Cold room A
Door
Cooper pipe
Compressors
Light
Voltage
Drainage
Cold room C
Cold room B
Cold room D
Door
Cooper pipe
Compressors
Control panel
Light
Voltage
Drainage
Automation and reporting(for all Cold room)
temperature recording system
failover function
control method
Other requirements(For all cold room)
condensate
Cold room door
temperature distribution
heater
lights
Description/Specification
1)center set point: -20℃;
2)Temperature tolerance ± 3℃
3) Internal net size : W4300mm*L4600mm*H3000mm
1) PIR or PU sandwich panel (special for cold room is better);
2) Fire-proof level:B1 or above (flame retardant) ,FM or similar certificate is a
plus;
3) Thickness of sandwich :>= 150mm;
4) Galvanized steel sheet thickness on the sandwich panel: >=0.5mm;
5)No odors and/or harmful substances;
6) 2mm thick non-slip aluminum plate is laid on the sandwich floor;
7) floor bearing: 200kg load will not cause significant deformation ;
8)Gaps were sealed by silicon glue after assembling;
1)Single swing door, made by same materials as wall;
2) Size: W 900mm*H 2000mm
3) Thermal insulation bridge;
4) Can be opened inside without key, even locked from outside;
5) No condensate water around the sealing strips;
1) Type and PN are suitable for the cooling agent;
2) Tube rubber insulation materials covered all cooper pipes and tied by taps
3)All the holes cross the wall should be sealed by foam materials;
1)two independent cooling systems;
2) Internal units (evaporator) are hanged on the ceiling or wall;
3) External units (condensator)are installed up the ceiling;
4) Compressor brand: Gulun, Bizzer or similar;
5) High and low pressure switch;
6) Thermol sensor beside the internal units;
1) Digital set point of temperature;
2) Light alarm when the temperature is out of range;
3) High- and low-pressure alarm;
1) LED light;
2)In cold room: >= 150Lux
3) switches are both in out and in cold room;
follow the the local code
1) DN32 PVC pipe;
2) Rubber insulation to prevent the condensate water out of the pipe;
water vapor barrier should be designed on the high temperature side
heater needs to be installed in the door frame & window of the cold room to prevent
the sealing strip from being frozen
The cold storage should use moisture-proof and mildew-proof lights, and the
illuminance should not be less than 300lux
Picture1 Picture2
image.png image.png
门整体图片 密封条等细节图片
image.png
外机图片 内机图片
控制盘图片
灯具图片
通气阀图片