DVM Technical Data Book - Control Systems

Control Systems

2014.04
DBEU-14042B(A)

SAMSUNG ELECTRONICS Co., LTD.


416 Maetan-3Dong, Yeongtong-Gu, Suwon City Gyeonggi-Do, Korea 443-742
Internet Website : www.dvmsystem.com Email : Airconditioner@samsung.com

Specifications may be subject to change without prior notice for product improvement.
I. Individual Control Systems II. Centralized control systems
1 Receiver & display unit 1 Interface module
MRK-A10N 1. MIM-N01
1) Features . . . . . . . . . . . . . . . . . . . . . 10 1) Features . . . . . . . . . . . . . . . . . . . . . 44
2) Wiring. . . . . . . . . . . . . . . . . . . . . . . 10 2) Product specification . . . . . . . . . . . 44
3) Description of parts . . . . . . . . . . . . 45
2 Wireless remote controller 4) Connection diagram . . . . . . . . . . . . 46
MR-DH00 5) Connection. . . . . . . . . . . . . . . . . . . 47
1) Features . . . . . . . . . . . . . . . . . . . . . 10 5) Display . . . . . . . . . . . . . . . . . . . . . . 48
2) Description of parts . . . . . . . . . . . . 11
3) Additional function . . . . . . . . . . . . . 12 2 ERV interface module
MIM-N10
3 Wired remote controller 1) Features . . . . . . . . . . . . . . . . . . . . . 49
1. MWR-WE10N 2) Product specification . . . . . . . . . . . 49
1) Features . . . . . . . . . . . . . . . . . . . . . 13 3) Description of parts . . . . . . . . . . . . 51
2) Product specification . . . . . . . . . . . 13 4) Connection diagram . . . . . . . . . . . . 52
3) Description of parts . . . . . . . . . . . . 14 5) Connection. . . . . . . . . . . . . . . . . . . 53
4) Optional function . . . . . . . . . . . . . . 16 6) Checking the operation . . . . . . . . . 54
5) Display . . . . . . . . . . . . . . . . . . . . . . 23
6) Communication diagram . . . . . . . . 25 3 OnOff controller
2. MWR-SH00N MCM-A202DN
1) Features . . . . . . . . . . . . . . . . . . . . . 27 1) Features . . . . . . . . . . . . . . . . . . . . . 55
2) Product specification . . . . . . . . . . . 27 2) Product specification . . . . . . . . . . . 55
3) Description of parts . . . . . . . . . . . . 28 3) Description of parts . . . . . . . . . . . . 56
4) Optional function . . . . . . . . . . . . . . 30 4) Optional function . . . . . . . . . . . . . . 57
5) Display . . . . . . . . . . . . . . . . . . . . . . 32 5) Connection diagram . . . . . . . . . . . . 58
6) Communication diagram . . . . . . . . 33 6) Display . . . . . . . . . . . . . . . . . . . . . . 61

4 ERV wired remote controller 4 Touch centralized controller


MWR-VH12N MCM-A300N
1) Features . . . . . . . . . . . . . . . . . . . . . 35 1) Features . . . . . . . . . . . . . . . . . . . . . 62
2) Product specification . . . . . . . . . . . 35 2) Product specification . . . . . . . . . . . 62
3) Description of parts . . . . . . . . . . . . 36 3) Description of parts . . . . . . . . . . . . 63
4) Option function. . . . . . . . . . . . . . . . 37 4) Connection diagram . . . . . . . . . . . . 64
5) Display . . . . . . . . . . . . . . . . . . . . . . 40 5) Connection. . . . . . . . . . . . . . . . . . . 65
6) Connection diagram . . . . . . . . . . . . 41 6) Main function . . . . . . . . . . . . . . . . . 67
2
IV. Power distribution system

CONTROL SYSTEM
INDIVIDUAL
5 Operation mode selection switch 1 Electricity meter interface module
MCM-C200 MIM-B16N
1) Features . . . . . . . . . . . . . . . . . . . . . 73 1) Features . . . . . . . . . . . . . . . . . . . . 128

CONTROL SYSTEM
CENTRALIZED
2) Installation . . . . . . . . . . . . . . . . . . . 73 2) Display and buttons . . . . . . . . . . . 128
3) Control example . . . . . . . . . . . . . . . 74 3) Connectors . . . . . . . . . . . . . . . . . 129
4) Address & option switches . . . . . . 129
5) Specifications on electricity meter. . 130
6) Installation . . . . . . . . . . . . . . . . . . 131
III. Integrated management

MANAGEMENT SYSTEM CISTRIBUTION SYSTEM


7) Wiring. . . . . . . . . . . . . . . . . . . . . . 132

INTEGRATED
8) Address assignment. . . . . . . . . . . 133
systems 9) MIM-B16N menu structure. . . . . . 133
10) Setting parameters on DMS2 (MIM-D00AN ) 136
11) Error codes. . . . . . . . . . . . . . . . . 136
1 DMS2
MIM-D00AN

POWER
1) Features . . . . . . . . . . . . . . . . . . . . . 76
2) Product specification . . . . . . . . . . . 76
3) Description of parts . . . . . . . . . . . . 77
4) Connection diagram . . . . . . . . . . . . 79
V. External control system
5) Wiring. . . . . . . . . . . . . . . . . . . . . . . 79
CONTROL SYSTEM
6) Function . . . . . . . . . . . . . . . . . . . . . 82 1 External contact interface module
MIM-B14 EXTERNAL
2 S-NET3 1) Features . . . . . . . . . . . . . . . . . . . . 138
2) Description of parts . . . . . . . . . . . 138
MST-P3P
3) Installation . . . . . . . . . . . . . . . . . . 138
1) Features . . . . . . . . . . . . . . . . . . . . 111
MANAGEMENT SYSTEM AIR CONDITIONER INSTALLATION

4) Control . . . . . . . . . . . . . . . . . . . . . 139
2) PC specification . . . . . . . . . . . . . . 111
BUILDING

3) System connection. . . . . . . . . . . . 111


4) Function . . . . . . . . . . . . . . . . . . . . 112 2 MTFC (Multi Tenant Function Controller)
5) Detail function description . . . . . . 113 MCM-C210N
1) Features . . . . . . . . . . . . . . . . . . . . 142
2) Product specification . . . . . . . . . . 142
TEST RUN TOOL FOR SYSTEM

3) Description of parts . . . . . . . . . . . 142


4) Connection diagram . . . . . . . . . . . 143
5) Connecting. . . . . . . . . . . . . . . . . . 143
6) Main function . . . . . . . . . . . . . . . . 144

3
VI. Building management systems VII. Test run tool for system
air conditioner installation
1 DMS L-net(Lonworks GW)
MIM-B18N 1 S-checker
1) Features . . . . . . . . . . . . . . . . . . . . 146
2) Product specification . . . . . . . . . . 146 MIM-C10N
3) Description of parts . . . . . . . . . . . 147 1) Features . . . . . . . . . . . . . . . . . . . . 186
4) Connection diagram . . . . . . . . . . . 149 2) Product specification . . . . . . . . . . 186
5) Wiring. . . . . . . . . . . . . . . . . . . . . . 149 3) Description of parts . . . . . . . . . . . 187
6) Commission . . . . . . . . . . . . . . . . . 152 4) Connection diagram . . . . . . . . . . . 188
7) Standard program identifier (SPID) . . 152 5) Connection. . . . . . . . . . . . . . . . . . 188
8) Item summary . . . . . . . . . . . . . . . 152 6) Main function . . . . . . . . . . . . . . . . 190
9) Network variable . . . . . . . . . . . . . 153
10) Network parameter chart . . . . . . . . 154
11) Network variable list. . . . . . . . . . . . . .155
2 S-converter
12) Detail description of network variable . . 156 MIM-C02N
1) Features . . . . . . . . . . . . . . . . . . . . 194
2 DMS B-net(BACnet GW) 2) Product specification . . . . . . . . . . 194
MIM-B17N 3) Description of parts . . . . . . . . . . . 195
1) Features . . . . . . . . . . . . . . . . . . . . 160 4) Connection diagram . . . . . . . . . . . 195
2) Product specification . . . . . . . . . . 160 5) Connection. . . . . . . . . . . . . . . . . . 196
3) Description of parts . . . . . . . . . . . 161 6) Display . . . . . . . . . . . . . . . . . . . . . 196
4) Connection diagram . . . . . . . . . . . 163
5) Wiring. . . . . . . . . . . . . . . . . . . . . . 163
6) Description of device ID . . . . . . . . 166
7) Object list . . . . . . . . . . . . . . . . . . . 167
8) Checking BACnet communication
through Wireshark . . . . . . . . . . . . 173
9) Standard object type . . . . . . . . . . . . 176
10) Property support specification . . . . . 177

4
Overview of DVM S
New communication system diargram
DMS B-net DMS L-net
(MIM-B17N) (MIM-B18N)
DMS-Bnet DMS-Lnet
S-NET3 (MST-P3P)

Lon
ACK SVC
Ethernet

DMS2
(MIM-D00AN)

Control layer Set layer

Max.16 outdoor units Max. 80 units


Max.15 Contollers Max. 128 indoor units (Includes ERV, MCU) (Max. 64 Indoor units, Max 16 MCU, Max.16 ERV) Max.16 Controllers

F1F2

R1R2 R1R2 Indoor units


CH1 Outdoor units F3F4
Wired RC
(MWR-WE10N)
(MWR-SH00N)

Local layer Max.2 Wired RC


Max.16 indoor units
CH2
Outdoor units

t4FU-BZFS ''
$PNNVOJDBUJPODIBOOFMPG0VUEPPS .BJO
VOJU 
CH3 *OEPPSVOJUBOE4FUMBZFSDPOUSPMMFS
Outdoor units
- Set layer controller : OnOff controller (MCM-A202DN),
Touch centralized controller (MCM-A300N)
t$POUSPM-BZFS 33
$PNNVOJDBUJPODIBOOFMPG0VUEPPS .BJO

VOJUBOE$POUSPMMBZFSDPOUSPMMFS
CH4 - Control layer controller : OnOff controller (MCM-A202DN),
Outdoor units Touch centralized controller (MCM-A300N),
DMS2 (MIM-D00AN), BACnet Gw (MIM-B17N),
LonWorks GW (MIM-B18N)
PIM
Max. 8 PIMs t-PDBM-BZFS ''
$PNNVOJDBUJPOCFUXFFOJOEPPSVOJUBOE
CH5 Wired remote controller

PIM (MIM-B16N)

t$BTF8IFO%7.4JTDPOOFDUFEUPDPOWFOUJPOBMTZTUFN t$BTF8IFO%7. JTDPOOFDUFEUPOFXTZTUFN

S-NET3 (MST-P3P) S-NET3 (MST-P3P)

DMS2
(MIM-D00A)

DMS2 OnOff controller


(MIM-D00AN) (MCM-A202DN)
OnOff controller MIM-N00 MIM-N01
(MCM-A202D)
MIM-N01
Interface module
(MIM-B13E)

%7.  DVM S DVM S %7. 

Conventional New communication New communication Conventional


communication system System System communication system
5
Compatibility table (New ¥ Conventional)

Conventional communication
Conventional communication Controller
SAC
Product DMS2
Interface OnOff
Outdoor unit Indoor unit (BACnet GW/ S-NET mini
module Controller
LonWorks GW)
Wired remote controller (MWR-WE10N)
Interface module I (MIM-N00) 7 O O O
Interface module II (MIM-N01) O O O O
Interface module III (MIM-N10) 7 O O O
New communication controller

OnOff Controller (MCM-A202DN)


DMS2 (MIM-D00AN)
BACnet GW (MIM-B17N)
LonWorks GW (MIM-B18N)
PIM (MIM-B16N) 7
S-NET 3 (MST-S3P,D3P,P3P) O
Touch centralized controller (MCM-A300N)
External contact interface module (MIM-B14) O
Receiver & display unit (MRK-A10N)
Wireless remote controller (MR-DH(C)00) O
MTFC (MCM-C210N)
S-Converter (MIM-C02N) O
Operation mode selection switch (MCM-C200) O

New communication SAC New communication Controller


Product DMS2
OnOff
Outdoor unit Indoor unit MIM-N00 MIM-N01 (BACnet GW/
Controller
LonWorks GW)
Wired remote controller (MWR-WE10N) O
Interface module I (MIM-N00) 7 O
Interface module II (MIM-N01) O O O
New communication controller

Interface module III (MIM-N10) 7 O O


OnOff Controller (MCM-A202DN) O O O O O
DMS2 (MIM-D00AN) O O O
BACnet GW (MIM-B17N) O O O
LonWorks GW (MIM-B18N) O O O
PIM (MIM-B16N) 7 O
S-NET 3 (MST-S3P,D3P,P3P) O
Touch centralized controller (MCM-A300N) O O O O O
External contact interface module (MIM-B14) O
Receiver & display unit (MRK-A10N) O
Wireless remote controller (MR-DH(C)00) O
MTFC (MCM-C210N) O
S-Converter (MIM-C02N) O
Operation mode selection switch (MCM-C200) O

7.*./XJMMCFJOUFHSBUFEUP.*./BUUIFFOEPG
7 MIM-N10 is only for ERV.

6
Conventional communication
Conventional communication Controller
SAC
Product DMS2
Interface OnOff
Outdoor unit Indoor unit (BACnet GW/ S-NET mini
module Controller
LonWorks GW)
Wired remote controller (MWR-WE10) O
Conventional communication controller

Interface module (MIM-B13D,E) O O O O


OnOff controller (MCM-A202D) O O O
Function controller (MCM-A100) O
DMS2 (MIM-D00A) O O O
BACnet GW (MIM-B17) O O
LonWorks GW (MIM-B18) O O
PIM (MIM-B16) O
S-NET 3 (MST-S3P,D3P,P3P) O
S-NET mini (MST-S3W) O O O
External contact interface module (MIM-B14) O
Receiver & display unit (MRK-A01) O
Wireless remote controller (MR-DH(C)00) O
Converter (MIM-C02) O
Operation mode selection switch (MCM-C200) O

New communication SAC New communication Controller


Product DMS2
OnOff
Outdoor unit Indoor unit MIM-N00 MIM-N01 (BACnet GW/
Controller
LonWorks GW)
Wired remote controller (MWR-WE10)
Conventional communication controller

Interface module (MIM-B13D,E)


OnOff controller (MCM-A202D) O O
Function controller (MCM-A100)
DMS2 (MIM-D00A) O O
BACnet GW (MIM-B17) O O
LonWorks GW (MIM-B18) O O
PIM (MIM-B16) V
S-NET 3 (MST-S3P,D3P,P3P) O
S-NET mini (MST-S3W) O O
External contact interface module (MIM-B14) O
Receiver & display unit (MRK-A01)
Wireless remote controller (MR-DH(C)00) O
Converter (MIM-C02)
Operation mode selection switch (MCM-C200) O

7
DVM CONTROL
SYSTEMS

8
I. Individual Control Systems

CONTROL SYSTEMS
INDIVIDUAL
1 Receiver & Display unit . . . . . . . . . . . . . . . 10
2 Wireless remote controller . . . . . . . . . . . . 10
3 Wired remote controller . . . . . . . . . . . . . . 13
4 ERV wired remote controller. . . . . . . . . . . 35

9
Control Systems

I Individual control systems


1. Receiver & Display unit
MRK-A10N
1) Features
Receiver wire
80 (Unit : mm)
24

130
4

Receiver & Display Unit t0QFSBUJPO5JNFSTFUUJOHEJTQMBZ


t$PODFBMFEXJSFMFTTTJHOBMSFDFJWFS t0QFSBUJPO0O0GGCVUUPO
t'JMUFSSFQMBDFNFOUTJHO t0QFSBUJPO0OEJTQMBZ-&% CMVF

t'BOPQFSBUJPOEJTQMBZ t%FGSPTUPQFSBUJPOEJTQMBZ-&% SFE


8JSJOH
t$POOFDUPOFFOEPGUIFSFDFJWFSXJSFXJUIUIF3FDFJWFS%JTQMBZVOJU1$#
t$POOFDUUIFPUIFSFOEPGUIFSFDFJWFSXJSFXJUIUIFEVDUUZQFJOEPPSVOJU1$#

Indoor unit PCB

Connector : 13Pin

Receiver & Display unit PCB

; Note
Š Wire length: 10m
Š Receiver & Display unit is only available for a duct type indoor unit.

2. Wireless remote controller


MR-DH00
1) Features
49
(Unit : mm)
29

Easy and convenient operation control


t0QFSBUJPO0/0''DPOUSPM
t'BOTQFFEDPOUSPM
138

t0QFSBUJPOUFNQFSBUVSFTFUUJOH
t'JMUFSSFQMBDFNFOUBMBSNSFTFU
t"JSTXJOHDPOUSPM
t4JNQMF0O0GGUJNFS
t*OEPPSVOJUPQUJPODPEFTFUUJOH

10
2) Description of parts


CONTROL SYSTEMS
② ⑨

INDIVIDUAL

⑩ ⑪
④ ⑫


⑥ TX ⑭
⑥ TY ⑬ TX
⑦ ⑬ TY


Ï ②, ⑥-1, ⑥-2, ⑧, ⑬-2, ⑳, is only supported and available in certain indoor units.

No Name Description
① 0O0GGCVUUPO 1SFTTUIJTCVUUPOUPUVSOPOPGGUIFJOEPPSVOJU
② 41MBTNBJPOCVUUPO 1SFTTUIJTCVUUPOUPUVSOPOPGGUIF41MBTNBJPO
③ 5VSCPCVUUPO Press this button to cool your room quickly and powerfully.
④ 5FNQ CVUUPO 1SFTTUIJTCVUUPOUPJODSFBTFEFDSFBTFUIFTFUUFNQFSBUVSFCZ¡$
)PSJ[POUBMBJSTXJOH
⑤ 1SFTTUIJTCVUUPOUPBDUJWBUFEFBDUJWBUFIPSJ[POUBMBJSGMPXNPWFNFOU
CVUUPO
⑥-1 #FFQ0GGCVUUPO Press this button to mute the beep sounds that occurs when pressing the button.
Press the 2nF function button and press this button to control individual indoor unit or all indoor
⑥-2 3PPNCVUUPO
units at once.
⑦ 0OUJNFSCVUUPO 1SFTTUIFCVUUPOUPTFUUIF0O5JNFSPO
⑧ OE'CVUUPO Press this button to select the function printed under the button. (Room, Blade function)
⑨ .PEFCVUUPO Press this button to select one of the 5 operation modes. (Auto, Cool, Dry, Fan, Heat)
⑩ 2VJFUCVUUPO Press this button to select quiet mode.
1SFTTUIJTCVUUPOUPBDUJWBUFEFBDUJWBUFWFSUJDBMBJSGMPXNPWFNFOU /PUBQQMJDBCMFUP%VDUUZQF
⑪ 7FSUJDBMBJSTXJOHCVUUPO
model)
⑫ FannnnnnCVUUPO 1SFTTUIJTCVUUPOUPTFMFDUPOFPGUIFGBOTQFFET "VUP -PX .FEJVNBOE)JHI

>
>

⑬-1 'JMUFS3FTFUCVUUPO Press this button to turn off the filter indicator light.
Press the 2nF function button and press this button to control individual blade unit or all blades
⑬-2 #MBEFCVUUPO
at once.
⑭ HPPEhTMFFQCVUUPO Press this button to set the good’sleep mode on.
⑮ 4FU$BODFMCVUUPO 1SFTTUIJTCVUUPOUPTFUPSDBODFMUIF0O0GG5JNFSBOEHPPETMFFQNPEF
⑯ 0GG5JNFSCVUUPO 1SFTTUIJTCVUUPOUPTFUUIF0GG5JNFSPO
⑰ Operation mode indicator Indicates the operation mode.
Set temperature & On/Off Basic – Indicates the set temperature.

set time indicator 5JNFSTFUUJOHo*OEJDBUFTUIF0O0GGTFUUJNF
⑲ On/Off timer indicator *OEJDBUFTUIF0O0GGUJNFSTFUUJOH

8IFO<#FFQPGG3PPN>CVUUPOJTQSFTTFEBGUFSQSFTTJOHUIFO'CVUUPO i3PPNwJOEJDBUPS
Room & Blade selection will be displayed with the selected indoor unit number.

indicator 
8IFO<'JMUFS3FTFU#MBEF>CVUUPOJTQSFTTFEBGUFSQSFTTJOHUIFO'CVUUPO i#MBEFwJOEJDBUPS
will be displayed with the selected blade number.
Transmission indicator Indicates when wireless signal is received (by pressing any buttons).
*OEJDBUFTXIFOO'CVUUPOJTQSFTTFE:PVDBOTFMFDUUIFTFDPOEGVODUJPO 4FMFDUJOH3PPN
2ndF indicator
Blade)
-PXCBUUFSZJOEJDBUPS Indicates the battery life.
"JSTXJOHJOEJDBUPS *OEJDBUFTXIFOWFSUJDBMPSIPSJ[POUBMBJSGMPXNPWFNFOU
Fan speed indicator Indicates the fan speed settings.
11
Control Systems

I Individual control systems


2. Wireless remote controller
MR-DH00
3) Additional function
 
0QUJPODPEFTFUUJOH
❶ Remove the batteries from the remote controller.
❷1SFTTUIF5FNQ< >BOE<>CVUUPOBUUIFTBNFUJNFBOEJOTFSUUIFCBUUFSJFT
❸ Set the 2 digits of option code.
*GZPVQSFTTUIF'BO<>CVUUPO ZPVDBODIBOHFUIFSJHIUEJHJU
>

*GZPVQSFTTUIF'BO<>CVUUPO ZPVDBODIBOHFUIFMFGUEJHJU
>

❹1SFTTUIF<.PEF>CVUUPOUPTFUUIFOFYUEJHJUTPGPQUJPODPEF
Input 20 digits in total.
❺ Press the button more than twice to set the indoor unit option code.
 8IFOJOEPPSVOJUPQUJPODPEFJTTFU BCFFQXJMMTPVOE8IFOUIFTFUUJOHJTJODPSSFDU BMMUIF-&%POUIFJOEPPSVOJUQBOFMXJMMGMJDLFS

Ú0QUJPODPEFJTDPNQPTFEXJUIUPUBMPGEJHJUTJODMVEJOHQBHFOVNCFS Setting Ex.) Option code: 012345 – 16789A – 212345 – 36789A
From the wireless remote controller, enter the option code without
QBHFOVNCFS    
Page 0 Page 1 Page 2 Page 3

¨ ¨ ¨ ¨
Option code input mode 'BO<>o3JHIUEJHJU 1SFTTUIF<.PEF>CVUUPO
ª
>

'BO<>o-FGUEJHJU to set the next 2 digits.


>

§ § § §
*GZPVQSFTTUIF<.PEF>CVUUPOBGUFSFOUFSJOHGJSTU
ª 10 digits, On timer indicator will change to Off.

¨ 1SFTTUIF<1PXFS>CVUUPONPSFUIBOUXPUJNFT
towards the indoor unit.

12
3. Wired remote controller
MWR-WE10N

1) Features
(Unit : mm)
120.0 19.5

CONTROL SYSTEMS
INDIVIDUAL
124.0

63.8
(1) Air conditioner / ERV control
t"$PQFSBUJPO0/0''DPOUSPM
t"$PQFSBUJPONPEF TFUUJOHUFNQFSBUVSF GBOTQFFE BJSGMPXEJSFDUJPOTFUUJOH
t"$JOEJWJEVBMCMBEFDPOUSPMBOEPDDVQBODZEFUFDUJPO
(Function is available when indoor units support any of above functions)
t&37PQFSBUJPO0/0''DPOUSPM
t&37PQFSBUJPONPEF GBOTQFFETFUUJOH
t"$&37FSSPSNPOJUPSJOH
t'JMUFSDMFBOJOHBMFSUBOESFTFUBMFSUUJNF
t*OEJWJEVBMHSPVQDPOUSPM JOEPPSVOJU&37JOUFSMPDLJOHDPOUSPM
t&OFSHZTBWJOHDPOUSPM
t$POUSPMNBYJNVN*OEPPSVOJU &37JOHSPVQXJUITJOHMFXJSFESFNPUFDPOUSPMMFS
 
&OFSHZTBWJOHPQFSBUJPO
t6QQFS-PXFSUFNQFSBUVSFMJNJUTFUUJOH
t"VUPNBUJDPQFSBUJPOTUPQ"VUPNBUJDBMMZTUPQTUIFPQFSBUJPO XIFOJUJTOPUVTFEGPSDFSUBJOQFSJPEPGUJNFTFUCZVTFS
 
8FFLMZPQFSBUJPOTDIFEVMFTFUUJOH
t8FFLMZPQFSBUJOHTDIFEVMF "$POMZ &37POMZ "$ &37

t"CMFUPTFUEFTJSFE"$PQFSBUJPONPEF TFUUJOHUFNQFSBUVSFBOEGBOTQFFEUPPQFSBUFCBTFEPOXFFLMZSFTFSWBUJPO
t"CMFUPBQQMZTDIFEVMFFYDFQUJPOEBZGPSGMVJENBOBHFNFOU
(4) User convenience function
t$IJMEMPDL
t%JGGFSFOUCVUUPOQFSNJTTJPOMFWFMT
 0QFSUJPONPEF UFNQFSBUVSFTFUUJOH 0/0'' GBOTQFFE

t3FBMUJNFDMPDL%JTQMBZTDVSSFOUUJNF EBZ 4VNNFSUJNFTVQQPSU

t#VJMUJOSPPNUFNQFSBUVSFTFOTPS
t4FSWJDFNPEFTVQQPSU
- Indoor unit cycle data monitoring
- Indoor unit option code setting and monitoring
- Indoor unit address and option setting and monitoring

2) Product specification
Power Supply DC12V
Power Consumption 2W
0QFSBUJOH5FNQFSBUVSFSBOHF 0°C~40°C
0QFSBUJOH)VNJEJUZSBOHF 30%RH~90%RH
Communication 2-wire PLC

CPNQBUJCMFQSPEVDU
Indoor unit AM7777N777777Model
13
Control Systems

I Individual control systems


3. Wired remote controller
MWR-WE10N

3) Description of parts
④ ⑤⑨⑩⑪ ⑫ ⑬
(1) Display




③ ⑯
⑥ ⑰
⑦ ⑱
⑧ ⑳ ⑲
-&%JOEJDBUPS (SFFO/PSNBM3FE/FFEUPCFDIFDLFE

0QFSBUJPO0O0GGCVUUPO

5FNQFSBUVSFTFUUJOHCVUUPO

Classification Indication Function


① Displays air conditioner operation

② %JTQMBZT2VJFU4MFFQPQFSBUJPO

③ %JTQMBZT*OEPPSUFNQFSBUVSF4FUUFNQFSBUVSF
Air
conditioner ④ Displays discharge temperature control
related ⑤ Displays CO2QPXFSDPOTVNQUJPO
information
⑥ Displays AC fan speed

⑦ Displays Blade selection

⑧ %JTQMBZT"JSTXJOH 6Q%O

⑨ 8FFLMZTDIFEVMF)PMJEBZTFUUJOHEJTQMBZT

⑩ Displays Current day( ) or scheduled day(_)


Schedule
related ⑪ Displays Schedule number
information
⑫ Displays Scheduled device selection

⑬ %JTQMBZT$VSSFOUUJNFEBZMJHIUTBWJOHUJNFTDIFEVMFEUJNF

Ventilator ⑭ %JTQMBZT7FOUJMBUPS &37


PQFSBUJPO
(ERV)
⑮ Displays Clean up
related
information ⑯ %JTQMBZT7FOUJMBUPS &37
GBOTQFFE

⑰ %JTQMBZT*OWBMJEPQFSBUJPO'JMUFSDMFBOJOH GJMUFSDMFBOJOHQFSJPE

⑱ %JTQMBZT%VTUCPYDMFBOJOHBMFSUDIFDLQBSUMPDL"MMMPDL
%JTQMBZT.PUJPOEFUFDUTFOTPS&YIBVTUIPPE&YUFSOBMJOUFSDPOOFDUJPODPOUSPM"VUP

Common DMFBO)VNJEJGZJOH&OFSHZTBWJOH0VUEPPSBJSTVQQMZJOUBLF$FOUSBMJ[FEDPOUSPM
function
⑳ Displays S-Plasma Ion
related
information Displays Indoor CO2 density

Displays Indoor humidity


%JTQMBZTSFNBJOJOHUJNFPGUIFBVUPTUPQUJNF&37EFMBZUJNF
- Solid : Hour unit, Blinking : Minute unit
14
(2) Buttons


CONTROL SYSTEMS
⑧ ⑱

INDIVIDUAL
② ⑬


③ ⑳


④⑪ ⑩⑯⑲ ⑭ ⑰

Classification Button Function


① 0QFSBUJPO0O0GGCVUUPO 5VSOUIFBJSDPOEJUJPOFSQPXFS0O0GG
② .PEFCVUUPO Selects the desired air conditioner operation

③ 5FNQFSBUVSFTFUUJOHCVUUPO Sets the desired temperature

④ 'BOTQFFECVUUPO Changes the air conditioner’s fan speed


Air
conditioner ⑤ "JSTXJOHCVUUPO Changes the air flow direction to move upward or downward
related ⑥ 5FNQCVUUPO Checks the indoor temperature
CVUUPO
⑦ 2VJFU4MFFQCVUUPO Selects quiet or sleep operation for the air conditioner
⑧ )VNJEJUZCVUUPO 5VSOTUIF")6IVNJEJGZJOHGVODUJPO0O0GG
⑨ #MBEFCVUUPO Selects a blade for individual control
⑩ .%4CVUUPO Set the power to automatically turn off if there is nobody in the room
⑪ Outdoor air intake Select the AHU Outdoor intake function
⑫ Schedule Button Select the schedule setting function
⑬ User Set Button Select the detailed setting function

⑭ /BWJHBUJPOBMCVUUPOT Move between items or change the item value

⑮ 4FUCVUUPO Save new setting

Common ⑯ &4$CVUUPO Return to general mode from schedule and detailed setting screens
function ⑰ %FMFUFCVUUPO Cancel the schedule setting
related
CVUUPO ⑱ "VUP$MFBOCVUUPO Use the auto cleaning function for your air conditioner

⑲ CO2<L8I>CVUUPO Display the amount of CO2 and the power consumption

⑳ 'JMUFS3FTFUCVUUPO 5VSOPGGUIFGJMUFSDMFBOJOHEJTQMBZT GJMUFSVTJOHUJNFSFTFU

41MBTNB*POCVUUPO Choose the S-Plasma ion function

0QFSBUJPO0O0GGCVUUPO 5VSOUIF7FOUJMBUPS &37


0O0GG
Ventilator .PEFCVUUPO 4FMFDUUIFEFTJSFEPQFSBUJPOGPSUIF7FOUJMBUPS &37

(ERV)
'BOTQFFECVUUPO $IBOHFUIFGBOTQFFEGPSZPVS7FOUJMBUPS &37

related
CVUUPOT &4BWFSCVUUPO Begin Energy Saving Operation
$MFBOVQCVUUPO 4FMFDUBJSQVSJGJDBUJPOUISPVHIUIFJOPVUMPBEDPOUSPMT

15
Control Systems

I Individual control systems


3. Wired remote controller
MWR-WE10N

3) Description of parts
(3) PCB

No. Name Description

① 4PGUXBSFVQHSBEFDPOOFDUPS It is used to upgrade the software

Communication and power


② $POOFDUJPOXJUIJOEPPSVOJU ''

XJSJOHUFSNJOBM

① 7 MWR-WE10N uses 2-wire power line communication.


4) Option function

UTFSTFUUJOHNPEF
Main 4VC SEG
Function Default 3BOHF Unit
menu menu Used
1 "VUPTUPQUJNFTFUUJOHDIFDLJOH 1,2 0 0~12 hours 1 hour
-PXFTUUFNQFSBUVSF 1,2 16 (61) _¡$ _¡'
¡$ ¡'

2 5FNQMJNJUT<¡$ ¡'
>
Highest temperature 3,4 30 (86) _¡$ _¡'
¡$ ¡'

All lock 1 0 o6OMPDL -PDL -


0O0GGCVUUPO 2 0 o6OMPDL o-PDL -
Mode button 3 0 o6OMPDL o-PDL -
3
-PDLPGQBSUJBMCVUUPO 5FNQFSBUVSFCVUUPO 4 0 o6OMPDL o-PDL -
Fan speed button 5 0 o6OMPDL o-PDL -
Schedule button 6 0 o6OMPDL o-PDL -
   ::..
1 Current date Setting (Year, Month, Date)  ___
  DD
4 %BZ 'SJEBZ %BZ
2 $VSSFOU5JNF4FUUJOH %BZ )PVS .JOVUF
Am,Pm PM 4VO_4BU"._1.__ )PVS
    Minute
4VNNFS5JNF6TFBOE 6TFPGTVNNFSUJNF :/
1 0 0 – No use, 1 – Use -
1
Setting Methods 4VNNFS5JNF"QQMJDBUJPO.FUIPE 2 0 0 – Weekly, 1 – Daily -
_UINPOUI
2 Summer time use (Weekly) Start (? Month, ? th Sunday)   ' -
1~4,F (last week)th week
5
_UINPOUI
3 Summer time use (Weekly) End (? Month, ? th Sunday)   ' -
1~4,F (last week)th week
4 Summer time use (Daily) Start (? Month, ? th Sunday)     +BO_%FD_UIEBZ Month, date
5 Summer time use (Daily) End (? Month, ? th Sunday)     +BO_%FD_UIEBZ Month, date
#BDLMJHIU5JNF4FUUJOH$IFDLJOH 1,2 5 0~30 sec 1sec
6 6TFPG-&% (SFFO
 :/
3 1 0 – No use, 1 – use -
6TFPG-&% 3FE
 :/
4 1 0 – No use, 1 – use -

7FOUJMBUPS &37
EFMBZ 7FOUJMBUPS &37
%FMBZ
1 0 0 – No use, 1 – use -
UJNFTFUUJOHDIFDLJOH "QQMJDBUJPO :/

7
<8IFOVTJOH7FOUJMBUPS
&37
JOUFSMPDLJOHDPOUSPM> %FMBZ5JNF 3,4 30 30~60 minutes 1 minute

0 Reset to user mode defaults (except the current time) 1 0 0 – No use, 1 – Reset -
16
f How to set the user mode

 
*GZPVXBOUUPTFUUIFEFUBJMFETFUUJOHT QSFTTUIF<6TFS4FU>CVUUPO
t:PVXJMMFOUFSUIF6TFS4FUNPEF BOEUIF<.BJO.FOV>XJMMCFEJTQMBZFE

(2) Refer to the Wired Remote Controller’s User Set list on the next
QBHFUPTFMFDUUIFEFTJSFENFOV
t6TJOHUIF[∧]/[∨] buttons, select a main menu number and press the [>] button

CONTROL SYSTEMS
to enter the sub-menu setting screen.

INDIVIDUAL
t6TJOHUIF[∧]/[∨] buttons, select a sub-menu number and press the [>] button
to enter the data setting screen.
t0ODFZPVIBWFFOUFSFEUIFTFUUJOHTDSFFO UIFDVSSFOUTFUUJOHXJMMCFEJTQMBZFE
t3FGFSUPUIFDIBSUGPSEBUBTFUUJOH
t6TJOHUIF[∧]/[∨] buttons, change the settings and press the [>] button to
move to the next setting.
t1SFTTUIF4FUCVUUPOUPTBWFUIFTFUUJOHBOEFYJUUPUIFTVCNFOVTFUUJOHTDSFFO
t1SFTTUIF&TDCVUUPOUPFYJUUPHFOFSBMNPEF

; Note
Š While setting the data, you can use the [∧]/[∨] buttons to set the range of SEG used.
Š8IJMFDPOGJHVSJOHUIFTFUUJOH QSFTTUIF<&TD>CVUUPOUPFYJUUPUIFTVCNFOVTFUUJOHTDSFFOXJUIPVUTBWJOHUIFTFUUJOH

f CuSSFOUUJNFTFUUJOH &YBNQMF

 
1SFTTUIF<6TFS4FU>CVUUPO  
*OUIFTVCNFOV TFMFDUhEBZ
t(Main Menu) will be displayed, and ".1. IPVS NJOVUFh
you can press the [∧]/[∨] buttons to tPress the [∧]/[∨] buttons to select no.
select No.4, which will set the current :PVDBOTFUUIFhEBZ ".1. IPVS
time. minute'.

(2) Press the [>]CVUUPOUPTFMFDU (8) Press the [>]CVUUPOUPTFMFDU


h:FBS .POUI %BUFhJOUIF UIFh%BZh
<4VCNFOV> tPress the [∧]/[∨] buttons to select
tPress the [∧]/[∨] buttons to select day (Sun~Sat).
/P:PVDBONPEJGZUIFZFBSNPOUI
date setting. (9) Press the [>]CVUUPOUPTFMFDU
h".PS1.h
(3) Press the [>]CVUUPOUPTFMFDU
tPress the [∧]/[∨] buttons to toggle
UIFh:FBSh between AM and PM.
tPress the [∧]/[∨] buttons to select
the year ('00~'99). (10) Press the [>]CVUUPOUPTFMFDU
UIFh)PVSh
(4) Press the [>]CVUUPOUPTFMFDU
tPress the [∧]/[∨] buttons to select
UIFh.POUIh the hour (01~12).
tPress the [∧]/[∨] buttons to select
month(01~12). (11) Press the [>]CVUUPOUPTFMFDU
UIFh.JOVUFh
(5) Press the [>]CVUUPOUPTFMFDU
tPress the [∧]/[∨] buttons to select
UIFh%BZh minute (00~59).
tPress the [∧]/[∨] buttons to select
day(01~31). (12) 1SFTTUIF<4FU>CVUUPOUP
DPNQMFUFUIFDVSSFOUUJNFTFUUJOH
 
1SFTTUIF<4FU>CVUUPOUP
t5IFTFUUJOHDIBOHFTBSFBQQMJFEBOE
DPNQMFUFZPVSTFUUJOHPG you can exit to general mode.
h:FBS .POUI %BZh
t5IFTFUUJOHDIBOHFTXJMMCFBQQMJFE  
1SFTTUIF<&TD>CVUUPOUPFYJUUP
and you can exit to the sub-menu. HFOFSBMNPEF
17
Control Systems

I Individual control systems


3. Wired remote controller
MWR-WE10N

4) Option function

Service mode
Main 4VC SEG
Function Default 3BOHF Unit
menu menu Used
Wired remote $PPMJOH)FBUJOHTFMFDUJPO 1 0 $PPMJOH)FBUJOH $PPMJOHPOMZ -
controller Option Use of wireless remote controller 2 1 0-No use, 1-Use -
1
TFUUJOHDIFDLJOH ."*/46#XJSFESFNPUFDPOUSPMMFS 3 0 0-MAIN, 1-SUB -
(1) 5FNQFSBUVSFVOJU 4 0 o$FMTJVT ¡$
o'BISFOIFJU ¡'

5FNQFSBUVSFTFOTPSTFMFDUJPO 1 0 0–Indoor unit, 1–Wired remote controller -


Use of average temperature 2 0 0-No use, 1-Use -
Wired remote
controller Option Use of Auto mode 3 1 0-No use, 1-Use -
2 0–Set temperature,1-Room temperature
TFUUJOHDIFDLJOH 5FNQFSBUVSFEJTQMBZ 4 0 -
(2)
o*OEPPSVOJU &37 o*OEPPS
"$0O0GGCVUUPOGVODUJPO 5 0 -
VOJUPOMZ o&37POMZ
-PDLCMBEF 1 0 6OMPDL -PDL -
#MBEFTFUUJOH -PDLCMBEF 2 0 6OMPDL -PDL -
1 3
checking -PDLCMBEF 3 0 6OMPDL -PDL -
-PDLCMBEF 4 0 6OMPDL -PDL -
Use of By-pass mode 1 0 0-No use, 1-Use
&37PQUJPO Use of Auto mode 2 0 0-No use, 1-Use
4
4FUUJOHDIFDLJOH Use of air purification mode 3 0 0-No use, 1-Use
Use of external control 4 0 0-No use, 1-Use
Room temperature Current room temperature 1, 2, 3 - _ ¡$
 ¡$

5
compensation 5FNQFSBUVSFDPNQFOTBUJPOWBMVF 4,5,6 - _ ¡$
 ¡$

number of connected Number of indoor units 1,2 0 0~16 -


6
indoor units /VNCFSPG&37T 3,4 0 0~16 -
7 5FNQFSBUVSFJODSFNFOUEFDSFNFOUVOJU ¡$POMZ
1 - ¡$ ¡$ ¡$ -
0-Unchanged,
0 Factory option setting 1 - -
1-Factory setting
1 Software code 1~6 - Software code -
2
2 Software version 1~6 - Software version -
1 Indoor unit room temperature 1,2,3 - Room temperature ¡$
2 *OEPPSVOJU&7"*/UFNQFSBUVSF 1,2,3 - &7"*/UFNQFSBUVSF ¡$
3 *OEPPSVOJU&7"065UFNQFSBUVSF 1,2,3 - &7"065UFNQFSBUVSF ¡$
4 *OEPPSVOJU&&7TUFQ 1,2,3 - &&7TUFQ -
Use of central control 1 - 0-No use, 1-Use -
Indoor unit option Use of drain pump 2 - 0-No use, 1-Use -
5
3 checking(1) Use of electric heater 3 - 0-No use, 1-Use -
Use of hot water coil 4 - 0-No use, 1-Use -
Use of external control 1 - 0-No use, 1-Use -
Use RPM compensation 2 - 0-No use, 1-Use -
Indoor unit option
6 Filter time 3 - 0-2000 hours, 1-1000 hours -
checking(2)
Heating temperature compensation 4 - ¡$ ¡$ -
&&7TUPQTUFQJOIFBUJOH 5 - TUFQ TUFQ -
Main address(00H~4FH,
Indoor unit main address 1, 2 - -
Hexadecimal digits)
Indoor unit setup address Main address (00H~4FH,
1 3, 4 - -
(Manual setting main address) Hexadecimal digits)
Indoor unit option RMC address (00H~FEH,
4 Indoor unit RMC address 5, 6 - -
setting 2)* Hexadecimal digits)
2 Indoor unit Product option code 1)* - Indoor unit option code -
3 *OEPPSVOJU*/45"--PQUJPO 1)* - Refer to the indoor unit -
4 *OEPPSVOJU*/45"--PQUJPO 
1)* - installation manual for details -

18
Main 4VC SEG
Function Default 3BOHF Unit
menu menu Used
4FUUJOHDIFDLJOHUIFEJGGFSFOUWBMVF 1, 2 - 0~30 1

CONTROL SYSTEMS
31.TFUUJOHDIFDLJOH 3, 4 - 0~25 1RPM

INDIVIDUAL
")6TFUUJOH 0- Pre,
1
checking Filter performance 5 - 1-Medium performance, -
2-High performance
)VNJEJUZTFUUJOHDIFDLJOH 6 - 0-30, 1-40, 2-50 -
5 Use of discharge temperature
Indoor unit, 1 - 0-No use, 1-Use -
AHU discharge control
2 Cooling discharge temperature 3, 4 - _¡$ ¡$
temperature
TFUUJOHDIFDLJOH Heating discharge temperature 5, 6 - _¡$ ¡$
Fresh Duct discharge Cooling discharge temperature 1, 2 - _¡$ ¡$
3
temperature checking Heating discharge temperature 3, 4 - _¡$ ¡$
Use of cold air prevention 1 - 0-No use, 1-Use -
&371MVTTFUUJOH Use of humidification 2 - 0-No use, 1-Use -
1
checking Use of fan operation in defrost 3 - 0-No use, 1-Use -
Use of humidification 4 - 0-No use, 1-Use -
&371MVTUFNQFSBUVSF Cooling 1, 2 - _¡$ ¡$
2
TFUUJOHDIFDLJOH Heating 3, 4 - _¡$ ¡$
6
&371MVT"VUPNPEF Set temperature 1, 2 - _¡$ ¡$
3 temperature
TFUUJOHDIFDLJOH Set temperature difference 3, 4 - _¡$ ¡$
4FUUJOHDIFDLJOHUIFDPNQFOTBUJPOUFNQFSBUVSF"
1, 2 - _¡$ ¡$
VOEFSUIF)FBUJOH&&7DPOUSPMGPS&371MVT
4
Checking the compensation temperature B under the /POVTFIVNJEJGJFS ¡$

3, 4 - -
)FBUJOH&&7DPOUSPMGPS&371MVT 6TFIVNJEJGJFS ¡$

5 &37 Air supply RPM 1, 2 - 10~27RPM 1 RPM


*OEPPSVOJUNBTUFSTFUUJOH 1, 2,3,
1 .BTUFSDIFDLJOH - Address -
checking 4,5,6
(F3F4 line Indoor
&37VOJUNBTUFSTFUUJOH 1, 2,3,
2 unit master) - Address -
checking 4,5,6
7 Mode master Mode master indoor unit 1, 2,3,
3 - Address -
JOEPPSVOJUTFUUJOH checking 4,5,6
checking
4 (F1F2 line Indoor Mode master indoor unit setting 1 - 0-No use, 1-Use, 2-Release -
unit master) 3)*
1 Factory setting 1 0 0-No use, 1-Reset -
0 2 Reset Power master reset 4)* 1 0 0-No use, 1-Reset -
3 Addressing reset 1 0 0-No use, 1-Reset -


4&(NFBOTPQUJPOTFUUJOHQBHF4&(_NFBOTPQUJPODPEF
2)* If you enter Main menu #4, you must select the targeted indoor unit address and then select the sub menu.

.PEFNBTUFSJOEPPSVOJU5IFJOEPPSVOJUXIJDIDBOEFDJEFUIFPQFSBUJPONPEF0UIFSJOEPPSVOJUGPMMPXT.PEFNBTUFS
indoor unit's operation mode.
4)* Power master reset : Setting for finding the most stable power supply indoor unit.

f5PTFUEJHJUPQUJPO
1BHF 0QUJPO4FUUJOH )PXUPNPWFCFUXFFOQBHFT
1BHF 1~5th digit option 1SFTTUIF<>CVUUPOUPHPUP1BHF
1BHF 6~10th digit option 1SFTTUIF<>CVUUPOUPHPUP1BHF
1BHF 11~15th digit option 1SFTTUIF<>CVUUPOUPHPUP1BHF
1BHF 16~20th digit option 1SFTTUIF<>CVUUPOUPHPUP1BHF
1BHF 21~24th digit option -
19
Control Systems

I Individual control systems


3. Wired remote controller
MWR-WE10N

4) Option function

Service mode
f How to set the service mode
(1) If you want to use the various additional functions for your Wired
3FNPUF$POUSPMMFS QSFTTUIF<4FU>BOE<&TD>CVUUPOTBUUIFTBNF
time for more than three seconds.
t:PVXJMMFOUFSUIFBEEJUJPOBMGVODUJPOTFUUJOHT BOEUIF<NBJONFOV>XJMMCFEJTQMBZFE

(2) Refer to the list of additional functions for your Wired Remote Controller
POUIFOFYUQBHF BOETFMFDUUIFEFTJSFENFOV
tUsing the [∧]/[∨] buttons, select a main menu number and press the [>] button
to enter the sub-menu setting screen.
tUsing the [∧]/[∨] buttons, select a sub-menu number and press the [>] button
to enter data setting screen.
tWhen you enter the setting stage, the current setting will be displayed.
tRefer to the chart for data settings.
tUsing the [∧]/[∨] buttons, select the settings. Press the [>] button to move to
the next setting.
t1SFTTUIF<4FU>CVUUPOUPTBWFUIFTFUUJOHTBOEFYJUUPUIFTVCNFOVTFUUJOHTDSFFO
t1SFTTUIF<&TD>CVUUPOUPFYJUUPOPSNBMNPEF
; Note
Š While setting the data, you can use the [∧]/[∨] buttons to set the range of SEG
Š8IJMFDPOGJHVSJOHUIFTFUUJOH QSFTTUIF<&TD>CVUUPOUPFYJUUPUIFTFUUJOHTVCNFOVXJUIPVUTBWJOHZPVSDIBOHFT

f&YBNQMFNFUIPEPGTFUUJOHXJSFESFNPUFDPOUSPMMFSPQUJPO
 
1SFTTUIF<4FU>BOE<&4$>CVUUPOTBUUIFTBNFUJNFGPSNPSFUIBOTFDPOET
t8IFO(Main menu) is displayed press the [∧]/[∨] button to select no.1.

(2) Press the [>] CVUUPOUPTFMFDUUIFOVNCFSZPVXJMMTFU


tPress the [∧]/[∨] button and select no.1

(3) Press the [>] CVUUPOUPFOUFSUIFEBUBTFUUJOHTUBHF


tWhen you enter the setting stage, the current setting value will be displayed.
f&YBNQMFPGEBUBTFUUJOHTUBHFEJTQMBZ

SEG1: Heat pump indoor unit


SEG2: Use wireless remote controller
SEG3: Master wired remote controller
4&(5FNQFSBUVSFEJTQMBZo$FMTJVT ¡$

(4) Press the [<]/[>] CVUUPOUPTFMFDUUIFEFTJSFE%BUB


tPress the [∧]/[∨] button to select no.1.
t5IFXJSFESFNPUFDPOUSPMMFSPQUJPOJTTFUGSPNCPUIDPPMJOHBOEIFBUJOHUPDPPMJOHPOMZ

 
1SFTT<4FU>CVUUPOUPDPNQMFUFUIFPQUJPOTFUUJOH
tSave the setting value and exit to sub menu.
20
 
1SFTT<&TD>CVUUPOUPFYJUUPOPSNBMNPEF
Built-in temperature sensor of wired remote controller
f5FNQFSBUVSFDPOUSPMXJUICVJMUJOUFNQFSBUVSFTFOTPS

CONTROL SYSTEMS
INDIVIDUAL
"QQMJFTUPBMMUIFJOEPPSVOJUTDPOOFDUFEXJUIJOBHSPVQ
(However, indoor unit is limited to DVM S series )

Ï Check the setting of the wired remote controller built-in sensor from the service menu.
Main 4VC Used Factory
Function Description Unit
menu menu SEG TFUUJOH
$PPMJOH)FBUJOHTFMFDUJPO 1 0 $PPMJOH)FBUJOH $PPMJOHPOMZ -
Wireless remote Use of wireless remote
2 1 0-No use, 1-Use -
controller controller
1
0QUJPOTFUUJOH ."*/46#XJSFESFNPUF
3 0 0-MAIN, 1-SUB -
checking (1) controller
5FNQFSBUVSFVOJU 4 0 o$FMTJVT ¡$
o'BISFOIFJU ¡'

1 5FNQFSBUVSFTFOTPSTFMFDUJPO 1 0 0–Indoor unit, 1–Wired remote controller -


Use of average temperature 2 0 0-No use, 1-Use -
Wireless remote
controller Use of Auto mode 3 1 0-No use, 1-Use -
2 0–Set temperature,1-Room temperature
0QUJPOTFUUJOH 5FNQFSBUVSFEJTQMBZ 4 0 -
checking (2)
o*OEPPSVOJU &37 o*OEPPSVOJU
"$0O0GGCVUUPOGVODUJPO 5 0 -
POMZ o&37POMZ

f HeBUJOHNPEFUFNQFSBUVSFDPNQFOTBUJPO

*OEPPSVOJU*/45"--PQUJPOTFUUJOH 3FGFSUPJOEPPSVOJUJOUBMMBUJPONBOVBM

SEG Function Value


)FBUJOHTFUUJOHUFNQFSBUVSF o¡$
21
compensation ¡$

; Note
Š8IFOCVJMUJOTFOTPSPGUIFXJSFESFNPUFDPOUSPMMFSJTVTFE IFBUJOHNPEFUFNQFSBUVSFDPNQFOTBUJPO ¡$PS ¡$
XJMMCFSFTFUUP¡$

Ï If there is no option switch on the indoor unit PCB, check the setting of the heating temperature compensation from the service menu.
Main 4VC Used Factory
Function Description Unit
menu menu SEG TFUUJOH
Use of external control 1 - 0-No use, 1-Use -
Use RPM compensation 2 - 0-No use, 1-Use -
Indoor
Filter time 3 - 0-2000 hours, 1-1000 hours -
3 6 unit option
checking(2) Heating temperature
4 - ¡$ ¡$ -
compensation
&&7TUPQTUFQJOIFBUJOH 5 - TUFQ TUFQ -

21
Control Systems

I Individual control systems


3. Wired remote controller
MWR-WE10N

4) Option function

Built-in temperature sensor of wired remote controller


f8IFODPNNVOJDBUJPOFSSPSPSQPXFSGBJMVSFPDDVSTXIJMFVTJOHCVJMUJOUFNQFSBUVSFTFOTPS

(1) When communication error occurs over 3 minutes,


t Indoor unit ignores the built-in temperature sensor and use indoor unit temperature sensor.
t Ignores the temperature compensation setting on the wired remote controller and use the compensation value set on indoor
unit instead.

(2) When communication resumes,


t Built-in temperature use is recovered.
t Setting must be done again to use the temperature compensation.

EOFSHZTBWJOHPQFSBUJPONPEF

N(ERV) : N(Indoor unit)

Ï&OFSHZTBWJOHPQFSBUJPONPEFJTBWBJMBCMFPOMZXIFOUIFSFJTBUMFBTUPOFJOEPPSVOJUBOE&37JTDPOOFDUFE
t By comparing indoor room temperature, setting temperature and outdoor temperature, wired remote controller changes
&37PQFSBUJPONPEFBOEGBOTQFFEUPNJOJNJ[FVOOFDFTTBSZPVUEPPSVOJUPQFSBUJPO
t &OFSHZTBWJOHPQFSBUJPOJTOPUBWBJMBCMFXIFO&37JTOPUDPOOFDUFE
t &OFSHZTBWJOHPQFSBUJPOJTOPUBWBJMBCMFXIFOA$FOUSBMJ[FEDPOUSPMJTTFU
t &OFSHZTBWJOHPQFSBUJPOXJMMOPUCFFYFDVUFEXIFO&37JTTFUUP0VUJOHNPEFPSTFUJOFYUFSOBMJOUFSMPDLJOHNPEF
t 5FNQFSBUVSFNFBTVSFNFOUJTTFUBTJOEPPSVOJUUFNQFSBUVSFTFOTPSBTEFGBVMU BOEJUDBOCFDIBOHFEEFQFOEJOHPOUIFXJSFE
remote controller option setting.

22
5) Display

Error display
&SSPSDPEFTGPSUIF8JSFE3FNPUF$POUSPMMFSBOEUIFQSPEVDUDPOOFDUFEUPUIF8JSFE3FNPUF$POUSPMMFSXJMMCF
displayed in the LCD display.

CONTROL SYSTEMS
INDIVIDUAL
LCD Display

f When an Error Occurs in Your Indoor/Outdoor Units (Product Group Display : A20)
t5IFQSPEVDUBEESFTTGPSUIFFSSPSXJMMCFEJTQMBZFE GPMMPXFECZUIFFSSPSDPEF
Example : Error 121 occurred in indoor unit with main address no. 18 (decimal numbers).

Refers to the indoor unit Outdoor unit address Indoor unit Main address Error code
(Displayed in hexadecimal) (Displayed in hexadecimal)

f When an Error Occurs in Your Ventilator(ERV) (Product Group Display : B30)


t5IFQSPEVDUBEESFTTGPSUIFFSSPSXJMMCFEJTQMBZFE GPMMPXFECZUIFFSSPSDPEF
Example : Error 121 occurred in indoor unit with main address no. 18 (decimal numbers).

Refers to the ERV unit ERV unit Main address Error code
(Displayed in hexadecimal)

f When an Error Occurs in Your Wired Remote Controller


tOnly an error code will be displayed. (No address will be displayed.)
Example : Error 601 has occurred at your Wired Remote Controller.

23
Control Systems

I Individual control systems


3. Wired remote controller
MWR-WE10N

5) Display

Wired remote controller error codes


Display Description Remarks
$PNNVOJDBUJPOFSSPSCFUXFFOXJSFESFNPUFDPOUSPMMFSBOEJOEPPS&37VOJUT
after successful communication

No communication between Master (Main) and Slave(Sub) wired remote


controllers

/PDPNNVOJDBUJPOCFUXFFOXJSFESFNPUFDPOUSPMMFSBOEJOEPPS&37VOJUT

8JSFESFNPUFDPOUSPMMFSJTDPOOFDUFEPO''DIBOOFM

5XPPSNPSFXJSFESFNPUFDPOUSPMMFSTBSFTFUBT.BTUFS .BJO
When using Master remote controller

%FUFDUJPOBWBJMBCMFGSPNCPUI.BTUFS
/P&37VOJUJOTUBMMFEGPSJOUFSMPDLJOHGVODUJPO
Slave wired remote controller

When external interlocking control is in


No indoor unit installed for interlocking function
use

0WFSJOEPPS&37JOEPPSVOJUTJOTUBMMFE

*OEPPSVOJUTPGEJGGFSFOUUFNQFSBUVSFTFUUJOH ¡$¡'
DPOOFDUFEUPTBNFXJSFE Detection available in Master wired
remote controller remote controller

Wired remote controller(s) has different temperature unit setting with indoor
unit(s)

Detection available in models with


5FNQFSBUVSFTFOTPS0QFO4IPSUFSSPS
temperature sensor

tMemory error
tNo damper feedback

; Note
Š'PSUIFFSSPSDPEFTGPSZPVSJOEPPSPVUEPPSVOJUTBOEWFOUJMBUPS &37
SFGFSUPUIFJOTUBMMBUJPONBOVBMPGFBDIEFWJDF

24

$PNNVOJDBUJPOEJBHSBN

Individual control (1) Control 1 indoor unit with 1 wired remote controller

F1/F2

Indoor unit

CONTROL SYSTEMS
Outdoor unit
F3/F4

INDIVIDUAL
Wired remote controller

Control All connected indoor units


Display Operation status of the connected indoor unit

Group control (1) Control multiple indoor units with 1 wired remote controller

Outdoor unit Indoor unit

Wired remote controller


Ú Maximum 16 indoor units can be connected

Control All connected indoor units


1SJPSJUZ%JTQMBZUIFTUBUVTPG7JFX.BTUFSJOEPPSVOJU
Display
Priority 2. Display the status of indoor unit which has the earliest Main address

Group control (2) Control multiple indoor units connected to different outdoor units with 1 wired remote controller

F1/F2

Outdoor unit
Outdoor unit

F3/F4
Wired remote controller

Ú Maximum 16 indoor units can be connected

Control All connected indoor units


1SJPSJUZ%JTQMBZUIFTUBUVTPG7JFX.BTUFSJOEPPSVOJU
Display
Priority 2. Display the status of indoor unit which has the earliest Main address

f Caution
When controlling group of indoor units connected to different outdoor unit, address of the each outdoor unit must be set differently.

25
Control Systems

I Individual control systems


3. Wired remote controller
MWR-WE10N


$PNNVOJDBUJPOEJBHSBN

Group control (3) Control 1 or multiple indoor units with 2 wired remote controllers

F1/F2

Indoor unit
Outdoor unit F3/F4

Wired remote controller

Master Slave Master Slave Ú Maximum 16 indoor units can be connected

Control All connected indoor units


1SJPSJUZ%JTQMBZUIFTUBUVTPG7JFX.BTUFSJOEPPSVOJU
Priority 2. Display the status of indoor unit which has the earliest Main address
Display
Ï 5XPXJSFESFNPUFDPOUSPMMFSTJEFOUJDBMMZEJTQMBZUIFPQFSBUJPOTUBUVTPGUIFJOEPPSVOJU
according to above priority.

Group control (4) Control multiple indoor units connected to different outdoor units with 2 wired remote controller

F1/F2

Outdoor unit
Indoor unit
Outdoor unit

F3/F4
Wired remote controller

Master Slave Ú Maximum 16 indoor units can be connected

Control All connected indoor units


1SJPSJUZ%JTQMBZUIFTUBUVTPG7JFX.BTUFSJOEPPSVOJU
Priority 2. Display the status of indoor unit which has the earliest Main address
Display
Ï 5XPXJSFESFNPUFDPOUSPMMFSTJEFOUJDBMMZEJTQMBZUIFPQFSBUJPOTUBUVTPGUIFJOEPPSVOJU
according to above priority.

f Caution
When controlling group of indoor units connected to different outdoor unit, address of the each outdoor unit must be set differently.

Max. distance between the farthest indoor unit and wired 100m
remote controller : 100m

Wired remote controller

26
MWR-SH00N

1) Features

CONTROL SYSTEMS
INDIVIDUAL
t4JNQMJGJFEXJSFESFNPUFDPOUSPMMFS
t"$PQFSBUJPO0/0''DPOUSPM
t'BOTQFFEDPOUSPM
t4FUUJOHPQFSBUJPOUFNQFSBUVSF
t3FTFUGJMUFSDMFBOJOHBMFSUJOEJDBUPS
t"EKVTUBJSGMPXEJSFDUJPO
t0QFSBUJPOPOPGGUJNFSGVODUJPO

(Unit : mm)
122.0

75.0
16.6

2) Product specification
Power supply %$7
Power consumption 1.5 W
0QFSBUJOHUFNQFSBUVSFSBOHF ¡$_¡$
0QFSBUJOHIVNJEJUZSBOHF 30 % RH~90 % RH
Communication XJSF1-$
.BYJNVNMFOHUIPGDPOOFDUJPO 100 m
.BYJNVNOVNCFSPG
16 indoor units
DPOUSPMMBCMFEFWJDFT

CPNQBUJCMFQSPEVDU
Indoor unit AM7777N777777Model

27
Control Systems

I Individual control systems


3. Wired remote controller
MWR-SH00N

3) Description of parts ⑩



③ ⑧
④ ⑦
⑤ ⑥



⑭ ⑰
⑮ ⑯

No. Name Description


Indicator will be on when remote controller usage restriction is set.
① Centralized control indicator
(%FWJDFTUIBUTVQQPSUDFOUSBMJ[FEDPOUSPM0O0GGDPOUSPMMFS %.4 5PVDIDFOUSBMJ[FEDPOUSPMMFSFUD

② Operation mode indicator *OEJDBUFTDVSSFOUPQFSBUJPONPEFXIFOUIFJOEPPSVOJUJTPQFSBUJOH $PPM"VUP%SZ'BO)FBU

③ Set temperature indicator Indicates the set temperature when the indoor unit turns on.
④ Fan speed indicator Indicates the fan speed settings.
⑤ "JSTXJOHJOEJDBUPS Indicates when vertical air swing is on.
⑥ Quiet mode indicator Indicates when quiet mode is on.
⑦ 'JMUFSDMFBOJOHJOEJDBUPS Indicates when preset filter cleaning period is passed.
: Indicates when On timer is set
: Indicates when Off timer is set
⑧ Timer indicator : ① 5JNFSNPEFo%JTQMBZTUIFTFUUJNFGPS0O0GGUJNFS
(Min. 30 minutes ~ Max. 18 hours)
② General mode - %JTQMBZTSFNBJOJOHUJNFCFGPSF5JNFSGVODUJPOXJMMFYFDVUF
5IJTJDPOXJMMCFEJTQMBZFEXIFOCVUUPOJTMPDLFEPSXIFOVOBWBJMBCMFGVODUJPO
(function which indoor unit does not support) is selected
⑨ Lock / Restricted indicator ① Icon On: All buttons are locked
② Icon blinks for 3 seconds: When partially locked button is pressed or unavailable function
(function which indoor unit does not support) is selected
⑩ SPi indicator Indicates that SPi or other cleaning function of the indoor unit is on.
⑪ Inspection indicator Indicates that inspection is required.
⑫ 0O0GGCVUUPO 1SFTTUIJTCVUUPOUPUVSOPOPGGUIFJOEPPSVOJU
⑬ .PEFCVUUPO Press this button to select the desired operation mode. (Auto ¤ Cool ¤ Dry ¤ Fan ¤ Heat)
1SFTTUIJTCVUUPOUPTFMFDUPOFPGUIFGBOTQFFETGSPN"VUP -PX .FEJVN )JHI 5VSCP
⑭ 'BOTQFFECVUUPO Available Fan Speed may differ depending on the operation mode of the indoor unit.
-PX¤ Medium ¤ High ¤5VSCP¤ Auto
1SFTTUIJTCVUUPOUPUVSOPOPGGUIFWFSUJDBMBJSTXJOHXIFOUIFJOEPPSVOJUTVQQPSUTWFSUJDBMBJS
⑮ "JSTXJOHCVUUPO
swing movement.
5IJTCVUUPODBOCFVTFEPOMZGPS5JNFS 6TFSNPEF 4FSWJDFNPEF
⑯ 4FU$BODFMCVUUPO
*Short press: Set (Save) * Press and hold for 3 seconds: Cancel
5JNFSCVUUPO'JMUFSSFTFU 4IPSUQSFTT:PVDBOTFUUIF0O0GGUJNFS

CVUUPO * Press and hold for 3 seconds: Resets the filter cleaning alert indicator.
① General mode
1SFTTUIJTCVUUPOUPJODSFBTFEFDSFBTFUIFTFUUFNQFSBUVSFCZQSFTFUVOJU
* Short press - adjust the temperature by 1℃ or 0.5℃ or 0.1℃ depending on the setting.
Temperature adjustment / * Press and hold – adjust the temperature by 1℃ every 0.5 second

5JNFBEKVTUNFOUCVUUPO ②5JNFSNPEF
1SFTTUIJTCVUUPOUPJODSFBTFEFDSFBTFUIFTFUUJNF
6QUPIPVST*ODSFBTFEFDSFBTFCZNJOVUFVOJU
0WFSIPVST*ODSFBTFEFDSFBTFCZIPVSVOJU
28
PCB
No. Name Description
Power/communication
① $POOFDUUPJOEPPSVOJU ''

connection terminal

CONTROL SYSTEMS
INDIVIDUAL

4) Option function

UTFSTFUUJOHNPEF
SEG in use
f How to set 1 2
Sub Menu
Main Menu

Up

Down
Left 3JHIU

<6TFSNPEFTDSFFO>
Exit Save
Press for more than 3
seconds simultaneously

Main
4VCNFOV Function Default 1BHFJOVTF 3BOHF Save
menu
0 1 Reset User mode to default value 0 1 0 - Disabled, 1 - Reset none
1 -PDLBMM 0 1 6OMPDL -PDL o
2 -PDL0O0GGCVUUPO 0 1 6OMPDL -PDL o
3 -PDL.PEFCVUUPO 0 1 6OMPDL -PDL o
1 Partially lock -PDL5FNQFSBUVSF
4 0 1 6OMPDL -PDL o
buttons adjustment button
5 -PDL'BOTQFFECVUUPO 0 1 6OMPDL -PDL o
6 -PDL5JNFSCVUUPO 0 1 6OMPDL -PDL o
1 5FNQFSBUVSF -PXFSUFNQFSBUVSF 16 1 16~30 o
2
2 restriction Upper temperature 30 1 16~30 o

29
Control Systems

I Individual control systems


3. Wired remote controller
MWR-SH00N

4) Option function
SEG in use
Service mode Sub Menu 1 2

f How to set Main Menu

Up

Down
Left 3JHIU

<4FSWJDFNPEFTDSFFO>
Exit Save
Press for more than 3 1BHFEJTQMBZ
seconds simultaneously
1BHF 1BHF 1BHF 1BHF 1BHF
On
Auto Cool Dry Fan Heat
1BHF 1BHF 1BHF 1BHF 1BHF
Off
Auto Cool Dry Fan Heat

Main 4VC 1BHF


Function Default value 3BOHF
menu menu in use
Reset the option setting of the wired remote
1 0 1 0 - Disable, 1 - Reset
controller to dafault value
2 Reset wired remote controller to factory default 0 1 0 - Disable, 1 - Reset
0 Reset
3 Power Master Reset 0 1 0 - Disable, 1 - Reset
4 Addressing Reset 0 1 0 - Disable, 1 - Reset
1 Check the number of connected indoor units 0 1 0~16
Wired
2 $IFDLUIFOVNCFSPGDPOOFDUFE&37 0 1 0~16
remote
1 Check the MICOM code of wired remote
3 controller none 1~3 MICOM code
controller
information Check the software version of the wired remote
4 none 1~3 Updated date
controller
Select address from one of the connected
indoor unit
Display example)
1 5BSHFUJOEPPSVOJUBEESFTTTFUUJOHTFUUJOH 7JFX.BTUFSJOEPPSVOJU 1~3
Page 1: 20 (Refers to indoor unit)
Page 2: 00 (Outdoor unit addres)
Page 3: 04 (Main address)
Main address of Main address
2 "EESFTT $IFDL4FUNBJOBEESFTT 1
5BSHFUJOEPPSVOJU (00H~4FH, Hexadecimal digits)
2 option Main address of 3.$ 
_'3.$ 
_'
3 setting $IFDL4FU3.$BEESFTT 1
5BSget indoor unit (Hexadecimal number) 1)7
Product option of
4 $IFDLTFUUIFQSPEVDUPQUJPO 1~10 Option code
target indoor unit
Installation option
5 $IFDL4FUJOTUBMMBUJPOPQUJPO 
1~10 Option code
of target indoor unit
Installation option of
6 $IFDL4FUJOTUBMMBUJPOPQUJPO 
1~10 Option code
target indoor unit (2)
7JFX.BTUFSJOEPPS Select address from one of the connected
1 $IFDL4FU $IFDL4FUJOEPPSVOJUWJFXNBTUFS 1~3
3 unit indoor unit (hexadecimal number)
2 view master No function - 1~3 -
$IFDL Check the address of the mode Master indoor Address of the mode Master indoor
1 none 1~3
Set Mode unit units
4
2 master Setting the mode Master indoor unit 2)7 none 1 0- Not set, 1-Set, 2-Cancel
indoor unit

1)7 When RMC(1) is set as F, RCM(2) can be set up to E only.


30 2)7.PEFNBTUFSJOEPPSVOJU5IFJOEPPSVOJUXIJDIDBOEFDJEFUIFPQFSBUJPONPEF0UIFSJOEPPSVOJUXJMMGPMMPXNPEFNBTUFSJOEPPSVOJUhTPQFSBUJPONPEF
Main 4VC 1BHF
Function Default value 3BOHF
menu menu in use
4FUJOEPPSVOJUGPShDPPMJMOHBOEIFBUJOHh 0- Cooling and heating, 1-Cooling
1 0 1
'cooling only' only
$IFDL Setting wireless remote controller usage
2 1 1 0 - Disable, 1 - Enable
Set option restriction
3 function of 4FUUJOH.BTUFS4MBWFXJSFESFNPUFDPOUSPMMFS 0 1 0-Master, 1-Slave
5
4 the wired Setting auto operation usage 1 1 0 - Disable, 1 - Enable
remote
5 5FNQFSBUVSFEJTQMBZ$FMTJVT ¡$
'BISFOIFJU ¡'
0 1 $FMTJVT ¡$
'BISFOIFJU ¡'

CONTROL SYSTEMS
controller
Set unit for desired temperature (0,1,2) (Only available
6 0 1 ¡$ ¡$ ¡$

INDIVIDUAL
XIFOUFNQFSBUVSFJTEJTQMBZFEJO$FMTJVT ¡$

SFUUJOHNPEFNBTUFSJOEPPSVOJU

F1/F2

Indoor unit
Outdoor
unit
F3/F4

Wired remote controller

t Only when the wired remote controller is connected to an indoor unit directly
(1:1 connection), you can set the mode master indoor unit that sets the
operation mode of the outdoor unit.

Press and hold for over 5 seconds


All connected indoor units will be set as Master indoor unit

Press and hold for over 5 seconds


All Master indoor unit setting will be canceled

System reset
t Reset the power of the simplified wired remote controller

Press and hold for over


5 seconds Power reset

31
Control Systems

I Individual control systems


3. Wired remote controller
MWR-SH00N

5) Display

Error display
t &SSPSDPEFTPGGPSUIFTJNQMJGJFEXJSFESFNPUFDPOUSPMMFSBOEUIFQSPEVDUDPOOFDUFEUPJUXJMMCFEJTQMBZFEPOUIF-$%EJTQMBZ

f8IFOBOFSSPSPDDVSTJOZPVSJOEPPSPVUEPPSVOJUT 1SPEVDUHSPVQEJTQMBZ"

t Address of the product with error and the error code will be displayed alternately.
&YBNQMFError 121 occurs for indoor unit No. 10 (Decimal digits)

Refers to the indoor unit Outdoor unit address Indoor unit Main address Error code
(Displayed in hexadecimal) (Displayed in hexadecimal)

f When an error occurs in your simplified wired remote controller


t Only an error code will be displayed. (No address will be displayed)
&YBNQMFError 601 has occurred on simplified remote controller

No. Error code Description of the error Remarks

1 t Communication error between wired remote controller ¥ Indoor unit -

t Communication error between Master ¥ Slave wired remote controller


2 -
- Error is only detected on slave wired remote controller

3 t Communication tracking error between wired remote controller ¥ Indoor unit -

4 t Exceeded maximum number of units (16 units) -

5 t 5XPPSNPSFXJSFESFNPUFDPOUSPMMFSTBSFTFUBT4MBWF -

t .FNPSZ FYUFSOBM30.
SFBEXSJUFFSSPS
5IJTFSSPSJTEFUFDUFEPOMZEVSJOHQPXFSSFTFU*GFSSPSPDDVSTPONFNPSZ
6 -
after power has turned on, it will not effect on operation of the wire
remote controller display and therefore error code will not be displayed.

32

$PNNVOJDBUJPOEJBHSBN

Individual control (1) Control 1 indoor unit with 1 wired remote controller

CONTROL SYSTEMS
F1/F2

INDIVIDUAL
Indoor unit
Outdoor unit
F3/F4
Wired remote controller

Control All connected indoor units


Display Operation status of the connected indoor unit

Group control (1) Control multiple indoor units with 1 wired remote controller

Outdoor unit Indoor unit

Wired remote controller


Ú Maximum 16 indoor units can be connected

Control All connected indoor units


Priority 1. Display the status of view master indoor unit
Display
Priority 2. Display the status of indoor unit which has the earliest Main address

Group control (2) Control multiple indoor units connected to different outdoor units with 1 wired remote controller

F1/F2

Outdoor unit
Outdoor unit

F3/F4
Wired remote controller

Ú Maximum 16 indoor units can be connected

Control All connected indoor units


Priority 1. Display the status of view master indoor unit
Display
Priority 2. Display the status of indoor unit which has the earliest Main address

f Caution
When controlling group of indoor units connected to different outdoor unit, address of the each outdoor unit must be set differently.
33
Control Systems

I Individual control systems


3. Wired remote controller
MWR-SH00N


$PNNVOJDBUJPOEJBHSBN

Group control (3) Control 1 or multiple indoor units with 2 wired remote controllers

F1/F2

Indoor unit
Outdoor unit F3/F4

Wired remote controller

Master Slave Master Slave Ú Maximum 16 indoor units can be connected

Control All connected indoor units


Priority 1. Display the status of view master indoor unit
Priority 2. Display the status of indoor unit which has the earliest Main address
Display
Ï 5XPXJSFESFNPUFDPOUSPMMFSTJEFOUJDBMMZEJTQMBZUIFPQFSBUJPOTUBUVTPGUIFJOEPPSVOJU
according to above priority.

Group control (4) Control multiple indoor units connected to different outdoor units with 2 wired remote controller

F1/F2

Outdoor unit
Indoor unit
Outdoor unit

F3/F4
Wired remote controller

Master Slave Ú Maximum 16 indoor units can be connected

Control All connected indoor units


Priority 1. Display the status of view master indoor unit
Priority 2. Display the status of indoor unit which has the earliest Main address
Display
Ï 5XPXJSFESFNPUFDPOUSPMMFSTJEFOUJDBMMZEJTQMBZUIFPQFSBUJPOTUBUVTPGUIFJOEPPSVOJU
according to above priority.

f Caution
When controlling group of indoor units connected to different outdoor unit, address of the each outdoor unit must be set differently.

Max. distance between the farthest indoor unit and wired 100m
remote controller : 100m

Wired remote controller

34
4. ERV wired remote controller
MWR-VH12N
1) Features
(Unit : mm)

CONTROL SYSTEMS
INDIVIDUAL
122.0

75.0
16.6

t8JSFESFNPUFDPOUSPMMFSGPS&37
t&37PQFSBUJPO0/0''DPOUSPM
t'BOTQFFEDPOUSPM
t0QFSBUJPONPEFTFUUJOH
t'JMUFSSFQMBDFNFOUBMBSNSFTFU
t0VUJOHNPEF
t4JNQMF0O0GGUJNFS

2) Product specification
Power supply %$7

Power consumption 1.5 W

0QFSBUJOHUFNQFSBUVSFSBOHF ¡$_¡$

0QFSBUJOHIVNJEJUZSBOHF 30 % RH~90 % RH

Communication XJSF1-$

.BYJNVNMFOHUIPGDPOOFDUJPO 100 m

.BYJNVNOVNCFSPGDPOUSPMMBCMFEFWJDFT &37T

CPNQBUJCMFQSPEVDU
&37 /FXDPNNVOJDBUJPO&37POMZ

35
Control Systems

I Individual control systems


4. ERV wired remote controller
MWR-VH12N
3) Description of parts


⑨ ⑦



② ④

⑩ ⑭

⑪ ⑮

⑫ ⑯

No. Name Description


*OEJDBUFTDVSSFOUPQFSBUJPONPEFXIFOUIF&37JTPQFSBUJOH
① Operation mode indicator
)FBU&9#Z1BTT"VUP2VJFU

Indicates when On timer is set.


Indicates when Off timer is set.
② Timer indicator
① 5JNFSNPEFo%JTQMBZTUIFTFUUJNFGPS0O0GGUJNFS .JONJOVUFT_.BYIPVST

② (FOFSBMNPEFo%JTQMBZTSFNBJOJOHUJNFCFGPSF5JNFSGVODUJPOXJMMFYFDVUF
③ 0VUJOHNPEFJOEJDBUPS Indicates when outing mode is on.
④ 'JMUFSDMFBOJOH QFSJPE
JOEJDBUPS Indicates when preset filter cleaning is required.
⑤ Fan speed indicator Indicates current fan speed settings.
⑥ S-Plasma ion(SPI) indicator (optional) Indicates when S-Plasma ion(SPI) function is on.
⑦ CO2 sensor indicator (optional) *OEJDBUFTJOEPPS$0EFOTJUZXIFOUIFTFOTPSJTPO *GUIF&37JTPQFSBUJOH

Indicates that inspection is required.


⑧ Indicates when an unavailable function which is not supported by indoor units is selected or
Inspection/Lock/Restricted indicator
when the button is locked.
Indicates when all buttons are locked.
Exhaust hood/Centralized/External
⑨ *OEJDBUFTXIFO&YIBVTUIPPE$FOUSBMJ[FE&YUFSOBMJOUFSMPDLJOHDPOUSPMJTPO
JOUFSMPDLJOHDPOUSPMJOEJDBUPS
⑩ 0O0GGCVUUPO 5PUVSO&37POPSPGG
5PTFMFDUBOPQFSBUJPONPEF )FBU&9J By-pass J Auto J Quiet)
⑪ 0QFSBUJPONPEFCVUUPO
J"WBJMBCMFPQFSBUJPONPEFJTBDDPSEJOHUP&377JFXNBTUFS
⑫ 5JNFSCVUUPO 5PTFUTJNQMFPOPGGUJNFSPSFYUFSOBMJOUFSMPDLJOHEFMBZ
5PTFUPSDBODFMUIFPQUJPO
⑬ 4FU$BODFMCVUUPO
J Press and hold the button for over 3 seconds to cancel the timer.
5PTFMFDUUIFGBOTQFFETPGJOEPPSVOJUT
⑭ 'BOTQFFECVUUPO J"WBJMBCMFGBOTQFFEEJGGFSTEFQFOEJOHPOUIFPQFSBUJPONPEFJOUIFGPMMPXJOHPSEFS-PXJ
Medium J High J5VSCPJ Auto.
① 5PUVSOUIFPVUJOHNPEFPOPSPGG
⑮ 0VUJOH'JMUFSSFTFUCVUUPO ② 5PUVSOUIFGJMUFSDMFBOJOHEJTQMBZPGG
J Press and hold the button for over 3 seconds to turn off the filter cleaning display.
5PNPWFUPUIFMBTUPSUIFOFYUJUFNTPSDIBOHFUIFTFUWBMVF
① Press the button to increase or decrease the set time during the timer is set.
J6QUPIPVST*ODSFBTFEFDSFBTFCZNJOVUFVOJU
⑯ 5JNFBEKVTUNFOUCVUUPO
J0WFSIPVST*ODSFBTFEFDSFBTFCZIPVSVOJU
② Press the button to increase or decrease the set time during external interlocking delay is set.
J Set the time by 1 minute unit between 30 minutes and 1 hour.

36
PCB

CONTROL SYSTEMS
INDIVIDUAL
No. Name Description
① 1PXFSDPNNVOJDBUJPO
① $POOFDUUPJOEPPSVOJU ''

connection terminal

4) Option function

UTFSTFUUJOHNPEF
f How to set
SEG used
12

Sub menu
Main menu

-FGU3JHIU

Press the buttons at Esc 6Q%PXO


the same time for over Set, Cancel
3 seconds

t 4&(JTEJWJEFEBTQBHFBDDPSEJOHUPEJTQMBZJOHPQFSBUJPONPEF <0O> <0GG>JDPO


PAGE 1 PAGE 2 PAGE 3 PAGE 4 PAGE 5

p p p p p

PAGE 6 PAGE 7 PAGE 8 PAGE 9 PAGE 10

p p p p

Main menu 4VCNFOV Function Default SEG in use 3BOHF Remarks


0 1 Reset User mode to default value 0 1 0 - Disabled, 1 - Reset
1 -PDLBMM 0 1 6OMPDL -PDL
2 -PDL0O0GGCVUUPO 0 1 6OMPDL -PDL
1 3 Partially -PDL.PEFCVUUPO 0 1 6OMPDL -PDL
lock
4 buttons -PDL'BOTQFFECVUUPO 0 1 6OMPDL -PDL
5 -PDL5JNFSCVUUPO 0 1 6OMPDL -PDL

37
Control Systems

I Individual control systems


4. ERV wired remote controller
MWR-VH12N
4) Option function

Service mode
f How to set
SEG used
12

Sub menu
Main menu

Press the buttons -FGU3JHIU


at the same time for
over 3 seconds Esc 6Q%PXO
Set, Cancel

Main 4VC SEG


Function Default value 3BOHF Remarks
menu menu in use
Reset the option setting of
1 &37XJSFESFNPUFDPOUSPMMFSUP 0 1 0 - Disabled, 1 - Reset
dafault value
0 Reset 3FTFU&37XJSFESFNPUF
2 0 1 0 - Disabled, 1 - Reset
controller to factory default
3 Power Master Reset2)* 0 1 0 - Disabled, 1 - Reset
4 Addressing Reset 0 1 0 - Disabled, 1 - Reset
Check the number of
1 0 1 0~16
connected indoor units
Check the number of
2 &37XJSFE 0 1 0~16
DPOOFDUFEWFOUJMBUPST &37

1 remote controller
Check the MICOM code of Page
3 information 0 MICOM code
&37XJSFESFNPUFDPOUSPMMFS 1~3
Check the software version of Page
4 0 Updated date
&37XJSFESFNPUFDPOUSPMMFS 1~3
&377JFX Page Address of registered device
1 4FUUJOH 5BSHFU

Master 1~3 Hexadecimal number4)*


Main address Main address
2 $IFDL4FUNBJOBEESFTT 1
of the target (00H~4FH, Hexadecimal digits)
Group address
RMC address
3 $IFDL4FU3.$BEESFTT 1 (00H~4FH, Hexadecimal
of the target
digits)3)*
"EESFTTPQUJPO
2 
Product option Page Option code of indoor units or
4 setting * $IFDLTFUUIFQSPEVDUPQUJPO
of the target 1~10 ventilators
Installation Refer to installation manuals
$IFDL4FUJOTUBMMBUJPOPQUJPO Page
5 option 1 of the of connected indoor units or
(1) 1~10
target ventilations
Installation Refer to installation manuals
$IFDL4FUJOTUBMMBUJPOPQUJPO Page
6 option 2 of the of connected indoor units or
(2) 1~10
target ventilations.

38
Main 4VC SEG
Function Default value 3BOHF Remarks
menu menu in use
$IFDL4FUJOEPPSVOJUWJFX Indoor unit Page Address of registered device No

CONTROL SYSTEMS
1 

$IFDL4FUWJFX master view Master 1~3 Hexadecimal number * function


3

INDIVIDUAL
master &37WJFX Page Address of registered device
2 $IFDL4FU&37WJFXNBTUFS 

master 1~3 Hexadecimal number *


$IFDL4FU 4FUUJOH.BTUFS4MBWF&37
1 0 1 0 - Master, 1 - Slave
option function wired remote controller
4
PG&37XJSFE Setting external
2 0 1 0 - No use, 1 - Use
remote controller interconnection control usage
Page
1 Air exhaust RPM none 0~9999
1~2
Page
2 Air intake RPM none 0~9999
1~2
3 Indoor temperature none 1 0~99
$IFDL4FU
5 4 ventilator Outdoor temperature none 1 0~99
5 &37
Indoor humidity none 1 0~99
6 Outdoor humidity none 1 0~99
Page
7 CO² sensor none 0~9999
1~2


8 FAN Step * none 1 0~31



 :PVNVTUTFMFDUUIFUBSHFUFEEFWJDFJOUIFTVCNFOVBOEUIFOTFUUIFBEESFTTPQUJPO

 1PXFS.BTUFS3FTFUJTBTFUUJOHGPSTVQQMZJOHUIFNPTUTUBCMFQPXFSUPUIF&37XJSFESFNPUFDPOUSPMMFSXIFOUIFDPOUSPMMFSJT
connected to multiple indoor units or ventilators as a group.

 3.$ 
_'3.$ 
_' )FYBEFDJNBMEJHJUT

RMC(2) can be set up to E only when RMC(1) is set as F.


(RMC(1) : Group channel, RMC(2) : Group address)
4)* Displays ventilator address (Hexadecimal digits)
 &Y
##JT&37.BJOBEESFTT
5)* Fan Step can be set when only one ventilator is connected.

System reset
t3FTFUUIFQPXFSPGUIF&37XJSFESFNPUFDPOUSPMMFS

Press and hold for over 5 seconds to


power reset

39
Control Systems

I Individual control systems


4. ERV wired remote controller
MWR-VH12N
5) Display

Error display
&SSPSDPEFTGPSUIF&37XJSFESFNPUFDPOUSPMMFSBOEUIFQSPEVDUDPOOFDUFEUPJUXJMMCFEJTQMBZFEPOUIF-$%EJTQMBZ

f8IFOBOFSSPSPDDVSTJOZPVSJOEPPSPVUEPPSVOJUT 1SPEVDUHSPVQEJTQMBZ"

t Address of the product with error and the error code will be displayed alternately.
Example : Error 101 occurs for indoor unit No. 10 (Decimal digits)

Indoor unit address


Refers to the indoor unit (Displayed in hexadecimal)

f8IFOBOFSSPSPDDVSTJOZPVSWFOUJMBUPS &37
BOE&37JOUFSGBDFNPEVMF 1SPEVDUHSPVQEJTQMBZC

t Address of the product with error and the error code will be displayed alternately.
&YBNQMF&SSPSPDDVSTGPSWFOUJMBUPS &37
/P %FDJNBMEJHJUT

&37BEESFTT %JTQMBZFEJOIFYBEFDJNBM

3FGFSTUPUIF&37 &37JOUFSGBDFNPEVMFBEESFTT %JTQMBZFEJOIFYBEFDJNBM

f When an error occurs in your ERV wired remote controller


t Only an error code will be displayed. (No address will be displayed.)
&YBNQMF&SSPSIBTPDDVSSFEBUZPVS&37XJSFESFNPUFDPOUSPMMFS

Error codes
Display Description
t5SBDLJOHFSSPSCFUXFFO&37XJSFESFNPUFDPOUSPMMFSBOEWFOUJMBUPS &37
GPSPWFSNJOVUFT
tNo indoor unit installed for interlocking function
t0WFS&37JOEPPSVOJUTJOTUBMMFE
t5IF&37XJSFESFNPUFDPOUSPMMFSNVTUCFSFTFUBGUFSDIFDLJOHUIFOVNCFSPGJOTUBMMFE&37JOEPPSVOJUT
t*OTUBMMBUJPOFSSPSJO4MBWF&37XJSFEremote controller
8IFOUXPPSNPSFTMBWF&37XJSFESFNPUFDPOUSPMMFSTBSFJOTUBMMFE

tNo communication between Master and Slave wired remote controllers


t$PNNVOJDBUJPOFSSPSCFUXFFO&37XJSFESFNPUFDPOUSPMMFSBOE&37JOEPPSVOJUT
8IFOUIFSFTOPDPNNVOJDBUJPOCFUXFFOUIFEFWJDFTGPSNJOVUFTBGUFSTVDDFTTGVM&37XJSFESFNPUFDPOUSPMMFS
tracking)
tEEPROM error

40

$POOFDUJPOEJBHSBN

Individual control 1 ERV, 1 wired remote controller

&37 &37 &37

CONTROL SYSTEMS
COM2(F3, F4) COM2(F3, F4) COM2(F3, F4)

INDIVIDUAL
&37XJSFESFNPUFDPOUSPMMFS &37XJSFESFNPUFDPOUSPMMFS &37XJSFESFNPUFDPOUSPMMFS

Control All connected ERVs


Display 4UBUVTPGDPOOFDUFE&37T

Group control (1) $POUSPMNVMUJQMF&37TXJUITJOHMFXJSFESFNPUFDPOUSPMMFS

&37 &37 &37

COM2(F3, F4) COM2(F3, F4)

&37XJSFESFNPUFDPOUSPMMFS

Control All connected ERVs


1SJPSJUZ%JTQMBZUIFPQFSBUJPOTUBUVTPG7JFX.BTUFS&37
Display
1SJPSJUZ%JTQMBZUIFPQFSBUJPOTUBUVTPG&37XIJDIIBTUIFFBSMJFTU.BJOBEESFTT

$POUSPMNVMUJQMF&37TDPOOFDUFEUPEJGGFSFOU&37JOUFSGBDFNPEVMFTXJUITJOHMFXJSFE
Group control (2)
remote controller
&37JOUFSGBDFNPEVMF

COM1(F1, F2)
CN2
BLK

CN4
CN3
RED

&37

&37JOUFSGBDFNPEVMF
COM2(F3, F4)
CN2
BLK

CN4
CN3
RED

COM1(F1, F2)

&37 &37XJSFESFNPUFDPOUSPMMFS

COM2(F3, F4)

Control All connected ERVs


1SJPSJUZ%JTQMBZUIFPQFSBUJPOTUBUVTPG7JFX.BTUFS&37
Display
1SJPSJUZ%JTQMBZUIFPQFSBUJPOTUBUVTPG&37XIJDIIBTUIFFBSMJFTU.BJOBEESFTT

41
Control Systems

I Individual control systems


4. ERV wired remote controller
MWR-VH12N

$POOFDUJPOEJBHSBN

Mixed installation $POOFDUJOEPPSVOJUTBOE&37TUPBTJOHMF&37XJSFESFNPUFDPOUSPMMFS

Outdoor unit

COM1(F1, F2) COM1(F1, F2) COM1(F1, F2)

&37

Indoor unit Indoor unit Indoor unit

COM2(F3, F4) COM2(F3, F4) COM2(F3, F4)

&37XJSFESFNPUFDPOUSPMMFS

Control All connected ERVs


1SJPSJUZ%JTQMBZUIFPQFSBUJPOTUBUVTPG7JFX.BTUFS&37
Display
1SJPSJUZ%JTQMBZUIFPQFSBUJPOTUBUVTPG&37XIJDIIBTUIFFBSMJFTU.BJOBEESFTT

f Caution
Š$POOFDUUIFEFWJDFTBTUIFBCPWFEJBHSBNGPSFYUFSOBMJOUFSMPDLJOHDPOUSPMXIJDIJOUFSMPDL&370O0GGXJUIJOEPPSVOJU0O0GG
Š&37XJSFESFNPUFDPOUSPMMFSDBOOPUDPOUSPMJOEPPSVOJUT
Š&37XJSFESFNPUFDPOUSPMMFSBOEXJSFESFNPUFDPOUSPMMFSGPSJOEPPSVOJUTDBOOPUCFDPOOFDUFEBUUIFTBNFUJNF "838&/FUD

MBYJNVNMFOHUIPGDPOOFDUJPO
.BYEJTUBODFCFUXFFOUIFGBSUIFTU&37BOEXJSFESFNPUF
controller : 100m 100m

42
II. Centralized control systems
1 Interface module . . . . . . . . . . . . . . . . . . . 44
2 ERV interface module . . . . . . . . . . . . . . . 49
3 OnOff controlle . . . . . . . . . . . . . . . . . . . . . 55

CONTROL SYSTEMS
CENTRALIZED
4 Touch centralized controller . . . . . . . . . . . 62
5 Operation mode selection switch . . . . . . 73

43
Control Systems

II Centralized control systems


1. Interface module
MIM-N01

1) Features
tCommunication interface module between new communication ERV and controller
tConnect 1 ERV interface module to Max. 16 ERVs
tIndividual control – Maximum 16 ERVs
tGroup control – Maximum 16 groups
tSupported communication type
1) Conventional communication outdoor unit ↔ New communication upper level controller
2) New communication outdoor unit ↔ Conventional communication upper level controller
❋ This interface module does not support conenction between
CN4

Conventional communication outdoor unit ↔ Conventional communication upper level controller /


Y-GRN
RED

New communication outdoor unit ↔ New communication upper level controller


YEL

CN3 CN2
RED BLK

59.4 (Unit : mm)

96.1
CN4

Y-GRN
RED
YEL

CN3 CN2
RED BLK

2) Product specification
Power Supply DC12V
Power Consumption 2.4 W
Operating Temperature range -10°C~50°C
Operating Humidity range 10%RH~90%RH
Communication RS485 x 2
Max.Communication Length 1000M
1) New communication outdoor unit ¥ Conventional communication
upper level controller
t''PVUEPPSVOJU
t33VQQFSMFWFMDPOUSPMMFS
Maximum number of connection 2) Conventional communication outdoor unit ¥ New communication
upper level controller
t''PVUEPPSVOJU
t335PUBMVQUPVQQFSMFWFMDPOUSPMMFST 0OMZ%.4 
BACnet/Lonworks Gateway connection is allowed)

44
Compatible Models
(1) New communication outdoor unit ¥ Conventional communication upper level controller
Outdoor unit AM7777X777777
① OnOff controller : MCM-A202D
② DMS2 : MIM-D00A
Upper level controller ③ BACnet Gateway : MIM-B17
④ Lonworks Gateway : MM-B18
⑤ S-NET mini : MST-S3W

> Function controller and S-NET 2 Plus are not supported.


t/FXDPNNVOJDBUJPO0VUEPPSVOJU .*./ .$."% 'VODUJPODPOUSPMMFS 9

t/FXDPNNVOJDBUJPO0VUEPPSVOJU .*./ .$."% 4/&51MVT 9

CONTROL SYSTEMS
(2) Conventional communication outdoor unit ¥ New communication upper level controller

CENTRALIZED
Outdoor unit %7.1MVT   $"$
① OnOff Controller: MCM-A202DN
② DMS2 : MIM-D00AN
Upper level controller ③ BACnet gateway : MIM-B17N
④ Lonworks gateway : MIM-B18N
⑤ Touch centralized controller : MCM-A300N

3) Description of parts
⑧ No. Name Description
F1/F2 communication Communication connector that connects to outdoor unit /

connector ''

② Power connector DC 12V
Communication indicator LED
(Left LED 3 : No function

Middle LED 1 : Blinks during it communicates with upper
③ Communication LED
level controller
Right LED 2 : Blinks during it communicates with
② ⑤ outdoor unit and indoor unit)
④ Address setting switch Sets the address of interface module
Software update 6TJOHUIJTDPOOFDUPS *OUFSGBDFNPEVMFTPGUXBSFDBOCF
④ ⑤
connector updated
① Displays the communication status between interface
⑥ 7-segment
module and outdoor unit/ERV
Upper level controller Communication connection channel to upper level
⑦ ⑦
communication channel controller R1/R2

SW1 Description
On : Manual address setting /
1
Off : Auto address setting
⑧ DIP switch 2 No function
3 No function
4 No function

; Note
X 8IFODPOOFDUJOHUPUIFDPOWFOUJPOBMDPNNVOJDBUJPODPOUSPMMFS BEESFTTNVTUCFTFUNBOVBMMZ
regardless to the SW1 setting.8IFOTFUUJOHUIFBEESFTTNBOVBMMZ NBLFTVSFUPTFUUIFBEESFTT
that is not assigned to other deivce already.
X 8IFODPOOFDUJOHUPUIFOFXDPNNVOJDBUJPODPOUSPMMFS 48NVTUCF0/UPTFU
UIFBEESFTTNBOVBMMZ BOENBLFTVSFUPTFUUIFBEESFTTUIBUJTOPUBTTJHOFEUPPUIFS
compatible interface module or outdoor units.

45
Control Systems

II Centralized control systems


1. Interface module
MIM-N01

4) Connection diagram

N ew communication outdoor unit ¥ Conventional communication upper level controller

C1/C2 C1/C2

Conventional communication

R1/R2
R1/R2 R1/R2 New communication

MIM-N01 MIM-N01 MIM-N01 MIM-N01

'' '' '' ''

Conventional communication outdoor unit ¥ New communication upper level controller

R1/R2
New communication

Conventional communication

MIM-N01 MIM-N01

'' ''

46
5) Connection

Connecting with OnOff controller


f Conventional communication outdoor unit ¥ New communication OnOff controller (MCM-A202DN)
f New communication outdoor unit ¥ Conventional communication OnOff controller (MCM-A202D)
OnOff controller

CONTROL SYSTEMS
CENTRALIZED
Connecting to Touch centralized controller
f Conventional communication outdoor unit ¥ New communication Touch centralized controller (ACM-A300N)
Touch centralized controller

Connecting to DMS 2 / BACnet GW / Lonwoks GW


f Conventional communication outdoor unit ¥ New communication DMS2 (MIM-D00AN) / BACnet GW (MIM-B17N) /
Lonworks GW (MIM-B18N)
f New communication outdoor unit ¥ Conventional communication DMS2 (MIM-D00AN) / BACnet GW (MIM-B17N) /
Lonworks GW (MIM-B18N)
DMS 2 / BACnet GW / Lonworks GW

; Note
X When connecting AM7777X777777PVUEPPSVOJUBOEOFXDPNNVOJDBUJPODPOUSPMMFS ZPVEPOhUIBWFUPDPOOFDUUIFNXJUI.*./
X 8IFODPOOFDUJOH$POWFOUJPOBMDPNNVOJDBUJPOPVUEPPSVOJUBOEDPOUSPMMFS FY.$."%
.*.#%PS.*.#&NVTUCFVTFE

47
Control Systems

II Centralized control systems


1. Interface module
MIM-N01

6) Display

Checking the operation

Software version is Display the set value Display the address of Outdoor unit detected Tracking completed
displayed after power of the rotary switch the interface module during tracking
is supplied 7 Displays the Main address of the communicating
indoor units alternately [Displays the indoor unit
that is set as (centralized control)]
Error display
f Communication error between outdoor unit f Communication error between upper level controller and
and the interface module the interface module after tracking has been completed

7 FF will be displayed to the indoor unit that has lost 7 When E1, E2 occurs at the same time, only E1
communication during normal communication. will be displayed.

f Interface module tracking failure

(1) Communication error between conventional communication outdoor unit ¥ New communication upper level controller
after tracking has been completed
t It will be displayed after failing 80 times of communication trial after interface module has started tracking (approximately 3 minutes)
(2) Communication error between New communication outdoor unit ¥ Conventional communication upper level controller
after tracking has been completed
t It will be displayed after failing the tracking process over 10 minutes from the interface module has started tracking.

f When problem occurs on EEPROM f When same address was assigned to more than one
interface module (Only detected when new communication
upper level controller is connected to conventional
communication outdoor unit)

Error display table


Display on new Display on Conventional
Error Display Error Code communication upper communication upper
level controller level controller
EEPROM Er-E4 E654 E654 -

Overlapped address Er-E5 E108 E108 -

Tracking failure Er-E3 E604 E201 -

Indoor unit communication error Er-E1 E615 E201 or E101 E615

Outdoor unit communication error Er-E1 E616 E202 E616


Upper level controller communication
48 error (Conventional type)
Er-E2 - - -
2. ERV interface module
MIM-N10

1) Features
tCommunication interface module between new communication ERV and controller
tConnect 1 ERV interface module to Max. 16 ERVs
tIndividual control – Maximum 16 ERVs
tGroup control – Maximum 16 groups
tSupported communication type
1) Conventional communication ERV ↔ New communication upper level controller
2) New communication ERV ↔ Conventional communication upper level controller
3) New communication ERV ↔ New communication upper level controller
CN4

❋ This interface module does not support connection between Conventional communication
ERV ↔ Conventional communication upper level controller
Y-GRN
RED
YEL

CONTROL SYSTEMS
CENTRALIZED
CN3 CN2
RED BLK

59.4 (Unit : mm)

96.1
CN4

Y-GRN
RED
YEL

CN3 CN2
RED BLK

2) Product specification
Power Supply DC12V
Power Consumption 2.4 W
Operating Temperature range -10°C~50°C
Operating Humidity range 10%RH~90%RH
Communication RS485 x 2
Maximum Communication Length 1000M
1) New communication ERV ↔ Conventional communication upper level controller
 ''&37&37T
R1/R2 : 1 upper level controller
2) Conventional communication ERV ↔ New communication upper level controller
 ''&37&37T
Maximum number of connection  335PUBMVQUPVQQFSMFWFMDPOUSPMMFST 0OMZ%.4 #"$OFU(8-POXPSLT(8
connection is allowed)
3) New communication ERV ↔ New communication upper level controller
 ''&37&37T
 335PUBMVQUPVQQFSMFWFMDPOUSPMMFST 0OMZ%.4 #"$OFU(8-POXPSLT(8
connection is allowed)

49
Control Systems

II Centralized control systems


2. ERV interface module
MIM-N10

2) Product specification

Compatible Models

(1) New communication ERV ¥ Conventional communication upper level controller


ERV New communication ERV
① OnOff controller : MCM-A202D
② DMS2 : MIM-D00A
Upper level controller ③ BACnet GW : MIM-B17
④ Lonworks GW : MIM-B18
⑤ S-NET mini : MST-S3W

❋ 'VODUJPODPOUSPMMFSBOE4/&51MVTBSFOPUTVQQPSUFE
 t/FXDPNNVOJDBUJPO&37 .*./ .$."% 'VODUJPODPOUSPMMFS 9

 t/FXDPNNVOJDBUJPO&37 .*./ .$."% 4/&51MVT 9

(2) Conventional communication ERV ¥ New communication upper level controller


ERV Conventional communication ERV (Except mechanical ERV)
① OnOff controller : MCM-A202DN
② DMS2 : MIM-D00AN
Upper level controller ③ BACnet GW : MIM-B17N
④ Lonworks GW : MIM-B18N
⑤ Touch centralized controller : MCM-A300N

(3) New communication ERV ¥ New communication upper level controller


ERV New communication ERV
① OnOff controller : MCM-A202DN
② DMS2 : MIM-D00AN
Upper level controller ③ BACnet GW : MIM-B17
④ Lonworks GW : MIM-B18
⑤ S-NET mini : MST-S3W

50
3) Description of parts
⑧ No. Name Description
''
Communication terminal that connects to outdoor unit /
① communication
⑥ ''PG&37
connector
② Power connector DC12V
Communication indicator LED
③ (Left LED 3 : No function
Communication
③ Middle RED : Blinks during it communicates with upper
LED
⑤ level controller

CN4

Right Y-GRN : Blinks during it communicates with ERV)


Y-GRN
RED
YEL

Address setting
④ Sets the address of interface module
switch

CN3 CN2 Software update 6TJOHUIJTDPOOFDUPS *OUFSGBDFNPEVMFTPGUXBSFDBOCF
① RED BLK

connector updated

CONTROL SYSTEMS
Displays the communication status between interface
⑥ 7-segment

CENTRALIZED
module and ERV

Upper level controller
⑦ communication Communication terminal to upper level controller R1/R2
channel
SW4 SW5

12 12 SW5 - No use
SW4 Description
0'' "VUPBEESFTTTFUUJOH TXJUDINVTUCFEPXO

1
0/ .BOVBMBEESFTTTFUUJOH TXJUDINVTUCFVQ

0'' /FXDPNNVOJDBUJPOVQQFSMFWFMDPOUSPMMFS↔
⑧ DIP switch Conventional communication ERV)
(Conventional communication upper level
2
controller ↔ New communication ERV)
ON (New communication upper level controller ↔
New communication ERV)
✽8IFOVQHSBEJOHUIFQSPHSBN 48NVTUCFTFUUP0/
status before proceeding upgrade regardless of the installation
condition.
"GUFSDPNQMFUJOHUIFEPXOMPBE TFUUIF%*1TXJUDI
correctly according to installation condition before supplying
the power.

; Note
Š8IFODPOOFDUJOHUPUIFDPOWFOUJPOBMDPNNVOJDBUJPODPOUSPMMFS BEESFTTNVTUCF
TFUNBOVBMMZSFHBSEMFTTUPUIF48TFUUJOH8IFOTFUUJOHUIFBEESFTTNBOVBMMZ 
make sure to set the address that is not assigned to other deivce already.
Š8IFODPOOFDUJOHUPUIFOFXDPNNVOJDBUJPODPOUSPMMFS 48NVTUCF0/UPTFU
UIFBEESFTTNBOVBMMZ BOENBLFTVSFUPTFUUIFBEESFTTUIBUJTOPUBTTJHOFEUP
other compatible interface module or outdoor units.

51
Control Systems

II Centralized control systems


2. ERV interface module
MIM-N10

4) Connection diagram

New communication ERV ↔ Conventional communication upper level controller

C1/C2 C1/C2

Conventional
communication

R1/R2 R1/R2 R1/R2 New


communication
MIM-N10 MIM-N10 MIM-N10 MIM-N10

'' '' '' ''

Conventional/new communication ERV ↔ New communication upper level controller

R1/R2 New
communication

MIM-N10 MIM-N10 Conventional


communication

'' ''

52
5) Connection

Connecting with OnOff controller

▶ Conventional communication ERV ↔ New communication OnOff controller (MCM-A202DN)


▶ New communication ERV ↔ Conventional communication OnOff controller (MCM-A202D)
OnOff controller

CONTROL SYSTEMS
CENTRALIZED
; Note
Š8IFODPOOFDUJOHDPOWFOUJPOBMDPNNVOJDBUJPO&37BOE0O0GGDPOUSPMMFS .$."%
.*.#%PS.*.#&
must be used.

53
Control Systems

II Centralized control systems


2. ERV Interface module
MIM-N10

5) Connection

Connecting with Touch centralized controller

▶ Conventional communication ERV ↔ New communication Touch centralized controller (MCM-A300N)


▶ New communication ERV ↔ Conventional communication Touch centralized controller (MCM-A300N)
Touch centralized controller

Connecting with DMS2 / BACnet GW / Lonwoks GW

▶ Conventional communication outdoor unit ↔ New communication DMS2(MIM-D00AN) / BACnet GW (MIM-B17N) /


Lonworks GW (MIM-B18N)
▶ New communication outdoor unit ↔ Conventional communication DMS2(MIM-D00A) / BACnet GW (MIM-B17) /
Lonworks GW (MIM-B18)
DMS 2 / BACnet GW / Lonworks GW

6) Checking the operation


 8IFOJOJUJBMJ[JOHQPXFSTVQQMZ  will be indicated after indicating the program cord.
 "GUFSSFDFJWJOHWBMJEDPNNVOJDBUJPONPSFUIBOPODF  will be indicated.
 8IFOUIFDPNNVOJDBUJPOJTOPSNBM UIF."*/"%%3&44PGUIFWFOUJMBUPSUIBUDBOCFDPOUSPMMFECZUIF&37JOUFSGBDFNPEVMFJT
indicated in order.
 8IFOUIFSFJTOPDPNNVOJDBUJPOCFUXFFOUIFWFOUJMBPUSBOEUIF&37JOUFSGBDFNPEVMFGPSNPSFUIBONJOVUFT  ↔ will be
indicated alternately.
 8IFOUIFSFJTOPDPNNVOJDBUJPOCFUXFFOBO&37JOUFSGBDFNPEVMFBOEBOVQQFSMFWFMDPOUSPMMFSGPSNPSFUIBONJOVUFT 
↔ will be indicated alternately.
 8IFOUIF&37JOUFSGBDFNPEVMFUSBDLJOHJTOPUDPNQMFUF  ↔ will be indicated alternately.
 8IFOUIFSFhTFSSPSPO&&130.PGUIF&37JOUFSGBDFNPEVMF  ↔ will be indicated alternately.
 8IFOTBNFBEESFTTXBTTFUUPNVMUJQMF&37JOUFSGBDFNPEVMFT  ↔ will be indicated alternately.
 8IFONPSFUIBOWFOUJMBUPSTBSFJOTUBMMFE  ↔ will be indicated alternately.
8IFOWFOUJMBUPSTBOEJOEPPSVOJUTBSFJOTUBMMFEUPHFUIFS  ↔ will be indicated alternately.

54
3. OnOff controller
MCM-A202DN

1) Features
6OJUNN

CONTROL SYSTEMS
CENTRALIZED
t.BYJNVNHSPVQDPOUSPMMFS .BYVOJUT

t8IPMF(SPVQ*OEJWJEVBMJOEPPSVOJUDPOUSPM 0O0GG

t3FTUSJDUJPOPOUIFVTFPGXJSFMFTTXJSFESFNPUFDPOUSPMMFSTBOEFYUFSOBMDPOUBDUDPOUSPM
t$PPMJOHBOEIFBUJOHNPEFDPOUSPM
t*OEPPSVOJUFSSPSEJTQMBZ

2) Product specification
Power supply "$7_7 )[
Power consumption 8
Operating Temperature range °$_°C
Operating Humidity range 3)_3)
Communication 34Y 33

Max. Communication length N

%FWJDF /VNCFS
*OEPPSVOJUT JODMVEJOH&37 .$6
 .BYJNVNJOEPPSVOJUT &37TBOE.$6T

Set layer 0VUEPPSVOJU 


0O0GGDPOUSPMMFS
5PUBM
5PVDIDFOUSBMJ[FEDPOUSPMMFS

Max. %FWJDF /VNCFS


connectable *OEPPSVOJUT JODMVEJOH&37 .$6

number of 0VUEPPSVOJU JODMVEJOHDPNQBUJCMF
device 
JOUFSGBDFNPEVMF.*./

0O0GGDPOUSPMMFS
Control layer  XIFO%.4 #"$OFUHBUFXBZ 
5PVDIDFOUSBMJ[FE
-PO8PSLTHBUFXBZJTDPOOFDUFE

DPOUSPMMFS
%.4
#"$OFU(8 5PUBM
-PO8PSLT(8

Compatible product
0VUEPPSVOJU AM7777X777777
0O0GGDPOUSPMMFS .$."%/

5PVDIDFOUSBMJ[FEDPOUSPMMFS .$."/

$POUSPMMFS %.4 .*.%"/

#"$OFU(8 .*.#/

-POXPSLT(8 .*.#/


7 Conventional communication outdoor unit requires interface module (MIM-N01) to establish connection
7 MIM-B13D, MIM-B13E, MIM-B04A Interface modules cannot be connected.
7 To connect ERV, MIM-N10 interface module is required. 55
Control Systems

II Centralized control systems


3. OnOff controller
MCM-A202DN

3) Description of parts




COOL
AUTO
HEAT


No. Name Description


ƒ It lights on when more than one indoor unit operates.
① Indoor unit operation LED
ƒ It flickers during indoor unit tracking process after power reset.
② All ON button Press All ON button to turn on all the indoor units.
③ All OFF button 1SFTT"MM0''CVUUPOUPUVSOPGGBMMUIFJOEPPSVOJUT
ƒ It lights on when one indoor unit of the group is operating.
Group indoor unit ƒ It also flickers when indoor unit has an error.

operation LED ƒ%VSJOHUSBDLJOHJOEPPSVOJUT -&%XIPTFOVNCFSJTFRVJWBMFOUUPJOEPPSVOJU3.$ 

address flickers.
⑤ Indoor unit control button 1SFTTFBDIJOEPPSVOJUCVUUPOUPDPOUSPMUIFFRVJWBMFOUVOJUPQFSBUJPO
Set operation mode selection switch to a certain mode and press indoor unit control
Operation mode selection
⑥ CVUUPOUPDPOUSPMPQFSBUJPONPEF8IFOFWFSQSFTTJOHBOZCVUUPOPOUIFDPOUSPMMFS TFU
switch
operation mode is delivered to the indoor unit.
ƒ C1 C2 : No function
⑦ Communication terminal
ƒ33$POOFDUUP0VUEPPSVOJU %.4 0O0GGDPOUSPMMFS
⑧ Power terminal AC200V~240V connection

; Note
Š Press button 11 and button 15 together for 5 seconds to reset the OnOff controller.

Software reset

56
Address & option switch
SW02 DIP SW Description
K1 K2 Restriction setting on wired/wireless remote control use
SW01
Cool
0'' 0'' Wired/Wireless remote control use is allowed all the time. Level 0
Auto
Option switch
Heat Wired/Wireless remote control use is allowed only if indoor unit is ON
by the OnOff controller.
ON 0''
8IFOJOEPPSVOJUTBSF0''CZUIF0O0GGDPOUSPMMFS SFNPUFDPOUSPMVTF
is prohibited. Level 1
Indoor unit RMC(1) The use of wireless/wired remote controllers and external contact
0'' ON
matching address control is prohibited. Level 2

CONTROL SYSTEMS
ON ON No function

CENTRALIZED
ƒ0''0O0GGDPOUSPMMFSVTF
K3
ƒ ON : Not use Onoff controller "MMCVUUPOTEPOhUXPSL

K4 No function

4) Optional function

Remote control restriction

f LEVEL 0
t ‘Allowed’ remote controller

f LEVEL 1
t Turned on by OnOff controller
– ‘Allowed’
t Turned off by OnOff controller
– ‘Prohibited’

f LEVEL 2
t ‘Prohibited’ remote controller

57
Control Systems

II Centralized control systems


3. OnOff controller
MCM-A202DN

4) Optional function

Operation mode selection switch


*UJTNBJOMZVTFEUPTFUJOEPPSVOJUPQFSBUJPONPEFUP$PPMJOH )FBUJOHPS"VUP

Indoor unit 1 Indoor unit 2 Indoor unit 3

Indoor unit operation


tCooling mode set  $PPMJOHPQFSBUJPOJOMBTUDPPMJOHTFUUFNQFSBUVSF GBOTQFFEBOEGBOEJSFDUJPO
tHeating mode set  )FBUJOHPQFSBUJPOJOMBTUIFBUJOHTFUUFNQFSBUVSF GBOTQFFEBOEGBOEJSFDUJPO
tAuto mode set  *OEPPSVOJUTLFFQUIFJSDVSSFOUPQFSBUJPONPEF TFUUFNQFSBUVSF GBOTQFFEBOEGBOEJSFDUJPO

Ú0QFSBUJPONPEFTFMFDUJPOTXJUDIEPFTOhUMPDLUIFJOEPPSVOJUPQFSBUJPONPEF

5) Connection diagram

Set layer connection (F1/F2)


t8IFO0O0GGDPOUSPMMFSPOMZDPOUSPMTJOEPPSVOJUTPGPVUEPPSVOJU UIFOJUDBOCFDPOOFDUFEUP''MJOFPGPVUEPPSVOJUPSJOEPPSVOJU
tMax. 16 Controllers can be connected to same communication line.
7Connectable controller: - OnOff controller (MCM-A202DN)
- Touch centralized controller (MCM-A300N)

Set layer

F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2

Set layer

F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2

58
Control layer connection (R1/R2)
t.BY$POUSPMMFSTDBOCFDPOOFDUFEUPTBNFDPNNVOJDBUJPOMJOF *ODBTFPG%.4#"$OFUHBUFXBZ-PO8PSLTHBUFXBZDPOOFDUJPO .BY

t.BYPVUEPPSVOJUTDBOCFDPOOFDUFEUPTBNFDPNNVOJDBUJPOMJOF *ODMVEFTJOUFSGBDFNPEVMF.*./

7Connectable controller : - Touch centralized controller (MCM-A300N).
- OnOff controller (MCM-A202DN).
%.4 .*.%"/
#"$OFUHBUFXBZ .*.#/
-PO8PLTHBUFXBZ .*.#/
0OMZPOFPGUIFUISFFNPEFMT

(1) Connection with outdoor unit


t8IFO0O0GGDPOUSPMMFSDPOUSPMTJOEPPSVOJUTPGNVMUJQMFPVUEPPSVOJUT UIFOJUTIPVMECFDPOOFDUFEUP33MJOFPGPVUEPPSVOJUT

F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2

CONTROL SYSTEMS
CENTRALIZED
F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2

Control layer

(2) Connection with DMS2/BACnet GW/Lonworks GW

f Case1

F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2

F1 F2 R1 R2

Ex.) DMS2 (MIM-D00AN)

Control layer

59
Control Systems

II Centralized control systems


3. OnOff controller
MCM-A202DN

5) Connection diagram

Control layer connection (R1/R2)

(2) Connection with DMS2/BACnet GW/Lonworks GW


f Case2

F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2

F1 F2 R1 R2

Ex.) DMS2 (MIM-D00AN)

Control layer

f Caution
t 8IFO0O0GGDPOUSPMMFSJTDPOOFDUFEUP0VUEPPSVOJUhT''MJOF ZPVDBOOPUDPOOFDU%.4UP0O0GGDPOUSPMMFShT33MJOF

Set layer

F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2

%.4 #"$OFUHBUFXBZ -PO8PSLTHBUFXBZNVTUCF


connected to Control layer

Ex.) DMS2 (MIM-D00AN)

60
6) Display

Various LED display


"GUFSQPXFSSFTFUUPUIF0O0GGDPOUSPMMFS JUDBSSJFTPVUJOEPPSVOJUUSBDLJOHQSPDFTT

Main : 0 Main : 1 Main : 2


Address : 1 RMC(1) : 1 RMC(1) : 1 RMC(1) : 1
RMC(2) : 0 RMC(2) : 1 RMC(2) : 2
R1/R2

CONTROL SYSTEMS
CENTRALIZED
Main : 0 Main : 1 Main : 2
RMC(1) : 1 RMC(1) : 1 RMC(1) : 1
RMC(2) : 3 RMC(2) : 4 RMC(2) : 5
R1/R2

Main : 0 Main : 1 Main : 2


RMC(1) : 2 RMC(1) : 2 RMC(1) : 2
RMC(2) : 6 RMC(2) : 7 RMC(2) : 8
R1/R2

(1) OnOff controller only communicate with indoor units which has same RMC(1) address with OnOff
controller's address.
(2) During tracking indoor units, LED whose number is equivalent to indoor unit RMC(2) address flickers.
tIn LED 00  LED 01  LED 02  LED 03  LED 04  LED 05 order

61
Control Systems

II Centralized control systems


4. Touch centralized controller
MCM-A300N

1) Features

Unit : mm
203

161
tJODIUPVDI-$%DPOUSPMMFS
t$POUSPMTNBYJNVNJOEPPSVOJUT

38
t$POUSPMTNBYJNVN[POFT
t4DIFEVMFDPOUSPM *OEPPSVOJUVTBHFSFTUSJDUJPO 
View indoor unit error history

2) Product specification
Power supply "$7_7 )[
Power consumption 110W
Operating temperature range 0°C~40°C
Operating humidity range 30%RH~90%RH
Communication 34Y ''PS33

External Digital Output 1


communication
port Digital Input 2

Maximum RS485 1000m


connection Digital Output 100m
length Digital Input 100m

Device Number
*OEPPSVOJUT JODMVEJOH&37 .$6
 .BYJNVNJOEPPSVOJUT &37TBOE.$6T

Set layer Outdoor unit 1


OnOff controller
Total 16
Touch centralized controller

Max. Device Number


connectable *OEPPSVOJUT JODMVEJOH&37 .$6
128
number of Outdoor unit (including
device 16
interface module MIM-N01)
Control layer OnOff controller
 XIFO%.4 #"$OFUHBUFXBZ 
Touch centralized
LonWorks gateway is connected)
controller
DMS2
BACnet GW Total 1
LonWorks GW

62
Compatible product
Outdoor unit AM7777X777777
OnOff controller (MCM-A202DN)
Touch centralized controller (MCM-A300N)
Controller DMS2 (MIM-D00AN)
BACnet gateway (MIM-B17N)
Lonworks gateway (MIM-B18N)

7 Conventional communication outdoor unit requires interface module (MIM-N01) to establish connection
7 MIM-B13D, MIM-B13E, MIM-B04A Interface modules cannot be connected.
7 To connect ERV, MIM-N10 interface module is required.

3) Description of parts

CONTROL SYSTEMS
CENTRALIZED

⑧ ③
⑦ ④
⑥ ⑤

No. Name Description


ƒ Button : Turn on/off the LCD screen
LCD On/Off button and ƒ Indicator

Indoor unit operation indicator - Blue : Turns on if any one of the indoor unit is in operation.
- Red : Turns on if nay one of the indoor unit has an error
② SD card slot Use to back-up data on SD card or updating S/W

③ Power terminal $POOFDU"$_7 )[QPXFS

④ Reset button Use to reset Touch centralized controller

⑤ DI-1 terminal Terminal block for connecting digital input signal from 3rd party device.

⑥ DI-2 terminal Terminal block for connecting digital input signal from 3rd party device.

ƒ Terminal block for digital output signal.


⑦ DO Terminal - Short : When any one of indoor units turns On
- Open :When all indoor units are off
ƒ 8IFODPOOFDUJOHUPTFUMBZFS$POOFDUUPPVUEPPSVOJUPSJOEPPSVOJU ''

⑧ 485 communication terminal ƒ8IFODPOOFDUJOHUPDPOUSPMMBZFS$POOFDUUPPVUEPPSVOJU 0O0GGDPOUSPMMFS 5PVDIDFOUSBMJ[FE


controller or DMS2 (R1/R2)

63
Control Systems

II Centralized control systems


4. Touch centralized controller
MCM-A300N

4) Connection diagram
S-NET 3

TCP/IP

Control layer

Touch centralized
OnOff controller OnOff controller controller

DMS2

RS485

Touch centralized
controller

Outdoor unit

Maximum 128
indoor units
(DVM series)

Set layer

64
5) Connection
Set layer connection (F1/F2)
t8IFO5PVDIDFOUSBMJ[FEDPOUSPMMFSPOMZDPOUSPMTJOEPPSVOJUTPGPVUEPPSVOJU UIFOJUDBOCFDPOOFDUFEUP''MJOFPGPVUEPPSVOJUPSJOEPPSVOJU
tMax. 16 Controllers can be connected to same communication line.
7Connectable controller: - OnOff controller (MCM-A202DN)
- Touch centralized controller (MCM-A300N)

Set layer

F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2

CONTROL SYSTEMS
Set layer

CENTRALIZED
F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2

Control layer connection (R1/R2)


t.BY$POUSPMMFSTDBOCFDPOOFDUFEUPTBNFDPNNVOJDBUJPOMJOF *ODBTFPG%.4#"$OFUHBUFXBZ-PO8PSLTHBUFXBZDPOOFDUJPO .BY

t.BYPVUEPPSVOJUTDBOCFDPOOFDUFEUPTBNFDPNNVOJDBUJPOMJOF *ODMVEFTJOUFSGBDFNPEVMF.*./

7Connectable controller : - Touch centralized controller (MCM-A300N).
- OnOff controller (MCM-A202DN).
%.4 .*.%"/
#"$OFUHBUFXBZ .*.#/
-PO8PLTHBUFXBZ .*.#/
0OMZPOFPGUIFUISFFNPEFMT

(1) Connection with outdoor unit


t8IFO5PVDIDFOUSBMJ[FEDPOUSPMMFSDPOUSPMTJOEPPSVOJUTPGNVMUJQMFPVUEPPSVOJUT UIFOJUTIPVMECFDPOOFDUFEUP33MJOFPGPVUEPPSVOJUT

F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2

F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2

Control layer
65
Control Systems

II Centralized control systems


4. Touch centralized controller
MCM-A300N

5) Connection

Control layer connection (R1/R2)

(2) Connection with DMS2 / BACnet GW / Lonworks GW

f Case1

F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2

F1 F2 R1 R2

Ex.) DMS2(MIM-D00AN)

Control layer

f Case2

F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2

F1 F2 R1 R2

Ex.) DMS2(MIM-D00AN)

Control layer

66
f Caution
t 8IFO5PVDIDFOUSBMJ[FEDPOUSPMMFSJTDPOOFDUFEUP0VUEPPSVOJUhT''MJOF %.4 #"$OFU(8 
LonWorks GW cannot be connected to same communication line.

Set layer

F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2

DMS2 / BACnet GW / LonWorks GW should be connected to


control layer.

CONTROL SYSTEMS
6) Main function

CENTRALIZED
Z one control

t You can create a zone by grouping multiple indoor units


t Maximum 12 zones can be created (Total up to 128 indoor units)

t You can set the name of Zone/indoor unit


t You can set the zone icon for purpose of each zone. 67
Control Systems

II Centralized control systems


4. Touch centralized controller
MCM-A300N

6) Main function

Grouping indoor units


t 'VODUJPOUPDPOUSPMBOENPOJUPSNVMUJQMFJOEPPSVOJUTUIBUBSFHSPVQFEBOEFYQSFTTFEBTTJOHMFJOEPPSVOJU

Displays number of indoor units in a group

Displays number of indoor units in a group

Schedule control

t Maximum 10 schedules can be created


68 t Excluded day setting is possible
Setting indoor unit usage restriction
(1) Cool lower limit/ Heat upper limit

CONTROL SYSTEMS
CENTRALIZED
t It can set the lower temperature limit in Cool mode and the upper temperature limit in Heat mode.
t This setting can be changed by other touch centralized controller and DMS2.

(2) Operation mode limit

t 5PQSFWFOUUIFXSPOHPQFSBUJPONPEFTFUUJOH JUDBOMJNJUUIFPQFSBUJPONPEFPGJOEPPSVOJU
- $PPMPOMZ)FBU "VUP )FBU
PQFSBUJPONPEFJTSFTUSJDUFE
)FBUPOMZ$PPM %SZ "VUP $PPM
PQFSBUJPONPEFJTSFTUSJDUFE

t This setting can be changed by other touch centralized controller and DMS2.

69
Control Systems

II Centralized control systems


4. Touch centralized controller
MCM-A300N

6) Main function

L ock function
t You can lock the functions of Touch centralized controller.

(1) Screen lock

t You can lock the screen.


1BTTXPSEJTSFRVJSFEXIFOZPVUSZUPVTFJU

(2) Operating panel lock

t You can set the access lock of each item of operating panel.
The locked item will be deactivated.

(3) Menu lock

t You can set the access lock of each menu.


70 1BTTXPSEJTSFRVJSFEXIFOZPVUSZUPVTFJU
Remote controller usage restriction
(1) Indoor unit operating panel

CONTROL SYSTEMS
CENTRALIZED
t You can set the controller restriction.
t You can set the type of controller which will be restricted when "Disable RC" is applied from operating panel.
[Settings] ¤ [Device settings] ¤ [Control level]

(2) Device settings

t You can set the type of controller which will be restricted when "Disable RC" is applied from operating panel.
3FNPUFDPOUSPMMFS3FTUSJDUXJSFEXJSFMFTTSFNPUFDPOUSPMMFSVTBHF 0O0GGDPOUSPMMFSVTBHFJTQPTTJCMF
- OnOff controller : Restricts wired/wireless remote controller and OnOff controller usage

71
Control Systems

II Centralized control systems


4. Touch centralized controller
MCM-A300N

6) Main function

Tracking

t Detects all the indoor and outdoor units that are connected to communication line of Touch centralized controller
t 8IFONVMUJQMFOVNCFSPG5PVDIDFOUSBMJ[FEDPOUSPMMFSJTDPOOFDUFEUPHFUIFS ZPVDBOVTFDIFDLCPYPG4) 4IPX)JEF
UPTFMFDU
indoor units that will be controlled from each Touch centralized controller.

Hiding indoor unit

t *OEPPSVOJUXJUIOPDIFDLNBSLPO4) 4IPX)JEF
DIFDLCPY XJMMOPUCFDPOUSPMMFEBOENPOJUPSFEGSPNUIF5PVDIDFOUSBMJ[FEDPOUSPMMFS

72
5. Operation mode selection switch
MCM-C200

1) Features

CONTROL SYSTEMS
CENTRALIZED
Operation mode selection switch
t0VUEPPSVOJUPQFSBUJPONPEFTFMFDUJPO $PPMJOH )FBUJOHPS"VUP

Ú Mixed operation mode protection

(Unit : mm)
70 21
120

2) Installation

tPQFSBUJPONPEFTFMFDUJPOTXJUDINVTUCFDPOOFDUFEUPPVUEPPSVOJU
Ú Max. distance between the outdoor unit PCB and the MCM-200: 100m

73
Control Systems

II Centralized control systems


5. Operation mode selection switch
MCM-C200

3) Control example
Initial condition C

t Cool/Heat Selector : Heating position


t*%6  4UPQNPEF *%6)FBUJOHNPEF
t Compressor ON

Sequence 1 Set the Cool/Heat selector to the Cooling position

① Change Cool/Heat Selector to Cooling


Result ② "VUPNBUJDBMMZDPNQSFTTPS0''
③ Running IDU4 stops

Sequence 2 Set IDU4 to Heating with Remote controller

① t IDU4 ignores Heating command


Result
t *%6LFFQT0''TUBUVT

; Note
Š Operation mode selection switch fixed indoor unit operation mode.
Š Indoor unit ignores opposite operation mode. (It will not accept the command and it will just beep shortly)

74
III. Integrated management systems
1 DMS2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
2 S-NET3. . . . . . . . . . . . . . . . . . . . . . . . . . . 111

MANAGEMENT SYSTEMS
INTEGRATED

75
Control Systems

III Integrated management systems


1. DMS2
MIM-D00AN

1) Features

t#VJMUJOXFCTFSWFSGPS1$JOEFQFOEFOUNBOBHFNFOUBOESFNPUFBDDFTTDPOUSPM
t.VMUJQMFVQQFSMBZFSDPOUSPMBDDFTT 4/&5 8FCDMJFOU

t8FFLMZ%BJMZTDIFEVMFDPOUSPM
t1PXFSEJTUSJCVUJPOGVODUJPO
t$VSSFOUUJNFNBOBHFNFOUFWFOEVSJOHQPXFSGBJMVSF GPSIPVST

t&NFSHFODZTUPQGVODUJPOXJUITJNQMFDPOUBDUJOUFSGBDF
t*OEJWJEVBM(SPVQDPOUSPMPGVQUPJOEPPSVOJUTBOE&37 ")6
t6TFSFEJUBCMFDPOUSPMMPHJD
t"DDFTTJCMFMFWFMNBOBHFNFOU
t%ZOBNJDTFDVSJUZNBOBHFNFOU
t0QFSBUJPOFSSPSIJTUPSZNBOBHFNFOU
t%BUBTUPSBHFJOOPOWPMBUJMFNFNPSZ4%NFNPSZ

6OJUNN

2) Product specification
Source %$"EBQUPS
Power Input _7"$ 
)[
Output 7"
Operating temperature
℃_℃
range
Operating humidity range 3)_3)
t-PXFSMFWFM34Y
Communication method
t6QQFSMFWFM&UIFSOFU#BTF5Y
External Digital Output 10
connection
port Digital Input 10

RS485 N
Maximum Digital Output N
length of
connection Digital Input N

Ethernet N 8IFOUIFSFJTOPSFQFBUFS




%FWJDF /VNCFSTQFSFBDIDIBOOFM 5PUBMOVNCFSGPSDIBOOFMT


*OEPPSVOJUT JODMVEJOH&37 .$6
 
Max.
0VUEPPSVOJU
connectable Control  
JODMVEJOHJOUFSGBDFNPEVMF.*./

number of layer
0O0GGDPOUSPMMFS
device 5PUBM 5PUBM
5PVDIDFOUSBMJ[FEDPOUSPMMFS
1*.JOUFSGBDFNPEVMF .*.# .*.#/
  

76
Compatible product
0VUEPPSVOJU ".77779777777
0O0GGDPOUSPMMFS .$."%/

$POUSPMMFS 5PVDIDFOUSBMJ[FEDPOUSPMMFS .$."/

1*.JOUFSGBDFNPEVMF .*.# .*.#/

7 Conventional communication outdoor unit requires interface module(MIM-N01).
7 MIM-B13D, MIM-B13E, MIM-B04A Interface modules cannot be connected.
7 To connect ERV, MIM-N10 interface module is required.
7 PIM connection is different depending on software version.
- Before 2.6.0.3 : MIM-B16 only
- 2.6.0.3 : MIM-B16N only
- After 2.6.1.7 : MIM-B16, MIM-B16N

3) Description of parts
Front

No Name Function
4IPXTDVSSFOUUJNFBOE*1BEESFTT
① LCD display 7BSJPVTNFTTBHFTXJMMCFEJTQMBZFE
① EFQFOEJOHPOCVUUPOJOQVU
5IFSFBSFCVUUPOT .FOV 
② T %PXO
S 6Q
4FU
BOEZPVDBO

MANAGEMENT SYSTEMS
② LCD operation button
BDDFTTUPNFOVBOENPWF DIFDL
UIFNFOV

INTEGRATED
$IFDL-&%TUBUVTTVDIBT1PXFS 
③ LED Indicator $16"MJWF &UIFSOFU-JOLFE"DUJWF 
$0._5939BOE$IFDL
③ 6OGBTUFOTDSFXTPOUIFCPUUPN
BOETFQBSBUFUIFCPUUPNDPWFSGSPN
④ DMS2 Bottom cover
④ %.4
5IFODIFDLDBCMFDPOOFDUJPOQBSU

LED indicator

Item Name Status


Power 1PXFSJOEJDBUPS 5VSOTCMVFXIFOUIFQPXFSJTTVQQMJFE
#MJOLTJOPSBOHFXJUITFDPOEJOUFSWBMTEVSJOH
CPU Alive $16PQFSBUJPOJOEJDBUPS
OPSNBMPQFSBUJPO
Ethernet - Linked *OUFSOFUDPOOFDUJPOJOEJDBUPS 5VSOTHSFFOEVSJOHOPSNBMDPOOFDUJPO
*OUFSOFUEBUBUSBOTNJTTJPO #MJOLTJOPSBOHFEVSJOHOPSNBMUSBOTNJTTJPO
Ethernet - Active
SFDFQUJPOJOEJDBUPS SFDFQUJPO
0O0GGDPOUSPMMFS0VUEPPSVOJUEBUB
COM1~5 - TX #MJOLTJOHSFFOEVSJOHOPSNBMUSBOTNJTTJPO
USBOTNJTTJPOJOEJDBUPS
0O0GGDPOUSPMMFS0VUEPPSVOJUEBUB
COM1~5 - RX #MJOLTJOHSFFOEVSJOHOPSNBMSFDFQUJPO
SFDFQUJPOJOEJDBUPS
*OEPPSPVUEPPSVOJU 5VSOTHSFFOXIFOUIFSFJTBOFSSPSPONPSFUIBO
Check
FSSPSDIFDLJOEJDBUPS POFJOEPPSPVUEPPSVOJUPSJODPNNVOJDBUJPO

77
Control Systems

III Integrated management systems


1. DMS2
MIM-D00AN

3) Description of parts

Bottom
DI Terminal2 DO Terminal1
$POOFDU%JHJUBM*OQVU $POOFDU%JHJUBM0VUQVU
$IBOOFM_$IBOOFM $IBOOFM_$IBOOFM

DI Terminal1 DO Terminal 2
$POOFDU%JHJUBM*OQVU $POOFDU%JHJUBM0VUQVU
$IBOOFM_$IBOOFM $IBOOFM_$IBOOFM

Power Terminal RS485 Communication


$POOFDU%.4BEBQUFS terminal
$POOFDUGPS34
DPNNVOJDBUJPOXJUIEFWJDFT
TVDIBT0O0GGDPOUSPMMFS
0VUEPPSVOJUT1*.
Reset Button $IBOOFM_$IBOOFM
3FTFU%.4
Cable tie groove
"SSBOHFDBCMFT
Serial Terminal DPOOFDUFEUP%.4
4FSWJDFBHFOUDIFDLT
FSSPSTUBUVT LAN Terminal
$POOFDU-"/DBCMF
SD Card Socket
4PDLFUGPSTVCNFNPSZ 4%PS..$

4VCNFNPSZJTGPS%.4QSPHSBNVQEBUFBOETFUJOGPSNBUJPOTBWJOH

Ú1VSDIBTF4%DBSETFQBSBUFMZ

Menu and display

DMS2 IP

Current time

Button Detail description


ƒ(FOFSBMEJTQMBZ%JTQMBZT*1BEESFTTPGUIF%.4BOEDVSSFOUUJNF
LCD display
ƒ*O.FOV%JTQMBZTNFOVJOGPSNBUJPOBOETFUWBMVF

ƒ"DDFTTNFOVBOETFMFDUNBJONFOV
ƒ$BODFMNFOVTFUUJOH

ƒ.PWFCFUXFFONFOV
ƒ$IBOHFUIFNFOVTFUUJOHT

ƒ.PWFCFUXFFONFOV
ƒ$IBOHFUIFNFOVTFUUJOHT

ƒ"DDFTTTVCNFOV
ƒ4BWFUIFDIBOHFPGNFOVTFUUJOHT
78
4) Connection diagram
f MIM-B16(PIM) should be connected separately with outdoor unit or controllers.
f MIM-B16N(PIM) can be connected with outdoor units or controllers to same channel of DMS2.

'PSQPXFSEJTUSJCVUJPO

1*. 0O0GG
%.4
DPOUSPMMFS

1PXFSMJOF
33

''

33

''

MANAGEMENT SYSTEMS
8BUUIPVSNFUFS
&MFDUSJDBM
TVCTUBUJPO

INTEGRATED
33 ''

5) Wiring

$)$IBOOFM

F1 F2 R1 R2

F1 F2 R1 R2

(1) Connecting outdoor unit directly


t.BYJNVNPVUEPPSVOJUTDBOCFDPOOFDUFEUPFBDIDIBOOFM
t5PUBMPVUEPPSVOJUTDBOCFDPOOFDUFE

(2) Connecting OnOff controller / Touch centralized controller


t.BYJNVN0O0GGDPOUSPMMFS5PVDIDFOUSBMJ[FEDPOUSPMMFSDBOCFDPOOFDUFEUPFBDIDIBOOFM

; Note
Š%.4DBODPOOFDUPVUEPPSVOJUBOE0O0GGDPOUSPMMFS5PVDIDFOUSBMJ[FEDPOUSPMMFSBUUIFTBNFUJNF
Š0VUEPPSVOJUBOE0O0GGDPOUSPMMFS5PVDIDFOUSBMJ[FEDPOUSPMMFSDBOCFDPOOFDUFEUPDPNNVOJDBUJPODIBOOFMBUUIFTBNFUJNF

79
Control Systems

III Integrated management systems


1. DMS2
MIM-D00AN

5) Wiring

Connecting with outdoor unit

DMS2

F1 F2
R1 R2
Outdoor unit

R1R2
R1R2

0 0 Outdoor unit
Outdoor unit
R1R2

R1R2

1 1 Outdoor unit
Maximum 16 Outdoor unit
connections

F F
Outdoor unit
Outdoor unit Ú0VUEPPSVOJUhTBEESFTTJTEFGJOFEBVUPNBUJDBMMZ
5IFBEESFTTDBOCFDIBOHFENBOVBMMZBMTP

Connecting with OnOff controller / Touch centralized controller

DMS2
ex) OnOff controller

Maximum 15
OnOff controllers

Outdoor unit
R1R2

Outdoor unit

R1R2

Outdoor unit
80
Connecting with outdoor unit and OnOff controller / Touch centralized controller

DMS2
R1R2 ex) OnOff controller

Maximum 16
outdoor units
1
Outdoor unit
R1R2

MANAGEMENT SYSTEMS
Outdoor unit

INTEGRATED
R1R2

3
Outdoor unit

Wiring distance

ⓐ ⓑ ⓒ

/FUXPSLSBEJVT

f Distance between DMS2 and OnOff controller / Touch centralized controller /outdoor unit
t%JTUBODFGSPNUIF%.4UPUIFGVSUIFTUEFWJDFDBOOPUFYDFFEN
tⓒ + ⓓ + ⓔ d 1000m

f Distance between DMS2 and upper level controller


t4JODF%.4TVQQPSUT#BTF5&UIFSOFU GJSTUSFQFBUFSPSVQQFSMFWFMDPOUSPMMFSGSPNUIF%.4DBOOPUCFGVSUIFSUIBON
 *&&&
5IFSFGPSF NBYJNVNOFUXPSLSBEJVTJTSFTUSJDUFEUPN

ⓐ, ⓑ, ⓒ, ⓓ, ⓔ = 100m

ⓐ ⓑ ⓒ ⓓ ⓔ

)6#
3FQFBUFS

.BYJNVNOVNCFSPGSFQFBUFST
ⓐN 81
Control Systems

III Integrated management systems


1. DMS2
MIM-D00AN

6) Function

Tracking
f 5SBDLJOHJTBOPQFSBUJPOUIBUGJOETEFWJDFTXIJDIBSFDPOOFDUFEUP%.4
5ISPVHIUSBDLJOHPQFSBUJPO EFWJDFTXIJDIBSFDPOOFDUFEUP%.4DBOSFDPHOJ[FJGUIFZBSFDPOOFDUJOHUP%.4
5PTVQFSWJTFBOEDPOUSPMTZTUFNBJSDPOEJUJPOFSVTJOH%.4 USBDLJOHTIPVMECFEPOFGJSTU

t8IFOPVUEPPSVOJUPSDPOUSPMMFSJTDPOOFDUFEUPDIBOOFM TFUBTi/&8w
t8IFO1*. .*.#/
JTDPOOFDUFEUPDIBOOFM TFUBTi*.w
t1*.TIPVMECFDPOOFDUFETFQBSBUFMZXJUIPVUEPPSVOJUPSDPOUSPMMFST

f :PVDBODIFDLUIFOVNCFSPGJOTUBMMFEEFWJDFT BEESFTTPGUIFEFWJDFTPSSFOBNFUIFJOEPPSVOJU
BGUFSUSBDLJOHJTDPNQMFUFE

*OEPPSVOJUOBNF
6TFSDBONPEJGZJU

*OEPPSVOJUBEESFTT

DMS2
0VUEPPSVOJUBEESFTT
$IBOOFMOVNCFS
%FWJDFUZQF
PVUEPPSVOJU
*OEPPSVOJU

82
Control & monitoring
f %.4DBODPOUSPMBOENPOJUPS.BYEFWJDFT *OEPPSVOJU &37 ")6

"OEJUBMTPDPOUSPMTBOENPOJUPSTFYUFSOBMDPOUBDUQPJOU %JHJUBMJOQVU %JHJUBMPVUQVU

MANAGEMENT SYSTEMS
INTEGRATED
Monitoring Control
*OEPPSVOJU &37 ")6 7BSJBCMFXFCSFNPUFDPOUSPMMFST
&YUFSOBMDPOUBDUQPJOU EFQFOETPOEFWJDFUZQF

Multiple language support


f %.4 .*.%"/
TVQQPSUTMBOHVBHFT

Set silent contol


f %.4 .*.%"/
DBODPOUPMJOEPPSVOJUXJUIPVUPQFSBUJPOCFFQJOHTPVOEVTJOHCFMPXTFUUJOHPQUJPO

t$POUSPMBOE.POJUPSJOH4FMFDUUIJTJGZPVXBOUUPDPOUSPMTJMFOUMZJOh$POUSPMBOE.POJUPSJOHhTDSFFOPG%.4
t4DIFEVMF4FMFDUUIJTJGZPVXBOUUPQFSGPSNh4DIFEVMFhTJMFOUMZ
t$POUSPMMPHJD4FMFDUUIJTJGZPVXBOUUPQFSGPSNh$POUSPMMPHJDhTJMFOUMZ

83
Control Systems

III Integrated management systems


1. DMS2
MIM-D00AN

6) Function

OnOff controller restriction


f %.4 .*.%"/
DBOSFTUSJDU0O0GGDPOUSPMMFS 5PVDIDFOUSBMJ[FEDPOUSPMMFSVTBHF

t4FMFDUUIJTJGZPVXBOUUPSFTUSJDUDPOUSPMMJOHGSPN0O0GGDPOUSPMMFSBOE5PVDIDFOUSBMJ[FEDPOUSPMMFSXIFOZPVEJTBCMF3$GSPNUIF%.4

Contact point control


f You can select emergency operation pattern

(1) Pattern 2

/PGVODUJPO
Patter 2
&YUFSOBMDPOUBDU -FWFMUSJHHFSFE

f Short external contact : Emergency stop f Open external contact : Resume operation
t5VSOTPGGBMMUIFJOEPPSVOJUTXIFOUIFSFJTBO0/ t"GUFS&NFSHFODZTUPQ UIFJOEPPSVOJUTTUBZJOUIFDVSSFOU
TJHOBMJOQVU 0''TUBUFT
t"MMUIFSFNPUFDPOUSPMVTFJTEJTBCMFE t"MMUIFSFNPUFDPOUSPMVTFJTSFTUPSFEUPUIFQSFWJPVTTUBUF
t$POUSPMGSPN4/&5JTVOBWBJMBCMF t4DIFEVMFDPOUSPMJTFOBCMFEBHBJO
t%JTBCMFTDIFEVMFDPOUSPM

(2) Pattern 3

&YUFSOBMDPOUBDU -FWFMUSJHHFSFE

Pattern 3
&YUFSOBMDPOUBDU -FWFMUSJHHFSFE

f External contact input to DI-1 f External contact input to DI-2


t4IPSUDPOUBDU4UBSUTBMMJOEPPSVOJUPQFSBUJPO t4IPSUDPOUBDU%JTBCMFTUIFVTFPGBMMXJSFE
t0QFODPOUBDU4UPQTBMMJOEPPSVOJUPQFSBUJPO XJSFMFTTSFNPUFDPOUSPMMFST
Ú4DIFEVMFDPOUSPMJTOPUJOUFSSVQUFEJO1BUUFSO t0QFODPOUBDU&OBCMFTUIFVTFPGBMMXJSFE
XJSFMFTTSFNPUFDPOUSPMMFST
(3) Pattern 4

&YUFSOBMDPOUBDU 1VMTFUSJHHFSFE

Pattern 4 %VSBUJPO_TFD
&YUFSOBMDPOUBDU 1VMTFUSJHHFSFE

%VSBUJPO_TFD

f External contact pulse input to DI-1 f External contact pulse input to DI-2
t4IPSUQVMTFUSJHHFSFE4UBSUTBMMJOEPPSVOJUPQFSBUJPO t4IPSUQVMTFUSJHHFSFE4UPQTBMMJOEPPSVOJUPQFSBUJPO

84 Ú4DIFEVMFDPOUSPMJTOPUJOUFSSVQUFEJO1BUUFSO
General external contact point control
%.4IBT%JHJUBMJOQVUPVUQVUQPSUTUPDIFDLUIFFYUFSOBMEFWJDFTUBUVTPSUVSOUIFN0O0GGUISPVHIDPOUBDUQPJOU

%JHJUBMJOQVU %JHJUBM0VUQVU

$IBOOFM $IBOOFM $IBOOFM $IBOOFM

f DI : Voltage free contact signal input (Open / Short)


t$IBOOFM $IBOOFMJTPDDVQJFEXJUI<&NFSHFODZTUPQ>GVODUJPO
t$IBOOFM_$IBOOFM%.4DBONPOJUPSUIFDPOUBDUTJHOBMJOQVUTUBUFPGFBDIDIBOOFM

f DO : Contact signal output (DC 12V)


t$IBOOFM $IBOOFM $IBOOFMBOE$IBOOFMJTPDDVQJFEXJUIPUIFSGVODUJPOT
t$IBOOFM_$IBOOFM%.4DBODPOUSPMDPOUBDUTJHOBMPVUQVU

; Note
Š%* %0   XJMMCFFYDMVEFEGSPNDPOUSPMBOENPOJUPSJOHTJODFJUJTCFJOHVTFECZJOUFSOBMGVODUJPOPG%.4

MANAGEMENT SYSTEMS
INTEGRATED
Indoor unit usage restriction
t0QFSBUJPOMJNJU5PQSFWFOUUIFXSPOHPQFSBUJPONPEFTFUUJOH JUDBOMJNJUUIFPQFSBUJPONPEFPGJOEPPSVOJU
t5FNQFSBUVSFMJNJU*UDBOTFUUIFMPXFSUFNQFSBUVSFMJNJUJO$PPMNPEFBOEUIFVQQFSUFNQFSBUVSFMJNJUJO)FBUNPEF

❹ 4FUUJOH6QQFSUFNQFSBUVSFMJNJUJO)FBUJOH
❸ $POUSPMNPEF
-PXFSUFNQFSBUVSFMJNJUJO$PPMJOH
❷ 0QFSBUJPONPEF
❶ *OEPPSVOJUBEESFTT SFTUSJDUJPO

0VUEPPSVOJU
❶ Check the indoor unit address.

7JSUVBM0O0GGDPOUSPMMFS *OEPPSVOJUNBJOBEESFTT
_%FQFOETPODIBOOFMOVNCFS

*OEPPSVOJUHSPVQBEESFTT 3.$ 

❷ Select the Limit mode


t*OEPPSVOJUTXJUIJOTBNFPVUEPPSVOJUNVTUCFTFUJOTBNFMJNJUNPEF
t"MMJOEPPSVOJUTPGPOFPVUEPPSVOJUTFUTBNFPQFSBUJPONPEFSFTUSJDUJPOBVUPNBUJDBMMZ

❸ Control mode will be set automatically depends on the seleceted restricted mode
t&Y
8IFOUIFSFTUSJDUFENPEFJTTFUUP<$PPMPOMZ>BOEUIFO<$POUSPMNPEF>JTTFUUP<$PPM>BVUPNBUJDBMMZ
*GVTFSTFU<)FBUJOHNPEF>VTJOHSFNPUFDPOUSPMMFSŠ*OEPPSVOJUJHOPSFTUIFDPNNBOE

❹ Set the Upper temperature limit in Heating and Lower temperature limit in Cooling.
t6QQFSUFNQFSBUVSFMJNJUJO)FBUJOHBOE-PXFSUFNQFSBUVSFMJNJUJO$PPMJOHDBOCFTFUEJGGFSFOUMZGPSFBDIJOEPPSVOJU
$PPMJOH$_$ )FBUJOH$_$

85
Control Systems

III Integrated management systems


1. DMS2
MIM-D00AN

6) Function

Logic control
What is logic control?
6TFSDBODPOUSPMUIFBJSDPOEJUJPOFS &37 ")6BOEEJHJUBMPVUQVUEFQFOEJOHPOUIFDPOEJUJPOT TVDIBTSPPNUFNQFSBUVSFBOE
PVUEPPSUFNQFSBUVSF TFUCZUIFVTFS*OQVUDPOEJUJPODBOCFVTFEXJUIQBSBNFUFSBOEJUXJMMCFDBMDVMBUFEXJUIBSJUINFUJDFRVBUJPO
4DIFEVMFGVODUJPOFYFDVUFTPQFSBUJPOCZUJNFCVUMPHJDDPOUSPMFYFDVUFTPQFSBUJPOBDDPSEJOHUPUIFDPOEJUJPOTUIBUTFUCZUIFVTFS

Examples of utilizing the logic control


$BTF
(PWFSONFOUSFHVMBUFTUIFMPXFTUSPPNUFNQFSBUVSFUPCF$JOQVCMJDQMBDFT8IFOUIFSPPNUFNQFSBUVSFJTMPXFSUIBO
$ BENJOJTUSBUPSNVTUUVSOPGGBMMUIFBJSDPOEJUJPOFSTJOUIFBSFB*TUIFSFBOZXBZGPSUIFBJSDPOEJUJPOFSUPUVSOPGG
BVUPNBUJDBMMZEFQFOEJOHPOUIFDFSUBJOSPPNUFNQFSBUVSF 
$BTF
%VSJOHTQSJOHBOEGBMM JUJTDPMEJOUIFNPSOJOHBOEXBSNJOUIFBGUFSOPPO5IFSFGPSF *NVTJOHUIFBJSDPOEJUJPOFSJOIFBUJOH
NPEFJOUIFNPSOJOHBOEDPPMJOHNPEFJOUIFBGUFSOPPO$BO*TFUUIFBJSDPOEJUJPOFSUPDIBOHFPQFSBUJPONPEFBVUPNBUJDBMMZ
EFQFOEJOHPOUIFPVUEPPSUFNQFSBUVSF 
$BTF
*NVTJOHBJSDPOEJUJPOFSXJUI&37*OUIFEBZTXJUIUIFPVUEPPSUFNQFSBUVSFSFMBUJWFMZMPXFSUIBOUIFJOEPPS *XBOUUPVTF
&37JOTUFBEPGUIFBJSDPOEJUJPOFSUPWFOUJMBUFBOENJOJNJ[FUIFBJSDPOEJUJPOFSVTF*TUIFSFBOZXBZUPTFUUIFBJSDPOEJUJPOFS
PS&37UPPQFSBUFBQQSPQSJBUFMZBOEBVUPNBUJDBMMZEFQFOEJOHPOUIFUFNQFSBUVSF

Input Output

4FMFDUUIFGBDUPSUPJOQVUDPOEJUJPO
ƒ%FWJDF GBDUPS
4FMFDUPVUQVUGBDUPS
&EJUUIFDPOEJUJPO ƒ%FWJDF GBDUPS
ƒ$PNQPVOEGBDUPS
ƒ$PNQBSJTPOPQFSBUPS
ƒ4UBOEBSEWBMVF
¨ &EJUPVUQVU
ƒ$SFBUFDPOUSPM

ƒ%VSBUJPO

Edit factor Compound Comparison Command


1PXFS factor operator 1PXFS
$VSSFOUUFNQ AND =
%FTJSFE
%FTJSFEUFNQ UFNQ
OR =>
Single 0VUEPPSUFNQ
factor .PEF =< .PEF
'BOTQFFE 'BOTQFFE
>
"JSGMPX
&OBCMF%JTBCMF3$ < "JSTXJOH
&OBCMF
$VSSFOUUFNQ z
Arithmetic  %JTBCMF3$
%FTJSFEUFNQ
factor 
0VUEPPSUFNQ
$VSSFOUUFNQ
Function
"WFSBHF %FTJSFEUFNQ
factor
86 0VUEPPSUFNQ
(1) Editing input factor





⑦ ⑨

MANAGEMENT SYSTEMS
① Click “Select a factor”. ¨ ② Select type of the factor ¨ ③ Click “Select a device”

INTEGRATED
ª
⑥ Click “Apply”. § ⑤ Select a detail item § ④ Select the device from the list.
ª
⑦ Select the comparison operator ¨ ⑧ Select a standard value ¨ ⑨ Select the duration

f Single factor : 1 device and 1 factor.

f Arithmetic : It means 2 devices are connected by arithmetic operator.

f Function : Use average value of various conditions from the device and create it as a factor.

87
Control Systems

III Integrated management systems


1. DMS2
MIM-D00AN

6) Function

Logic control
(1) Editing input factor

t$PNQPVOEGBDUPS"/% 03 /PTFMFDUJPO


&Y
"QQMZh"/%hPSh03hUPGBDUPST
Š JOQVU
"OE JOQVU
03 JOQVU

t$PNQBSJTPOPQFSBUPS     z


t4UBOEBSEWBMVF4UBOEBSEWBMVFPGUIFGBDUPS
&Y
8IFOUIFGBDUPSJTi0VUEPPSUFNQFSBUVSFPGUIFJOEPPSVOJUOVNCFSw UIFOTUBOEBSEWBMVFJTWBMVFPGUIFi0VUEPPSUFNQFSBUVSFw
Ši0VUEPPSUFNQFSBUVSFPGUIFJOEPPSVOJUOVNCFSw
t%VSBUJPO%VSBUJPODBOCFTFUCFUXFFO_NJO

Item Comparison operator Standard value


1PXFS  z 0O 0GG
$VSSFOUUFNQ      z 5FNQFSBUVSFWBMVF OVNCFS

%FTJSFEUFNQ      z 5FNQFSBUVSFWBMVF OVNCFS

0VUTJEFUFNQ      z 5FNQFSBUVSFWBMVF OVNCFS

.PEF  z "VUP $PPM %SZ 'BO )FBU


'BOTQFFE  z "VUP -PX .FE )JHI
"JSGMPX  z 7FSUJDBM )PSJ[POUBM "MM /POF
&OBCMF3$  z 0/ 0'' -FWFM

(2) Editing output factor ③

0OMZA4JOHMFXJMMCFMJTUFE

i$VSSFOUUFNQwBOEi0VUEPPSUFNQw
DBOOPUCFTFMFDUFE ⑤

① ⑥

① Click “Select a factor”. ¨ ② Click “Select a device”. ¨ ③ Select the device from the list.
ª
⑥ Select “Command”. § ⑤ Click “Apply”. § ④ Select a detail item to control.
ª
⑦ Click “Save”.
88
(3) Control example – Setting
Ex) Set the ERV to turn off together when the indoor unit turns off

❶$MJDL<$POUSPMMPHJDNBOBHFNFOU>Š<4FUUJOHDPOUSPMMPHJD>GSPN%.4NFOV$MJDL<3FHJTUFS>UPDSFBUFOFXDPOUSPMMPHJD

❷ &OUFS/BNF QFSJPEEBZBOEUJNFGPSOFXDPOUSPMMPHJD

MANAGEMENT SYSTEMS
INTEGRATED
❸ Create input condition : Click [Select a factor] from the ‘Input’ window.

89
Control Systems

III Integrated management systems


1. DMS2
MIM-D00AN

6) Function

Logic control
(3) Control example – Setting
❹ Click [Select a device], then [Device selection] window will pop up.
Select a indoor unit to apply the new control logic.

❺ Create input condition : When the device is selected, click [Power] and click [Apply].
Ú<1PXFS>NFBOTUIFPQFSBUJPOTUBUF 0O0GG


❻ Create input condition :Select ‘=’ as a comparison operator and select “Off” as a standard value.
t.FBOJOH&YFDVUFPVUQVUDPOUSPMXIFOEFWJDFJTPGG

90
❼ Create output : From the output window, select the device to apply the control when input condition is satisfied.
Click [Apply] when selection is completed.

❽ Create output : Select “Power” as a factor of the selected device and click [Apply].

MANAGEMENT SYSTEMS
INTEGRATED
❾ Create output : From the output window, select the control to be executed when input condition is satisfied.
t5VSOPGGUIF&37OP

❿ Click [Save] when the setting is completed.

To apply the new logic control, select the created logic and click [Apply].

91
Control Systems

III Integrated management systems


1. DMS2
MIM-D00AN

6) Function

Logic control
(4) Control example – Control logic
Ex) Control logic 1 : Turn on 4 indoor units when outdoor temperature is 30°C or higher.
Control logic 2 : Turn off 4 indoor units when outdoor temperature is 26°C.

Control logic 1

❶Input : 8IFOPVUEPPSUFNQFSBUVSFJT¡$PSIJHIFS ❷ 8IFODPOEJUJPOMBTUFEGPSNJOJVUF ❸Output : 5VSOPOJOEPPSVOJUT

Control logic 2

92 ❶Input : 8IFOPVUEPPSUFNQFSBUVSFJT¡$PSMPXFS ❷Output : 5VSOPGGJOEPPSVOJUT


Register control logic

➊$MJDL

➋$MJDL

MANAGEMENT SYSTEMS
INTEGRATED
Control logic applied

"QQMJDBUJPODPNQMFUFE

93
Control Systems

III Integrated management systems


1. DMS2
MIM-D00AN

6) Function

Power distribution
t8IFSFEPFTQPXFSDPOTVNQUJPOPDDVST

"JSDPOEJUJPOJOHTZTUFN

0VUEPPSVOJUGBO

$PNQSFTTPS 0VUEPPSVOJU1$# *OEPPSVOJU1$# *OEPPSVOJUGBO

System power consumption includes:


1. Main power - $PNQSFTTPSPQFSBUJPOQPXFS
2. Fan power*OEPPS0VUEPPSVOJUGBOPQFSBUJPO
3. Stand-by power 1SFIFBUJOHDPJMQPXFS *OEPPS0VUEPPS1$#QPXFS

(1) DMS2 power distribution theory


"MMUIFTZTUFNJOGPSNBUJPOPGQPXFSBOEJOEPPSPVUEPPSPQFSBUJPOJTBMXBZTNPOJUPSFECZUIF%.4GPSQPXFSEJTUSJCVUJPODBMDVMBUJPO

*%6*OEPPSVOJU

5ISPVHI1*.
*%6" *%6#
.FBTVSFEQPXFS
DPOTVNQUJPO
*%6$
Operation information
1. Outdoor/Indoor unit
operation
2. Indoor unit fan operation
3. Stand-by operation *%6%
Power distribution result
5ISPVHI0O0GGDPOUSPMMFST
BOEJOUFSGBDFNPEVMFT

%FNBOEDBQBDJUZPG*%6"
*%6"TFMFDUSJDQPXFS  5PUBMQPXFS Y
DPOTVNQUJPO DPOTVNQUJPO 5PUBMEFNBOEDBQBDJUZPGBMM*%6T

)FSF %FNBOEDBQBDJUZ.BJODBQBDJUZ 'BODBQBDJUZ 4UBOECZDBQBDJUZ

; Note
Š%FNBOEDBQBDJUZNFBOTUIFWBMVFUIBUQBSBNFUFSTPGEJGGFSFOUVOJUTMJLFSFRVJSFEQPXFSBOESFGSJHFSBOUBNPVOUBSF
USBOTGPSNFEJOUPBTBDPNNPOOVNCFSUPNBLFFBTZBMHFCSBJDDBMDVMBUJPO

94
(2) Main capacity
5IJTJTEFUFSNJOFEEZOBNJDBMMZXJUIUIFDPNCJOBUJPOPGWBSJPVTSFGSJHFSBUJOHQBSBNFUFSTTVDIBTEJGGFSFODFCFUXFFOSPPNBOETFU
UFNQFSBUVSFPSFWBQPSBUPSJOQVUPVUQVUUFNQFSBUVSF
5IFTFQBSBNFUFST BTBSFTVMU EFUFSNJOFUIFSFGSJHFSBOUBNPVOUGMPXJOHJOUPUIFJOEPPSVOJUCZDPOUSPMMJOH&&7TUFQT

(3) Fan capacity


5IJTJTDPOTUBOUWBMVFGPSJOEPPSVOJUNPEFMT*UEJGGFSTEFQFOEJOHPOJOEPPSVOJUTPGEJGGFSFOUDBQBDJUZ
8IFOUIFJOEPPSVOJUTUBSUT$PPMJOH )FBUJOH "VUPBOE'BONPEFT GBODBQBDJUZWBMVFTPGUIFJOEPPSVOJUTBSFBMXBZTNPOJUPSFECZ
UIF%.4%.4HBUIFSTDBQBDJUZPG[FSPWBMVFXIFOUIFZTUPQPQFSBUJOH

(4) Stand-by capacity


4UBOECZDBQBDJUZJTDPOTUBOUGPSBMMJOEPPSVOJUTSFHBSEMFTTPGUIFJSPQFSBUJPOT4JODFTUBOECZQPXFSJTDPOTVNFEBMMUIFUJNFCZ
1$#TBOEQSFIFBUJOHDPJMTJOUIFPVUEPPSVOJU XIPTFWBMVFJTNPOJUPSFEXJUIUIFTBNFGSBDUJPOXIJDIJTSFMBUJWFMZTNBMMDPNQBSFEUPNBJO
DBQBDJUZPSGBODBQBDJUZ

(5) What if the room temperature begins to reach the set temperature?
*GUIFSPPNUFNQFSBUVSFCFHJOTUPSFBDIUIFTFUUFNQFSBUVSF UIFJOEPPSVOJUEPFTOPUIBWFUPFYUSBDUUIFGVMMSFGSJHFSBOUBNPVOUUP
LFFQUIFTFUDPOEJUJPO$BQBDJUZGSPNUIFJOEPPSVOJUHPFTEPXOUPJOEJDBUFUIFPVUEPPSVOJUUIBUJUEPFTOPUOFFESFGSJHFSBOUBUUIF
GVMMDBQBDJUZTUBUF

MANAGEMENT SYSTEMS
8IFOUIFSPPNUFNQFSBUVSFIBTSFBDIFEUIFTFUUFNQFSBUVSF UIFSFJTOPOFFEUPQVNQUIFSFGSJHFSBOUJOUPUIFJOEPPSVOJU*OEPPSVOJU

INTEGRATED
HPFTJOUPUIFUIFSNBMMZ0''TUBUFBOETFOETDBQBDJUZPG[FSPWBMVFUPUIFPVUEPPSVOJUBOEUIF%.4 XIJDISFTVMUTJOGBOPSTUBOECZ
QPXFSEJTUSJCVUJPOPOMZ

(6) Capacity accumulation and power distribution


%.4HBUIFSTQPXFSDPOTVNQUJPOBOEDBQBDJUZWBMVFTEVSJOHPOFEBZ
"UNJEOJHIU EBZQPXFSDPOTVNQUJPOJTEJTUSJCVUFEUPUIFJOEPPSVOJUTVTJOHUIFHBUIFSFEJOGPSNBUJPO
 
IPVS

%VSJOHIPVST $BMDVMBUFTDPOTVNFEQPXFSGPSEBZ
3FBETFWFSZJOEPPSVOJUPQFSBUJPO $BMDVMBUFTBDDVNVMBUFEDBQBDJUZWBMVFT
3FBETXBUUIPVSNFUFSWBMVF %JTUSJCVUFTEBZQPXFSDPOTVNQUJPO
"DDVNVMBUFTDBQBDJUZWBMVFT $MFBSTBDDVNVMBUFEDBQBDJUZWBMVFT

(7) Undesirable situation protection


&WFOXIFOUIFSFPDDVSSFEDPNNVOJDBUJPOFSSPSCFUXFFOUIF%.4BOE1*.PS%.4DBOOPMPOHFSHBUIFSQPXFSDPOTVNQUJPO 
%.4TUPSFTQPXFSEJTUSJCVUJPOSBUJPGPSBMMJOEPPSVOJUT"TTPPOBTDPNNVOJDBUJPOCFUXFFOUIFNSFTVNFTBOEQPXFSJOGPSNBUJPOJT
USBOTNJUUFEUPUIF%.4 QPXFSEJTUSJCVUJPOEVSJOHUIFJOUFSSVQUFEQFSJPEJTSFDPWFSFEBTOPSNBMDPOEJUJPO

(8) Not equal stand-by power distribution (In case all the indoor units are stopped)
4JODFUIFSFBMXBZTFYJTUTFSSPSJOFBDIQPXFSDPOTVNQUJPOBNPVOU EJTUSJCVUFETUBOECZQPXFSNBZOPUCFFRVBMGPSEJGGFSFOU
BJSDPOEJUJPOJOHTZTUFN#VUUIFEJGGFSFODFJTTPTNBMMUIBUJUJTOFHMJHJCMF

3VO 4UPQ 4UPQ 4UPQ 4UPQ

#$ %&
" # $
% & #z%

95
Control Systems

III Integrated management systems


1. DMS2
MIM-D00AN

6) Function

Power distribution

Power distribution equation

%.4

1*.

1PXFSTVQQMZ

33 (

(

(

1PXFSTVQQMZ
G1

f When configuring the DMS2 and the whole system, mapping of watt-hour meters for indoor/outdoor units must be precisely
assigned for correct power distribution.

.BJO 'BO 4UBOECZDBQBDJUZPGJOEPPSVOJU9


*OEPPSVOJUQPXFS9JO(8BUUIPVS"Y
5PUBMDBQBDJUZPG(

.BJO 'BO 4UBOECZDBQBDJUZPGJOEPPSVOJU9


*OEPPSVOJUQPXFS9JO(8BUUIPVS#Y
5PUBMDBQBDJUZPG(
'BO 4UBOECZDBQBDJUZPGJOEPPSVOJU9
8BUUIPVS%Y
5PUBM'BO4UBOECZDBQBDJUZPG(

.BJO 'BO 4UBOECZDBQBDJUZPGJOEPPSVOJU9


*OEPPSVOJUQPXFS9JO( (8BUUIPVS$Y
5PUBMDBQBDJUZPG( (
'BO 4UBOECZDBQBDJUZPGJOEPPSVOJU9
8BUUIPVS&Y
5PUBM'BO4UBOECZDBQBDJUZPG( (
96
Example

4VQQPTFDBQBDJUZWBMVFTBDDVNVMBUFEBUEVSJOHPOFXIPMFEBZJTBTGPMMPXT

4USPOH
DPPMJOH 8FFLDPPMJOH 'BONPEF 4UPQ

L8IDPOTVNFE
PVUEPPS JOEPPS

.BJODBQBDJUZ .BJODBQBDJUZ .BJODBQBDJUZ .BJODBQBDJUZ


'BODBQBDJUZ 'BODBQBDJUZ 'BODBQBDJUZ 'BODBQBDJUZ
4UBOECZDBQBDJUZ 4UBOECZDBQBDJUZ 4UBOECZDBQBDJUZ 4UBOECZDBQBDJUZ
4VN 4VN 4VN 4VN

MANAGEMENT SYSTEMS
INTEGRATED
*OEPPSVOJUDBQBDJUZ Y
1EPG*OEPPSVOJU" Y5PUBML8I L8I
5PUBMDBQBDJUZ    

Y
1EPG*OEPPSVOJU# L8I
   

Y
1EPG*OEPPSVOJU$ L8I
   

Y
1EPG*OEPPSVOJU% L8I
   

97
Control Systems

III Integrated management systems


1. DMS2
MIM-D00AN

6) Function

Power distribution

Installation example (Allowed)

%.4

1*.

1PXFSTVQQMZ

33
(

(

(

1PXFSTVQQMZ
G1

Mapping watt-hour meters to indoor/outdoor units


t8BUUIPVSNFUFS"JTNBQQFEUPBMMJOEPPSPVUEPPSVOJUTJO(

t8BUUIPVSNFUFS#JTNBQQFEUPUIFPVUEPPSVOJUJO(

t8BUUIPVSNFUFS$JTNBQQFEUPUIFPVUEPPSVOJUTJO(BOE(

t8BUUIPVSNFUFS%JTNBQQFEUPUIFJOEPPSVOJUTJO( (

t8BUUIPVSNFUFS&JTNBQQFEUPUIFJOEPPSVOJUTJO(

Ú*OTUBMMBUJPOBCPWFJTBMMPXFEXJUIQSPQFSNBQQJOHDPOGJHVSBUJPO

; Note
Š8BUUIPVSNFUFSDBOCFTIBSFEUPUIFNVMUJQMFJOEPPSPVUEPPSTZTUFNT

98
Installation example (Not allowed)

%.4

1*.

1PXFSTVQQMZ

(
33

MANAGEMENT SYSTEMS
INTEGRATED
(

(

1PXFSTVQQMZ
G1

All indoor units in one outdoor unit must have the same power source.
t*OTUBMMBUJPOBCPWFDBOOPUCFBWBJMBCMFGPSUIFSFBTPOUIBUPOFJOEPPSVOJUJO(IBTEJGGFSFOUQPXFSTPVSDFGSPNUIFPUIFSJOEPPSVOJUT
*OUIJTDBTF GSBDUJPOBMQPXFSPG%DPOTVNFECZUIFTFQBSBUFQPXFSFEJOEPPSVOJUJO(JTEJTUSJCVUFEUPUIFJOEPPSVOJUTJO(BOE(

99
Control Systems

III Integrated management systems


1. DMS2
MIM-D00AN

6) Function

Power distribution
(10) Setting the inspection section
*GZPVXBOUUPDIFDLUIFEJTUSJCVUJPOSFTVMUCZUJNFQFSJPE TFUUIFUJNFTFDUJPO
:PVNVTUVTF4/&5UPDIFDLUIFEJTUSJCVUJPOSFTVMUCZUJNFQFSJPE

(11) Setting the power distribution environment


5IJTJTJNQPSUBOUUBTLGPSDIFDLJOHQSFDJTFFOFSHZDPOTVNQUJPOPGUIFPVUEPPSJOEPPSVOJU&BDIXBUUIPVSNFUFSDPOOFDUFEUP
PVUEPPSVOJUNVTUCFDIFDLFEGPSXIJDIDIBOOFMPGUIF1*.JOUFSGBDFNPEVMFJUJTDPOOFDUFE
5IFO1*.DIBOOFMNVTUCFTFUBDDPSEJOHUPUIFPVUEPPSVOJU

*OEPPSVOJUTNVTUCFDIFDLFEXIJDIXBUUIPVSNFUFSJUJTDPOOFDUFEUPBOEUIFO1*.DIBOOFMPGUIFDPSSFTQPOEJOHXBUUIPVS
NFUFSNVTUCFTFUBDDPSEJOHUPJOEPPSVOJU1*.DIBOOFMBTTIPXOCFMPX

100
Example of watt hour meter installation ❶ Installing watt-hour meter to outdoor/ indoor unit

.BJODJSDVJUCSFBLFS

1*.
8BUUIPVSNFUFS" $)
8BUUIPVSNFUFS# $)
Address 0 8BUUIPVSNFUFS$ $)
8BUUIPVSNFUFS% $)

A/ B

R1/R2

A B C D
1 phase power

0 1 2

MANAGEMENT SYSTEMS
F1/F2

INTEGRATED
1JQF
DPOOFDUJPO
R1/R2

0 1 2

F1/F2

1JQF
DPOOFDUJPO
3 phase power

Ú$POOFDUBQQSPQSJBUFXBUUIPVSNFUFSUPPVUEPPSJOEPPSVOJU

101
Control Systems

III Integrated management systems


1. DMS2
MIM-D00AN

6) Function

Power distribution

Example of watt hour meter installation ❷ Installing 1 watt-hour meter to all indoor units

.BJODJSDVJUCSFBLFS
1*.
8BUUIPVSNFUFS" $)
8BUUIPVSNFUFS# $)
Address 0 8BUUIPVSNFUFS$ $)
8BUUIPVSNFUFS% $)

A B C

A/ B
R1/R2

1 phase power

0 1 2

F1/F2
1JQF
DPOOFDUJPO
R1/R2

0 1 2

F1/F2
1JQF
DPOOFDUJPO
3 phase power

4JODFBMMJOEPPSVOJUT
BSFDPOOFDUFEUP
XBUUIPVSNFUFS 1*.
DIBOOFMBEESFTTPGBMM
JOEPPSVOJUTJTTBNF

102
Example of watt hour meter installation ❸ Using CT watt-hour meter to and outdoor unit

.BJODJSDVJUCSFBLFS
RS T N

1*.  

 
Address 0  
R1/R2

$5UZQFXBUUIPVSNFUFS
8BUUIPVSNFUFS" $)
8BUUIPVSNFUFS# $)
3 phase 4 wire voltage
R1/R2

8BUUIPVSNFUFS$ $)
8BUUIPVSNFUFS% $)
A B C D
1 phase power

0 1 2

MANAGEMENT SYSTEMS
F1/F2

INTEGRATED
1JQF
DPOOFDUJPO
R1/R2

0 1 2

F1/F2

1JQF
DPOOFDUJPO
3 phase power

<4FUUJOHBOEDIFDLJOH
XBUUIPVSNFUFS>
'SPNUIFNFOV $5
QSPQPSUJPOPGUIF$5
XBUUIPVSNFUFSNVTU
CFFOUFSFE

; Note
t"GUFSFOUFSJOH$5QSPQPSUJPOPGUIF$5XBUUIPVSNFUFS XBUUIPVSNFUFSNVTUCFTFUUPDPSSFDUPVUEPPSJOEPPSVOJUT
GSPNUIF<$IBOOFMTFUUJOHCZJOEPPSVOJU>XJOEPX

103
Control Systems

III Integrated management systems


1. DMS2
MIM-D00AN

6) Function

Power distribution

Checking the watt-hour meter connection

,JMPXBUUIPVSIJTUPSZPGUIFXBUUIPVSNFUFS DPOOFDUFEUPFBDI1*.JOUFSGBDFNPEVMF DBOCFDIFDLFE


.BYJNVNEBZTXPSUIPG,JMPXBUUIPVSIJTUPSZDBOCFDIFDLFE

104
Setting virtual watt-hour meter

8IFOXBUUIPVSNFUFSPS1*.JOUFSGBDFNPEVMFJTOPUJOTUBMMFEUPBXBUUIPVSNFUFSDIBOOFM WJSUVBMDIBOOFMDBOCFVTFEUPNBOVBMMZ
EJTUSJCVUFUIFQPXFSEJTUSJCVUJPO

MANAGEMENT SYSTEMS
INTEGRATED
tMaximum 128 virtual channel can be used.
tAddress of the virtual channel will be displayed as following.
(24~31).(1~16)

; Note
t8IFO1*.JOUFSGBDFNPEVMFJTOPUJOTUBMMFE 1*.DIBOOFMPGUIFPVUEPPSJOEPPSVOJUXJMMCFJOBDUJWF

105
Control Systems

III Integrated management systems


1. DMS2
MIM-D00AN

6) Function

Power distribution

Caution

1PXFSEJTUSJCVUJPOGVODUJPOJTPOMZTVQQPSUFEUPBJSDPOEJUJPOFSTBOE")6&37JTOPUTVQQPSUFE

%.4 0O0GGDPOUSPMMFS 0VUEPPSVOJU


.BJO .BJO .BJO
3.$ 3.$ 3.$

33

0OMZBQQMJFTUPJOEPPSVOJU

106
User authorization management

MANAGEMENT SYSTEMS
INTEGRATED
tAdmin (Administrator) : $BOBDDFTTBMMNFOVT BDDFTTJCMFNFOVDBOOPUCFDIBOHFE
tManager : %FGBVMUTFUUJOHo$BOBDDFTTBMMNFOVT BDDFTTJCMFNFOVDBOCFDIBOHFE
tRegular user : %FGBVMUTFUUJOHo$BOBDDFTT<$POUSPMBOENPOJUPSJOH>NFOVPOMZ

Editing user authorization

t"DDFTTJCMFNFOVBVUIPSJ[BUJPOPGNBOBHFSJTFEJUBCMF
4FMFDUEFTFMFDUUIFDIFDLCPYPGUIFGVODUJPOBOETBWFUIFTFUUJOHUPDIBOHFUIFBVUIPSJ[BUJPO

107
Control Systems

III Integrated management systems


1. DMS2
MIM-D00AN

6) Function

User management

f You can add or delete the user who access DMS2 through web.

f Authorization of the added user can be set from [Admin], [Manager], [Regular user].

108
Zone management
t;POFFEJU6TFSDBOBSSBOHFUIFJOEPPSVOJUTGPSDPOWFOJFOUNBOBHFNFOU
t4FUUJOHUIFVTFSBVUIPSJ[BUJPO$BOSFTUSJDUBDDFTTJCMFJOEPPSVOJUTEFQFOEJOHPOUIFVTFS*%

Zone edit

MANAGEMENT SYSTEMS
INTEGRATED
Initial setting

Zone edit :
ƒAdd, delete zone
ƒChange name
ƒMove indoor unit

109
Control Systems

III Integrated management systems


1. DMS2
MIM-D00AN

6) Function

Setting the user authorization

f Authorization to control and monitor a zone of indoor units can be assigned according to User ID
❶Select the zone and select a user ID who can access the zone.
t"DDFTTBVUIPSJ[BUJPODBOCFTFUCZ[POF
❷After setting, click [Save] to complete the authorization setting.

f User access authorization applies to all indoor units of the zone in same manager.

110
2. S-NET3
MST-P3P

1) Features

PC program designed to manage system air


conditioners in a large site.
ƒ.BY%.4DPOOFDUJPO
ƒ.BY JOEPPSVOJUDPOUSPMMJOHBOENPOJUPSJOH
ƒ*OUFHSBUFENBOBHFNFOUPGJOEPPSVOJUT WFOUJMBUPST
BOE")6
ƒ.BOBHFTPQFSBUJPOBOEFSSPSIJTUPSZ
ƒ$IFDLJOEPPSPVUEPPSVOJUDZDMFEBUB
ƒ*OUFHSBUFENBOBHFNFOUPGQFBLDPOUSPMJOTJOHMFQSPHSBN

MANAGEMENT SYSTEMS
2) PC specifications

INTEGRATED
Item Model Details
$16 1FOUJVNPSBCPWF
.FNPSZ .PSFUIBO.#
PC
)%% .PSFUIBO(CZUFTQBDFBWBJMBCMF ; Note
/FUXPSL . Model .4511
8JOEPXT/5 8JOEPXT 8JOEPXT91  Number of connection .BY%.4T
OS 
8JOEPXT7*45" 8JOEPXT

3) System connection

4/&5 0O0GG *OEPPS0VUEPPSVOJUT


DPOUSPMMFS

%.4

)6#

*OUFSOFU

111
Control Systems

III Integrated management systems


2. S-NET3
MST-P3P

4) Function
(1) S-NET3 function description
7JFXUIFNBOBHFNFOU
$POUSPMBOENPOJUPSUIFJOEPPSVOJUT NBY VOJUT

TUSVDUVSF
$IFDLBOESFGFSUIFTUBUFPGWBSJPVTEFWJDFTTVDIBTJOEPPSPVUEPPSVOJUT 
7JFXUIFJOTUBMMBUJPOTUSVDUVSF
0O0GGDPOUSPMMFS BOE*.
4FUUIFPQFSBUJPONPEF UFNQFSBUVSF GBOTQFFE BOEGBO
*OEPPSVOJU&37DPOUSPM
Control & Monitoring $POUSPM.POJUPSJOHEJSFDUJPOPGJOEPPSVOJU&37
*OEPPSVOJU&37NPOJUPSJOH .POJUPSUIFTUBUVTPGJOEPPSVOJU&37
$IFDLUIFPVUEPPSVOJUTDZDMFEBUBBOEUIFDZDMFEBUBPGUIFMJOLFEJOEPPS
7JFXPVUEPPSVOJU
VOJUT
7JFX%.4 $IFDLUIFTUBUVTEBUBPGUIFDPOUSPMVOJUMJOLFEUP%.4

$SFBUFOFXTDIFEVMF 4FUOFXTDIFEVMF

7JFXTDIFEVMF $IFDLUIFTDIFEVMFPGUIFTFMFDUFEJOEPPSVOJU

4UBSU4UPQTDIFEVMF 4UBSU4UPQTDIFEVMFBQQMJDBUJPO
Schedule
4UPSF$BMMTDIFEVMF 4UPSF$BMMBQSFQBSFETDIFEVMF

7JFXEBJMZTDIFEVMF $POGJSNFBDITDIFEVMFCZEBUF

4FUDPNNPOFYDFQUJPOEBUF 4FUUIFEBUFXIJDITDIFEVMFPQFSBUJPOJTOPUBQQMJFEPO

6TBHFUJNFBOEQPXFS $IFDLUIFVTBHFUJNFBOEQPXFSGPSUPUBM HSPVQ BOEJOEJWJEVBMJOEPPSVOJUT


'PSQSFQBSJOHUIFSFQPSUPOUIFQPXFSDPOTVNQUJPOCZFBDIJOEPPSVOJUGPSUIF
1PXFSDPOTVNQUJPOSFQPSU
QFSJPETFU
Usage time and power
1PXFSEJTUSJCVUJPO
&EJUBOJOEPPSVOJUTQPXFSNBOBHFNFOUTUSVDUVSF
NBOBHFNFOUHSPVQFEJUJPO
4FUUIFFMFDUSJDJUZSBUFTFDUJPO 4FUVQUPTFDUJPOTGPSFMFDUSJDJUZCJMMJOHNBOBHFNFOU

*OEPPSVOJUTUBUVT $IFDLUIFTUBUVTPGJOEPPSVOJUPQFSBUJPOUFNQFSBUVSFTFUUJOHQFSQFSJPE

Statistics and analysis 6TBHFUJNFBOEQPXFS $IFDLUIFVTBHFUJNFBOEQPXFSGPSUPUBM HSPVQ BOEJOEJWJEVBMJOEPPSVOJUT

*OEPPSVOJUVTBHF 5IFVTBHFSBUJPPGBMMJOEPPSVOJUTGPSBTQFDJGJDQFSJPE
4FUUIFFOWJSPONFOUSFMBUFEUP4/&5
4FUFOWJSPONFOU
QBTTXPSE MBOHVBHF UFNQFSBUVSFVOJU

4FU%.4 4FUUIF%.4UPDPOOFDUXJUI4/&5

3FGFSFWFOUMPH 3FGFSUIFXBSOJOH FSSPS EBUBPGJOEPPSVOJUT


System management
3FOFXJOTUBMMFEEFWJDF
.PEJGZ4/&5EBUBJGJOTUBMMBUJPOEBUBIBTCFFODIBOHFE
JOGPSNBUJPO
%.4CBDLVQSFTUPSF #BDLVQUIFEBUBPG%.4DPOOFDUFEUP4/&5

4/&5CBDLVQSFTUPSF #BDLVQUIFEBUBPG4/&5

112
(2) User functions
.BOBHFBSBOHFPGGVODUJPOTBDDFTTJCMFUPEJGGFSFOUUZQFTPGVTFSTTVDIBTSFHVMBSVTFS BENJOJTUSBUPSBOEJOTUBMMFS

User Administrator Installer


7JFXUIFUPUBMJOEPPSVOJU 0 0 0
4USVDUVSFFEJUJOH 9 0 0
5IFMJTUPGJOTUBMMFEEFWJDFT 9 0 0
8IPMFJOEPPSVOJUTUPQ 0 0 0
*OEPPSVOJU&37DPOUSPM.POJUPSJOH 0 0 0
7JFXUIFNBOBHFNFOUTUSVDUVSF 0 0 0
7JFXUIFJOTUBMMBUJPOTUSVDUVSF 9 0 0
7JFXPVUEPPSVOJUT %.4 9 0 0
4DIFEVMF 9 0 0
*OEPPSVOJUPQFSBUJPOTFUUJOH 9 9 0
6TBHFUJNFBOEQPXFS 9 0 0

MANAGEMENT SYSTEMS
1PXFSDPOTVNQUJPOSFQPSU 9 0 0
1PXFSEJTUSJCVUJPONBOBHFNFOUHSPVQFEJU 9 0 0

INTEGRATED
1PXFSEJTUSJCVUJPOTFDUJPOTFUUJOH 9 9 0
4UBUJTUJDT"OBMZTJT 9 0 0
4/&5TFUUJOH 9 0 0
%.4TFUUJOH 9 9 0
&WFOUMPHSFGFSFODF 9 0 0
5SBDLJOH 9 9 0
%.4SFTUPSBUJPO 9 9 0
%.4CBDLVQ 9 0 0
4/&5SFTUPSBUJPOCBDLVQ 9 0 0

5) Detail function description


(1) S-NET3 display

Log-in

4FMFDUVTFS
4FMFDUBENJOJTUSBUPS
4FMFDUJOTUBMMFS

1BTTXPSEJOQVU

-PHJOCVUUPO

113
Control Systems

III Integrated management systems


2. S-NET3
MST-P3P

5) Detail function description


(1) S-NET3 display
Control and monitoring
.BOBHFNFOUTUSVDUVSF $POUSPMNPOJUPSJOHXJOEPX
NPOJUPSJOHXJOEPX

.PWFUP*OEPPS
.BOBHFNFOU
VOJUDPOUSPM
TUSVDUVSF*OTUBMMBUJPO
XJOEPX
TUSVDUVSFEJTQMBZ
XJOEPX
*OEPPSVOJU
DPOUSPM

&37DPOUSPM

.BJONFOV
XJOEPX
-PHFSSPSEJTQMBZ
XJOEPX

Installation structure window


4FMFDUUIFJOTUBMMBUJPOTUSVDUVSFUBCUIFOTFMFDU%.4DPOOFDUFEUP4/&5JUJTQPTTJCMFUPTFFUIFQSPHSBNWFSTJPO TUBUVTPGUIF
TFMFDUFE%.4 UIFQSPHSBNWFSTJPOBOEDPNNVOJDBUJPOTUBUVTPG0O0GGDPOUSPMMFS
*GJOEPPSPSPVUEPPSVOJUJTTFMFDUFEBUUIFJOTUBMMBUJPOTUSVDUVSF JUJTQPTTJCMFUPDIFDLUIFIBSEXBSFJOGPSNBUJPOPGUIFTFMFDUFEEFWJDF

Selecting management structure Selecting installation structure

f When DMS2 & OnOff controller are selected.


t%.4TUBUVT %.4QSPHSBNWFSTJPO 
MBTUUSBDLJOHEBUFBOE.BTUFS4MBWFTFUUJOH
TUBUF
t%JTQMBZTNPEFMOBNF TPGUXBSFWFSTJPO 
DPNNVOJDBUJPOTUBUFPGDFOUSBMJ[FE
DPOUSPMMFS 1*.

114
Installation structure window

f When outdoor unit is selected

MANAGEMENT SYSTEMS
INTEGRATED
t0VUEPPSVOJUDZDMFEBUB PVUEPPSVOJUNPEFM JOUFSGBDFNPEVMFNPEFMBOEJOUFSGBDFNPEVMFQSPHSBNWFSTJPOJTEJTQMBZFE

f When indoor unit is selected

t*OEPPSVOJUPQFSBUJPOTUBUVT JOEPPSVOJUDZDMFEBUBBOEJOEPPSVOJUNPEFMDPEFJTEJTQMBZFE

115
Control Systems

III Integrated management systems


2. S-NET3
MST-P3P

5) Detail function description


(1) S-NET3 display

Installation structure window

f When DI is selected

f When DO is selected

116
Control

t$POUSPMJOEPPSVOJU&37UISPVHIUIFDPOUSPMXJOEPXUIBUBQQFBSTPOUIFTDSFFO
t$POUSPMUPUBMJOEPPSVOJUT UIFPQFSBUJPONPEFPGJOEPPSVOJUT NVMUJQMFTFMFDUJPO UFNQFSBUVSF GBOTQFFE BOEGBOEJSFDUJPO
t4FU6QQFS-PXFSUFNQFSBUVSFMJNJUTPUIBUUFNQFSBUVSFDBOOPUCFTFUPVUTJEFPGUIFMJNJUFEUFNQFSBUVSFSBOHF
t&OBCMFEJTBCMFSFNPUFDPOUSPMVTBHF
t$IFDLUIFTDIFEVMFPGUIFTFMFDUFEJOEPPSVOJU

f Deselect device f Selecting indoor unit and ERV together

MANAGEMENT SYSTEMS
INTEGRATED
f Selecting indoor unit f Selecting ERV

117
Control Systems

III Integrated management systems


2. S-NET3
MST-P3P

5) Detail function description


(1) S-NET3 display

Schedule control

❶ Schedule setting
t"CMFUPTFUBTDIFEVMFUPDPOUSPMJOEPPSVOJUTBOE&37T DSFBUJOH NPEJGZJOH EFMFUJOH

t"CMFUPTFUXFFLMZ EBJMZ POFEBZTDIFEVMF
t"CMFUPDPOUSPMUIFPQFSBUJPONPEF UFNQFSBUVSFTFUUJOH GBOTQFFE GBOEJSFDUJPOEVSJOHUIFTDIFEVMFDPOUSPM

4DIFEVMFMJTU
XJOEPX

4DIFEVMFEJTQMBZXJOEPX

Ú&BTZTDIFEVMFDPOUSPMGPSVTFSXJUIUIFXJ[BSENFUIPE TUFQCZTUFQTFUUJOH


f The 1st step (select a schedule mode)

0OFEBZPOMZ 3FQFBUEBJMZ 3FQFBUXFFLMZ

f The 2nd step (select the indoor units to apply a schedule to)
t%JTQMBZUIFUPUBMJOEPPSVOJUTJO4/&5
t"CMFUPTFMFDUJOEJWJEVBMJOEPPSVOJUT 0O0GGDPOUSPMMFS %.4

118
Schedule control

f The 3rd step (schedule operation setting)


t4FUVQUJNFCZESBHHJOHPOUIFUJNFUBCMF
t4FUUIFTDIFEVMFXJUIUIFDPOUSPMQBOFMPOUIFSJHIU 0QFSBUJPONPEFUFNQFSBUVSFTFUUJOH GBOTQFFE GBOEJSFDUJPOBOE
SFNPUFDPOUSPMVTF

t$MJDLUIFTDIFEVMFUJNFTFUVQXJOEPXUPEJTQMBZBTDIFEVMFNPEJGJDBUJPOXJOEPX BCMFUPNPEJGZBTDIFEVMFUJNF 
PQFSBUJPONPEFBOEUFNQFSBUVSFTFUUJOH


$POUSPMQBOFM
$MJDLUXJDF

5JNFNPEJGJDBUJPO

MANAGEMENT SYSTEMS
CBTFEPONJOVUFT

5FNQFSBUVSFTFUUJOH

INTEGRATED
0QFSBUJPONPEF
3FNPUFDPOUSPMVTF

5JNFTFUUJOHCZESBHHJOH
CBTFEPONJOVOJU

4DIFEVMFNPEJGJDBUJPOQBOFM

f The 4th step (Schedule period and exception date setting)


t$MJDLUIFEBUFPOUIFDBMFOEBSUPTFUUIFEBUF PODFTFMFDUFE UIFEFTJHOBUFEEBUFJTEJTQMBZFEJOSFE


4DIFEVMFOBNF

4DIFEVMFQFSJPETFUUJOH

4DIFEVMFFYDFQUJPO
EBUFTFUUJOH

f Schedule setting completion


t%JTQMBZTBTDIFEVMFMJTUUPCFBVUPNBUJDBMMZ
BQQMJFEUPUIFTDIFEVMF

%JTQMBZUIFOBNFPG %JTQMBZTFUTDIFEVMF
TFUTDIFEVMF

119
Control Systems

III Integrated management systems


2. S-NET3
MST-P3P

5) Detail function description


(1) S-NET3 display

Schedule control

❷ Schedule modification
t$MJDLUIFTFUTDIFEVMFEJTQMBZXJOEPXUXJDFUPEJTQMBZUIFNPEJGJDBUJPOQBOFM
5IFOJUJTQPTTJCMFUPNPEJGZWBSJPVTGVODUJPOTTVDIBTTDIFEVMFUJNF PQFSBUJPONPEFBOEUFNQFSBUVSFTFUUJOH
t"CMFUPDBSSZPVUWBSJPVTGVODUJPOTTVDIBTBTDIFEVMFOBNFDIBOHF TDIFEVMFEFMFUF JOEPPSVOJUBEEJUJPOBOEEFMFUJPOXJUIUIFJDPOT
POUIFMFGUNFOVXJOEPX

"EE%FMFUFJOEPPSVOJUGPSTDIFEVMFDPOUSPM
%FMFUFBTFUTDIFEVMF
.PEJGZBTDIFEVMFOBNF

Usage time and power consumption


❶ Usage time and power
t"CMFUPTFBSDIGPSUIFQPXFSDPOTVNQUJPOBOEVTBHFUJNFCZEJGGFSFOUDPOEJUJPOTJODMVEJOHUIFUPUBMJOEPPSVOJUTBQQMJFEUP4/&5 
0O0GGDPOUSPMMFS JOEJWJEVBMJOEPPSVOJU0O0GGDPOUSPMMFS JOEJWJEVBMJOEPPSVOJU

5PUBMJOEPPSVOJUVTBHFSFGFSFODF *OEJWJEVBMJOEPPSVOJUVTBHFSFGFSFODF

❷ Power consumption report


t"CMFUPQSJOUPVUUIFBNPVOUPGQPXFSDPOTVNFEGPSBTQFDJGJDQFSJPEPGUJNFJOUIFGPSNPGSFQPSU
t5IFBQQMJDBCMFGPSNBUTJODMVEF1%' 595 )5.- $47 .)5 &9$&- HSBQIJDEPDVNFOUT

5ZQFTPGEPDVNFOUUPCFTUPSFE

120
Usage time and power consumption

❸ Power management structure editing


t+VTUBTUIFTUSVDUVSBMFEJUJOHBUUIFNPOJUPSJOH QPXFSNBOBHFNFOUDBOCFSFTUSVDUVSFEUPFOTVSFHSFBUFSDPOWFOJFODFGPS
BENJOJTUSBUPST
t0ODFUIFQPXFSNBOBHFNFOUTUSVDUVSFJTFEJUFE QPXFSDPOTVNQUJPOSFQPSUBOEVTBHFDBOCFSFGFSSFEJOUIFFEJUFEGPSNBUT

1PXFSTUSVDUVSFFEJUJOHNFOV

1PXFSTUSVDUVSFFEJUJOHXJOEPX

MANAGEMENT SYSTEMS
INTEGRATED
❹ Power section setting
t*UDBOCFSFGFSSFEBOEEJWJEFEJOUPNBYTFDUJPOTGPSQPXFSDPOTVNQUJPOSFGFSFODF
t*UJTQPTTJCMFUPSFGFSPSQSFQBSFSFQPSUTGPSVTBHFUJNFBOEQPXFSDPOTVNQUJPOCZEJWJEJOHTFDUJPOCZFBDIIPVS

"CMFUPBEKVTUUIFTFDUJPOTCZJOQVUUJOHSFMFWBOUUJNF

121
Control Systems

III Integrated management systems


2. S-NET3
MST-P3P

5) Detail function description


(1) S-NET3 display

Statistics and analysis

❶ Indoor unit status


t"CMFUPTFFUIFPQFSBUJPOTUBUVTPGTFMFDUFEJOEPPSVOJUTBOESPPNUFNQFSBUVSFGPSUIFQSFTFOUBOEUIFQBTU
t"CMFUPSFGFSUPUIFPQFSBUJPOTUBUVTGPSUIFMBTUUXPEBZT*GUIFSFGFSFODFEBZJTPVUPGSBOHF BOFSSPSNFTTBHFXJOEPXXJMMBQQFBS

)PVSMZJOEPPSVOJUPQFSBUJPOBOE
UFNQFSBUVSFEJTQMBZ

4FMFDU
JOEPPSVOJU %JTQMBZFSSPSTJGUIFXSPOH
QFSJPEIBTCFFOTFU

❷ Power consumption of indoor units


t%JTQMBZTUIFVTFUJNFBOEQPXFSDPOTVNQUJPOSBUJPTGPSUIFJOEPPSVOJUTDPOOFDUFEUPFBDI%.4

1FSJPESFGFSFODF

%.4TFMFDUJPO

122
System management
❶ Environment setting
t4FUUIFFOWJSPONFOUPG4/&5
t4FUBENJOJTUSBUPSQBTTXPSE MBOHVBHF UFNQFSBUVSFVOJU EFGBVMUWBMVFGPSJOEPPSVOJU FUD
t%FUFSNJOFJGQFBLQPXFSXJMMCFEJTQMBZFEPSOPUJOUIFNFOVTFUUJOH ,PSFBONBSLFUPOMZ


-BOHVBHFTFUUJOH
-PHEBUFWJFXTFUUJOH
5FNQFSBUVSFVOJUTFUUJOH*UJTTFUBVUPNBUJDBMMZ
EFQFOEJOHPOJOEPPSVOJU

MANAGEMENT SYSTEMS
INTEGRATED
❷ DMS2 setting
t4FUUIF%.4UPDPOOFDUXJUI4/&5
t$MJDLATBWFBGUFSJOQVUUJOH*1BOEQBTTXPSET 
BOEJUXJMMBUUFNQUUPNBLFDPNNVOJDBUJPOXJUI4/&5BOE%.4UIFOEJTQMBZ
OPSNBMXIFODPNNVOJDBUJPOJTNBEF

%.4TFUVQXJOEPX

8IFOB%.4UPDPOOFDUXJUI %.4UJNFTFUUJOH
4/&5JTBEEFE

1BTTXPSEJOQVU
%.4TBDDFTT*1JOQVU

; Note
Š%.4IBTUXPQBTTXPSET0OFJTBQBTTXPSEOFFEFEUPDPOOFDUUPB%.4XFCDMJFOU TFUBUUIFVTFSNBOBHFNFOU
UIFPUIFSJT
OFDFTTBSZUPNBLFBDDFTTUP4/&5 TFUBUUIFTZTUFNFOWJSPONFOU

Š8IFOUIFXSPOHQBTTXPSEGPS4/&5JTJOQVU BNFTTBHFJOEJDBUJOH%.4oBDDPVOUSFDPHOJUJPOGBJMVSFBQQFBST

123
Control Systems

III Integrated management systems


2. S-NET3
MST-P3P

5) Detail function description


(1) S-NET3 display

System management
❸ View event log
t"CMFUPDIFDLWBSJPVTJOGPSNBUJPOTVDIBTJOEPPSPVUEPPSVOJUTDPOOFDUFEUP4/&5 DPOUSPMEFWJDFFSSPSXBSOJOH JOGPSNBUJPO
EFUBJMTCZEBUF

4FUUIFMJTUPGFWFOUT
2VFSZQFSJPETFUUJOH

&WFOUEJTQMBZ

❹ Information update of the installed device


t"CMFUPDBSSZPVUJOGPSNBUJPOVQEBUFPSUSBDLJOHGPSUIFJOTUBMMFEEFWJDF
t5SBDLJOHJOWPMWFTSFDFJWJOHEBUBGSPN%.4BGUFSUSBDLJOHJUTPBTUPSFOFXEBUB XIFSFBTEBUBSFOFXBMJOWPMWFTDPSSFDUJOHEBUB
GSPN%.4BGUFSSFDFJWJOHEBUBXJUIPVU%.4USBDLJOH

-JTUPGDPOUSPMEFWJDFTDPOOFDUFEUP%.4 5SBDLJOHJTVOEFSXBZ

124
System management
❺ DMS2 backup and restoration
t"CMFUPCBDLVQBOESFTUPSFUIF%.4EBUBDPOOFDUFEUP4/&5
t#BDLVQSFGFSTUPBDUJWJUJFTPGTUPSJOHEBUBJOUIFEBUBGPMEFSJO1$
4FMFDUBMM%.4T
#BDLVQ
3FTUPSBUJPO
*OEJDBUFBCBDLVQGJMFJODMVEJOHUIF
EJSFDUPSZQBUI

*OEJDBUFBCBDLVQEBUF

MANAGEMENT SYSTEMS
INTEGRATED
❻ S-NET3 backup and restoration
t"CMFUPCBDLVQBOESFTUPSFEBUBPG4/&5
t#BDLVQJOWPMWFTJOCBDLJOHVQBMMEBUBJO4/&55IVT JGCBDLVQEBUBJTSFTUPSFEJOB1$XIFSF4/&5JTJOTUBMMFE 
JUXJMMQSPEVDFUIFTBNFFOWJSPONFOUUIBUJTQSFWJPVTMZVTFE

125
Control Systems

III Integrated management systems


2. S-NET3
MST-P3P

5) Detail function description


(2) S-NET3 log information

Log Contents
E9000 $POOFDUJPOJNQPTTJCMF
E9001 $POOFDUJPOEFOJFE
E9002 $POOFDUJPOGJOJTIFE
E9010 8*/,EFOJFE
E9011 %.4QBTTXPSEBVUIFOUJDBUJPOGBJMVSF
E9012 4FSJBMFYDIBOHFGBJMVSF
E9100 (FOFSBMFSSPSPOJOTUSVDUJPOUSBOTNJTTJPO
E9150 "UUFNQUUPUSBOTNJUUPB%.4OPUJODPOOFDUJPO
E9151 "UUFNQUUPUSBOTNJUUPB%.4OPUSFHJTUFSFE
E9200 (FOFSBMFSSPSPOSFTQPOTFBDDFQUBODF
E9250 5IFSFJTOPSFTQPOTFUPUIFSFRVFTUFEDPNNBOEEVFUP%.4GBJMVSFBOEPSOFUXPSLEFMBZ
E9300 9.-HFOFSBUJOH
E9400 9.-QBSTJOH
E9401 *OTUBMMBUJPOJOGPSNBUJPOPO4/&5BOE%.4EPFTOPUNBUDI DIFDLUSBDLJOHJOGPSNBUJPO
E9999 *OJUJBMJ[FEEFWJDFJOGPSNBUJPOVQEBUJOHEFWJDFTUBUVT
I101 $PNNPOVTFSMPHJO
I102 "ENJOJTUSBUPSVTFSMPHJO
I103 *OTUBMMFSMPHJO
I104 -PHJO
I105 -PHPVU
I201 5SBDLJOH
I202 3FRVFTUUPUSBDLJOH
I301 3FRVFTUUPTDIFEVMFDIBOHF
I801 *OTFSU%.4
I802 %FMFUF%.4
I803 %.4UJNFTFUUJOH
I9700 %.4DPOOFDUJPOBOEBVUIPSJ[BUJPOTVDDFTTGVM
I9701 3FDPOOFDUJPO
I9801 &NFSHFODZTUPQ

126
IV. Power distribution system
1 &MFDUSJDJUZNFUFSJOUFSGBDFNPEVMF       128

DISTRIBUTION SYSTEM
POWER

127
Control Systems

IV Power distribution system


1. Electricity meter interface module
MIM-B16N

1) Features

(Unit : mm)
240 64.80

Front view Side view

t1VMTFPVUQVUFMFDUSJDJUZNFUFSJOUFSGBDFVOJU
(max. 8 meters) Input : 100~240V AC, 50/60Hz, 1.0A
Power supply (adapter)
tDIBOOFMFOFSHZDPOTVNQUJPOEJTQMBZJOSFBMUJNF Output : 12V DC, 3.0A
t4ZTUFNDPOGJHVSBUJPOXJUICVUUPONBOJQVMBUJPO Operating temperature range -10ºC ~ 50ºC
t7BSJPVTUFYUNFTTBHFTJO-$%
t$VSSFOUDPNNVOJDBUJPOTUBUFJOEJDBUJPO Operating humidity range 10%RH~90%RH

DMS2 : 1000m
Maximum wiring length
Electricity meter : 200m

Electricity meter : max. 8 units


Number of interfaces
DMS2 : 1 unit

2) Display and buttons


③ ⑦

⑤ ⑥

No. Name Description


Information on current electricity readings, settings and operation state is displayed
① LCD window
(16 character x 2 line LCD).
Various menus are selected to monitor current electricity readings, to make
② Menu button
configuration settings for electricity meters, and to check the error/settings.
③ Power (blue) It’s ON when power is supplied normally.

④ Communication (orange) It blinks when communication between DMS2 and MIM-B16N normally works.

⑤ Pulse input (orange) Each of the 8 LEDs blinks whenever a pulse from an electricity meter is detected.

⑥ Communication (orange) Reserved

⑦ Check It’s ON when errors occur in communication or pulse input from electricity meters.

128

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGXY_ YWX[TW[TY\GGG㝘䟸G[aZ]aY_
3) Connectors

③ ④ ⑤

No. Name Description


8 terminals are allocated to interface pulse-type electricity meters. Each terminal is seen
① Pulse input terminals
with a dedicated address on DMS2.
② Power input 1PXFSTVQQMZWJBUIFQPXFSBEBQUFS

③ Reset button 1SFTTUIFCVUUPOUPSFTFUUIF.*.#/

④ COM1 Connection terminal for RS485 communication with DMS2.

⑤ COM2 Reserved

4) Address & option switches

SW1 SW2 SW3 SW4

DISTRIBUTION SYSTEM
POWER
Address switch Option switch

No Name Description

1 SW1 No function

2 SW2 MIM-B16N address switch. Address greater than 7 (8~F) is not recognized.

3 SW3 No function

4 SW4 No function

129

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGXY` YWX[TW[TY\GGG㝘䟸G[aZ]aY`
Control Systems

IV Power distribution system


1. Electricity meter interface module
MIM-B16N

5) Specifications on electricity meter


tCurrent flow on output : Current-sinking
tPulse rate :
1PXFSNFUFS_8IQVMTF OPEFDJNBMQVMTFSBUFBMMPXFE

(BTNFUFS_N3/pulse
8BUFSNFUFS_MJUFSQVMTF OPEFDJNBMQVMTFSBUFBMMPXFE

tPulse width :_NTXJUI UPMFSBODF OPEFDJNBMQVMTFSBUFBMMPXFE

tTime interval between pulses : min. 3ms


tAllowable current sinking : min. 15mA
tWithstanding voltage : min. 15V DC
tInterface circuitry : Electronic isolation circuitry recommended, no voltage output

1VMTFHFOFSBUJPOGSPN
electricity meter

Current source
Current sink Current flow(max. 15mA)

Current flow

Waveform of CH1~8

Over 4ms

20~1000ms

; Note
Š Interface circuitry of an electricity meter has to withstand min. 15mA and min. 15V DC, both of which are applied by MIM-B16N.
Š Even though MIM-B16N interface circuitry is realized with electric isolation components, it’s highly recommended that interface
circuitry of an electricity meter be designed with isolation to ensure robustness from contact spike or electric interference
during wiring.

130

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGXZW YWX[TW[TY\GGG㝘䟸G[aZ]aY`
6) Installation
MIM-B16N must not be installed in a way that power to MIM-B16N is off when one of the over-current circuit breakers
is switched off. Power supply to MIM-B16N must be off only when all the power supplies to refrigerant systems whose
power consumptions are monitored by the MIM-B16N are cut off. This is because every pulse from electricity meters of
some alive refrigerant systems must be sensed normally even if power supplies to
other refrigerant systems have troubles.
t&YBNQMF
8IFOUIFDJSDVJUCSFBLFS $.JTTXJUDIFEPGGGPSTPNFSFBTPOXIJMFUIFPUIFSTBSFTUJMMPO QVMTFTGSPNUIFFMFDUSJDJUZ
meters, EM1, EM2 and EM3 are not calculated by MIM-B16N, whose power is off by the CM1. This installation could
lead to errors in electricity billing function when power interruption in local areas occurs.

Main circuit breaker


for entire air-conditioning system

EM1 EM2 EM3 EM4


Pulse signal

CM1 AC Power
OFF

0 1 2

F1/F2

Refrigerant pipe

0 1 2

F1/F2

DISTRIBUTION SYSTEM
Refrigerant pipe

POWER
t&YBNQMF
&WFOXIFOUIFDJSDVJUCSFBLFS $.JTTXJUDIFEPGGXIJMFUIFPUIFSTBSFPO QVMTFTGSPNUIFFMFDUSJDJUZNFUFST &.
EM2 and EM3 are still calculated by MIM-B16N, whose power is not interrupted by CM1.

Main power breaker


for air-conditioning AC Power

EM1 EM2 EM3 EM4


Pulse signal

CM1
OFF

0 1 2

F1/F2

Refrigerant pipe

0 1 2

F1/F2

Refrigerant pipe

131

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGXZX YWX[TW[TY\GGG㝘䟸G[aZ]aZW
Control Systems

IV Power distribution system


1. Electricity meter interface module
MIM-B16N

7) Wiring
f Wiring to electricity meter
t Attention must be paid to make polarized connection between an electricity meter and MIM-B16N with correct specifications
on wires.
1VMTFUZQFFMFDUSJDJUZNFUFS MIM-B16N

+ + + +
Typical interface circuitry

+ +
Cable : 6OTIJFMEFEXJSFNN2 VCTF or equivalent
Length :.BYN

f Wiring to DMS2
t Make sure that communication cable is wired between DMS2 and MIM-B16N with the right polarity.
%.4 .*.%"/
MIM-B16N

A B A B

’ to another MIM-B16N
Cable : 6OTIJFMEFEXJSF_NN2 VCTF or equivalent
Length : .BYN

f Caution
t MIM-B16N can be connected with outdoor units/controllers to same channel of DMS2.
Ex) %.4$)1*. 0VUEPPSVOJU 0

1*. 5PVDIDPOUSPMMFS 0

J DM2, Outdoor unit or Controller should be new communication applied products.


J MIM-B16N should be connected to dedicated channel of DMS2.

132

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGXZY YWX[TW[TY\GGG㝘䟸G[aZ]aZX
8) Address assignment
Each of the electricity meters is assigned with the dedicated address depending on MIM-B16N address setting and the
position of the pulse input terminals.

SW1 SW2

CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8

f Electricity meter address assignment table


Pulse input terminal
SW2
CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8
0        
1        
2        
3        
4        
5        
6        
7        
8~15 Not recognized

CISTRIBUTION SYSTEM
9) MIM-B16N menu structure

POWER
Normal Display 1. Monitoring 1.1 Address

1.2 Option S/W


Current Time
1.3 Micom Ver.

CH1: 00000.0kWh 1.4 DB Code


CH2: 00000.0kWh
. 2. Configuration 2.1 Password
.
. 2.2 Meter Type
Displayed CH8: 00000.0kWh
repeatedly
2.3 Pulse Rate

2.4 Date&Time

2.5 Channel Use

2.6 Value Set

2.7 Value Clear

3. Check 3.1 Pulse Input

3.2 COM’ Check

3.3 Pulse Width

133

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGXZZ YWX[TW[TY\GGG㝘䟸G[aZ]aZX
Control Systems

IV Power distribution system


1. Electricity meter interface module
MIM-B16N

9) MIM-B16N menu structure


Main menu Sub menu Description

5IF.*.#/BEESFTTJTEJTQMBZFEXJUIUIFQIZTJDBMBEESFTT48BEEFECZ)POUIF
LCD window.
Ex) LCD SW2 setting
1.Monitoring
)  1.1 Address
31H 1
1*."EESFTT
… …
1.1 Address
37H 7 58 30 FF

1*. Address Fixed

Option switch setting to ON is displayed with the position number at the corresponding
positions while setting to OFF is shown with the mark ‘X’.
Monitoring Ex)
Option SW 1.2 Option S/W Example display : 1X
tOption switch 1 : On
1X
tOption switch 2 : Off

*UEJTQMBZT1*.TPGUXBSFWFSTJPO
Ex)
Micom version 1.3 Micom Ver.
130123

*UEJTQMBZT1*.TPGUXBSF%#DPEF
Ex)
DB Code 1.4 DB Code
DB91-01128A

The password, which is asked to enter to change the configuration setting, is used to prevent
VOBVUIPSJ[FEQFSTPOTGSPNBDDFTTJOH.*.#/'BDUPSZTFUUJOHJTA
1BTTXPSE Ex)

You can select each channel’s meter type.


Meter type %FGBVMUWBMVF1PXFS.FUFS
5ZQF1PXFS.FUFS (BTNFUFS 8BUFS.FUFS

You can set pulse rate of meter which connected to each channel.
Configuration [Range]
1VMTF8JEUI 1PXFSNFUFS_8IQVMTF /PEFDJNBMQVMTFSBUFBMMPXFE

(BTNFUFS_N3/pulse
8BUFSNFUFS_MJUFSQVMTF /PEFDJNBMQVMTFSBUFBMMPXFE

Date & time You can set current date and time.

You can set Enable/Disable state of each channel.


Channel use
*GZPVTFUi%JTBCMFw UIFO1*.EPFTOUEJTQMBZNFUFSWBMVFPGUIFEJTBCMFEDIBOOFM

Value set Initial meter value must be set as a starting point for each of the enabled interface channels.

Value clear Each or all the initial meter values are cleared when selected.

134

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGXZ[ YWX[TW[TY\GGG㝘䟸G[aZ]aZX
Main menu Sub menu Description

When pulse input is detected during the test period, the channel numbers are displayed.
Otherwise, the character ‘X’ is displayed on the corresponding channel position.
1VMTF*OQVU

Make a loopback connection between COM1 and COM2 to check if the DMS2
communication channel is working or not. Care must be taken for the connection polarity.

COM Check

When the COM1 communication channel is normal, the message ‘OK’ is displayed on the
LCD window.

Check It checks if the pulse width values of actually connected meter are valid or not.
t0,8IFOUIFQVMTFJTWBMJE QVMTFJTWBMJEXIFOIJHIQVMTFJTCFUXFFO_NTFD
0,
(M:####msec) will be displayed. #### represents the duration of the high pulse.

t/(8IFOUIFQVMTFJTJOWBMJE QVMTFJTWBMJEXIFOIJHIQVMTFJTCFUXFFO_NTFD
PS
XIFOUIFSFJTOPQVMTFJOQVUTGPSTFDPOET
/( .NTFD
XJMMCFEJTQMBZFE
1*.EPFTOPUDBMDVMBUFUIFFOFSHZDPOTVNQUJPOEVSJOHUIFDIFDLJOHQSPDFTT5IF
calculation will start after the check and returning to the upper menu.
1VMTF8JEUI

3.3 Pulse Width CH1 Check Start

DISTRIBUTION SYSTEM
CH1 Check OK Checking...

POWER
CH1 Check End
NG (M:0000msec)

135

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGXZ\ YWX[TW[TY\GGG㝘䟸G[aZ]aZX
Control Systems

IV Power distribution system


1. Electricity meter interface module
MIM-B16N

10) Setting parameters on DMS2 (MIM-D00AN)


f The following parameters for MIM-B16N can be also set and monitored on DMS2 (MIM-D00AN)
t.FUFSWBMVF .FUFSUZQFQVMTFSBUF $IBOOFMTUBUVT 5JNFTFUUJOH 1*.QBTTXPSE

<5SBDLJOHSFTVMUQBHF1*.i4FUUJOHw>

❋ DMS2 setting for MIM-B16N parameters

11) Error code


Error code Description
E613 &SSPSXIJDIPDDVSTXIFOUIFSFJTOPDPNNVOJDBUJPOCFUXFFO%.4BOE1*.4*.GPSNJOVUFT
E632 t&SSPSXIJDIPDDVSTXIFOUIFQVMTFXBTJOQVUEJGGFSFOUMZGSPNUIF1*.TFUUJOH
t *GUIFQVMTFXBTJOQVUUFEBUUIFWBMVFPVUTJEFPGNT_NTSBOHFGPSNPSFUIBOUJNFTPS
when high pulse was inputted for over 3 minutes)
E654 Memory Read/Write error.
E108 Error which occurs when same address was assigned to different devices.

136

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGXZ] YWX[TW[TY\GGG㝘䟸G[aZ]aZY
V. External control systems
1 External contact interface module . . . . . . 138
2 Multi tenant function controller (MTFC). . . 142

CONTROL SYSTEMS
EXTERNAL

137

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGXZ^ YWX[TW[TY\GGG㝘䟸G[aZ]aZY
Control Systems

V External control systems


1. External contact interface module
MIM-B14
1) Features
80 (Unit : mm)

50
Interlock DVM air-conditioner with external controller
t*OEPPSVOJU0O0GGDPOUSPMCZUIFFYUFSOBMDPOUBDU 6TBCMFFRVJQNFOU$BSELFZ 5JNFS 4FOTPS

t0VUQVUUIFJOEPPSVOJUUIFSNP0/0''TUBUFBOEPQFSBUJPOTUBUVT
t0VUQVUUIFJOEPPSVOJUFSSPSTUBUF

2) Description of parts
Contact
No. Input/Output Operation
rating
④ 7"$
① Error state Normal:Close, Error:Open
3A
⑤ Indoor unit Thermo On/Off [Output signal]
or Operation State output
7"$  4&(5IFSNP0O0GG
② (It depends on indoor SEG 15 =1 Operation On/Off
3A
unit's INSTALL option
setting SEG 15.) (On:contact close, Off:contact open)
① ② ③
5V DC,
③ Operation signal input load -
5mA
④ Connector for indoor unit - -
⑤ Connector for indoor unit - -
3) Installation
External contact line wiring
Indoor unit thermo Error signal
ON/OFF signal output
Voltage free contract signal input
Ex) Sensor, Card-key, Timer
7"$ "

*OEPPSVOJU1$#

Connect
wire

; Note
Š External operation input load: 5V DC/5mA.
Š5IFMFOHUIPGXJSJOHCFUXFFO.*.#BOEFYUFSOBMDPOUSPMFRVJQNFOUJTNNBY
Š To use external contact control system, indoor unit's INSTALL option setting is required.
(Refer to indoor unit installation manual)
7 SEG 14 - External control setting (Default : No use)
Š After installed, the first operation will be conducted with Auto mode, Set temp. 24°C, Auto Fan speed.
Š If the indoor unit in OFF status is turned ON through external contact signal; it will operate in the last operation status before
138 it was turned off.

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGXZ_ YWX[TW[TY\GGG㝘䟸G[aZ]aZY
4) Control

Timing diagram for external contact control


Ex1)

; Note
Š IDU stands for Indoor Unit.
No prioritized operation between the R/C and the external contact I/M.

Ex2)

CONTROL SYSTEM
EXTERNAL

; Note
Š IDU stands for Indoor Unit.
After power reset, indoor unit operates as previous state. (IDU has power recovery function)

139

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGXZ` YWX[TW[TY\GGG㝘䟸G[aZ]aZY
Control Systems

V External control systems


1. External contact interface module
MIM-B14
4) Control
Ex3)

; Note
Š IDU stands for Indoor Unit.
After power reset, if IDU is turn ON by external contact, it starts as Auto mode, 24ºC, Auto fan speed.

Ex4)

; Note
Š IDU stands for Indoor Unit.
After power reset, IDU ignores initial external signal state.

140

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX[W YWX[TW[TY\GGG㝘䟸G[aZ]aZY
f Operation input
It is possible to set the method of indoor unit control by external contact signal.
t Method 1. Turn On/Off the indoor units by external contact signal
t Method 2. Set standby/Turn Off the indoor unit by external contact signal
t Method 3. Return to the last status / Turn Off the indoor unit by external contract signal

Method 1 Method 2 Method 3


Indoor unit INSTALL option
setting
SEG 14 = 1 SEG 14 = 2 SEG 14 = 3
(Refer to inidoor unit
installation manual)

Short Š Return to the last


Indoor unit operation by Short Š Indoor unit On Short Š Standby
status of indoor unit
external contact Open Š Indoor unit Off Open Š Indoor unit Off
Open Š Indoor unit Off

Short Š Available Short Š Available Short Š Available


Remote controller use
Open Š Available Open Š Unavailable Open Š Unavailable

f Operation output

DVM S series indoor unit

Output signal 4&( Thermo On/Off


SEG 15 = 1 Operation On/Off
Output signal delay time None

Error signal

t Thermo off : Status where refrigerant is not flowing in either cooling/heating operation because desired temperature has been reached.

CONTROL SYSTEM
EXTERNAL

141

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX[X YWX[TW[TY\GGG㝘䟸G[aZ]aZZ
Control Systems

V External control systems


2. Multi tenant function controller (MTFC)
MCM-C210N
1) Features

110 (Unit: mm)

75
t Multi tenant function controller is an auxiliary power supply device which allows indoor unit to turn off (close EEV) normally and
maintain communication when main power supply is cut.
t It is used in site such as hotel where individual power is supplied to the indoor unit
>5PJOUBMMUIF.5'$ DPOOFDUJPODBCMFGPSUIFQPXFS USBOTGPSNFSBOEUIF*1 *OHSFTT1SPUFDUJPO
CPYNVTU
be purchased separately at the installation site.
>4QFDJGJDBUJPOPGUIFUSBOTGPSNFS6-4UBOEBSE $MBTT 7BDœ)[

2) Product specification
AC 24V
Power supply
)[
Power consumption 8
Operating temperature range ¡$_¡$
Operating humidity range 3)_3)
Maximum length of connection 3m
Number of control devices 1 indoor unit

3) Description of parts




No. Name Description


① Terminal for auxiliary power Connect AC 24 V power
To check for AC single phase power cut-off of the indoor unit, connect the
② Terminal for indoor unit power connection
power cable to the multi tenant function controller.
③ DC 12 V output terminal Terminal which supplies DC 12 V to indoor unit
④ DC 5V output terminal Terminal which supplies DC 5V to indoor unit
t-&%0/When AC single phase power for indoor unit is cut-off and DC 12 V, DC 5 V
⑤ Operation status indicator LED is output normally from the multi tenant function controller
t-&%0''When AC single phase is supplied normally to the indoor unit

142

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX[Y YWX[TW[TY\GGG㝘䟸G[aZ]aZZ
4) Connection diagram

ELCB ELCB ELCB ELCB ELCB


AC single phase AC single phase AC single phase AC single phase AC single phase
power power power power power
ELCB
"$7
AC 24 V
transformer

MTFC MTFC MTFC MTFC


DC 5V DC 5V DC 5V DC 5V
DC 12V DC 12V DC 12V DC 12V

Outdoor unit

Indoor unit Indoor unit Indoor unit Indoor unit


DC 5V DC 5V DC 5V DC 5V
F1/F2 DC 12V DC 12V DC 12V DC 12V

5) Connecting

UL Standard, Class 2, 24 VAC *OEPPSVOJU1$#

24 Vac mX mY }X }Y mZ m[

24 Vac ±15 %G
50/60 Hz
CONTROL SYSTEM
%$1PXFSDBCMF 7


EXTERNAL
%$1PXFSDBCMF 7

s
u

*OEPPSVOJU1$#
download

*OEPPSVOJU"$1PXFS

143

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX[Z YWX[TW[TY\GGG㝘䟸G[aZ]aZ[
Control Systems

V External control system


2. Multi tenant function controller
MCM-C210N

6) Main fucntion

f Multi tenant function controller operation


t When AC power (that is supplied to indoor unit) is cut-off, it supplies auxiliary power (DC 12 V, DC 5 V) to the indoor unit.
t When AC power (that is supplied to indoor unit) is supplied normally, it cuts-off the auxiliary power (DC 12 V, DC 5 V) to the indoor unit.

f Detail information of the indoor unit when the power is supplied by MTFC
Item Operation Detail information
Indoor unti operation OFF Remain indoor unit in off status, turning on is not possible

EEV control Close Operation off, follows indoor unit's EEV control

Self error diagnosis Operating Detects error such as EEV close/open by executing self-diagnosis

Displaying error on panel Case 1) The errors of itself : it displays.


Display partially
display Case 2) The errors of the other units : it doesn’t display.

Oepration of the connected


OFF 1PXFSDVU OPUXPSLJOH

wired remote controller

1BOFMEJTQMBZ All off All LEDs is off

Input outdoor unit key mode


Not operating The others are operated except the indoor unit in MTFC mode
(Test run)
Controlliing
Not operating Remain off status, turning on is not possible
from the control device

Option setting from wireles remote controller, wired remote controller


Setting option code Not operating
BOE4/&51SPFUDJTOPUQPTTJCMF

1PTTJCMFPOMZUISPVHI
Recognition of MTFC status 6TJOH4/&51SP VTFSDBODIFDL.5'$XPSLJOHTUBUVT
4/&51SP

Beep Not operating -

f When AC single phase power is normally supplied to indoor unit


t Indoor unit operates normally.

f Caution
t Wired remote controller for group control cannot be installed to an indoor unit which Multi Tenant Function controller was installed.
t EEV operation of the stopped Heat mode will be controlled in same condition as noise reduction control option when
Multi Tenant Function Controller operates.
t If the Multi Tenant Function Controller operates while multiple indoor units are working in mixed operation mode
(cooling and heating at the same time), dew may form on the indoor unit fan.

144

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX[[ YWX[TW[TY\GGG㝘䟸G[aZ]aZ[
VI. Building management systems
1 DMS L-net (Lonworks GW) . . . . . . . . . . . 146
2 DMS B-net (BACnet GW). . . . . . . . . . . . . 160

MANAGEMENT SYSTEM
BUILDING

145

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX[\ YWX[TW[TY\GGG㝘䟸G[aZ]aZ[
Control Systems

VI Building management system


1. DMS L-net (Lonworks GW)
MIM-B18N

1) Features

DMS-Lnet (Unit : mm)

Lon
ACK SVC

t For LonWork protocol system.


t Support DMS2 control function at the same time.

2) Product specification
Source DC Adaptor
Power
Input 100~240VAC (±10%), 50/60Hz
supply
Output 12V 3A

Operating temperature
-10ºC ~ 50º C
range
Operating humidity range 10%RH ~ 90%RH

Lower layer : RS485 x 5


Communication
Upper layer : Ethernet 100Base-T x 1
connection LonWorks layer : TP/FT-10A(Free topology 78kbps)
External Digital Output 8
connection
port Digital Input 

RS485 N

Digital Output N


Maximum
length of Digital Input N
connection
Ethernet N 8IFOUIFSFJTOPSFQFBUFS

LonWorks N 8IFODPOOFDUJOHXJUI#VTUZQFN




Device Numbers per each channel Total number for 5 channels


Indoor units (including ERV, MCU) 128 128
Max. Outdoor unit (including compatible interface
connectable Control 16 
NPEVMF.*./

number of layer
device OnOff controller
Total 15 Total 75
Touch centralized controller
1*.JOUFSGBDFNPEVMF .*.# .*.#/
 8 8

146

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX[] YWX[TW[TY\GGG㝘䟸G[aZ]aZ\
Compatible product
Outdoor unit AM7777X777777
0O0GGDPOUSPMMFS .$."%/

Controller 5PVDIDFOUSBMJ[FEDPOUSPMMFS .$."/

1*.JOUFSGBDFNPEVMF .*.# .*.#/

7 Conventional communication outdoor unit requires compatible interface module (MIM-N01) to establish connection
7 MIM-B13D, MIM-B13E, MIM-B04A Interface modules cannot be connected.
7 To connect ERV, MIM-N10 interface module is required.
7 PIM connection is different depending on software version.
- Before 2.6.0.3 : MIM-B16 only
- 2.6.0.3 : MIM-B16N only
- After 2.6.1.7 : MIM-B16, MIM-B16N

3) Description of parts

Front
DMS-Lnet
No Name Function
① LCD display Displays current time or menu.

② Menu button Access the setting menu.

② S/T button Select function or setting item in the setting menu.


Lon
ACK SVC

Set button Enter or check setting item in the setting menu.

③ ③ Bottom cover
Unscrew 2 screws on the bottom to remove the
cover and check the cable connections.

LED indicator

① ② ③ ④ ⑤⑥ ⑦ ⑧ ⑨
No. Item Name Status
① Power 1PXFSJOEJDBUPS Turns blue when the power is supplied.
Blinks in orange with 1 second intervals during
② CPU Alive $16PQFSBUJPOJOEJDBUPS
normal operation.
③ Ethernet-Linked Internet connection indicator Turns green during normal connection.
④ Ethernet-Active Internet data transmission/reception indicator Blinks in orange during normal transmission/reception.
MANAGEMENT SYSTEM

Channel 1~4 OnOff controller/Interface


⑤ COM1~4-TX Blinks in green during normal transmission.
BUILDING

module Data transmission indicator


Channel 1~4 OnOff controller/interface
⑥ COM1~4-RX Blinks in green during normal reception.
module Data reception indicator
⑦ Lon ACK LonWorks data reception indicator Blinks in green during normal reception.
⑧ Lon SVC LonWorks device status indicator Blinks in green during un-configured.
Indoor/Outdoor unit communication status Turns green when there is an error on more than
⑨ Check
indicator one indoor/outdoor unit or in communication.

147

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX[^ YWX[TW[TY\GGG㝘䟸G[aZ]aZ\
Control Systems

VI Building management system


1. DMS L-net (Lonworks GW)
MIM-B18N

3) Description of parts

Bottom
DI terminal 1 DI terminal 2 DO terminal 3 DO terminal 4 Lon terminal RS485 Communication terminal

1PXFSUFSNJOBM Serial terminal Ethernet terminal


Reset button SD card socket Cable tie groove

Name Description
DI terminal 1 Digital Input connection terminal, Channel1~Channel5

DI terminal 2 %JHJUBM*OQVUDPOOFDUJPOUFSNJOBM $IBOOFM_$IBOOFM

DO terminal 3 Digital Output connection terminal, Channel1~Channel5

DO terminal 4 Digital Output connection terminal, Channel6~Channel8

Lon terminal 5FSNJOBM#MPDLGPS-PO8PSLTDPNNVOJDBUJPO 51'5

Reset button Reset LonWorks Gateway

Serial terminal Service check port

SD card socket Sub memory (for program update and set information saving) socket

RS485 communication terminal RS485 port for communication with OnOff controller / interface module

Ethernet Terminal Connect LAN cable

Cable tie groove Groove for arranging cables

148

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX[_ YWX[TW[TY\GGG㝘䟸G[aZ]aZ]
4) Connection diagram
f MIM-B16(PIM) should be connected separately with outdoor units or controllers.
f MIM-B16N(PIM) can be connected with outdoor units or controllers to same channel of DMS2. LonWorks
communication BMS
DMS-Lnet

Samsung RS485
communication
For power distribution

1*. OnOff LonWorks GW


controller

1PXFSMJOF
R1-R2

F1-F2

R1-R2

F1-F2

Watt-hour meter
Electrical
substation

R1-R2 F1-F2

5) Wiring

(CH = Channel)

F1 F2 R1 R2 MANAGEMENT SYSTEM

F1 F2 R1 R2
BUILDING

(1) Connecting outdoor unit directly


t.BYJNVNPVUEPPSVOJUTDBOCFDPOOFDUFEUPFBDIDIBOOFM
t5PUBMPVUEPPSVOJUTDBOCFDPOOFDUFE

(2) Connecting OnOff controller/Touch centralized controller


t.BYJNVN0O0GGDPOUSPMMFS5PVDIDFOUSBMJ[FEDPOUSPMMFSDBOCFDPOOFDUFEUPFBDIDIBOOFM

; Note
Š LonWorks GW can connect outdoor unit and OnOff controller/Touch centralized controller at the same time.
Š Outdoor unit and OnOff controller/Touch centralized controller can be connected to 1 communication channel at the same time.

149

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX[` YWX[TW[TY\GGG㝘䟸G[aZ]aZ^
Control Systems

VI Building management system


1. DMS L-net (Lonworks GW)
MIM-B18N

5) Wiring

Connecting with outdoor unit

LonWorks GW

F1 F2
R1 R2
Outdoor unit

R1R2
R1R2

0 0 Outdoor unit
Outdoor unit
R1R2

R1R2

1 1 Outdoor unit
Maximum 16 Outdoor unit
connections

' '
Outdoor unit
Outdoor unit Ú Outdoor unit's address is defined automatically.
The address can be changed manually also.

Connecting with OnOff controller

LonWorks GW

Maximum 15
OnOff controllers

Outdoor unit
R1R2

Outdoor unit

R1R2

Outdoor unit
150

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX\W YWX[TW[TY\GGG㝘䟸G[aZ]aZ^
Connecting with outdoor unit and OnOff controller

LonWorks GW
R1R2

Maximum 16
outdoor units
1
Outdoor unit
R1R2

2
Outdoor unit
R1R2

3
Outdoor unit

Wiring distance
DMS-Lnet

ⓐ ⓑ ⓒ

Network radius

f Distance between LonWorks GW and OnOff controller/outdoor unit


MANAGEMENT SYSTEM

t%JTUBODFGSPNUIF-PO8PSLT(8UPUIFGVSUIFTUEFWJDFDBOOPUFYDFFEN
BUILDING

tⓒ + ⓓ + ⓔ d 1000m

f Distance between LonWorks GW and upper level controller


t4JODF-PO8PSLT(8TVQQPSUT#BTF5&UIFSOFU GJSTUSFQFBUFSPSVQQFSMFWFMDPOUSPMMFSGSPNUIF-PO8PSLT(8DBOOPUCF
GVSUIFSUIBON *&&&
5IFSFGPSF NBYJNVNOFUXPSLSBEJVTJTSFTUSJDUFEUPN

ⓐ, ⓑ, ⓒ, ⓓ, ⓔ = 100m DMS-Lnet

ⓐ ⓑ ⓒ ⓓ ⓔ

HUB
Repeater

Maximum number of repeaters = 4


ⓐN 151

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX\X YWX[TW[TY\GGG㝘䟸G[aZ]aZ_
Control Systems

VI Building management system


1. DMS L-net (Lonworks GW)
MIM-B18N

6) Commission
t'PS$PNNJTTJPOPQFSBUJPOXJUI#.4 QSFTTUIF<4FU>CVUUPO
for more than 3 seconds.

t8IFOZPVQSFTT4FSWJDF1JO /FVSPO*%XJMMCFTFOUBOE<47$>-&%PG
the front panel will be lit up for a second.

7) Standard program identifier (SPID)


t Manufacturers : Samsung Electronics Co., Ltd. MID: 191
t %FWJDF$MBTTFT(BUFXBZT)7"$(BUFXBZT
t Usage (Device Subclass) : Utility {11}
t $IBOOFM5ZQFT51'5\*%^

Object Types Description SFPT Name


 SCC – Generic 4'15TQBDF$PNGPSU$POUSPMMFS

Ú1SPHSBN*%#'#

8) Item summary
Item Function
Operation On/Off
Operation mode
Air flow direction
Common
Fan speed
Device error information
Model, address, type information
Set temperature
Indoor temperature
Filter replacement alert/ reset
Remote controller level
Indoor unit AHU
Control & Monitoring Thermostat information
Operation restriction setting (Cooling/Heating)
Setting lowest temperature/ restriction
Setting highest temperature/ restriction
1PXFSDPOTVNQUJPO
Operation time
Emergency stop
DMS2 DI/DO
Additional functions
DMS2 lock
DMS2 error information
System error information

152

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX\Y YWX[TW[TY\GGG㝘䟸G[aZ]aZ_
9) Network variable
(1) Indoor unit/ ERV/ AHU kit object
No. Name Type M/O Description
1 nviONOff SNVT_switch O ON/OFF command
2 NviApplicMode SNVT_hvac_mode O Setting operating mode
3 nviSetpoint SNVT_temp_p O Setting desire temperature
4 nviFanStatus SNVT_switch O Setting fan speed
5 nviERVMode SNVT_count O Setting ERV operation mode
6 nviFilterReset SNVT_switch O Filter reset command
7 nviUserLockout SNVT_switch O Setting the restriction of remote control use
8 nviOccOpMode SNVT_switch O Setting cooling only mode / heating only mode
9 nviCoolTempLock SNVT_switch O Setting the low temperature limit
10 nviHeatTempLock SNVT_switch O Setting the high temperature limit
11 nvoSpaceTemp SNVT_temp_p M Display indoor temperature
12 nvoApplicMode SNVT_hvac_mode O Display operating mode
13 nvoSetpoint SNVT_temp_p O Display desire temperature
14 nvoOnOff SNVT_switch O Display ON/OFF status
15 nvoFanStatus SNVT_switch O Display fan speed
16 nvoERVMode SNVT_count O Display ERV operating mode
17 nvoErrorCode SNVT_count O Display Error code
Remote control lock, Filter sign, Thermo ON/OFF,
18 nvoDeviceAlarm SNVT_state O
Error occurrence status display
19 nvoOccOpMode SNVT_switch O Cooling only/Heating only setup status display
20 nvoCoolTempLock SNVT_switch O Display low temperature limit setting status
21 nvoHeatTempLock SNVT_switch O Display high temperature limit setting status
22 nvoUserLockout SNVT_switch O Display the restriction of remote control use
23 nvoEnergyConp SNVT_elec_kwh_l O %JTQMBZFMFDUSJDJUZVTBHF 5JNF1FSJPE

24 nvoEnergyCon SNVT_elec_kwh_l O Display electricity usage (Basic date)


25 nvoRuntimep SNVT_time_hour O %JTQMBZVTFEIPVST 1FSJPE

26 nvoRuntime SNVT_time_hour O Display used hours (Basic date)


27 nvoDevListDesc SNVT_str_asc O Indoor unit HW information

(2) DVM system object


No. Name Type M/O Description
1 nviDigitalOut[6] SNVT_ switch O Control Digital output of DMS
2 nviAllOff SNVT_hvac_emerg O Control all indoor unit / ERV OFF
3 nvoDigitalOut[6] SNVT_ switch O Display Digital output status of DMS
4 nvoDigitalIn[8] SNVT_ switch O Display Digital input status of DMS
5 nvoSystemLock SNVT_ switch O Display System Lock status of DMS
MANAGEMENT SYSTEM

Display communication error of the sub device


6 nvoDMS2Alarm SNVT_ count O connected to DMS
BUILDING

7 nvoSystemAlarm SNVT_ count O Display error satus

(3) Configuration properties


No. Name Type M/O Description
SNVT_time_sec
1 nciSndHrtBt O Send Heartbeat
4$15NBY4FOE5JNF
SNVT_time_sec
2 nciMinOutTm O Minimum Send Time
4$15NJO4FOE5JNF
SNVT_temp_p
3 nciMinDeltaTemp O Min. difference before update
4$15NJO%FMUB5FNQ
SNVT_time_sec
4 nciDelayStatrup O Delay time after a power-up
4$15QXSVQ%FMBZ
153

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX\Z YWX[TW[TY\GGG㝘䟸G[aZ]aZ`
Control Systems

VI Building management system


1. DMS L-net (Lonworks GW)
MIM-B18N

10) Network parameter chart


(1) Indoor unit/ ERV/ AHU kit object

SSACIndoor[nn](objectid=1-128)

nvoSpaceTemp SNVT_temp_p
nviOnOff SNVT_switch nvoApplicMode SNVT_hvac_mode
nviApplicMode SNVT_hvac_mode nvoSetPoint SNVT_temp_p
nviSetPoint SNVT_temp_p nvoOnOff SNVT_switch
nviFanStatus SNVT_switch nvoFanStatus SNVT_switch
nviERVMode SNVT_count nvoERVMode SNVT_count
nviFilterReset SNVT_switch nvoErrorCode SNVT_count
nviUserLockout SNVT_switch nvoDeviceAlarm SNVT_state
nviOccOpMode SNVT_switch nvoOccOpMode SNVT_switch
nviCoolTempLock SNVT_switch nvoCoolTempLock SNVT_switch
nviHeatTempLock SNVT_switch nvoHeatTempLock SNVT_switch
nvoUserLockout SNVT_switch
nvoEnergyConp SNVT_elec_kwh_I
nvoEnergyCon SNVT_elec_kwh_I
nvoRuntimep SNVT_time_hour
nvoRuntime SNVT_time_hour
nvoDevListDesc SNVT_str_asc

(2) DMS system object

SSACSystem(objectid=129)

nvoDigitalOut[6] SNVT_switch

nviDigitalOut[6]_switch nvoDigitalIn[8] SNVT_switch

nviAllOff SNVT_hvac_emerg nvoSystemLock SNVT_switch

nvoDMS2Alarm SNVT_count

nvoSystemAlarm SNVT_count

Configuration Properties
nciSndHrtBt
nciMinOutTm
nciMinDelta Temp
nciDelayStartup

154

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX\[ YWX[TW[TY\GGG㝘䟸G[aZ]aZ`
11) Network variable list
t Supported NV (Network Variable) is different depending on the connected devices.

No. NV Name Description Indoor ERV AHU Kit

1 nviOnOff ON/OFF command O O O

2 nviApplicMode Setting operating mode O X O

3 nviSetpoint Setting desirable temperature O X O

4 nviFanStatus Setting fan swing and speed O O X

5 nviERVMode Setting ERV operation mode X O X

6 nviFilterReset Filter reset command O O O

7 nviUserLockout Setting the restriction of remote control use O O O

8 nviOccOpMode Setting cooling only mode / Setting heating only mode O X O

9 nviCoolTempLock Setting the low temperature limit O X O

10 nviHeatTempLock Setting the high temperature limit O X O

11 nvoSpaceTemp Display indoor temperature O X O

12 nvoApplicMode Display operating mode O X O

13 nvoSetpoint Display desire temperature O X O

14 nvoOnOff Display ON/OFF status O O O

15 nvoFanStatus Display wind speed and direction O O X

16 nvoERVMode Display ERV operating mode X O X

17 nvoErrorCode Display Error code O O O


Remote control Lock, Filter Sign, Thermo ON/OFF,
18 nvoDeviceAlarm O O O
Error occurrence status display
19 nvoOccOpMode Cooling only/Heating only setup status display O X O

20 nvoCoolTempLock Low temperature limit setting status display O X O

21 nvoHeatTempLock High temperature limit setting status display O X O

22 nvoUserLockout Display the restriction of remote control use O O O

23 nvoEnergyConp Display electricity usage O X X

24 nvoEnergyCon Monitor total electricity usage O X X

25 nvoRuntimep %JTQMBZVTFEIPVST 1FSJPE


O X O
MANAGEMENT SYSTEM

26 nvoRuntime Monitor total operation hours O X O


BUILDING

The summary of device information (Model, Address,


27 nvoDevListDesc O O O
Operation Status)

155

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX\\ YWX[TW[TY\GGG㝘䟸G[aZ]aZ`
Control Systems

VI Building management system


1. DMS L-net (Lonworks GW)
MIM-B18N

12) Detail description of network variable


(1) Indoor unit/ ERV/ AHU kit object

1-1. nvoSpaceTemp(11) 1-5. nvoFanStatus(15), nviFanStatus(4)


Description Indoor temperature Description Fan Speed and direction
SNVT Type SNVT_temp_p: Signed Long, 2 bytes SNVT Type SNVT_switch: Unsigned/signed Short
Value and operation 3BOHF¡$_¡$ Value State
Auto  -
Low  -
Mid  -
1-2. nvoApplicMode(12), nviApplicMode(2) High  -
Value and operation Eco  -
Description Operation Mode status Turbo  -
SNVT_hvac_mode: Auto "OZ
SNVT Type Enumeration(hvac_t)
)7"$@"650 Stop - 
1: HVAC_HEAT Up-Down - 1
3: HVAC_COOL
Value and operation 7Supporting modes are different according to indoor units.
6: HVAC_OFF
- Indoor unit: Auto, Low, Mid, High
9: HVAC_FAN_ONLY
14: HVAC_DEHUMID - ERV : Mid, High, Turbo
- AHU Kit: High
7Invalid Value: Automatically set as HVAC_AUTO
7When an indoor unit operation mode is Auto or Dehumid,
Fan speed is controlled as ‘Auto’.

1-3. nvoSetpoint(13), nviSetpoint(3) 7When an indoor unit operation mode is FAN ONLY,
‘Auto’cannot be controlled by Fan speed.
Description Set Temperature
SNVT Type SNVT_temp_p: Signed Long, 2 bytes
$PPM¡$_¡$  1-6. nvoERVMode(16), nviERVMode(5)
Value and operation
)FBU¡$~¡$
Description ERV Operation Mode
7Invalid Value: Automatically set up as minimum or
maximum value. SNVT_count: Unsigned Long, 2
SNVT Type bytes
7When setting temperature, only an integer value is applied.
"VUP

A decimal point is ignored.


1: H/R
Value and operation ( 2: Air purification )
3: Sleep
1-4. nvoOnOff(14), nviOnOff(1) 4: Normal
Description Power ON/OFF status 7( ) : Function that is not supported now.
SNVT Type SNVT_switch: Unsigned/signed Short
Value State
Value and operation OFF   1-7. nvoErrorCode(17)
ON  1
Description Error Code
SNVT_count: Unsigned Long, 2
SNVT Type bytes
7BMJE3BOHF_
Value and operation ¤ No Error
Refer to list of Error code

156

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX\] YWX[TW[TY\GGG㝘䟸G[aZ]aZ`
1-8. nvoDeviceAlarm(18) 1-13. nvoEnergyCon(24)
1. Remote control restriction status Electric consumption value after
2. Filter alert status Description
Description baselin
3. Thermo On/Off status SNVT_elec_kwh_I: Signed Quad,
4. Error alert Status SNVT Type 4bytes
SNVT Type SNVT_state: 16 Unsigned Bitfields 3BXSBOHF_
Value and operation
Byte Bit9 Bit8 Operation Remark 3FTPMVUJPO
  Unlock nvo
Flags
 1 Level1 User
_1
1  Lock Lockout
1-14. nvoRunTimep(25)
Byte Bit value Operation Remark
Indoor unit usage within the
 No alarm nvo Description
Value and operation period
2 Filter
1 Alarm SNVT_time_hour: Signed Long,
Alarm SNVT Type
 Thermo Off Thermo 2bytes
Flags
1
_2 1 Thermo On On/Off Value and operation 3BXSBOHF_
 No Error nvo
 Error
1 Error
Code
1-15. nvoRunTime(26)
Description Indoor unit usage after baseline
1-9. nvoOccOpMode(19), nviOccOpModeCmd(8) SNVT_time_hour: Signed Long,
SNVT Type 2bytes
Description Operation Mode restriction
Value and operation 3BXSBOHF_
SNVT Type SNVT_switch: Unsigned/singed Short
Value State 7Energy consumption and Runtime are the accumulated value
Unlock   during the user setting period.
Value and operation
Cool only  1 7The data above is for reference so you can not use them for
Heat only  1
official billing.

1-10. nvoCoolTempLock(20), nviCoolTempLock(9)


1-15. nviFilterReset(6)
Setting/monitoring Lower limit
Description temperature Description Filter alert reset
and function toggle SNVT Type SNVT_switch: Unsigned/singed Short
SNVT Type SNVT_switch: Unsigned/singed Short
Value State Operation remark
Operation Value State Value and operation 0.0 0 No Action
Unlock 18.0 ~ 30.0 0 100.0 1 Filter Reset
Value and operation Lock 18.0 ~ 30.0 1
$PPM°C ~ °C

1-15. nviUserLockout(7), nvoUserLockout(22)


1-11. nvoHeatTempLock(21), nviHeatTempLock(10)
Description Remote control restriction
Setting/monitoring upper limit
Description temperature SNVT Type SNVT_switch: Unsigned/singed Short
and function toggle Value State Operation remark
SNVT Type SNVT_switch: Unsigned/signed Short 0.0 0 Unlock
Value and operation
Operation Value State 100.0 1 Level 1
100.0 2 Lock
MANAGEMENT SYSTEM

Unlock 16.0 ~ 30.0 0


Value and operation Lock 16.0 ~ 30.0 1
BUILDING

)FBU°C ~°C
1-15. nvoDevListDesc(27)

Description Device Information


1-12. nvoEnergyConp(23)
SNVT_str_asc: Unsigned Character
SNVT Type Array, 31bytes
Electric consumption value within
Description
the period Refer to Expansion of
SNVT_elec_kwh_I: Signed Quad, Value and operation nvoDevListDesc
SNVT Type 4bytes
3BXSBOHF_
Value and operation
3FTPMVUJPO

157

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX\^ YWX[TW[TY\GGG㝘䟸G[aZ]aZ`
Control Systems

VI Building management system


1. DMS L-net (Lonworks GW)
MIM-B18N

12) Detail description of network variable


(1) Indoor unit/ ERV/ AHU kit object

2-17. Expansion of nvoDevListDesc

desription character value


<> Alphabet or digit
[1] Alphabet or digit
[2] Alphabet or digit
Model information
[3] Alphabet or digit
[4] Alphabet or digit
[5] Alphabet or digit

[6] Separator Underbar(_) 


[7] Centralized controller Alphabet or digit
[8] address Alphabet or digit
[9] Separator 1FSJPE 

<> Alphabet or digit
Interface Module address
[11] Alphabet or digit
[12] Separator 1FSJPE 

[13] Alphabet or digit
Indoor Unit Address
[14] Alphabet or digit
[15] Separator Underbar(_) 
ascii.
[16] Unit type JOEPPSVOJU ")6 &37
[17] Separator Underbar(_) 
DMS Format
[18] Operation mode "VUP $PPM %FIVNJE
3: Fan, 4: Heat
[19] ON/OFF  
<> Fan speed      
[21] Fan Swing  
[22] Error  
[23] Separator Underbar(_) 
[24] Second significant digit
[25] TFU1PJOUUFNQFSBUF First significant digit
[26] First decimal place
[27] Second significant digit
[28] Space temperate(*) First significant digit
[29] First decimal place
<> Null padding  

(7
*GUIFWBMVFJTBOFHBUJWFOVNCFS JUJTEJTQMBZFEBTTJHO EJHJU TJOHMFEJHJU

158

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX\_ YWX[TW[TY\GGG㝘䟸G[aZ]aZ`
(2) DMS System object
2-1. nvoDigitalOut(3), nviDigitalOut(1)

Description Digital output status on DMS


SNVT Type SNVT_switch: Unsigned/singed Short
Value State
Value and operation OFF  
ON  1

2-2. nvoDigitalIn(4)

Description Digital Input status on DMS


SNVT Type SNVT_switch: Unsigned/singed Short
Value State
Value and operation OFF  
ON  1

2-3. nvoSystemLock(5)

Description System lock status of DMS(only monitoring available)


SNVT Type SNVT_switch: Unsigned/singed Short
Value State
Value and operation Unlock  
Lock  1

2-4. nvoDMSAlarm(6)
Description DMS Alarm
SNVT Type SNVT_count : Unsigned Long, 2 bytes
/PSNBM
8 : Emergency stop
5SBDJOHJOQSPHSFTT
Value and operation
5SBDLJOHGBJMFE
-PO.PEVMF¥ DMS2 communication Error
0CKFDU*%6QEBUF

2-5. nvoSystemAlarm(7)
MANAGEMENT SYSTEM

Description SIM/PIM Communication Error Code


SNVT Type SNVT_count: Unsigned Long, 2 bytes
BUILDING

Value and operation 4*.1*.$PNNVOJDBUJPO&SSPS3FGFSUPMJTUPG&SSPSDPEF

2-6. nviAllOff(2)
Description All indoor units turn off
SNVT Type Enumeration, emerg_t
&.&3(@/03."-
Value and operation
4 : EMERG_SHUTDOWN

159

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX\` YWX[TW[TY\GGG㝘䟸G[aZ]aZ`
Control Systems

VI Building management system


2. DMS B-net (BACnet GW)
MIM-B17N

1) Features

DMS-Bnet (Unit : mm)

t'PS#"$OFUQSPUPDPMTZTUFN4VQQPSU%.4DPOUSPMGVODUJPOBUUIFTBNFUJNF

2) Product specification
Source DC Adaptor
Power
Input 100~240VAC (±10%), 50/60Hz
supply
Output 12V 3A

Operating temperature
-10ºC ~ 50º C
range
Operating humidity range 10%RH ~ 90%RH

Communication Lower layer : RS485 x 5


connection Upper layer : Ethernet 100Base-T x 1(BACnet IP)

External Digital Output 


connection
port Digital Input 

RS485 N
Maximum Digital Output N
length of
connection Digital Input N

Ethernet N 8IFOUIFSFJTOPSFQFBUFS




Device Numbers per each channel Total number for 5 channels


Indoor units (including ERV, MCU) 128 256
Max. Outdoor unit (including compatible interface
connectable Control 16 
number of layer NPEVMF.*./

device OnOff controller


Total 15 Total 75
Touch centralized controller
1*.JOUFSGBDFNPEVMF .*.# .*.#/
 8 8

160

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX]W YWX[TW[TY\GGG㝘䟸G[aZ]a[X
Compatible product
Outdoor unit AM7777X777777
0O0GGDPOUSPMMFS .$."%/

Controller 5PVDIDFOUSBMJ[FEDPOUSPMMFS .$."/

1*.JOUFSGBDFNPEVMF .*.# .*.#/


7 Conventional communication outdoor unit requires compatible interface module (MIM-N01) to establish connection
7 MIM-B13D, MIM-B13E, MIM-B04A Interface modules cannot be connected.
7 To connect ERV, MIM-N10 interface module is required.
7 PIM connection is different depending on software version.
- Before 2.6.0.3 : MIM-B16 only
- 2.6.0.3 : MIM-B16N only
- After 2.6.1.7 : MIM-B16, MIM-B16N

3) Description of parts
(1) Front

DMS-Bnet No Name Function


① LCD display Displays current time or menu

② Menu button Access the setting menu

Select function or setting item in the setting


② S/T button
menu

Set button Enter or check setting item in the setting menu

③ Unscrew 2 screws on the bottom to remove


③ Bottom cover
the cover and check the cable connections

(2) LED indicator

① ② ③ ④ ⑤⑥ ⑦

No. Item Name Status


① Power 1PXFSJOEJDBUPS Turns blue when the power is supplied
Blinks in orange with 1 second intervals during
② CPU Alive $16PQFSBUJPOJOEJDBUPS
normal operation
MANAGEMENT SYSTEM

③ Ethernet–Linked Internet connection indicator Turns green during normal connection


Blinks in orange during normal transmission/
BUILDING

④ Ethernet–Active Internet data transmission/reception indicator


reception
Channel 1~5 OnOff controller/Interface module
⑤ COM1~5 – TX Blinks in green during normal transmission
Data transmission indicator
Channel 1~5 OnOff controller/interface module
⑥ COM1~5 – RX Blinks in green during normal reception
Data reception indicator
⑦ Check Indoor/Outdoor unit Communication status indicator Turns green when communication error occurs

161

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX]X YWX[TW[TY\GGG㝘䟸G[aZ]a[X
Control Systems

VI Building management system


2. DMS B-net (BACnet GW)
MIM-B17N

3) Description of parts
(3) Bottom
DI terminal 1 DI terminal 2 DO terminal 3 DO terminal 4 RS485 Communication terminal

1PXFSUFSNJOBM Serial terminal Ethernet terminal


Reset button SD card socket Cable tie groove

Name Description
DI terminal 1 Digital Input connection terminal, Channel 1~Channel 5

DI terminal 2 %JHJUBM*OQVUDPOOFDUJPOUFSNJOBM $IBOOFM_$IBOOFM

DO terminal 3 Digital Output connection terminal, Channel 1~Channel 5

DO terminal 4 Digital Output connection terminal, Channel 6~Channel 8

Reset button Reset BACnet Gateway

Serial terminal Sevice check port

SD card socket Sub memory (for program update and set information saving) socket

RS485 communication terminal RS485 port for communication with OnOff controller / interface module

Ethernet Terminal Connect LAN cable

Cable tie groove Groove for arranging cables

162

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX]Y YWX[TW[TY\GGG㝘䟸G[aZ]a[X
4) Connection diagram
f MIM-B16(PIM) should be connected separately with outdoor units or controllers.
f MIM-B16N(PIM) can be connected with outdoor units or controllers to same channel of DMS2. BACnet
communication BMS
Samsung RS485
communication
For power distribution

1*. OnOff
BACnet GW
controller

1PXFSMJOF
R1-R2

F1-F2

R1-R2

F1-F2

Watt-hour meter
Electrical
substation

R1-R2 F1-F2

5) Wiring

(CH = Channel)

F1 F2 R1 R2 MANAGEMENT SYSTEM

F1 F2 R1 R2
BUILDING

(1) Connecting outdoor unit directly


t.BYJNVNPVUEPPSVOJUTDBOCFDPOOFDUFEUPFBDIDIBOOFM
t5PUBMPVUEPPSVOJUTDBOCFDPOOFDUFE

(2) Connecting OnOff controller/Touch centralized controller


t.BYJNVN0O0GGDPOUSPMMFS5PVDIDFOUSBMJ[FEDPOUSPMMFSDBOCFDPOOFDUFEUPFBDIDIBOOFM

; Note
Š BACnet GW can connect outdoor unit and OnOff controller/Touch centralized controller at the same time.
Š Outdoor unit and OnOff controller/Touch centralized controller can be connected to 1 communication channel at the same time.

163

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX]Z YWX[TW[TY\GGG㝘䟸G[aZ]a[Y
Control Systems

VI Building management system


2. DMS B-net (BACnet GW)
MIM-B17N

5) Wiring

Connecting with outdoor unit

BACnet GW

F1 F2
R1 R2
Outdoor unit

R1R2
R1R2

0 0 Outdoor unit
Outdoor unit
R1R2

R1R2

1 1 Outdoor unit
Maximum 16 Outdoor unit
connections

' '
Outdoor unit
Outdoor unit Ú Outdoor unit's address is defined automatically.
The address can be changed manually also.

Connecting with OnOff controller

BACnet GW

Maximum 15
OnOff controllers

Outdoor unit
R1R2

Outdoor unit

R1R2

Outdoor unit
164

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX][ YWX[TW[TY\GGG㝘䟸G[aZ]a[Z
Connecting with outdoor unit and OnOff controller

BACnet GW
R1R2

Maximum 16
outdoor units
1
Outdoor unit
R1R2

2
Outdoor unit
R1R2

3
Outdoor unit

Wiring distance
DMS-Bnet

ⓐ ⓑ ⓒ

Network radius

f Distance between BACnet GW and OnOff controller/outdoor unit


MANAGEMENT SYSTEM

t%JTUBODFGSPNUIF#"$OFU(8UPUIFGVSUIFTUEFWJDFDBOOPUFYDFFEN
BUILDING

tⓒ + ⓓ + ⓔ d 1000m

f Distance between BACnet GW and upper level controller


t4JODF#"$OFU(8TVQQPSUT#BTF5&UIFSOFU GJSTUSFQFBUFSPSVQQFSMFWFMDPOUSPMMFSGSPNUIF#"$OFU(8
DBOOPUCFGVSUIFSUIBON *&&&
5IFSFGPSF NBYJNVNOFUXPSLSBEJVTJTSFTUSJDUFEUPN

ⓐ, ⓑ, ⓒ, ⓓ, ⓔ = 100m DMS-Bnet

ⓐ ⓑ ⓒ ⓓ ⓔ

HUB
Repeater

Maximum number of repeaters = 4


ⓐN 165

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX]\ YWX[TW[TY\GGG㝘䟸G[aZ]a[[
Control Systems

VI Building management system


2. DMS B-net (BACnet GW)
MIM-B17N

6) Description of device ID
DNET – Range CPP – Range INDOOR – Range
Item
[Digit 2] [Digit 3] [Digit 2]
OnOff Controller _ _ 64
1*. _ _ 64

DMS DI/DO _ _ 64

_
Interface Module _ 64
(16 x 16)
Indoor Unit, ERV
_ _ _
AHU kit, EHS
Gateway _  64

Ex) Device Instance Number (Gateway ID) Indoor unit main address
ƒ Indoor Unit
ƒ DNET (Gateway number) : 9
ƒ *OEPPS6OJU"EESFTT
9 417 32
ƒ Device ID: 941732
 Y 
OnOff controller address Interface module address

Checking device ID from BACnet Gateway


t$MJDLA0CKFDU*%GSPNUIFA0CKFDU*%DPMVNO
Detail information window will appear and detail information will be displayed.

166

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX]] YWX[TW[TY\GGG㝘䟸G[aZ]a[[
7) Object list
(1) Indoor unit
Single indoor unit has following point list.

Unit Status value


Instance Object
Object Object Name Inactive Active
Number Type
Text-1 Text-2 Text-3 Text-4 Text-5
1 Indoor temperature AI AC_RoomTemp_xx_xxxxxx ℃

2 Set temperature AV AC_Temp_Set_xx_xxxxxx ℃

3 Setting lower temperature limit AV AC_Cool_LimitTemp_xx_xxxxxx ℃

4 Setting upper temperature limit AV AC_Heat_LimitTemp_xx_xxxxxx ℃

The power value of an indoor


5 AI AC_Baseline_kWh_xx_xxxxxx kWh
unit after the basic date

The number of hours usage of an


6 AI AC_Baseline_Minute_xx_xxxxxx Minute
indoor unit after the basic date

7 Power value within period AI "$@1FSJPE@L8I@YY@YYYYYY kWh

The number of hours usage of


8 AI "$@1FSJPE@.JOVUF@YY@YYYYYY Minute
an indoor unit within period

9 Power On/Off BV "$@1PXFS@YY@YYYYYY Off On

Applying lower temperature


 BV AC_Cool_Limit_set_xx_xxxxxx False True
limit setting

Applying upper temperature


11 BV AC_Heat_Limit_set_xx_xxxxxx False True
limit setting

12 Filter sign status BI AC_FilterSign_xx_xxxxxx False True

13 Filter sign reset BO AC_FilterSign_Reset_xx_xxxxxx False True

14 Operation mode status MV AC_Operation_Mode_xx_xxxxxx Auto Cool Heat Fan Dry

15 Fan speed status MV AC_FanSpeed_xx_xxxxxx Auto Low Mid High

16 Air flow direction status MV AC_FanFlow_xx_xxxxxx None Vertical Horizon All

No Cool Heat
17 Operation mode limit status MV AC_Mode_Limit_xx_xxxxxx
Limit Only Only

Enable Disable Conditional


18 Remote controller limit status MV AC_Remocon_Limit_xx_xxxxxx
RC RC RC

Integrated error code of both


MANAGEMENT SYSTEM

19 AI AC_Error_Code_xx_xxxxxx Refer to Samsung integrated error code list


indoor unit and outdoor unit
BUILDING

(7) SPI setting BV "$@41*@YY@YYYYYY False True

21(7) HumanSensor setting BV AC_MDS_xx_xxxxxx False True

When the error occurred, send event to list of


22(7) AC Indoor Notify NC AC_Notify_xx_xxxxxx
destination in the recipient_list. (Max : 8)

Ú Temperature setting range can be different depending on the model and the common range is as follows :
"VUP„$_„$
$PPM„$_„$
)FBU„$_„$
'BO5FNQFSBUVSFDBOOPUCFBEKVTUFE
%SZ„$_„$
(7)
Mark is optionally supported.
167

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX]^ YWX[TW[TY\GGG㝘䟸G[aZ]a[[
Control Systems

VI Building management system


2. DMS B-net (BACnet GW)
MIM-B17N

7) Object list
(2) AHU kit
Single AHU unit has following point list.

Unit Status value


Instance Object
Object Object Name Inactive Active
Number Type
Text-1 Text-2 Text-3 Text-4 Text-5
1 Indoor Temperature AI AHU_RoomTemp_xx_xxxxxx ℃

2 Set temperature AV AHU_Temp_Set_xx_xxxxxx ℃

3 Setting lower temperature limit AV AHU_Cool_LimitTemp_xx_xxxxxx ℃

4 Setting upper temperature limit AV AHU_Heat_LimitTemp_xx_xxxxxx ℃


The power value of an indoor
5 AI AHU_Baseline_kWh_xx_xxxxxx kWh
unit after the basic date
The number of hours usage of an
6 AI AHU_Baseline_Minute_xx_xxxxxx Minute
indoor unit after the basic date
7 Power value within period AI ")6@1FSJPE@L8I@YY@YYYYYY kWh
The number of hours usage of
8 AI ")6@1FSJPE@.JOVUF@YY@YYYYYY Minute
an indoor unit within period
9 Power On/Off BV ")6@1PXFS@YY@YYYYYY Off On
Applying lower temperature
 BV AHU_Cool_Limit_set_xx_xxxxxx False True
limit setting
Applying upper temperature
11 BV AHU_Heat_Limit_set_xx_xxxxxx False True
limit setting
12 Filter sign status BI AHU_FilterSign_xx_xxxxxx False True

13 Filter sign reset BO AHU_FilterSign_Reset_xx_xxxxxx False True

14 Operation mode status MV AHU_Operation_Mode_xx_xxxxxx Auto Cool Heat Fan Dry


No Cool Heat
15 Operation mode limit status MV AHU_Mode_Limit_xx_xxxxxx
Limit Only Only
Enable Disable Conditional
16 Remote controller limit status MV AHU_Remocon_Limit_xx_xxxxxx
RC RC RC
Integrated error code of both
17 AI AHU_Error_Code_xx_xxxxxx Refer to Samsung integrated error code list
indoor unit and outdoor unit
Discharge cooling set
18(7) AV AHU_DisCoolSetTemp_xx_xxxxxx °C
temperature
Discharge heating set
19(7) AV AHU_DisHeatSetTemp_xx_xxxxxx °C
temperature
Discharge current
(7) AI AHU_Dis_CurrentTemp_xx_xxxxxx °C
temperature
21(7) Humidification setting BV AHU_Humidification_xx_xxxxxx Off On
(7)
22 Outdoor air intake setting BV AHU_OAIntake_xx_xxxxxx Off On

23(7) Outdoor cooling setting BV AHU_OutdoorCool_xx_xxxxxx Off On

24(7) Fan speed status MV AHU_FanSpeed_xx_xxxxxx Low Mid High


(7)
25 Set humidity status MV AHU_SetHumidity_xx_xxxxxx Low Mid High
(7)
26 Current humidity status MI AHU_CurrentHumidity_xx_xxxxxx Low Mid High
When the error occurred, send event to list
27 AHU Notify NC AHU_Notify_xx_xxxxxx
of destination in the recipient_list. (Max : 8)
(7)
Mark is optionally supported.
168

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX]_ YWX[TW[TY\GGG㝘䟸G[aZ]a[\
(3) ERV
Single ERV unit has following point list.

Unit Status value


Instance Object
Object Object Name Inactive Active
Number Type
Text-1 Text-2 Text-3 Text-4 Text-5

1 Power On/Off operation BV &37@1PXFS@YY@YYYYYY Off On

2 Filter sign status BI ERV_FilterSign_xx_xxxxxx False True

3 Filter sign reset BO ERV_FilterSign_Reset_xx_xxxxxx False True

4 Operation mode status MV ERV_Operation_Mode_xx_xxxxxx Auto HeatEx Bypass Sleep

5 Fan speed status MV ERV_FanSpeed_xx_xxxxxx Low High Turbo

Enable Disable Conditional


6 Remote controller limit status MV ERV_Remocon_Limit_xx_xxxxxx
RC RC RC
Integrated error code of ERV
7 AI ERV_Error_Code_xx_xxxxxx Refer to list of error code
unit
When the error occurred, send event to list
8 ERV Notify NC ERV_Notify_xx_xxxxxx
of destination in the recipient_list. (Max : 8)

MANAGEMENT SYSTEM
BUILDING

169

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX]` YWX[TW[TY\GGG㝘䟸G[aZ]a[\
Control Systems

VI Building management system


2. DMS B-net (BACnet GW)
MIM-B17N

7) Object list
(4) EHS
Unit Status value
Instance Object Object Object Name Inactive Active
Number Type
Text-1 Text-2 Text-3 Text-4
1 Room temperature AI EHS_RoomTemp_xx_xxxxxx °C

2 Set temperature AV EHS_Temp_Set_xx_xxxxxx °C Use when displayed temperature type is set


to 'Room'.
3 Set temperature of water out AV EHS_WaterOutTemp_Set_xx_xxxxxx °C Use when displayed temperature type is set
to 'WaterOut'.
4 Set temperature of hot water AV EHS_HotWaterTemp_Set_xx_xxxxxx °C

5 Setting lower temperature limit AV EHS_Cool_LimitTemp_xx_xxxxxx °C Use when displayed temperature type is set
to 'Room'.
6 Setting upper temperature limit AV EHS_Heat_LimitTemp_xx_xxxxxx °C Use when displayed temperature type is set
to 'Room'.
7 Lower temperature limit for water out AV EHS_WOCoolLimitTemp_xx_xxxxxx °C

8 Upper temperature limit for water out AV EHS_WOHeatLimitTemp_xx_xxxxxx °C

9 Upper temperature limit for hot water AV EHS_WTHeatlLimitTemp_xx_xxxxxx °C

 The power value after the basic date AI EHS_Baseline_kWh_xx_xxxxxx kWh

11 The number of hours usage of an in- AI EHS_Baseline_Minute_xx_xxxxxx Minute


door unit after the basic date
12 1PXFSWBMVFXJUIJOQFSJPE AI &)4@1FSJPE@L8I@YY@YYYYYY kWh

13 The number of hours usage of an in- AI &)4@1FSJPE@.JOVUF@YY@YYYYYY Minute


door unit within period
14 Current temperature of water out AI EHS_WOCurrentTemp_xx_xxxxxx °C

15 Current temperature of hot water AI EHS_HotWaterTemp_xx_xxxxxx °C

16 Displayed temperature type BI EHS_ControlTempType_xx_xxxxxx Room WaterOut

17 Thermostat usage BI EHS_Thermostat_xx_xxxxxx False True

18 Outing BI EHS_GoOut_xx_xxxxxx Off On

19 1PXFS0O0GG BV &)4@1PXFS@YY@YYYYYY Off On

 Setting lower temperature limit BV EHS_Cool_LimitTemp_Set_xx_xxxxxx False True Use when displayed tempera-
ture type is set to 'Room'.
21 Setting upper temperature limit BV EHS_Heat_LimitTemp_Set_xx_xxxxxx False True Use when displayed tempera-
ture type is set to 'Room'.
22 Apply lower temperature limit for water BV EHS_WOCoolLimitFlag_xx_xxxxxx False True Use when displayed tempera-
out ture type is set to 'WaterOut'.
23 Apply upper temperature limit for water BV EHS_WOHeatLimitFlag_xx_xxxxxx False True Use when displayed tempera-
out ture type is set to 'WaterOut'.
24 Apply upper temperature limit for hot BV EHS_WTHeatLimitFlag_xx_xxxxxx False True
water
25 On/Off status of hot water mode BV &)4@)PU8BUFS@1PXFS@YY@YYYYYY Off On

26 Status of quiet operation BV EHS_Sleep_xx_xxxxxx Off On

27 Operation mode status MV EHS_Operation_Mode_xx_xxxxxx Auto Cool Heat

28 Operation mode limit status MV EHS_Mode_Limit_xx_xxxxxx No Limit Cool Only Heat Only

29 Remote controller limit status MV EHS_Remocon_Limit_xx_xxxxxx Enable RC Disable RC Conditional RC

 Status of hot water operation mode MV EHS_HotWater_Mode_xx_xxxxxx * Force Eco Standard 1PXFS

31 Integrated error code of both indoor unit AI EHS_Error_Code_xx_xxxxxx


and outdoor unit
32 EHS notifiy NC EHS_Notify_xx_xxxxxx When the error occurred, send event to list of destination in
the recipient_list. (Max : 8)
Force hot water mode (7 marked) will be supported later. It is the point list of Hydro Unit and Hydro Unit HT.

170

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX^W YWX[TW[TY\GGG㝘䟸G[aZ]a[\
 
4*. 1*.

4JOHMF4*. 1*.
IBTGPMMPXJOHQPJOUMJTU
Instance Object
Object Object Name Status value
Number Type
1 SIM (PIM) error code AI SIM_Error_Code_xx_xx Refer to list of error code
When the error occurred, send event
2 SIM (PIM) Notify NC SIM_Notify_xx_xx
to list of destination in the recipient_list. (Max : 8)

(6) OnOff Controller


Single OnOff Controller has following point list.
Instance Object
Object Object Name Status value
Number Type
OnOff Controller Refer to the list of the integrated
1 AI Central_Error_Code_xx_xx
error code error code
When the error occurred, send
OnOff Controller
2 NC Central_Notify_xx_xx event to list of destination in the
notify
recipient_list. (Max : 8)

(7) Interface module (Outdoor unit)


Single Interface(Outdoor unit) module has following point list.

Unit Status value


Instance Object
Object Object Name Inactive Active
Number Type
Text-1 Text-2 Text-3 Text-4 Text-5
1 Outside temperature AI ODU_Outside_Temp_xx_xxxx °C
_¡$_¡$_¡$
ODU_Cool_Compensation_xx_
2(7) Cool capacity compensation AV _¡$_¡$_¡$
xxxx
6 : 13~15°C / 14 : Auto control (from ODU)
LHDN¤LHDN¤
LHDN¤LHDN¤
ODU_Heat_Compensation_xx_
3(7) Heat capacity compensation AV LHDN¤LHDN¤
xxxx
LHDN¤LHDN¤
LHDN¤"VUPDPOUSPM GSPN0%6

4 Compressor status BI ODU_Comp_Status_xx_xxxx False True u u


5 Interface module error code AI Repeater_Error_Code_xx_xxxx Refer to the list of the integrated error code
When the error occurred, send event to list
MANAGEMENT SYSTEM

6 Interface module notify NC IM_Notify_xx_xxxx


of destination in the recipient_list. (Max : 8)
BUILDING

(7)
Mark is optionally supported.

171

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX^X YWX[TW[TY\GGG㝘䟸G[aZ]a[\
Control Systems

VI Building management system


2. DMS B-net (BACnet GW)
MIM-B17N

7) Object list
(8) BACnet Gateway
BACnet Gateway has following point list.

Instance Control and Object


Object Name Status value
Number Monitoring Type
1 All device OFF BO ALL_OFF_xx Inactive : All devices Off
/PSNBM &NFSHFODZTUPQ
5SBDLJOHJOQSPHSFTT
1 DMS2 Status AI DMS2_Status_xx 5SBDLJOHGBJMFE
%.4¥ BACnet
Communication failed
BACnetApp_Error_
1 BACnet error code AI BACnet error code
Code_xx
When the error occurred, send event to list
2 Gateway Notify NC GW_Notify_xx
of destination in the recipient_list. (Max : 8)

(9) Digital input / output


Digital input / output Gateway has following point list.

Unit Status value


Instance Object
Object Object Name Inactive Active
Number Type
Text-1 Text-2 Text-3 Text-4 Text-5
1 Digital Input 1 BI %*@@YY@YY #"$OFU(BUFXBZ3FTFSWFE
Off On
2 Digital Input 2 BI %*@@YY@YY #"$OFU(BUFXBZ3FTFSWFE
Off On
3 Digital Input 3 BI %*@@YY@YY Off On
4 Digital Input 4 BI %*@@YY@YY Off On
5 Digital Input 5 BI %*@@YY@YY Off On
6 Digital Input 6 BI %*@@YY@YY Off On
7 Digital Input 7 BI %*@@YY@YY Off On
8 Digital Input 8 BI %*@@YY@YY Off On
9 Digital Input 9 BI %*@@YY@YY Off On
 Digital Input 10 BI %*@@YY@YY Off On
11 Digital Output 1 BO %0@@YY@YY #"$OFU(BUFXBZ3FTFSWFE
Off On
12 Digital Output 2 BO %0@@YY@YY #"$OFU(BUFXBZ3FTFSWFE
Off On
13 Digital Output 3 BO %0@@YY@YY Off On
14 Digital Output 4 BO %0@@YY@YY Off On
15 Digital Output 5 BO %0@@YY@YY Off On
16 Digital Output 6 BO %0@@YY@YY Off On
17 Digital Output 7 BO %0@@YY@YY Off On
18 Digital Output 8 BO %0@@YY@YY Off On

f Caution
t You may use ALL_OFF command to turn on all the indoor units but it is not recommended.
t If communication error occurs on devices such as SIM/OnOff Controller/Interface Module etc, other functions such as
power distribution may also create a problem. You must have BMS system to check the errors and you must take action
immediately.

172

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX^Y YWX[TW[TY\GGG㝘䟸G[aZ]a[\
8) Checking BACnet communication through Wireshark
(1) Who-is (I-Am)
t"GUFSEFWJDFJOTUBODFOVNCFSTIBWFCFFOBVUPNBUJDBMMZBTTJHOFE 8IPJTDPNNBOEXIJDIJTSFRVFTUFEJOUIF8JSFTIBSLXJMMCF
replied by i-am from the devices.

(2) ReadPropertyMultiple
t3FRVFTUBMMTUBUVTEBUBT
t%FWJDFEFTDSJQUJPO #"$OFUOFUXPSLOVNCFSEFWJDFOPEF*% TUBUVT #"$OFU."$BEESFTTWFSTJPO .BY"1%6MFOHUI
BDDFQUFE "1%6SFUSJFT UJNFPVU TVQQPSUFETFSWJDFT TVQQPSUFEPCKFDUUZQFTBOETPPO

ReadPropertyMultiple Request ReadPropertyMultiple Response


MANAGEMENT SYSTEM
BUILDING

Continuum CyberStation

173

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX^Z YWX[TW[TY\GGG㝘䟸G[aZ]a[]
Control Systems

VI Building management system


2. DMS B-net (BACnet GW)
MIM-B17N

8) Checking BACnet communication through Wireshark


(3) ReadPropertyMultiple
t0CKFDU@.VMUJ4UBUF*OQVU

Request

Response

(4) WriteProperty
t$IBOHFUIF'BO4QFFEGSPN"VUPUP-PX

3FRVFTU8SJUF1SPQFSUZ 'BO4QFFEA"VUPŠ ‘Low’)


2. Response - SimpleACK
3FRVFTU3FBE1SPQFSUZ.VMUJQMF 'BO4QFFE

3FTQPOTFo3FBE1SPQFSUZ.VMUJQMF 'BO4QFFEA-PX


WriteProperty ReadPropertyMultiple

174

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX^[ YWX[TW[TY\GGG㝘䟸G[aZ]a[^
(5) Subscribe COV

Request

Response

(6) COV Notification

Notification
MANAGEMENT SYSTEM
BUILDING

Response

175

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX^\ YWX[TW[TY\GGG㝘䟸G[aZ]a[_
Control Systems

VI Building management system


2. DMS B-net (BACnet GW)
MIM-B17N

9) Standard object type


Object Type Support Description
[Indoor temperature], [The power value after the basic date],
[The number of hours usage of an indoor unit after the basic date],
<1PXFSWBMVFXJUIJOQFSJPE> <5IFOVNCFSPGIPVSTVTBHFPGBOJOEPPSVOJUXJUIJO
Analog Input „ period], [Indoor unit error code], [AHU error code], [ERV error code], [AHU error code],
[ERV error code], [Centralized controller error code], [Interface module error code],
[SIM interface module error code], [DMS status], [DMS error],
[Discharge current temperature], [Outside temperature]
Analog Output …
[Set temperature], [Setting lower temperature limit],
[Setting upper temperature limit], [Discharge cooling set temperature],
Analog Value „
[Discharge heating set temperature], [Cool capacity compensation],
[Heat capacity compensation]

Averaging …

Binary Input „ [DI], [Filter sign status], [Compressor status]

Binary Output „ [DO], [Filter sign reset], [All Device off]

<1PXFS0OPGGDPOUSPM> <4FUUJOHUIFGVDOUJPOPGMJNJUJOHMPXFSUFNQFSBUVSF>
<4FUUJOHUIFGVODUJPOPGMJNJUJOHVQQFSUFNQFSBUVF> <41*TFUUJOH>
Binary Value „
[HumanSensor setting], [Humidification setting], [Outdoor air intake setting],
[Ourdoor cooling setting]
Calendar …
Command …
[DMS], [A/C Indoor Unit], [ERV], [AHU], [SIM], [Centralized controller],
Device „
[Interface module], [DDC]
Event Enrollment …
File …
Group …
Life Safety Point …
Life Safety Zone …
Loop …
Multi-state Input „ [Current humidity status]
Multi-state Output …
[Operation mode control], [Fan speed control], [Air flow direction control],
Multi-state Value „ [Setting Cool only/ Heat only/ No Limit ], [Control Enable RC/ Disable RC /Level1],
[Set humidity status]

[AC Indoor Notify], [ERV Notify], [AHU Notify], [Centralized Controller Notify],
Notification Class „
[Interface Module Notify], [SIM Notify], [Gateway Notify]
Program …
Pulse Converter …
Schedule …
Trend Log …
Access Door …
Event Log …
Load Control …
Structured View …
Trend Log Multiple …

176

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX^] YWX[TW[TY\GGG㝘䟸G[aZ]a[_
10) Property support specification
(1) Device property
Check
Property identifier Property data Support DMS2
code
1 0CKFDUJEFOUJGJFS #"$OFU0CKFDU*EFOUJGJFS R V Individual identifier
SAMSUNG DVM
2 0CKFDUOBNF CharaterString R V
Gateway
3 0CKFDUUZQF #"$OFU0CKFDU5ZQF R V DEVICE
During communication:
i01&3"5*0/"-w
4 System status BACnetDeviceStatus R V
Error with DMS2:
i/0/@01&3"5*0/"-w
Samsung Electronics
5 Vendor name CharacterString R V
CO., Ltd.
6 Vendor identifier Unsigned16 R V 
7 Model name CharterString R V MIM-B17N
8 Firmware revision CharterString R V 
9 Application software version CharterString R V 
10 Location CharterString O X
%.4@#"$OFU*1
11 Description CharterString O V
<WFS>
12 1SPUPDPMWFSTJPO Unsigned R V 
13 1SPUPDPMDPOGPSNBODFDMBTT Unsigned(1..6) R X
14 1SPUPDPMTFSWJDFTTVQQPSUFE BACnetServicesSupported R V For each device
15 1SPUPDPMPCKFDUUZQFTTVQQPSUFE #"$OFU0CKFDU5ZQFT4VQQPSUFE R V For each device
16 0CKFDUMJTU BACnetidentifier BACnet sequence [N] R V For each device
17 .BY"1%6MFOHUIBDDFQUFE Unsigned R V 1476
18 Segmentation supported BACnetSegmentation R V NO-SEGMENTATION
(1)
19 VT classes supported BACnetVTClass O X
(1)
20 Active VT sessions BACnetVTSessions O X
21 Local time Time O V Supported
22 Local date Date O V Supported
23 UTC offset INTEGER O X
24 Daylight savings timeout BOOLEAN O X
MANAGEMENT SYSTEM

(2)
25 "1%6TFHNFOUUJNFPVU Unsigned O X
26 "1%6UJNFPVU Unsigned R V 
BUILDING

27 /VNCFSPG"1%6SFUSJFT Unsigned R V 3
28 List of session keys BACnetSessionKey O X
(3)
29 Time synchronization recipients BACnetRecipient O X
(4)
30 Max master Unsigned(1..127) O V X
(4)
31 Max info frames Unsigned O V X
32 Device address binding BACnetAddressBinding R V X
33 1SPUPDPMSFWJTJPO Unsigned R V 2

177

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX^^ YWX[TW[TY\GGG㝘䟸G[aZ]a[_
Control Systems

VI Building management system


2. DMS B-net (BACnet GW)
MIM-B17N

10) Property support specification


(2) Analog Input Property
Check
Property identifier Property data Support DMS2
code
1 0CKFDUJEFOUJGJFS #"$OFU0CKFDU*EFOUJGJFS R V

2 0CKFDUOBNF CharaterString R V

3 0CKFDUUZQF #"$OFU0CKFDU5ZQF R V
4 1SFTFOUWBMVF REAL R(1) V
AI_Instance_device
5 Description CharacterString O V
address
6 Device type CharacterString O
Communication
Status_Flags FAULT flag
7 Status Flags BACnetStatusFlags R V
Š True OUT_OF_SERVICE
Š TRUE
8 Event state BACnetEventState R V General Error
Status_Flags FAULT flag
Š TRUE
FAULT if Reliability is not
NO_FALUT_DETECTED
9 Reliability BACnetReliability O V Communication error Š
COMMUNICATION_
FAILURE
General error Š
Unreliable_other
Communication error
10 Out of service BOOLEAN R V
Š TRUE
11 Update interval Unsigned O

12 Units BACnetEngineeringUnits R V

13 Min pres value REAL O V

14 .BY1SFT7BMVF REAL O V

15 Resolution REAL O

16 COV increment REAL O(2) V

17 Time delay Unsigned O(3)

18 Notification class Unsigned O(3)

19 High limit REAL O(3)

20 Low limit REAL O(3)

21 Deadband REAL O(3)

22 Limit Enable BACnetLimitEnable O(3)

23 Event enable BACnetEventTransitionBits O(3)

24 Acked transition BACnetEventTransitionBits O(3)

25 Notify type BACnetNotifyType O(3)

178

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX^_ YWX[TW[TY\GGG㝘䟸G[aZ]a[_
(3) Analog output property
Check
Property identifier Property data Support DMS2
code
1 0CKFDUJEFOUJGJFS #"$OFU0CKFDU*EFOUJGJFS R V

2 0CKFDUOBNF CharaterString R V
3 0CKFDUUZQF #"$OFU0CKFDU5ZQF R V DEVICE
4 1SFTFOUWBMVF REAL W V
AI_Instance_device
5 Description CharacterString O V
address
6 Device type CharacterString O
Communication
Status_Flags FAULT flag
7 Status Flags BACnetStatusFlags R V
Š True OUT_OF_SERVICE
Š TRUE
8 Event state BACnetEventState R V General Error
Status_Flags FAULT flag
Š TRUE
FAULT if Reliability is not
NO_FALUT_DETECTED
9 Reliability BACnetReliability O V Communication error Š
COMMUNICATION_
FAILURE
General error Š
Unreliable_other
Communication error
10 Out of service BOOLEAN R V
Š TRUE
11 Units BACnetEngineeringUnits R V

12 Min pres value REAL O V

13 .BY1SFT7BMVF REAL O V

14 Resolution REAL O

15 1SJPSJUZBSSBZ #"$OFU1SJPSJUZ"SSBZ R V

16 Relinquish default REAL R V

17 COV increment REAL O(1)

18 Time Delay Unsigned O(2)


MANAGEMENT SYSTEM

19 Notification class Unsigned O(2)


BUILDING

20 High limit REAL O(2)

21 Low limit REAL O(2)

22 Deadband REAL O(2)

23 Limit enable BACnetLimitEnable O(2)

24 Event Enable BACnetEventTransitionBits O(2)

25 Acked transition BACnetEventTransitionBits O(2)

25 Notify type BACnetNotifyType O(2)

179

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX^` YWX[TW[TY\GGG㝘䟸G[aZ]a[`
Control Systems

VI Building management system


2. DMS B-net (BACnet GW)
MIM-B17N

10) Property support specification


(4) Binary input property
Check
Property identifier Property data Support DMS2
code
1 0CKFDUJEFOUJGJFS #"$OFU0CKFDU*EFOUJGJFS R V

2 0CKFDUOBNF CharaterString R V

3 0CKFDUUZQF #"$OFU0CKFDU5ZQF R V
4 1SFTFOUWBMVF #"$OFU#JOBSZ17 W V
AI_Instance_device
5 Description CharacterString O V
address
6 Device type CharacterString O
Communication
Status_Flags FAULT flag
7 Status Flags BACnetStatusFlags R V
Š True OUT_OF_SERVICE
Š TRUE
8 Event state BACnetEventState R V General Error
Status_Flags FAULT flag
Š TRUE
FAULT if Reliability is not
NO_FALUT_DETECTED
9 Reliability BACnetReliability O V Communication error Š
COMMUNICATION_
FAILURE
General error Š
Unreliable_other
Communication error
10 Out of service BOOLEAN R V
Š TRUE
11 1PMBSJUZ #"$OFU1PMBSJUZ R V
12 Inactive text CharacterString O(1) V New
13 Active text CharacterString O(1) V New
14 Change of state time BACnetDateTime O(2)

15 Change of state count Unsigned O(2)


O(2)
16 Time of state count reset BACnetDateTime
O(3)
17 Elapsed active time Unsigned32 O(3)

18 Time of active time reset BACnetDate Time O

19 Time delay Unsigned O(4)

20 Notification class Unsigned O(4)

21 Alarm value #"$OFU#JOBSZ17 O(4)

22 Event enable BACnetEventTransitionBits O(4)

23 Acked transition BACnetEventTransitionBits O(4)

24 Notify type BACnetNotifyType O(4)

180

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX_W YWX[TW[TY\GGG㝘䟸G[aZ]a[`
(5) Binary output property
Check
Property identifier Property data Support DMS2
code
1 0CKFDUJEFOUJGJFS #"$OFU0CKFDU*EFOUJGJFS R V

2 0CKFDUOBNF CharaterString R V

3 0CKFDUUZQF #"$OFU0CKFDU5ZQF R V
4 1SFTFOUWBMVF #"$OFU#JOBSZ17 W V
AI_Instance_device
5 Description CharacterString O V
address
6 Device type CharacterString O
Communication
Status_Flags FAULT flag
7 Status Flags BACnetStatusFlags R V
Š True OUT_OF_SERVICE
Š TRUE
8 Event state BACnetEventState R V General Error
Status_Flags FAULT flag
Š TRUE
FAULT if Reliability is not
NO_FALUT_DETECTED
9 Reliability BACnetReliability O V Communication error Š
COMMUNICATION_
FAILURE
General error Š
Unreliable_other
Communication error
10 Out of service BOOLEAN R V
Š TRUE
11 1PMBSJUZ #"$OFU1PMBSJUZ R V

12 Inactive text CharacterString O(1) V

13 Active text CharacterString O(1) V

14 Change of state time BACnetDateTime O(2)

15 Change of state count Unsigned O(2) V


O(2)
16 Time of State count reset BACnetDateTime V
O(3)
17 Elapsed active time Unsigned32 O(3)

18 Time of active time reset BACnetDate Time O

19 Minimum off time Unsigned32 O

20 Minimum on time Unsigned32 O

21 1SJPSJUZBSSBZ #"$OFU1SJPSJUZ"SSBZ R
MANAGEMENT SYSTEM

22 Relinquish default #"$OFU#JOBSZ17 R


BUILDING

23 Time delay Unsigned O(4)

24 Notification class Unsigned O(4)

25 Alarm value #"$OFU#JOBSZ17 O(4)

26 Event enable BACnetEventTransitionBits O(4)

27 Acked transition BACnetEventTransitionBits O(4)

28 Notify type BACnetNotifyType O(4)

181

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX_X YWX[TW[TY\GGG㝘䟸G[aZ]a[`
Control Systems

VI Building management system


2. DMS B-net (BACnet GW)
MIM-B17N

10) Property support specification


(6) Multi-state input property
Check
Property identifier Property data Support DMS2
code
1 0CKFDUJEFOUJGJFS #"$OFU0CKFDU*EFOUJGJFS R V

2 0CKFDUOBNF CharaterString R V

3 0CKFDUUZQF #"$OFU0CKFDU5ZQF R V
4 1SFTFOUWBMVF Unsigned R(1) V
M_Instance_device
5 Description CharacterString O V
address
6 Device type CharacterString O
Communication
Status_Flags FAULT flag
7 Status Flags BACnetStatusFlags R V
Š True OUT_OF_SERVICE
Š TRUE
8 Event state BACnetEventState R V General Error
Status_Flags FAULT flag
Š TRUE
FAULT if Reliability is not
NO_FALUT_DETECTED
9 Reliability BACnetReliability O V Communication error Š
COMMUNICATION_
FAILURE
General error Š
Unreliable_other
Communication error
10 Out of service BOOLEAN R V
Š TRUE
11 Number of states Unsigned R V
BACnet sequence of
12 State text O V
characterString
13 Time delay Unsigned O(2)

14 Notification class Unsigned O(2)

15 Alarm values Unsigned list O(2)

16 Fault values Unsigned list O(2)

17 Event enable BACnetEventTransitionBits O(2)

18 Acked transition BACnetEventTransitionBits O(2)

19 Notify type BACnetNotifyType O(2)

182

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX_Y YWX[TW[TY\GGG㝘䟸G[aZ]a[`
(7) Multi-state output property
Check
Property identifier Property data Support DMS2
code
1 0CKFDUJEFOUJGJFS #"$OFU0CKFDU*EFOUJGJFS R V

2 0CKFDUOBNF CharaterString R V

3 0CKFDUUZQF #"$OFU0CKFDU5ZQF R V
4 1SFTFOUWBMVF Unsigned R(1) V
M_Instance_device
5 Description CharacterString O V
address
6 Device type CharacterString O
Communication
Status_Flags FAULT flag
7 Status Flags BACnetStatusFlags R V
Š True OUT_OF_SERVICE
Š TRUE
8 Event state BACnetEventState R V General Error
Status_Flags FAULT flag
Š TRUE
FAULT if Reliability is not
NO_FALUT_DETECTED
9 Reliability BACnetReliability O V Communication error Š
COMMUNICATION_
FAILURE
General error Š
Unreliable_other
Communication error
10 Out of service BOOLEAN R V
Š TRUE
11 Number of states Unsigned R V
BACnet arrangement of
12 State text O V
CharacterString
13 Time delay Unsigned O(2)

14 Notification class Unsigned O(2)

15 Alarm values Unsigned list O(2)

16 Fault values Unsigned list O(2)

17 Event enable BACnetEventTransitionBits O(2)


MANAGEMENT SYSTEM

18 Acked transition BACnetEventTransitionBits O(2)


BUILDING

19 Notify type BACnetNotifyType O(2)

183

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX_Z YWX[TW[TY\GGG㝘䟸G[aZ]a[`
DVM CONTROL
SYSTEMS

184

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX_[ YWX[TW[TY\GGG㝘䟸G[aZ]a[`
VII. Test run tool for system
air contioner installation
1 S-checker. . . . . . . . . . . . . . . . . . . . . . . . . 186
2 S converter . . . . . . . . . . . . . . . . . . . . . . . . 194

AIR CONDITIONER INSTALLATION


5&4536/500-'034:45&.

185

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX_\ YWX[TW[TY\GGG㝘䟸G[aZ]a[`
Control Systems

VII Test run tool for system air conditioner installation


1. S-Checker
MIM-C10N

1) Features

tExecute test run for Samsung system air conditioner


and inspects the parts (EEV, Sensor).
tIt can be linked with mobile application to allow saving
and monitoring data of the test run.

(Unit:mm)
96.00 36.60
RESET

Live Wi-Fi 485 Error


DOWNLOAD

OFF/ON
POWER
REPORT

124.00
TEMP.1
EEV2

TEMP.2
EEV1

PRESSURE

2) Product specification
Power supply 7_7"$ )[
Power consumption #FMPX8
Operating temperature range ¡$_¡$
Operating humidity range 3)_3)
RS485 1PSU2hUZ 1
Communication
Wi-Fi Supportablity Supported
Maximum RS485 m  N
number of
Indoor unit EA 64
controllable
devices Outdoor unit EA 1

>4VQQPSUFETQFDJGJDBUJPOPGUIFNPCJMFBQQMJDBUJPO3FTPMVUJPOPWFS9 PQUJNJ[FEBU9
- OS : Android 2.3~4.12

Compatible product
Outdoor unit AM7777X777777Model
Indoor unit AM7777N777777Model

186

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX_] YWX[TW[TY\GGG㝘䟸G[aZ]a\W
3) Description of parts ⑬ LINK S-NET
Micro-SD

⑭ ⑮
⑧ ⑨
⑦ ⑩

RESET
Live Wi-Fi 485 Error

DOWNLOAD

OFF/ON

POWER

REPORT

TEMP.1

EEV2

TEMP.2
⑫ ⑤

EEV1

PRESSURE

DC JACK DC 12 V RS-485

No. Name Description


① Reset button Use to reset S-checker
② Power button Use to turn on/off the power for S-checker.
③ Report button Use to create report for test run.
$POOFDUPSGPSUFNQFSBUVSFTFOTPSUIBUJTDPOOFDUFEUPQJUDIQJODPOOFDUPS
Temperature sensor inpsection
④ Temperature value can be checked from the S-checker by connecting the temperature sensor
connector 1
directly.

$POOFDUPSGPSUFNQFSBUVSFTFOTPSUIBUJTDPOOFDUFEUPQJUDIQJODPOOFDUPS
Temperature sensor inpsection
⑤ Temperature value can be checked from the S-checker by connecting the temperature sensor
connector 2
directly

Pressure sensor inspection Connector for connecting high/low pressure sensor of the outdoor unit.

connector (4 pin) 1SFTTVSFWBMVFDBOCFDIFDLFEGSPNUIF4DIFDLFSCZDPOOFDUJOHUIFUFNQFSBUVSFTFOTPSEJSFDUMZ
⑦ System operation status LED Turns on when the S-Checker is operating normally.
⑧ Wi-Fi connection LED Turns on when the data is being tranmitted to mobile through Wi-Fi
⑨ RS-485 operation status LED Turns on when data is transmitted and received through RS-485 communication
⑩ System Error LED Turns on when error occurs on S-checker.
⑪ LCD display Check the current information and the items in menu that can be selected by menu buttons.
⑫ Menu buttons Use to move and select from menu.
⑬ USB for S-Net Pro 2 .JOJ64#GPSDPOOFDUJOHXJUI4/&51SP
⑭ USB for system Use to download program etc.
⑮ IR tranceiver Use to transmit IR.
⑯ Micro SD slot Slot to insert Micro SD card.
⑰ PBA download connector 6TFUPEPXOMPBE4DIFDLFSUISPVHI1$
EEV inspection connector 1 (5
⑱ $IFDLGPSFSSPSPO&&7TFOTPS $".5ZQF 1JO

Pin)
EEV inspection connector 2 (6
AIR CONDITIONER INSTALLATION
5&4536/500-'034:45&.

⑲ $IFDLGPSFSSPSPO&&7TFOTPS &%.5ZQF 1JO

Pin)
⑳ DC 12 V adapter Use to connect independent 12 V power.

DC 12 V connector Connector to use 12V power from air-conditioner

RS-485 connector Connector for RS-485 communication.

187

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX_^ YWX[TW[TY\GGG㝘䟸G[aZ]a\W
Control Systems

VII Test run tool for system air conditioner installation


1. S-Checker
MIM-C10N

4) Connection diagram

F1/F2

Outdoor unit
(New communication)
4NBSU1IPOF

5BCMFU1$
SD Card

micro SD S-checker
Indoor unit Indoor unit

USB cable
/PUF1$
4/&51SP

5) Connecting

Connecting with outdoor unit

Outdoor unit
F1 F2 R1 R2
S-checker

DC JACK DC 12 V RS-485

No polarity

Connecting with S-NET Pro 2

LINK S-NET
Micro-SD

USB cable (supplied)

188

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX__ YWX[TW[TY\GGG㝘䟸G[aZ]a\W
Connecting with mobile device

F1/F2

Outdoor unit
(New communication)

S-checker

4NBSU1IPOF
Indoor unit Indoor unit

f Method 1- Search for S-Checker

f Method 2- Scan from mobile application


AIR CONDITIONER INSTALLATION
5&4536/500-'034:45&.

189

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX_` YWX[TW[TY\GGG㝘䟸G[aZ]a\X
Control Systems

VII Test run tool for system air conditioner installation


1. S-Checker 
MIM-C10N

6) Main function

Test run report


tTest run report menu will inspect the system in real time and notify the result.
Section Function
During outdoor unit test run, test run
Inspection step for
prgress will be displayed in the
test run
progress bar on top part.

Status for items of test run will be


Items for test run displayed and 'NG' will be
displayed for undetermined items.

Input site Install engineer can input the site


information information

Make Test Run File : Saves


&&130.EBUBPO4$IFDLFS
When saving is completed “LOG:
Ready to make Report” message
will appear.
Create test run
report
tAfter completing the test run report, data Make Report :
will be saved on the folder (name : mBiss) Creates Test Run Report.
of mobile device as csv and pdf file. 1SPHSFTTDBOCFDIFDLFEGSPN
“LOG: Making Test Run Report.
Display of the cycle information 1SPHSFTTJT99wNFTTBHF

tCycle Info : it displays cycle data of the indoor and outdoor unit.
 %JTQMBZFEJUFNJTTBNFBT4/&51SP

[Cycle info : Outdoor unit] [Cycle info : Indoor unit]


Displays the cycle information Displays the cycle information
of the connected outdoor unit. of the connected indoor unit.
Maximum of 64 indoor units'
data can be displayed.

190

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX`W YWX[TW[TY\GGG㝘䟸G[aZ]a\X
Install monitoring
tIt displays the installation information of the outdoor unit and indoor unit.

Install monitor: Outdoor unit Install monitor: Indoor unit

Checking the status of device


t:PVDBODPOOFDUQSFTTVSFTFOTPS UFNQFSBUVSFTFOTPS &&7DPOOFDUPS UIBUJTDPOOFDUFEUPUIF1#"PGJOEPPSBOEPVUEPPSVOJU

to the terminal on the S-checker and check the status of the device.

Type of sensor Displayed contents


Resistence value, displays
Temperature sensor
temperature

Pressure sensor Voltage value, displays pressure

EEV drive Related information during


information driving
AIR CONDITIONER INSTALLATION

Control + 15 more than real


5&4536/500-'034:45&.

Full Open
maximum value

Full Close Control the opening of EEV as 0

Ú When control EEV, you can connect only Direct


Acting Type or Gear Type

191

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX`X YWX[TW[TY\GGG㝘䟸G[aZ]a\Y
Control Systems

VII Test run tool for system air conditioner installation


1. S-Checker 
MIM-C10N

6) Main function

Checking the communication

t Through Comm. Check menu, communication status between indoor/outdoor unit can be checked.
t Indoor unit can be connected to S-checker alone without outdoor unit, to check the communication status of indoor unit.

Setting the indoor unit option

t You can check the option code of indoor unit from the S-checker.
t Option code setting can be applied to multiple numbers of indoor unit at once.

192

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX`Y YWX[TW[TY\GGG㝘䟸G[aZ]a\Y
Other functions

t A/C S/W Upgrade: Firmware for indoor and outdoor unit of system air conditioner can be upgraded.
t Unit control: This function restricts general operation if auto trial operation is incompleted.
t Refrigerant check: This is a detect function according to piping option which calculates the amount of refrigerant to see if it's adequate.

AIR CONDITIONER INSTALLATION


5&4536/500-'034:45&.

193

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX`Z YWX[TW[TY\GGG㝘䟸G[aZ]a\Y
Control Systems

VII Test run tool for system air conditioner installation


2. S-Converter
MIM-C02N

1) Features

t$PNNVOJDBUJPODPOWFSUJOHNPEVMFUPDPOOFDU4BNTVOHTZTUFNBJSDPOEJUJPOFSUPB1$
t Main purpose for use
- To coonect with test run program

[Test run program]


· S-NET Pro : Conventional communication
· S-NET Pro 2 : New communication

28.00 (Unit:mm)
66.50
22.00
55.30
13.00
92.00

80.30

92.00

2) Product specification
Power supply %$7 CFMPXN"
Power consumption Below 3 W
Operating temperature range ¡$_¡$
Operating humidity range 3)_3)
Communication RS485 1PSU2hUZ 1
Maximum
length of RS485 m N
connection

194

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX`[ YWX[TW[TY\GGG㝘䟸G[aZ]a\Y
3) Description of parts

③ ⑤


⑨ ⑩



⑤ ⑧

No. Name Description


① 1PXFS-&% Display power status
485 communication / 2 line
② Displays communication status when outdoor uint 2 line remote controller is connected
communication LED
③ 232 LED %JTQMBZTDPNNVOJDBUJPOTUBUVTXJUIUIF1$
USB-RS232 connection
④ $POOFDUJPOUFSNJOBMGPSDPNNVOJDBUJPOXJUIUIF1$
terminal
Only applies to new communication indoor unit
2 line communication
⑤ 2 line communication connection terminal between indoor unit - wired remote controller
connection terminal
(For R&D testing)
Downloader connection
⑥ 1#"EPXOMPBEDPOOFDUJPOUFSNJOBM
terminal
RS485 communication
⑦ Conenction cable for connecting with indoor/outdoor unit's F1, F2 communication terminal
connection terminal
Only used when S-converter is used as SW downloader for the product
⑧ TARGET OFF – ON button - *GUIF4$POWFSUFSTVQQMJFTUIFQPXFSUISPVHIUIF1#"PGUIFQSPEVDUUIBUXJMMEPXOMPBEUIF48 UIJT
button resets the power that was supplied through the S-Converter

⑨ USB-to-232 cable $BCMFUIBUDPOOFDUT4$POWFSUFSBOE1$

Only used when S-converter is used as SW downloader for the product


⑩ SW downloader cable
$POOFDU4$POWFSUFS 1JO
BOEUIFEPXOMPBEFSUFSNJOBM 1JO 1JO
PGUIFQSPEVDUhT1$#

4) Connection diagram
AIR CONDITIONER INSTALLATION
5&4536/500-'034:45&.

F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2

195

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX`\ YWX[TW[TY\GGG㝘䟸G[aZ]a\Z
Control Systems

VII Test run tool for system air conditioner installation


2. S-Converter
MIM-C02N

5) Connecting

Connecting with outdoor unit

F1 F2 R1 R2

Connecting with PC

6) Display
(1) POWER LED
t When connected to Conventional communication outdoor unit - LED blinks
t When connected to new communication outdoor unit - LED is on

(2) 232 LED


t LED blinks every time control signal is transmitted from the Test run program
t If the LED doesn't blink even though the test run program sends control command, check if the program is appropriate for the
communication type (Conventional communication/new communication)

(3) 485/ 2-LINE LED


t LED blinks when the data is being transmitted from the 485 or 2-line communication device
Ú 485 communication cable - outdoor unit connection (Connects test run program)
2-line communication device - wired remote controller connection (connects program for the developer)
t If the LED doesn't turn on, check if the communication cable is disconnected/short or check if the device is appropriate for the
196 communication type (Conventional communication/new communication)

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX`] YWX[TW[TY\GGG㝘䟸G[aZ]a\[
MEMO

197

[¥]Uw–žŒ™G‹š›™‰œ›–•Gš š›Œ”¥U•‹‹GGGX`^ YWX[TW[TY\GGG㝘䟸G[aZ]a\[