SICOM

PC software: Communications program

USER´S MANUAL

EN_FANOX_SICOM_MANUAL_COMSof tware_SICOM_R009.pdf
1. INTRODUCTION ...............................................................................................................4
2. HOW TO INSTALL SICOM SOFTWARE ..................................................................................5
3. HOW TO COMMUNICATE WITH THE COMPUTER ..................................................................6
3.1. COMMUNICATION THROUGH LOCAL FRONT PORT (USB OR RS232): ................................................................7
3.2. COMMUNICATION THROUGH REMOTE ETHERNET PORT (RJ45): ..................................................................... 11
3.3. COMMUNICATION THROUGH WIFI: ............................................................................................................... 17
4. PASSWORD TO START THE SESSION.................................................................................. 23
5. WHAT IS SHOWN IN MAIN SCREEN ................................................................................... 26
6. STATES MENU ............................................................................................................... 31
7. SETTINGS MENU ............................................................................................................ 35
7.1. HOW TO CHANGE A SETTING .......................................................................................................................... 37
7.2. HOW TO SAVE A SETTINGS FILE....................................................................................................................... 45
7.3. HOW TO OPEN A SETTINGS FILE ...................................................................................................................... 46
8. CONFIGURATION ........................................................................................................... 48
8.1. HOW TO CHANGE THE CONFIGURATION.......................................................................................................... 50
8.1.1. Demand configuration ................................................................................................................... 62
8.2. HOW TO SAVE A CONFIGURATION FILE............................................................................................................ 67
8.3. HOW TO OPEN A CONFIGURATION FILE........................................................................................................... 69
9. EVENTS MENU .............................................................................................................. 72
9.1. HOW TO SAVE THE EVENTS............................................................................................................................. 78
9.2. HOW TO DELETE THE EVENTS.......................................................................................................................... 80
10. FAULT REPORTS MENU................................................................................................ 83
10.1. HOW TO DELETE FAULTS REPORTS.............................................................................................................. 87
11. OSCILLOGRAPHIC RECORDS MENU ................................................................................ 89
11.1. HOW TO SAVE AN OSCILLOGRAPHIC RECORD .............................................................................................. 93
12. LOAD DATA PROFILING (LDP) MENU.............................................................................. 97
12.1. HOW TO SAVE THE DEMAND.................................................................................................................... 102
12.2. HOW TO DELETE THE DEMAND................................................................................................................. 104
13. SET DATE AND TIME MENU ........................................................................................ 107
14. COUNTERS MENU..................................................................................................... 113
15. COMMAN DS MENU .................................................................................................. 117
16. CHANGE ACCESS MENU ............................................................................................. 120
17. SICOM OFFLINE – SETTING FILE................................................................................... 125
17.1. HOW TO CREATE A NEW SETTINGS FILE FROM OFFLINE MODE ................................................................... 125
17.2. HOW TO OPEN A SETTINGS FILE FROM OFFLINE MODE .............................................................................. 131
17.2.1. Old settings file (pr eviously saved before SICOM version 1.0.0.46)................................... 131
17.2.2. New settings file (pr eviously saved from SICOM version 1.0.0.46 onwards)................... 135
17.3. HOW TO SEND A SETTINGS FILE................................................................................................................ 138
18. SICOM OFFLINE – CONFIGURATION FILE....................................................................... 144
18.1. HOW TO CREATE A NEW CONFIGURATION FILE FROM OFFLINE MODE........................................................ 144
18.2. HOW TO OPEN A CONFIGURATION FILE FROM OFFLINE MODE................................................................... 152
18.2.1. Old configuration file (previously saved befor e SICOM version 1.0.0.46) ........................ 152

www.f anox.com Rev.09 2/163


18.2.2. New configuration file (previously saved from SICOM version 1.0.0.46 onw ards) ........ 153
18.2.3. How to send a configuration file to the relay ......................................................................... 156

www.f anox.com Rev.09 3/163


1. INTRODUCTION
The SICom program works with the Windows® Windows 7, Windows 8 and Windows 10 operating
system and can be used to gain access to all of the relays inf ormation, to modify the settings and
to save events using a graphic user interf ace.
The main operations that can be carried out using the SICom program are as f ollows:
• General data reading: Complete model, Version, Serial number, etc.
• States reading
• Measurements reading
• Reading and changing settings
• Reading and changing conf iguration
• Reading and deleting events
• Reading and deleting f ault reports
• Reading and deleting demand current (load data prof iling)
• Reading and saving oscillographic records in Comtrade f ormat
• Changing the user passwords
• Saving and Loading settings f iles
• Saving and Loading conf iguration f iles
• Saving events and f ault reports
• Saving demand current (load data prof iling)
• Date-time synchronization
• Conf iguring the communication parameters
• Reading and changing counters
• Commands f or opening and closing the circuit breaker and block/unblock the recloser
• Conf iguration of the inputs
• Conf iguration of the outputs
• Conf iguration of the causes that start a Fault Report

www.f anox.com Rev.09 4/163


2. HOW TO INSTALL SICOM SOFTWARE
To install the SICom it is necessary the f ollowing link:
http://f anox.blob.core.windows.net/sicom/publish.htm
The link will open the next screen, where key “install” must be pressed:

Once it is pressed INSTALL, the SICOM will be installed automatically. Following this advice, the update of the sof tware does not require any user´s action,
this is, if the SICOM is run being the laptop connected to Internet, The SICOM updates itself when it is started. Besides, the necessary drivers depending on
the operative system can be downloaded f rom this page.

Offline mode is also available to prepare the settings and configuration files without having the relay connected to the lapt op, reducing engineering and
commissioning time.

www.f anox.com Rev.08 5/163


3. HOW TO COMMUNICATE WITH THE COMPUTER
It is possible to connect with the SICOM through the f ront local port or through the rear ethernet port if it is available in the relay.
SICom program uses Modbus (RTU or TCP/IP) protocol, so only the ports with this protocol can be used to establish the communication.
Follow the next steps to start the session:
• Connect the relay to the PC through a port that uses Modbus RTU protocol (depending on the relay this port can be USB, RS232, RS485, RJ45
(ethernet) or WiFi).
• Open the SICom previously installed and press START. The f ollowing screen will appear:

www.f anox.com Rev.08 6/163


3.1. Communication through local front port (USB or RS232):
All Fanox relays can communicate with the SICOM through the local f ront port. Once the relay is switched on, connect it to the laptop through a USB or RS232
cable, depending on the available f ront port in the relay.

1. Select the option “Wired RS232/USB” option:

www.f anox.com Rev.08 7/163


2. Check the associated “COM” to the used port. To check it, “Device manager→Ports (COM and LPT)”:

3. Set the associated “COM” in the SICOM option called “Select a port”. If only one port is connected to the laptop, the SICOM will recognize it automatically:

www.f anox.com Rev.08 8/163


www.f anox.com Rev.08 9/163
4. Check the “Local communication slave address” in the relay and set it in “Modbus address” of the SICOM. By def ault, this address is set to “1”, but the
user can change it f rom 1 to 254:

www.f anox.com Rev.08 10/163


3.2. Communication through remote ethernet port (RJ45):
If the relay is provided with Ethernet communication port and Modbus TCP/IP protocol associated to it, it is possible to use it to communicate with the SICOM.
Once the relay is switched on, connect the Ethernet port f rom the relay to the laptop (point to point).

1. Select in the SICOM the option “Wired Ethernet”

www.f anox.com Rev.08 11/163


1. Check in relay HMI in “GENERAL SETTINGS→Rear TCP COM” menu the set protocol. It is necessary to have it set to MODBUS TCP to
communicate with the SICOM (if you need to change the protocol to set it to Modbus TCP, af ter changing it, switch the relay o f f and switch it on
again). Go down in this menu and check the IP address

2. Check the IP address set in the relay f or this Modbus TCP protocol and set it in the relay (this IP can be set by the user) and keep the TCP port to 502.

www.f anox.com Rev.08 12/163


3. Ensure, the laptop settings f or the ethernet port are in the same segmented network of the relay. To check it:

Go to “Control panel→ Network and Sharing Center → Change adapter settings” (on the lef t menu)

Right click on the Ethernet port you are using (the one that is connected to the relay) and click on properties (last option):

Double click on Internet protocol version 4 (TCP/IPv4):

www.f anox.com Rev.08 13/163


www.f anox.com Rev.08 14/163
Set the IP of the relay changing the last bits, f or example:

NOTE: It is possible to change the IP address of the relay directly to the same segmented network of the laptop (avoiding the steps described in this
point 3), if it is known.

www.f anox.com Rev.08 15/163


5. Check in relay HMI in “GENERAL SETTINGS→MODBUS TCP” menu, the slave address. By def ault this address is 2 (going down in this menu you can
check the port that will be 502). You need to set this address in “Modbus address” of the SICOM. By def ault, this address is set to “2”, but the user can
change it f rom 1 to 254:

www.f anox.com Rev.08 16/163


3.3. Communication through WiFi:
If the relay is provided with wireless communication, it is possible to use it to communicate with the SICOM.
Once the relay is switched on, connect to the relay WiFi the Ethernet port f rom the relay to the laptop (point to point).

1. Select in the SICOM the option “Wired Ethernet”

www.f anox.com Rev.08 17/163


2. Check in relay HMI in “GENERAL SETTINGS→WIFI COM” the IP address and the port that will be 502:

www.f anox.com Rev.08 18/163


3. Ensure, the laptop settings f or the WIFI port are in the same segmented network of the relay. To check it:

Go to “Control panel→ Network and Sharing Center → Change adapter settings” (on the lef t menu)

Right click on the WIFI port you are using (the one that is connected to the relay) and click on properties (last option):

www.f anox.com Rev.08 19/163


Double click on Internet protocol version 4 (TCP/IPv4):

Set the IP of the relay changing the last bits, f or example:

www.f anox.com Rev.08 20/163


NOTE: It is possible to change the IP address of the relay directly to the same segmented network of the laptop (avoiding the steps described in this
point 3), if it is known.
4. Check in relay HMI in “GENERAL SETTINGS→WIFI COM” the Slave address that by def ault is 1 (although the user can change it f rom 1 to 247):

www.f anox.com Rev.08 21/163


:

www.f anox.com Rev.08 22/163


4. PASSWORD TO START THE SESSION

The password will be dif f erent depending on the relay. By def ault it is:

For SIA f amily the def ault password is 5555


For SIL and SIR f amily the password is: Fanox/5555
In any case, it can be changed by the user.
Set the corresponding password (depending on the used relay) and press OK to start the session:

Once the session is correctly started, the f ollowing screen will be open:

www.f anox.com Rev.08 23/163


• If there is some parameter wrong selected, a message will appear inf orming about it, and the session will not start.

www.f anox.com Rev.08 24/163


At the moment, it is not possible to work of fline; this is, without being connected to the relay.

www.f anox.com Rev.08 25/163


5. WHAT IS SHOWN IN MAIN SCREEN
The main screen is divided in dif f erent parts:
On the top of the screen all the dif f erent options of the relay are displayed.

www.f anox.com Rev.08 26/163


From the lef t to the right it is shown:
Stop → It is used to stop the session
States → It is used to see all the states
Settings → It is used to consult and change the dif f erent settings
Conf iguration → It allows to access to the relay outputs, inputs and logical signals that can be conf igured.
Events → All the events can be downloaded to analyze them
Faults → All the f ault reports can be downloaded to analyze them
Oscillo → It allows downloading the oscillographic registers in COMTRADE f ormat.
Demand → It allow to analyze the demand of current
Set Date/Time → It is used to synchronize the relay
Set Counters → Modif y the value of the counters is permitted thanks to this menu
Execute Command → It allows to carry out dif f erent commands
Change access → The access levels can be modif ied thanks to this menu

 NOTE: Depending on the relay some of this menu can be not available

www.f anox.com Rev.08 27/163


On the lef t of the screen it is explained the meaning of each digit that makes up the model of the relay.

www.f anox.com Rev.08 28/163


Just above of that explanation the complete model of the relay, the version, the serial number and the identif ication of the relay can be checked. Besides, on
the right, the date and time can be consulted.

www.f anox.com Rev.08 29/163


In the centre of the screen it can be appreciated the States grouped by criteria (a f lag symbolizes that some state of the criterion is activated), the measures
and the counters (if they are available)

www.f anox.com Rev.08 30/163


6. STATES MENU
Press “States” option:

www.f anox.com Rev.08 31/163


The f ollowing screen will be opened:

www.f anox.com Rev.08 32/163


The f lags located on the lef t, represent the activation of some of the states of the corresponding criterion.
To show the dif f erent states of each criterion, make one click on that criterion. In this case, the activated states of the criterion are represented by a yellow
triangle (instead of a f lag):

www.f anox.com Rev.08 33/163


To hide some of the criteria previously opened, press the arrow next to its name:

www.f anox.com Rev.08 34/163


7. SETTINGS MENU
To access to the dif ferent settings of the relay, press “Settings” option:

www.f anox.com Rev.08 35/163


The f ollowing window will be opened:

www.f anox.com Rev.08 36/163


7.1. How to change a setting
On the lef t of settings screen all the protection f unctions are listed (the list will depend on the model of the relay). Select the desired f unction and all the settings
related with it, will be displayed:

www.f anox.com Rev.08 37/163


If there is an arrow on the right of a parameter, press it to check the options and select the required option:

www.f anox.com Rev.08 38/163


If there is not an arrow, place the cursor on the parameter setting and the range (minimum and maximum value), the unit and t he step will be shown. In this way
the user can know which values are correct and which values are out of range.

www.f anox.com Rev.08 39/163


By def ault, only one settings table is shown. If the relay has more than one table they can be selected pressing the option at the bottom of the screen:

To close the settings of a protection f unction, make double click on the protection f unction on the lef t of the screen.

www.f anox.com Rev.08 40/163


When a setting is changed, a yellow triangle will appear on the right of that parameter (inf orming that a change has happened but it has not been sent yet). To
send the changes to the relay press “Send Settings” (up on the lef t):

If the action is correct, a message conf irming it will appear on the screen:

www.f anox.com Rev.08 41/163


www.f anox.com Rev.08 42/163
If a value out of range is written, a symbol inf orming about it will appear and the option “Send Settings” will not be availa ble:

www.f anox.com Rev.08 43/163


Setting changed made from HMI:
If the settings menu is not opened, once the menu is opened, the new setting will appear in the SICom.

If the settings menu is already opened, af ter the changes in HMI, it is necessary to press “Ref resh Settings” to visualize th e changes in the SICom:

www.f anox.com Rev.08 44/163


7.2. How to save a settings file
It is possible to save a settings f ile thanks to “Save Settings ” menu. When this option is pressed all the settings will be displayed, and a window to save these
settings will be opened:

To save as “.ses” (settings) f ile: To save as a “.xml” (excel) f ile:

It will be possible to select a name f or the f ile and the wanted location. A message conf irming the action will be shown.

www.f anox.com Rev.08 45/163


7.3. How to open a settings file
It is possible to open a settings f ile previously saved and if it is wanted, sending it to the relay. To achieve it, press “Open Settings” key, select the f ile you need
and in that window press “open”:

www.f anox.com Rev.08 46/163


All the settings will be displayed and if some setting in the opened f ile is dif ferent f rom the previously adjusted, they will appear with a yellow triangle on the right.
To send them to the relay, press “Send Settings”.

If there are several settings f ile f or dif f erent relays, please take care of selecting the correct one. If an incompatible f ile is selected SICom will not open the
document.

www.f anox.com Rev.08 47/163


8. CONFIGURATION
Press “Conf iguration” option:

www.f anox.com Rev.08 48/163


A window with the Outputs, Leds and Logical signals will be opened. If the relay of f ers demand of current, it will also appear :

www.f anox.com Rev.08 49/163


8.1. How to change the configuration
Expand the options to see all the signals that can be conf igured:

www.f anox.com Rev.08 50/163


Selecting a signal, the dif f erent f ields to configure will be opened :

These f ields are:


• Criteria Operation
• State Time
• Gate Output

Last f ield specif ies the signal that it is being conf igured.
CRITERIA

www.f anox.com Rev.08 51/163


This f ield is made up of all criteria included in “States menu” in the relay, this is, protection f unctions, inputs, outputs, logic, communications… All the options
that can be assigned to outputs, leds and logical signals will appear:

STATE

www.f anox.com Rev.08 52/163


Once, a criterion is selected, the dif f erent states associated to that criterion will appear in “State” f ield:

GATE

www.f anox.com Rev.08 53/163


The next f ield is “gate”. It is possible to choose between OR, NOR, AND, NAND. The inputs of these gates will be the signals selected in Criteria f ield:

OPERATION

www.f anox.com Rev.08 54/163


Finally, logical gate can be selected between Latch, Pulse, Several pulses or Timer (depending on model some of these options will not be available). The input
of this logical gate will be the output of the previous gate:

Logical gate selection guide

www.f anox.com Rev.08 55/163


The conf igured signal will make a pulse of the adjusted milliseconds once the input signal is activated.

Input

T
Output

The conf igured signal waits the adjusted milliseconds to activate itself .

Input

T
Output

www.f anox.com Rev.08 56/163


The conf igured signal will be activated till it is externally reset (command, reset key, communications…), though the input signal drops off.

Input

Output

The conf igured signal will make pulses of the adjusted milliseconds while the input signal is activated.

Input

T T T
Output

www.f anox.com Rev.08 57/163


TIME
The f ield “time” is only available if pulse, pulses or timer option is selected. Positioning the cursor on the corresponding box the range the step and the unit will
be shown:

www.f anox.com Rev.08 58/163


Once the conf iguration is f inished a message that it has not been sent will appear at the bottom of the screen. Press “Send conf iguration” and it will be sent to
the relay:

www.f anox.com Rev.08 59/163


If the conf iguration is sent correctly, a message conf irming it will be shown:

NOTE: If the time and operation are changed, it is necessary to switch the relay of f and to switch it on again to charge it in the relay. If these mentioned
parameters are not changed, this action is not necessary to have the conf iguration charged in the relay.

www.f anox.com Rev.08 60/163


Configuration change made from HMI:
If conf iguration menu is not opened once the menu is opened, the new conf iguration will appear in the SICom.
If the conf iguration menu is already opened, af ter the changes in HMI, it is necessary to press “Ref resh Conf iguration” to vi sualize the changes in the SICom.

www.f anox.com Rev.08 61/163


8.1.1. Demand configuration
If the demand of current is available in the relay, it will appear in conf iguration menu:

www.f anox.com Rev.08 62/163


Select the Demand f rom the options that are shown on the lef t of the screen and the conf igurable parameters will be displayed:

www.f anox.com Rev.08 63/163


Positioning the cursor on each parameter, the range of conf iguration, the step and the unit could be checked:

www.f anox.com Rev.08 64/163


Select the desired value (a message reminding the conf iguration has not been sent, will be shown on the bottom of the screen) and send it to the relay pressing
“Send conf iguration” key:

www.f anox.com Rev.08 65/163


If the action f inalizes successf ully a message inf orming about it will appear:

www.f anox.com Rev.08 66/163


8.2. How to save a configuration file
It is possible to save a conf iguration f ile thanks to “Save Conf iguration” menu. When this option is pressed, a window to sav e this conf iguration will be opened:

The name of the f ile and the wanted location can be selected

www.f anox.com Rev.08 67/163


Finally a message conf irming the conf iguration has been saved will appear on the screen.

www.f anox.com Rev.08 68/163


8.3. How to open a configuration file
It is possible to open a conf iguration f ile previously saved and if it is wanted, sending it to the relay. To achieve it, press “Open Conf iguration” key, select the f ile
you need and press “open”:

www.f anox.com Rev.08 69/163


A message conf irming that the conf iguration has been loaded correctly will appear on the screen.
At the bottom of the screen, a message reminding the new conf iguration has not been sent will be shown.

Press “Send Conf iguration” to send it to the relay

www.f anox.com Rev.08 70/163


Respect to the conf iguration f iles, it is very important that the f ile corresponds to the model of the relay. If an incorrect f ile is selected SICom cannot open that
f ile and the program will inf orm about it:

www.f anox.com Rev.08 71/163


9. EVENTS MENU
Press “Events” key:

www.f anox.com Rev.08 72/163


A window with all the events registered in the relay will be shown:

www.f anox.com Rev.08 73/163


The f ollowing inf ormation is available:

• Function: The criterion that has originated the event.

• Identif ier: Identif ication number of the event.

• Description of the f unction: The specif ic state of the criterion that has originated the event.

• Event state: If the event has been originated because of an activation or deactivation of the state.

• Associated measure: The measure in the moment of the register. If this measure is registered with the corresponding unit, it will be shown as well.

• Date: Time stamp of the event.

www.f anox.com Rev.08 74/163


On the lef t of the screen all the criteria that generate events appear. Pressing one of those options, the events are f iltered according to that criterion:

www.f anox.com Rev.08 75/163


To return to all the events, press the complete model on the lef t of the screen:

www.f anox.com Rev.08 76/163


Once the events menu is opened, if some new event is generated in the relay, press “Ref resh Events” key to visualize them :

www.f anox.com Rev.08 77/163


9.1. How to save the events
To save the events, press “Save Events” key. A window will be opened to choose the name and the desired location:

www.f anox.com Rev.08 78/163


To f inalize the action, a message inf orming that the events have been saved will be shown on the screen:

www.f anox.com Rev.08 79/163


9.2. How to delete the events
To delete the events of the relay, press “Delete Events” key. A question to conf irm the erasing will be shown:

www.f anox.com Rev.08 80/163


If “ok” option is pressed the events will be erased in the relay and a message conf irming it will appear on the screen:

www.f anox.com Rev.08 81/163


Af ter this operation, only one event will be registered, this is, “Events erased”.

www.f anox.com Rev.08 82/163


10. FAULT REPORTS MENU
Press “Faults” option:

www.f anox.com Rev.08 83/163


The f ollowing screen will be opened. On the lef t, all the f aults registered on the relay can be checked:

The number of f ault reports will depend on the relay. If a f ault report has not been registered, a ‘-‘ will appear in its place.

www.f anox.com Rev.08 84/163


Select the wanted f ault report and the events related with it will be displayed:

The same inf ormation as in “events” option can be checked.

www.f anox.com Rev.08 85/163


Once the “f aults” menu is opened, if some new f ault report is generated in the relay, press “Ref resh Faults” key to visualize them:

www.f anox.com Rev.08 86/163


10.1. How to delete faults reports
To delete the f ault reports of the relay, press “Delete Faults” key. A question to conf irm the erasing will be shown :

www.f anox.com Rev.08 87/163


If “ok” option is pressed the f ault reports will be erased in the relay and a message conf irming it will appear on the screen:

Once the f ault report is erased, the corresponding oscillographic record is also erased .

www.f anox.com Rev.08 88/163


11. OSCILLOGRAPHIC RECORDS MENU
Press “Oscillo” option:

www.f anox.com Rev.08 89/163


The f ollowing window will be opened. On the lef t of the screen the oscillographic records saved in the relay will appear:

The oscillographic records number will depend on the relay.

www.f anox.com Rev.08 90/163


Select the wanted record to visualize it on the screen:

www.f anox.com Rev.08 91/163


It is possible to select the digital and analogue channels to visualize thanks to the options on the lef t (at the bottom) of the sc reen:

www.f anox.com Rev.08 92/163


11.1. How to save an oscillographic record
It is possible to save oscillographic records thanks to “Save Oscillos” key. When this option is pressed a window to save the selected oscillograpic record will
be opened:

In this window it is possible to select a name f or the f ile and the wanted location.

www.f anox.com Rev.08 93/163


The oscillographic record will be saved in COMTRADE f ormat. This universal f ormat can be opened with the majority of the oscillography visualizers in the
market:

www.f anox.com Rev.08 94/163


When the oscillographic record is saved, a message inf orming about it will appear on the screen:

www.f anox.com Rev.08 95/163


The option “Delete Oscillos” is not available because this action is carried out through “f ault reports” menu, this is, when a f ault report is deleted t he corresponding
oscillographic record is also deleted:

www.f anox.com Rev.08 96/163


12. LOAD DATA PROFILING (LDP) MENU
If relay of f ers Demand of current (this f eature will depend on the used relay), press “Demand” key:

www.f anox.com Rev.08 97/163


A window with the register will be opened:

www.f anox.com Rev.08 98/163


The available inf ormation is as f ollows:

• Date and time of each register.

• Maximum current.

• Maximum current at the end of the register.

• Phase A Current.

• Phase B Current.

• Phase C Current.

• Neutral Current.

www.f anox.com Rev.08 99/163


Thanks to the options on the lef t of the screen (at the bottom); the signals to visualize can be selected:

www.f anox.com Rev.08 100/163


If the registration of demand continues and this menu is open, press “Ref resh Demand” to update the inf ormation:

www.f anox.com Rev.08 101/163


12.1. How to save the demand
To save the demand, press “Save Demand” key. A window will be opened to choose the name and the desired location:

www.f anox.com Rev.08 102/163


If the action is f inished correctly, a message inf orming the demand has been saved will be shown on the screen:

www.f anox.com Rev.08 103/163


12.2. How to delete the demand
To delete the demand of the relay, press “Delete Demand” key. A question to conf irm the erasing will be shown:

If “ok” option is pressed the Demand will be erased in the relay and a message conf irming it will appear on the screen:

www.f anox.com Rev.08 104/163


www.f anox.com Rev.08 105/163
Once the demand is erased, all the registers will show the same date and currents equal to 0 amperes:

www.f anox.com Rev.08 106/163


13. SET DATE AND TIME MENU
It is possible to synchronize the relay using SICom program. To carry it out, press “Set Date/Time” option:

www.f anox.com Rev.08 107/163


A window with two options will appear. These options are:
• Current date and time
• Custom date and time.

www.f anox.com Rev.08 108/163


If f irst option is chosen the relay date and time will synchronize with the date and time of the PC:
A message conf irming the change will appear:

www.f anox.com Rev.08 109/163


Finally, it will be possible to check the date and time in the relay and SICom is the same as in the PC:

www.f anox.com Rev.08 110/163


If second option is selected the user can enter a wanted date (time is not available yet):

www.f anox.com Rev.08 111/163


The relay will be updated with this new value:

www.f anox.com Rev.08 112/163


14. COUNTERS MENU
If the relay is provided with counters it is possible to adjust the wanted value thanks to SICom program.
Press “Set counters” option:

www.f anox.com Rev.08 113/163


A window with the dif f erent counters will be shown:

www.f anox.com Rev.08 114/163


Put in each box the wanted value. Bef ore pressing “ok” yellow triangles will appear on the right of the boxes to alert the user the changes have not been sent:

www.f anox.com Rev.08 115/163


Af ter pressing “ok” option the new counters will be sent to the relay and a message inf orming about it will be displayed:

www.f anox.com Rev.08 116/163


15. COMMANDS MENU
If the relay has commands, it is possible to carry them out through SICom program:
Press “Execute Command” key:

www.f anox.com Rev.08 117/163


A window to choose between the dif f erent commands will be shown (these commands will depend on the used relay). Expand the box and all the options will
appear:

www.f anox.com Rev.08 118/163


Select the wanted command and press “ok” option to carry it out. A message inf orming about this action will appear on the scr een:

www.f anox.com Rev.08 119/163


16. CHANGE ACCESS MENU
The dif ferent access levels and their corresponding passwords can be changed pressing “Change Access” option:

www.f anox.com Rev.08 120/163


Pressing “Change Access” option a window with the def ault values will be displayed:

Level 2→ Password 2222 Level 4→ Password 4444


Level 3→ Password 3333 Level 5→ Password: 5555

www.f anox.com Rev.08 121/163


Insert the wanted password and associate that password to the wanted level:

www.f anox.com Rev.08 122/163


Af ter pressing “ok” option a message inf orming the new conf iguration has been sent will be shown on the screen:

www.f anox.com Rev.08 123/163


Please, take into account that the new password must have f our characters, if more or less characters are written, the box will stay in green colour and the “ok”
key will not be available:

In summary, the password has to be made up of 4 characters (numbers, letters or symbols). Less or more than 4 characters will not be accepted.

www.f anox.com Rev.08 124/163


17. SICOM OFFLINE – SETTING FILE
17.1. How to create a new settings file from offline mode
To create a new settings f ile in of f line mode f ollow the next steps:
1. Open SICOM sof tware
2. Press FILE / NEW / SICOM EQUIPMENT SETTINGS

www.f anox.com Rev.08 125/163


3. Select the relay to set and the corresponding FIRMWARE version and press OK:

 NOTE: Be caref ul when the Firmware version is selected, because depending on the version dif f erent settings are available.

www.f anox.com Rev.08 126/163


4. Select the complete model of the relay and press OK to access to the settings f ile:

 NOTE: It is very important to select the model correctly. Although in Of f line mode all the combinations are accepted, to send the f ile to the relay in Online
mode the correct model is mandatory.

www.f anox.com Rev.08 127/163


5. A window with all the settings will be open. It is possible to select the desire values to create the settings f ile. Each cha nge will be shown with a yellow
triangle on the right of the setting.

www.f anox.com Rev.08 128/163


6. Af ter all the settings are selected press SAVE AS to save the settings f ile. This settings f ile will be prepared to be sent t o the relay in online mode. It is
possible to select where the f ile will be saved and the name of the f ile can be chosen:

NOTE: If the selected model is not correct, the option SAVE AS will not be available.

www.f anox.com Rev.08 129/163


7. Once the action is f inished a message, conf irming that the f ile is saved, will be appeared on the screen:

www.f anox.com Rev.08 130/163


17.2. How to open a settings file from offline mode

17.2.1. Old settings file (previously saved before SICOM version 1.0.0.46)
If settings f ile was saved bef ore 1.0.0.46 SICOM version:

1. Open SICOM sof tware, Press FILE / OPEN or double click directly on the saved settings f ile (both options are valid).

www.f anox.com Rev.08 131/163


2. Select the corresponding settings f ile and press Open:

www.f anox.com Rev.08 132/163


3. Due to the f ile is old, the SICOM recognizes the relay but it is necessary to choose the Firmware version. Once this version is selected press OK:

www.f anox.com Rev.08 133/163


4. The f ile will be open. It is possible to change the settings if it is necessary. To save the new f ile f ollow the steps explai ned in “1.1. How to create a new
settings f ile” paragraph

www.f anox.com Rev.08 134/163


17.2.2. New settings file (previously saved from SICOM version 1.0.0.46 onwards)
If settings f ile was saved f rom 1.0.0.46 SICOM version onwards the steps to open a settings f ile are explained next:

1. Open SICOM sof tware and press FILE / OPEN or double click directly on the saved settings f ile (both options are valid):

www.f anox.com Rev.08 135/163


2. Select the settings f ile (previously saved) and press Open:

www.f anox.com Rev.08 136/163


3. The f ile will be open. It is possible to change the settings if it is necessary. To save the new f ile f ollow the steps explai ned in “1.1. How to create a new
settings f ile” paragraph.

www.f anox.com Rev.08 137/163


17.3. How to send a settings file
Once the relay is connected to the PC it is possible to send the settings f ile previously saved I of f line mode. To send this settings f ile to the relay f ollow the next
steps:

1. Connect the relay to the PC and start the session. Press “Settings” to access to the corresponding window:

www.f anox.com Rev.08 138/163


2. Press “Open Settings” option:

www.f anox.com Rev.08 139/163


3. Choose the corresponding settings f ile (previously saved in online or of f line mode) and press “Open”:

www.f anox.com Rev.08 140/163


4. If the settings f ile is correct it will be open an pressing “Send Settings” option the settings f ile will be sent to the relay:

www.f anox.com Rev.08 141/163


5. If all the process is correct a message inf orming about it will be shown on the screen:

www.f anox.com Rev.08 142/163


6. If settings f ile does not correspond to the connected relay, when “Open settings” is pressed, the f ollowing window will be shown:

www.f anox.com Rev.08 143/163


18. SICOM OFFLINE – CONFIGURATION FILE
18.1. How to create a new configuration file from offline mode
To create a new conf iguration f ile in of f line mode f ollow the next steps:
1. Open SICOM sof tware
2. Press FILE / NEW / SICOM EQUIPMENT CONFIGURATION

www.f anox.com Rev.08 144/163


3. Select the relay to conf igure and the corresponding FIRMWARE version and press OK:

 NOTE: Be caref ul when the Firmware version is selected, because depending on the version dif f erent conf iguration is available.

www.f anox.com Rev.08 145/163


4. Select the complete model of the relay and press OK to access to the settings f ile:

 NOTE: It is very important to select the model correctly. Although in Of f line mode all the combinations are accepted, to send the f ile to the relay in Online
mode the correct model is mandatory.

www.f anox.com Rev.08 146/163


5. A window with the dif f erent options to configure will be open:

www.f anox.com Rev.08 147/163


6. When the options on the lef t are open, it is discovered the conf iguration is empty.

www.f anox.com Rev.08 148/163


7. Select the desired conf iguration and a message, reminding the user that the conf iguration is not saved, will be shown:

www.f anox.com Rev.08 149/163


8. Press “Save As” option to save the conf iguration f ile. This f ile will be prepared to be sent to the relay in online mode. It is possible to select where the
f ile will be saved and the name of the f ile can be chosen:

www.f anox.com Rev.08 150/163


9. Once the action is f inished a message, conf irming that the f ile is saved correctly, will be appeared on the screen:

www.f anox.com Rev.08 151/163


18.2. How to open a configuration file from offline mode

18.2.1. Old configuration file (previously saved before SICOM version 1.0.0.46)
The f irst important thing is to know that old conf iguration f iles cannot be open with SICOM Of f line mode. To open a conf iguration f ile, it is necessary to create
one with this last SICOM version (1.0.0.46).

www.f anox.com Rev.08 152/163


18.2.2. New configuration file (previously saved from SICOM version 1.0.0.46 onwards)
Once a conf iguration f ile is created (f rom online or o f f line f ile), f ollow next steps to open it f rom of fline mode:

1. Open SICOM sof tware and press FILE / OPEN or double click directly on the saved settings f ile (both options are valid):

www.f anox.com Rev.08 153/163


2. Select the conf iguration f ile and take care of selecting “SICOM Equip ment Conf iguration (*.sec)” at the bottom (right side) of the screen (by def ault “SICOM
Equipment Settings (*.ses)” f ile” appears) and press “Open” option:

www.f anox.com Rev.08 154/163


3. The f ile will be open. It is possible to change the conf iguration if it is necessary. To save the new f ile f ollow the steps explained in “2.1. How to create a
new conf iguration f ile” paragraph.

www.f anox.com Rev.08 155/163


18.2.3. How to send a configuration file to the relay
Once the relay is connected to the PC it is possible to send the conf iguration f ile previously saved. To send this conf iguration f ile to the relay f ollow the next
steps:
1. Connect the relay to the PC and start the session. Press “Conf iguration” to access to the corresponding window:

www.f anox.com Rev.08 156/163


2. Press “Open conf iguration” option.

www.f anox.com Rev.08 157/163


3. Choose the corresponding conf iguratio n f ile (previously saved in online or of fline mode) and press “Open”:

www.f anox.com Rev.08 158/163


4. If the f ile is correct, a message inf orming about it, will be shown on the screen:

www.f anox.com Rev.08 159/163


5. If af ter pressing open conf iguration the selected conf iguration f ile is not correct, a message, inf orming about it, will be shown. This message inf orms that the
selected f ile does not correspond to the connected relay:

www.f anox.com Rev.08 160/163


6. Taking into account the correct conf iguration f ile, press “Send conf iguration” to send it to the relay. Bef ore sending it, a message inf orming about it will
appear at the bottom of the screen:

www.f anox.com Rev.08 161/163


7. If everything works successf ully, a message inf orming about this f act will be shown: