Temperature Controler TZN-series - Datasheets
Temperature Controler TZN-series - Datasheets
1 Event 1 output
TZ4ST
2 Event 1 + Event 2 output
Option output R Event 1 + PV transmission output(DC4-20mA)
1 Event 1 output
2 Event 1 + Event 2 output
Others R Event 1 + PV transmission output(DC4-20mA)
A Event 1 + Event 2 + PV transmission output(DC4-20mA)
T Event 1 + RS485 communication output
B Event 1 + Event 2 + RS485 communication output
TZN4
S DIN W48×H48mm (terminal block type)
TZ4 SP DIN W48×H48mm (plug type)※2
Size
ST DIN W48×H48mm (terminal block type)
M DIN W72×H72mm
TZ4/TZN4 W DIN W96×H48mm
H DIN W48×H96mm
L DIN W96×H96mm
Digit
4 9999(4digit)
Item TZ Temperature Controller
TZN Temperature Controller
※The unit cannot be configured with any random combination from the above ordering information. Please refer to
Specifications for possible configurations.
※1: Only applies to TZ4SP, TZ4ST, TZ4L, and TZN4M.
※2: 11-pin sockets (PG-11, PS-11(N)) are sold separately.
H-72
Dual PID Auto Tuning Control
Specifications (A)
Photoelectric
Sensors
TZ4SP TZ4M TZ4W TZ4H TZ4L
Series TZ4ST
TZN4S TZN4M TZN4W TZN4H TZN4L (B)
AC power Square shaped noise by noise simulator (pulse width 1㎲) ±2kV R-phase, S-phase (R)
Noise AC/DC※1 Square shaped noise by noise Square shaped noise by noise simulator (pulse width 1㎲) ±2kV R-phase,
Graphic/
Logic
power simulator (pulse width 1㎲) ±500V S-phase Panels
R-phase, S-phase
Memory retention Approx. 10 years (non-volatile semiconductor memory type) (S)
Field
Environ- Ambient temp. -10 to 50℃, storage: -20 to 60℃
Network
Devices
ment Ambient humi. 35 to 85%RH, storage: 35 to 85%RH
Approval (except AC/DC power type) (T)
Software
TZ4SP: TZ4M: TZ4W: TZ4H: TZ4L:
Approx. 205g Approx. 360g Approx. 365g Approx. 365g Approx. 474g
※2 (Approx. 144g) Approx. 218g (Approx. 228g) (Approx. 246g) (Approx. 246g) (Approx. 304g)
Weight
TZN4S: (Approx. 162g) TZN4M: TZN4W: TZN4H: TZN4L:
Approx. 226g Approx.355g Approx. 351g Approx. 351g Approx. 474g
(Approx. 164g) (Approx. 246g) (Approx. 232g) (Approx. 232g) (Approx. 303g)
※1: AC/DC power models are only available for TZ4SP, TZ4ST, TZ4L, TZN4M
※2: The weight includes packaging. The weight in parentheses is for unit only.
※Environment resistance is rated at no freezing or condensation.
H-73
TZN/TZ Series
Connections
※RTD: DPt100Ω (3-wire type), JPt100Ω (3-wire type) ※T.C (Thermocouple): K, J, R, E, T, S, W, N
※In case of Analog input, please use T.C (Thermocouple) terminal and be careful about polarity.
TZ4SP
SV2 IN
Max.5VDC
250㎂
6 + SOURCE
- B'
5 7 - 100-240VAC 50/60Hz 5VA
TC 24VAC 50/60Hz 7VA MAIN OUT
B 8 24-48VDC 6W
+ 4
SSR Current
SENSOR - H
A 9 - -
3 9
RTD + C
MAIN OUT 9
10 250VAC 3A 1c V mA
2 Resistive load
EV1 OUT 11 10 + 10
250VAC 1 L +
1A 1a 12VDC ±3V DC4-20mA
30mA Max. Load 600Ω Max.
TZ4ST
PV OUT
DC4-20mA
EV2 OUT 250VAC 1A 1a
+
SV2 IN 1 5 10 +
SOURCE
Max.5VDC 100-240VAC 50/60Hz 5VA MAIN OUT
-
250㎂
-
2 6 -
11 24VAC 50/60Hz 7VA SSR Current
B' 24-48VDC 6W
TC -
+ B 3 7 12 H - -
MAIN OUT 12 12
SENSOR + C V
A 4 8 13 250VAC 3A 1c 13 13
mA
TZN4S
TZ4M
-
EV1 OUT
250VAC
6 13 H
1A 1a MAIN OUT
EV2 OUT
5 12 +
C
250VAC 3A 1c
Resistive load
250VAC
1A 1a 4 11 L
RS485(A+) + MAIN OUT
-
B'
3 SV2 IN 10 PV OUT SSR Current
TC Max.5VDC DC4-20mA
+ B 2 250㎂ 9 RS485(B-) - - -
SENSOR A 1 8 13 13
V mA
RTD
14 15 16 SOURCE 12 12
7 100-240VAC + +
50/60Hz 6VA 12VDC ±3V DC4-20mA
30mA Max. Load 600Ω Max.
H-74
Dual PID Auto Tuning Control
TZN4M (A)
Photoelectric
Sensors
-
EV1 OUT H
250VAC 1A 1a MAIN OUT (B)
+ Fiber
250VAC 3A 1c MAIN OUT Optic
EV2 OUT C Resistive load Sensors
250VAC 1A 1a L SSR Current
- - (C)
B' RS485(A+) + Door/Area
- 7 7 mA
Sensors
V
TC PV OUT
+ B SV2 IN
DC4-20mA 6 6
Max.5VDC + + (D)
RS485(B-) -
250㎂ Proximity
SENSOR A 12VDC ±3V DC4-20mA Sensors
RTD + 30mA Max. Load 600Ω Max.
SOURCE
- 100-240VAC 50/60Hz 6VA (E)
24VAC 50/60Hz 8VA Pressure
Sensors
24-48VDC 7W
(F)
TZ4W/TZN4W Rotary
Encoders
MAIN OUT
250VAC 3A 1c PV OUT
Resistive load DC4-20mA SOURCE (G)
100-240VAC Connectors/
H L + - 50/60Hz 6VA Sockets
RS485 RS485
- + C (A+) (B-)
(H)
17 16 15 14 13 12 11 10 9 MAIN OUT Temperature
Controllers
SSR Current
(I)
- - SSRs / Power
8 7 6 5 4 3 2 1 15 15 Controllers
V mA
B' B A 14 14
+ + (J)
RTD 12VDC ±3V DC4-20mA Counters
EV1 OUT EV2 OUT SV2 IN - +
250VAC 250VAC Max.5VDC 30mA Max. Load 600Ω Max.
SENSOR
1A 1a 1A 1a 250㎂ TC
(K)
Timers
TZ4H/TZN4H
(L)
SV2 IN
5 14 +
250VAC 3A 1c SSR Current (N)
Max.5VDC C Resistive load
250㎂ 4 13 L
-
Display
Units
-
RS485(A+) + 15 15
B' 3 12 PV OUT V mA
-
TC DC4-20mA 14 14 (O)
+ B 2 11 + +
Sensor
Controllers
SENSOR RS485(B-) - 12VDC ±3V DC4-20mA
A 1 10 30mA Max. Load 600Ω Max. (P)
RTD SOURCE Switching
9 100-240VAC Mode Power
Supplies
50/60Hz 6VA
(Q)
Stepper Motors
& Drivers
TZ4L/TZN4L
& Controllers
(R)
Graphic/
Logic
EV1 OUT 8 17 Panels
250VAC 1A 1a
EV2 OUT
7 16 (S)
Field
MAIN OUT Network
250VAC 1A 1a -
6 15 H SSR Current
Devices
+ MAIN OUT
SV2 IN 5 14 C
250VAC 3A 1c
- - (T)
Max.5VDC Resistive load
250㎂ 4 13 L 15 15 Software
V mA
RS485(A+) + 14 14
-
B'
3 12 PV OUT
+ +
TC B DC4-20mA 12VDC ±3V DC4-20mA
+ 2 11 30mA Max. Load 600Ω Max.
RS485(B-) -
SENSOR A
1 10 SOURCE
RTD
100-240VAC 50/60Hz 6VA
9 24VAC 50/60Hz 8VA
24-48VDC 7W
H-75
TZN/TZ Series
TZ4SP
48
TEMPERATURE CONTROLLER °C
SV2 PV
AT
OUT
SV
45
EV1
EV2
TZ4SP
TEMPERATURE CONTROLLER
TZ4ST
48
TEMPERATURE CONTROLLER °C
SV2 PV
AT
OUT
SV
45
EV1
EV2
TZ4ST
TEMPERATURE CONTROLLER
8.7 98.8
107.5
TZN4S
48
45
10 79.5 10.5
100
TZ4M
72
67
TZ4M
TEMPERATURE CONTROLLER
13 90 10
113
H-76
Dual PID Auto Tuning Control
(C)
Door/Area
Sensors
67
(D)
Proximity
Sensors
(E)
Pressure
Sensors
10 73
(F)
83 Rotary
Encoders
TZ4W (G)
Connectors/
Sockets
96
(H)
Temperature
SV2 AT OUT EV1 EV2 Controllers
(I)
48
45
SSRs / Power
Controllers
TZ4W
TEMPERATURE CONTROLLER
(J)
Counters
13 90 10
(K)
TZN4W Timers
96 (L)
Panel
Meters
(M)
Tacho /
Speed / Pulse
Meters
48
45
(N)
Display
Units
13 90 10 (O)
Sensor
Controllers
TZ4H (P)
Switching
48 Mode Power
Supplies
(Q)
Stepper Motors
& Drivers
& Controllers
(R)
Graphic/
Logic
Panels
96
90
(S)
SV2 AT OUT EV1 EV2 Field
Network
Devices
(T)
Software
TZ4H
TEMPERATURE CONTROLLER
13 90 10
H-77
TZN/TZ Series
TZN4H (unit: mm)
48
TEMPERATURE CONTROLLER
PV °C
SV
96
90
SV2 AT OUT EV1 EV2
MD AT
13 90 10
TZ4L 96
90
SV2 AT OUT EV1 EV2
13 90 10
TZN4L
96
90
13 90 10
(unit: mm)
Panel cut-out dimensions Size
A B C D
A Series
TZ4SP, TZ4ST
Min. 55 Min. 62 45.5+0.5 45.5+0.5
TZN4S
0 0
0 0
C 0 0
H-78
Dual PID Auto Tuning Control
Bracket (unit: mm) (A)
TZ4ST, TZ4SP, TZN4S Series Z4L, TZN4L, TZ4M, TZN4M,
T Photoelectric
Sensors
TZ4H, TZN4H, TZ4W, TZN4W Series
(B)
30 Fiber
Optic
45.4
Sensors
61
12
10
(C)
Door/Area
Sensors
73
4.2
3.9
41
4.5
(D)
10
Proximity
Sensors
7.4 15
3.5
(E)
Pressure
12.2 47.8 Sensors
48 61
(F)
Rotary
Encoders
(I)
SSRs / Power
Controllers
(J)
Counters
(K)
Timers
Input Type And Range
(L)
Input type Decimal point Display Temperature range (℃) Temperature range (℉) Panel
Meters
K (CA) 1 KCaH -100 to 1300 -148 to 2372
(M)
K (CA) 0.1 KCaL -100.0 to 999.9 Not supported Tacho /
Speed / Pulse
Meters
J (IC) 1 JIcH 0 to 800 32 to 1472
J (IC) 0.1 JIcL 0.0 to 800.0 Not supported (N)
Display
Units
R (PR) 1 R PR 0 to 1700 32 to 3092
H-79
TZN/TZ Series
Unit Description
1 1
2
2
6
3 3
4 5 4 6
7 5
7
8 9
10 8 9
key
H-80
Dual PID Auto Tuning Control
※2: Press the key after checking or changing the values in parameter settings to
(F)
3 sec. save the setting value and move to the next parameter. Rotary
RUN mode ※Hold the key for 3 seconds anytime during parameter settings to save the setting Encoders
(N)
Display
Integral I 0 etting range: 0 to 3,600 sec.
S Units
time ※Integral operation is turned OFF when set to 0.
(O)
Sensor
Derivative ※Only appears during PID
D 0 Setting range: 0 to 3,600 sec. Controllers
time ※Derivative operation is turned OFF when set to 0. control (proportional band
[P] set to over )0). (P)
Switching
Mode Power
Control Setting range: 1 to 120 sec. Supplies
T 20
period ※Set to a small value in SSR drive output models. (Q)
(i.e. 2 sec.) Stepper Motors
& Drivers
& Controllers
Ramp
RAPU 10
up time Setting range: 1 to 99 min.
※Only appears when ramp function [RAMP] of parameter group
Ramp 2 is set to ON.
RAPD 10
down time
Setting range: OFF Unlock
H-81
TZN/TZ Series
● Parameter group 2 ※1: : ( )key-Switch fields, , key-Change values
※2: Press the key after checking or changing the values in parameter
RUN mode settings to save the setting value and move to the next parameter.
※Hold the key for 3 seconds anytime during parameter settings to save the
3 sec.
setting value and return to RUN mode.
※The dotted line parameters may not appear depending on the model or
+ 3 sec. other parameter settings.
PV display ※1 SV display
Input type IN-T KCaH Setting range:refer to " Input Type and Temperature Range".
※2
Auto-tuning
AtT TVN1 TVN2
mode
Temperature
UNIT ?C ?F
unit
SV
H-SC 1300
high-limit
Trans. output
FS-H 1300
high-limit
Setting range: refer to " Input Type and Temperature Range".
※Only appears in models that support PV transmission.
Trans. output
FS-L `00
low-limit
Ramp
RAMP OFF ON
function
Com.
BPS 2400 4800 9600
speed ※Only appears in models
that support RS485
communication
Com.
ㅁㅇ ADRS 01 Setting range: 1 to 99 (address)
address
H-82
Dual PID Auto Tuning Control
Parameter Default Parameter Default Parameter Default Parameter Default Parameter Default Parameter Default
(B)
SU-2 0 P #0 IN-B 0 IN-T KCaH O-FT HEAT FS-L `00 Fiber
Optic
Sensors
AL1 10 I 0 REST )0 EU-1 AL-1 UNIT ?C RAMP OFF
AL2 10 D 0 RAPU 10 EU-2 AL-2 H-SC 1300 BPS 2400 (C)
Door/Area
LBA 600 T 20 RAPD 10 AL-T AL-A L-SC `00 ADRS 01 Sensors
Functions (E)
You can control an additional temperature value at a desired The ramp function can delay the rate of temperature rise/
range by using SV2. Connect a contact signal (under 5VDC, fall. If the SV value is changed during stabilized control, the (F)
Rotary
250㎂) at the external terminal, to operate in the range temperature of the controlled target will rise/fall during ramp Encoders
where the signal turns ON. Set the SV2 temperature in SV2 up/down time [RAPU, RAPD] of parameter group 1. The
temperature [SU-2] in parameter group 1. ramp function activates when the power is reset or when (G)
Connectors/
Temperature the SV value is changed during stable control. Sockets
SV 2 [SU-2]
※The ramp up/down time [RAPU, RAPD] appear only when
(H)
the ramp function [RAMP] of parameter group 2 is set to Temperature
SV Controllers
ON.
●RAMP up time[RAPU] (I)
SSRs / Power
When delaying the rise of initial control temperature or Controllers
External terminal (SV2 IN) Time changing the SV during stable control, you can delay
ON temperature rise. Set the ramp up time [RAPU] longer than (J)
Counters
E.g.)The internal temperature of an electric oven may the temperature rise time (tu) when not using the ramp
drop rapidly if the door is opened while the oven function.
is maintaining a specific temperature. Set SV2 : Not using ramp function
(K)
Temperature Timers
temperature [SU-2] to a higher value than SV, and : Using ramp function
input a signal to the external terminal (SV2 IN), to Changed SV
(L)
quickly raise the temperature. Panel
Auto-tuning Meters
Initial SV
Auto-tuning allows the temperature controller to detect the (M)
Tacho /
thermal characteristics and response rates of the control Speed / Pulse
Meters
target. It then calculates the PID time constant and sets the
value to allow fast response rates and high accuracy. Hold (N)
the key for 3 seconds during RUN mode to start auto- Display
Units
tuning. The auto-tuning indicator will blink. When auto- Time
tu tu
tuning is completed, the auto-tuning indicator will durn off (O)
and the PID time constant will be saved to each parameter Ramp up time Ramp up time
Sensor
Controllers
of parameter group 1. The saved parameters can be [RAPU] [RAPU]
adjusted as desired. (P)
Switching
Auto-tuning based on SV ●Ramp down time [RAPD] Mode Power
Supplies
Auto-tuning Delays declining temperature. Set the ramp down time
TUN1 Temperature [RAPD] longer than the temperature decline time (td) when (Q)
SV Stepper Motors
mode
[TUN1]
not using the ramp function. & Drivers
& Controllers
H-83
TZN/TZ Series
Alarm(Event)
Alarm output can be configured by combining alarm operation and alarm options. Set the alarm operation in event 1/2 [EU1,
EU2] of parameter group 2, and set the alarm options in alarm option[AL-T].
1)Alarm operation
Mode Name Alarm operation Description
ㅁAL-0 - - Alarm output not used.
OFF H ON
Deviation If the deviation of PV and SV are higher than
AL-1 high-limit SV PV the high-limit deviation, the alarm output turns
alarm 100℃ 110℃ ON.
High-limit deviation: 10℃
ON H OFF
Deviation If the deviation of PV and SV are higher than
AL-2 low-limit PV SV the low-limit deviation, the alarm output turns
alarm 90℃ 100℃ ON.
Low-limit deviation: 10℃
Deviation ON H OFF H ON
If the deviation of PV and SV are higher than
high-limit
AL-3 PV SV PV the high-limit deviation or low-limit deviation, the
/low-limit
90℃ 100℃ 110℃ alarm output turns ON.
alarm
High-limit/low-limit deviation: 10℃
Deviation OFF H ON H OFF
high-limit If the deviation of PV and SV are higher than
AL-4 /low-limit PV SV PV the high-limit deviation or low-limit deviation, the
reverse 90℃ 100℃ 110℃ alarm output turns OFF.
alarm High-limit/low-limit deviation: 10℃
OFF H ON OFF H ON
Absolute
value Alarm output turns ON when PV is higher than
AL-5 PV SV SV PV
high-limit 90℃ 100℃
the absolute value.
100℃ 110℃
alarm
Absolute value alarm: 90℃ Absolute value alarm: 110℃
ON H OFF ON H OFF
Absolute
value Alarm output turns ON when PV is lower than
AL-6 PV SV SV PV
low-limit the absolute value.
90℃ 100℃ 100℃ 110℃
alarm
Absolute value alarm: 90℃ Absolute value alarm: 110℃
Alarm output turns ON when sensor
SBA Sensor break -
disconnection is detected.
Alarm output turns ON when loop break is
LBA Loop break -
detected.
※ H: Alarm output hysteresis[AHYS]
2)Alarm options
Mode Name Description
AL-A Standard alarm Alarm output turns ON upon alarm condition, and alarm output turns OFF when condition is cleared.
AL-B Alarm latch Alarm output turns ON and maintains ON upon alarm condition.
The first alarm condition is ignored. It will operate as standard alarm from the second alarm condition. If it is under
Standby
AL-C alarm condition when power is supplied, it will ignore the condition and operate as standard alarm from the next
sequence
alarm condition.
Alarm latch
It will operate as both alarm latch and standby sequence upon alarm condition. If it is under alarm condition when
AL-D and standby
power is supplied, it will ignore the condition and operate as alarm latch from the next alarm condition.
sequence
3) Sensor break alarm
Alarm output turns ON when sensor is not connected or loses its connection during temperature control. Sensor
disconnection can be tested by connecting buzzers or other devices to the alarm output contact. Sensor break alarm output
operates through EV1 OUT or EV2 OUT contacts. Alarm output is disengaged after resetting the power.
H-84
Dual PID Auto Tuning Control
Dual PID control RS485 communication (A)
The response rate of the PID control can be selected Applicable for models that support RS485 communication.
Photoelectric
Sensors
depending on the characteristics of the control target. Please refer to ' Ordering Information'.
Select high-speed response mode or low-speed response It is used to transmit PV or SV, and/or set the SV.
(B)
Fiber
mode [PIdF, PIdS] from PID method [PIDT] of parameter Optic
Used in machinery that may require warming up. Parity bit None
(injection molding machine, electric furnace, etc.) Stop bit 1-bit fixed (G)
Connectors/
Sockets
Temp. ※It is not allowed to set overlapping communication address at
SV the same communication line. Use twisted pair wire for RS485 (H)
PV communication. Temperature
Controllers
Application of system organization
※Only for RS485 communication output model. (I)
Low- SSRs / Power
RS232C Controllers
speed or USB RS485
Terminating resistance
t Time (100 to 120Ω)
response B(-) RS485
DEVICE
[PIdS] A(+) #31 (J)
Used to minimize overshoot (S). Time (t) required to Comm. Counters
reach SV may be slower. converter
B(-)
A(+) B(-)
RS485
A(+) B(-)
RS485
A(+) B(-)
RS485
Used for machinery or environments where overshoot DEVICE DEVICE DEVICE
Computer OFF #1 #2 #30
may cause explosion or fire. (oil temperature control, ON (K)
Timers
metal plating machinery, etc.) A(+)
Used to correct deviation from external devices such as sold separately). Please use twisted pair wire for RS485 (M)
temperature controllers. communication.
Tacho /
Speed / Pulse
E.g.)If the actual temperature is 80℃ but the display value Meters
is 78℃, set the input correction [IN-B] value to 2 and Communication control ordering (N)
it will display 80℃ as the display value. Display
1. The communication control ordering of TZ/TZN Series is Units
of temperature rising time and falling time may differ then able to start communicating. Controllers
depending on factors such as the heat capacity of the 3. Initial communication will be started by master system. (P)
Switching
control device or the heater. A certain amount of deviation When Command signal comes out from master system Mode Power
occurs even under stable conditions. then TZ/TZN Series will respond. Supplies
H-85
TZN/TZ Series
Communication Command and Block Response
Format of Command and Response ● Read of process/Setting value
STX 101 100 R/W X/D ETX FSC 1. In case of receiving normal process value:
The data is transmitted adding ACK [60H].
Start Address Header Text END BCC (In case process value is +123.4)
Code Code Code Code Code
A S E F N
C T 0 1 R D P 0 Symbol 103 102 101 100 Decimal T S U
point
Calculation range of Block Check Character K X X C L
L
① Start code
A S E B N
It indicates the first of Block STX → [02H], C T 0 1 R D P 0 Space 1 2 3 4 1 T C U
in case of response, ACK will be added. K X X C L
L
② Address code B
06 02 30 31 52 44 50 30 20 31 32 33 34 31 03 C 00
This code is master system can discern TZ/TZN Series C
and able to set within range of 01 to 99. (BCD ASCII)
③ Header code: 2. In case process value is -100
It indicates command as 2 alphabets as below. A S E B N
U
RX (Read request) → R [52H], X [58H] C T 0 1 R D P 0 - 0 1 0 0 0 T C L
K X X C
RD (Read response) → R [52H], D [44H] L
WX (Write request) → W [57H], R [58H] B
06 02 30 31 52 44 50 30 2D 30 31 30 30 30 03 C 00
WD (Write response) → W [57H], D [44H] C
④ Text: It indicates the detail contents of Command/ ※It is responded with 1 byte sized NULL (00H) at the end
Response. (see command) of response frame (next BCC 16).
⑤ END code: It indicates the end of Block. ETX → [03H]
● Write of setting value
⑥ BCC: It indicates XOR operating value from the first to
ETX of the protocol as abbreviation of TZ/TZN. In case setting value is -100
A S E F
C T 0 1 W D S 0 Symbol 103 102 101 100 T S
K X X C
Communication Command
A S E B
● Read [RX] of measurement/setting value: C T 0 1 W D S 0 - 0 1 0 0 T C
K X X C
Address 01, Command RX
1.Command (Master) B
06 02 30 31 57 44 53 30 2D 30 31 30 30 03 C
① Command C
H-86
Dual PID Auto Tuning Control
LLLL Blinks when the measured input value is lower than the temperature range. temperature range. (C)
Door/Area
Sensors
Proper Usage
(D)
Troubleshooting Proximity
Sensors
Please separate the unit wiring from high voltage lines or power lines to prevent inductive noise. (K)
Use the following shaped M3.5 crimp terminals. Timers
Max. 7.2mm
(L)
Panel
Install a power switch or circuit breaker to control the power supply. Meters
The power switch or circuit breaker should be installed where it is easily accessible by the user. (M)
The unit is designed for use as a temperature controller. Do not use the unit as a volt-meter or an ampere-meter. Tacho /
Speed / Pulse
When using thermocouple temperature sensors, prescribed extension wiring must be used. Using general wiring may Meters
cause temperature deviation where the thermocouple meets the wire. (N)
When using RTD temperature sensors, 3-wire type wiring must be used. When extending the wires, use 3 wires that Display
Units
have the same length and thickness. Different line resistance may cause temperature deviation.
If the power line and the input signal line must be close to each other, make sure to install a line filter on the power line (O)
Sensor
for noise protection and use a shielded input signal line. Controllers
Keep away from the high frequency instruments. (High frequency welding machine & sewing machine, large
(P)
capacity SCR controller). Switching
If the unit displays HHHH or LLLLafter supplying measured input, there may be a problem with the measured input. Mode Power
Supplies
Disconnect the power and check the wiring.
(Q)
When changing user input settings, please disconnect the power. Adjust the internal switch (S/W1, S/W2) as required, Stepper Motors
& Drivers
connect the power and select the input type [IN-T] of parameter group 2. & Controllers
The SSR drive output, current output are separated and insulated from internal circuits of the unit. (R)
Do not connect the power supply to the event output terminal or sensor terminals. Graphic/
Logic
This unit may be used in the following environments. Panels
①Indoors (S)
Field
②Pollution degree 2 Network
③Altitude under 2,000m Devices