Car park ventilation systems are required The ventilation requirements for car parks The Approved Documents describe three
to achieve two objectives. are detailed in: traditional methods of ventilation for car
parks, as follows.
Firstly, when the car park is in general Approved Document B to the Building
use, it is important that the exhaust gases Regulations (England and Wales); 1. Open Sided Car Parks
produced by vehicles are effectively Scottish Buildings Standards Technical These are completely above ground level
removed and that there are no pockets of Handbooks (Scotland); Technical with permanent wall openings on each
stagnant air. Booklet E (Northern Ireland). level, equal to 5% of the plan area,
arranged to provide cross ventilation.
Secondly, in the event of a fire, assistance Approved Document F - Ventilation These openings are considered to provide
needs to be given to the Fire Service to sufficient ventilation for clearance of both
clear smoke from the car park during and BS 7346-7: 2006 smoke and vehicle exhaust fumes.
after the fire.
BS 5588 Series 2. Naturally Ventilated Car Parks
Car park ventilation systems may in These have permanent wall openings on
addition be designed to provide clear APEA Code of Practice each level, equal to 2.5% of the plan area,
smoke free access for fire fighters to arranged to provide cross flow ventilation.
tackle the seat of the fire, or alternatively SVA guidance This is sufficient ventilation
to protect means of escape from the car for smoke clearance, but in addition
park. These more complex systems are in BR 368 mechanical extract providing three air
excess of Building Regulations changes per hour is needed to remove
requirements and are used as With regards to BS 7346-7: 2006, exhaust fumes.
compensating features when other “Components for Smoke and Heat Control
requirements are not met. Systems. Code of practice on functional Note: The 5% and 2.5% areas are defined
recommendations and calculation in the 2006 edition of Approved
This leaflet is intended to provide an methods for smoke and heat control Document F as "equivalent areas". For
understanding of the legislative framework systems for covered car parks”, this openings that are obstructed in any way,
and how car park ventilation systems can gives design guidance on ventilation of by louvres, screens, etc, the aerodynamic
help meet legislative requirements and car parks, including both Building coefficient of the obstruction is required
achieve the design objectives. Regulations compliant systems and fire for the calculation of the equivalent area.
engineered systems.
2
East Side Plaza, Gunwharf Quays, Portsmouth
8 Cyclone induction fans and 3 Jetstream impulse fans
move the air from the entrance ramp towards the
extract system, which was also supplied by Colt.
3. Mechanically Ventilated Car Parks Colt Car Park Ventilation Systems can be There are a number of issues relating to
Where natural ventilation is not possible, a designed to meet the requirements of other ducted mechanical extract systems which
mechanical extract system should be used. international standards such as the NFPA often cause problems for designers:
For mechanically ventilated car parks, the and Australia/New Zealand standards, and
basic requirements are that there should be Colt has installations of Car Park The ductwork runs underneath the
a mechanical ventilation system that will Ventilation Systems in many countries ceiling, reducing the already restricted
provide 6 air changes per hour (ACH) for around the world. height normally available.
general ventilation on all levels and 10
ACH on the fire floor in the event of a We would be pleased to assist you in the Downstand beams require the ducting
fire. The system should be capable of development of designs for your car park to be set down below them, thus
operating at temperatures of up to 300°C wherever it may be. diminishing the height even further.
for 60 minutes and ductwork and fixings
should be made from materials that have a Low level extract points are required,
melting point above 800°C. The system often needing protective barriers to
should have at least 2 extract fans, each surround them, and these take up
providing 50% of the extract, with a valuable floor space.
secondary power supply to operate in the
event of a mains power failure. Extract The ductwork gives the car park a
points should be designed with 50% of the cluttered look and can interfere with
outlets at high level and 50% at low level. CCTV coverage.
3
Impulse Ventilation Systems
CAR PARK FIRES 2002 WHAT ARE IMPULSE VENTILATION FEATURES AND BENEFITS OF IMPULSE
SYSTEMS? SYSTEMS
In recent years jet fan or impulse Easier and quicker installation - Impulse
116 fires (estimated) technology has established itself as the fans are much quicker and easier to install
occurred in car park new standard in car park ventilation. than extensive ducting
Impulse ventilation systems are an
buildings
alternative to ducted mechanical extract Lower excavation costs - Low profile
systems, overcoming many of the fans can be kept within downstand beams
Of these 60 fires started in problems associated with such systems.
Lower maintenance - No distribution
vehicles An impulse fan is similar to a tunnel jet ductwork to clean
fan, but has a reduced diameter in order to
maximise headroom. It comprises an axial Optimal use of space - Increased
One of the 60 cases spread fan with inlet and exhaust attenuators and headroom or lower car park build height,
to 9 other vehicles. 1 fire any necessary guards and flow distribution with an increased number of parking bays
control devices.
spread to 1 other vehicle Better car park security - No ducting
A series of such free- blowing fans, improves CCTV coverage, keeping the
mounted under the ceiling, induce air environment safer and lighter
Approx 50% of fires were movement from the air inlet openings
“deliberate” towards pre-designated extract points, Sprinklers - Impulse systems are
moving smoke and fumes with it. The eminently suitable for use with sprinkler
number and location of fans are carefully systems. Where legislation requires
At least 2 cases of fires in chosen to match the system design sprinklers, it is possible for the approving
requirements, and in order to ensure that authority to accept the deletion of
car park buildings of 14
there are no dead spots for fumes and sprinklers where an improved car park
storeys smoke to stagnate and collect. ventilation will be installed. In this
instance, the impulse system will need to
be able to maintain clear access conditions
Source: BRE for fire-fighters.
4
Becad Hospital, Middlesex
By re-assessing the design, Colt was able to
reduce a competitor's 35 impulse fans to 12
Cyclone induction fans.
vehicle stopped vehicle stopped vehicles will continue driving to the exit
The principles of car park impulse ventilation have been developed from procedures used for tunnel ventilation. In the event of a fire, smoke will be ‘pushed’ and
‘pulled’ to the exit. Vehicles in front of the fire will continue through to the exit, whilst vehicles behind the fire will, of course, have to stop. Although trapped, these
vehicles should be safe from the smoke.
CO Detectors
(typically every 400m2)
Fan positioning needs to take into account roof The introduction of CO detectors allows use of a more
geometry (particularly deep downstand roof sophisticated control system to match the ventilation
beams) and risk of airflow blockage by tall vehicles. rate to the car park usage, further reducing running
costs and noise levels.
5
The Colt Jetstream Impulse Unit
6
CASE HISTORY
Arsenal
FEATURES AND BENEFITS A Colt impulse ventilation system has been installed at the new
Emirates Stadium, constructed by Sir Robert McAlpine Ltd for
Proven performance – Independently
tested and certified in accordance with EN
Arsenal Football Club, in north London. Colt also supplied plant
12101-3: 2002 room louvres in a contract worth £1.2 million in total.
Durable – Hot dipped galvanized finish The Colt impulse system consists of 59 reversible Jetstream
with a 4mm thick fan casing, resistant to
fans, four 1800mm extract fans, and all their associated carbon
potential corrosion.
dioxide, smoke and heat detectors and controls.The fans are
Adjustable pitch aerofoil section mounted under the ceiling around the car park, to move air and
impellers, set and tested in the factory, to smoke towards each extraction point, avoiding the need for the
provide optimum aerodynamic extensive ductwork that would be required for a traditional
performance.
system.
A minimum protection to IP55 on fan
electrics enables fan maintenance and The benefits of the system include a more open environment,
cleaning by pressure washing. External better CCTV coverage and lower initial and running costs. In
padlockable isolator switch protected to
the interests of maximum efficiency, with the reversible impulse
IP65.
fans linked to a wind direction sensor, the system can move the
Slimline appearance - Standard version airflow around the car park in either a clockwise or anti-
uses spigot fixing of attenuators and clockwise direction depending on the wind direction.
streamlined attenuator lining to maintain a
slim, clean profile.
7
The Design Approaches
8
The Observatory Apartments, Walsall
CFD plan of a typical car park showing Air speed contours at high level, Air speed contours at low level,
Colt Cyclone fan locations, openings day-to-day ventilation day-to-day ventilation
and areas
9
Testing
In 2004 Colt conducted the first UK full These tests demonstrated that properly A video is available to view at
scale comparative tests between traditional designed impulse systems can clear the www.coltinfo.co.uk.
methods of mechanical ventilation and smoke more quickly than ducted systems.
impulse ventilation in Bristol. For more information please see leaflet:
PD 56 “Full Scale ‘live’ Smoke Tests”.
The table shows the range of times taken in the demonstrations to achieve visibility
distances and for the car park to become clear of smoke.
10
Grd level
Cyclone
7200
Impulse
The aim of the tests was to demonstrate Fan
7200
30000
11
Induction Ventilation Systems
Induction ventilation is a further In a recent project in the centre of London, Cyclone fans were
enhancement of the impulse ventilation
concept. specified since they saved significant dig-out costs. The contractor
would have needed to speand an additional £248,000 excavating
Using the same principles as impulse
ventilators, induction fans are yet slimmer,
an additional 150mm of earth in order to accommodate the greater
more efficient and powerful, thus reducing unit depths of an alternative system
the number of units required. A typical
induction fan has a throw of
approximately 40 m as opposed to 20 m Fewer units mean lower cabling and In addition, the units are inverter
for an impulse fan. The floor area controls requirements and lower controlled for a further reduction in power
ventilated per fan is significantly greater, installation and maintenance costs. consumed.
equating to a requirement for fewer units.
Air turbulence is dramatically reduced when using a Colt Cyclone CPV fan
12
CASE HISTORY
Paradise Street
ARCHITECT: Building Design Partnership
MAIN CONTRACTOR: Laing O’Rourke/Crown House
SERVICES CONSULTANT: WSP
FIRE CONSULTANT: Tenos
Colt has won the contract for what is believed smoke from a potential fire into defined
to be the UK’s first smoke control system for corridors. So, this is a fully designed scheme
means-of-escape for a car park. It has been rather than a simple air change rate scheme.We
designed specifically to enable occupants to are not merely clearing the smoke - we are
escape from a car park and to assist fire-fighting controlling it."
crews, rather than simply as a smoke clearance
system that is commonly applied to car parks. Prior to the award of the contract, engineers
from Colt and the Building Research
The £1.28 million project - part of Liverpool’s Establishment demonstrated the effectiveness of
£920 million Paradise Street retail, leisure and the Colt impulse scheme for the Paradise Street
residential development - involves the supply and project by conducting a series of hot smoke
installation of a Colt impulse car park ventilation tests in a simulated car park in Middlesbrough.
system for the massive 56,000sq m, 2,000-space These established the accuracy of CFD
car park being built beneath Chavasse Park in modelling Colt had made before the test, and
Liverpool. predicted that the scheme of impulse fans would
be capable of controlling the spread of smoke
The four-storey underground car park will be from a car fire and keeping significant areas of
fitted with 80 Cyclone induction fans and 22 the car park smoke free.
Jetstream impulse fans.These are designed to
keep smoke completely away from the escape Colt started installing the system in September
routes without the need for smoke curtains or 2006 with commissioning and hand over
physical barriers. scheduled for November 2007 and the car park
is due to open early in 2008.
John Perry, senior consultant at Colt, explained:
"Nearly all of the car parks we have done in the Smoke control for means-of-escape is described
UK so far are smoke clearance systems, not on p8. Please see p19 for a schematic diagram of
smoke control systems.With the former, you this project.
have a designated extract rate.This car park is
different because it is so large (with the largest
level being 232m by 95m) that we have to move
13
The Colt Cyclone Induction Unit
General description
The Cyclone induction unit comprises a AIRFLOW
A
Versions
- Two fan sizes, with overall depths of
320mm and 255mm respectively
Finishes
Cyclone is supplied in polyester powder
light grey RAL 7035, with the option of a
polyester powder coating to any RAL
colour.
Certification
Cyclone 100 and 50 with their standard
isolator fully meet the F300 time/ Type Cyclone 100 Cyclone 50
temperature classification of the EN
12101-3:2003 standard following CE
CE marking High temperature High temperature
independent tests, demonstrating that the 300ºC for one hour 300ºC for one hour
unit will operate at 300°C for 60 minutes.
They CE marked. Test Certificates are Unit height A 320mm 255mm
available on request. Unit length B 1670mm 1260mm
Unit width C 1150mm 820mm
Overall depth 320mm 255mm
Thrust 100 N 50 N
Motor power 2.6 kW 1.4 kW
14
CASE HISTORY
The Postbox, Birmingham
CLIENT: Cala Homes
ARCHITECT: Ian Darby Partnership
MAIN CONTRACTOR: Taylor Woodrow
M&E CONTRACTOR: Rotary North West
15
Extract Systems
There needs to be an adequately designed All Colt extract fans have been tested to Colt also provide:
ventilation system to extract the air. In the exacting standards of EN 12101-3:
addition, where the natural air supply is 2002. Ductwork, including attenuators,
insufficient, supply fans may also be grilles, volume control dampers, shut-
required. All Colt extract systems are designed to off dampers, bends and transitions.
produce a maximum of 55 dBA externally
Depending on the scope required, Colt is at 3m from the extract fan discharge Weathered external terminations,
able to provide a wide variety of grilles and NR 55 at 3m inside the car including louvres, dampers, turrets,
mechanical extract fan and motor park in day-to-day mode. Lower noise gravity shutters, cowls and motorised
assemblies to suit the required duty and levels are possible on request. ventilators such as the Seefire and
temperature rating. These include long Meteor.
case, short case and plate mounted axial Colt is able to mix and match components
fans. to suit the requirements of almost any
mechanical extract system.
There are 14 standard sizes ranging from
315mm up to 2000mm diameter, with
duties of up to 100 m3/s, and motor power
ratings of up to 75 kW.
16
B5 Southside, Birmingham
2 Inlet Fans, 13 Cyclones, 2 Extract
Fans, Dampers and Grilles, CO &
Smoke Detectors
Extract fans at The Foundation, Liverpool Extract plant at Gunwharf Quays, Portsmouth
17
Controls & Sensors
The design of the controls and sensors is Using a single output detector, two stage For a smoke control system, addressable
an integral part of the car park ventilation control can be provided, typically detection is required to pinpoint the fire
system. The arrangement of sensors is switching at 15-20ppm of CO. Using location to allow correct selection of fan
determined at the design stage, along with variable output detectors, the system can operation to maintain the required clear
the controls cause and effect, which provide additional stages or modulate to areas.
determines the way in which the equipment match the ventilation rate to the car park
responds to any given conditions. usage. Colt can provide carbon monoxide
detectors, heat/smoke sensors and fire
Day to day condition Fire condition alarm inputs along with all their necessary
The simplest (but rarely used) option is to For a smoke clearance system, detection is controls and battery back up facilities,
run the system at a constant speed, required to indicate which level of the car linked into an addressable fire detection
providing a ventilation rate of 6 ACH park contains the fire, if the car park has system.
throughout the car park. To reduce energy more than one level. Upon detection all
costs a CO detection system is used to fans on that level operate at high speed, all
allow the system to run at a reduced other fans are switched off and the extract
ventilation rate in periods when vehicle fans are switched to full speed, extracting
movements are low. only from the fire level.
Fire Heat
Rated Detector
Isolator Junction Junction
J
Box Level 2 Box J
Cyclone Carbon Monoxide HD
Fans Detector
Extract Inlet
HD HD Damper
Damper CO CO
CO Detector
Heat
J J
Detector
18
Gunwharf Quays, Portsmouth
Air Movement
19
A Member of the British Parking Association
Colt can offer the complete package, Colt Smoke Control systems are suited to Part of the Colt Group of companies,
which could include: both commercial and industrial Colt Service offers a comprehensive
buildings, and may be adapted to suit range of maintenance packages
Scheme design. CFD analysis and most architectural requirements. incorporating the maintenance and
report repair of all building services equipment
Over the years Colt has funded a large including non Colt products.
Supply of impulse fans, extract and/or proportion of the research into smoke
inlet fans, ductwork (for extract) and control, and its representatives maintain Colt Service provides a 24 hour, 365
dampers, control systems and wiring, an unparalleled level of technical day emergency cover as standard.
CO and heat/smoke detectors expertise.
MAINTENANCE
Installation and wiring Colt’s CFD modelling approach is
reliable and has been confirmed by Maintenance of a smoke control system
Commissioning empirical full scale hot smoke tests. is essential. Regular maintenance
protects your investment and brings
Service and maintenance. Colt's in-house research and peace of mind that the system will
development capability ensures that Colt operate effectively in an emergency.
A free full system check will be carried fire protection systems are designed,
out approximately 9 months after a tested and updated by Colt to meet or British Standard BS 5588-12
“Colt” and the Colt logo are registered trademarks of Colt International
Smoke Control System has been installed exceed relevant legislation and standards. recommends that smoke control systems
Licensing Limited. © Colt International Licensing Limited 2006.
and commissioned by Colt. Besides the should be serviced at least once a year
Subject to modification. Publication number PD 52: 01/07 V3
opportunity to check that the system is The majority of Colt's Smoke Control and tested weekly.
performing as designed, this will allow systems are manufactured in the UK
for any further training of local personnel under BS EN ISO 9001:2000 and BS EN
that may be necessary. Assuming that this ISO 14001:2004.
visit falls within the warranty period, any
defective parts would be replaced free of
charge. A test certificate will be issued.
People feel better in Colt conditions Architectural Solutions Colt International Limited
New Lane Havant
terna
In t Climate Control Hampshire PO9 2LY
io
nal
3
0
9