Metal part + Gasket) Metal part + Gasket) for 1 MVA, 1.6 MVA, 2 MVA ,11/0.433 KV transformer: Rated Voltage - 17.5 KV, Rated Current - 250 A, One minute Power frequency withstand Voltage Dry and Wet - 38 KV, Voltage Phase to earth - 12/sqrt(3) KV, Minimum Cantilever Strength - 1000 N, Dry lighting impulse withstand voltage (1.2/50 us) - 95 KV peak, Minimum Creepage Distance - 31 mm/ KV, Standard: IS - 2099, Bushing and metal parts confirm to IS - 3347 & 8603