Professional Documents
Culture Documents
Control Systems
2014.04
DBEU-14042B(A)
Specifications may be subject to change without prior notice for product improvement.
I. Individual Control Systems II. Centralized control systems
1 Receiver & display unit 1 Interface module
MRK-A10N 1. MIM-N01
1) Features . . . . . . . . . . . . . . . . . . . . . 10 1) Features . . . . . . . . . . . . . . . . . . . . . 44
2) Wiring. . . . . . . . . . . . . . . . . . . . . . . 10 2) Product specification . . . . . . . . . . . 44
3) Description of parts . . . . . . . . . . . . 45
2 Wireless remote controller 4) Connection diagram . . . . . . . . . . . . 46
MR-DH00 5) Connection. . . . . . . . . . . . . . . . . . . 47
1) Features . . . . . . . . . . . . . . . . . . . . . 10 5) Display . . . . . . . . . . . . . . . . . . . . . . 48
2) Description of parts . . . . . . . . . . . . 11
3) Additional function . . . . . . . . . . . . . 12 2 ERV interface module
MIM-N10
3 Wired remote controller 1) Features . . . . . . . . . . . . . . . . . . . . . 49
1. MWR-WE10N 2) Product specification . . . . . . . . . . . 49
1) Features . . . . . . . . . . . . . . . . . . . . . 13 3) Description of parts . . . . . . . . . . . . 51
2) Product specification . . . . . . . . . . . 13 4) Connection diagram . . . . . . . . . . . . 52
3) Description of parts . . . . . . . . . . . . 14 5) Connection. . . . . . . . . . . . . . . . . . . 53
4) Optional function . . . . . . . . . . . . . . 16 6) Checking the operation . . . . . . . . . 54
5) Display . . . . . . . . . . . . . . . . . . . . . . 23
6) Communication diagram . . . . . . . . 25 3 OnOff controller
2. MWR-SH00N MCM-A202DN
1) Features . . . . . . . . . . . . . . . . . . . . . 27 1) Features . . . . . . . . . . . . . . . . . . . . . 55
2) Product specification . . . . . . . . . . . 27 2) Product specification . . . . . . . . . . . 55
3) Description of parts . . . . . . . . . . . . 28 3) Description of parts . . . . . . . . . . . . 56
4) Optional function . . . . . . . . . . . . . . 30 4) Optional function . . . . . . . . . . . . . . 57
5) Display . . . . . . . . . . . . . . . . . . . . . . 32 5) Connection diagram . . . . . . . . . . . . 58
6) Communication diagram . . . . . . . . 33 6) Display . . . . . . . . . . . . . . . . . . . . . . 61
CONTROL SYSTEM
INDIVIDUAL
5 Operation mode selection switch 1 Electricity meter interface module
MCM-C200 MIM-B16N
1) Features . . . . . . . . . . . . . . . . . . . . . 73 1) Features . . . . . . . . . . . . . . . . . . . . 128
CONTROL SYSTEM
CENTRALIZED
2) Installation . . . . . . . . . . . . . . . . . . . 73 2) Display and buttons . . . . . . . . . . . 128
3) Control example . . . . . . . . . . . . . . . 74 3) Connectors . . . . . . . . . . . . . . . . . 129
4) Address & option switches . . . . . . 129
5) Specifications on electricity meter. . 130
6) Installation . . . . . . . . . . . . . . . . . . 131
III. Integrated management
INTEGRATED
8) Address assignment. . . . . . . . . . . 133
systems 9) MIM-B16N menu structure. . . . . . 133
10) Setting parameters on DMS2 (MIM-D00AN ) 136
11) Error codes. . . . . . . . . . . . . . . . . 136
1 DMS2
MIM-D00AN
POWER
1) Features . . . . . . . . . . . . . . . . . . . . . 76
2) Product specification . . . . . . . . . . . 76
3) Description of parts . . . . . . . . . . . . 77
4) Connection diagram . . . . . . . . . . . . 79
V. External control system
5) Wiring. . . . . . . . . . . . . . . . . . . . . . . 79
CONTROL SYSTEM
6) Function . . . . . . . . . . . . . . . . . . . . . 82 1 External contact interface module
MIM-B14 EXTERNAL
2 S-NET3 1) Features . . . . . . . . . . . . . . . . . . . . 138
2) Description of parts . . . . . . . . . . . 138
MST-P3P
3) Installation . . . . . . . . . . . . . . . . . . 138
1) Features . . . . . . . . . . . . . . . . . . . . 111
MANAGEMENT SYSTEM AIR CONDITIONER INSTALLATION
4) Control . . . . . . . . . . . . . . . . . . . . . 139
2) PC specification . . . . . . . . . . . . . . 111
BUILDING
3
VI. Building management systems VII. Test run tool for system
air conditioner installation
1 DMS L-net(Lonworks GW)
MIM-B18N 1 S-checker
1) Features . . . . . . . . . . . . . . . . . . . . 146
2) Product specification . . . . . . . . . . 146 MIM-C10N
3) Description of parts . . . . . . . . . . . 147 1) Features . . . . . . . . . . . . . . . . . . . . 186
4) Connection diagram . . . . . . . . . . . 149 2) Product specification . . . . . . . . . . 186
5) Wiring. . . . . . . . . . . . . . . . . . . . . . 149 3) Description of parts . . . . . . . . . . . 187
6) Commission . . . . . . . . . . . . . . . . . 152 4) Connection diagram . . . . . . . . . . . 188
7) Standard program identifier (SPID) . . 152 5) Connection. . . . . . . . . . . . . . . . . . 188
8) Item summary . . . . . . . . . . . . . . . 152 6) Main function . . . . . . . . . . . . . . . . 190
9) Network variable . . . . . . . . . . . . . 153
10) Network parameter chart . . . . . . . . 154
11) Network variable list. . . . . . . . . . . . . .155
2 S-converter
12) Detail description of network variable . . 156 MIM-C02N
1) Features . . . . . . . . . . . . . . . . . . . . 194
2 DMS B-net(BACnet GW) 2) Product specification . . . . . . . . . . 194
MIM-B17N 3) Description of parts . . . . . . . . . . . 195
1) Features . . . . . . . . . . . . . . . . . . . . 160 4) Connection diagram . . . . . . . . . . . 195
2) Product specification . . . . . . . . . . 160 5) Connection. . . . . . . . . . . . . . . . . . 196
3) Description of parts . . . . . . . . . . . 161 6) Display . . . . . . . . . . . . . . . . . . . . . 196
4) Connection diagram . . . . . . . . . . . 163
5) Wiring. . . . . . . . . . . . . . . . . . . . . . 163
6) Description of device ID . . . . . . . . 166
7) Object list . . . . . . . . . . . . . . . . . . . 167
8) Checking BACnet communication
through Wireshark . . . . . . . . . . . . 173
9) Standard object type . . . . . . . . . . . . 176
10) Property support specification . . . . . 177
4
Overview of DVM S
New communication system diargram
DMS B-net DMS L-net
(MIM-B17N) (MIM-B18N)
DMS-Bnet DMS-Lnet
S-NET3 (MST-P3P)
Lon
ACK SVC
Ethernet
DMS2
(MIM-D00AN)
F1F2
t4FU-BZFS ''
$PNNVOJDBUJPODIBOOFMPG0VUEPPS .BJO
VOJU
CH3 *OEPPSVOJUBOE4FUMBZFSDPOUSPMMFS
Outdoor units
- Set layer controller : OnOff controller (MCM-A202DN),
Touch centralized controller (MCM-A300N)
t$POUSPM-BZFS 33
$PNNVOJDBUJPODIBOOFMPG0VUEPPS .BJO
VOJUBOE$POUSPMMBZFSDPOUSPMMFS
CH4 - Control layer controller : OnOff controller (MCM-A202DN),
Outdoor units Touch centralized controller (MCM-A300N),
DMS2 (MIM-D00AN), BACnet Gw (MIM-B17N),
LonWorks GW (MIM-B18N)
PIM
Max. 8 PIMs t-PDBM-BZFS ''
$PNNVOJDBUJPOCFUXFFOJOEPPSVOJUBOE
CH5 Wired remote controller
PIM (MIM-B16N)
DMS2
(MIM-D00A)
Conventional communication
Conventional communication Controller
SAC
Product DMS2
Interface OnOff
Outdoor unit Indoor unit (BACnet GW/ S-NET mini
module Controller
LonWorks GW)
Wired remote controller (MWR-WE10N)
Interface module I (MIM-N00) 7 O O O
Interface module II (MIM-N01) O O O O
Interface module III (MIM-N10) 7 O O O
New communication controller
7.*./XJMMCFJOUFHSBUFEUP.*./BUUIFFOEPG
7 MIM-N10 is only for ERV.
6
Conventional communication
Conventional communication Controller
SAC
Product DMS2
Interface OnOff
Outdoor unit Indoor unit (BACnet GW/ S-NET mini
module Controller
LonWorks GW)
Wired remote controller (MWR-WE10) O
Conventional communication controller
7
DVM CONTROL
SYSTEMS
8
I. Individual Control Systems
CONTROL SYSTEMS
INDIVIDUAL
1 Receiver & Display unit . . . . . . . . . . . . . . . 10
2 Wireless remote controller . . . . . . . . . . . . 10
3 Wired remote controller . . . . . . . . . . . . . . 13
4 ERV wired remote controller. . . . . . . . . . . 35
9
Control Systems
130
4
8JSJOH
t$POOFDUPOFFOEPGUIFSFDFJWFSXJSFXJUIUIF3FDFJWFS%JTQMBZVOJU1$#
t$POOFDUUIFPUIFSFOEPGUIFSFDFJWFSXJSFXJUIUIFEVDUUZQFJOEPPSVOJU1$#
Connector : 13Pin
; Note
Wire length: 10m
Receiver & Display unit is only available for a duct type indoor unit.
t0QFSBUJPOUFNQFSBUVSFTFUUJOH
t'JMUFSSFQMBDFNFOUBMBSNSFTFU
t"JSTXJOHDPOUSPM
t4JNQMF0O0GGUJNFS
t*OEPPSVOJUPQUJPODPEFTFUUJOH
10
2) Description of parts
①
⑱
CONTROL SYSTEMS
② ⑨
③
INDIVIDUAL
⑲
⑩ ⑪
④ ⑫
⑳
⑤
⑥ TX ⑭
⑥ TY ⑬ TX
⑦ ⑬ TY
⑧
⑮
⑯
Ï ②, ⑥-1, ⑥-2, ⑧, ⑬-2, ⑳, is only supported and available in certain indoor units.
No Name Description
① 0O0GGCVUUPO 1SFTTUIJTCVUUPOUPUVSOPOPGGUIFJOEPPSVOJU
② 41MBTNBJPOCVUUPO 1SFTTUIJTCVUUPOUPUVSOPOPGGUIF41MBTNBJPO
③ 5VSCPCVUUPO Press this button to cool your room quickly and powerfully.
④ 5FNQCVUUPO 1SFTTUIJTCVUUPOUPJODSFBTFEFDSFBTFUIFTFUUFNQFSBUVSFCZ¡$
)PSJ[POUBMBJSTXJOH
⑤ 1SFTTUIJTCVUUPOUPBDUJWBUFEFBDUJWBUFIPSJ[POUBMBJSGMPXNPWFNFOU
CVUUPO
⑥-1 #FFQ0GGCVUUPO Press this button to mute the beep sounds that occurs when pressing the button.
Press the 2nF function button and press this button to control individual indoor unit or all indoor
⑥-2 3PPNCVUUPO
units at once.
⑦ 0OUJNFSCVUUPO 1SFTTUIFCVUUPOUPTFUUIF0O5JNFSPO
⑧ OE'CVUUPO Press this button to select the function printed under the button. (Room, Blade function)
⑨ .PEFCVUUPO Press this button to select one of the 5 operation modes. (Auto, Cool, Dry, Fan, Heat)
⑩ 2VJFUCVUUPO Press this button to select quiet mode.
1SFTTUIJTCVUUPOUPBDUJWBUFEFBDUJWBUFWFSUJDBMBJSGMPXNPWFNFOU /PUBQQMJDBCMFUP%VDUUZQF
⑪ 7FSUJDBMBJSTXJOHCVUUPO
model)
⑫ FannnnnnCVUUPO 1SFTTUIJTCVUUPOUPTFMFDUPOFPGUIFGBOTQFFET "VUP
-PX
.FEJVNBOE)JHI
>
>
⑬-1 'JMUFS3FTFUCVUUPO Press this button to turn off the filter indicator light.
Press the 2nF function button and press this button to control individual blade unit or all blades
⑬-2 #MBEFCVUUPO
at once.
⑭ HPPEhTMFFQCVUUPO Press this button to set the good’sleep mode on.
⑮ 4FU$BODFMCVUUPO 1SFTTUIJTCVUUPOUPTFUPSDBODFMUIF0O0GG5JNFSBOEHPPETMFFQNPEF
⑯ 0GG5JNFSCVUUPO 1SFTTUIJTCVUUPOUPTFUUIF0GG5JNFSPO
⑰ Operation mode indicator Indicates the operation mode.
Set temperature & On/Off Basic – Indicates the set temperature.
⑱
set time indicator 5JNFSTFUUJOHo*OEJDBUFTUIF0O0GGTFUUJNF
⑲ On/Off timer indicator *OEJDBUFTUIF0O0GGUJNFSTFUUJOH
8IFO<#FFQPGG3PPN>CVUUPOJTQSFTTFEBGUFSQSFTTJOHUIFO'CVUUPO
i3PPNwJOEJDBUPS
Room & Blade selection will be displayed with the selected indoor unit number.
⑳
indicator
8IFO<'JMUFS3FTFU#MBEF>CVUUPOJTQSFTTFEBGUFSQSFTTJOHUIFO'CVUUPO
i#MBEFwJOEJDBUPS
will be displayed with the selected blade number.
Transmission indicator Indicates when wireless signal is received (by pressing any buttons).
*OEJDBUFTXIFOO'CVUUPOJTQSFTTFE:PVDBOTFMFDUUIFTFDPOEGVODUJPO 4FMFDUJOH3PPN
2ndF indicator
Blade)
-PXCBUUFSZJOEJDBUPS Indicates the battery life.
"JSTXJOHJOEJDBUPS *OEJDBUFTXIFOWFSUJDBMPSIPSJ[POUBMBJSGMPXNPWFNFOU
Fan speed indicator Indicates the fan speed settings.
11
Control Systems
*GZPVQSFTTUIF'BO<>CVUUPO
ZPVDBODIBOHFUIFMFGUEJHJU
>
❹1SFTTUIF<.PEF>CVUUPOUPTFUUIFOFYUEJHJUTPGPQUJPODPEF
Input 20 digits in total.
❺ Press the button more than twice to set the indoor unit option code.
8IFOJOEPPSVOJUPQUJPODPEFJTTFU
BCFFQXJMMTPVOE8IFOUIFTFUUJOHJTJODPSSFDU
BMMUIF-&%POUIFJOEPPSVOJUQBOFMXJMMGMJDLFS
Ú0QUJPODPEFJTDPNQPTFEXJUIUPUBMPGEJHJUTJODMVEJOHQBHFOVNCFS Setting Ex.) Option code: 012345 – 16789A – 212345 – 36789A
From the wireless remote controller, enter the option code without
QBHFOVNCFS
Page 0 Page 1 Page 2 Page 3
¨ ¨ ¨ ¨
Option code input mode 'BO<>o3JHIUEJHJU 1SFTTUIF<.PEF>CVUUPO
ª
>
§ § § §
*GZPVQSFTTUIF<.PEF>CVUUPOBGUFSFOUFSJOHGJSTU
ª 10 digits, On timer indicator will change to Off.
¨ 1SFTTUIF<1PXFS>CVUUPONPSFUIBOUXPUJNFT
towards the indoor unit.
12
3. Wired remote controller
MWR-WE10N
1) Features
(Unit : mm)
120.0 19.5
CONTROL SYSTEMS
INDIVIDUAL
124.0
63.8
(1) Air conditioner / ERV control
t"$PQFSBUJPO0/0''DPOUSPM
t"$PQFSBUJPONPEF
TFUUJOHUFNQFSBUVSF
GBOTQFFE
BJSGMPXEJSFDUJPOTFUUJOH
t"$JOEJWJEVBMCMBEFDPOUSPMBOEPDDVQBODZEFUFDUJPO
(Function is available when indoor units support any of above functions)
t&37PQFSBUJPO0/0''DPOUSPM
t&37PQFSBUJPONPEF
GBOTQFFETFUUJOH
t"$&37FSSPSNPOJUPSJOH
t'JMUFSDMFBOJOHBMFSUBOESFTFUBMFSUUJNF
t*OEJWJEVBMHSPVQDPOUSPM
JOEPPSVOJU&37JOUFSMPDLJOHDPOUSPM
t&OFSHZTBWJOHDPOUSPM
t$POUSPMNBYJNVN*OEPPSVOJU&37JOHSPVQXJUITJOHMFXJSFESFNPUFDPOUSPMMFS
&OFSHZTBWJOHPQFSBUJPO
t6QQFS-PXFSUFNQFSBUVSFMJNJUTFUUJOH
t"VUPNBUJDPQFSBUJPOTUPQ"VUPNBUJDBMMZTUPQTUIFPQFSBUJPO
XIFOJUJTOPUVTFEGPSDFSUBJOQFSJPEPGUJNFTFUCZVTFS
8FFLMZPQFSBUJPOTDIFEVMFTFUUJOH
t8FFLMZPQFSBUJOHTDIFEVMF "$POMZ
&37POMZ
"$&37
t"CMFUPTFUEFTJSFE"$PQFSBUJPONPEF
TFUUJOHUFNQFSBUVSFBOEGBOTQFFEUPPQFSBUFCBTFEPOXFFLMZSFTFSWBUJPO
t"CMFUPBQQMZTDIFEVMFFYDFQUJPOEBZGPSGMVJENBOBHFNFOU
(4) User convenience function
t$IJMEMPDL
t%JGGFSFOUCVUUPOQFSNJTTJPOMFWFMT
0QFSUJPONPEF
UFNQFSBUVSFTFUUJOH
0/0''
GBOTQFFE
t#VJMUJOSPPNUFNQFSBUVSFTFOTPS
t4FSWJDFNPEFTVQQPSU
- Indoor unit cycle data monitoring
- Indoor unit option code setting and monitoring
- Indoor unit address and option setting and monitoring
2) Product specification
Power Supply DC12V
Power Consumption 2W
0QFSBUJOH5FNQFSBUVSFSBOHF 0°C~40°C
0QFSBUJOH)VNJEJUZSBOHF 30%RH~90%RH
Communication 2-wire PLC
CPNQBUJCMFQSPEVDU
Indoor unit AM7777N777777Model
13
Control Systems
3) Description of parts
④ ⑤⑨⑩⑪ ⑫ ⑬
(1) Display
①
⑭
②
⑮
③ ⑯
⑥ ⑰
⑦ ⑱
⑧ ⑳ ⑲
-&%JOEJDBUPS (SFFO/PSNBM3FE/FFEUPCFDIFDLFE
0QFSBUJPO0O0GGCVUUPO
5FNQFSBUVSFTFUUJOHCVUUPO
② %JTQMBZT2VJFU4MFFQPQFSBUJPO
③ %JTQMBZT*OEPPSUFNQFSBUVSF4FUUFNQFSBUVSF
Air
conditioner ④ Displays discharge temperature control
related ⑤ Displays CO2QPXFSDPOTVNQUJPO
information
⑥ Displays AC fan speed
⑧ %JTQMBZT"JSTXJOH 6Q%O
⑨ 8FFLMZTDIFEVMF)PMJEBZTFUUJOHEJTQMBZT
⑬ %JTQMBZT$VSSFOUUJNFEBZMJHIUTBWJOHUJNFTDIFEVMFEUJNF
⑰ %JTQMBZT*OWBMJEPQFSBUJPO'JMUFSDMFBOJOH GJMUFSDMFBOJOHQFSJPE
⑱ %JTQMBZT%VTUCPYDMFBOJOHBMFSUDIFDLQBSUMPDL"MMMPDL
%JTQMBZT.PUJPOEFUFDUTFOTPS&YIBVTUIPPE&YUFSOBMJOUFSDPOOFDUJPODPOUSPM"VUP
⑲
Common DMFBO)VNJEJGZJOH&OFSHZTBWJOH0VUEPPSBJSTVQQMZJOUBLF$FOUSBMJ[FEDPOUSPM
function
⑳ Displays S-Plasma Ion
related
information Displays Indoor CO2 density
⑫
⑨
CONTROL SYSTEMS
⑧ ⑱
INDIVIDUAL
② ⑬
①
⑮
③ ⑳
⑤
⑥
⑦
④⑪ ⑩⑯⑲ ⑭ ⑰
Common ⑯ &4$CVUUPO Return to general mode from schedule and detailed setting screens
function ⑰ %FMFUFCVUUPO Cancel the schedule setting
related
CVUUPO ⑱ "VUP$MFBOCVUUPO Use the auto cleaning function for your air conditioner
(ERV)
'BOTQFFECVUUPO $IBOHFUIFGBOTQFFEGPSZPVS7FOUJMBUPS &37
related
CVUUPOT &4BWFSCVUUPO Begin Energy Saving Operation
$MFBOVQCVUUPO 4FMFDUBJSQVSJGJDBUJPOUISPVHIUIFJOPVUMPBEDPOUSPMT
15
Control Systems
3) Description of parts
(3) PCB
XJSJOHUFSNJOBM
②
4) Option function
UTFSTFUUJOHNPEF
Main 4VC SEG
Function Default 3BOHF Unit
menu menu Used
1 "VUPTUPQUJNFTFUUJOHDIFDLJOH 1,2 0 0~12 hours 1 hour
-PXFTUUFNQFSBUVSF 1,2 16 (61) _¡$ _¡'
¡$ ¡'
2 5FNQMJNJUT<¡$ ¡'
>
Highest temperature 3,4 30 (86) _¡$ _¡'
¡$ ¡'
7FOUJMBUPS &37
EFMBZ 7FOUJMBUPS &37
%FMBZ
1 0 0 – No use, 1 – use -
UJNFTFUUJOHDIFDLJOH "QQMJDBUJPO :/
7
<8IFOVTJOH7FOUJMBUPS
&37
JOUFSMPDLJOHDPOUSPM> %FMBZ5JNF 3,4 30 30~60 minutes 1 minute
0 Reset to user mode defaults (except the current time) 1 0 0 – No use, 1 – Reset -
16
f How to set the user mode
*GZPVXBOUUPTFUUIFEFUBJMFETFUUJOHT
QSFTTUIF<6TFS4FU>CVUUPO
t:PVXJMMFOUFSUIF6TFS4FUNPEF
BOEUIF<.BJO.FOV>XJMMCFEJTQMBZFE
(2) Refer to the Wired Remote Controller’s User Set list on the next
QBHFUPTFMFDUUIFEFTJSFENFOV
t6TJOHUIF[∧]/[∨] buttons, select a main menu number and press the [>] button
CONTROL SYSTEMS
to enter the sub-menu setting screen.
INDIVIDUAL
t6TJOHUIF[∧]/[∨] buttons, select a sub-menu number and press the [>] button
to enter the data setting screen.
t0ODFZPVIBWFFOUFSFEUIFTFUUJOHTDSFFO
UIFDVSSFOUTFUUJOHXJMMCFEJTQMBZFE
t3FGFSUPUIFDIBSUGPSEBUBTFUUJOH
t6TJOHUIF[∧]/[∨] buttons, change the settings and press the [>] button to
move to the next setting.
t1SFTTUIF4FUCVUUPOUPTBWFUIFTFUUJOHBOEFYJUUPUIFTVCNFOVTFUUJOHTDSFFO
t1SFTTUIF&TDCVUUPOUPFYJUUPHFOFSBMNPEF
; Note
While setting the data, you can use the [∧]/[∨] buttons to set the range of SEG used.
8IJMFDPOGJHVSJOHUIFTFUUJOH
QSFTTUIF<&TD>CVUUPOUPFYJUUPUIFTVCNFOVTFUUJOHTDSFFOXJUIPVUTBWJOHUIFTFUUJOH
f CuSSFOUUJNFTFUUJOH &YBNQMF
1SFTTUIF<6TFS4FU>CVUUPO
*OUIFTVCNFOV
TFMFDUhEBZ
t(Main Menu) will be displayed, and ".1.
IPVS
NJOVUFh
you can press the [∧]/[∨] buttons to tPress the [∧]/[∨] buttons to select no.
select No.4, which will set the current :PVDBOTFUUIFhEBZ
".1.
IPVS
time. minute'.
4) Option function
Service mode
Main 4VC SEG
Function Default 3BOHF Unit
menu menu Used
Wired remote $PPMJOH)FBUJOHTFMFDUJPO 1 0 $PPMJOH)FBUJOH
$PPMJOHPOMZ -
controller Option Use of wireless remote controller 2 1 0-No use, 1-Use -
1
TFUUJOHDIFDLJOH ."*/46#XJSFESFNPUFDPOUSPMMFS 3 0 0-MAIN, 1-SUB -
(1) 5FNQFSBUVSFVOJU 4 0 o$FMTJVT ¡$
o'BISFOIFJU ¡'
5
compensation 5FNQFSBUVSFDPNQFOTBUJPOWBMVF 4,5,6 - _ ¡$
¡$
18
Main 4VC SEG
Function Default 3BOHF Unit
menu menu Used
4FUUJOHDIFDLJOHUIFEJGGFSFOUWBMVF 1, 2 - 0~30 1
CONTROL SYSTEMS
31.TFUUJOHDIFDLJOH 3, 4 - 0~25 1RPM
INDIVIDUAL
")6TFUUJOH 0- Pre,
1
checking Filter performance 5 - 1-Medium performance, -
2-High performance
)VNJEJUZTFUUJOHDIFDLJOH 6 - 0-30, 1-40, 2-50 -
5 Use of discharge temperature
Indoor unit, 1 - 0-No use, 1-Use -
AHU discharge control
2 Cooling discharge temperature 3, 4 - _¡$ ¡$
temperature
TFUUJOHDIFDLJOH Heating discharge temperature 5, 6 - _¡$ ¡$
Fresh Duct discharge Cooling discharge temperature 1, 2 - _¡$ ¡$
3
temperature checking Heating discharge temperature 3, 4 - _¡$ ¡$
Use of cold air prevention 1 - 0-No use, 1-Use -
&371MVTTFUUJOH Use of humidification 2 - 0-No use, 1-Use -
1
checking Use of fan operation in defrost 3 - 0-No use, 1-Use -
Use of humidification 4 - 0-No use, 1-Use -
&371MVTUFNQFSBUVSF Cooling 1, 2 - _¡$ ¡$
2
TFUUJOHDIFDLJOH Heating 3, 4 - _¡$ ¡$
6
&371MVT"VUPNPEF Set temperature 1, 2 - _¡$ ¡$
3 temperature
TFUUJOHDIFDLJOH Set temperature difference 3, 4 - _¡$ ¡$
4FUUJOHDIFDLJOHUIFDPNQFOTBUJPOUFNQFSBUVSF"
1, 2 - _¡$ ¡$
VOEFSUIF)FBUJOH&&7DPOUSPMGPS&371MVT
4
Checking the compensation temperature B under the /POVTFIVNJEJGJFS ¡$
3, 4 - -
)FBUJOH&&7DPOUSPMGPS&371MVT 6TFIVNJEJGJFS ¡$
4&(NFBOTPQUJPOTFUUJOHQBHF4&(_NFBOTPQUJPODPEF
2)* If you enter Main menu #4, you must select the targeted indoor unit address and then select the sub menu.
.PEFNBTUFSJOEPPSVOJU5IFJOEPPSVOJUXIJDIDBOEFDJEFUIFPQFSBUJPONPEF0UIFSJOEPPSVOJUGPMMPXT.PEFNBTUFS
indoor unit's operation mode.
4)* Power master reset : Setting for finding the most stable power supply indoor unit.
f5PTFUEJHJUPQUJPO
1BHF 0QUJPO4FUUJOH )PXUPNPWFCFUXFFOQBHFT
1BHF 1~5th digit option 1SFTTUIF<>CVUUPOUPHPUP1BHF
1BHF 6~10th digit option 1SFTTUIF<>CVUUPOUPHPUP1BHF
1BHF 11~15th digit option 1SFTTUIF<>CVUUPOUPHPUP1BHF
1BHF 16~20th digit option 1SFTTUIF<>CVUUPOUPHPUP1BHF
1BHF 21~24th digit option -
19
Control Systems
4) Option function
Service mode
f How to set the service mode
(1) If you want to use the various additional functions for your Wired
3FNPUF$POUSPMMFS
QSFTTUIF<4FU>BOE<&TD>CVUUPOTBUUIFTBNF
time for more than three seconds.
t:PVXJMMFOUFSUIFBEEJUJPOBMGVODUJPOTFUUJOHT
BOEUIF<NBJONFOV>XJMMCFEJTQMBZFE
(2) Refer to the list of additional functions for your Wired Remote Controller
POUIFOFYUQBHF
BOETFMFDUUIFEFTJSFENFOV
tUsing the [∧]/[∨] buttons, select a main menu number and press the [>] button
to enter the sub-menu setting screen.
tUsing the [∧]/[∨] buttons, select a sub-menu number and press the [>] button
to enter data setting screen.
tWhen you enter the setting stage, the current setting will be displayed.
tRefer to the chart for data settings.
tUsing the [∧]/[∨] buttons, select the settings. Press the [>] button to move to
the next setting.
t1SFTTUIF<4FU>CVUUPOUPTBWFUIFTFUUJOHTBOEFYJUUPUIFTVCNFOVTFUUJOHTDSFFO
t1SFTTUIF<&TD>CVUUPOUPFYJUUPOPSNBMNPEF
; Note
While setting the data, you can use the [∧]/[∨] buttons to set the range of SEG
8IJMFDPOGJHVSJOHUIFTFUUJOH
QSFTTUIF<&TD>CVUUPOUPFYJUUPUIFTFUUJOHTVCNFOVXJUIPVUTBWJOHZPVSDIBOHFT
f&YBNQMFNFUIPEPGTFUUJOHXJSFESFNPUFDPOUSPMMFSPQUJPO
1SFTTUIF<4FU>BOE<&4$>CVUUPOTBUUIFTBNFUJNFGPSNPSFUIBOTFDPOET
t8IFO(Main menu) is displayed press the [∧]/[∨] button to select no.1.
1SFTT<4FU>CVUUPOUPDPNQMFUFUIFPQUJPOTFUUJOH
tSave the setting value and exit to sub menu.
20
1SFTT<&TD>CVUUPOUPFYJUUPOPSNBMNPEF
Built-in temperature sensor of wired remote controller
f5FNQFSBUVSFDPOUSPMXJUICVJMUJOUFNQFSBUVSFTFOTPS
CONTROL SYSTEMS
INDIVIDUAL
"QQMJFTUPBMMUIFJOEPPSVOJUTDPOOFDUFEXJUIJOBHSPVQ
(However, indoor unit is limited to DVM S series )
Ï Check the setting of the wired remote controller built-in sensor from the service menu.
Main 4VC Used Factory
Function Description Unit
menu menu SEG TFUUJOH
$PPMJOH)FBUJOHTFMFDUJPO 1 0 $PPMJOH)FBUJOH
$PPMJOHPOMZ -
Wireless remote Use of wireless remote
2 1 0-No use, 1-Use -
controller controller
1
0QUJPOTFUUJOH ."*/46#XJSFESFNPUF
3 0 0-MAIN, 1-SUB -
checking (1) controller
5FNQFSBUVSFVOJU 4 0 o$FMTJVT ¡$
o'BISFOIFJU ¡'
f HeBUJOHNPEFUFNQFSBUVSFDPNQFOTBUJPO
*OEPPSVOJU*/45"--PQUJPOTFUUJOH 3FGFSUPJOEPPSVOJUJOUBMMBUJPONBOVBM
; Note
8IFOCVJMUJOTFOTPSPGUIFXJSFESFNPUFDPOUSPMMFSJTVTFE
IFBUJOHNPEFUFNQFSBUVSFDPNQFOTBUJPO ¡$PS¡$
XJMMCFSFTFUUP¡$
Ï If there is no option switch on the indoor unit PCB, check the setting of the heating temperature compensation from the service menu.
Main 4VC Used Factory
Function Description Unit
menu menu SEG TFUUJOH
Use of external control 1 - 0-No use, 1-Use -
Use RPM compensation 2 - 0-No use, 1-Use -
Indoor
Filter time 3 - 0-2000 hours, 1-1000 hours -
3 6 unit option
checking(2) Heating temperature
4 - ¡$
¡$ -
compensation
&&7TUPQTUFQJOIFBUJOH 5 - TUFQ
TUFQ -
21
Control Systems
4) Option function
EOFSHZTBWJOHPQFSBUJPONPEF
Ï&OFSHZTBWJOHPQFSBUJPONPEFJTBWBJMBCMFPOMZXIFOUIFSFJTBUMFBTUPOFJOEPPSVOJUBOE&37JTDPOOFDUFE
t By comparing indoor room temperature, setting temperature and outdoor temperature, wired remote controller changes
&37PQFSBUJPONPEFBOEGBOTQFFEUPNJOJNJ[FVOOFDFTTBSZPVUEPPSVOJUPQFSBUJPO
t &OFSHZTBWJOHPQFSBUJPOJTOPUBWBJMBCMFXIFO&37JTOPUDPOOFDUFE
t &OFSHZTBWJOHPQFSBUJPOJTOPUBWBJMBCMFXIFOA$FOUSBMJ[FEDPOUSPMJTTFU
t &OFSHZTBWJOHPQFSBUJPOXJMMOPUCFFYFDVUFEXIFO&37JTTFUUP0VUJOHNPEFPSTFUJOFYUFSOBMJOUFSMPDLJOHNPEF
t 5FNQFSBUVSFNFBTVSFNFOUJTTFUBTJOEPPSVOJUUFNQFSBUVSFTFOTPSBTEFGBVMU
BOEJUDBOCFDIBOHFEEFQFOEJOHPOUIFXJSFE
remote controller option setting.
22
5) Display
Error display
&SSPSDPEFTGPSUIF8JSFE3FNPUF$POUSPMMFSBOEUIFQSPEVDUDPOOFDUFEUPUIF8JSFE3FNPUF$POUSPMMFSXJMMCF
displayed in the LCD display.
CONTROL SYSTEMS
INDIVIDUAL
LCD Display
f When an Error Occurs in Your Indoor/Outdoor Units (Product Group Display : A20)
t5IFQSPEVDUBEESFTTGPSUIFFSSPSXJMMCFEJTQMBZFE
GPMMPXFECZUIFFSSPSDPEF
Example : Error 121 occurred in indoor unit with main address no. 18 (decimal numbers).
Refers to the indoor unit Outdoor unit address Indoor unit Main address Error code
(Displayed in hexadecimal) (Displayed in hexadecimal)
Refers to the ERV unit ERV unit Main address Error code
(Displayed in hexadecimal)
23
Control Systems
5) Display
/PDPNNVOJDBUJPOCFUXFFOXJSFESFNPUFDPOUSPMMFSBOEJOEPPS&37VOJUT
8JSFESFNPUFDPOUSPMMFSJTDPOOFDUFEPO''DIBOOFM
5XPPSNPSFXJSFESFNPUFDPOUSPMMFSTBSFTFUBT.BTUFS .BJO
When using Master remote controller
%FUFDUJPOBWBJMBCMFGSPNCPUI.BTUFS
/P&37VOJUJOTUBMMFEGPSJOUFSMPDLJOHGVODUJPO
Slave wired remote controller
0WFSJOEPPS&37JOEPPSVOJUTJOTUBMMFE
*OEPPSVOJUTPGEJGGFSFOUUFNQFSBUVSFTFUUJOH ¡$¡'
DPOOFDUFEUPTBNFXJSFE Detection available in Master wired
remote controller remote controller
Wired remote controller(s) has different temperature unit setting with indoor
unit(s)
tMemory error
tNo damper feedback
; Note
'PSUIFFSSPSDPEFTGPSZPVSJOEPPSPVUEPPSVOJUTBOEWFOUJMBUPS &37
SFGFSUPUIFJOTUBMMBUJPONBOVBMPGFBDIEFWJDF
24
$PNNVOJDBUJPOEJBHSBN
Individual control (1) Control 1 indoor unit with 1 wired remote controller
F1/F2
Indoor unit
CONTROL SYSTEMS
Outdoor unit
F3/F4
INDIVIDUAL
Wired remote controller
Group control (1) Control multiple indoor units with 1 wired remote controller
Group control (2) Control multiple indoor units connected to different outdoor units with 1 wired remote controller
F1/F2
Outdoor unit
Outdoor unit
F3/F4
Wired remote controller
f Caution
When controlling group of indoor units connected to different outdoor unit, address of the each outdoor unit must be set differently.
25
Control Systems
$PNNVOJDBUJPOEJBHSBN
Group control (3) Control 1 or multiple indoor units with 2 wired remote controllers
F1/F2
Indoor unit
Outdoor unit F3/F4
Group control (4) Control multiple indoor units connected to different outdoor units with 2 wired remote controller
F1/F2
Outdoor unit
Indoor unit
Outdoor unit
F3/F4
Wired remote controller
f Caution
When controlling group of indoor units connected to different outdoor unit, address of the each outdoor unit must be set differently.
Max. distance between the farthest indoor unit and wired 100m
remote controller : 100m
26
MWR-SH00N
1) Features
CONTROL SYSTEMS
INDIVIDUAL
t4JNQMJGJFEXJSFESFNPUFDPOUSPMMFS
t"$PQFSBUJPO0/0''DPOUSPM
t'BOTQFFEDPOUSPM
t4FUUJOHPQFSBUJPOUFNQFSBUVSF
t3FTFUGJMUFSDMFBOJOHBMFSUJOEJDBUPS
t"EKVTUBJSGMPXEJSFDUJPO
t0QFSBUJPOPOPGGUJNFSGVODUJPO
(Unit : mm)
122.0
75.0
16.6
2) Product specification
Power supply %$7
Power consumption 1.5 W
0QFSBUJOHUFNQFSBUVSFSBOHF ¡$_¡$
0QFSBUJOHIVNJEJUZSBOHF 30 % RH~90 % RH
Communication XJSF1-$
.BYJNVNMFOHUIPGDPOOFDUJPO 100 m
.BYJNVNOVNCFSPG
16 indoor units
DPOUSPMMBCMFEFWJDFT
CPNQBUJCMFQSPEVDU
Indoor unit AM7777N777777Model
27
Control Systems
③ Set temperature indicator Indicates the set temperature when the indoor unit turns on.
④ Fan speed indicator Indicates the fan speed settings.
⑤ "JSTXJOHJOEJDBUPS Indicates when vertical air swing is on.
⑥ Quiet mode indicator Indicates when quiet mode is on.
⑦ 'JMUFSDMFBOJOHJOEJDBUPS Indicates when preset filter cleaning period is passed.
: Indicates when On timer is set
: Indicates when Off timer is set
⑧ Timer indicator : ① 5JNFSNPEFo%JTQMBZTUIFTFUUJNFGPS0O0GGUJNFS
(Min. 30 minutes ~ Max. 18 hours)
② General mode - %JTQMBZTSFNBJOJOHUJNFCFGPSF5JNFSGVODUJPOXJMMFYFDVUF
5IJTJDPOXJMMCFEJTQMBZFEXIFOCVUUPOJTMPDLFEPSXIFOVOBWBJMBCMFGVODUJPO
(function which indoor unit does not support) is selected
⑨ Lock / Restricted indicator ① Icon On: All buttons are locked
② Icon blinks for 3 seconds: When partially locked button is pressed or unavailable function
(function which indoor unit does not support) is selected
⑩ SPi indicator Indicates that SPi or other cleaning function of the indoor unit is on.
⑪ Inspection indicator Indicates that inspection is required.
⑫ 0O0GGCVUUPO 1SFTTUIJTCVUUPOUPUVSOPOPGGUIFJOEPPSVOJU
⑬ .PEFCVUUPO Press this button to select the desired operation mode. (Auto ¤ Cool ¤ Dry ¤ Fan ¤ Heat)
1SFTTUIJTCVUUPOUPTFMFDUPOFPGUIFGBOTQFFETGSPN"VUP
-PX
.FEJVN
)JHI
5VSCP
⑭ 'BOTQFFECVUUPO Available Fan Speed may differ depending on the operation mode of the indoor unit.
-PX¤ Medium ¤ High ¤5VSCP¤ Auto
1SFTTUIJTCVUUPOUPUVSOPOPGGUIFWFSUJDBMBJSTXJOHXIFOUIFJOEPPSVOJUTVQQPSUTWFSUJDBMBJS
⑮ "JSTXJOHCVUUPO
swing movement.
5IJTCVUUPODBOCFVTFEPOMZGPS5JNFS
6TFSNPEF
4FSWJDFNPEF
⑯ 4FU$BODFMCVUUPO
*Short press: Set (Save) * Press and hold for 3 seconds: Cancel
5JNFSCVUUPO'JMUFSSFTFU 4IPSUQSFTT:PVDBOTFUUIF0O0GGUJNFS
⑰
CVUUPO * Press and hold for 3 seconds: Resets the filter cleaning alert indicator.
① General mode
1SFTTUIJTCVUUPOUPJODSFBTFEFDSFBTFUIFTFUUFNQFSBUVSFCZQSFTFUVOJU
* Short press - adjust the temperature by 1℃ or 0.5℃ or 0.1℃ depending on the setting.
Temperature adjustment / * Press and hold – adjust the temperature by 1℃ every 0.5 second
⑱
5JNFBEKVTUNFOUCVUUPO ②5JNFSNPEF
1SFTTUIJTCVUUPOUPJODSFBTFEFDSFBTFUIFTFUUJNF
6QUPIPVST*ODSFBTFEFDSFBTFCZNJOVUFVOJU
0WFSIPVST*ODSFBTFEFDSFBTFCZIPVSVOJU
28
PCB
No. Name Description
Power/communication
① $POOFDUUPJOEPPSVOJU ''
connection terminal
CONTROL SYSTEMS
INDIVIDUAL
①
4) Option function
UTFSTFUUJOHNPEF
SEG in use
f How to set 1 2
Sub Menu
Main Menu
Up
Down
Left 3JHIU
<6TFSNPEFTDSFFO>
Exit Save
Press for more than 3
seconds simultaneously
Main
4VCNFOV Function Default 1BHFJOVTF 3BOHF Save
menu
0 1 Reset User mode to default value 0 1 0 - Disabled, 1 - Reset none
1 -PDLBMM 0 1 6OMPDL
-PDL o
2 -PDL0O0GGCVUUPO 0 1 6OMPDL
-PDL o
3 -PDL.PEFCVUUPO 0 1 6OMPDL
-PDL o
1 Partially lock -PDL5FNQFSBUVSF
4 0 1 6OMPDL
-PDL o
buttons adjustment button
5 -PDL'BOTQFFECVUUPO 0 1 6OMPDL
-PDL o
6 -PDL5JNFSCVUUPO 0 1 6OMPDL
-PDL o
1 5FNQFSBUVSF -PXFSUFNQFSBUVSF 16 1 16~30 o
2
2 restriction Upper temperature 30 1 16~30 o
29
Control Systems
4) Option function
SEG in use
Service mode Sub Menu 1 2
Up
Down
Left 3JHIU
<4FSWJDFNPEFTDSFFO>
Exit Save
Press for more than 3 1BHFEJTQMBZ
seconds simultaneously
1BHF 1BHF 1BHF 1BHF 1BHF
On
Auto Cool Dry Fan Heat
1BHF 1BHF 1BHF 1BHF 1BHF
Off
Auto Cool Dry Fan Heat
CONTROL SYSTEMS
controller
Set unit for desired temperature (0,1,2) (Only available
6 0 1 ¡$
¡$
¡$
INDIVIDUAL
XIFOUFNQFSBUVSFJTEJTQMBZFEJO$FMTJVT ¡$
SFUUJOHNPEFNBTUFSJOEPPSVOJU
F1/F2
Indoor unit
Outdoor
unit
F3/F4
t Only when the wired remote controller is connected to an indoor unit directly
(1:1 connection), you can set the mode master indoor unit that sets the
operation mode of the outdoor unit.
System reset
t Reset the power of the simplified wired remote controller
31
Control Systems
5) Display
Error display
t &SSPSDPEFTPGGPSUIFTJNQMJGJFEXJSFESFNPUFDPOUSPMMFSBOEUIFQSPEVDUDPOOFDUFEUPJUXJMMCFEJTQMBZFEPOUIF-$%EJTQMBZ
f8IFOBOFSSPSPDDVSTJOZPVSJOEPPSPVUEPPSVOJUT 1SPEVDUHSPVQEJTQMBZ"
t Address of the product with error and the error code will be displayed alternately.
&YBNQMFError 121 occurs for indoor unit No. 10 (Decimal digits)
Refers to the indoor unit Outdoor unit address Indoor unit Main address Error code
(Displayed in hexadecimal) (Displayed in hexadecimal)
5 t 5XPPSNPSFXJSFESFNPUFDPOUSPMMFSTBSFTFUBT4MBWF -
t .FNPSZ FYUFSOBM30.
SFBEXSJUFFSSPS
5IJTFSSPSJTEFUFDUFEPOMZEVSJOHQPXFSSFTFU*GFSSPSPDDVSTPONFNPSZ
6 -
after power has turned on, it will not effect on operation of the wire
remote controller display and therefore error code will not be displayed.
32
$PNNVOJDBUJPOEJBHSBN
Individual control (1) Control 1 indoor unit with 1 wired remote controller
CONTROL SYSTEMS
F1/F2
INDIVIDUAL
Indoor unit
Outdoor unit
F3/F4
Wired remote controller
Group control (1) Control multiple indoor units with 1 wired remote controller
Group control (2) Control multiple indoor units connected to different outdoor units with 1 wired remote controller
F1/F2
Outdoor unit
Outdoor unit
F3/F4
Wired remote controller
f Caution
When controlling group of indoor units connected to different outdoor unit, address of the each outdoor unit must be set differently.
33
Control Systems
$PNNVOJDBUJPOEJBHSBN
Group control (3) Control 1 or multiple indoor units with 2 wired remote controllers
F1/F2
Indoor unit
Outdoor unit F3/F4
Group control (4) Control multiple indoor units connected to different outdoor units with 2 wired remote controller
F1/F2
Outdoor unit
Indoor unit
Outdoor unit
F3/F4
Wired remote controller
f Caution
When controlling group of indoor units connected to different outdoor unit, address of the each outdoor unit must be set differently.
Max. distance between the farthest indoor unit and wired 100m
remote controller : 100m
34
4. ERV wired remote controller
MWR-VH12N
1) Features
(Unit : mm)
CONTROL SYSTEMS
INDIVIDUAL
122.0
75.0
16.6
t8JSFESFNPUFDPOUSPMMFSGPS&37
t&37PQFSBUJPO0/0''DPOUSPM
t'BOTQFFEDPOUSPM
t0QFSBUJPONPEFTFUUJOH
t'JMUFSSFQMBDFNFOUBMBSNSFTFU
t0VUJOHNPEF
t4JNQMF0O0GGUJNFS
2) Product specification
Power supply %$7
0QFSBUJOHUFNQFSBUVSFSBOHF ¡$_¡$
0QFSBUJOHIVNJEJUZSBOHF 30 % RH~90 % RH
Communication XJSF1-$
.BYJNVNMFOHUIPGDPOOFDUJPO 100 m
.BYJNVNOVNCFSPGDPOUSPMMBCMFEFWJDFT &37T
CPNQBUJCMFQSPEVDU
&37 /FXDPNNVOJDBUJPO&37POMZ
35
Control Systems
⑧
⑨ ⑦
⑥
①
⑤
② ④
③
⑩ ⑭
⑪ ⑮
⑫ ⑯
⑬
② (FOFSBMNPEFo%JTQMBZTSFNBJOJOHUJNFCFGPSF5JNFSGVODUJPOXJMMFYFDVUF
③ 0VUJOHNPEFJOEJDBUPS Indicates when outing mode is on.
④ 'JMUFSDMFBOJOH QFSJPE
JOEJDBUPS Indicates when preset filter cleaning is required.
⑤ Fan speed indicator Indicates current fan speed settings.
⑥ S-Plasma ion(SPI) indicator (optional) Indicates when S-Plasma ion(SPI) function is on.
⑦ CO2 sensor indicator (optional) *OEJDBUFTJOEPPS$0EFOTJUZXIFOUIFTFOTPSJTPO *GUIF&37JTPQFSBUJOH
36
PCB
CONTROL SYSTEMS
INDIVIDUAL
No. Name Description
① 1PXFSDPNNVOJDBUJPO
① $POOFDUUPJOEPPSVOJU ''
connection terminal
4) Option function
UTFSTFUUJOHNPEF
f How to set
SEG used
12
Sub menu
Main menu
-FGU3JHIU
p p p p p
p p p p
37
Control Systems
Service mode
f How to set
SEG used
12
Sub menu
Main menu
1 remote controller
Check the MICOM code of Page
3 information 0 MICOM code
&37XJSFESFNPUFDPOUSPMMFS 1~3
Check the software version of Page
4 0 Updated date
&37XJSFESFNPUFDPOUSPMMFS 1~3
&377JFX Page Address of registered device
1 4FUUJOH 5BSHFU
38
Main 4VC SEG
Function Default value 3BOHF Remarks
menu menu in use
$IFDL4FUJOEPPSVOJUWJFX Indoor unit Page Address of registered device No
CONTROL SYSTEMS
1
INDIVIDUAL
master &37WJFX Page Address of registered device
2 $IFDL4FU&37WJFXNBTUFS
System reset
t3FTFUUIFQPXFSPGUIF&37XJSFESFNPUFDPOUSPMMFS
39
Control Systems
Error display
&SSPSDPEFTGPSUIF&37XJSFESFNPUFDPOUSPMMFSBOEUIFQSPEVDUDPOOFDUFEUPJUXJMMCFEJTQMBZFEPOUIF-$%EJTQMBZ
f8IFOBOFSSPSPDDVSTJOZPVSJOEPPSPVUEPPSVOJUT 1SPEVDUHSPVQEJTQMBZ"
t Address of the product with error and the error code will be displayed alternately.
Example : Error 101 occurs for indoor unit No. 10 (Decimal digits)
f8IFOBOFSSPSPDDVSTJOZPVSWFOUJMBUPS &37
BOE&37JOUFSGBDFNPEVMF 1SPEVDUHSPVQEJTQMBZC
t Address of the product with error and the error code will be displayed alternately.
&YBNQMF&SSPSPDDVSTGPSWFOUJMBUPS &37
/P %FDJNBMEJHJUT
&37BEESFTT %JTQMBZFEJOIFYBEFDJNBM
Error codes
Display Description
t5SBDLJOHFSSPSCFUXFFO&37XJSFESFNPUFDPOUSPMMFSBOEWFOUJMBUPS &37
GPSPWFSNJOVUFT
tNo indoor unit installed for interlocking function
t0WFS&37JOEPPSVOJUTJOTUBMMFE
t5IF&37XJSFESFNPUFDPOUSPMMFSNVTUCFSFTFUBGUFSDIFDLJOHUIFOVNCFSPGJOTUBMMFE&37JOEPPSVOJUT
t*OTUBMMBUJPOFSSPSJO4MBWF&37XJSFEremote controller
8IFOUXPPSNPSFTMBWF&37XJSFESFNPUFDPOUSPMMFSTBSFJOTUBMMFE
40
$POOFDUJPOEJBHSBN
CONTROL SYSTEMS
COM2(F3, F4) COM2(F3, F4) COM2(F3, F4)
INDIVIDUAL
&37XJSFESFNPUFDPOUSPMMFS &37XJSFESFNPUFDPOUSPMMFS &37XJSFESFNPUFDPOUSPMMFS
&37XJSFESFNPUFDPOUSPMMFS
$POUSPMNVMUJQMF&37TDPOOFDUFEUPEJGGFSFOU&37JOUFSGBDFNPEVMFTXJUITJOHMFXJSFE
Group control (2)
remote controller
&37JOUFSGBDFNPEVMF
COM1(F1, F2)
CN2
BLK
CN4
CN3
RED
&37
&37JOUFSGBDFNPEVMF
COM2(F3, F4)
CN2
BLK
CN4
CN3
RED
COM1(F1, F2)
&37 &37XJSFESFNPUFDPOUSPMMFS
COM2(F3, F4)
41
Control Systems
Outdoor unit
&37
&37XJSFESFNPUFDPOUSPMMFS
f Caution
$POOFDUUIFEFWJDFTBTUIFBCPWFEJBHSBNGPSFYUFSOBMJOUFSMPDLJOHDPOUSPMXIJDIJOUFSMPDL&370O0GGXJUIJOEPPSVOJU0O0GG
&37XJSFESFNPUFDPOUSPMMFSDBOOPUDPOUSPMJOEPPSVOJUT
&37XJSFESFNPUFDPOUSPMMFSBOEXJSFESFNPUFDPOUSPMMFSGPSJOEPPSVOJUTDBOOPUCFDPOOFDUFEBUUIFTBNFUJNF "838&/FUD
MBYJNVNMFOHUIPGDPOOFDUJPO
.BYEJTUBODFCFUXFFOUIFGBSUIFTU&37BOEXJSFESFNPUF
controller : 100m 100m
42
II. Centralized control systems
1 Interface module . . . . . . . . . . . . . . . . . . . 44
2 ERV interface module . . . . . . . . . . . . . . . 49
3 OnOff controlle . . . . . . . . . . . . . . . . . . . . . 55
CONTROL SYSTEMS
CENTRALIZED
4 Touch centralized controller . . . . . . . . . . . 62
5 Operation mode selection switch . . . . . . 73
43
Control Systems
1) Features
tCommunication interface module between new communication ERV and controller
tConnect 1 ERV interface module to Max. 16 ERVs
tIndividual control – Maximum 16 ERVs
tGroup control – Maximum 16 groups
tSupported communication type
1) Conventional communication outdoor unit ↔ New communication upper level controller
2) New communication outdoor unit ↔ Conventional communication upper level controller
❋ This interface module does not support conenction between
CN4
CN3 CN2
RED BLK
96.1
CN4
Y-GRN
RED
YEL
CN3 CN2
RED BLK
2) Product specification
Power Supply DC12V
Power Consumption 2.4 W
Operating Temperature range -10°C~50°C
Operating Humidity range 10%RH~90%RH
Communication RS485 x 2
Max.Communication Length 1000M
1) New communication outdoor unit ¥ Conventional communication
upper level controller
t''PVUEPPSVOJU
t33VQQFSMFWFMDPOUSPMMFS
Maximum number of connection 2) Conventional communication outdoor unit ¥ New communication
upper level controller
t''PVUEPPSVOJU
t335PUBMVQUPVQQFSMFWFMDPOUSPMMFST 0OMZ%.4
BACnet/Lonworks Gateway connection is allowed)
44
Compatible Models
(1) New communication outdoor unit ¥ Conventional communication upper level controller
Outdoor unit AM7777X777777
① OnOff controller : MCM-A202D
② DMS2 : MIM-D00A
Upper level controller ③ BACnet Gateway : MIM-B17
④ Lonworks Gateway : MM-B18
⑤ S-NET mini : MST-S3W
CONTROL SYSTEMS
(2) Conventional communication outdoor unit ¥ New communication upper level controller
CENTRALIZED
Outdoor unit %7.1MVT
$"$
① OnOff Controller: MCM-A202DN
② DMS2 : MIM-D00AN
Upper level controller ③ BACnet gateway : MIM-B17N
④ Lonworks gateway : MIM-B18N
⑤ Touch centralized controller : MCM-A300N
3) Description of parts
⑧ No. Name Description
F1/F2 communication Communication connector that connects to outdoor unit /
①
connector ''
⑥
② Power connector DC 12V
Communication indicator LED
(Left LED 3 : No function
③
Middle LED 1 : Blinks during it communicates with upper
③ Communication LED
level controller
Right LED 2 : Blinks during it communicates with
② ⑤ outdoor unit and indoor unit)
④ Address setting switch Sets the address of interface module
Software update 6TJOHUIJTDPOOFDUPS
*OUFSGBDFNPEVMFTPGUXBSFDBOCF
④ ⑤
connector updated
① Displays the communication status between interface
⑥ 7-segment
module and outdoor unit/ERV
Upper level controller Communication connection channel to upper level
⑦ ⑦
communication channel controller R1/R2
SW1 Description
On : Manual address setting /
1
Off : Auto address setting
⑧ DIP switch 2 No function
3 No function
4 No function
; Note
X 8IFODPOOFDUJOHUPUIFDPOWFOUJPOBMDPNNVOJDBUJPODPOUSPMMFS
BEESFTTNVTUCFTFUNBOVBMMZ
regardless to the SW1 setting.8IFOTFUUJOHUIFBEESFTTNBOVBMMZ
NBLFTVSFUPTFUUIFBEESFTT
that is not assigned to other deivce already.
X 8IFODPOOFDUJOHUPUIFOFXDPNNVOJDBUJPODPOUSPMMFS
48NVTUCF0/UPTFU
UIFBEESFTTNBOVBMMZ
BOENBLFTVSFUPTFUUIFBEESFTTUIBUJTOPUBTTJHOFEUPPUIFS
compatible interface module or outdoor units.
45
Control Systems
4) Connection diagram
C1/C2 C1/C2
Conventional communication
R1/R2
R1/R2 R1/R2 New communication
R1/R2
New communication
Conventional communication
MIM-N01 MIM-N01
'' ''
46
5) Connection
CONTROL SYSTEMS
CENTRALIZED
Connecting to Touch centralized controller
f Conventional communication outdoor unit ¥ New communication Touch centralized controller (ACM-A300N)
Touch centralized controller
; Note
X When connecting AM7777X777777PVUEPPSVOJUBOEOFXDPNNVOJDBUJPODPOUSPMMFS
ZPVEPOhUIBWFUPDPOOFDUUIFNXJUI.*./
X 8IFODPOOFDUJOH$POWFOUJPOBMDPNNVOJDBUJPOPVUEPPSVOJUBOEDPOUSPMMFS FY.$."%
.*.#%PS.*.#&NVTUCFVTFE
47
Control Systems
6) Display
Software version is Display the set value Display the address of Outdoor unit detected Tracking completed
displayed after power of the rotary switch the interface module during tracking
is supplied 7 Displays the Main address of the communicating
indoor units alternately [Displays the indoor unit
that is set as (centralized control)]
Error display
f Communication error between outdoor unit f Communication error between upper level controller and
and the interface module the interface module after tracking has been completed
7 FF will be displayed to the indoor unit that has lost 7 When E1, E2 occurs at the same time, only E1
communication during normal communication. will be displayed.
(1) Communication error between conventional communication outdoor unit ¥ New communication upper level controller
after tracking has been completed
t It will be displayed after failing 80 times of communication trial after interface module has started tracking (approximately 3 minutes)
(2) Communication error between New communication outdoor unit ¥ Conventional communication upper level controller
after tracking has been completed
t It will be displayed after failing the tracking process over 10 minutes from the interface module has started tracking.
f When problem occurs on EEPROM f When same address was assigned to more than one
interface module (Only detected when new communication
upper level controller is connected to conventional
communication outdoor unit)
1) Features
tCommunication interface module between new communication ERV and controller
tConnect 1 ERV interface module to Max. 16 ERVs
tIndividual control – Maximum 16 ERVs
tGroup control – Maximum 16 groups
tSupported communication type
1) Conventional communication ERV ↔ New communication upper level controller
2) New communication ERV ↔ Conventional communication upper level controller
3) New communication ERV ↔ New communication upper level controller
CN4
❋ This interface module does not support connection between Conventional communication
ERV ↔ Conventional communication upper level controller
Y-GRN
RED
YEL
CONTROL SYSTEMS
CENTRALIZED
CN3 CN2
RED BLK
96.1
CN4
Y-GRN
RED
YEL
CN3 CN2
RED BLK
2) Product specification
Power Supply DC12V
Power Consumption 2.4 W
Operating Temperature range -10°C~50°C
Operating Humidity range 10%RH~90%RH
Communication RS485 x 2
Maximum Communication Length 1000M
1) New communication ERV ↔ Conventional communication upper level controller
''&37&37T
R1/R2 : 1 upper level controller
2) Conventional communication ERV ↔ New communication upper level controller
''&37&37T
Maximum number of connection 335PUBMVQUPVQQFSMFWFMDPOUSPMMFST 0OMZ%.4
#"$OFU(8-POXPSLT(8
connection is allowed)
3) New communication ERV ↔ New communication upper level controller
''&37&37T
335PUBMVQUPVQQFSMFWFMDPOUSPMMFST 0OMZ%.4
#"$OFU(8-POXPSLT(8
connection is allowed)
49
Control Systems
2) Product specification
Compatible Models
❋ 'VODUJPODPOUSPMMFSBOE4/&51MVTBSFOPUTVQQPSUFE
t/FXDPNNVOJDBUJPO&37.*./.$."%'VODUJPODPOUSPMMFS 9
50
3) Description of parts
⑧ No. Name Description
''
Communication terminal that connects to outdoor unit /
① communication
⑥ ''PG&37
connector
② Power connector DC12V
Communication indicator LED
③ (Left LED 3 : No function
Communication
③ Middle RED : Blinks during it communicates with upper
LED
⑤ level controller
②
CN4
Address setting
④ Sets the address of interface module
switch
④
CN3 CN2 Software update 6TJOHUIJTDPOOFDUPS
*OUFSGBDFNPEVMFTPGUXBSFDBOCF
① RED BLK
⑤
connector updated
CONTROL SYSTEMS
Displays the communication status between interface
⑥ 7-segment
CENTRALIZED
module and ERV
⑦
Upper level controller
⑦ communication Communication terminal to upper level controller R1/R2
channel
SW4 SW5
12 12 SW5 - No use
SW4 Description
0'' "VUPBEESFTTTFUUJOH
TXJUDINVTUCFEPXO
1
0/ .BOVBMBEESFTTTFUUJOH
TXJUDINVTUCFVQ
0'' /FXDPNNVOJDBUJPOVQQFSMFWFMDPOUSPMMFS↔
⑧ DIP switch Conventional communication ERV)
(Conventional communication upper level
2
controller ↔ New communication ERV)
ON (New communication upper level controller ↔
New communication ERV)
✽8IFOVQHSBEJOHUIFQSPHSBN
48NVTUCFTFUUP0/
status before proceeding upgrade regardless of the installation
condition.
"GUFSDPNQMFUJOHUIFEPXOMPBE
TFUUIF%*1TXJUDI
correctly according to installation condition before supplying
the power.
; Note
8IFODPOOFDUJOHUPUIFDPOWFOUJPOBMDPNNVOJDBUJPODPOUSPMMFS
BEESFTTNVTUCF
TFUNBOVBMMZSFHBSEMFTTUPUIF48TFUUJOH8IFOTFUUJOHUIFBEESFTTNBOVBMMZ
make sure to set the address that is not assigned to other deivce already.
8IFODPOOFDUJOHUPUIFOFXDPNNVOJDBUJPODPOUSPMMFS
48NVTUCF0/UPTFU
UIFBEESFTTNBOVBMMZ
BOENBLFTVSFUPTFUUIFBEESFTTUIBUJTOPUBTTJHOFEUP
other compatible interface module or outdoor units.
51
Control Systems
4) Connection diagram
C1/C2 C1/C2
Conventional
communication
R1/R2 New
communication
'' ''
52
5) Connection
CONTROL SYSTEMS
CENTRALIZED
; Note
8IFODPOOFDUJOHDPOWFOUJPOBMDPNNVOJDBUJPO&37BOE0O0GGDPOUSPMMFS .$."%
.*.#%PS.*.#&
must be used.
53
Control Systems
5) Connection
54
3. OnOff controller
MCM-A202DN
1) Features
6OJUNN
CONTROL SYSTEMS
CENTRALIZED
t.BYJNVNHSPVQDPOUSPMMFS .BYVOJUT
t8IPMF(SPVQ*OEJWJEVBMJOEPPSVOJUDPOUSPM 0O0GG
t3FTUSJDUJPOPOUIFVTFPGXJSFMFTTXJSFESFNPUFDPOUSPMMFSTBOEFYUFSOBMDPOUBDUDPOUSPM
t$PPMJOHBOEIFBUJOHNPEFDPOUSPM
t*OEPPSVOJUFSSPSEJTQMBZ
2) Product specification
Power supply "$7_7
)[
Power consumption 8
Operating Temperature range °$_°C
Operating Humidity range 3)_3)
Communication 34Y 33
%FWJDF /VNCFS
*OEPPSVOJUT JODMVEJOH&37
.$6
.BYJNVNJOEPPSVOJUT
&37TBOE.$6T
0O0GGDPOUSPMMFS
Control layer XIFO%.4
#"$OFUHBUFXBZ
5PVDIDFOUSBMJ[FE
-PO8PSLTHBUFXBZJTDPOOFDUFE
DPOUSPMMFS
%.4
#"$OFU(8 5PUBM
-PO8PSLT(8
Compatible product
0VUEPPSVOJU AM7777X777777
0O0GGDPOUSPMMFS .$."%/
5PVDIDFOUSBMJ[FEDPOUSPMMFS .$."/
$POUSPMMFS %.4 .*.%"/
#"$OFU(8 .*.#/
-POXPSLT(8 .*.#/
7 Conventional communication outdoor unit requires interface module (MIM-N01) to establish connection
7 MIM-B13D, MIM-B13E, MIM-B04A Interface modules cannot be connected.
7 To connect ERV, MIM-N10 interface module is required. 55
Control Systems
3) Description of parts
①
⑥
②
③
⑥
COOL
AUTO
HEAT
④
⑧
; Note
Press button 11 and button 15 together for 5 seconds to reset the OnOff controller.
Software reset
56
Address & option switch
SW02 DIP SW Description
K1 K2 Restriction setting on wired/wireless remote control use
SW01
Cool
0'' 0'' Wired/Wireless remote control use is allowed all the time. Level 0
Auto
Option switch
Heat Wired/Wireless remote control use is allowed only if indoor unit is ON
by the OnOff controller.
ON 0''
8IFOJOEPPSVOJUTBSF0''CZUIF0O0GGDPOUSPMMFS
SFNPUFDPOUSPMVTF
is prohibited. Level 1
Indoor unit RMC(1) The use of wireless/wired remote controllers and external contact
0'' ON
matching address control is prohibited. Level 2
CONTROL SYSTEMS
ON ON No function
CENTRALIZED
0''0O0GGDPOUSPMMFSVTF
K3
ON : Not use Onoff controller "MMCVUUPOTEPOhUXPSL
K4 No function
4) Optional function
f LEVEL 0
t ‘Allowed’ remote controller
f LEVEL 1
t Turned on by OnOff controller
– ‘Allowed’
t Turned off by OnOff controller
– ‘Prohibited’
f LEVEL 2
t ‘Prohibited’ remote controller
57
Control Systems
4) Optional function
Ú0QFSBUJPONPEFTFMFDUJPOTXJUDIEPFTOhUMPDLUIFJOEPPSVOJUPQFSBUJPONPEF
5) Connection diagram
Set layer
F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2
Set layer
F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2
58
Control layer connection (R1/R2)
t.BY$POUSPMMFSTDBOCFDPOOFDUFEUPTBNFDPNNVOJDBUJPOMJOF *ODBTFPG%.4#"$OFUHBUFXBZ-PO8PSLTHBUFXBZDPOOFDUJPO
.BY
t.BYPVUEPPSVOJUTDBOCFDPOOFDUFEUPTBNFDPNNVOJDBUJPOMJOF *ODMVEFTJOUFSGBDFNPEVMF.*./
7Connectable controller : - Touch centralized controller (MCM-A300N).
- OnOff controller (MCM-A202DN).
%.4 .*.%"/
#"$OFUHBUFXBZ .*.#/
-PO8PLTHBUFXBZ .*.#/
0OMZPOFPGUIFUISFFNPEFMT
F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2
CONTROL SYSTEMS
CENTRALIZED
F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2
Control layer
f Case1
F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2
F1 F2 R1 R2
Control layer
59
Control Systems
5) Connection diagram
F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2
F1 F2 R1 R2
Control layer
f Caution
t 8IFO0O0GGDPOUSPMMFSJTDPOOFDUFEUP0VUEPPSVOJUhT''MJOF
ZPVDBOOPUDPOOFDU%.4UP0O0GGDPOUSPMMFShT33MJOF
Set layer
F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2
60
6) Display
CONTROL SYSTEMS
CENTRALIZED
Main : 0 Main : 1 Main : 2
RMC(1) : 1 RMC(1) : 1 RMC(1) : 1
RMC(2) : 3 RMC(2) : 4 RMC(2) : 5
R1/R2
(1) OnOff controller only communicate with indoor units which has same RMC(1) address with OnOff
controller's address.
(2) During tracking indoor units, LED whose number is equivalent to indoor unit RMC(2) address flickers.
tIn LED 00 LED 01 LED 02 LED 03 LED 04 LED 05 order
61
Control Systems
1) Features
Unit : mm
203
161
tJODIUPVDI-$%DPOUSPMMFS
t$POUSPMTNBYJNVNJOEPPSVOJUT
38
t$POUSPMTNBYJNVN[POFT
t4DIFEVMFDPOUSPM
*OEPPSVOJUVTBHFSFTUSJDUJPO
View indoor unit error history
2) Product specification
Power supply "$7_7
)[
Power consumption 110W
Operating temperature range 0°C~40°C
Operating humidity range 30%RH~90%RH
Communication 34Y ''PS33
Device Number
*OEPPSVOJUT JODMVEJOH&37
.$6
.BYJNVNJOEPPSVOJUT
&37TBOE.$6T
62
Compatible product
Outdoor unit AM7777X777777
OnOff controller (MCM-A202DN)
Touch centralized controller (MCM-A300N)
Controller DMS2 (MIM-D00AN)
BACnet gateway (MIM-B17N)
Lonworks gateway (MIM-B18N)
7 Conventional communication outdoor unit requires interface module (MIM-N01) to establish connection
7 MIM-B13D, MIM-B13E, MIM-B04A Interface modules cannot be connected.
7 To connect ERV, MIM-N10 interface module is required.
3) Description of parts
CONTROL SYSTEMS
CENTRALIZED
②
①
⑧ ③
⑦ ④
⑥ ⑤
⑤ DI-1 terminal Terminal block for connecting digital input signal from 3rd party device.
⑥ DI-2 terminal Terminal block for connecting digital input signal from 3rd party device.
63
Control Systems
4) Connection diagram
S-NET 3
TCP/IP
Control layer
Touch centralized
OnOff controller OnOff controller controller
DMS2
RS485
Touch centralized
controller
Outdoor unit
Maximum 128
indoor units
(DVM series)
Set layer
64
5) Connection
Set layer connection (F1/F2)
t8IFO5PVDIDFOUSBMJ[FEDPOUSPMMFSPOMZDPOUSPMTJOEPPSVOJUTPGPVUEPPSVOJU
UIFOJUDBOCFDPOOFDUFEUP''MJOFPGPVUEPPSVOJUPSJOEPPSVOJU
tMax. 16 Controllers can be connected to same communication line.
7Connectable controller: - OnOff controller (MCM-A202DN)
- Touch centralized controller (MCM-A300N)
Set layer
F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2
CONTROL SYSTEMS
Set layer
CENTRALIZED
F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2
t.BYPVUEPPSVOJUTDBOCFDPOOFDUFEUPTBNFDPNNVOJDBUJPOMJOF *ODMVEFTJOUFSGBDFNPEVMF.*./
7Connectable controller : - Touch centralized controller (MCM-A300N).
- OnOff controller (MCM-A202DN).
%.4 .*.%"/
#"$OFUHBUFXBZ .*.#/
-PO8PLTHBUFXBZ .*.#/
0OMZPOFPGUIFUISFFNPEFMT
F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2
F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2
Control layer
65
Control Systems
5) Connection
f Case1
F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2
F1 F2 R1 R2
Ex.) DMS2(MIM-D00AN)
Control layer
f Case2
F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2
F1 F2 R1 R2
Ex.) DMS2(MIM-D00AN)
Control layer
66
f Caution
t 8IFO5PVDIDFOUSBMJ[FEDPOUSPMMFSJTDPOOFDUFEUP0VUEPPSVOJUhT''MJOF
%.4
#"$OFU(8
LonWorks GW cannot be connected to same communication line.
Set layer
F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2
CONTROL SYSTEMS
6) Main function
CENTRALIZED
Z one control
6) Main function
Schedule control
CONTROL SYSTEMS
CENTRALIZED
t It can set the lower temperature limit in Cool mode and the upper temperature limit in Heat mode.
t This setting can be changed by other touch centralized controller and DMS2.
t 5PQSFWFOUUIFXSPOHPQFSBUJPONPEFTFUUJOH
JUDBOMJNJUUIFPQFSBUJPONPEFPGJOEPPSVOJU
- $PPMPOMZ)FBU
"VUP )FBU
PQFSBUJPONPEFJTSFTUSJDUFE
)FBUPOMZ$PPM
%SZ
"VUP $PPM
PQFSBUJPONPEFJTSFTUSJDUFE
t This setting can be changed by other touch centralized controller and DMS2.
69
Control Systems
6) Main function
L ock function
t You can lock the functions of Touch centralized controller.
t You can set the access lock of each item of operating panel.
The locked item will be deactivated.
CONTROL SYSTEMS
CENTRALIZED
t You can set the controller restriction.
t You can set the type of controller which will be restricted when "Disable RC" is applied from operating panel.
[Settings] ¤ [Device settings] ¤ [Control level]
t You can set the type of controller which will be restricted when "Disable RC" is applied from operating panel.
3FNPUFDPOUSPMMFS3FTUSJDUXJSFEXJSFMFTTSFNPUFDPOUSPMMFSVTBHF
0O0GGDPOUSPMMFSVTBHFJTQPTTJCMF
- OnOff controller : Restricts wired/wireless remote controller and OnOff controller usage
71
Control Systems
6) Main function
Tracking
t Detects all the indoor and outdoor units that are connected to communication line of Touch centralized controller
t 8IFONVMUJQMFOVNCFSPG5PVDIDFOUSBMJ[FEDPOUSPMMFSJTDPOOFDUFEUPHFUIFS
ZPVDBOVTFDIFDLCPYPG4) 4IPX)JEF
UPTFMFDU
indoor units that will be controlled from each Touch centralized controller.
t *OEPPSVOJUXJUIOPDIFDLNBSLPO4) 4IPX)JEF
DIFDLCPY
XJMMOPUCFDPOUSPMMFEBOENPOJUPSFEGSPNUIF5PVDIDFOUSBMJ[FEDPOUSPMMFS
72
5. Operation mode selection switch
MCM-C200
1) Features
CONTROL SYSTEMS
CENTRALIZED
Operation mode selection switch
t0VUEPPSVOJUPQFSBUJPONPEFTFMFDUJPO $PPMJOH
)FBUJOHPS"VUP
(Unit : mm)
70 21
120
2) Installation
tPQFSBUJPONPEFTFMFDUJPOTXJUDINVTUCFDPOOFDUFEUPPVUEPPSVOJU
Ú Max. distance between the outdoor unit PCB and the MCM-200: 100m
73
Control Systems
3) Control example
Initial condition C
; Note
Operation mode selection switch fixed indoor unit operation mode.
Indoor unit ignores opposite operation mode. (It will not accept the command and it will just beep shortly)
74
III. Integrated management systems
1 DMS2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
2 S-NET3. . . . . . . . . . . . . . . . . . . . . . . . . . . 111
MANAGEMENT SYSTEMS
INTEGRATED
75
Control Systems
1) Features
t#VJMUJOXFCTFSWFSGPS1$JOEFQFOEFOUNBOBHFNFOUBOESFNPUFBDDFTTDPOUSPM
t.VMUJQMFVQQFSMBZFSDPOUSPMBDDFTT 4/&5
8FCDMJFOU
t8FFLMZ%BJMZTDIFEVMFDPOUSPM
t1PXFSEJTUSJCVUJPOGVODUJPO
t$VSSFOUUJNFNBOBHFNFOUFWFOEVSJOHQPXFSGBJMVSF GPSIPVST
t&NFSHFODZTUPQGVODUJPOXJUITJNQMFDPOUBDUJOUFSGBDF
t*OEJWJEVBM(SPVQDPOUSPMPGVQUPJOEPPSVOJUTBOE&37
")6
t6TFSFEJUBCMFDPOUSPMMPHJD
t"DDFTTJCMFMFWFMNBOBHFNFOU
t%ZOBNJDTFDVSJUZNBOBHFNFOU
t0QFSBUJPOFSSPSIJTUPSZNBOBHFNFOU
t%BUBTUPSBHFJOOPOWPMBUJMFNFNPSZ4%NFNPSZ
6OJUNN
2) Product specification
Source %$"EBQUPS
Power Input _7"$
)[
Output 7"
Operating temperature
℃_℃
range
Operating humidity range 3)_3)
t-PXFSMFWFM34Y
Communication method
t6QQFSMFWFM&UIFSOFU#BTF5Y
External Digital Output 10
connection
port Digital Input 10
RS485 N
Maximum Digital Output N
length of
connection Digital Input N
number of layer
0O0GGDPOUSPMMFS
device 5PUBM 5PUBM
5PVDIDFOUSBMJ[FEDPOUSPMMFS
1*.JOUFSGBDFNPEVMF .*.#
.*.#/
76
Compatible product
0VUEPPSVOJU ".77779777777
0O0GGDPOUSPMMFS .$."%/
$POUSPMMFS 5PVDIDFOUSBMJ[FEDPOUSPMMFS .$."/
1*.JOUFSGBDFNPEVMF .*.#
.*.#/
7 Conventional communication outdoor unit requires interface module(MIM-N01).
7 MIM-B13D, MIM-B13E, MIM-B04A Interface modules cannot be connected.
7 To connect ERV, MIM-N10 interface module is required.
7 PIM connection is different depending on software version.
- Before 2.6.0.3 : MIM-B16 only
- 2.6.0.3 : MIM-B16N only
- After 2.6.1.7 : MIM-B16, MIM-B16N
3) Description of parts
Front
No Name Function
4IPXTDVSSFOUUJNFBOE*1BEESFTT
① LCD display 7BSJPVTNFTTBHFTXJMMCFEJTQMBZFE
① EFQFOEJOHPOCVUUPOJOQVU
5IFSFBSFCVUUPOT .FOV
② T %PXO
S 6Q
4FU
BOEZPVDBO
MANAGEMENT SYSTEMS
② LCD operation button
BDDFTTUPNFOVBOENPWF
DIFDL
UIFNFOV
INTEGRATED
$IFDL-&%TUBUVTTVDIBT1PXFS
③ LED Indicator $16"MJWF
&UIFSOFU-JOLFE"DUJWF
$0._5939BOE$IFDL
③ 6OGBTUFOTDSFXTPOUIFCPUUPN
BOETFQBSBUFUIFCPUUPNDPWFSGSPN
④ DMS2 Bottom cover
④ %.4
5IFODIFDLDBCMFDPOOFDUJPOQBSU
LED indicator
77
Control Systems
3) Description of parts
Bottom
DI Terminal2 DO Terminal1
$POOFDU%JHJUBM*OQVU $POOFDU%JHJUBM0VUQVU
$IBOOFM_$IBOOFM $IBOOFM_$IBOOFM
DI Terminal1 DO Terminal 2
$POOFDU%JHJUBM*OQVU $POOFDU%JHJUBM0VUQVU
$IBOOFM_$IBOOFM $IBOOFM_$IBOOFM
4VCNFNPSZJTGPS%.4QSPHSBNVQEBUFBOETFUJOGPSNBUJPOTBWJOH
Ú1VSDIBTF4%DBSETFQBSBUFMZ
DMS2 IP
Current time
"DDFTTNFOVBOETFMFDUNBJONFOV
$BODFMNFOVTFUUJOH
.PWFCFUXFFONFOV
$IBOHFUIFNFOVTFUUJOHT
.PWFCFUXFFONFOV
$IBOHFUIFNFOVTFUUJOHT
"DDFTTTVCNFOV
4BWFUIFDIBOHFPGNFOVTFUUJOHT
78
4) Connection diagram
f MIM-B16(PIM) should be connected separately with outdoor unit or controllers.
f MIM-B16N(PIM) can be connected with outdoor units or controllers to same channel of DMS2.
'PSQPXFSEJTUSJCVUJPO
1*. 0O0GG
%.4
DPOUSPMMFS
1PXFSMJOF
33
''
33
''
MANAGEMENT SYSTEMS
8BUUIPVSNFUFS
&MFDUSJDBM
TVCTUBUJPO
INTEGRATED
33 ''
5) Wiring
$)$IBOOFM
F1 F2 R1 R2
F1 F2 R1 R2
; Note
%.4DBODPOOFDUPVUEPPSVOJUBOE0O0GGDPOUSPMMFS5PVDIDFOUSBMJ[FEDPOUSPMMFSBUUIFTBNFUJNF
0VUEPPSVOJUBOE0O0GGDPOUSPMMFS5PVDIDFOUSBMJ[FEDPOUSPMMFSDBOCFDPOOFDUFEUPDPNNVOJDBUJPODIBOOFMBUUIFTBNFUJNF
79
Control Systems
5) Wiring
DMS2
F1 F2
R1 R2
Outdoor unit
R1R2
R1R2
0 0 Outdoor unit
Outdoor unit
R1R2
R1R2
1 1 Outdoor unit
Maximum 16 Outdoor unit
connections
F F
Outdoor unit
Outdoor unit Ú0VUEPPSVOJUhTBEESFTTJTEFGJOFEBVUPNBUJDBMMZ
5IFBEESFTTDBOCFDIBOHFENBOVBMMZBMTP
DMS2
ex) OnOff controller
Maximum 15
OnOff controllers
Outdoor unit
R1R2
Outdoor unit
R1R2
Outdoor unit
80
Connecting with outdoor unit and OnOff controller / Touch centralized controller
DMS2
R1R2 ex) OnOff controller
Maximum 16
outdoor units
1
Outdoor unit
R1R2
MANAGEMENT SYSTEMS
Outdoor unit
INTEGRATED
R1R2
3
Outdoor unit
Wiring distance
ⓐ ⓑ ⓒ
ⓓ
/FUXPSLSBEJVT
ⓔ
f Distance between DMS2 and OnOff controller / Touch centralized controller /outdoor unit
t%JTUBODFGSPNUIF%.4UPUIFGVSUIFTUEFWJDFDBOOPUFYDFFEN
tⓒ + ⓓ + ⓔ d 1000m
ⓐ, ⓑ, ⓒ, ⓓ, ⓔ = 100m
ⓐ ⓑ ⓒ ⓓ ⓔ
)6#
3FQFBUFS
.BYJNVNOVNCFSPGSFQFBUFST
ⓐN 81
Control Systems
6) Function
Tracking
f 5SBDLJOHJTBOPQFSBUJPOUIBUGJOETEFWJDFTXIJDIBSFDPOOFDUFEUP%.4
5ISPVHIUSBDLJOHPQFSBUJPO
EFWJDFTXIJDIBSFDPOOFDUFEUP%.4DBOSFDPHOJ[FJGUIFZBSFDPOOFDUJOHUP%.4
5PTVQFSWJTFBOEDPOUSPMTZTUFNBJSDPOEJUJPOFSVTJOH%.4
USBDLJOHTIPVMECFEPOFGJSTU
t8IFOPVUEPPSVOJUPSDPOUSPMMFSJTDPOOFDUFEUPDIBOOFM
TFUBTi/&8w
t8IFO1*. .*.#/
JTDPOOFDUFEUPDIBOOFM
TFUBTi*.w
t1*.TIPVMECFDPOOFDUFETFQBSBUFMZXJUIPVUEPPSVOJUPSDPOUSPMMFST
f :PVDBODIFDLUIFOVNCFSPGJOTUBMMFEEFWJDFT
BEESFTTPGUIFEFWJDFTPSSFOBNFUIFJOEPPSVOJU
BGUFSUSBDLJOHJTDPNQMFUFE
*OEPPSVOJUOBNF
6TFSDBONPEJGZJU
*OEPPSVOJUBEESFTT
DMS2
0VUEPPSVOJUBEESFTT
$IBOOFMOVNCFS
%FWJDFUZQF
PVUEPPSVOJU
*OEPPSVOJU
82
Control & monitoring
f %.4DBODPOUSPMBOENPOJUPS.BYEFWJDFT *OEPPSVOJU
&37
")6
MANAGEMENT SYSTEMS
INTEGRATED
Monitoring Control
*OEPPSVOJU
&37
")6 7BSJBCMFXFCSFNPUFDPOUSPMMFST
&YUFSOBMDPOUBDUQPJOU EFQFOETPOEFWJDFUZQF
t$POUSPMBOE.POJUPSJOH4FMFDUUIJTJGZPVXBOUUPDPOUSPMTJMFOUMZJOh$POUSPMBOE.POJUPSJOHhTDSFFOPG%.4
t4DIFEVMF4FMFDUUIJTJGZPVXBOUUPQFSGPSNh4DIFEVMFhTJMFOUMZ
t$POUSPMMPHJD4FMFDUUIJTJGZPVXBOUUPQFSGPSNh$POUSPMMPHJDhTJMFOUMZ
83
Control Systems
6) Function
t4FMFDUUIJTJGZPVXBOUUPSFTUSJDUDPOUSPMMJOHGSPN0O0GGDPOUSPMMFSBOE5PVDIDFOUSBMJ[FEDPOUSPMMFSXIFOZPVEJTBCMF3$GSPNUIF%.4
(1) Pattern 2
/PGVODUJPO
Patter 2
&YUFSOBMDPOUBDU -FWFMUSJHHFSFE
f Short external contact : Emergency stop f Open external contact : Resume operation
t5VSOTPGGBMMUIFJOEPPSVOJUTXIFOUIFSFJTBO0/ t"GUFS&NFSHFODZTUPQ
UIFJOEPPSVOJUTTUBZJOUIFDVSSFOU
TJHOBMJOQVU 0''TUBUFT
t"MMUIFSFNPUFDPOUSPMVTFJTEJTBCMFE t"MMUIFSFNPUFDPOUSPMVTFJTSFTUPSFEUPUIFQSFWJPVTTUBUF
t$POUSPMGSPN4/&5JTVOBWBJMBCMF t4DIFEVMFDPOUSPMJTFOBCMFEBHBJO
t%JTBCMFTDIFEVMFDPOUSPM
(2) Pattern 3
&YUFSOBMDPOUBDU -FWFMUSJHHFSFE
Pattern 3
&YUFSOBMDPOUBDU -FWFMUSJHHFSFE
&YUFSOBMDPOUBDU 1VMTFUSJHHFSFE
Pattern 4 %VSBUJPO_TFD
&YUFSOBMDPOUBDU 1VMTFUSJHHFSFE
%VSBUJPO_TFD
f External contact pulse input to DI-1 f External contact pulse input to DI-2
t4IPSUQVMTFUSJHHFSFE4UBSUTBMMJOEPPSVOJUPQFSBUJPO t4IPSUQVMTFUSJHHFSFE4UPQTBMMJOEPPSVOJUPQFSBUJPO
84 Ú4DIFEVMFDPOUSPMJTOPUJOUFSSVQUFEJO1BUUFSO
General external contact point control
%.4IBT%JHJUBMJOQVUPVUQVUQPSUTUPDIFDLUIFFYUFSOBMEFWJDFTUBUVTPSUVSOUIFN0O0GGUISPVHIDPOUBDUQPJOU
%JHJUBMJOQVU %JHJUBM0VUQVU
; Note
%*
%0
XJMMCFFYDMVEFEGSPNDPOUSPMBOENPOJUPSJOHTJODFJUJTCFJOHVTFECZJOUFSOBMGVODUJPOPG%.4
MANAGEMENT SYSTEMS
INTEGRATED
Indoor unit usage restriction
t0QFSBUJPOMJNJU5PQSFWFOUUIFXSPOHPQFSBUJPONPEFTFUUJOH
JUDBOMJNJUUIFPQFSBUJPONPEFPGJOEPPSVOJU
t5FNQFSBUVSFMJNJU*UDBOTFUUIFMPXFSUFNQFSBUVSFMJNJUJO$PPMNPEFBOEUIFVQQFSUFNQFSBUVSFMJNJUJO)FBUNPEF
❹ 4FUUJOH6QQFSUFNQFSBUVSFMJNJUJO)FBUJOH
❸ $POUSPMNPEF
-PXFSUFNQFSBUVSFMJNJUJO$PPMJOH
❷ 0QFSBUJPONPEF
❶ *OEPPSVOJUBEESFTT SFTUSJDUJPO
0VUEPPSVOJU
❶ Check the indoor unit address.
7JSUVBM0O0GGDPOUSPMMFS *OEPPSVOJUNBJOBEESFTT
_%FQFOETPODIBOOFMOVNCFS
*OEPPSVOJUHSPVQBEESFTT 3.$
❸ Control mode will be set automatically depends on the seleceted restricted mode
t&Y
8IFOUIFSFTUSJDUFENPEFJTTFUUP<$PPMPOMZ>BOEUIFO<$POUSPMNPEF>JTTFUUP<$PPM>BVUPNBUJDBMMZ
*GVTFSTFU<)FBUJOHNPEF>VTJOHSFNPUFDPOUSPMMFS*OEPPSVOJUJHOPSFTUIFDPNNBOE
❹ Set the Upper temperature limit in Heating and Lower temperature limit in Cooling.
t6QQFSUFNQFSBUVSFMJNJUJO)FBUJOHBOE-PXFSUFNQFSBUVSFMJNJUJO$PPMJOHDBOCFTFUEJGGFSFOUMZGPSFBDIJOEPPSVOJU
$PPMJOH$_$
)FBUJOH$_$
85
Control Systems
6) Function
Logic control
What is logic control?
6TFSDBODPOUSPMUIFBJSDPOEJUJPOFS
&37
")6BOEEJHJUBMPVUQVUEFQFOEJOHPOUIFDPOEJUJPOT
TVDIBTSPPNUFNQFSBUVSFBOE
PVUEPPSUFNQFSBUVSF
TFUCZUIFVTFS*OQVUDPOEJUJPODBOCFVTFEXJUIQBSBNFUFSBOEJUXJMMCFDBMDVMBUFEXJUIBSJUINFUJDFRVBUJPO
4DIFEVMFGVODUJPOFYFDVUFTPQFSBUJPOCZUJNFCVUMPHJDDPOUSPMFYFDVUFTPQFSBUJPOBDDPSEJOHUPUIFDPOEJUJPOTUIBUTFUCZUIFVTFS
Input Output
4FMFDUUIFGBDUPSUPJOQVUDPOEJUJPO
%FWJDF
GBDUPS
4FMFDUPVUQVUGBDUPS
&EJUUIFDPOEJUJPO %FWJDF
GBDUPS
$PNQPVOEGBDUPS
$PNQBSJTPOPQFSBUPS
4UBOEBSEWBMVF
¨ &EJUPVUQVU
$SFBUFDPOUSPM
%VSBUJPO
④
②
③
⑤
⑧
⑦ ⑨
①
MANAGEMENT SYSTEMS
① Click “Select a factor”. ¨ ② Select type of the factor ¨ ③ Click “Select a device”
INTEGRATED
ª
⑥ Click “Apply”. § ⑤ Select a detail item § ④ Select the device from the list.
ª
⑦ Select the comparison operator ¨ ⑧ Select a standard value ¨ ⑨ Select the duration
f Function : Use average value of various conditions from the device and create it as a factor.
87
Control Systems
6) Function
Logic control
(1) Editing input factor
0OMZA4JOHMFXJMMCFMJTUFE
②
④
i$VSSFOUUFNQwBOEi0VUEPPSUFNQw
DBOOPUCFTFMFDUFE ⑤
① ⑥
⑦
① Click “Select a factor”. ¨ ② Click “Select a device”. ¨ ③ Select the device from the list.
ª
⑥ Select “Command”. § ⑤ Click “Apply”. § ④ Select a detail item to control.
ª
⑦ Click “Save”.
88
(3) Control example – Setting
Ex) Set the ERV to turn off together when the indoor unit turns off
❶$MJDL<$POUSPMMPHJDNBOBHFNFOU><4FUUJOHDPOUSPMMPHJD>GSPN%.4NFOV$MJDL<3FHJTUFS>UPDSFBUFOFXDPOUSPMMPHJD
❷ &OUFS/BNF QFSJPEEBZBOEUJNFGPSOFXDPOUSPMMPHJD
MANAGEMENT SYSTEMS
INTEGRATED
❸ Create input condition : Click [Select a factor] from the ‘Input’ window.
89
Control Systems
6) Function
Logic control
(3) Control example – Setting
❹ Click [Select a device], then [Device selection] window will pop up.
Select a indoor unit to apply the new control logic.
❺ Create input condition : When the device is selected, click [Power] and click [Apply].
Ú<1PXFS>NFBOTUIFPQFSBUJPOTUBUF 0O0GG
❻ Create input condition :Select ‘=’ as a comparison operator and select “Off” as a standard value.
t.FBOJOH&YFDVUFPVUQVUDPOUSPMXIFOEFWJDFJTPGG
90
❼ Create output : From the output window, select the device to apply the control when input condition is satisfied.
Click [Apply] when selection is completed.
❽ Create output : Select “Power” as a factor of the selected device and click [Apply].
MANAGEMENT SYSTEMS
INTEGRATED
❾ Create output : From the output window, select the control to be executed when input condition is satisfied.
t5VSOPGGUIF&37OP
To apply the new logic control, select the created logic and click [Apply].
91
Control Systems
6) Function
Logic control
(4) Control example – Control logic
Ex) Control logic 1 : Turn on 4 indoor units when outdoor temperature is 30°C or higher.
Control logic 2 : Turn off 4 indoor units when outdoor temperature is 26°C.
Control logic 1
Control logic 2
➊$MJDL
➋$MJDL
MANAGEMENT SYSTEMS
INTEGRATED
Control logic applied
"QQMJDBUJPODPNQMFUFE
93
Control Systems
6) Function
Power distribution
t8IFSFEPFTQPXFSDPOTVNQUJPOPDDVST
"JSDPOEJUJPOJOHTZTUFN
0VUEPPSVOJUGBO
*%6*OEPPSVOJU
5ISPVHI1*.
*%6" *%6#
.FBTVSFEQPXFS
DPOTVNQUJPO
*%6$
Operation information
1. Outdoor/Indoor unit
operation
2. Indoor unit fan operation
3. Stand-by operation *%6%
Power distribution result
5ISPVHI0O0GGDPOUSPMMFST
BOEJOUFSGBDFNPEVMFT
%FNBOEDBQBDJUZPG*%6"
*%6"TFMFDUSJDQPXFS 5PUBMQPXFS Y
DPOTVNQUJPO DPOTVNQUJPO 5PUBMEFNBOEDBQBDJUZPGBMM*%6T
; Note
%FNBOEDBQBDJUZNFBOTUIFWBMVFUIBUQBSBNFUFSTPGEJGGFSFOUVOJUTMJLFSFRVJSFEQPXFSBOESFGSJHFSBOUBNPVOUBSF
USBOTGPSNFEJOUPBTBDPNNPOOVNCFSUPNBLFFBTZBMHFCSBJDDBMDVMBUJPO
94
(2) Main capacity
5IJTJTEFUFSNJOFEEZOBNJDBMMZXJUIUIFDPNCJOBUJPOPGWBSJPVTSFGSJHFSBUJOHQBSBNFUFSTTVDIBTEJGGFSFODFCFUXFFOSPPNBOETFU
UFNQFSBUVSFPSFWBQPSBUPSJOQVUPVUQVUUFNQFSBUVSF
5IFTFQBSBNFUFST
BTBSFTVMU
EFUFSNJOFUIFSFGSJHFSBOUBNPVOUGMPXJOHJOUPUIFJOEPPSVOJUCZDPOUSPMMJOH&&7TUFQT
(5) What if the room temperature begins to reach the set temperature?
*GUIFSPPNUFNQFSBUVSFCFHJOTUPSFBDIUIFTFUUFNQFSBUVSF
UIFJOEPPSVOJUEPFTOPUIBWFUPFYUSBDUUIFGVMMSFGSJHFSBOUBNPVOUUP
LFFQUIFTFUDPOEJUJPO$BQBDJUZGSPNUIFJOEPPSVOJUHPFTEPXOUPJOEJDBUFUIFPVUEPPSVOJUUIBUJUEPFTOPUOFFESFGSJHFSBOUBUUIF
GVMMDBQBDJUZTUBUF
MANAGEMENT SYSTEMS
8IFOUIFSPPNUFNQFSBUVSFIBTSFBDIFEUIFTFUUFNQFSBUVSF
UIFSFJTOPOFFEUPQVNQUIFSFGSJHFSBOUJOUPUIFJOEPPSVOJU*OEPPSVOJU
INTEGRATED
HPFTJOUPUIFUIFSNBMMZ0''TUBUFBOETFOETDBQBDJUZPG[FSPWBMVFUPUIFPVUEPPSVOJUBOEUIF%.4
XIJDISFTVMUTJOGBOPSTUBOECZ
QPXFSEJTUSJCVUJPOPOMZ
%VSJOHIPVST
$BMDVMBUFTDPOTVNFEQPXFSGPSEBZ
3FBETFWFSZJOEPPSVOJUPQFSBUJPO $BMDVMBUFTBDDVNVMBUFEDBQBDJUZWBMVFT
3FBETXBUUIPVSNFUFSWBMVF %JTUSJCVUFTEBZQPXFSDPOTVNQUJPO
"DDVNVMBUFTDBQBDJUZWBMVFT $MFBSTBDDVNVMBUFEDBQBDJUZWBMVFT
(8) Not equal stand-by power distribution (In case all the indoor units are stopped)
4JODFUIFSFBMXBZTFYJTUTFSSPSJOFBDIQPXFSDPOTVNQUJPOBNPVOU
EJTUSJCVUFETUBOECZQPXFSNBZOPUCFFRVBMGPSEJGGFSFOU
BJSDPOEJUJPOJOHTZTUFN#VUUIFEJGGFSFODFJTTPTNBMMUIBUJUJTOFHMJHJCMF
#$
%&
" # $
% & #z%
95
Control Systems
6) Function
Power distribution
%.4
1*.
1PXFSTVQQMZ
33 (
(
(
1PXFSTVQQMZ
G1
f When configuring the DMS2 and the whole system, mapping of watt-hour meters for indoor/outdoor units must be precisely
assigned for correct power distribution.
4VQQPTFDBQBDJUZWBMVFTBDDVNVMBUFEBUEVSJOHPOFXIPMFEBZJTBTGPMMPXT
4USPOH
DPPMJOH 8FFLDPPMJOH 'BONPEF 4UPQ
L8IDPOTVNFE
PVUEPPSJOEPPS
MANAGEMENT SYSTEMS
INTEGRATED
*OEPPSVOJUDBQBDJUZ Y
1EPG*OEPPSVOJU" Y5PUBML8I L8I
5PUBMDBQBDJUZ
Y
1EPG*OEPPSVOJU# L8I
Y
1EPG*OEPPSVOJU$ L8I
Y
1EPG*OEPPSVOJU% L8I
97
Control Systems
6) Function
Power distribution
%.4
1*.
1PXFSTVQQMZ
33
(
(
(
1PXFSTVQQMZ
G1
t8BUUIPVSNFUFS#JTNBQQFEUPUIFPVUEPPSVOJUJO(
t8BUUIPVSNFUFS$JTNBQQFEUPUIFPVUEPPSVOJUTJO(BOE(
t8BUUIPVSNFUFS%JTNBQQFEUPUIFJOEPPSVOJUTJO((
t8BUUIPVSNFUFS&JTNBQQFEUPUIFJOEPPSVOJUTJO(
Ú*OTUBMMBUJPOBCPWFJTBMMPXFEXJUIQSPQFSNBQQJOHDPOGJHVSBUJPO
; Note
8BUUIPVSNFUFSDBOCFTIBSFEUPUIFNVMUJQMFJOEPPSPVUEPPSTZTUFNT
98
Installation example (Not allowed)
%.4
1*.
1PXFSTVQQMZ
(
33
MANAGEMENT SYSTEMS
INTEGRATED
(
(
1PXFSTVQQMZ
G1
All indoor units in one outdoor unit must have the same power source.
t*OTUBMMBUJPOBCPWFDBOOPUCFBWBJMBCMFGPSUIFSFBTPOUIBUPOFJOEPPSVOJUJO(IBTEJGGFSFOUQPXFSTPVSDFGSPNUIFPUIFSJOEPPSVOJUT
*OUIJTDBTF
GSBDUJPOBMQPXFSPG%DPOTVNFECZUIFTFQBSBUFQPXFSFEJOEPPSVOJUJO(JTEJTUSJCVUFEUPUIFJOEPPSVOJUTJO(BOE(
99
Control Systems
6) Function
Power distribution
(10) Setting the inspection section
*GZPVXBOUUPDIFDLUIFEJTUSJCVUJPOSFTVMUCZUJNFQFSJPE
TFUUIFUJNFTFDUJPO
:PVNVTUVTF4/&5UPDIFDLUIFEJTUSJCVUJPOSFTVMUCZUJNFQFSJPE
*OEPPSVOJUTNVTUCFDIFDLFEXIJDIXBUUIPVSNFUFSJUJTDPOOFDUFEUPBOEUIFO1*.DIBOOFMPGUIFDPSSFTQPOEJOHXBUUIPVS
NFUFSNVTUCFTFUBDDPSEJOHUPJOEPPSVOJU1*.DIBOOFMBTTIPXOCFMPX
100
Example of watt hour meter installation ❶ Installing watt-hour meter to outdoor/ indoor unit
.BJODJSDVJUCSFBLFS
1*.
8BUUIPVSNFUFS" $)
8BUUIPVSNFUFS# $)
Address 0 8BUUIPVSNFUFS$ $)
8BUUIPVSNFUFS% $)
A/ B
R1/R2
A B C D
1 phase power
0 1 2
MANAGEMENT SYSTEMS
F1/F2
INTEGRATED
1JQF
DPOOFDUJPO
R1/R2
0 1 2
F1/F2
1JQF
DPOOFDUJPO
3 phase power
Ú$POOFDUBQQSPQSJBUFXBUUIPVSNFUFSUPPVUEPPSJOEPPSVOJU
101
Control Systems
6) Function
Power distribution
Example of watt hour meter installation ❷ Installing 1 watt-hour meter to all indoor units
.BJODJSDVJUCSFBLFS
1*.
8BUUIPVSNFUFS" $)
8BUUIPVSNFUFS# $)
Address 0 8BUUIPVSNFUFS$ $)
8BUUIPVSNFUFS% $)
A B C
A/ B
R1/R2
1 phase power
0 1 2
F1/F2
1JQF
DPOOFDUJPO
R1/R2
0 1 2
F1/F2
1JQF
DPOOFDUJPO
3 phase power
4JODFBMMJOEPPSVOJUT
BSFDPOOFDUFEUP
XBUUIPVSNFUFS
1*.
DIBOOFMBEESFTTPGBMM
JOEPPSVOJUTJTTBNF
102
Example of watt hour meter installation ❸ Using CT watt-hour meter to and outdoor unit
.BJODJSDVJUCSFBLFS
RS T N
1*.
Address 0
R1/R2
$5UZQFXBUUIPVSNFUFS
8BUUIPVSNFUFS" $)
8BUUIPVSNFUFS# $)
3 phase 4 wire voltage
R1/R2
8BUUIPVSNFUFS$ $)
8BUUIPVSNFUFS% $)
A B C D
1 phase power
0 1 2
MANAGEMENT SYSTEMS
F1/F2
INTEGRATED
1JQF
DPOOFDUJPO
R1/R2
0 1 2
F1/F2
1JQF
DPOOFDUJPO
3 phase power
<4FUUJOHBOEDIFDLJOH
XBUUIPVSNFUFS>
'SPNUIFNFOV
$5
QSPQPSUJPOPGUIF$5
XBUUIPVSNFUFSNVTU
CFFOUFSFE
; Note
t"GUFSFOUFSJOH$5QSPQPSUJPOPGUIF$5XBUUIPVSNFUFS
XBUUIPVSNFUFSNVTUCFTFUUPDPSSFDUPVUEPPSJOEPPSVOJUT
GSPNUIF<$IBOOFMTFUUJOHCZJOEPPSVOJU>XJOEPX
103
Control Systems
6) Function
Power distribution
104
Setting virtual watt-hour meter
8IFOXBUUIPVSNFUFSPS1*.JOUFSGBDFNPEVMFJTOPUJOTUBMMFEUPBXBUUIPVSNFUFSDIBOOFM
WJSUVBMDIBOOFMDBOCFVTFEUPNBOVBMMZ
EJTUSJCVUFUIFQPXFSEJTUSJCVUJPO
MANAGEMENT SYSTEMS
INTEGRATED
tMaximum 128 virtual channel can be used.
tAddress of the virtual channel will be displayed as following.
(24~31).(1~16)
; Note
t8IFO1*.JOUFSGBDFNPEVMFJTOPUJOTUBMMFE
1*.DIBOOFMPGUIFPVUEPPSJOEPPSVOJUXJMMCFJOBDUJWF
105
Control Systems
6) Function
Power distribution
Caution
1PXFSEJTUSJCVUJPOGVODUJPOJTPOMZTVQQPSUFEUPBJSDPOEJUJPOFSTBOE")6&37JTOPUTVQQPSUFE
33
0OMZBQQMJFTUPJOEPPSVOJU
106
User authorization management
MANAGEMENT SYSTEMS
INTEGRATED
tAdmin (Administrator) : $BOBDDFTTBMMNFOVT
BDDFTTJCMFNFOVDBOOPUCFDIBOHFE
tManager : %FGBVMUTFUUJOHo$BOBDDFTTBMMNFOVT
BDDFTTJCMFNFOVDBOCFDIBOHFE
tRegular user : %FGBVMUTFUUJOHo$BOBDDFTT<$POUSPMBOENPOJUPSJOH>NFOVPOMZ
t"DDFTTJCMFNFOVBVUIPSJ[BUJPOPGNBOBHFSJTFEJUBCMF
4FMFDUEFTFMFDUUIFDIFDLCPYPGUIFGVODUJPOBOETBWFUIFTFUUJOHUPDIBOHFUIFBVUIPSJ[BUJPO
107
Control Systems
6) Function
User management
f You can add or delete the user who access DMS2 through web.
f Authorization of the added user can be set from [Admin], [Manager], [Regular user].
108
Zone management
t;POFFEJU6TFSDBOBSSBOHFUIFJOEPPSVOJUTGPSDPOWFOJFOUNBOBHFNFOU
t4FUUJOHUIFVTFSBVUIPSJ[BUJPO$BOSFTUSJDUBDDFTTJCMFJOEPPSVOJUTEFQFOEJOHPOUIFVTFS*%
Zone edit
MANAGEMENT SYSTEMS
INTEGRATED
Initial setting
Zone edit :
Add, delete zone
Change name
Move indoor unit
109
Control Systems
6) Function
f Authorization to control and monitor a zone of indoor units can be assigned according to User ID
❶Select the zone and select a user ID who can access the zone.
t"DDFTTBVUIPSJ[BUJPODBOCFTFUCZ[POF
❷After setting, click [Save] to complete the authorization setting.
f User access authorization applies to all indoor units of the zone in same manager.
110
2. S-NET3
MST-P3P
1) Features
MANAGEMENT SYSTEMS
2) PC specifications
INTEGRATED
Item Model Details
$16 1FOUJVNPSBCPWF
.FNPSZ .PSFUIBO.#
PC
)%% .PSFUIBO(CZUFTQBDFBWBJMBCMF ; Note
/FUXPSL . Model .4511
8JOEPXT/5
8JOEPXT
8JOEPXT91
Number of connection .BY%.4T
OS
8JOEPXT7*45"
8JOEPXT
3) System connection
%.4
)6#
*OUFSOFU
111
Control Systems
4) Function
(1) S-NET3 function description
7JFXUIFNBOBHFNFOU
$POUSPMBOENPOJUPSUIFJOEPPSVOJUT NBY
VOJUT
TUSVDUVSF
$IFDLBOESFGFSUIFTUBUFPGWBSJPVTEFWJDFTTVDIBTJOEPPSPVUEPPSVOJUT
7JFXUIFJOTUBMMBUJPOTUSVDUVSF
0O0GGDPOUSPMMFS
BOE*.
4FUUIFPQFSBUJPONPEF
UFNQFSBUVSF
GBOTQFFE
BOEGBO
*OEPPSVOJU&37DPOUSPM
Control & Monitoring $POUSPM.POJUPSJOHEJSFDUJPOPGJOEPPSVOJU&37
*OEPPSVOJU&37NPOJUPSJOH .POJUPSUIFTUBUVTPGJOEPPSVOJU&37
$IFDLUIFPVUEPPSVOJUTDZDMFEBUBBOEUIFDZDMFEBUBPGUIFMJOLFEJOEPPS
7JFXPVUEPPSVOJU
VOJUT
7JFX%.4 $IFDLUIFTUBUVTEBUBPGUIFDPOUSPMVOJUMJOLFEUP%.4
$SFBUFOFXTDIFEVMF 4FUOFXTDIFEVMF
7JFXTDIFEVMF $IFDLUIFTDIFEVMFPGUIFTFMFDUFEJOEPPSVOJU
4UBSU4UPQTDIFEVMF 4UBSU4UPQTDIFEVMFBQQMJDBUJPO
Schedule
4UPSF$BMMTDIFEVMF 4UPSF$BMMBQSFQBSFETDIFEVMF
7JFXEBJMZTDIFEVMF $POGJSNFBDITDIFEVMFCZEBUF
4FUDPNNPOFYDFQUJPOEBUF 4FUUIFEBUFXIJDITDIFEVMFPQFSBUJPOJTOPUBQQMJFEPO
*OEPPSVOJUTUBUVT $IFDLUIFTUBUVTPGJOEPPSVOJUPQFSBUJPOUFNQFSBUVSFTFUUJOHQFSQFSJPE
*OEPPSVOJUVTBHF 5IFVTBHFSBUJPPGBMMJOEPPSVOJUTGPSBTQFDJGJDQFSJPE
4FUUIFFOWJSPONFOUSFMBUFEUP4/&5
4FUFOWJSPONFOU
QBTTXPSE
MBOHVBHF
UFNQFSBUVSFVOJU
4FU%.4 4FUUIF%.4UPDPOOFDUXJUI4/&5
4/&5CBDLVQSFTUPSF #BDLVQUIFEBUBPG4/&5
112
(2) User functions
.BOBHFBSBOHFPGGVODUJPOTBDDFTTJCMFUPEJGGFSFOUUZQFTPGVTFSTTVDIBTSFHVMBSVTFS
BENJOJTUSBUPSBOEJOTUBMMFS
MANAGEMENT SYSTEMS
1PXFSDPOTVNQUJPOSFQPSU 9 0 0
1PXFSEJTUSJCVUJPONBOBHFNFOUHSPVQFEJU 9 0 0
INTEGRATED
1PXFSEJTUSJCVUJPOTFDUJPOTFUUJOH 9 9 0
4UBUJTUJDT"OBMZTJT 9 0 0
4/&5TFUUJOH 9 0 0
%.4TFUUJOH 9 9 0
&WFOUMPHSFGFSFODF 9 0 0
5SBDLJOH 9 9 0
%.4SFTUPSBUJPO 9 9 0
%.4CBDLVQ 9 0 0
4/&5SFTUPSBUJPOCBDLVQ 9 0 0
Log-in
4FMFDUVTFS
4FMFDUBENJOJTUSBUPS
4FMFDUJOTUBMMFS
1BTTXPSEJOQVU
-PHJOCVUUPO
113
Control Systems
.PWFUP*OEPPS
.BOBHFNFOU
VOJUDPOUSPM
TUSVDUVSF*OTUBMMBUJPO
XJOEPX
TUSVDUVSFEJTQMBZ
XJOEPX
*OEPPSVOJU
DPOUSPM
&37DPOUSPM
.BJONFOV
XJOEPX
-PHFSSPSEJTQMBZ
XJOEPX
114
Installation structure window
MANAGEMENT SYSTEMS
INTEGRATED
t0VUEPPSVOJUDZDMFEBUB
PVUEPPSVOJUNPEFM
JOUFSGBDFNPEVMFNPEFMBOEJOUFSGBDFNPEVMFQSPHSBNWFSTJPOJTEJTQMBZFE
t*OEPPSVOJUPQFSBUJPOTUBUVT JOEPPSVOJUDZDMFEBUBBOEJOEPPSVOJUNPEFMDPEFJTEJTQMBZFE
115
Control Systems
f When DI is selected
f When DO is selected
116
Control
t$POUSPMJOEPPSVOJU&37UISPVHIUIFDPOUSPMXJOEPXUIBUBQQFBSTPOUIFTDSFFO
t$POUSPMUPUBMJOEPPSVOJUT
UIFPQFSBUJPONPEFPGJOEPPSVOJUT
NVMUJQMFTFMFDUJPO
UFNQFSBUVSF
GBOTQFFE
BOEGBOEJSFDUJPO
t4FU6QQFS-PXFSUFNQFSBUVSFMJNJUTPUIBUUFNQFSBUVSFDBOOPUCFTFUPVUTJEFPGUIFMJNJUFEUFNQFSBUVSFSBOHF
t&OBCMFEJTBCMFSFNPUFDPOUSPMVTBHF
t$IFDLUIFTDIFEVMFPGUIFTFMFDUFEJOEPPSVOJU
MANAGEMENT SYSTEMS
INTEGRATED
f Selecting indoor unit f Selecting ERV
117
Control Systems
Schedule control
❶ Schedule setting
t"CMFUPTFUBTDIFEVMFUPDPOUSPMJOEPPSVOJUTBOE&37T DSFBUJOH
NPEJGZJOH
EFMFUJOH
t"CMFUPTFUXFFLMZ
EBJMZ
POFEBZTDIFEVMF
t"CMFUPDPOUSPMUIFPQFSBUJPONPEF
UFNQFSBUVSFTFUUJOH
GBOTQFFE
GBOEJSFDUJPOEVSJOHUIFTDIFEVMFDPOUSPM
4DIFEVMFMJTU
XJOEPX
4DIFEVMFEJTQMBZXJOEPX
Ú&BTZTDIFEVMFDPOUSPMGPSVTFSXJUIUIFXJ[BSENFUIPE TUFQCZTUFQTFUUJOH
f The 2nd step (select the indoor units to apply a schedule to)
t%JTQMBZUIFUPUBMJOEPPSVOJUTJO4/&5
t"CMFUPTFMFDUJOEJWJEVBMJOEPPSVOJUT
0O0GGDPOUSPMMFS
%.4
118
Schedule control
$POUSPMQBOFM
$MJDLUXJDF
5JNFNPEJGJDBUJPO
MANAGEMENT SYSTEMS
CBTFEPONJOVUFT
5FNQFSBUVSFTFUUJOH
INTEGRATED
0QFSBUJPONPEF
3FNPUFDPOUSPMVTF
5JNFTFUUJOHCZESBHHJOH
CBTFEPONJOVOJU
4DIFEVMFNPEJGJDBUJPOQBOFM
4DIFEVMFOBNF
4DIFEVMFQFSJPETFUUJOH
4DIFEVMFFYDFQUJPO
EBUFTFUUJOH
%JTQMBZUIFOBNFPG %JTQMBZTFUTDIFEVMF
TFUTDIFEVMF
119
Control Systems
Schedule control
❷ Schedule modification
t$MJDLUIFTFUTDIFEVMFEJTQMBZXJOEPXUXJDFUPEJTQMBZUIFNPEJGJDBUJPOQBOFM
5IFOJUJTQPTTJCMFUPNPEJGZWBSJPVTGVODUJPOTTVDIBTTDIFEVMFUJNF
PQFSBUJPONPEFBOEUFNQFSBUVSFTFUUJOH
t"CMFUPDBSSZPVUWBSJPVTGVODUJPOTTVDIBTBTDIFEVMFOBNFDIBOHF
TDIFEVMFEFMFUF
JOEPPSVOJUBEEJUJPOBOEEFMFUJPOXJUIUIFJDPOT
POUIFMFGUNFOVXJOEPX
"EE%FMFUFJOEPPSVOJUGPSTDIFEVMFDPOUSPM
%FMFUFBTFUTDIFEVMF
.PEJGZBTDIFEVMFOBNF
5PUBMJOEPPSVOJUVTBHFSFGFSFODF *OEJWJEVBMJOEPPSVOJUVTBHFSFGFSFODF
5ZQFTPGEPDVNFOUUPCFTUPSFE
120
Usage time and power consumption
1PXFSTUSVDUVSFFEJUJOHNFOV
1PXFSTUSVDUVSFFEJUJOHXJOEPX
MANAGEMENT SYSTEMS
INTEGRATED
❹ Power section setting
t*UDBOCFSFGFSSFEBOEEJWJEFEJOUPNBYTFDUJPOTGPSQPXFSDPOTVNQUJPOSFGFSFODF
t*UJTQPTTJCMFUPSFGFSPSQSFQBSFSFQPSUTGPSVTBHFUJNFBOEQPXFSDPOTVNQUJPOCZEJWJEJOHTFDUJPOCZFBDIIPVS
"CMFUPBEKVTUUIFTFDUJPOTCZJOQVUUJOHSFMFWBOUUJNF
121
Control Systems
)PVSMZJOEPPSVOJUPQFSBUJPOBOE
UFNQFSBUVSFEJTQMBZ
4FMFDU
JOEPPSVOJU %JTQMBZFSSPSTJGUIFXSPOH
QFSJPEIBTCFFOTFU
1FSJPESFGFSFODF
%.4TFMFDUJPO
122
System management
❶ Environment setting
t4FUUIFFOWJSPONFOUPG4/&5
t4FUBENJOJTUSBUPSQBTTXPSE
MBOHVBHF
UFNQFSBUVSFVOJU
EFGBVMUWBMVFGPSJOEPPSVOJU
FUD
t%FUFSNJOFJGQFBLQPXFSXJMMCFEJTQMBZFEPSOPUJOUIFNFOVTFUUJOH ,PSFBONBSLFUPOMZ
-BOHVBHFTFUUJOH
-PHEBUFWJFXTFUUJOH
5FNQFSBUVSFVOJUTFUUJOH*UJTTFUBVUPNBUJDBMMZ
EFQFOEJOHPOJOEPPSVOJU
MANAGEMENT SYSTEMS
INTEGRATED
❷ DMS2 setting
t4FUUIF%.4UPDPOOFDUXJUI4/&5
t$MJDLATBWFBGUFSJOQVUUJOH*1BOEQBTTXPSET
BOEJUXJMMBUUFNQUUPNBLFDPNNVOJDBUJPOXJUI4/&5BOE%.4UIFOEJTQMBZ
OPSNBMXIFODPNNVOJDBUJPOJTNBEF
%.4TFUVQXJOEPX
8IFOB%.4UPDPOOFDUXJUI %.4UJNFTFUUJOH
4/&5JTBEEFE
1BTTXPSEJOQVU
%.4TBDDFTT*1JOQVU
; Note
%.4IBTUXPQBTTXPSET0OFJTBQBTTXPSEOFFEFEUPDPOOFDUUPB%.4XFCDMJFOU TFUBUUIFVTFSNBOBHFNFOU
UIFPUIFSJT
OFDFTTBSZUPNBLFBDDFTTUP4/&5 TFUBUUIFTZTUFNFOWJSPONFOU
8IFOUIFXSPOHQBTTXPSEGPS4/&5JTJOQVU
BNFTTBHFJOEJDBUJOH%.4oBDDPVOUSFDPHOJUJPOGBJMVSFBQQFBST
123
Control Systems
System management
❸ View event log
t"CMFUPDIFDLWBSJPVTJOGPSNBUJPOTVDIBTJOEPPSPVUEPPSVOJUTDPOOFDUFEUP4/&5
DPOUSPMEFWJDFFSSPSXBSOJOH
JOGPSNBUJPO
EFUBJMTCZEBUF
4FUUIFMJTUPGFWFOUT
2VFSZQFSJPETFUUJOH
&WFOUEJTQMBZ
-JTUPGDPOUSPMEFWJDFTDPOOFDUFEUP%.4 5SBDLJOHJTVOEFSXBZ
124
System management
❺ DMS2 backup and restoration
t"CMFUPCBDLVQBOESFTUPSFUIF%.4EBUBDPOOFDUFEUP4/&5
t#BDLVQSFGFSTUPBDUJWJUJFTPGTUPSJOHEBUBJOUIFEBUBGPMEFSJO1$
4FMFDUBMM%.4T
#BDLVQ
3FTUPSBUJPO
*OEJDBUFBCBDLVQGJMFJODMVEJOHUIF
EJSFDUPSZQBUI
*OEJDBUFBCBDLVQEBUF
MANAGEMENT SYSTEMS
INTEGRATED
❻ S-NET3 backup and restoration
t"CMFUPCBDLVQBOESFTUPSFEBUBPG4/&5
t#BDLVQJOWPMWFTJOCBDLJOHVQBMMEBUBJO4/&55IVT
JGCBDLVQEBUBJTSFTUPSFEJOB1$XIFSF4/&5JTJOTUBMMFE
JUXJMMQSPEVDFUIFTBNFFOWJSPONFOUUIBUJTQSFWJPVTMZVTFE
125
Control Systems
Log Contents
E9000 $POOFDUJPOJNQPTTJCMF
E9001 $POOFDUJPOEFOJFE
E9002 $POOFDUJPOGJOJTIFE
E9010 8*/,EFOJFE
E9011 %.4QBTTXPSEBVUIFOUJDBUJPOGBJMVSF
E9012 4FSJBMFYDIBOHFGBJMVSF
E9100 (FOFSBMFSSPSPOJOTUSVDUJPOUSBOTNJTTJPO
E9150 "UUFNQUUPUSBOTNJUUPB%.4OPUJODPOOFDUJPO
E9151 "UUFNQUUPUSBOTNJUUPB%.4OPUSFHJTUFSFE
E9200 (FOFSBMFSSPSPOSFTQPOTFBDDFQUBODF
E9250 5IFSFJTOPSFTQPOTFUPUIFSFRVFTUFEDPNNBOEEVFUP%.4GBJMVSFBOEPSOFUXPSLEFMBZ
E9300 9.-HFOFSBUJOH
E9400 9.-QBSTJOH
E9401 *OTUBMMBUJPOJOGPSNBUJPOPO4/&5BOE%.4EPFTOPUNBUDI
DIFDLUSBDLJOHJOGPSNBUJPO
E9999 *OJUJBMJ[FEEFWJDFJOGPSNBUJPOVQEBUJOHEFWJDFTUBUVT
I101 $PNNPOVTFSMPHJO
I102 "ENJOJTUSBUPSVTFSMPHJO
I103 *OTUBMMFSMPHJO
I104 -PHJO
I105 -PHPVU
I201 5SBDLJOH
I202 3FRVFTUUPUSBDLJOH
I301 3FRVFTUUPTDIFEVMFDIBOHF
I801 *OTFSU%.4
I802 %FMFUF%.4
I803 %.4UJNFTFUUJOH
I9700 %.4DPOOFDUJPOBOEBVUIPSJ[BUJPOTVDDFTTGVM
I9701 3FDPOOFDUJPO
I9801 &NFSHFODZTUPQ
126
IV. Power distribution system
1 &MFDUSJDJUZNFUFSJOUFSGBDFNPEVMF 128
DISTRIBUTION SYSTEM
POWER
127
Control Systems
1) Features
(Unit : mm)
240 64.80
t1VMTFPVUQVUFMFDUSJDJUZNFUFSJOUFSGBDFVOJU
(max. 8 meters) Input : 100~240V AC, 50/60Hz, 1.0A
Power supply (adapter)
tDIBOOFMFOFSHZDPOTVNQUJPOEJTQMBZJOSFBMUJNF Output : 12V DC, 3.0A
t4ZTUFNDPOGJHVSBUJPOXJUICVUUPONBOJQVMBUJPO Operating temperature range -10ºC ~ 50ºC
t7BSJPVTUFYUNFTTBHFTJO-$%
t$VSSFOUDPNNVOJDBUJPOTUBUFJOEJDBUJPO Operating humidity range 10%RH~90%RH
DMS2 : 1000m
Maximum wiring length
Electricity meter : 200m
①
②
③ ⑦
④
⑤ ⑥
④ Communication (orange) It blinks when communication between DMS2 and MIM-B16N normally works.
⑤ Pulse input (orange) Each of the 8 LEDs blinks whenever a pulse from an electricity meter is detected.
⑦ Check It’s ON when errors occur in communication or pulse input from electricity meters.
128
[¥]UwGG ¥UGGGXY_ YWX[TW[TY\GGG㝘䟸G[aZ]aY_
3) Connectors
③ ④ ⑤
⑤ COM2 Reserved
DISTRIBUTION SYSTEM
POWER
Address switch Option switch
No Name Description
1 SW1 No function
2 SW2 MIM-B16N address switch. Address greater than 7 (8~F) is not recognized.
3 SW3 No function
4 SW4 No function
129
[¥]UwGG ¥UGGGXY` YWX[TW[TY\GGG㝘䟸G[aZ]aY`
Control Systems
(BTNFUFS_N3/pulse
8BUFSNFUFS_MJUFSQVMTF OPEFDJNBMQVMTFSBUFBMMPXFE
1VMTFHFOFSBUJPOGSPN
electricity meter
Current source
Current sink Current flow(max. 15mA)
Current flow
Waveform of CH1~8
Over 4ms
20~1000ms
; Note
Interface circuitry of an electricity meter has to withstand min. 15mA and min. 15V DC, both of which are applied by MIM-B16N.
Even though MIM-B16N interface circuitry is realized with electric isolation components, it’s highly recommended that interface
circuitry of an electricity meter be designed with isolation to ensure robustness from contact spike or electric interference
during wiring.
130
[¥]UwGG ¥UGGGXZW YWX[TW[TY\GGG㝘䟸G[aZ]aY`
6) Installation
MIM-B16N must not be installed in a way that power to MIM-B16N is off when one of the over-current circuit breakers
is switched off. Power supply to MIM-B16N must be off only when all the power supplies to refrigerant systems whose
power consumptions are monitored by the MIM-B16N are cut off. This is because every pulse from electricity meters of
some alive refrigerant systems must be sensed normally even if power supplies to
other refrigerant systems have troubles.
t&YBNQMF
8IFOUIFDJSDVJUCSFBLFS
$.JTTXJUDIFEPGGGPSTPNFSFBTPOXIJMFUIFPUIFSTBSFTUJMMPO
QVMTFTGSPNUIFFMFDUSJDJUZ
meters, EM1, EM2 and EM3 are not calculated by MIM-B16N, whose power is off by the CM1. This installation could
lead to errors in electricity billing function when power interruption in local areas occurs.
CM1 AC Power
OFF
0 1 2
F1/F2
Refrigerant pipe
0 1 2
F1/F2
DISTRIBUTION SYSTEM
Refrigerant pipe
POWER
t&YBNQMF
&WFOXIFOUIFDJSDVJUCSFBLFS
$.JTTXJUDIFEPGGXIJMFUIFPUIFSTBSFPO
QVMTFTGSPNUIFFMFDUSJDJUZNFUFST
&.
EM2 and EM3 are still calculated by MIM-B16N, whose power is not interrupted by CM1.
CM1
OFF
0 1 2
F1/F2
Refrigerant pipe
0 1 2
F1/F2
Refrigerant pipe
131
[¥]UwGG ¥UGGGXZX YWX[TW[TY\GGG㝘䟸G[aZ]aZW
Control Systems
7) Wiring
f Wiring to electricity meter
t Attention must be paid to make polarized connection between an electricity meter and MIM-B16N with correct specifications
on wires.
1VMTFUZQFFMFDUSJDJUZNFUFS MIM-B16N
+ + + +
Typical interface circuitry
+ +
Cable : 6OTIJFMEFEXJSFNN2 VCTF or equivalent
Length :.BYN
f Wiring to DMS2
t Make sure that communication cable is wired between DMS2 and MIM-B16N with the right polarity.
%.4 .*.%"/
MIM-B16N
A B A B
to another MIM-B16N
Cable : 6OTIJFMEFEXJSF_NN2 VCTF or equivalent
Length : .BYN
f Caution
t MIM-B16N can be connected with outdoor units/controllers to same channel of DMS2.
Ex) %.4$)1*.0VUEPPSVOJU 0
1*.5PVDIDPOUSPMMFS 0
132
[¥]UwGG ¥UGGGXZY YWX[TW[TY\GGG㝘䟸G[aZ]aZX
8) Address assignment
Each of the electricity meters is assigned with the dedicated address depending on MIM-B16N address setting and the
position of the pulse input terminals.
SW1 SW2
CISTRIBUTION SYSTEM
9) MIM-B16N menu structure
POWER
Normal Display 1. Monitoring 1.1 Address
2.4 Date&Time
133
[¥]UwGG ¥UGGGXZZ YWX[TW[TY\GGG㝘䟸G[aZ]aZX
Control Systems
5IF.*.#/BEESFTTJTEJTQMBZFEXJUIUIFQIZTJDBMBEESFTT48BEEFECZ)POUIF
LCD window.
Ex) LCD SW2 setting
1.Monitoring
) 1.1 Address
31H 1
1*."EESFTT
… …
1.1 Address
37H 7 58 30 FF
Option switch setting to ON is displayed with the position number at the corresponding
positions while setting to OFF is shown with the mark ‘X’.
Monitoring Ex)
Option SW 1.2 Option S/W Example display : 1X
tOption switch 1 : On
1X
tOption switch 2 : Off
*UEJTQMBZT1*.TPGUXBSFWFSTJPO
Ex)
Micom version 1.3 Micom Ver.
130123
*UEJTQMBZT1*.TPGUXBSF%#DPEF
Ex)
DB Code 1.4 DB Code
DB91-01128A
The password, which is asked to enter to change the configuration setting, is used to prevent
VOBVUIPSJ[FEQFSTPOTGSPNBDDFTTJOH.*.#/'BDUPSZTFUUJOHJTA
1BTTXPSE Ex)
You can set pulse rate of meter which connected to each channel.
Configuration [Range]
1VMTF8JEUI 1PXFSNFUFS_8IQVMTF /PEFDJNBMQVMTFSBUFBMMPXFE
(BTNFUFS_N3/pulse
8BUFSNFUFS_MJUFSQVMTF /PEFDJNBMQVMTFSBUFBMMPXFE
Date & time You can set current date and time.
Value set Initial meter value must be set as a starting point for each of the enabled interface channels.
Value clear Each or all the initial meter values are cleared when selected.
134
[¥]UwGG ¥UGGGXZ[ YWX[TW[TY\GGG㝘䟸G[aZ]aZX
Main menu Sub menu Description
When pulse input is detected during the test period, the channel numbers are displayed.
Otherwise, the character ‘X’ is displayed on the corresponding channel position.
1VMTF*OQVU
Make a loopback connection between COM1 and COM2 to check if the DMS2
communication channel is working or not. Care must be taken for the connection polarity.
COM Check
When the COM1 communication channel is normal, the message ‘OK’ is displayed on the
LCD window.
Check It checks if the pulse width values of actually connected meter are valid or not.
t0,8IFOUIFQVMTFJTWBMJE QVMTFJTWBMJEXIFOIJHIQVMTFJTCFUXFFO_NTFD
0,
(M:####msec) will be displayed. #### represents the duration of the high pulse.
t/(8IFOUIFQVMTFJTJOWBMJE QVMTFJTWBMJEXIFOIJHIQVMTFJTCFUXFFO_NTFD
PS
XIFOUIFSFJTOPQVMTFJOQVUTGPSTFDPOET
/( .NTFD
XJMMCFEJTQMBZFE
1*.EPFTOPUDBMDVMBUFUIFFOFSHZDPOTVNQUJPOEVSJOHUIFDIFDLJOHQSPDFTT5IF
calculation will start after the check and returning to the upper menu.
1VMTF8JEUI
DISTRIBUTION SYSTEM
CH1 Check OK Checking...
POWER
CH1 Check End
NG (M:0000msec)
135
[¥]UwGG ¥UGGGXZ\ YWX[TW[TY\GGG㝘䟸G[aZ]aZX
Control Systems
<5SBDLJOHSFTVMUQBHF1*.i4FUUJOHw>
136
[¥]UwGG ¥UGGGXZ] YWX[TW[TY\GGG㝘䟸G[aZ]aZY
V. External control systems
1 External contact interface module . . . . . . 138
2 Multi tenant function controller (MTFC). . . 142
CONTROL SYSTEMS
EXTERNAL
137
[¥]UwGG ¥UGGGXZ^ YWX[TW[TY\GGG㝘䟸G[aZ]aZY
Control Systems
50
Interlock DVM air-conditioner with external controller
t*OEPPSVOJU0O0GGDPOUSPMCZUIFFYUFSOBMDPOUBDU 6TBCMFFRVJQNFOU$BSELFZ
5JNFS
4FOTPS
t0VUQVUUIFJOEPPSVOJUUIFSNP0/0''TUBUFBOEPQFSBUJPOTUBUVT
t0VUQVUUIFJOEPPSVOJUFSSPSTUBUF
2) Description of parts
Contact
No. Input/Output Operation
rating
④ 7"$
① Error state Normal:Close, Error:Open
3A
⑤ Indoor unit Thermo On/Off [Output signal]
or Operation State output
7"$
4&(5IFSNP0O0GG
② (It depends on indoor SEG 15 =1 Operation On/Off
3A
unit's INSTALL option
setting SEG 15.) (On:contact close, Off:contact open)
① ② ③
5V DC,
③ Operation signal input load -
5mA
④ Connector for indoor unit - -
⑤ Connector for indoor unit - -
3) Installation
External contact line wiring
Indoor unit thermo Error signal
ON/OFF signal output
Voltage free contract signal input
Ex) Sensor, Card-key, Timer
7"$
"
*OEPPSVOJU1$#
Connect
wire
; Note
External operation input load: 5V DC/5mA.
5IFMFOHUIPGXJSJOHCFUXFFO.*.#BOEFYUFSOBMDPOUSPMFRVJQNFOUJTNNBY
To use external contact control system, indoor unit's INSTALL option setting is required.
(Refer to indoor unit installation manual)
7 SEG 14 - External control setting (Default : No use)
After installed, the first operation will be conducted with Auto mode, Set temp. 24°C, Auto Fan speed.
If the indoor unit in OFF status is turned ON through external contact signal; it will operate in the last operation status before
138 it was turned off.
[¥]UwGG ¥UGGGXZ_ YWX[TW[TY\GGG㝘䟸G[aZ]aZY
4) Control
; Note
IDU stands for Indoor Unit.
No prioritized operation between the R/C and the external contact I/M.
Ex2)
CONTROL SYSTEM
EXTERNAL
; Note
IDU stands for Indoor Unit.
After power reset, indoor unit operates as previous state. (IDU has power recovery function)
139
[¥]UwGG ¥UGGGXZ` YWX[TW[TY\GGG㝘䟸G[aZ]aZY
Control Systems
; Note
IDU stands for Indoor Unit.
After power reset, if IDU is turn ON by external contact, it starts as Auto mode, 24ºC, Auto fan speed.
Ex4)
; Note
IDU stands for Indoor Unit.
After power reset, IDU ignores initial external signal state.
140
[¥]UwGG ¥UGGGX[W YWX[TW[TY\GGG㝘䟸G[aZ]aZY
f Operation input
It is possible to set the method of indoor unit control by external contact signal.
t Method 1. Turn On/Off the indoor units by external contact signal
t Method 2. Set standby/Turn Off the indoor unit by external contact signal
t Method 3. Return to the last status / Turn Off the indoor unit by external contract signal
f Operation output
Error signal
t Thermo off : Status where refrigerant is not flowing in either cooling/heating operation because desired temperature has been reached.
CONTROL SYSTEM
EXTERNAL
141
[¥]UwGG ¥UGGGX[X YWX[TW[TY\GGG㝘䟸G[aZ]aZZ
Control Systems
75
t Multi tenant function controller is an auxiliary power supply device which allows indoor unit to turn off (close EEV) normally and
maintain communication when main power supply is cut.
t It is used in site such as hotel where individual power is supplied to the indoor unit
>5PJOUBMMUIF.5'$
DPOOFDUJPODBCMFGPSUIFQPXFS
USBOTGPSNFSBOEUIF*1 *OHSFTT1SPUFDUJPO
CPYNVTU
be purchased separately at the installation site.
>4QFDJGJDBUJPOPGUIFUSBOTGPSNFS6-4UBOEBSE
$MBTT
7BD)[
2) Product specification
AC 24V
Power supply
)[
Power consumption 8
Operating temperature range ¡$_¡$
Operating humidity range 3)_3)
Maximum length of connection 3m
Number of control devices 1 indoor unit
3) Description of parts
③
①
④
⑤
②
142
[¥]UwGG ¥UGGGX[Y YWX[TW[TY\GGG㝘䟸G[aZ]aZZ
4) Connection diagram
Outdoor unit
5) Connecting
24 Vac mX mY }X }Y mZ m[
24 Vac ±15 %G
50/60 Hz
CONTROL SYSTEM
%$1PXFSDBCMF 7
EXTERNAL
%$1PXFSDBCMF 7
s
u
*OEPPSVOJU1$#
download
*OEPPSVOJU"$1PXFS
143
[¥]UwGG ¥UGGGX[Z YWX[TW[TY\GGG㝘䟸G[aZ]aZ[
Control Systems
6) Main fucntion
f Detail information of the indoor unit when the power is supplied by MTFC
Item Operation Detail information
Indoor unti operation OFF Remain indoor unit in off status, turning on is not possible
EEV control Close Operation off, follows indoor unit's EEV control
Self error diagnosis Operating Detects error such as EEV close/open by executing self-diagnosis
1PTTJCMFPOMZUISPVHI
Recognition of MTFC status 6TJOH4/&51SP
VTFSDBODIFDL.5'$XPSLJOHTUBUVT
4/&51SP
f Caution
t Wired remote controller for group control cannot be installed to an indoor unit which Multi Tenant Function controller was installed.
t EEV operation of the stopped Heat mode will be controlled in same condition as noise reduction control option when
Multi Tenant Function Controller operates.
t If the Multi Tenant Function Controller operates while multiple indoor units are working in mixed operation mode
(cooling and heating at the same time), dew may form on the indoor unit fan.
144
[¥]UwGG ¥UGGGX[[ YWX[TW[TY\GGG㝘䟸G[aZ]aZ[
VI. Building management systems
1 DMS L-net (Lonworks GW) . . . . . . . . . . . 146
2 DMS B-net (BACnet GW). . . . . . . . . . . . . 160
MANAGEMENT SYSTEM
BUILDING
145
[¥]UwGG ¥UGGGX[\ YWX[TW[TY\GGG㝘䟸G[aZ]aZ[
Control Systems
1) Features
Lon
ACK SVC
2) Product specification
Source DC Adaptor
Power
Input 100~240VAC (±10%), 50/60Hz
supply
Output 12V 3A
Operating temperature
-10ºC ~ 50º C
range
Operating humidity range 10%RH ~ 90%RH
RS485 N
number of layer
device OnOff controller
Total 15 Total 75
Touch centralized controller
1*.JOUFSGBDFNPEVMF .*.#
.*.#/
8 8
146
[¥]UwGG ¥UGGGX[] YWX[TW[TY\GGG㝘䟸G[aZ]aZ\
Compatible product
Outdoor unit AM7777X777777
0O0GGDPOUSPMMFS .$."%/
Controller 5PVDIDFOUSBMJ[FEDPOUSPMMFS .$."/
1*.JOUFSGBDFNPEVMF .*.#
.*.#/
7 Conventional communication outdoor unit requires compatible interface module (MIM-N01) to establish connection
7 MIM-B13D, MIM-B13E, MIM-B04A Interface modules cannot be connected.
7 To connect ERV, MIM-N10 interface module is required.
7 PIM connection is different depending on software version.
- Before 2.6.0.3 : MIM-B16 only
- 2.6.0.3 : MIM-B16N only
- After 2.6.1.7 : MIM-B16, MIM-B16N
3) Description of parts
Front
DMS-Lnet
No Name Function
① LCD display Displays current time or menu.
①
② Menu button Access the setting menu.
③ ③ Bottom cover
Unscrew 2 screws on the bottom to remove the
cover and check the cable connections.
LED indicator
① ② ③ ④ ⑤⑥ ⑦ ⑧ ⑨
No. Item Name Status
① Power 1PXFSJOEJDBUPS Turns blue when the power is supplied.
Blinks in orange with 1 second intervals during
② CPU Alive $16PQFSBUJPOJOEJDBUPS
normal operation.
③ Ethernet-Linked Internet connection indicator Turns green during normal connection.
④ Ethernet-Active Internet data transmission/reception indicator Blinks in orange during normal transmission/reception.
MANAGEMENT SYSTEM
147
[¥]UwGG ¥UGGGX[^ YWX[TW[TY\GGG㝘䟸G[aZ]aZ\
Control Systems
3) Description of parts
Bottom
DI terminal 1 DI terminal 2 DO terminal 3 DO terminal 4 Lon terminal RS485 Communication terminal
Name Description
DI terminal 1 Digital Input connection terminal, Channel1~Channel5
SD card socket Sub memory (for program update and set information saving) socket
RS485 communication terminal RS485 port for communication with OnOff controller / interface module
148
[¥]UwGG ¥UGGGX[_ YWX[TW[TY\GGG㝘䟸G[aZ]aZ]
4) Connection diagram
f MIM-B16(PIM) should be connected separately with outdoor units or controllers.
f MIM-B16N(PIM) can be connected with outdoor units or controllers to same channel of DMS2. LonWorks
communication BMS
DMS-Lnet
Samsung RS485
communication
For power distribution
1PXFSMJOF
R1-R2
F1-F2
R1-R2
F1-F2
Watt-hour meter
Electrical
substation
R1-R2 F1-F2
5) Wiring
(CH = Channel)
F1 F2 R1 R2 MANAGEMENT SYSTEM
F1 F2 R1 R2
BUILDING
; Note
LonWorks GW can connect outdoor unit and OnOff controller/Touch centralized controller at the same time.
Outdoor unit and OnOff controller/Touch centralized controller can be connected to 1 communication channel at the same time.
149
[¥]UwGG ¥UGGGX[` YWX[TW[TY\GGG㝘䟸G[aZ]aZ^
Control Systems
5) Wiring
LonWorks GW
F1 F2
R1 R2
Outdoor unit
R1R2
R1R2
0 0 Outdoor unit
Outdoor unit
R1R2
R1R2
1 1 Outdoor unit
Maximum 16 Outdoor unit
connections
' '
Outdoor unit
Outdoor unit Ú Outdoor unit's address is defined automatically.
The address can be changed manually also.
LonWorks GW
Maximum 15
OnOff controllers
Outdoor unit
R1R2
Outdoor unit
R1R2
Outdoor unit
150
[¥]UwGG ¥UGGGX\W YWX[TW[TY\GGG㝘䟸G[aZ]aZ^
Connecting with outdoor unit and OnOff controller
LonWorks GW
R1R2
Maximum 16
outdoor units
1
Outdoor unit
R1R2
2
Outdoor unit
R1R2
3
Outdoor unit
Wiring distance
DMS-Lnet
ⓐ ⓑ ⓒ
ⓓ
Network radius
ⓔ
t%JTUBODFGSPNUIF-PO8PSLT(8UPUIFGVSUIFTUEFWJDFDBOOPUFYDFFEN
BUILDING
tⓒ + ⓓ + ⓔ d 1000m
ⓐ, ⓑ, ⓒ, ⓓ, ⓔ = 100m DMS-Lnet
ⓐ ⓑ ⓒ ⓓ ⓔ
HUB
Repeater
[¥]UwGG ¥UGGGX\X YWX[TW[TY\GGG㝘䟸G[aZ]aZ_
Control Systems
6) Commission
t'PS$PNNJTTJPOPQFSBUJPOXJUI#.4
QSFTTUIF<4FU>CVUUPO
for more than 3 seconds.
t8IFOZPVQSFTT4FSWJDF1JO
/FVSPO*%XJMMCFTFOUBOE<47$>-&%PG
the front panel will be lit up for a second.
Ú1SPHSBN*%#'#
8) Item summary
Item Function
Operation On/Off
Operation mode
Air flow direction
Common
Fan speed
Device error information
Model, address, type information
Set temperature
Indoor temperature
Filter replacement alert/ reset
Remote controller level
Indoor unit AHU
Control & Monitoring Thermostat information
Operation restriction setting (Cooling/Heating)
Setting lowest temperature/ restriction
Setting highest temperature/ restriction
1PXFSDPOTVNQUJPO
Operation time
Emergency stop
DMS2 DI/DO
Additional functions
DMS2 lock
DMS2 error information
System error information
152
[¥]UwGG ¥UGGGX\Y YWX[TW[TY\GGG㝘䟸G[aZ]aZ_
9) Network variable
(1) Indoor unit/ ERV/ AHU kit object
No. Name Type M/O Description
1 nviONOff SNVT_switch O ON/OFF command
2 NviApplicMode SNVT_hvac_mode O Setting operating mode
3 nviSetpoint SNVT_temp_p O Setting desire temperature
4 nviFanStatus SNVT_switch O Setting fan speed
5 nviERVMode SNVT_count O Setting ERV operation mode
6 nviFilterReset SNVT_switch O Filter reset command
7 nviUserLockout SNVT_switch O Setting the restriction of remote control use
8 nviOccOpMode SNVT_switch O Setting cooling only mode / heating only mode
9 nviCoolTempLock SNVT_switch O Setting the low temperature limit
10 nviHeatTempLock SNVT_switch O Setting the high temperature limit
11 nvoSpaceTemp SNVT_temp_p M Display indoor temperature
12 nvoApplicMode SNVT_hvac_mode O Display operating mode
13 nvoSetpoint SNVT_temp_p O Display desire temperature
14 nvoOnOff SNVT_switch O Display ON/OFF status
15 nvoFanStatus SNVT_switch O Display fan speed
16 nvoERVMode SNVT_count O Display ERV operating mode
17 nvoErrorCode SNVT_count O Display Error code
Remote control lock, Filter sign, Thermo ON/OFF,
18 nvoDeviceAlarm SNVT_state O
Error occurrence status display
19 nvoOccOpMode SNVT_switch O Cooling only/Heating only setup status display
20 nvoCoolTempLock SNVT_switch O Display low temperature limit setting status
21 nvoHeatTempLock SNVT_switch O Display high temperature limit setting status
22 nvoUserLockout SNVT_switch O Display the restriction of remote control use
23 nvoEnergyConp SNVT_elec_kwh_l O %JTQMBZFMFDUSJDJUZVTBHF 5JNF1FSJPE
[¥]UwGG ¥UGGGX\Z YWX[TW[TY\GGG㝘䟸G[aZ]aZ`
Control Systems
SSACIndoor[nn](objectid=1-128)
nvoSpaceTemp SNVT_temp_p
nviOnOff SNVT_switch nvoApplicMode SNVT_hvac_mode
nviApplicMode SNVT_hvac_mode nvoSetPoint SNVT_temp_p
nviSetPoint SNVT_temp_p nvoOnOff SNVT_switch
nviFanStatus SNVT_switch nvoFanStatus SNVT_switch
nviERVMode SNVT_count nvoERVMode SNVT_count
nviFilterReset SNVT_switch nvoErrorCode SNVT_count
nviUserLockout SNVT_switch nvoDeviceAlarm SNVT_state
nviOccOpMode SNVT_switch nvoOccOpMode SNVT_switch
nviCoolTempLock SNVT_switch nvoCoolTempLock SNVT_switch
nviHeatTempLock SNVT_switch nvoHeatTempLock SNVT_switch
nvoUserLockout SNVT_switch
nvoEnergyConp SNVT_elec_kwh_I
nvoEnergyCon SNVT_elec_kwh_I
nvoRuntimep SNVT_time_hour
nvoRuntime SNVT_time_hour
nvoDevListDesc SNVT_str_asc
SSACSystem(objectid=129)
nvoDigitalOut[6] SNVT_switch
nvoDMS2Alarm SNVT_count
nvoSystemAlarm SNVT_count
Configuration Properties
nciSndHrtBt
nciMinOutTm
nciMinDelta Temp
nciDelayStartup
154
[¥]UwGG ¥UGGGX\[ YWX[TW[TY\GGG㝘䟸G[aZ]aZ`
11) Network variable list
t Supported NV (Network Variable) is different depending on the connected devices.
155
[¥]UwGG ¥UGGGX\\ YWX[TW[TY\GGG㝘䟸G[aZ]aZ`
Control Systems
1-3. nvoSetpoint(13), nviSetpoint(3) 7When an indoor unit operation mode is FAN ONLY,
‘Auto’cannot be controlled by Fan speed.
Description Set Temperature
SNVT Type SNVT_temp_p: Signed Long, 2 bytes
$PPM¡$_¡$
1-6. nvoERVMode(16), nviERVMode(5)
Value and operation
)FBU¡$~¡$
Description ERV Operation Mode
7Invalid Value: Automatically set up as minimum or
maximum value. SNVT_count: Unsigned Long, 2
SNVT Type bytes
7When setting temperature, only an integer value is applied.
"VUP
156
[¥]UwGG ¥UGGGX\] YWX[TW[TY\GGG㝘䟸G[aZ]aZ`
1-8. nvoDeviceAlarm(18) 1-13. nvoEnergyCon(24)
1. Remote control restriction status Electric consumption value after
2. Filter alert status Description
Description baselin
3. Thermo On/Off status SNVT_elec_kwh_I: Signed Quad,
4. Error alert Status SNVT Type 4bytes
SNVT Type SNVT_state: 16 Unsigned Bitfields 3BXSBOHF_
Value and operation
Byte Bit9 Bit8 Operation Remark 3FTPMVUJPO
Unlock nvo
Flags
1 Level1 User
_1
1 Lock Lockout
1-14. nvoRunTimep(25)
Byte Bit value Operation Remark
Indoor unit usage within the
No alarm nvo Description
Value and operation period
2 Filter
1 Alarm SNVT_time_hour: Signed Long,
Alarm SNVT Type
Thermo Off Thermo 2bytes
Flags
1
_2 1 Thermo On On/Off Value and operation 3BXSBOHF_
No Error nvo
Error
1 Error
Code
1-15. nvoRunTime(26)
Description Indoor unit usage after baseline
1-9. nvoOccOpMode(19), nviOccOpModeCmd(8) SNVT_time_hour: Signed Long,
SNVT Type 2bytes
Description Operation Mode restriction
Value and operation 3BXSBOHF_
SNVT Type SNVT_switch: Unsigned/singed Short
Value State 7Energy consumption and Runtime are the accumulated value
Unlock during the user setting period.
Value and operation
Cool only 1 7The data above is for reference so you can not use them for
Heat only 1
official billing.
)FBU°C ~°C
1-15. nvoDevListDesc(27)
157
[¥]UwGG ¥UGGGX\^ YWX[TW[TY\GGG㝘䟸G[aZ]aZ`
Control Systems
(7
*GUIFWBMVFJTBOFHBUJWFOVNCFS
JUJTEJTQMBZFEBTTJHO
EJHJU
TJOHMFEJHJU
158
[¥]UwGG ¥UGGGX\_ YWX[TW[TY\GGG㝘䟸G[aZ]aZ`
(2) DMS System object
2-1. nvoDigitalOut(3), nviDigitalOut(1)
2-2. nvoDigitalIn(4)
2-3. nvoSystemLock(5)
2-4. nvoDMSAlarm(6)
Description DMS Alarm
SNVT Type SNVT_count : Unsigned Long, 2 bytes
/PSNBM
8 : Emergency stop
5SBDJOHJOQSPHSFTT
Value and operation
5SBDLJOHGBJMFE
-PO.PEVMF¥ DMS2 communication Error
0CKFDU*%6QEBUF
2-5. nvoSystemAlarm(7)
MANAGEMENT SYSTEM
2-6. nviAllOff(2)
Description All indoor units turn off
SNVT Type Enumeration, emerg_t
&.&3(@/03."-
Value and operation
4 : EMERG_SHUTDOWN
159
[¥]UwGG ¥UGGGX\` YWX[TW[TY\GGG㝘䟸G[aZ]aZ`
Control Systems
1) Features
t'PS#"$OFUQSPUPDPMTZTUFN4VQQPSU%.4DPOUSPMGVODUJPOBUUIFTBNFUJNF
2) Product specification
Source DC Adaptor
Power
Input 100~240VAC (±10%), 50/60Hz
supply
Output 12V 3A
Operating temperature
-10ºC ~ 50º C
range
Operating humidity range 10%RH ~ 90%RH
RS485 N
Maximum Digital Output N
length of
connection Digital Input N
160
[¥]UwGG ¥UGGGX]W YWX[TW[TY\GGG㝘䟸G[aZ]a[X
Compatible product
Outdoor unit AM7777X777777
0O0GGDPOUSPMMFS .$."%/
Controller 5PVDIDFOUSBMJ[FEDPOUSPMMFS .$."/
1*.JOUFSGBDFNPEVMF .*.#
.*.#/
7 Conventional communication outdoor unit requires compatible interface module (MIM-N01) to establish connection
7 MIM-B13D, MIM-B13E, MIM-B04A Interface modules cannot be connected.
7 To connect ERV, MIM-N10 interface module is required.
7 PIM connection is different depending on software version.
- Before 2.6.0.3 : MIM-B16 only
- 2.6.0.3 : MIM-B16N only
- After 2.6.1.7 : MIM-B16, MIM-B16N
3) Description of parts
(1) Front
① ② ③ ④ ⑤⑥ ⑦
161
[¥]UwGG ¥UGGGX]X YWX[TW[TY\GGG㝘䟸G[aZ]a[X
Control Systems
3) Description of parts
(3) Bottom
DI terminal 1 DI terminal 2 DO terminal 3 DO terminal 4 RS485 Communication terminal
Name Description
DI terminal 1 Digital Input connection terminal, Channel 1~Channel 5
SD card socket Sub memory (for program update and set information saving) socket
RS485 communication terminal RS485 port for communication with OnOff controller / interface module
162
[¥]UwGG ¥UGGGX]Y YWX[TW[TY\GGG㝘䟸G[aZ]a[X
4) Connection diagram
f MIM-B16(PIM) should be connected separately with outdoor units or controllers.
f MIM-B16N(PIM) can be connected with outdoor units or controllers to same channel of DMS2. BACnet
communication BMS
Samsung RS485
communication
For power distribution
1*. OnOff
BACnet GW
controller
1PXFSMJOF
R1-R2
F1-F2
R1-R2
F1-F2
Watt-hour meter
Electrical
substation
R1-R2 F1-F2
5) Wiring
(CH = Channel)
F1 F2 R1 R2 MANAGEMENT SYSTEM
F1 F2 R1 R2
BUILDING
; Note
BACnet GW can connect outdoor unit and OnOff controller/Touch centralized controller at the same time.
Outdoor unit and OnOff controller/Touch centralized controller can be connected to 1 communication channel at the same time.
163
[¥]UwGG ¥UGGGX]Z YWX[TW[TY\GGG㝘䟸G[aZ]a[Y
Control Systems
5) Wiring
BACnet GW
F1 F2
R1 R2
Outdoor unit
R1R2
R1R2
0 0 Outdoor unit
Outdoor unit
R1R2
R1R2
1 1 Outdoor unit
Maximum 16 Outdoor unit
connections
' '
Outdoor unit
Outdoor unit Ú Outdoor unit's address is defined automatically.
The address can be changed manually also.
BACnet GW
Maximum 15
OnOff controllers
Outdoor unit
R1R2
Outdoor unit
R1R2
Outdoor unit
164
[¥]UwGG ¥UGGGX][ YWX[TW[TY\GGG㝘䟸G[aZ]a[Z
Connecting with outdoor unit and OnOff controller
BACnet GW
R1R2
Maximum 16
outdoor units
1
Outdoor unit
R1R2
2
Outdoor unit
R1R2
3
Outdoor unit
Wiring distance
DMS-Bnet
ⓐ ⓑ ⓒ
ⓓ
Network radius
ⓔ
t%JTUBODFGSPNUIF#"$OFU(8UPUIFGVSUIFTUEFWJDFDBOOPUFYDFFEN
BUILDING
tⓒ + ⓓ + ⓔ d 1000m
ⓐ, ⓑ, ⓒ, ⓓ, ⓔ = 100m DMS-Bnet
ⓐ ⓑ ⓒ ⓓ ⓔ
HUB
Repeater
[¥]UwGG ¥UGGGX]\ YWX[TW[TY\GGG㝘䟸G[aZ]a[[
Control Systems
6) Description of device ID
DNET – Range CPP – Range INDOOR – Range
Item
[Digit 2] [Digit 3] [Digit 2]
OnOff Controller _ _ 64
1*. _ _ 64
_
Interface Module _ 64
(16 x 16)
Indoor Unit, ERV
_ _ _
AHU kit, EHS
Gateway _ 64
Ex) Device Instance Number (Gateway ID) Indoor unit main address
Indoor Unit
DNET (Gateway number) : 9
*OEPPS6OJU"EESFTT
9 417 32
Device ID: 941732
Y
OnOff controller address Interface module address
166
[¥]UwGG ¥UGGGX]] YWX[TW[TY\GGG㝘䟸G[aZ]a[[
7) Object list
(1) Indoor unit
Single indoor unit has following point list.
No Cool Heat
17 Operation mode limit status MV AC_Mode_Limit_xx_xxxxxx
Limit Only Only
Ú Temperature setting range can be different depending on the model and the common range is as follows :
"VUP$_$
$PPM$_$
)FBU$_$
'BO5FNQFSBUVSFDBOOPUCFBEKVTUFE
%SZ$_$
(7)
Mark is optionally supported.
167
[¥]UwGG ¥UGGGX]^ YWX[TW[TY\GGG㝘䟸G[aZ]a[[
Control Systems
7) Object list
(2) AHU kit
Single AHU unit has following point list.
[¥]UwGG ¥UGGGX]_ YWX[TW[TY\GGG㝘䟸G[aZ]a[\
(3) ERV
Single ERV unit has following point list.
MANAGEMENT SYSTEM
BUILDING
169
[¥]UwGG ¥UGGGX]` YWX[TW[TY\GGG㝘䟸G[aZ]a[\
Control Systems
7) Object list
(4) EHS
Unit Status value
Instance Object Object Object Name Inactive Active
Number Type
Text-1 Text-2 Text-3 Text-4
1 Room temperature AI EHS_RoomTemp_xx_xxxxxx °C
5 Setting lower temperature limit AV EHS_Cool_LimitTemp_xx_xxxxxx °C Use when displayed temperature type is set
to 'Room'.
6 Setting upper temperature limit AV EHS_Heat_LimitTemp_xx_xxxxxx °C Use when displayed temperature type is set
to 'Room'.
7 Lower temperature limit for water out AV EHS_WOCoolLimitTemp_xx_xxxxxx °C
Setting lower temperature limit BV EHS_Cool_LimitTemp_Set_xx_xxxxxx False True Use when displayed tempera-
ture type is set to 'Room'.
21 Setting upper temperature limit BV EHS_Heat_LimitTemp_Set_xx_xxxxxx False True Use when displayed tempera-
ture type is set to 'Room'.
22 Apply lower temperature limit for water BV EHS_WOCoolLimitFlag_xx_xxxxxx False True Use when displayed tempera-
out ture type is set to 'WaterOut'.
23 Apply upper temperature limit for water BV EHS_WOHeatLimitFlag_xx_xxxxxx False True Use when displayed tempera-
out ture type is set to 'WaterOut'.
24 Apply upper temperature limit for hot BV EHS_WTHeatLimitFlag_xx_xxxxxx False True
water
25 On/Off status of hot water mode BV &)4@)PU8BUFS@1PXFS@YY@YYYYYY Off On
28 Operation mode limit status MV EHS_Mode_Limit_xx_xxxxxx No Limit Cool Only Heat Only
Status of hot water operation mode MV EHS_HotWater_Mode_xx_xxxxxx * Force Eco Standard 1PXFS
170
[¥]UwGG ¥UGGGX^W YWX[TW[TY\GGG㝘䟸G[aZ]a[\
4*. 1*.
4JOHMF4*. 1*.
IBTGPMMPXJOHQPJOUMJTU
Instance Object
Object Object Name Status value
Number Type
1 SIM (PIM) error code AI SIM_Error_Code_xx_xx Refer to list of error code
When the error occurred, send event
2 SIM (PIM) Notify NC SIM_Notify_xx_xx
to list of destination in the recipient_list. (Max : 8)
(7)
Mark is optionally supported.
171
[¥]UwGG ¥UGGGX^X YWX[TW[TY\GGG㝘䟸G[aZ]a[\
Control Systems
7) Object list
(8) BACnet Gateway
BACnet Gateway has following point list.
f Caution
t You may use ALL_OFF command to turn on all the indoor units but it is not recommended.
t If communication error occurs on devices such as SIM/OnOff Controller/Interface Module etc, other functions such as
power distribution may also create a problem. You must have BMS system to check the errors and you must take action
immediately.
172
[¥]UwGG ¥UGGGX^Y YWX[TW[TY\GGG㝘䟸G[aZ]a[\
8) Checking BACnet communication through Wireshark
(1) Who-is (I-Am)
t"GUFSEFWJDFJOTUBODFOVNCFSTIBWFCFFOBVUPNBUJDBMMZBTTJHOFE
8IPJTDPNNBOEXIJDIJTSFRVFTUFEJOUIF8JSFTIBSLXJMMCF
replied by i-am from the devices.
(2) ReadPropertyMultiple
t3FRVFTUBMMTUBUVTEBUBT
t%FWJDFEFTDSJQUJPO
#"$OFUOFUXPSLOVNCFSEFWJDFOPEF*%
TUBUVT
#"$OFU."$BEESFTTWFSTJPO
.BY"1%6MFOHUI
BDDFQUFE
"1%6SFUSJFT
UJNFPVU
TVQQPSUFETFSWJDFT
TVQQPSUFEPCKFDUUZQFTBOETPPO
Continuum CyberStation
173
[¥]UwGG ¥UGGGX^Z YWX[TW[TY\GGG㝘䟸G[aZ]a[]
Control Systems
Request
Response
(4) WriteProperty
t$IBOHFUIF'BO4QFFEGSPN"VUPUP-PX
3FTQPOTFo3FBE1SPQFSUZ.VMUJQMF 'BO4QFFEA-PX
WriteProperty ReadPropertyMultiple
174
[¥]UwGG ¥UGGGX^[ YWX[TW[TY\GGG㝘䟸G[aZ]a[^
(5) Subscribe COV
Request
Response
Notification
MANAGEMENT SYSTEM
BUILDING
Response
175
[¥]UwGG ¥UGGGX^\ YWX[TW[TY\GGG㝘䟸G[aZ]a[_
Control Systems
Averaging
<1PXFS0OPGGDPOUSPM>
<4FUUJOHUIFGVDOUJPOPGMJNJUJOHMPXFSUFNQFSBUVSF>
<4FUUJOHUIFGVODUJPOPGMJNJUJOHVQQFSUFNQFSBUVF>
<41*TFUUJOH>
Binary Value
[HumanSensor setting], [Humidification setting], [Outdoor air intake setting],
[Ourdoor cooling setting]
Calendar
Command
[DMS], [A/C Indoor Unit], [ERV], [AHU], [SIM], [Centralized controller],
Device
[Interface module], [DDC]
Event Enrollment
File
Group
Life Safety Point
Life Safety Zone
Loop
Multi-state Input [Current humidity status]
Multi-state Output
[Operation mode control], [Fan speed control], [Air flow direction control],
Multi-state Value [Setting Cool only/ Heat only/ No Limit ], [Control Enable RC/ Disable RC /Level1],
[Set humidity status]
[AC Indoor Notify], [ERV Notify], [AHU Notify], [Centralized Controller Notify],
Notification Class
[Interface Module Notify], [SIM Notify], [Gateway Notify]
Program
Pulse Converter
Schedule
Trend Log
Access Door
Event Log
Load Control
Structured View
Trend Log Multiple
176
[¥]UwGG ¥UGGGX^] YWX[TW[TY\GGG㝘䟸G[aZ]a[_
10) Property support specification
(1) Device property
Check
Property identifier Property data Support DMS2
code
1 0CKFDUJEFOUJGJFS #"$OFU0CKFDU*EFOUJGJFS R V Individual identifier
SAMSUNG DVM
2 0CKFDUOBNF CharaterString R V
Gateway
3 0CKFDUUZQF #"$OFU0CKFDU5ZQF R V DEVICE
During communication:
i01&3"5*0/"-w
4 System status BACnetDeviceStatus R V
Error with DMS2:
i/0/@01&3"5*0/"-w
Samsung Electronics
5 Vendor name CharacterString R V
CO., Ltd.
6 Vendor identifier Unsigned16 R V
7 Model name CharterString R V MIM-B17N
8 Firmware revision CharterString R V
9 Application software version CharterString R V
10 Location CharterString O X
%.4@#"$OFU*1
11 Description CharterString O V
<WFS>
12 1SPUPDPMWFSTJPO Unsigned R V
13 1SPUPDPMDPOGPSNBODFDMBTT Unsigned(1..6) R X
14 1SPUPDPMTFSWJDFTTVQQPSUFE BACnetServicesSupported R V For each device
15 1SPUPDPMPCKFDUUZQFTTVQQPSUFE #"$OFU0CKFDU5ZQFT4VQQPSUFE R V For each device
16 0CKFDUMJTU BACnetidentifier BACnet sequence [N] R V For each device
17 .BY"1%6MFOHUIBDDFQUFE Unsigned R V 1476
18 Segmentation supported BACnetSegmentation R V NO-SEGMENTATION
(1)
19 VT classes supported BACnetVTClass O X
(1)
20 Active VT sessions BACnetVTSessions O X
21 Local time Time O V Supported
22 Local date Date O V Supported
23 UTC offset INTEGER O X
24 Daylight savings timeout BOOLEAN O X
MANAGEMENT SYSTEM
(2)
25 "1%6TFHNFOUUJNFPVU Unsigned O X
26 "1%6UJNFPVU Unsigned R V
BUILDING
27 /VNCFSPG"1%6SFUSJFT Unsigned R V 3
28 List of session keys BACnetSessionKey O X
(3)
29 Time synchronization recipients BACnetRecipient O X
(4)
30 Max master Unsigned(1..127) O V X
(4)
31 Max info frames Unsigned O V X
32 Device address binding BACnetAddressBinding R V X
33 1SPUPDPMSFWJTJPO Unsigned R V 2
177
[¥]UwGG ¥UGGGX^^ YWX[TW[TY\GGG㝘䟸G[aZ]a[_
Control Systems
2 0CKFDUOBNF CharaterString R V
3 0CKFDUUZQF #"$OFU0CKFDU5ZQF R V
4 1SFTFOUWBMVF REAL R(1) V
AI_Instance_device
5 Description CharacterString O V
address
6 Device type CharacterString O
Communication
Status_Flags FAULT flag
7 Status Flags BACnetStatusFlags R V
True OUT_OF_SERVICE
TRUE
8 Event state BACnetEventState R V General Error
Status_Flags FAULT flag
TRUE
FAULT if Reliability is not
NO_FALUT_DETECTED
9 Reliability BACnetReliability O V Communication error
COMMUNICATION_
FAILURE
General error
Unreliable_other
Communication error
10 Out of service BOOLEAN R V
TRUE
11 Update interval Unsigned O
12 Units BACnetEngineeringUnits R V
14 .BY1SFT7BMVF REAL O V
15 Resolution REAL O
178
[¥]UwGG ¥UGGGX^_ YWX[TW[TY\GGG㝘䟸G[aZ]a[_
(3) Analog output property
Check
Property identifier Property data Support DMS2
code
1 0CKFDUJEFOUJGJFS #"$OFU0CKFDU*EFOUJGJFS R V
2 0CKFDUOBNF CharaterString R V
3 0CKFDUUZQF #"$OFU0CKFDU5ZQF R V DEVICE
4 1SFTFOUWBMVF REAL W V
AI_Instance_device
5 Description CharacterString O V
address
6 Device type CharacterString O
Communication
Status_Flags FAULT flag
7 Status Flags BACnetStatusFlags R V
True OUT_OF_SERVICE
TRUE
8 Event state BACnetEventState R V General Error
Status_Flags FAULT flag
TRUE
FAULT if Reliability is not
NO_FALUT_DETECTED
9 Reliability BACnetReliability O V Communication error
COMMUNICATION_
FAILURE
General error
Unreliable_other
Communication error
10 Out of service BOOLEAN R V
TRUE
11 Units BACnetEngineeringUnits R V
13 .BY1SFT7BMVF REAL O V
14 Resolution REAL O
15 1SJPSJUZBSSBZ #"$OFU1SJPSJUZ"SSBZ R V
179
[¥]UwGG ¥UGGGX^` YWX[TW[TY\GGG㝘䟸G[aZ]a[`
Control Systems
2 0CKFDUOBNF CharaterString R V
3 0CKFDUUZQF #"$OFU0CKFDU5ZQF R V
4 1SFTFOUWBMVF #"$OFU#JOBSZ17 W V
AI_Instance_device
5 Description CharacterString O V
address
6 Device type CharacterString O
Communication
Status_Flags FAULT flag
7 Status Flags BACnetStatusFlags R V
True OUT_OF_SERVICE
TRUE
8 Event state BACnetEventState R V General Error
Status_Flags FAULT flag
TRUE
FAULT if Reliability is not
NO_FALUT_DETECTED
9 Reliability BACnetReliability O V Communication error
COMMUNICATION_
FAILURE
General error
Unreliable_other
Communication error
10 Out of service BOOLEAN R V
TRUE
11 1PMBSJUZ #"$OFU1PMBSJUZ R V
12 Inactive text CharacterString O(1) V New
13 Active text CharacterString O(1) V New
14 Change of state time BACnetDateTime O(2)
180
[¥]UwGG ¥UGGGX_W YWX[TW[TY\GGG㝘䟸G[aZ]a[`
(5) Binary output property
Check
Property identifier Property data Support DMS2
code
1 0CKFDUJEFOUJGJFS #"$OFU0CKFDU*EFOUJGJFS R V
2 0CKFDUOBNF CharaterString R V
3 0CKFDUUZQF #"$OFU0CKFDU5ZQF R V
4 1SFTFOUWBMVF #"$OFU#JOBSZ17 W V
AI_Instance_device
5 Description CharacterString O V
address
6 Device type CharacterString O
Communication
Status_Flags FAULT flag
7 Status Flags BACnetStatusFlags R V
True OUT_OF_SERVICE
TRUE
8 Event state BACnetEventState R V General Error
Status_Flags FAULT flag
TRUE
FAULT if Reliability is not
NO_FALUT_DETECTED
9 Reliability BACnetReliability O V Communication error
COMMUNICATION_
FAILURE
General error
Unreliable_other
Communication error
10 Out of service BOOLEAN R V
TRUE
11 1PMBSJUZ #"$OFU1PMBSJUZ R V
21 1SJPSJUZBSSBZ #"$OFU1SJPSJUZ"SSBZ R
MANAGEMENT SYSTEM
181
[¥]UwGG ¥UGGGX_X YWX[TW[TY\GGG㝘䟸G[aZ]a[`
Control Systems
2 0CKFDUOBNF CharaterString R V
3 0CKFDUUZQF #"$OFU0CKFDU5ZQF R V
4 1SFTFOUWBMVF Unsigned R(1) V
M_Instance_device
5 Description CharacterString O V
address
6 Device type CharacterString O
Communication
Status_Flags FAULT flag
7 Status Flags BACnetStatusFlags R V
True OUT_OF_SERVICE
TRUE
8 Event state BACnetEventState R V General Error
Status_Flags FAULT flag
TRUE
FAULT if Reliability is not
NO_FALUT_DETECTED
9 Reliability BACnetReliability O V Communication error
COMMUNICATION_
FAILURE
General error
Unreliable_other
Communication error
10 Out of service BOOLEAN R V
TRUE
11 Number of states Unsigned R V
BACnet sequence of
12 State text O V
characterString
13 Time delay Unsigned O(2)
182
[¥]UwGG ¥UGGGX_Y YWX[TW[TY\GGG㝘䟸G[aZ]a[`
(7) Multi-state output property
Check
Property identifier Property data Support DMS2
code
1 0CKFDUJEFOUJGJFS #"$OFU0CKFDU*EFOUJGJFS R V
2 0CKFDUOBNF CharaterString R V
3 0CKFDUUZQF #"$OFU0CKFDU5ZQF R V
4 1SFTFOUWBMVF Unsigned R(1) V
M_Instance_device
5 Description CharacterString O V
address
6 Device type CharacterString O
Communication
Status_Flags FAULT flag
7 Status Flags BACnetStatusFlags R V
True OUT_OF_SERVICE
TRUE
8 Event state BACnetEventState R V General Error
Status_Flags FAULT flag
TRUE
FAULT if Reliability is not
NO_FALUT_DETECTED
9 Reliability BACnetReliability O V Communication error
COMMUNICATION_
FAILURE
General error
Unreliable_other
Communication error
10 Out of service BOOLEAN R V
TRUE
11 Number of states Unsigned R V
BACnet arrangement of
12 State text O V
CharacterString
13 Time delay Unsigned O(2)
183
[¥]UwGG ¥UGGGX_Z YWX[TW[TY\GGG㝘䟸G[aZ]a[`
DVM CONTROL
SYSTEMS
184
[¥]UwGG ¥UGGGX_[ YWX[TW[TY\GGG㝘䟸G[aZ]a[`
VII. Test run tool for system
air contioner installation
1 S-checker. . . . . . . . . . . . . . . . . . . . . . . . . 186
2 S converter . . . . . . . . . . . . . . . . . . . . . . . . 194
185
[¥]UwGG ¥UGGGX_\ YWX[TW[TY\GGG㝘䟸G[aZ]a[`
Control Systems
1) Features
(Unit:mm)
96.00 36.60
RESET
OFF/ON
POWER
REPORT
124.00
TEMP.1
EEV2
TEMP.2
EEV1
PRESSURE
2) Product specification
Power supply 7_7"$
)[
Power consumption #FMPX8
Operating temperature range ¡$_¡$
Operating humidity range 3)_3)
RS485 1PSU2hUZ 1
Communication
Wi-Fi Supportablity Supported
Maximum RS485 m
N
number of
Indoor unit EA 64
controllable
devices Outdoor unit EA 1
>4VQQPSUFETQFDJGJDBUJPOPGUIFNPCJMFBQQMJDBUJPO3FTPMVUJPOPWFS9
PQUJNJ[FEBU9
- OS : Android 2.3~4.12
Compatible product
Outdoor unit AM7777X777777Model
Indoor unit AM7777N777777Model
186
[¥]UwGG ¥UGGGX_] YWX[TW[TY\GGG㝘䟸G[aZ]a\W
3) Description of parts ⑬ LINK S-NET
Micro-SD
⑯
⑭ ⑮
⑧ ⑨
⑦ ⑩
RESET
Live Wi-Fi 485 Error
DOWNLOAD
⑰
OFF/ON
②
POWER
⑪
REPORT
③
④
TEMP.1
⑱
EEV2
TEMP.2
⑫ ⑤
⑲
EEV1
PRESSURE
⑥
DC JACK DC 12 V RS-485
$POOFDUPSGPSUFNQFSBUVSFTFOTPSUIBUJTDPOOFDUFEUPQJUDIQJODPOOFDUPS
Temperature sensor inpsection
⑤ Temperature value can be checked from the S-checker by connecting the temperature sensor
connector 2
directly
Pressure sensor inspection Connector for connecting high/low pressure sensor of the outdoor unit.
⑥
connector (4 pin) 1SFTTVSFWBMVFDBOCFDIFDLFEGSPNUIF4DIFDLFSCZDPOOFDUJOHUIFUFNQFSBUVSFTFOTPSEJSFDUMZ
⑦ System operation status LED Turns on when the S-Checker is operating normally.
⑧ Wi-Fi connection LED Turns on when the data is being tranmitted to mobile through Wi-Fi
⑨ RS-485 operation status LED Turns on when data is transmitted and received through RS-485 communication
⑩ System Error LED Turns on when error occurs on S-checker.
⑪ LCD display Check the current information and the items in menu that can be selected by menu buttons.
⑫ Menu buttons Use to move and select from menu.
⑬ USB for S-Net Pro 2 .JOJ64#GPSDPOOFDUJOHXJUI4/&51SP
⑭ USB for system Use to download program etc.
⑮ IR tranceiver Use to transmit IR.
⑯ Micro SD slot Slot to insert Micro SD card.
⑰ PBA download connector 6TFUPEPXOMPBE4DIFDLFSUISPVHI1$
EEV inspection connector 1 (5
⑱ $IFDLGPSFSSPSPO&&7TFOTPS
$".5ZQF 1JO
Pin)
EEV inspection connector 2 (6
AIR CONDITIONER INSTALLATION
5&4536/500-'034:45&.
Pin)
⑳ DC 12 V adapter Use to connect independent 12 V power.
187
[¥]UwGG ¥UGGGX_^ YWX[TW[TY\GGG㝘䟸G[aZ]a\W
Control Systems
4) Connection diagram
F1/F2
Outdoor unit
(New communication)
4NBSU1IPOF
5BCMFU1$
SD Card
micro SD S-checker
Indoor unit Indoor unit
USB cable
/PUF1$
4/&51SP
5) Connecting
Outdoor unit
F1 F2 R1 R2
S-checker
DC JACK DC 12 V RS-485
No polarity
LINK S-NET
Micro-SD
188
[¥]UwGG ¥UGGGX__ YWX[TW[TY\GGG㝘䟸G[aZ]a\W
Connecting with mobile device
F1/F2
Outdoor unit
(New communication)
S-checker
4NBSU1IPOF
Indoor unit Indoor unit
189
[¥]UwGG ¥UGGGX_` YWX[TW[TY\GGG㝘䟸G[aZ]a\X
Control Systems
6) Main function
tCycle Info : it displays cycle data of the indoor and outdoor unit.
%JTQMBZFEJUFNJTTBNFBT4/&51SP
190
[¥]UwGG ¥UGGGX`W YWX[TW[TY\GGG㝘䟸G[aZ]a\X
Install monitoring
tIt displays the installation information of the outdoor unit and indoor unit.
Full Open
maximum value
191
[¥]UwGG ¥UGGGX`X YWX[TW[TY\GGG㝘䟸G[aZ]a\Y
Control Systems
6) Main function
t Through Comm. Check menu, communication status between indoor/outdoor unit can be checked.
t Indoor unit can be connected to S-checker alone without outdoor unit, to check the communication status of indoor unit.
t You can check the option code of indoor unit from the S-checker.
t Option code setting can be applied to multiple numbers of indoor unit at once.
192
[¥]UwGG ¥UGGGX`Y YWX[TW[TY\GGG㝘䟸G[aZ]a\Y
Other functions
t A/C S/W Upgrade: Firmware for indoor and outdoor unit of system air conditioner can be upgraded.
t Unit control: This function restricts general operation if auto trial operation is incompleted.
t Refrigerant check: This is a detect function according to piping option which calculates the amount of refrigerant to see if it's adequate.
193
[¥]UwGG ¥UGGGX`Z YWX[TW[TY\GGG㝘䟸G[aZ]a\Y
Control Systems
1) Features
t$PNNVOJDBUJPODPOWFSUJOHNPEVMFUPDPOOFDU4BNTVOHTZTUFNBJSDPOEJUJPOFSUPB1$
t Main purpose for use
- To coonect with test run program
28.00 (Unit:mm)
66.50
22.00
55.30
13.00
92.00
80.30
92.00
2) Product specification
Power supply %$7
CFMPXN"
Power consumption Below 3 W
Operating temperature range ¡$_¡$
Operating humidity range 3)_3)
Communication RS485 1PSU2hUZ 1
Maximum
length of RS485 m N
connection
194
[¥]UwGG ¥UGGGX`[ YWX[TW[TY\GGG㝘䟸G[aZ]a\Y
3) Description of parts
③ ⑤
②
④
①
⑨ ⑩
⑦
⑥
⑤ ⑧
4) Connection diagram
AIR CONDITIONER INSTALLATION
5&4536/500-'034:45&.
F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2
195
[¥]UwGG ¥UGGGX`\ YWX[TW[TY\GGG㝘䟸G[aZ]a\Z
Control Systems
5) Connecting
F1 F2 R1 R2
Connecting with PC
6) Display
(1) POWER LED
t When connected to Conventional communication outdoor unit - LED blinks
t When connected to new communication outdoor unit - LED is on
[¥]UwGG ¥UGGGX`] YWX[TW[TY\GGG㝘䟸G[aZ]a\[
MEMO
197
[¥]UwGG ¥UGGGX`^ YWX[TW[TY\GGG㝘䟸G[aZ]a\[