17=- .6$'% .6%'&
.17$% .17$% .6$'% .6%'%
.17%7 .17$%7 .6$'% .6%'&
.17($ .17(' .6$'% .6%'%
.17(' .17(' .6$(% .6$('
.17(' .17(' .6$(% .6$('
.17() .17') .6$(' .6$('
.17/) .17'/ .6$(' .6$('
.17<$ .17=- .6$()$ .6$(7$)
KSA .6$(5 .6$$(
.6$&) .6%&) .6$(6$ .6$(7$
.6$'$ .6%&0 .6$(= .6%=)
.6$$= Cancelled .6$/& .6$'/&
.6$'$ .6%60 .6$/3 .6$'/(
.6$'$ .6%60 .6$/3 .6$'/)
.6$6) .6%6) .6$6) .6%6(
.6$6) .6%6) .6$6) .6%6(
.6$$% .6$$% .6$6) .6%6(
Former cat. numbers New cat. numbers Former cat. numbers New cat. numbers
KSA (cont.) .6%<$ .6%<$
.6$7& .6$'7& .6%)$ .6$$)
.6$;& .6$';& .6%<$ .6%<$
.6$$= Cancelled KSE
.6$'% .6%'& .6(&' .6%&1
.6$'% .6%'% .6(&) .6%&)
.6$'% .6%'& .6(&* .6%&*
.6$'% .6%'% .6(6' .6%6'
.6$(' .6$(' .6(6' .6%6'
.6$(' .6$(' .6(6* .6%6*
.6$6) .6%6( .6('$ .6%60
.6$6) .6%6( .6('$ .6%60
.6$6) .6%6( .6(6' .6%61
.6$$% .6$$% .6(6' .6%61
.6$$% .6$$%' .6(6) .6%6)
.6$$% .6$$% .6(6) .6%6)
.6$$% .6$$%* .6(6' .6%6'
.6$%7 .6$$%7 .6(6' .6%6'
.6$(' .6$(' .6(6* .6%6*
.6$(' .6$(' .6('$ .6%60
.6$(' .6$(' .6('$ .6%60
.6$(' .6$(' .6(6' .6%6(
.6$(' .6$(' .6(6' .6%6(
.6$(' .6$(' .6(6) .6%6)
.6$()$ .6$(7$) .6(6) .6%6)
.6$(5 .6$$( .6('% .6%'&
.6$(6$ .6$(7$ .6('% .6%'&
.6$/& .6$'/& .6(6' .6%6(
.6$/3 .6$'/( .6(6' .6%6(
.6$/3 .6$'/) .6(6' .6%6(
.6$7& .6$'7& .6(6) .6%6)
.6$;& .6$';& .6(6) .6%6)
.6$(' .6$(' .6(6) .6%6)
.6$(' .6$(' .6(6* .6%6*
.6$6) .6%6( .6('% .6%'&
.6$6) .6%6( .6('% .6%'&
.6$()$ .6$(7$) .6(6) .6%6(
.6$(5 .6$$( .6(6) .6%6(
.6$(6$ .6$(7$ .6(6) .6%6(
.6$(= .6%=) .6(<$ .6(<$
.6$/& .6$'/& .6(<$ .6(<$
.6$/3 .6$'/( .6('% .6%'&
.6$/3 .6$'/) .6('% .6%'&
.6$7& .6$'7& .6(6) .6%6(
.6$;& .6$';& .6(6) .6%6(
KSB .6(6) .6%6(
.6%)$ .6$$) .6(<$ .6(<$
.6%<$ .6%<$
.6%)$ .6$$)
Index 3
Introduction 8
Design guides and characteristics 29
Canalis KDP 57
Canalis KBA and KBL industrial luminaires 85
Canalis KBB 113
Canalis KN 139
Canalis KS 175
Canalis KS riser 229
Canalis KT 253
7HFKQLFDOVSHFL¿FDWLRQV
Maintenance 267
Recommendations for special applications 273
Catalogue numbers 309
Canalis worldwide
Canalis worldwide 316
Tertiary
Name Lighting and low voltage Medium voltage High Country
voltage
KDP KBA KBB KN KS KT
2I¿FHV
Air France (headquarters) b b France
PD202244.eps
Allianz b b Germany
Axa b b France
Chamber of Commerce b b Luxembourg
Commerz Bank b b Germany
Lexel b b b Sweden
Telefónica b b Spain
Trade Center b b Spain
RDC tower b b Tunisia
Turning Torso b Sweden
Vodafone b b New Zealand
Colt b b France
Digiplex b b Sweden
IBM b b b b Spain, Italy
MCI-Worldcom b b b b ,WDO\8QLWHG.LQJGRP
Mc Donald’s b France
Radisson SAS Stansted Airport b 8QLWHG.LQJGRP
Soldeo Andorra Hotel b b Spain
Hospitals
Children Clinic b b Sweden
PD202247.eps
Auchan b b b b b b World
B&Q b b b 8QLWHG.LQJGRP
Carrefour b b b b b b World
Coop b b b Italy
Fnac b b Spain, France
Ikea b b b b b China, Spain, France,
Sweden
Mark & Spencer b Belgium, Spain,
8QLWHG.LQJGRP
Toys’R Us b Spain
Other industries
Aerospace industry
Airbus b b b Italy
Food-processing industry
Coca-Cola b b Spain, Italy, Belgium
Danone b b b World
Pasquier b b France
Livestock production farms and greenhouses
Favier henhouse b b France
Greenhouse b Netherlands
Ceramic industry
Esmalglas ceramic b b b b b Spain
Electricity
Legrand b France, Turkey
Watch-making
Rolex b b b Switzerland
Microelectronics
Intel b b b b Irelande
ST Micro-électronique b b b b France
Lead industry and water treatment
Grundfos b China
Industrial technology
Bosch b b China
Telephony
Phillips b Netherlands
Nokia b b Sweden
Textile industry
Louis Vuitton b b b Spain
Delta b b Israel
Infrastructures
Name Lighting and low voltage Medium voltage High Country
voltage
KDP KBA KBB KN KS KT
Airports
Paris airport b b b b b France
PD202250.eps
Marine
Chantier de l’Atlantique b b France
PD202251.eps
Meyerwerft b b Germany
Undergrounds
Guanghzou underground b China
PD202252.eps
Other infrastructures
Alexandria library b b Egypt
Centre international d’exposition b b China
de Suzhou
CERN b b Switzerland
Stade de France b b France
DEBU022EN 09-2011