RCEL
Electric Actuators 006–009
INSTALLATION B. ELECTRIC WIRING
1. Mounting on valve, see instruction A. NOTE: Electric wiring must be carried out
2. Electric wiring, see instruction B. by qualified personnel only!
3. Adjustment, see instruction C.
4. Manual operation, see instruction D. 1. Loosen the screws on the cover and lift it off.
2. Check the voltage marked on the actuator
NOTE: label.
Only electric wiring, acc. to instruction B, 3. Connect according to the enclosed wiring
is required when the actuator is delivered diagram or, if the actuator is of standard
from Remote Control mounted on a valve. design, according to the wiring diagram
It is adjusted and ready for operation. below. The wiring diagram is drawn in unaf-
fected position (the valve in intermediate
position).
WARNING
Remove power before the cover 4. Test run the actuator from the intermediate
is dismantled! position checking that the actuator turns in
The actuator must be handled with the the correct direction.
utmost care when the cover is removed 5. Test run the actuator and check that the
and the power connected!
limit switches work correctly.
A. MOUNTING ON VALVE 6. Check that the cable entries and possible
1. Operate the valve manually to fully open blind plug are sealed.
or fully closed position before the actuator 7. Mount the cover.
is mounted. Wiring diagram No NU 12000C. Standard.
2. Operate the actuator manually (see
instruction D) to fully open or fully closed
Instruction No 433C
position.
RED
3. Check that the actuator and valve stem CAPACITOR
T.P
BLUE
are in correct position. Please note, valve
and actuator must be in the same mode N
WHITE
5. Operate the valve manually with the aid of CLS CLOSE LIMIT SWITCH
OLS OPEN LIMIT SWITCH
the actuator handwheel and check that the YELLOW
2 AOLS ACLS AUX. CLOSE LIMIT SWITCH
AOLS AUX. OPEN LIMIT SWITCH
valve moves with normal resistance. BROWN 3 1
TP THERMAL PROTECTOR