Cold room A

wall,ceiling and floor material

Door

Cooper pipe

Compressors

control and alarm system

Light

Voltage
Drainage

water vapor barrier

Cold room (2-8℃)

Cold room C

Cold room B
Cold room D

specification of wall,ceiling and floor material

Door

Cooper pipe

Compressors

Control panel

Light

Voltage
Drainage
Automation and reporting(for all Cold room)
temperature recording system

failover function

control method
Other requirements(For all cold room)
condensate
Cold room door

temperature distribution
heater

lights
Description/Specification
1)center set point: -20℃;
2)Temperature tolerance ± 3℃
3) Internal net size : W4300mm*L4600mm*H3000mm
1) PIR or PU sandwich panel (special for cold room is better);
2) Fire-proof level:B1 or above (flame retardant) ,FM or similar certificate is a
plus;
3) Thickness of sandwich :>= 150mm;
4) Galvanized steel sheet thickness on the sandwich panel: >=0.5mm;
5)No odors and/or harmful substances;
6) 2mm thick non-slip aluminum plate is laid on the sandwich floor;
7) floor bearing: 200kg load will not cause significant deformation ;
8)Gaps were sealed by silicon glue after assembling;
1)Single swing door, made by same materials as wall;
2) Size: W 900mm*H 2000mm
3) Thermal insulation bridge;
4) Can be opened inside without key, even locked from outside;
5) No condensate water around the sealing strips;
1) Type and PN are suitable for the cooling agent;
2) Tube rubber insulation materials covered all cooper pipes and tied by taps
3)All the holes cross the wall should be sealed by foam materials;
1)two independent cooling systems;
2) Internal units (evaporator) are hanged on the ceiling or wall;
3) External units (condensator)are installed up the ceiling;
4) Compressor brand: Gulun, Bizzer or similar;
5) High and low pressure switch;
6) Thermol sensor beside the internal units;
1) Digital set point of temperature;
2) Light alarm when the temperature is out of range;
3) High- and low-pressure alarm;
1) LED light;
2)In cold room: >= 150Lux
3) switches are both in out and in cold room;
follow the the local code
1) DN32 PVC pipe;
2) Rubber insulation to prevent the condensate water out of the pipe;
water vapor barrier should be designed on the high temperature side

1)center set point -5℃;


2)Temperature tolerance ± 3℃
1)Internal size:W6450mm*L9600mm*H3850mm;
2) one construction pillar is inside;
3) Slide door, made by same materials as wall;
4) Size: W 120mm*H 2000mm
5) External units (condensates)are installed out of the building;
1)Internal size:W9800mm*L12700mm*H3850mm;
2) one construction pillar is inside;
3) Slide door, made by same materials as wall;
4) Size: W 120mm*H 2000mm
5) External units (condensates)are installed out of the building;
1)Internal size:(W4650mm*L4400mm+ W1900mm*L1900mm)*H2700mm;
2) Single swing door: W 900mm* H2000mm;
3) External units (condensates)are installed up on the ceiling, ensure the ceiling
load is enough to support the external units ;
1) Polyurethane foam sandwich panel (special for cold room is better);
2) Fire-proof level:B1 or above (flame retardant) ,FM or similar certificate is a
plus;
3) Thickness of sandwich :>= 100mm;
4) Galvanized steel sheet thickness on the sandwich panel: >=0.5mm;
5)No odors and/or harmful substances;
6) 3mm thick non-slip aluminum plate is laid on the sandwich floor;
7) floor bearing: 300kg load will not cause significant deformation ;
8)Gaps were sealed by silicon glu after assembling;
1) Thermal insulation bridge;
2) Can be opened inside without key, even locked from outside;
3) No condensate water around the sealing strips;
4)Air curtain machine start when door is opening;
1) Type and PN are suitable for the cooling agent;
2) tube rubber insulation materials covered all cooper pipes and tied by taps
3)All the holes cross the wall should be sealed by foam materials;
1)At least two independent refrigeration systems in each cold room;
2) Internal units (evaporator) are hanged on the ceiling or wall;
3) External units (condensator)are installed up the ceiling;
4) Compressor brand: Gulun, Bizzer or simila;
5) High and low pressure switch;
6) Thermol sensor
7) Cooling agent : R404A
1)Timed automatic cream;
2)Digital set and monitor the room temperature;
3) Compressor overload protection;
4)Compressor Low and high pressure protection;
5)Automatic temperature recording is a plus;
6) Pilot lamps for different compressors: power, running, breakdown;
7)every system has independent power switches, contractors, relay , monitors
etc.;
1) LED light;
2)In cold room: >= 150Lux
3) switches are both in out and in cold room;
follow the local code
1) DN32 UPVC pipe;
2) Rubber insulation to prevent the condensate water out of the pipe;
The cold storage needs to be equipped with a temperature recording system, which
records temperature parameters at least every 5 minutes, and the stored parameter
can not be modified
Use HMI to monitor the realtime Temperature
Cold room door should be linked with air curtain
Equipment failure information should be recorded, such as emergency stop,
compressor failure, etc.
Cold room needs to have auto restart function after power failure
Cold room should have Auto / Manual function
The condensed water needs to be connected to the sewer pipe
A suitable door lock mechanism should be used to ensure that the personnel in the
cold room can leave smoothly.

heater needs to be installed in the door frame & window of the cold room to prevent
the sealing strip from being frozen
The cold storage should use moisture-proof and mildew-proof lights, and the
illuminance should not be less than 300lux