Professional Documents
Culture Documents
net/publication/237585065
CITATIONS READS
6 403
4 authors, including:
Some of the authors of this publication are also working on these related projects:
Analysis and Testing of Battery Charge Controllers with Maximum Power Point Tracking: Performance and Efficiency View project
All content following this page was uploaded by Stefan Krauter on 18 March 2014.
- 619 -
which the experiments were carried out was 32 m by
16 m with a height of 6 m and got a white plaster inner
surface.
2.2 Passively ventilated PV facade element While the effect of the variation of the air duct is 2.6
In the first experimental arrangement, representing a K only (see Table 2), it could be neglected in terms of
conventional PV curtain facade, a variable air duct output power in the observed range.
was let between the facade and the wall. Figure 2 2.3 Actively ventilated PV facade element
shows the test set-up of this passive ventilated PV
The “Laboratorio Fotovoltaico” at “Universidade
facade.
Federal do Rio de Janeiro (UFRJ) has carried out
these measurements. In order to minimize the
dispersion of air velocity along the width of the PV
facade, an array of 16 fans was used. The aim of this
experiment was to evaluate the maximum possible
- 620 -
effect of active ventilation: Therefore front- and insulation layer of the building wall. Fig. 4 shows the
backside of the PV module were both ventilated and test arrangement (temperature measurement
the module was mounted with its long side towards configuration was the same as the one used at the
horizontal (see Fig. 3.). The air velocities (measured at conventional PV facade element, as shown in Fig. 5).
the front of the module, 40 mm above the module
surface) shown in column A of Table 3 allowed a
reduction of cell temperature by 16 K relative to
natural convection. This resulted in an increase in
power output by 7.2%.
- 621 -
structures (max. 18 K). The heat flow in the flowing by Krauter 1993 and by Krauter and Hanitsch 1996.
-2
water is about 380 W m , see Table 8. The reflection losses ρ opt for the modules used
(calculated with a three layer model, including optical
dispersion and non-ideal antireflective coating)
amount to 13.1%. The actual photovoltaic conversion
efficiency ηPV measured at G = 700 W m and Tcell =
-2
- 622 -
could be expressed by h nc as follows (according to are presented in Table 8; the computed values are
Merker 1987): reasonably fitting to the measurements with maximal
k k deviations of +5.9% to –7.9%.
hnc = Nu = 0.56 Ra1/4 (7)
l nc l
g l3 SUMMARY & DISCUSSION
Ra = Pr ⋅ Gr = Pr ⋅
ν 2 (T f − Ta ) (8)
Fig. 6 shows the thermal response to the different
-2
T h e backside of the PV curtain facade could be types of PV facades irradiated at 700 W m for four
modeled as an air-duct with heating from one side. hours. Stationary values are reached after 1-2 hours.
For this case (Gr >1) VDI 1994 gives a solution as
follows:
1/ 4
g β (Tb − Taw )d 4
Nu = .61 ⋅ ( Pr ⋅ Gr )
1/ 4
= .61⋅ Pr ⋅ (9)
ν2l
The properties for air required could be found in
Table 6 as a function of temperature. According to
VDI 1994 a reasonable value to use as reference
temperature for these properties is the average
between ambient and body temperature. Sandberg
and Moshfegh (1998) have carried out further
investigations on this subject.
-3 -1
For fo rced convection within a range of .13· 10 m s
< v < 1.33· 102 m s-1 the heat transfer coefficient can
be found (derived from VDI 1994 and Merker 1987) as:
hv =
k Nu v k
l
=
l
( 2 1/ 2
Nulam + Nutur
2
(10) )
Nulam = 0.664⋅ Re1/ 2 Pr1/3 (11)
Figure 6. Temperature as a function of time for
0.037 Pr Re 0 .8 -2
Nu tur = (12) different types of PV facade elements ( G=700Wm ).
(
1 + 2.433 Re −0 .1 Pr 2 /3 − 1 ) Table 9 offers an overview of the different measures
with: and the consequences on yield and costs:
-1
vρ l 1. Active ventilation by forced convection of 2 m s
Re = (13) results in a maximum reduction of operating cell
µ
temperatures of 18 K. This leads to an 8% increase in
At the experiment for forced convection, front and the electrical power output in comparison to
back heat transfer is about the same: conventional PV facades.
qcb ≈ q cf = hv (Tf -Ta). 2. Thermal insulating PV facade elements (TIPVE) at k
-1
For air velocities v < 1 m s heat transfer by natural = .32 W K-1 m-1 lead to a temperature increase of 20.7
convection could be more than by forced conve ction. K, which causes a 9.3% loss of electrical yield (related
In case of similar direction of natural and forced to conventional PV curtain facades). Depending on
convection Churchill 1977 therefore suggests a the value of the PV-generated electricity in relation to
superposition of both components: the possible savings in installation costs such a
hc =
k
l
(
Nuv3 + Nunc
3
) 1/ 3
(14)
solution may become an attractive option.
3. Hybrid thermal insulating PV facade elements
The heat flux dissipated by the water flow at the last (HYTIPVE), combined with water cooling systems
experiment is: (which may also be used for hot water applications)
allow an electrical yield that is 9% higher than for
q w = cw m& ( Toutlet − Tinlet ) (15)
conventional PV-facades.
with: In order to facilitate further simulation of cell
m& = ρw ⋅ V& (16) temperatures, efficiencies and energy yields, the
model of the thermal process was given. The
The heat and power fluxes of the different simulation carried out (see Table 8) showed
experiments have been calculated, using data from reasonable small deviations to the measurements and
Tables 2 to 7, the characteristic dimensions given the can be used for further investigations of building
Figures, and using equations (1) to (16). The results integration of photovoltaic elements. Energy
- 623 -
consumption of equipment used for ventilation and
pumping are not representative. Wachsmann 2000 ACKNOWLEDGEMENTS
gives some first results relating pumping power to The authors would like to express their sincere thanks
gain of PV yield by cooling for large PV pumping to Bodo von Moltke who built the solar simulator, to
systems. Economic investigations concerning the Leopoldo Bastos who enabled instrumentation to
invested and operational costs of additional measure air velocity, also to Rodrigo Guido Araújo
components (as fans, water pumps, insulation, who built the solar simulator in Rio, and for the
installation and substitutive effects) relating to the support of Solon AG who financed a major part of
yield are given on the way. this project.
Table 8. Simulation of heat and power flows for different types of PV facade elements (PVE),
calculated according to equations (1) to (15) using data from Tables 2 to 7.
conv. PVE -
ventilated at
HYTIPVE
47.7· 10-6
air duct of
flow rate
150 mm
TIPVE
2 m/s
PVE
m3/s
Energy flow
ρ opt G in W m-2 92.0 92.0 92.0 92.0
P PV /A in W m-2 54.1 53.3 43.8 42.3
-2
q k in W m 4.2 0 0 17.4
Qrf in W m-2 81.4 94.4 219.3 393.2
-2 *)
qrb in W m 0 94.4 110.4 0
-2
Qcf in W m 35.9 164.3 109.7 196.5
-2
Qcb in W m 0 164.3 125.2 0
-2
Qw in W m 379.2 0 0 0
-2
Sum of energy flows in W m 646.8 662.7 700.4 741.4
-2
Relative difference from 700 W m - 7.6% - 5.3% + 0.06% + 5.9 %
*)
At the conv. PVE wall temperature was set to Taw =0.5(Tb +Ta ) for radiation exchange between module back and
wall.
Table 9. Measurements of stationary temperatures for different types of PV facade elements (PVE)
- 624 -
conv. PVE -
HYTIPVE
47.7· 10-6
air duct of
ventilated
flow rate
150 mm
at 2 m/s
TIPVE
PVE
m3/s
Tcell in °C 36.8 39.6 55.9 77.1
Ta in °C 23.1 24 22.2 22.8
∆Tcell vs. conventional PV façade
19.9 18 0 20.7
in K (ref. To Ta= 20°C)
Gain of electrical yield 9.0 % 8.1 % 0% -9.3 %
Relative expenditure related to
1.2-1.4 1.1-1.2 1.0 0.8-0.9
conv. PV façade (new building)
Crick F.J., Wishaw A., Pearsall N., Hynes K., Shaw Nordmann T., Dürr M. and A. Frölich „The 32 kW
M., Young G. and Baker P. „PV cladding thermal PV Installation on the Grain Silo of the Stadtmühle
gains: experimental results from three PV cladding CMZ – the First Installation for the Zurich Solar
nd
systems investigating the effects on the design on Power Exchange“. Proceedings of the 2 World
the operational temperature“. In Proceedings of the Conference and exhibition on Photovoltaic Energy
2nd World Conference and exhibition on Conversion, 6-10 July, Vienna, Austria, pp. 1983-
Photovoltaic Energy Conversion, 6-10 July, Vienna, 1986 (1998).
Austria, pp. 2062-2065, (1998). Posansky M. and S. Gnos „Building Integrated
Churchill S. W. „A Comprehensive Correlating Photovoltaic Systems: Examples of realised Hybrid
Equation fo r Laminar, Assisting, Forced and Free PV-Power Plants with specially conceived PV-
Convection“. AIChE 10, 10-16, (1977). Modules for Building Integration“. Proceedings of
th
the 12 E.C. Photovoltaic Conference, 11-14 April.
Emery K., Burdick J., Caiyem Y., Dunlavy D., Field Amsterdam, Netherlands. (1994)
H., Kroposki B. and T. Moriatry T. „Temperature
Dependence of Photovoltaic Cells, Modules, and Sandberg M. and Moshfegh B. „Flow and Heat
Transfer in the air gap behind photovoltaic panels “.
- 625 -
Renewable and Sustainable Energy Reviews 2, 287- PV module (°C, K)
301 (1998). Tinlet Temperature of water inlet (°C, K)
Tlower Backside temperature at the lower part
VDI „VDI Wärmeatlas“, 7th Ed., Verband Deutscher
of the PV module (°C, K)
Ingenieure (Eds), VDI, Düsseldorf, Germany, 1994.
Toutlet Temperature of water outlet (°C, K)
Wach smann, U., „ Extended Use of Photovoltaic Tupper Backside temperature at the upper part
Pumping Systems “. Master thesis at UFRJ and TU of the PV module (°C, K)
Berlin (in German), 2000. TCV Temperature coefficient of voltage
dV/dT (V K-1)
Wilshaw A. R., Bates J. R. and N. M. Pearsall.
TCC Temperature coefficient of current
„Photovoltaic Module Operating Temperature -1
dC/dT (A K )
Effects“. Proceedings of EuroSun’96, Munich,
TCP Temperature coefficient of power
Germany, pp. 940-944 (1996).
dP/dT (W K-1)
TIPVE Thermal Insulating PV facade element
NOMENCLATURE v Air velocity (m s-1)
V Voltage (V)
A Area (m2)
V mpp Voltage at Maximum Power Point (V)
AM Relative Air Mass
V oc Open circuit voltage (V)
c Specific heat (J kg -1 K-1)
V& Volume flow (m 3 s -1)
d Depth of air duct (m)
-2 WSV 95 German Heat Preserving Edict of
E Irradiance (W m )
1995 (“Wärmeschutzverordnung”)
G Global irradiance (W m-2)
Gr Grashof number (-)
Greek letters
g Standard gravitational acceleration
-2 β Thermal expansion coefficient (K-1)
(9.8067 m s )
-2 -1 ∆Tcell Difference of cell temperature related
h Heat transfer coefficient (W m K )
to reference conditions (K)
HYTIPVE Hybrid Thermal Insulating PV facade
ηPV Efficiency of PV conversion (-)
Element
ε Thermal emittance (-)
I Electrical current (A)
λ Wavelength (m)
Impp Current at Maximum Power Point (A)
ν Cinematic viscosity (m2 s-2)
Isc Short circuit current (A)
-1 -1 µ Dynamic viscosity
k Thermal conductivity (W m K )
(kg m-1 s-1 = N m -2 s -1 = Pa s)
l characteristic length relevant for heat
ρ Density (kg m -3)
transfer (m)
ρ op Optical reflectance (-)
m Mass (kg)
m& σ Stefan Boltzmann constant (5.67 10-8 W
Mass flow (kg s -1)
m-2 K-4)
MPP Maximum Power Point
Nu Nusselt number
Subscripts
P Electrical power (W)
a ambient
Pmpp Electrical power at Maximum Power
aw artificial wall
Point (W)
b backside
Pr Prandl number (-)
bw building wall
PV Photovoltaic
c convective
PVE Photovoltaic Facade Element
cf convective front
Pt 100 Electrical resistor made of Platinum
cb convective back
used for temperature measurements
f front
(100 Ohms at 0°C)
-2 k conductive
q Heat flux (W m )
kf conductive front
Ra Raleigh number (-)
kb conductive back
Re Reynolds number (-)
lam laminar
Si Silicon
nc natural convection
STC Standard Test Conditions (irradiance of
-2 r radiative
1000 W m , spectrum AM 1.5, and a
rb radiative back
solar cell temperature of 25°C)
rf radiative front
t Time (s)
tur turbulent
T Temperature (°C, K)
v forced convection
Tcell Solar cell temperature (°C, K)
w water
Tcenter Backside temperature at the center of a
- 626 -