Bangladesh Power Development Board


CERS FORM No-21/A2

TRANSFORMER OIL TEST REPORT.


Sender: Executive Engineer, Project Division-1, Power Distribution System Development Project, Sylhet
Division, BPDB, Sylhet.
Reference No: 27.11.9100.728.07.006.21-563 , Dated:-.14/06/2021
Sample of Transformer: 20/26MVA,T-1 Transformer, Sl. No.- TB 190077 .
From (Station): 33/11KV, 2 x 20/26MVA Botteswar GIS Substation, BPDB,Sylhet.
No. Of Sample Supplied: 03 (three) nos.
CERS Received No.- 2316 , Dated :15/06/2021
CERS I.T No:21061542.
Standard Test value of Oil.
Sl. Test
Characteristics Value T-1, Sl. No: TB 190077
No. Method
Main Tank Middle valve OLTC
1. Appearance IEC 296 -- Clear Clear Clear
System Good > 40 KV 47 23 13
Dielectric Breakdown Voltage
2.
Voltage (KV)
IEC 156 below or
Fair 30 to 40 KV -- -- --
equal 72.5 KV Poor < 30 KV -- -- --
Serviceaged Oil
2.0 at 900c. (Maxm) -- -- --
Dielectric Dissipation IEC 247
1.0 at 260c. (Maxm) -- -- --
3.
Factor (tan δ) at 26°c.(%) 0.5 at 900c. (Maxm) -- -- --
New oil
0.2 at 260c. (Maxm) -- -- --
4. Dielectric Constant BS 148 2.2 -- -- --
5. Resistivity (Ohm. cm) at 26°c. IEC 296 1x10 Ohm. Cm (Minm)
14
3x1014 8x1013 5x1012
6. Specific Gravity at 26°c. IEC 296 0.895 at 200c gm/cm3(Maxm) 0.875 0.875 0.875
System Voltage Good < 30 PPM
IEC
7. Moisture Content 26°c. 60814
below or equal 72.5 Fair 30 to 40 PPM 29 41 57
KV Poor > 40 PPM
Good > 28 mN/m
IEC
8. Interfacial Tension 26°c. 60422
Fair 22 to 28 mN/m -- -- --
Poor < 22 mN/m
Remarks: -
a) Main tank results are good.
b) Middle valve & OLTC results are poor.
c) Oil need to be centrifuge by following instructions, than send again to CERS, Tongi for test.
 Using 10µm inlet filter & 0.1 µm outlet filter.
 Operating temperature should not be above 60oC.
 Maintain vacuum pressure 0.08 to 0.1 Mpa.

Sub-Assistant Engineer Assistant/Sub-Divisional Executive Engineer


CERS,BPDB,Tongi,Gazipur. Engineer CERS,
Ò‡kL nvwmbvi D‡`¨vM, N‡i N‡i we`y¨rÓ

evsjv‡`k we`y¨r
ZË¡veavqK cÖ‡KŠkjxi `ßi
wmBAviGm, weD‡ev, UsMx,
MvRxcyi|

Dbœqb †evW© ‡Uwj‡db t 9811178,d¨v·t 9811182|

Bangladesh Power Development Board


CERS FORM No-21/A2

TRANSFORMER OIL TEST REPORT.


Sender: Executive Engineer, Project Division-1, Power Distribution System Development Project, Sylhet
Division, BPDB, Sylhet.
Reference No: 27.11.9100.728.07.006.21-563 , Dated:-.14/06/2021
Sample of Transformer: 20/26MVA,T-2 Transformer, Sl. No.- TB 190078 .
From (Station): 33/11KV, 2 x 20/26MVA Botteswar GIS Substation, BPDB,Sylhet.
No. Of Sample Supplied: 03 (three) nos.
CERS Received No.- 2316 , Dated :15/06/2021
CERS I.T No:21061542.
Standard Test value of Oil.
Sl. Test
Characteristics Value T-2, Sl. No: TB 190078
No. Method
Main Tank Middle valve OLTC
1. Appearance IEC 296 -- Clear Clear Clear
System Good > 40 KV 29 34 13
Dielectric Breakdown Voltage
2.
Voltage (KV)
IEC 156 below or
Fair 30 to 40 KV -- -- --
equal 72.5 KV Poor < 30 KV -- -- --
Serviceaged Oil
2.0 at 900c. (Maxm) -- -- --
Dielectric Dissipation IEC 247
1.0 at 260c. (Maxm) -- -- --
3.
Factor (tan δ) at 26°c.(%) 0.5 at 900c. (Maxm) -- -- --
New oil
0.2 at 260c. (Maxm) -- -- --
4. Dielectric Constant BS 148 2.2 -- -- --
5. Resistivity (Ohm. cm) at 26°c. IEC 296 1x10 Ohm. Cm (Minm)
14
1x1014 3x1014 5x1013
6. Specific Gravity at 26°c. IEC 296 0.895 at 200c gm/cm3(Maxm) 0.875 0.875 0.875
System Voltage Good < 30 PPM
IEC
7. Moisture Content 26°c. 60814
below or equal 72.5 Fair 30 to 40 PPM 40 31 42
KV Poor > 40 PPM
Good > 28 mN/m
IEC
8. Interfacial Tension 26°c. 60422
Fair 22 to 28 mN/m -- -- --
Poor < 22 mN/m
Remarks: -
a) Middle valve results are fair.
b) Main tank & OLTC results are poor.
c) Oil need to be centrifuge by following instructions, than send again to CERS, Tongi for test.
 Using 10µm inlet filter & 0.1 µm outlet filter.
 Operating temperature should not be above 60oC.
 Maintain vacuum pressure 0.08 to 0.1 Mpa.
Ò‡kL nvwmbvi D‡`¨vM, N‡i N‡i we`y¨rÓ

evsjv‡`k we`y¨r
ZË¡veavqK cÖ‡KŠkjxi `ßi
wmBAviGm, weD‡ev, UsMx,
MvRxcyi|

Dbœqb
Sub-Assistant Engineer
CERS,BPDB,Tongi,Gazipur.
†evW©
Assistant/Sub-Divisional
Engineer CERS,
‡Uwj‡db t 9811178,d¨v·t 9811182|
Executive Engineer

Bangladesh Power Development


CERS,BPDB,Tongi,Gazipur Board
BPDB,Tongi,Gazipur.

CERS FORM No-21/A2

TRANSFORMER OIL (DGA) TEST REPORT.


Sender: Executive Engineer, Project Division-1, Power Distribution System Development Project, Sylhet
Division, BPDB, Sylhet.
Reference No: 27.11.9100.728.07.006.21-563 , Dated:-.14/06/2021
Sample of Transformer: 20/26MVA,T-1 Transformer, Sl. No.- TB 190077 .
From (Station): 33/11KV, 2 x 20/26MVA Botteswar GIS Substation, BPDB,Sylhet.
No. Of Sample Supplied: 03 (three) nos.
CERS Received No.- 2316 , Dated :15/06/2021
CERS I.T No:21061542.

Name of Dissolve Gases


Test value of Oil. IEEE C57.104 Limits (ppm)* Results
Main Tank Middle valve OLTC Normal Warning
Hydrogen H2 <5 <5 <5 ≤ 100 > 700 According to
IEEE C57.104
Carbon Di Oxide CO2 737 1023 740 ≤ 2500 > 4000 TM guide line,
DGA test data
Carbon Monoxide CO 19 10 10 ≤ 350 > 570
is satisfactory.
Ethylene C2H4 7 10 7 ≤ 50 > 100

Ethane C2H6 5 1 12 ≤ 65 > 100

Methane CH4 3 5 <1 ≤ 120 > 400

Acetylene C2H2 <0.5 0.5 <0.5 ≤1 >9

TDCG 34 26 30 ≤ 720 > 1920

Sub-Assistant Engineer Assistant/Sub-Divisional Executive Engineer


CERS,BPDB,Tongi,Gazipur. Engineer CERS,
CERS,BPDB,Tongi,Gazipur BPDB,Tongi,Gazipur.
Ò‡kL nvwmbvi D‡`¨vM, N‡i N‡i we`y¨rÓ

evsjv‡`k we`y¨r
ZË¡veavqK cÖ‡KŠkjxi `ßi
wmBAviGm, weD‡ev, UsMx,
MvRxcyi|

Dbœqb †evW© ‡Uwj‡db t 9811178,d¨v·t 9811182|

Bangladesh Power Development Board

CERS FORM No-21/A2

TRANSFORMER OIL (DGA) TEST REPORT.


Sender: Executive Engineer, Project Division-1, Power Distribution System Development Project, Sylhet
Division, BPDB, Sylhet.
Reference No: 27.11.9100.728.07.006.21-563 , Dated:-.14/06/2021
Sample of Transformer: 20/26MVA,T-2 Transformer, Sl. No.- TB 190078 .
From (Station): 33/11KV, 2 x 20/26MVA Botteswar GIS Substation, BPDB,Sylhet.
No. Of Sample Supplied: 03 (three) nos.
CERS Received No.- 2316 , Dated :15/06/2021
CERS I.T No:21061542.

Name of Dissolve Gases


Test value of Oil. IEEE C57.104 Limits (ppm)* Results
Main Tank Middle valve OLTC Normal Warning
Hydrogen H2 <5 <5 <5 ≤ 100 > 700 According to
IEEE C57.104
Carbon Di Oxide CO2 647 664 373 ≤ 2500 > 4000 TM guide line,
DGA test data
Carbon Monoxide CO 15 17 3 ≤ 350 > 570
is satisfactory.
Ethylene C2H4 4 4 10 ≤ 50 > 100

Ethane C2H6 4 9 12 ≤ 65 > 100

Methane CH4 1 7 9 ≤ 120 > 400

Acetylene C2H2 0 0 0 ≤1 >9

TDCG 24 36 33 ≤ 720 > 1920

Sub-Assistant Engineer Assistant/Sub-Divisional Executive Engineer


CERS,BPDB,Tongi,Gazipur. Engineer CERS,
CERS,BPDB,Tongi,Gazipur BPDB,Tongi,Gazipur.
Ò‡kL nvwmbvi D‡`¨vM, N‡i N‡i we`y¨rÓ

evsjv‡`k we`y¨r
ZË¡veavqK cÖ‡KŠkjxi `ßi
wmBAviGm, weD‡ev, UsMx,
MvRxcyi|

Dbœqb †evW© ‡Uwj‡db t 9811178,d¨v·t 9811182|

Bangladesh Power Development Board


Memo No: 27.11.3300.512.47.001.21. Dated: / / 2021.

Executive Engineer
Project Division-1
Power Distribution System Development Project
Sylhet Division, BPDB, Sylhet.
Subject: Transformer oil test bill.
Reference No: 27.11.9100.728.07.006.21-563, Dated:- 6/14/2021.
CERS Received No.-2316, Dated :6/15/2021.
CERS I.T No: 21061542.
The following bill has to be paid by depositing Pay-order/Bank draft in favor of Deputy Director
(Account) RAO,BPDB, Tongi, Account no: SND-66, Pubali Bank, Tongi Branch, Gazipur. Testing process
will start after submitting that Pay-order/Bank draft to the office of the undersigned.
Sl. No Test Name Number of Sample Bill/Sample Total (Taka)
1. Dielectric Breakdown Voltage Test 06(Six) 225/- 1350
2. Resistivity Test 06(Six) 300/- 1800
3. Specific Gravity Test 06(Six) 225/- 1350
4. Moisture Content Test 06(Six) 2000/- 12000
5. Dissolved Gas Analysis (DGA) Test 06(Six) 10000/- 60000
In Word: Seventy six thousands five hundred taka only Total Bill: 76500

Sub-Assistant Engineer Assistant/Sub-Divisional Engineer


CERS, BPDB, Tongi, Gazipur. CERS, BPDB, Tongi, Gazipur.
Bill No...333....... Bill Date:....6/15/2021........

Executive Engineer.
Division-3
CERS, BPDB, Tongi, Gazipur.
Memo No: 27.11.3300.512.47.001.21. Dated: / / 2021.
Copy to:-
1. Sub-Divisional Engineer, Oil Test Section, CERS, BPDB, Tongi, Gazipur.
2. Master Copy.
3. Office Copy.

Executive Engineer.
Ò‡kL nvwmbvi D‡`¨vM, N‡i N‡i we`y¨rÓ

evsjv‡`k we`y¨r
ZË¡veavqK cÖ‡KŠkjxi `ßi
wmBAviGm, weD‡ev, UsMx,
MvRxcyi|

Dbœqb †evW© ‡Uwj‡db t 9811178,d¨v·t 9811182|

Bangladesh Power Development Board


Division-3
CERS, BPDB, Tongi, Gazipur.

Memo No: 27.11.3300.512.47.001.21. Dated: / / 2021.

Executive Engineer
Project Division-1
Power Distribution System Development Project
Sylhet Division, BPDB, Sylhet.

Sub : Test Report of Transformer Oil.


Ref. No. : 27.11.9100.728.07.006.21-563, Dated:-14/06/2021.

Enclosed herewith the Test report of Transformer Oil which was communicated
vide memo under reference for your information & necessary action please.

Enclosed: As stated.

Superintending Engineer
CERS, BPDB, Tongi, Gazipur.