SCHEDULE OF TECHNICAL PARTICULARS FOR GRID CONNECTED INVERTER

Instructions / Notes

1. Any other deviation of the inverter from IEEE 1574-2003 and/or Grid code, rather than
the particulars mentioned below in this schedule should be mentioned clearly and
separately
2. The test certificates /compliance certificates from the independent agencies or any accredited
agency or one of the following institutions in Sri lanka, Should be submitted to prove the
above mentioned values.

a. Department of Electrical Engineering, University of Moratuwa


b. National Engineering and Research and Development Centre (NERD)
c. Industrial Technology Institute (ITI)
3. If the test certificates/compliance certificates are from an accredited agencies,
documentary evidence shall be submitted relevant to their accreditation.

Description Specified Particulars


1) Name of the supplier
2) Supplier Registration No.
3) Inverter manufacturer
4) Country of origin
5) Independent Agency of
submitting test reports
6) Is an accredited agency
mentioned in 5Note3
7) Model No.

8) Support standards
IEEE 1547 - 2003 Grid Code/LECO Inverter
Unit Ref. Value Ref. Value Ref. of Value
test
Certificate
9)Rated Power output
% 4.1.3 +/- 5%
10)Synchronization W.r.t
prevailing voltage level

__________________________________________
Signature and stamp of the supplier/
Consultant Engineer

Page 1 of 3
Description Specified Particulars
11) Over Voltage and under voltage V 6.2.2 Unless within
tripping conditions 6% of 230

a) Clearing time to abnormal S 4.2.3


voltages (% of base voltage)

i. V < 50 S <0.2
ii. 50 <= V < 88 S < 2.00
iii. 110 <= V < 120 S < 1.00
iv. V >= 120 S 0.2
12) Over and under frequency Hz 6.2.2 Unless within
tripping condition 47-52

a) Clearing time to abnormal S


Frequencies <=30kw (in Hz)
i. >52 S 0.2
ii. <47 S 0.2
b) Clearing time to S
abnormal frequency>30 kw
i. >52 S 0.2
ii. <{49.5-47} (adjustable set point) S Adjustable to
<0.2 – 300
13) Capability to withstand voltage % 4.1.8.3 220% 6.3 220%
w.r.t. to the interconnection
voltage
14) Grounding scheme 4.1.2 TT system

15) Reconnection time S 4.2.6 Adjusta 6.2.2 > 180


ble up
to 300
16) Limitation of dc injection % 4.3.1 <0.5
Current w.r.t. full rated output
Current at the point of DR
Connection
17) Output voltage waveform 6.6 50 Hz,
Sinusoidal

__________________________________________
Signature and stamp of the supplier/
Consultant Engineer

Page 2 of 3
Description Specified Particulars
18) Power quality 6.11 Required
Measurements as per IEC
61400-21
19) Harmonic Distortion (HD) 4.3.3 6.7

a) h < 11 % <4 <4


b) 11 < h < 17 % <2 <2
c) 17 < h < 23 % < 1.5 <1.5
d) 23 < h <35 % <0.6 <0.6
e) 35 < h % <0.3 <0.3
f) THD <5 <5
20) Emission of inter harmonic 6.11 Required Submit
Currents from the power separately
Electronic converter as per
Grid code

I / We certified that

1. The above filled particulars are true and correct.


2. I / We know non submission of test reports causes rejection of net metering application
/s relevant this inverter.