DOC.NO. : HI-16-2024-B (Rev.

3)

 CUSTOMER : LARSEN & TOUBRO ECC


 PROJECT : WDFC Phase-II, EMP-16 Project (Makarpura JNPT Section)

GUARANTEED TECHNICAL
PARTICULAR (GTP)

OF

220(245)kV 50kA

Gas Insulated Switchgear

27 April, 2017

DATE: DESCRIPTION REVISION

28 Aug,2017 REVISED CT SPECIFICATION 3


15 May,2017 REVISED AS PER CUSTOMER COMMENTS DATED 12 MAY,2017 2
03 May,2017 REVISED AS PER CUSTOMER COMMENTS DATED 03 MAY,2017 1
27 April,2017 FIRST SUBMISSION FOR APPROVAL 0
INDEX
Sl.No. DESCRIPTION PAGE NO.
1 GIS………………………………………………………………………………………….
……..………….3

a General Data………………………………………………………………..
……..………….3

2 Configuration…………………………………………………………………………
……..………….3

3 Service Conditions…………………………………………………………….
……..………….3

4 Design Conditions…………………………………………………….
……..………….4

4.A Enclosure……………………………………………………………………….
……..………….4

4.B Support Structure……………………………………………………….


……..………….5

4.C Grounding………………………………………………………. ……..………….5

5 System Parameters……………………………………………….……..………….5

6 Delivery conditions……………………………………………….
……..………….6

7 Bus Bar …………………………………………………….. ……..…………6

8 SF6 Gas…………………………………………………………. ……..………….7

9 Pressure ……...………………………………………………………….
……..………….7

10 Circuit Breaker…………………………………………………………..
……..………….9

11 Disconnectors…………………………………………………………
……..…………12

12 Grounding Switch

12.a Maintenance Grounding Switch……………………………. ……..…………14

12.b Fast Acting Grounding Switch………………………………………..


……..…………14

13 Current Transformers…………………………………………………..…………16

14 Voltage Transformers…………………………………………………
……..………..20

15 Enclosed Surge Arrester…………………………………………………………..


……..………..21

16 Local Control Cubicle………………………………………………………..


……..………..23

17 GIS to Line Connection………………………………………………………..


……..………..23

18 GIS to TRF Connection………………………………………………………..


……..………..23

19 Cable Sealing End………………………………………………………..


……..………..23

20 Maintenance………………………………………………………..
……..………..24
Page 3 .

Sl No Particulars Data/Value Reference Clause

1 GIS
a General Data
i Name of manufacturer (OEM) Hyosung T&D India General Detail

ii Country of Origin India General Detail

iii Delivery from (location) Khed City, Pune General Detail


iv Model Designation HSG-305B As per Manufacturer's Type Test
Type tested at: KERI and CESI
v Name of Laboratory www.keri.re.kr As per Manufacturer's Type Test
E-mail Address of Laboratory www.cesi.it
Chapter 21 , Cl. 21.1.1 ,Page 283,
vi Installation (indoor or outdoor) Indoor
Part 3 of CA
IEC 62271-203
IEC 62271-100 Chapter 21 , Cl. 21.2 ,Page 284,
IEC 62271-102 Part 3 of CA
vii Standards applicable
IEC 62271-1 Chapter 22 , Cl. 22.3.6.1 ,Page 360
IEC 60099-4 Part 3 of CA
IEC 62271-209
viii No. of Phases 3 phases As per SLD
Chapter 21 , Cl. 21.1.1 ,Page 283,
ix Single or Three Phase design Sigle phase design
Part 3 of CA

As per GIS Layout Drawing


2 Configuration

i Number of Feeder bays (MSETCL) 2 As per Bidder's SLD

ii Number of Scott transformer bays (DFCCIL) 2 As per Bidder's SLD

iii Number of Bus coupler bay 1 As per Bidder's SLD

iv Number of Traction transformer bays (C/R) 2 As per Bidder's SLD

Through Cable Through Cable


v GIS to transformer connection
(Not in GIS manufacturer scope) (In Scope of L&T)

Through Cable Through Cable


vi GIS to Feeder connection
(Not in GIS manufacturer scope) (In Scope of L&T)

vii Number of Voltage Transformer 28 As per Bidder's SLD

viii Number of Surge Arrester 6 As per Bidder's SLD

ix Future extension possibility YES As per Bidder's SLD

3 Service Conditions
Chapter 21 , Cl. 21.4.36.a ,Page 290,
i Ambient Air Temp range. in Deg. C 50 deg C
Part 3 of CA
ii Max Temp. in Deg. C 50 deg C As per IEC 62271-230 ,Table 1,Page 10

iii Min Temp. in Deg. C -5 deg C As per IEC 62271-230 ,Table 1,Page 10

iv Daily Average Temp. in Deg. C N/A N/A


Chapter 21 , Cl. 21.1.1 ,Page 283,
v Solar Radiation W/sq mtr N/A (Indoor Installation)
Part 3 of CA
Chapter 21 , Cl. 21.4.36 ,Page 290,
vi Altitude above MSL, in mtr < 1000
Part 3 of CA
As per IEC 60815, Table-2 ,Page 13,
vii Pollution class III (as Bushing CD is 25 mm/kV)
Part 3 of CA
Chapter 21 , Cl. 21.15.2 ,Page 309,
viii Creepage Distance in mm/kV 25 mm/kV (for HV test bushing)
Part 3 of CA
Chapter 21 , Cl. 21.4.36 ,Page 290,
ix Relative humidity 95%
Part 3 of CA
x Condensation N/A N/A

xi Vibration Level N/A N/A

xii Noise Level As per NEMA As per SG 4-2000,Table 4-2,Page 26,

xiii Induced Electromagnetic Disturbance, in kV N/A N/A

Guaranteed Technical Particulars_220kV WDFC Phase-II EMP-16 Project (Makarpura JNPT Section)
Page 4 .

xiv Seismic conditions

a Vertical (Max) 0.5g As per Manufacturer's Seismic analysis

b Horizontal (Max) 0.5g As per Manufacturer's Seismic analysis

4 Design Conditions
4.A Enclosure
Datasheet-A1, Sl.No. 3.3 A , Page 376,
i Material Aluminum Alloy
Part 3 of CA

KS-D 6008/ENAC-42100 Chapter 22 , Cl. 22.2.3.8 ,Page 340,


ii Code of pressure vessel
or Equivalent Part 3 of CA

KS-D 6008/ENAC-42100 Chapter 22 , Cl. 22.2.3.8 ,Page 340,


iii Material grade & applicable standard
or Equivalent Part 3 of CA

iv Design temp. in Deg. C 80⁰ C As per Manufacturer's Type test Report

Enclosure Outdia(Busbar) : 406mm


v Outside diameter in mm As per Manufacturer's Type test Report
Conductor Outdia(Busbar) : 100mm

vi Wall Thickness, in mm 10 mm As per Manufacturer's Type test Report

vii Painting Shade & Thickness

RAL:7032
Other detail as per the submitted
a External As per Manufacturer's Standard Practice
document of " Standard Painting Sysytem"
(Doc.No. HI-16-0024-F_R0)

RAL:7032
Other detail as per the submitted
b Internal As per Manufacturer's Standard Practice
document of " Standard Painting Sysytem"
(Doc.No. HI-16-0024-F_R0)

Datasheet-A1, Sl.No. 3.3 B , Page 376 &


viii Degree of Protection IP 4X As per Manufacturer's Type test report,
Part 3 of CA
ix Inductance in mH/m 0.28 mH/m Manufacturer's Intellectual data

x Capacitance in pF/m 44.41 pF/m Manufacturer's Intellectual data

8.15 µΩ/m (Enclosure)


xi Resistance in Ohm/m Manufacturer's Intellectual data
10.23 µΩ/m (Conductor)

xii Expansion Bellow


Chapter 21 , Cl. 21.5.1 ,Page 291,
a Material Stainless Steel
Part 3 of CA

Min allowable adjustable displacement


b ±10mm As per Manufacturer's Standard Practice
Longitudinal Transverse

xiii Sealing system

a Type O-ring and Packing As per Manufacturer's Standard Practice

xiv Estimated life of GIS in years 30 years Manufacturer's Intellectual data

xv Barrier
Chapter 21 , Cl. 21.4.3 ,Page 286,
a Material Epoxy resin
Part 3 of CA
b Dielectric strength Same as GIS N/A

Max. Temp. Rise of enclosure


xvi
(as per IEC 62271-1,Table 3,Page39)

a Accessible Parts 30 Deg.C As per IEC 62271-1 , Table 3, Page 39

b Non-accessible Parts 40 Deg.C As per IEC 62271-1 , Table 3, Page 39

Guaranteed Technical Particulars_220kV WDFC Phase-II EMP-16 Project (Makarpura JNPT Section)
Page 5 .

4.B Support Structure

i Material Hot Dip Galvanized Steel As per Manufacturer's Standard Practice

ii Minimum thickness of galvanizing 80µm and above As per Standard Painting System

iii Foundation Channels/ Anchor bolts Anchor bolts As per Manufacturer's Standard Practice

4.C Grounding

i Grounding Material Painted or Plated copper As per Manufacturer's Standard Practice

ii Grounding of complete GIS YES As per Manufacturer's Standard Practice

iii Grounding of individual compartment YES As per Manufacturer's Standard Practice

N/A (Ring Type Insulator is applied with


iv Grounding at flange joints As per Manufacturer's Standard Practice
Aluminum outer and epoxy in centre)

5 System Parameters
Datasheet-A1, Sl.No. 1.2 , Page 376,
i Highest System voltage in kV 245 kV
Part 3 of CA
Datasheet-A1, Sl.No 1.1 , Page 376,
ii Rated voltage of System in kV 220 kV
Part 3 of CA

iii Rated voltage of Equipment in kV 300 kV As per Manufacturer's Type test Report

Rated Insulation level Phase to Earth and


iv
between Phases

One Min Power Frequency withstand voltage As per IEC 62271-203, Table 2 ,
a 460 kV
KVrms Page 14

b Switching Impulse withstand voltage, kVp

- Phase to Earth NA NA

- Between Phases NA NA

As per IEC 62271-203, Table 2 ,


c Lightning Impulse withstand voltage, kVp 1050 kVp
Page 14

Chapter 21 , Cl. 21.10.8.3 ,Page 299,


v Rated Frequency 50 Hz
Part 3 of CA
2000 A : As per customer's SLD
vi Rated current in Amp {2000} 3150 A 3150 A : As per Manufacturer's Type test
report
2000 A : As per customer's SLD
vii Rated current at 50 ℃ (equipment) in Amp {2000} 3150 A 3150 A : As per Manufacturer's Type test
report
2000 A : As per customer's SLD
viii Rated current at 50 ℃ (bus bar) in Amp {2000} 3150 A 3150 A : As per Manufacturer's Type test
report
ix Rated Short circuit withstand current kArms 50 kA As per customer's SLD

a Duration in sec 3s As per customer's SLD

As per IEC 62271-1, Cl 4.6 ,


b Peak, kAp 125 kAp
Page 40

Internal Fault withstand time without burn through As per IEC 62271-203, Table 4,
x As per table 4 (IEC 62271-203)
in ms Page 22

Enclosure withstand time for an internal fault in


xi 0.5 As per Manufacturer's Type test Report
sec. (Burn through is acceptable)

Guaranteed Technical Particulars_220kV WDFC Phase-II EMP-16 Project (Makarpura JNPT Section)
Page 6 .

xii Estimated total energy loss at

As per Manufacturer's Design Development


a 100% of rated capacity As per Design Criteria
Data

As per Manufacturer's Design Development


b 75% of rated capacity As per Design Criteria
Data

As per Manufacturer's Design Development


c 50% of rated capacity As per Design Criteria
Data

As per Manufacturer's Design Development


d 25% of rated capacity As per Design Criteria
Data

xiii Phase labeling B,Y,R As per Manufacturer's Standard Practice

Auxiliary supply (AC Voltage, Frequency; DC


xiv
voltage)

Chapter 21 , Cl. 21.10.8.3.v ,Page 300, Cl.


21.11.2.1.,Page 301,Cl. 21.12.1.,Page 303
a - Operation 220Vdc
& Cl. 21.13.2.,Page 304
Part 3 of CA

Chapter 21 , Cl. 21.10.8.3.v ,Page 300, Cl.


21.11.2.1.,Page 301,Cl. 21.12.1.,Page 303
b - Control 220Vdc
& Cl. 21.13.2.,Page 304
Part 3 of CA

Chapter 21 , Cl. 21.4.31,Page 290,


c - Illumination & heater 240Vac
Part 3 of CA
6 Delivery conditions

a Bays fully assembled at works CB module & Bus bar with bus DS As per Manufacturer's Standard Practice

(5000mm x 2500mm x 4000mm )


b Dimensions of longest section for transportation As per Manufacturer's Standard Design
(L x B x H) (Approx.)

c Weight of heaviest package 7000 kg (Approx.) As per Manufacturer's Standard Design

d Pressure of N2 gas during transportation 0.03 Mpa.G (Minimum) As per Manufacturer's Standard Practice

SF6 gas monitoring system provided


e N/A (N2 Gas will be filled) As per Manufacturer's Standard Practice
during transportation

xvi Method of interlocking Electrical As per Manufacturer's Standard Design

7 Bus Bar - -

i Configuration (Single / Double) Double Bus (As per Single Line Diagram) As per Bidder's SLD

ii No of Phases 1x3phase (As per Single Line Diagram) As per Bidder's SLD

As per Manufacturer's Standard Practice &


iii Material Aluminium Alloy Chapter 21, Cl. 21.4.8, Page 287
Part 3 of CA

Enclosure Outdia : 406mm


iv Size As per Manufacturer's Standard Design
Conductor Outdia : 100mm

2000 A : As per customer SLD


v Rating {2000} 3150 A 3150 A : As per Manufacturer's Type test
report
vi Current density adopted 0.65A/mm2 Manufacturer's Intellectual data
2
vii Current density as per type test report 0.65A/mm Manufacturer's Intellectual data

viii Short time current withstand rating in kA 50 kA As per customer's SLD

ix Duration 3s As per customer's SLD

Guaranteed Technical Particulars_220kV WDFC Phase-II EMP-16 Project (Makarpura JNPT Section)
Page 7 .

x Resistance per phase 10.23 x 10-6 Ω/m Manufacturer's Intellectual data

xi Surge impedance 450 ohm Manufacturer's Intellectual data

xii SF6 immersed insulator - -


Chapter 21 , Cl. 21.4.3 ,Page 286,
a Material Epoxy Resin
Part 3 of CA
b Dielectric Strength 460 kVrms, 1 min Same as GIS
Chapter 21 , Cl. 21.4.3 ,Page 286,
xiii Maximum Partial Discharges measured at HSV Less than 5 pC
Part 3 of CA
8 SF6 Gas
i Applicable standard IEC 60376 IEC 60376

Quantity of SF6 Gas of complete GIS at


ii As per GIS Gas System Diagram As per GIS Gas System Diagram
filling pressure, in kg

Quantity of SF6 Gas of largest compartment


iii As per GIS Gas System Diagram As per GIS Gas System Diagram
GIS at filling pressure, in kg

iv Nos of Gas compartments As per GIS Gas System Diagram As per GIS Gas System Diagram
Quantity of SF6 Gas of individual compartment
As per GIS Gas System Diagram As per GIS Gas System Diagram
v GIS
at filling pressrue, in kg
vi Maximum permissible dew point, in Deg.C -5 ℃ Manufacturer's Intellectual data

vii Composition of Gas

As per IEC 60376, Table 1,


a SF6 > 99.90 % by weight ≥ 99.90
Page 15

As per IEC 60376, Table 1,


b Air < 500 ppm by weight (0.25 vol.-%) ≤ 500
Page 15

As per IEC 60376, Table 1,


c CF4 < 500 ppm by weight (0.1 vol.-%) ≤ 500
Page 15

As per IEC 60376, Table 1,


d H2O < 15 ppm by weight (0.012 vol.-%) ≤ 15
Page 15

As per IEC 60376, Table 1,


e Mineral oil < 10 ppm by weight ≤ 10
Page 15

As per IEC 60376, Table 1,


f Acidity, in terms of HF < 0.3 ppm by weight ≤ 0.3
Page 15

Hydrolysable fluorides, As per IEC 60376, Table 1,


g ≤1
In terms of HF < 1 ppm by weight Page 15

9 Pressure
i Design pressure
Manufacturer's Intellectual data
a Circuit breaker (Mpa.G) 0.90 (As per Manufacturer's Type Test)

Manufacturer's Intellectual data


b Other compartments (Mpa.G) 0.72 (As per Manufacturer's Type Test)

ii Rated filling pressure


Manufacturer's Intellectual data
a Circuit breaker (Mpa.G) 0.71 (As per GIS Gas System Diagram) (As per Manufacturer's Type Test)

Manufacturer's Intellectual data


b Other compartments (Mpa.G) 0.55 (As per GIS Gas System Diagram) (As per Manufacturer's Type Test)

iii Type tested pressure


Manufacturer's Intellectual data
a Circuit breaker (Mpa.G) 4.50 (As per Manufacturer's Type Test)

Manufacturer's Intellectual data


b Other compartments(Mpa.G) 3.60 (As per Manufacturer's Type Test)

Guaranteed Technical Particulars_220kV WDFC Phase-II EMP-16 Project (Makarpura JNPT Section)
Page 8 .

iv Routine test pressure


Chapter 21 , Cl. 21.8 ,Page 292,
a Circuit breaker (Mpa.G) 1.90
Part 3 of CA
Chapter 21 , Cl. 21.8 ,Page 292,
b Other compartments (Mpa.G) 1.50 (DS,ES, etc)/ 1.13 (GIB)
Part 3 of CA
v Operating pressure of PRD

a Circuit breaker (Mpa.G) 1.20 Manufacturer's Intellectual data

b Other compartments (Mpa.G) 1.20 Manufacturer's Intellectual data

vi Alarm Pressure

a Circuit breaker (Mpa.G) (As per Gas System Diagram) (As per Gas System Diagram)

i First Stage Alarm 0.69 Mpa.G (As per Gas System Diagram)

ii Second Stage Alarm 0.67 Mpa.G (As per Gas System Diagram)

iii Third Stage Alarm 0.65 Mpa.G (As per Gas System Diagram)

b Other compartments (Mpa.G) (As per Gas System Diagram) (As per Gas System Diagram)

i First Stage Alarm 0.52 Mpa.G (As per Gas System Diagram)

ii Second Stage Alarm 0.50 Mpa.G (As per Gas System Diagram)
CB lock out Pressure (Mpa.G)
c {SF6 gas pressure at which CB operate 0.65 (As per Gas System Diagram)
satisfactorily}
d Overpressure signaling N/A N/A
Chapter 21 , Cl. 21.4.10 ,Page 287,
vii Maximum SF6 Gas leakage rate, in % per year Less than 0.5%
Part 3 of CA

Guaranteed Technical Particulars_220kV WDFC Phase-II EMP-16 Project (Makarpura JNPT Section)
Page 9 .

10 Circuit Breaker
i Applicable standard IEC 62271-100 IEC 62271-100

ii Type HCSP-305B (Puffer Type) As per Manufacturer's Type test Report

iii Operating Mechanism type Single phase ,Spring charged by motor As per Manufacturer's Standard Design

iv No. of phases 3 phases As per customer's SLD

2000 A : As per customer's SLD


v Rated current in Amp {2000} 3150 A 3150 A : As per Manufacturer's Type test
report
Chapter 21 , Cl. 21.10.2 ,Page 293,
vi Mechanical Endurance class M2
Part 3 of CA
vii Electrical Endurance class NA NA
Chapter 21 , Cl. 21.10.2 ,Page 293,
viii Restrike probability class C2
Part 3 of CA
ix Rated SC breaking current 50 kA As per customer's SLD

x Rated SC breaking current - single phase test 50 kA As per customer's SLD

As per IEC 62271-100, Table-9,


xi Rated Line charging breaking current 200 A
Page 66

As per IEC 62271-100, Table-9,


xii Rated Cable charging breaking current 315 A
Page 66

xiii Capacitor bank switching capability, BC1 BC2 N/A N/A

xiv Inductive current N/A N/A

As per IEC 62271-110,


Cl. 6.115.2
xv Reactive current Max. 315A / Min. 100A
Cl. 6.115.3
Page 17

As per IEC 62271-100, Cl.4.106


xvi Out of phase making & breaking current 12.5 kA
Page 65

As per IEC 62271-100, Cl.A.4.1


xvii Rated short line fault current As per IEC 62271-100
Page 265

Transient Recovery Voltage for Terminal Faults As per IEC 62271-100, Table-5,
xviii 446kV
(Table-5, Page 59 IEC 62271-100) Page 59

xix TRV characteristic As per IEC 62271-100 As per IEC 62271-100


Chapter 21 , Cl. 21.10.8.3.k ,Page 299,
xx First Pole to Clear factor 1.3
Part 3 of CA

xxi No. of interrupters per phase 1 As per Manufacturer's Standard Design

xxii Type of arcing contacts Finger As per Manufacturer's Standard Design

xxiii Material of main contact Copper and Arc metal As per Manufacturer's Standard Design

xxiv Material of Arcing contacts Copper and Arc metal As per Manufacturer's Standard Design

xxv Filter material Adsorbent As per Manufacturer's Standard Design

xxvi Timings of operations

- Opening at nominal control voltage <34ms Manufacturer's Intellectual Data


a
- Opening at minimum control voltage <40ms Manufacturer's Intellectual Data

b Closing time at nominal control voltage <80ms Manufacturer's Intellectual Data

Maximum pole discrepancy time As per IEC 62271-100, Cl.5.101


xxvii 3.3 ms/ 5 ms
Tripping / Closing Page 76

Guaranteed Technical Particulars_220kV WDFC Phase-II EMP-16 Project (Makarpura JNPT Section)
Page 10 .

Chapter 21 , Cl. 21.10.8.3.n,Page 299,


xxviii Rated operating duty cycle O-0.3S-CO-3min-CO
Part 3 of CA
xxix Tripping Coils
Chapter 21 , Cl. 21.10.6.2.2,Page 296,
a - No of coils 2
Part 3 of CA
Chapter 21 , Cl. 21.10.8.3.v ,Page 300, Cl.
21.11.2.1.,Page 301,Cl. 21.12.1.,Page 303
b - Rated Volage 220 Vdc
& Cl. 21.13.2.,Page 304
Part 3 of CA
Chapter 21 , Cl. 21.10.6.2.5,Page 296,
c - Operating range of DC Voltage 70%-110%
Part 3 of CA
d - Rated Current Less than 10 A Manufacturer's Intellectual data

e - Rated Watts 372.9 Watts Manufacturer's Intellectual data

f - Resistance 123.6± 5% ohm Manufacturer's Intellectual data

xxx Closing Coil


Chapter 21 , Cl. 21.10.6.2.5,Page 296,
a - No of coils 1
Part 3 of CA
Chapter 21 , Cl. 21.10.8.3.v ,Page 300, Cl.
21.11.2.1.,Page 301,Cl. 21.12.1.,Page 303
b - Rated Volage 220 Vdc
& Cl. 21.13.2.,Page 304
Part 3 of CA
Chapter 21 , Cl. 21.10.6.2.5,Page 296,
c - Operating range of DC Voltage 85%-110%
Part 3 of CA
d - Rated Current Less than 10 A Manufacturer's Intellectual data

e - Rated Watts 342.7 Watts Manufacturer's Intellectual data

f - Resistance 141.2 ohm Manufacturer's Intellectual data

xxxi Spring Charging Motor Spring charged by DC motor(220kV) N/A

Chapter 21 , Cl. 21.10.8.3.v ,Page 300, Cl.


21.11.2.1.,Page 301,Cl. 21.12.1.,Page 303
a - Rated Volage 220 Vdc
& Cl. 21.13.2.,Page 304
Part 3 of CA

b - Rated Current 4A Manufacturer's Intellectual data

c - Rated Watts 600 W Manufacturer's Intellectual data

xxxii Spring charging time at rated Aux supply Less than 10 s Manufacturer's Intellectual data

xxxiii Spring charging time at min Aux supply Less than 10 s Manufacturer's Intellectual data

xxxiv Maintenance required after nos. of operation at

As per Manufacturer's Design Development


a No load Every 2,000 operation
Data

As per Manufacturer's Design Development


b Rated current Every 2,000 operation
Data

As per Manufacturer's Design Development


c 25% of rated SC current Every 100 operation
Data

As per Manufacturer's Design Development


d 50% of rated SC current Every 30 operation
Data

As per Manufacturer's Design Development


e Rated SC current Every 10 operation
Data

No of operations after switching off of motor Aux. Chapter 21 , Cl. 21.10.6.3.3,Page 297,
f O-C-O
supply Part 3 of CA

xxxv Provision of antipumping YES N/A

xxxvi Provision of Manual trip YES N/A

xxxvii Electrical interlocking YES N/A

xxxviii Padlocking YES N/A

Guaranteed Technical Particulars_220kV WDFC Phase-II EMP-16 Project (Makarpura JNPT Section)
Page 11 .

Permissible Temp. rise of CB contacts


Ambient temp (+10 Deg.C to +40 Deg.C) as per As per IEC 62271-1, Table 3,
xxxix 65 Deg. C {Table-3 IEC 62271-1}
IEC 62271-1 (Cl. 6.5.4 - Ambient Air Temp.,Page Page 70
70 )

As per IEC 62271-100, Cl. 9.101.2,


xl Short circuit breaking current time constant 45 ms
Page 46

As per IEC 62271-100, Cl. 6.106.5,


xli DC Component 43%
Page 153

xlii Minimum dead time for

As per IEC 62271-100, Cl. 3.7.140


a Three Phase Auto-reclosing 300 ms
Page 39

As per IEC 62271-100, Cl. 3.7.140


b Single Phase Auto-reclosing 300 ms
Page 39

As per Manufacturer's Design Development


xliii Type of Indicator & operation counter Mechanical
Data

Guaranteed Technical Particulars_220kV WDFC Phase-II EMP-16 Project (Makarpura JNPT Section)
Page 12 .

11 DISCONNECTORS
i Applicable standard IEC 62271-102 IEC 62271-102

ii Type HDMO-305C/D As per Manufacturer's Type test Report

iii Rated current in Amp for


2000 A : As per customer's SLD
a - Bus disconnector {2000} 3150 A 3150 A : As per Manufacturer's Type test
report
2000 A : As per customer's SLD
b - Line disconnector {2000} 3150 A 3150 A : As per Manufacturer's Type test
report
2000 A : As per customer's SLD
c - Transformer disconnector {2000} 3150 A 3150 A : As per Manufacturer's Type test
report
2000 A : As per customer's SLD
d - Voltage Transformer disconnector {2000} 3150 A 3150 A : As per Manufacturer's Type test
report

Maximum Current that can be safely


iv
interrupted by the isolator (Amp).

- Inductive N/A N/A

- Capacitive N/A N/A

Rate Short time withstand Current in kA, for 3


v 50 kA As per customer's SLD
sec

As per IEC 62271-1, Cl 4.6 ,


vi Rated peak short time Current, kAp 125 kAp
Page 40

As per IEC 62271-102, Table F.2 ,


vii Rated bus charging current, in Amp 0.25A
Page 88

viii Type of contacts Bal Seal As per Manufacturer's Standard Design

ix Material of contacts Copper with silver plated As per Manufacturer's Standard Design

Current Density at minimum cross section 110-Aluminium


x Manufacturer's Intellectual data
(A/sq mm) 220-Copper

Rated lightning impulse withstand voltage across As per IEC 62271-203, Table 2 ,
xi 1050(+170) kVp
the open gap, kVp Page 14

As per IEC 62271-203, Table 2 ,


xii Rated Power Freq withstand voltage ,kVrms 460kV
Page 14

Rated Power Freq withstand voltage across the As per IEC 62271-203, Table 3 ,
xiii 595 kV
open gap, kVrms Page 14

xiv Mechanical Endurance class M2 As per Manufacturer's Type test Report

xv Type of Operating Mechanism Motor drive and manual As per Manufacturer's Standard Design

xvi Operating Motor details

a - Type Permanent magnet motor As per Manufacturer's Standard Design

Chapter 21 , Cl. 21.10.8.3.v ,Page 300, Cl.


21.11.2.1.,Page 301,Cl. 21.12.1.,Page 303
b - Rated Voltage 220 Vdc
& Cl. 21.13.2.,Page 304
Part 3 of CA

c - Rated Current Less than 3A Manufacturer's Intellectual data

d - Rated Watts 260 W Manufacturer's Intellectual data

xvii Operating Time

Guaranteed Technical Particulars_220kV WDFC Phase-II EMP-16 Project (Makarpura JNPT Section)
Page 13 .

a - Closing Less than 3 s Manufacturer's Intellectual data

b - Opening Less than 3 s Manufacturer's Intellectual data

xviii Type of Indicator Mechanical As per Manufacturer's Standard Design

Guaranteed Technical Particulars_220kV WDFC Phase-II EMP-16 Project (Makarpura JNPT Section)
Page 14 .

12 Grounding Switch
12.a Maintenance Grounding Switch
i Applicable standard IEC 62271-102 IEC 62271-102

ii Type HEMO-305B As per Manufacturer's Type test Report

Rate Short time withstand Current in kA, for 3


iii 50 kA As per customer's SLD
sec

As per IEC 62271-1, Cl 4.6 ,


iv Rated peak short time Current, kAp 125 kAp
Page 40

Rated lightning impulse withstand voltage across As per IEC 62271-203, Table 2 ,
v 1050(+170) kVp
the open gap, kVp Page 14

As per IEC 62271-203, Table 2 ,


vi Rated Power Freq withstand voltage , kVrms 460 kV
Page 14

vii Type of Operating Mechanism Motor drive and manual As per Manufacturer's Standard Design

viii Operating Motor details

a - Type Permanent magnet motor As per Manufacturer's Standard Design

Chapter 21 , Cl. 21.10.8.3.v ,Page 300, Cl.


21.11.2.1.,Page 301,Cl. 21.12.1.,Page 303
b - Rated Voltage 220 Vdc
& Cl. 21.13.2.,Page 304
Part 3 of CA

c - Rated Current Less than 3A Manufacturer's Intellectual data

d - Rated Watts 260 W Manufacturer's Intellectual data

ix Operating Time
a - Closing Less than 3 s Manufacturer's Intellectual data

b - Opening Less than 3 s Manufacturer's Intellectual data

x Type of Indicator Mechanical As per Manufacturer's Standard Design

12.b Fast Acting Grounding Switch


i Applicable standard IEC 62271-102 IEC 62271-102

ii Type HEMS-305B As per Manufacturer's Type test Report

Rate Short time withstand Current in kA, for 3


iii 50 kA As per customer's SLD
sec

As per IEC 62271-1, Cl 4.6 ,


iv Rated peak short time Current, kAp 125 kAp
Page 40

Rated induced current switching capability Electrostatical: 10 A Electrostatical: 10 A


v
Rated capacitive current switching capability Electromagnetical : 160 A Electromagnetical : 160 A

Rated lightning impulse withstand voltage across As per IEC 62271-203, Table 2 ,
vi 1050(+170) kVp
the open gap, kVp Page 14

As per IEC 62271-203, Table 2 ,


vii Rated Power Freq withstand voltage,kVrms 460 kV
Page 14

As per IEC 62271-102, Cl 3.4.105.2 ,


viii Electrical Endurance class E1
Page 12

ix Type of Operating Mechanism Motor drive spring charged and manual As per Manufacturer's Standard Design

x Operating Motor details

a - Type Permanent magnet motor As per Manufacturer's Standard Design

Guaranteed Technical Particulars_220kV WDFC Phase-II EMP-16 Project (Makarpura JNPT Section)
Page 15 .

Chapter 21 , Cl. 21.10.8.3.v ,Page 300, Cl.


21.11.2.1.,Page 301,Cl. 21.12.1.,Page 303
b - Rated Voltage 220 Vdc
& Cl. 21.13.2.,Page 304
Part 3 of CA

c - Rated Current Less than 3 A Manufacturer's Intellectual data

d - Rated Watts 260 W Manufacturer's Intellectual data

xi Operating Time

Less than 5 s
a - Closing Manufacturer's Intellectual data
(including spring charging time)

Less than 5 s
b - Opening Manufacturer's Intellectual data
(including spring charging time)

xii Type of Indicator Mechanical As per Manufacturer's Standard Design

Guaranteed Technical Particulars_220kV WDFC Phase-II EMP-16 Project (Makarpura JNPT Section)
Page 16 .

13 Current Transformers
i Type Ring Type As per Manufacturer's Standard Design

ii Material Copper As per Manufacturer's Standard Design

iii Position of Current Transformer As per SLD As per SLD

iv Reference Standard IEC 60044-1 IEC 60044-1

150% (at highest ratio) Chapter 21 , Cl. 21.14.1.4.5,Page 306,


v Rated Continuous thermal current
200% (other than highest ratio) Part 3 of CA

vi Rated Short Time current 50 kA As per customer's SLD

vii Duration 3s As per customer's SLD

As per IEC 62271-1, Cl 4.6 ,


viii Dynamic Current withstand 125 kAp
Page 40

As per IEC 62271-203, Table 2 ,


ix 1.2/50 micro sec. impulse withstand voltage 1050 kVp
Page 14

As per IEC 62271-203, Table 2 ,


x One minute power frequency withstand voltage 460 kV rms
Page 14

xi Number of primary winding 1 As per Manufacturer's Standard Design


Current Transformer details for MSETCL Line
xii
Bays
A Total number of cores 5 As per Bidder's SLD

a Metering core
i -Ratio 1600-800/1 A As per Bidder's SLD

20 VA For 800/1A Tap


ii -Output Burden As per Bidder's SLD
40VA For 1600/1A Tap

iii -Accuracy class 0.2S (For All Taps) As per Bidder's SLD

iv -Instrument Security Factor <5 As per Bidder's SLD

b Protection core

i -Ratio 1600-800/1 A As per Bidder's SLD

ii -Output Burden N/A As per Bidder's SLD

iii -Accuracy class PS (For All Taps) As per Bidder's SLD

iv -Accuracy Limit Factor N/A As per Bidder's SLD

v Knee point voltage (Vk) (in V) (for all cores)


a For 1600/1A Tap ≥ 1600 V As per Bidder's SLD

b For 800/1A Tap ≥ 800 V As per Bidder's SLD

Magnetizing current (Imag) at Vk/2 (in mA )


vi
(for all cores)

a For 1600/1A Tap ≤30 mA As per Bidder's SLD

b For 800/1A Tap ≤60 mA As per Bidder's SLD

Secondary resistance (Rct) (in Ohms)


vii
(for all cores)

a For 1600/1A Tap ≤16 ohms As per Bidder's SLD

b For 800/1A Tap ≤8 ohms As per Bidder's SLD


Current Transformer details for Bus coupler
xiii
Bay
A Total number of cores 4 As per Bidder's SLD

a Metering core
i -Ratio 1600-800/1 A As per Bidder's SLD
20 VA For 800/1A Tap
ii -Output Burden As per Bidder's SLD
40VA For 1600/1A Tap
iii -Accuracy class 0.2S (For All Taps) As per Bidder's SLD

iv -Instrument Security Factor <5 As per Bidder's SLD

Guaranteed Technical Particulars_220kV WDFC Phase-II EMP-16 Project (Makarpura JNPT Section)
Page 17 .

b Protection core
i -Ratio 1600-800/1 A As per Bidder's SLD

ii -Output Burden N/A As per Bidder's SLD

iii -Accuracy class PS (For All Taps) As per Bidder's SLD

iv -Accuracy Limit Factor N/A As per Bidder's SLD

v Knee point voltage (Vk) (in V) (for all cores)

a For 1600/1A Tap ≥ 1600 V As per Bidder's SLD

b For 800/1A Tap ≥ 800 V As per Bidder's SLD

Magnetizing current (Imag) at Vk/2 (in mA )


vi
(for all cores)

a For 1600/1A Tap ≤30 mA As per Bidder's SLD

b For 800/1A Tap ≤60 mA As per Bidder's SLD

Secondary resistance (Rct) (in Ohms)


vii
(for all cores)

a For 1600/1A Tap ≤16 ohms As per Bidder's SLD

b For 800/1A Tap ≤8 ohms As per Bidder's SLD


Current Transformer details for DFCCIL Bays
xiv
(Scott Transformer)
A Total number of cores 4 As per Bidder's SLD

a Metering core
i -Ratio 500-250/1 A As per Bidder's SLD
20 VA For 250/1A Tap
ii -Output Burden As per Bidder's SLD
40VA For 500/1A Tap
iii -Accuracy class 0.2S (For All Taps) As per Bidder's SLD

iv -Instrument Security Factor <5 As per Bidder's SLD

b Protection core (Type-I)


i -Ratio 500-250/1 A As per Bidder's SLD

ii -Output Burden N/A As per Bidder's SLD

iii -Accuracy class PS (For All Taps) As per Bidder's SLD

iv -Accuracy Limit Factor N/A As per Bidder's SLD

v Knee point voltage (Vk) (in V) (for all cores)


a For 500/1A Tap ≥ 500 V As per Bidder's SLD

b For 250/1A Tap ≥ 250 V As per Bidder's SLD


Magnetizing current (Imag) at Vk/2 (in mA )
vi
(for all cores)
a For 500/1A Tap ≤40 mA As per Bidder's SLD

b For 250/1A Tap ≤80 mA As per Bidder's SLD

Secondary resistance (Rct) (in Ohms)


vii
(for all cores)

a For 500/1A Tap ≤5 ohms As per Bidder's SLD

b For 250/1A Tap ≤2.5 ohms As per Bidder's SLD

c Protection core (Type-II)


i -Ratio 500-250/1 A As per Bidder's SLD

ii -Output Burden 20 VA (For All Taps) As per Bidder's SLD

iii -Accuracy class 5P20 (For All Taps) As per Bidder's SLD

iv -Accuracy Limit Factor 20 As per Bidder's SLD

v Knee point voltage (Vk) (in V) (for all cores)

a For 500/1A Tap N/A As per Bidder's SLD

b For 250/1A Tap N/A As per Bidder's SLD

Guaranteed Technical Particulars_220kV WDFC Phase-II EMP-16 Project (Makarpura JNPT Section)
Page 18 .

Magnetizing current (Imag) at Vk/2 (in mA )


vi
(for all cores)

a For 500/1A Tap N/A As per Bidder's SLD

b For 250/1A Tap N/A As per Bidder's SLD

Secondary resistance (Rct) (in Ohms)


vii
(for all cores)

a For 500/1A Tap ≤5 ohms As per Bidder's SLD

b For 250/1A Tap ≤2.5 ohms As per Bidder's SLD


Current Transformer details for C/R Bays
xv
(Traction Transformer)
A Total number of cores 4 As per Bidder's SLD

a Metering core
i -Ratio 500-250/1 A As per Bidder's SLD
20 VA For 250/1A Tap
ii -Output Burden As per Bidder's SLD
40VA For 500/1A Tap
iii -Accuracy class 0.2S (For All Taps) As per Bidder's SLD

iv -Instrument Security Factor <5 As per Bidder's SLD

b Protection core (Type-I)


i -Ratio 500-250/1 A As per Bidder's SLD

ii -Output Burden N/A As per Bidder's SLD

iii -Accuracy class PS (For All Taps) As per Bidder's SLD

iv -Accuracy Limit Factor N/A As per Bidder's SLD

v Knee point voltage (Vk) (in V) (for all cores)

a For 500/1A Tap ≥ 500 V As per Bidder's SLD

b For 250/1A Tap ≥ 250 V As per Bidder's SLD

Magnetizing current (Imag) at Vk/2 (in mA )


vi
(for all cores)

a For 500/1A Tap ≤40 mA As per Bidder's SLD

b For 250/1A Tap ≤80 mA As per Bidder's SLD

Secondary resistance (Rct) (in Ohms)


vii
(for all cores)

a For 500/1A Tap ≤5 ohms As per Bidder's SLD

b For 250/1A Tap ≤2.5 ohms As per Bidder's SLD

c Protection core (Type-II)


i -Ratio 500-250/1 A As per Bidder's SLD

ii -Output Burden 20 VA (For All Taps) As per Bidder's SLD

iii -Accuracy class 5P20 (For All Taps) As per Bidder's SLD

iv -Accuracy Limit Factor 20 As per Bidder's SLD

v Knee point voltage (Vk) (in V) (for all cores)

a For 500/1A Tap N/A As per Bidder's SLD

b For 250/1A Tap N/A As per Bidder's SLD

Magnetizing current (Imag) at Vk/2 (in mA )


vi
(for all cores)

a For 500/1A Tap N/A As per Bidder's SLD

b For 250/1A Tap N/A As per Bidder's SLD

Secondary resistance (Rct) (in Ohms)


vii
(for all cores)

a For 500/1A Tap N/A As per Bidder's SLD

b For 250/1A Tap N/A As per Bidder's SLD

Guaranteed Technical Particulars_220kV WDFC Phase-II EMP-16 Project (Makarpura JNPT Section)
Page 19 .

Current Transformer details for Bus Current


xvi
Transformer (Tariff Metering)
A Total number of core 1 As per Bidder's SLD

a Metering core (Main Meter CT)


i -Ratio 300/1 A As per Bidder's SLD

ii -Output Burden 15 VA As per Bidder's SLD

iii -Accuracy class 0.2S As per Bidder's SLD

B Total number of core 1 As per Bidder's SLD

a Metering core (Check Meter CT)


i -Ratio 300/1 A As per Bidder's SLD

ii -Output Burden 15 VA As per Bidder's SLD

iii -Accuracy class 0.2S As per Bidder's SLD

xvii -Instrument Security Factor <5 As per Bidder's SLD

As per IEC 60044-1, Table 8.2.2.1 ,


xviiI Partial Discharge Level <5
Page 57

As per IEC 60044-1, Table 2 ,


xix Insulation class of seconadry winding E
Page 33

As per IEC 60044-1, Cl.5.1.4,


xx Basic Insulation Level 3kV for 1 minute
Page 41

Guaranteed Technical Particulars_220kV WDFC Phase-II EMP-16 Project (Makarpura JNPT Section)
Page 20 .

14 Voltage Transformers
Chapter 21 , Cl. 21.14.1.4.5,Page 306,
i Type Inductive type
Part 3 of CA
ii Position of Voltage Transformer Main bus , Line bay & Traction TRF bay As per Bidder's SLD

iii Reference Standard IEC 60044-2 IEC 60044-2

iv Rated primary voltage (Ur) 220/√3 kV As per Bidder's SLD

v Rated Secondary Voltage 110/√3 V As per Bidder's SLD

vi Phase configuration Single phase As per Bidder's SLD

vii Purpose Metering & Protection As per Bidder's SLD

viii Number of secondaries


a Voltage Transformer for MSETCL Line bays 3 As per Bidder's SLD
Voltage Transformer for Bus Voltage
b 3 As per Bidder's SLD
Transformer
Voltage Transformer for C/R Traction
c 2 As per Bidder's SLD
Transformer bays
Voltage Transformer for Tariff Metering Voltage
d 1 As per Bidder's SLD
Transformer

ix Max. Continuous Thermal Burden 1000 VA As per Manufacturer's Standard Design

x Rated output of each secondary winding 200 VA As per customer's SLD


(Voltage Transformer for MSETCL Line bays)

xi Rated output of each secondary winding 50 VA As per customer's SLD


(Voltage Transformer other than MSETCL Line bays)

xii Total simultaneous burden

Voltage Transformer with three secondaries with


a 200 VA As per Manufacturer's Standard Design
200VA burden

Voltage Transformer with three secondaries with


b 150 VA As per Manufacturer's Standard Design
50VA burden

Voltage Transformer with two secondaries with


c 100 VA As per Manufacturer's Standard Design
50VA burden

Voltage Transformer with one secondaries with


d 50 VA As per Manufacturer's Standard Design
50VA burden

As per IEC 60044-2, Table 2


xiii Rated Over Voltage Factor - Continuous 1.2Un
Page 29

As per IEC 60044-2, Table 2


xiv Short Time Over Voltage Factor 1.5Un
Page 29

As per IEC 60044-2, Table 2


xv Duration 30sec
Page 29

As per IEC 60044-2, Table 4


xvi Power Frequency withstand Voltage 460 kV
Page 33

As per IEC 60044-2, Table 4


xvii Lightning Impulse withstand voltage 1050 kVp
Page 33

Chapter 21 , Cl. 21.14.3.1.2.i,Page 308,


xviii Partial Discharge Level Below 10
Part 3 of CA

Power Frequency withstand Voltage of Chapter 21 , Cl. 21.14.3.1.2.f.Page 308,


xix 3 kV
secondary circuit Part 3 of CA

xx Accuracy Class 3P,0.2 As per customer's SLD

Guaranteed Technical Particulars_220kV WDFC Phase-II EMP-16 Project (Makarpura JNPT Section)
Page 21 .

15 Enclosed Surge Arrester


i Name of manufacturer To be informed To be informed

ii Service Condition Indoor Indoor

iii Arrester Type Zinc oxide Zinc oxide


Chapter 21 , Cl. 21.16.5.j.Page 312,
iv Arrester Class Class 3
Part 3 of CA
v Applicable Standard IEC 60099-4 IEC 60099-4
Chapter 21 , Cl. 21.16.5.a.Page 311,
vi Rated System Voltage (kV) 245 kV
Part 3 of CA
Chapter 21 , Cl. 21.16.5.c.Page 312,
vii Rated Arrester voltage (kV) 198 kV
Part 3 of CA
Chapter 21 , Cl. 21.16.5.g.Page 312,
viii Max continuous operaing voltage (MCOV) 168 kV
Part 3 of CA
Chapter 21 , Cl. 21.16.5.e.Page 312,
ix Rated Frequency 50 Hz
Part 3 of CA

Nominal Discharge Current (kA) with 8/20 Micro Chapter 21 , Cl. 21.16.5.d.Page 312,
x 10 kA
second wave Part 3 of CA

Chapter 21 , Cl. 21.16.5.j.Page 312,


xi Line Discharge Class Class 3
Part 3 of CA
xii Maximum Residual voltage at:

a 10kA 1/2µs 485 kV As per Manufacturer's Standard Design

b 5kA 8/20µs 439 kV As per Manufacturer's Standard Design

c 10kA 8/20µs 462 kV As per Manufacturer's Standard Design

d 20kA 8/20µs 504 kV As per Manufacturer's Standard Design

e 40kA 8/20µs 550 kV As per Manufacturer's Standard Design

Chapter 21 , Cl. 21.16.5.h.Page 312,


f 1kA 30/60µs 500 kV
Part 3 of CA
Chapter 21 , Cl. 21.16.5.f.Page 312,
xiii Minimum single impulse energy capability 8 kJ/kV
Part 3 of CA
xiv Insulation withstand voltage tests

a Lightning impulse withstand voltage 1050 kVp As per Manufacturer's Standard Design

b Power frequency withstand voltage 460 kV As per Manufacturer's Standard Design

c Switching Impulse withstand voltage N/A As per Manufacturer's Standard Design

xv Surge counter Yes As per Manufacturer's Standard Design

xvi Scale range of current leakage meter 0-30 mA As per Manufacturer's Standard Design

xvii Disconnecting link for GIS High Voltage Test No As per Manufacturer's Standard Design

xviii Rated SF6 gas pressure 0.61 Mpa.G As per Manufacturer's Standard Design

xix Min. (Guaranteed) SF6 gas pressure 0.55 Mpa.G As per Manufacturer's Standard Design

xx Design (Max.) SF6 gas pressure 0.7 Mpa.G As per Manufacturer's Standard Design

Guaranteed Technical Particulars_220kV WDFC Phase-II EMP-16 Project (Makarpura JNPT Section)
Page 22 .

xxi SF6 gas leakage 0.5% per year As per Manufacturer's Standard Design

xxii Protection level of enclosure Same as GIS As per Manufacturer's Standard Design

xxiii Painting Shade Informed later As per Manufacturer's Standard Design

xxiv Materials of enclosure Aluminium As per Manufacturer's Standard Design

xxv Height of arrester 1460 mm As per Manufacturer's Standard Design

xxvi Gas Weight Approx. 7 As per Manufacturer's Standard Design

xxvii Total weight Approx. 135 As per Manufacturer's Standard Design

xxviii Leakage Monitor Yes As per Manufacturer's Standard Design

Guaranteed Technical Particulars_220kV WDFC Phase-II EMP-16 Project (Makarpura JNPT Section)
Page 23 .

16 Local Control Cubicle


i Name of Manufacturer (OEM of GIS) To be informed. To be informed.

Indoor
ii Location in GIS As per Bidder's Layout
(Stand alone in front of GIS)

iii Material Cold rolled sheet steel As per Manufacturer's Standard Design

iv Sheet Thickness Min. 2mm As per Manufacturer's Standard Design

v Degree of Protection IP 42 As per Manufacturer's Standard Design

vi Padlocking arrangement Built in locking facility N/A

vii Major components of Local Control Cubicle


a - Bay control mimic diagram As per Local Control Cubicle schematic N/A

b - Control Switches As per Local Control Cubicle schematic N/A

c - Indication lamps As per Local Control Cubicle schematic N/A

d - Position indicators As per Local Control Cubicle schematic N/A

e - Annunciation scheme As per Local Control Cubicle schematic N/A

f - Auxiliary relays As per Local Control Cubicle schematic N/A

g - Contact multiplication relays As per Local Control Cubicle schematic N/A

h - System parameters display As per Local Control Cubicle schematic N/A


i - Heater with thermostat As per Local Control Cubicle schematic N/A

- Interface terminal blocks for relaying


j As per Local Control Cubicle schematic N/A
& protection

17 GIS to Line Connection


i Nos of XLPE cable can be terminated In scope of L&T N/A
ii Type of cable termination required In scope of L&T N/A

18 GIS to Transformer Connection


i Nos of XLPE cable can be terminated In scope of L&T N/A
ii Type of cable termination required In scope of L&T N/A

19 Cable Sealing End

i Reference Standard IEC-62271-209 IEC-62271-209

Datasheet-A1, Sl.No. 1.2 , Page 376,


ii Rated Voltage (Ur) 245 kV
Part 3 of CA

2000 A : As per customer's SLD


iii Rated normal current (Ir) {2000} 3150 A 3150 A : As per Manufacturer's Type test
report

Bushing Design-composite, dry bushing with Dry type according


iv As per Bidder's Drawing
graded insulation (IEC 62271-209)

Rated short-duration power-frequency withstand As per IEC 62271-203, Table 2 ,


v 460 kV
voltage Page 14

As per IEC 62271-203, Table 2 ,


vi Rated lightning impulse withstand voltage 1050
Page 14

vii Mounting position Vertical As per bidder's Layout

viii Number of sealing end/phase one As per bidder's Layout

Guaranteed Technical Particulars_220kV WDFC Phase-II EMP-16 Project (Makarpura JNPT Section)
Page 24 .

20 Maintenance

Maximum down time for replacement or removal As per OEM manual


i N/A
of any part (Will be provided before dispatch)

Maximum down time for degassing and refilling As per OEM manual
ii N/A
the biggest compartment (Will be provided before dispatch)

As per OEM manual


iii Time between two refilling of SF6 gas N/A
(Will be provided before dispatch)

As per OEM manual


iv Recommended period for overhauling N/A
(Will be provided before dispatch)

Not yet
v Operation and Maintenance manual attached N/A
(Will be provided before dispatch)

vi Nearest local service centre Khedcity , Pune N/A

vii Minimum time of availabiliity of local service Within 2~3 Days N/A
viii Availability of spares at local service centre Yes N/A
Yes
ix List of Special tools attached (Doc. No.HI-16-0024-G-Special Tools N/A
List_R1)
Yes
x List of Spare parts attached (Doc. No.HI-16-2024-S-Special Tools N/A
List_R4)

Note : Value mentioned in { XYZ} is based on customer requirement

Guaranteed Technical Particulars_220kV WDFC Phase-II EMP-16 Project (Makarpura JNPT Section)