K3GA00-PV03-01

Operating instructions

ebm-papst Mulfingen GmbH & Co. KG 1. SAFETY REGULATIONS AND INFORMATION


Bachmühle 2
D-74673 Mulfingen Read these operating instructions carefully before starting work on the
Phone +49 (0) 7938 81-0 device. Observe the following warnings to prevent malfunctions or
Fax +49 (0) 7938 81-110 danger to persons.
info1@de.ebmpapst.com These operating instructions are to be regarded as part of the device.
www.ebmpapst.com The device is only to be sold or passed on together with the operating
instructions.
CONTENTS These operating instructions may be duplicated and distributed to inform
about potential dangers and their prevention.
1. SAFETY REGULATIONS AND INFORMATION 1
1.1 Hazard levels for warnings
1.1 Hazard levels for warnings 1
1.2 Staff qualifications 1 These operating instructions use the following hazard levels to indicate
1.3 Basic safety rules 1 potentially hazardous situations and important safety regulations:
1.4 Voltage 1
DANGER
1.5 Safety and protective features 2
Indicates an imminently hazardous situation which will result in
1.6 Electromagnetic radiation 2
death or serious injury if the specified actions are not taken.
1.7 Mechanical movement 2
Compliance with the instructions is imperative.
1.8 Emissions 2
1.9 Hot surface 2 WARNING
1.10 Transport 2 Indicates a potentially hazardous situation which can result in
1.11 Storage 2 death or serious injury if the specified actions are not taken.
Exercise extreme caution while working.
2. INTENDED USE 3
CAUTION
3. TECHNICAL DATA 4 Indicates a potentially hazardous situation which can result in
3.1 Product drawing 4 minor or moderate injury or damage to property if the specified
3.2 Nominal data 5 actions are not taken.
3.3 Data according to Commission Regulation (EU) 327/2011 5 NOTE
3.4 Technical description 5 A potentially harmful situation can occur and, if not avoided, can
3.5 Mounting data 6 lead to property damage.
3.6 Transport and storage conditions 6
3.7 Electromagnetic compatibility 6 1.2 Staff qualifications
4. CONNECTION AND STARTUP 6 The device may only be transported, unpacked, installed, operated,
4.1 Mechanical connection 6 maintained and otherwise used by suitably qualified, trained and
4.2 Electrical connection 7 authorized technical staff.
4.3 Connection in terminal box 8 Only authorized specialists are permitted to install the device, to carry
4.4 Factory settings 9 out a test run and to perform work on the electrical installation.
4.5 Connection diagram 10
1.3 Basic safety rules
4.6 Checking connections 12
4.7 Switching on the device 12 The safety hazards associated with the device must be assessed again
4.8 Switching off the device 12 following installation in the final product.
The locally applicable industrial safety regulations are always to be
Translation of the original operating instructions

5. INTEGRATED PROTECTIVE FEATURES 12 observed when working on the device.


Keep the workplace clean and tidy. Untidiness in the work area
6. MAINTENANCE, MALFUNCTIONS, POSSIBLE 13 increases the risk of accidents.
CAUSES AND REMEDIES Note the following when working on the device:
6.1 Vibration testing 13
; Do not perform any modifications, additions or conversions on the
6.2 Cleaning 14
device without the approval of ebm-papst.
6.3 Safety inspection 14
6.4 Disposal 14 1.4 Voltage
; Check the device's electrical equipment at regular intervals; see
Chapter 6.3 Safety inspection.
; Replace loose connections and defective cables immediately.
DANGER
Electrically charged device
Risk of electric shock
→ When working on an electrically charged device, stand on a
rubber mat.

Item no. 55793-5-9970 · ENU · Change 94781 · Approved 2018-01-23 · Page 1 / 15

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
K3GA00-PV03-01
Operating instructions

WARNING DANGER
Live terminals and connections even with device Ejected parts
switched off Missing protective devices may cause balancing weights or
Electric shock broken fan blades to be ejected and cause injuries.
→ Wait five minutes after disconnecting the voltage at all poles → Take appropriate safety measures.
before opening the device.
WARNING
CAUTION Rotating device
In the event of a fault, the rotor and the impeller will be Long hair and dangling items of clothing, jewelry and the like
energized can become entangled and be pulled into the device. Injuries
The rotor and the impeller have basic insulation. can result.
→ Do not touch the rotor and impeller once installed. → Do not wear any loose-fitting or dangling clothing or jewelry
while working on rotating parts.
CAUTION
If control voltage or a stored speed set value is applied, → Protect long hair with a cap.
the motor will restart automatically, e.g. after a power
failure. 1.8 Emissions
Risk of injury WARNING
→ Keep out of the device’s danger zone.# When working on Depending on the installation and operating conditions,
the device, switch off the line voltage and ensure that it the sound pressure level may exceed 70 dB(A).
cannot be switched back on. Risk of noise-induced hearing loss
→ Wait until the device comes to a stop. → Take appropriate technical safety measures.
→ After working on the device, remove any tools or other → Protect operating personnel with appropriate safety
objects from the device. equipment such as hearing protection.
→ Also observe the requirements of local agencies.
1.5 Safety and protective features
DANGER 1.9 Hot surface
Protective device missing and protective device not CAUTION
functioning High temperature on electronics housing
Without a protective device there is a risk of serious injury, for Risk of burns
instance if the hands reach or are sucked into the device during
operation. → Ensure sufficient protection against accidental contact.

→ Operate the device only with a fixed protective device and 1.10 Transport
guard grille.
→ The fixed protective device must be able to withstand the WARNING
kinetic energy of a fan blade that becomes detached at Transporting the fan
maximum speed. There must not be any gaps which it is Injuries from tipping or slipping
possible to reach into with the fingers, for example. → The fan is always to be transported with care and in its
→ The device is a built-in component. As the operator, you original packaging. #If set down too hard or at an angle for
are responsible for ensuring that the device is secured example, the impact can lead to bearing damage or
adequately. deformation of the frame or impeller. #It must be ensured that
the fans cannot tip over during transportation and handling.
Translation of the original operating instructions

→ Stop the device immediately if you notice a missing or


ineffective protective device. → Secure the fan(s) with appropriate equipment such as a
lashing strip so that nothing can slip or tip, especially when
1.6 Electromagnetic radiation stacking multiple fans. #Also make allowance for possible
wind forces.
NOTE
Electrical or electromagnetic interference after installing 1.11 Storage
the device in customer equipment.
WARNING
→ Verify that the entire setup is EMC-compliant. Storing the fan
Injuries from tipping or slipping
1.7 Mechanical movement
→ The fans must always be stored and handled so that they
DANGER cannot tip over.
Rotating device → Secure the fan(s) with appropriate equipment such as a
Risk of injury to body parts coming into contact with the rotor or lashing strip so that nothing can slip or tip, especially when
the impeller. stacking multiple fans.
→ Secure the device against accidental contact. → Also take possible wind forces into consideration.
→ Before working on the system/machine, wait until all ; Store the device, partially or fully assembled, in a dry place,
parts have come to a standstill. protected against the weather and free from vibration, in the original
packaging in a clean environment.

Item no. 55793-5-9970 · ENU · Change 94781 · Approved 2018-01-23 · Page 2 / 15

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
K3GA00-PV03-01
Operating instructions

; Protect the device against environmental effects and dirt until final ● Using the device as a safety component or to perform safety-related
installation. functions.
; We recommend storing the device for no longer than one year in ● Operation with completely or partially disassembled or manipulated
order to guarantee trouble-free operation and the longest possible protective devices.
service life. ● In addition, all applications not listed among the intended uses.
; Even devices explicitly intended for outdoor use are to be stored as
described prior to commissioning.
; Maintain the storage temperature, see
Chapter 3.6 Transport and storage conditions.
; Make sure that all cable glands are fitted with dummy plugs.

2. INTENDED USE
The device is exclusively designed as a built-in device for conveying
air according to its technical data.
Any other usage above and beyond this does not conform with the
intended purpose and constitutes misuse of the device.
Customer equipment must be capable of withstanding the mechanical
and thermal stresses that can arise from this product. This applies for the
entire service life of the equipment in which this product is installed.
Intended use also includes
● The device is only to be used in power systems with grounded
neutral (TN/TT power systems), in power systems with phase
conductor grounding, or in IT power systems.
● The device is to be used in networks with network quality
characteristics as per EN 50160.
● Using the device only in stationary systems.
● Performing all maintenance work.
● Conveying air at an ambient air pressure between 800 mbar and
1050 mbar.
● Using the device within the permitted ambient temperature range; see
Chapter 3.6 Transport and storage conditions and
Chapter 3.2 Nominal data.
● Operating the device with all protective devices.
● Following the operating instructions.

Improper use
In particular, operating the device in the following ways is prohibited and
Translation of the original operating instructions

could be hazardous:
● Operating the device in an unbalanced state, e.g. due to dirt deposits
or ice formation.
● Resonant operation, operation with severe vibration. This also
includes vibration transmitted to the fan from the customer installation.
● Operation in medical equipment with a life-sustaining or life-support
function.
● Conveying solids in the flow medium.
● Painting the device
● Connections (e.g. screws) coming loose during operation.
● Opening the terminal box during operation.
● Standing or walking on the device
● Conveying air that contains abrasive particles.
● Conveying highly corrosive air, e.g. salt spray. Exception: devices
designed for salt spray and correspondingly protected.
● Conveying air with high dust content, e.g. suctioning off sawdust.
● Operating the device close to flammable materials or components.
● Operating the device in an explosive atmosphere.

Item no. 55793-5-9970 · ENU · Change 94781 · Approved 2018-01-23 · Page 3 / 15

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
K3GA00-PV03-01
Operating instructions

3. TECHNICAL DATA

3.1 Product drawing

All dimensions in mm.

1 Inlet ring with pressure tap (k-factor: 1200)


2 Mounting position for vibration-absorbing elements, tightening torque max. 40 Nm
3 Cable diameter min. 5 mm, max. 13 mm, tightening torque 4 ± 0.6 Nm
4 Cable diameter min. 16 mm, max. 20.5 mm, tightening torque 6 ± 0.9 Nm
5 Tightening torque 3.5 ± 0.5 Nm
Translation of the original operating instructions

6 Mounting holes for FlowGrid


7 Installation position: shaft horizontal (motor support plate must stand upright) or rotor on bottom; rotor on top on request

Item no. 55793-5-9970 · ENU · Change 94781 · Approved 2018-01-23 · Page 4 / 15

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
K3GA00-PV03-01
Operating instructions

3.2 Nominal data 3.4 Technical description


Motor M3G200-QA Weight 178.4 kg
Size 1000 mm
Phase 3~ Motor size 200
Nominal voltage / VAC 400 Rotor surface Painted black
Nominal voltage 380 .. 480 Electronics housing Die-cast aluminum
range / VAC material
Frequency / Hz 50/60 Impeller material Sheet aluminum
Method of obtaining ml Support plate material Sheet steel, galvanized
data Spacer material Aluminum
Speed (rpm) / min-1 750 Inlet nozzle material Sheet steel, galvanized
Power consumption / W 6340 Number of blades 5
Current draw / A 9.8 Direction of rotation Clockwise, viewed toward rotor
Min. ambient -25 Degree of protection IP54
temperature / °C Insulation class "F"
Max. ambient 40 Moisture (F) / H1
temperature / °C Environmental (H)
ml = Max. load · me = Max. efficiency · fa = Free air protection class
cs = Customer specification · ce = Customer equipment Ambient temperature Occasional start-up between -40°C and -
Subject to change note 25°C is permissible.
For continuous operation at
3.3 Data according to Commission Regulation (EU) 327/ temperatures below -25°C (e.g.
2011 refrigeration applications) we recommend
our fan design with special low-
Actual Req. 2015
temperature bearings.
01 Overall efficiency ηes / % 71.2 59.9
Installation position See product drawing
02 Measurement category A
Condensation On rotor side
03 Efficiency category Static
drainage holes
04 Efficiency grade N 73.3 62
Mode S1
05 Variable speed drive Yes
Motor mounting Ball bearing
06 Year of manufacture The year of manufacture is specified on the
product's rating label. Technical features - Output 10 VDC, max. 10 mA
07 Manufacturer ebm-papst Mulfingen GmbH & Co. KG - Output 20 VDC, max. 50 mA
Amtsgericht (court of registration) Stuttgart · - Output for slave 0-10 V
HRA 590344
D-74673 Mulfingen - Operation and alarm display
08 Type K3GA00-PV03-01 - Input for sensor 0-10 V or 4-20 mA
- External 24 V input (parameter setting)
09 Power consumption Ped / kW 6.35
- External release input
09 Air flow qv / m³/h 27600
- Alarm relay
09 Pressure increase total psf / 570
- Integrated PI controller
Pa
- Motor current limitation
10 Speed (rpm) n / min-1 750 - PFC, passive
Translation of the original operating instructions

11 Specific ratio* 1.01 - RS-485 MODBUS-RTU


12 Recycling/disposal Information on recycling and disposal is
provided in the operating instructions.
- Soft start
13 Maintenance Information on installation, operation and - EEPROM write cycles: 100,000
maintenance is provided in the operating maximum
instructions. - Control input 0-10 VDC / PWM
14 Additional components Components used to calculate the energy
efficiency that are not apparent from the
- Control interface with SELV potential
measurement category are detailed in the safely disconnected from the mains
CE declaration. - Thermal overload protection for
* Specific ratio = 1 + pfs / 100 000 Pa electronics/motor
- Line undervoltage / phase failure
Data obtained at optimum efficiency level. The ErP data is determined using a motor-impeller
combination in a standardized measurement setup. detection
Touch current <= 3.5 mA
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)
Electrical hookup Terminal box
Motor protection Reverse polarity and locked-rotor
protection

Item no. 55793-5-9970 · ENU · Change 94781 · Approved 2018-01-23 · Page 5 / 15

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
K3GA00-PV03-01
Operating instructions

Protection class I (with customer connection of protective 4. CONNECTION AND STARTUP


earth)
Conformity with EN 61800-5-1; CE 4.1 Mechanical connection
standards
Approval UL 1004-7 + 60730; CSA C22.2 No. 77 DANGER
+ CAN/CSA-E60730-1; EAC Heavy and unwieldy device.
Crushing hazard
With regard to cyclic speed loads, note that the rotating parts of
→ Do not grasp or transport the device by the fan impeller.
the device are designed for a maximum of one million load
Move the device with a crane using ropes or cloth straps.
cycles. If you have special questions, consult ebm-papst for
There are holes drilled in the support structure that can be
support.
used for transport.
; Use the device in accordance with its degree of protection.
→ After installation, ensure that the blades on the fan
Information on surface quality impeller are not deformed or bent.
The surfaces of the products conform to the generally applicable industrial CAUTION
standard. The surface quality may change during the production period. Risk of cutting and crushing when removing device
This has no effect on strength, dimensional stability and dimensional from packaging
accuracy. → Carefully remove the device from the packaging by grasping
The color pigments in the paints used perceptibly react to UV light over hold of the frame. Never subject to any impact.
the course of time. This does not however in any way affect the
→ Wear safety shoes and cut-resistant safety gloves.
technical properties of the products. The product is to be protected against
UV radiation to prevent the formation of patches and fading. Changes in CAUTION
color are not a reason for complaint and are not covered by the warranty. Device weighs over 25 kg! Heavy load when unpacking
device.
3.5 Mounting data Risk of physical injury, such as back injuries.
Strength class of 10.9 → Use suitable hoisting equipment to remove the device from
screws its packaging.
; Secure the screws against unintentional loosening (e.g. use self- NOTE
locking screws). Damage to the device from vibration
Any further mounting data required can be taken from the product Bearing damage, shorter service life
drawing or Section Chapter 4.1 Mechanical connection. → The fan must not be subjected to force or excessive vibration
from sections of the installation. #It is advisable to use spring
3.6 Transport and storage conditions or rubber isolators for decoupling (not included in scope of
delivery). The fan is to be operated sufficiently far away from
Max. permitted +80 °C the resonant frequency of the vibration isolators. #If the fan is
ambient temp. for connected to air ducts, the connection should be isolated
motor (transport/ from vibration, e.g. using compensators or similar elements.
storage)
→ Ensure stress-free attachment of the fan to the sub-structure.
Min. permitted -40 °C
ambient temp. for ; The fan may not be handled in the area around the inlet nozzle during
motor (transport/ transport and installation.
storage) There is a risk of damage to the impeller.
Translation of the original operating instructions

; Check the device for transport damage. Damaged devices are not to
3.7 Electromagnetic compatibility be installed.
EMC immunity to According to EN 61000-6-2 (industrial ; Install the undamaged device in accordance with your application.
interference environment)
4.1.1 Installation of RadiPac fan
EMC interference According to EN 61000-6-4 (industrial
emission environment) During installation, transport the RadiPac only with suitable hoisting and
supporting equipment. Use only suitable ropes or chains (see Chapter
3.4 Technical description for product weight). Note that the angle
between the ropes or chains may be between 0° and 60°. To attach the
hoisting equipment, use four M10 eye bolts that can turn under load;
screw the eye bolts into the available threaded holes. Do not use
standard DIN 580 eye bolts. The maximum acceleration during transport
may not exceed 2 g.

Item no. 55793-5-9970 · ENU · Change 94781 · Approved 2018-01-23 · Page 6 / 15

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
K3GA00-PV03-01
Operating instructions

NOTE
Device malfunctions possible
Route the device's control lines separately from the supply line.
→ Maintain the greatest possible clearance.
Recommendation: clearance > 10 cm (separate cable
routing)
NOTE
Water ingress into wires or cables
Water ingress at the customer end of the cable can damage the
device.
→ Make sure the end of the cable is connected in a dry
environment.
Only connect the device to circuits that can be switched off with
an all-pole disconnection switch.

Fig. 1: Illustration showing transport of RadiPac fan 4.2.1 Requirements


CAUTION ; Check whether the information on the nameplate matches the
Possible damage to the device connection data.
If the device slips during installation, serious damage can result. ; Before connecting the device, make sure the power supply matches
→ Ensure that the device is securely positioned at its place of the device voltage.
installation until all fastening screws have been tightened. ; Only use cables designed for the current level indicated on the
● The fan must not be strained on fastening. nameplate.
For determining the cross-section, note the sizing criteria according
4.2 Electrical connection to EN 61800-5-1. The protective earth must have a cross-section
equal to or greater than that of the phase conductor.
DANGER We recommend the use of 105 °C cables. Ensure that the minimum
Voltage on the device cable cross-section is at least
Electric shock AWG 26 / 0.13 mm².
→ Always connect a protective earth first.
Protective earth contact resistance according to EN 61800-5-1
→ Check the protective earth.
Compliance with the resistance specifications according to EN 61800-5-
DANGER 1 for the protective earth connection circuit must be verified in the end
Faulty insulation application. Depending on the installation situation, it may be necessary
Risk of fatal injury from electric shock to connect an additional protective earth conductor by way of the extra
→ Use only cables that meet the specified installation protective earth terminal provided on the device. The protective earth
regulations for voltage, current, insulation material, capacity, terminal is located on the housing and provided with a protective earth
etc. symbol and a hole.
→ Route cables so that they cannot be touched by any
4.2.2 Supply connection and fuses
rotating parts.
Assignment of supply cable cross-sections and their required fuses (line
Translation of the original operating instructions

DANGER
protection only, no equipment protection).
Electrical charge (>50 µC) between phase conductor and
protective earth connection after switching off supply Nominal Fuse Automatic Cable Cable
with multiple devices connected in parallel. voltage circuit cross- cross-
Electric shock, risk of injury breaker section section
→ Ensure sufficient protection against accidental contact. VDE UL VDE mm² *AWG
Before working on the electrical hookup, short the supply 3/PE AC 20 A 20 A C20A 2.5 14
and PE connections. 380-480
VAC
CAUTION 3/PE AC 25 A 25 A C25A 4.0 12
Voltage 380-480
The fan is a built-in component and has no disconnecting switch. VAC
→ Only connect the fan to circuits that can be switched off with
an all-pole disconnection switch. * AWG = American Wire Gauge
→ When working on the fan, secure the system/machine in
which the fan is installed so as to prevent it from being
switched back on.

Item no. 55793-5-9970 · ENU · Change 94781 · Approved 2018-01-23 · Page 7 / 15

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
K3GA00-PV03-01
Operating instructions

4.2.3 Reactive currents 4.3.2 Connecting wires to terminals


Because of the EMC filter integrated for compliance with EMC WARNING
limits (interference emission and immunity to interference), Live terminals and connections even with device
reactive currents can be measured in the supply line even switched off
when the motor is at a standstill and the line voltage is switched Electric shock
on. → Wait five minutes after disconnecting the voltage at all poles
● The values are typically in the range < 350 mA. before opening the device.
● At the same time, the effective power in this operating state ; Remove the cap from the cable gland.
(operational readiness) is typically < 6 W. Only remove caps where cables are fed in.
4.2.4 Residual current circuit breaker (RCCB) ; Route the wire(s) (not included in scope of delivery) into the terminal
box.
If the use of a residual current device (RCD) is required in your ; First connect the "PE" (protective earth).
installation, only AC/DC-sensitive residual current devices
(type B or B+) are permissible. As with variable frequency ; Connect the wires to the corresponding terminals.
drives, residual current devices cannot provide personal safety Use a screwdriver to do so.
while operating the device. When the device power supply is When connecting, ensure that no wire ends fan out.
switched on, pulsed charging currents from the capacitors in the
integrated EMC filter can lead to the instant tripping of residual
current devices. We recommend the use of residual current
circuit breakers (RCCB) with a trip threshold of 300 mA and
delayed tripping (super-resistant, characteristic K).

4.2.5 Leakage current


For asymmetrical power systems or if a phase fails, the
leakage current can increase to a multiple of the nominal value.

4.2.6 Locked-rotor protection


Due to the locked-rotor protection, the starting current (LRA) is
equal to or less than the nominal current (FLA).

4.3 Connection in terminal box

4.3.1 Preparing cables for connection


Only strip the cable as far as necessary, ensuring that the cable gland is
sealed and there is no strain on the connections. For tightening torques,
see Chapter 3.1 Product drawing.
NOTE
Tightness and strain relief are dependent on the cable
Translation of the original operating instructions

used.
→ This must be checked by the user.

Fig. 3: Connecting wires to terminals


; Seal the terminal box.

4.3.3 Cable routing


Water must be prevented from reaching the cable gland along the cable.
NOTE
Damage caused by moisture penetration.
Moisture can penetrate into the terminal box if water is
constantly present at the cable glands.
Fig. 2: Recommended stripped lengths in mm (inside terminal box)
→ To prevent the constant accumulation of water at the cable
Legend: CL = control lines
glands, the cable should be routed in a U-shaped loop
wherever possible.# If this is not possible, a drip edge can

Item no. 55793-5-9970 · ENU · Change 94781 · Approved 2018-01-23 · Page 8 / 15

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
K3GA00-PV03-01
Operating instructions

be produced by fitting a cable tie directly in front of the cable


gland for example.

4.4 Factory settings


Factory settings made for the device by ebm-papst.
Mode parameter set 1 PWM control
Mode parameter set 2 PWM control
Fan/device address 01
Max. PWM / % 100
Min. PWM / % 5
Save set value to Yes
EEPROM
Set value requirement Analog (linear)
Direction of action Positive (heating)
parameter set 1
Direction of action Positive (heating)
parameter set 2
Translation of the original operating instructions

Item no. 55793-5-9970 · ENU · Change 94781 · Approved 2018-01-23 · Page 9 / 15

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
K3GA00-PV03-01
Operating instructions

4.5 Connection diagram


Translation of the original operating instructions

Drawing preliminary!

No. Conn. Designation Function/assignment


KL 1 1 L1 Supply connection, power supply; for nominal voltage range see technical data
KL 1 2 L2 Supply connection, power supply; for nominal voltage range see technical data
KL 1 3 L3 Supply connection, power supply; for nominal voltage range see technical data
PE PE Ground connection, PE connection
KL 2 1 NO Status relay, floating status contact, make for failure
KL2 2 COM Status relay, floating status contact, changeover contact, common connection, contact rating 250 VAC/max. 2
A (AC1)/min. 10 mA
KL2 3 NC Status relay, floating status contact, break for failure
KL 3 1 RSA Bus connection RS485, RSA, MODBUS-RTU; SELV
KL 3 2 RSB Bus connection RS485, RSB, MODBUS-RTU; SELV
KL 3 3 / 10 GND Reference ground for control interface; SELV
KL 3 4 Ain1 U Analog input 1, set value: 0-10 V, Ri = 100 kΩ, adjustable curve, only usable as alternative to input Ain1 I;
SELV
KL 3 5 + 10 V Fixed voltage output 10 VDC, + 10 V +/-3%, max. 10 mA, short-circuit-proof, power supply for ext. devices
(e.g. potentiometers); SELV

Item no. 55793-5-9970 · ENU · Change 94781 · Approved 2018-01-23 · Page 10 / 15

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
K3GA00-PV03-01
Operating instructions

No. Conn. Designation Function/assignment


KL 3 6 Ain1 I Analog input 1, set value: 4-20 mA, Ri = 100 Ω, adjustable curve, only usable as alternative to input Ain1 U;
SELV
KL 3 7 Din1 Digital input 1: enable electronics,
enable: pin open or applied voltage 5-50 VDC
disable: bridge to GND or applied voltage < 1 VDC
reset function: triggers software reset after a level change to < 1 VDC; SELV
KL 3 8 Din2 Digital input 2: Switching parameter sets 1/2, according to EEPROM setting, the valid or used parameter set
can be selected via bus or via digital input DIN2.
Parameter set 1: pin open or applied voltage 5-50 VDC
Parameter set 2: bridge to GND or applied voltage < 1 VDC; SELV
KL 3 9 Din3 Digital input 3: according to EEPROM setting, the integrated controller's direction of action can be selected via
bus or digital input Din3;
normal: pin open or applied voltage 5-50 VDC
inverse: bridge to GND or applied voltage < 1 VDC; SELV
KL 3 11 Ain2 U Analog input 2, measured value: 0-10 V, Ri = 100 kΩ, adjustable curve, only usable as alternative to input
Ain2 I; SELV
KL 3 12 + 20 V Fixed voltage output 20 VDC, + 20 V +25/-10%, max. 50 mA, short-circuit-proof, power supply for ext.
devices (e.g. sensors); SELV
Alternatively: +24 VDC input for parameterization without line voltage
KL 3 13 Ain2 I Analog input 2, measured value: 4-20 mA, Ri = 100 Ω, adjustable curve, only usable as alternative to input
Ain2 U; SELV
KL 3 14 Aout Analog output 0-10 VDC, max. 5 mA, output of current motor modulation level / motor speed
adjustable curve; SELV
Translation of the original operating instructions

Item no. 55793-5-9970 · ENU · Change 94781 · Approved 2018-01-23 · Page 11 / 15

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
K3GA00-PV03-01
Operating instructions

4.6 Checking connections 4.8 Switching off the device


; Ensure isolation from supply (all phases). Switching off the device during operation:
; Make sure a restart is impossible ; Switch off the device via the control input.
; Check the cables for proper fit. ; Do not switch the motor (e.g. in cyclic operation) on and off via power
; Screw the terminal box cover back on again. Terminal box tightening supply.
torque, see Chapter 3.1 Product drawing. Switching off the device for maintenance:
; Route the cables in the terminal box so that the terminal box cover ; Switch off the device via the control input.
closes without resistance. ; Do not switch the motor (e.g. in cyclic operation) on and off via power
; Use all screw plugs. Insert the screws by hand to avoid damage to supply.
the threads. ; Disconnect the device from the power supply.
; Make sure the terminal box is completely closed and sealed and that ; When disconnecting, be sure to disconnect the ground connection last.
all screws and cable glands have been properly tightened.

4.7 Switching on the device


5. INTEGRATED PROTECTIVE FEATURES
The device may only be switched on if it has been installed properly and
in accordance with its intended use, including the required safety The integrated protective functions cause the motor to switch off
mechanisms and professional electrical hookup. This also applies for automatically in the event of the faults described in the table.
devices which have already been equipped with plugs and terminals or Fault Safety feature description/
similar connectors by the customer. function
WARNING Rotor position detection error An automatic restart follows.
Hot motor housing Blocked rotor ; After the blockage is
Risk of fire removed, the motor restarts
automatically.
→ Ensure that no combustible or flammable materials are
located close to the fan. Line undervoltage (line voltage ; If the line voltage returns to
outside of permitted nominal permitted values, the motor
; Before switching on, check the device for visible external damage voltage range) restarts automatically.
and make sure the protective devices are functional.
Phase failure A phase of the supply voltage
; Check the fan's air flow paths for foreign matter and remove any fails for at least 5 s.
foreign matter found. ; When all phases are correctly
; Apply the nominal supply voltage. supplied again, the motor
; Start the device by changing the input signal. automatically restarts after 10-40
s.
NOTE
Damage to the device from vibration
Bearing damage, shorter service life
→ Low-vibration operation of the fan must be ensured over the
entire speed control range. #Severe vibration can arise for
instance from inexpert handling, transportation damage and
resultant imbalance or be caused by component or structural
resonance. #Speed ranges with excessively high vibration
Translation of the original operating instructions

levels and possibly resonant frequencies must be


determined in the course of fan commissioning. #Either run
through the resonant range as quickly as possible with
speed control or find another remedy.# Operation with
excessively high vibration levels can lead to premature
failure.

→ The maximum permissible vibration severity must not


exceed 3.5 mm/s and should be checked at intervals of 6
months. #It is to be measured at the motor mount at the
motor support plate in all three 3 dimensions, see Chapter 6.
Maintenance, malfunctions, possible causes and remedies.

Item no. 55793-5-9970 · ENU · Change 94781 · Approved 2018-01-23 · Page 12 / 15

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
K3GA00-PV03-01
Operating instructions

6. MAINTENANCE, MALFUNCTIONS, POSSIBLE Deficient cooling Improve cooling. Let


the device cool down.
CAUSES AND REMEDIES To reset the error
Do not perform any repairs on your device. Send the device to ebm- message, switch off
papst for repair or replacement. the line voltage for at
least 25 s and then
WARNING switch it on again.
Live terminals and connections even with device Alternatively, reset
switched off the error message by
Electric shock applying a control
→ Wait five minutes after disconnecting the voltage at all poles signal of < 0.5 V to
before opening the device. Din1 or by shorting
CAUTION Din1 to GND.
If control voltage or a stored speed set value is applied, Ambient temperature Reduce the ambient
the motor will restart automatically, e.g. after a power too high temperature. Let the
failure. device cool down.
Risk of injury To reset the error
message, switch off
→ Keep out of the device’s danger zone.# When working on
the line voltage for at
the device, switch off the line voltage and ensure that it
least 25 s and then
cannot be switched back on.
switch it on again.
→ Wait until the device comes to a stop. Alternatively, reset
→ After working on the device, remove any tools or other the error message by
objects from the device. applying a control
signal of < 0.5 V to
If the device is out of use for over four months, we recommend Din1 or by shorting
switching it on for at least four hours at full speed to allow any Din1 to GND.
condensation to evaporate and to move the bearings.
Impermissible point of Correct the operating
Malfunction/fault Possible cause Possible remedy operation (e.g. back point. Let the device
Impeller not Imbalance in rotating Clean the device; pressure too high) cool down.
running smoothly parts replace it if imbalance To reset the error
persists after cleaning. message, switch off
Make sure no the line voltage for at
weight clips are least 25 s and then
removed during switch it on again.
cleaning. Alternatively, reset
Motor not turning Mechanical blockage Switch off, isolate the error message by
from supply and applying a control
remove mechanical signal of < 0.5 V to
blockage. Din1 or by shorting
Line voltage faulty Check line voltage, Din1 to GND.
restore power supply.
Attention! The error In the event of further malfunctions, contact ebm-papst.
Translation of the original operating instructions

message resets
automatically.
Device restarts 6.1 Vibration testing
automatically without
warning. Checking of fan for mechanical vibration based on ISO 14694.
Recommendation: Every 6 months. Max. vibration severity is 3.5 mm/
Faulty connection Isolate from supply,
s, measured at the motor fastening diameter on the motor support plate in
correct connection;
the direction of the motor axis of rotation and perpendicular to this.
see connection
diagram.
Broken motor winding Replace device

Item no. 55793-5-9970 · ENU · Change 94781 · Approved 2018-01-23 · Page 13 / 15

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
K3GA00-PV03-01
Operating instructions

Tightness of Visual inspection At least every Retighten,


cable gland 6 months replace if
damaged
Condensation Visual inspection At least every Open holes
drainage holes 6 months
for clogging,
where necessary
Abnormal acoustic At least every Replace device
bearing noise 6 months
Vibration test Vibration tester, Recommended Clean impeller
start-up or every 6 months or replace device
deceleration
measurement

6.4 Disposal
For ebm-papst, environmental protection and resource preservation are
Fig. 4: Example illustrating vibration measurement. The arrangement of top priority corporate goals.
the sensors depends on the device concerned and the installation ebm-papst operates an environmental management system which is
certified in accordance with ISO 14001 and rigorously implemented
situation.
around the world on the basis of German standards.
6.2 Cleaning Right from the development stage, ecological design, technical safety
and health protection are fixed criteria.
NOTE The following section contains recommendations for ecological disposal
Damage to the device during cleaning of the product and its components.
Malfunction possible 6.4.1 Country-specific legal requirements
→ Do not clean the device using a water jet or high-pressure
cleaner. NOTE
Country-specific legal requirements
→ Do not use any acid, alkali or solvent-basedcleaning
Always observe the applicable country-specific legal
agents.
regulations with regard to the disposal of products or waste
→ Do not use any pointed or sharp-edged objects for cleaning occurring in the various phases of the life cycle. The
corresponding disposal standards are also to be heeded.
6.3 Safety inspection
6.4.2 Disassembly
NOTE
High-voltage test Disassembly of the product must be performed or supervised by
The integrated EMC filter has Y capacitors. The tripping current qualified personnel with the appropriate technical knowledge.
is exceeded when AC testing voltage is applied. The product is to be disassembled into suitable components for disposal
→ Test the device with DC voltage when you perform the employing standard procedures for motors.
legally required high-voltage test. The voltage to be used WARNING
corresponds to the peak value of the AC voltage required by Heavy parts of the product may drop off. Some of the
the standard. product components are heavy. These components
Translation of the original operating instructions

What to check How to check How often What action? could drop off during disassembly.
This can result in fatal or serious injury and material damage.
Contact Visual inspection At least every Repair or
protection 6 months replacement of → Secure components before unfastening to stop them falling.
cover for device
6.4.3 Component disposal
intactness or
damage The products are mostly made of steel, copper, aluminum and plastic.
Device for Visual inspection At least every Replacement of Metallic materials are generally considered to be fully recyclable.
damage to 6 months device Separate the components for recycling into the following categories:
blades and ● Steel and iron
housing
● Aluminum
Fastening the Visual inspection At least every Fasten
cables 6 months ● Non-ferrous metal, e.g. motor windings
Insulation of Visual inspection At least every Replace cables ● Plastics, particularly with brominated flame retardants, in accordance
cables for 6 months with marking
damage ● Insulating materials
Impeller for Visual inspection At least every Clean impeller ● Cables and wires
wear/deposits/ 6 months or replace device
corrosion and ● Electronic scrap, e.g. circuit boards
damage

Item no. 55793-5-9970 · ENU · Change 94781 · Approved 2018-01-23 · Page 14 / 15

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
K3GA00-PV03-01
Operating instructions

Only ferrite magnets and not rare earth magnets are used in external
rotor motors from ebm-papst Mulfingen GmbH & Co. KG.
; Ferrite magnets can be disposed of in the same way as normal iron
and steel.
Electrical insulating materials on the product, in cables and wires are
made of similar materials and are therefore to be treated in the same
manner.
The materials concerned are as follows:
● Miscellaneous insulators used in the terminal box
● Power cables
● Cables for internal wiring
● Electrolytic capacitors
Dispose of electronic components employing the proper procedures for
electronic scrap.

→ Please contact ebm-papst for any other questions on disposal.


Translation of the original operating instructions

Item no. 55793-5-9970 · ENU · Change 94781 · Approved 2018-01-23 · Page 15 / 15