1- Electrical, Diesel & Jockey Pump Flow Required

Pump Flow for electrical pump 1000 gpm


Pump Flow for Diesel pump 1000 gpm

Pump Flow for jockey pump = 10 % FF PUMP 100 gpm

2- Electrical, Diesel & Jockey Pump head Required

Based on Calculation Get Required Head ELECTRICAL PUMP 184.4 Psi


Based on Calculation Get Required Head DIESEL PUMP 184.4 Psi
Required Head JOCKEY PUMP= FF PUMP HEAD + PSI 191.4 Psi
Automatic Irrigation System Calculation

Irrigation Water Demand Requirement

Plant Description Area / Quantity Watering Rate LPD


Shrubs 431.47 m2 16 liters/ day/m2 6903.52
Turf or Grass 1872 m2 12 liters/ day/m2 22464
Ground Cover 1160 m2 12 liters/ day/m2 13920
Trees 115 No. 120 liters/ day/m2 13800
Palms 8 No. 150 liters/ day/m2 1200
Total Watering Rate 58287.52
Adding 2% as Factor Of Safety 59453.27

From Perivious Data Get


Storage tank for 1 day = 59.5 m3