Topic Page
Available 1756 I/O Modules 2
ControlLogix I/O Accessories 243
Additional Resources 245
The ControlLogix® architecture provides a wide range of input and output modules to span many
applications, from high-speed digital to process control. The ControlLogix architecture uses
Producer-Consumer technology, which allows input information and output status to be shared
among multiple ControlLogix controllers.
Each ControlLogix I/O module mounts in a ControlLogix chassis and requires either a removable
terminal block (RTB) or a 1492 interface module (IFM) to connect all field-side wiring. RTBs and
IFMs are not included with the I/O modules. They must be ordered separately.
1756 ControlLogix I/O Specifications
1756-IA8D
L1
1756-IA16
ST 0 1 2 3 4 5 6 7 O L2-1 L2-1
FLT 0 1 2 3 4 5 6 7 K
L2 L1
1756-IA16I
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11 12 13 14 15 K
Daisy Chain to
Other RTBs
1756-IA32
1756-IB16
IN-1 IN-0
+5V
Group 0
IN-0 IN-3 IN-2
Daisy Chain
GND-0 to Other IN-5 IN-4 Group 0
RTBs
IN-11 IN-10
DC INPUT Group 1 IN-12 Group 1
IN-13
ST 0 1 2 3 4 5 6 7 O
IN-15 IN14
ST 8 9 10 11 12 13 14 15 K
GND-1 GND-1
- +
DC COM
1756-IB16D
ST 0 1 2 3 4 5 6 7
– +
FLT 0 1 2 3 4 5 6 7 O
K DC COM
ST 8 9 10 11 12 13 14 15
FLT 8 9 10 11 12 13 14 15
DIAGNOSTIC
Recommended Leakage Resistor Size 1/4 W, 5% Supply Voltage
3.9K 10V DC
5.6K 12V DC
15K 24V DC
20K 30V DC
1756-IB16I
ControlLogix DC (10…30V) isolated input module
1756-IB161
Simplified Schematic Isolated DC-0 (-) GND-0 DC-0 (+)
1 2 IN-0
Wiring DC-1 (-) GND-1 DC-1 (+)
+5V 3 4 IN-1
IN-0 GND-2 5 6 IN-2
GND-3 7 8 IN-3
Source Input Wiring
GND-4 10 9 IN-4
GND-0 DC-5 (-) GND-5 12 11 IN-5 (+) DC-5 (+)
DC-6 (-) GND-6 14 13 IN-6 (+) DC-6 (+)
GND GND-7 16 15 IN-7
Jumper Bar (Cut to Length) GND-8 18 17 IN-8
GND-9 20 19 IN-9
ControlLogix Display GND-10 22 21 IN-10
Backplane GND-11 IN-11
24 23
Interface GND-12 IN-12 Sink Input
Nonisolated 26 25
Wiring Wiring
GND-13 28 27 IN-13
GND-14 30 29 IN-14
GND-15 32 31 IN-15
DC (-) GND-15 34 33 Not Used DC (+)
Not Used 36 35 Not Used
Additional jumper bars are available
as cat. no. 1756-JMPR.
DC INPUT
Daisy Chain to Other RTBs
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11 12 13 14 15 K
1756-IB16IF
Simplified Schematic
Isolated Wiring
1756-IB16IF
GND-0 2 1 IN-0
DC-1 (-) GND-1 4 3 IN-1 DC-1 (+)
DC-2 (-) GND-2 6 5 IN-2 DC-2 (+)
GND-3 8 7 IN-3
Source Input Wiring GND-4 10 9 IN-4
DC-5 (-) GND-5 12 11 IN-5 (+) DC-5 (+)
DC-6 (-) GND-6 14 13 IN-6 (+) DC-6 (+)
GND-7 16 15 IN-7
Jumper Bar Cut to Length GND-8 18 17 IN-8
GND-9 20 19 IN-9
Sink Input Wiring
GND-10 22 21 IN-10
GND-11 24 23 IN-11
GND-12 26 25 IN-12
Nonisolated Wiring
GND-13 28 27 IN-13
GND-14 30 29 IN-14
GND-15 32 31 IN-15
DC (-) GND-15 34 33 Not Used DC (+)
Not Used 36 35 Not Used
ST 01 2 3 4 5 6 7 O
ST 8 9 10 11 12 13 14 15 K
PEER DEVICE
1756-IB16ISOE
SOE INPUT
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11 12 13 14 15 K
1756-IB32
+5V
Current Limiter IN-1 2 1 IN-0
IN-0
IN-3 4 3 IN-2
GND-0 IN-5 6 5 IN-4
Group 0 IN-7 8 7 IN-6 Group 0
GND IN-9 10 9 IN-8
Daisy Chain IN-10
IN-11 12 11
to Other RTBs
ControlLogix Display IN-13 14 13 IN-12
Backplane IN-15 16 15 IN-14
Interface GND-0 18 17 GND-0
IN-17 20 19 IN-16
IN-19 22 21 IN-18
IN-21 24 23 IN-20
IN-23 26 25 IN-22
Group 1 Group 1
IN-25 28 27 IN-24
IN-27 30 29 IN-26
DC INPUT
IN-29 32 31 IN-28
ST 0 1 2 3 4 5 6 7 IN-31 34 33 IN-30
1 1 1 1 1 1 O
ST 8 9 0 1 2 3 4 5 GND-1 36 35 GND-1
K
1 1 1 1 2 2 2 2
ST 6 7 8 9 0 1 2 3
2 2 2 2 2 2 3 3
ST 4 5 6 7 8 9 0 1
DC COM – +
1756-IC16
Simplified Schematic 2 1
IN-1 IN-0
+5V 4 3
IN-0
IN-3 IN-2
6 5
GND-0 IN-5 IN-4
Group 0 Group 0
8 7
GND IN-7 IN-6
10 9
ControlLogix Display GND-0 GND-0
Backplane 12 11
Interface IN-9 IN-8
14 13
IN-11 IN-10
16 15
Group 1 IN-13 IN-11 Group 1
18 17
IN-15 IN-14
DC INPUT 20 19
GND-1 GND-1
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11 12 13 14 15K
Daisy Chain to
Other RTBs – +
DC COM
1756-IF4FXOF2F
ControlLogix high-speed input/output analog module
ANALOG INPUT
ANALOG OUTPUT
CAL
OK
1756-IF6CIS
1756-IF6CIS 2-wire Transmitter Connected to the Module 1756-IF6CIS 2-wire Transmitter Connected to the Module and an External,
and the Module Providing 24V DC Loop Power User-provided Power Supply Providing 24V DC Loop Power
2 1 2 1
A
VOUT-1 VOUT-0 VOUT-1 VOUT-0 i
4 3 4 3
A
IN-1/I IN-0/I IN-1/I IN-0/I
A 2-wire
6 5 6 5
Transmitter
RTN-1 RTN-0 i RTN-1 RTN-0 24V DC
A – +
8 7 8 7
VOUT-3 VOUT-2 VOUT-3 VOUT-2
10 9 10 9
IN-3/I IN-2/I Shield Ground IN-3/I IN-2/I
12 11 12 11
RTN-3 RTN-2 RTN-3 RTN-2 Shield Ground
14 13 14 13
Not Used Not Used Not Used Not Used
16 15 16 15
VOUT-5 VOUT-4 VOUT-5 VOUT-4
18 17 18 17
IN-5/I IN-4/I IN-5/I IN-4/I
20 19 20 19
RTN-5 RTN-4 RTN-5 RTN-4
Place additional loop devices (such as strip chart recorders) at either A location in the current loop.
1756-IF6CIS 4-wire Transmitter Connected to the Module and an External,
User-provided Power Supply Providing 24V DC Loop Power
2 1
VOUT-1 VOUT-0 i
4 3
A + +
IN-1/I IN-0/I
4-wire 24V DC ANALOG INPUT
6 5
Transmitter
RTN-1 RTN-0
A – – CAL
8 7
VOUT-3 VOUT-2 OK
10 9
IN-3/I IN-2/I
12 11
RTN-3 RTN-2 Shield Ground
14 13
Not Used Not Used
16 15
VOUT-5 VOUT-4
18 17
IN-5/I IN-4/I
20 19
RTN-5 RTN-4
• Place additional loop devices (such as strip chart recorders) at either A location in
the current loop.
• User-supplied power supply must not exceed 150VA.
1756-IF6I
2 1 2 1
Place additional loop devices (such as strip chart recorders) at either A location.
1756-IF6I Voltage
Voltage Input
2 1
IN-1/V IN-0/V +
4 3
User Analog
IN-1/I IN-0/I Input Device
6 5
RET-1 RET-0 –
8 7
Device
External
IN-3/V IN-2/V Power
10 9
ANALOG INPUT
IN-3/I IN-2/I
CAL
12 11
RET-3 RET-2 OK
14 13
Not Used Not Used
16 15
IN-5/V IN-4/V
18 17
IN-5/I IN-4/I Shield Ground
20 19
RET-5 RET-4
1756-IF8
• Use this table when wiring your module in Differential mode. • Use this table when wiring your module in Differential mode.
This channel Uses these terminals This channel Uses these terminals
Channel 0 IN-0 (+), IN-1 (-), i RTN-0 Channel 0 IN-0 (+), IN-1 (-)
Channel 1 IN-2 (+), IN-3 (-), i RTN-2 Channel 1 IN-2 (+), IN-3 (-)
Channel 2 IN-4 (+), IN-5 (-), i RTN-4 Channel 2 IN-4 (+), IN-5 (-)
Channel 3 IN-6 (+), IN-7 (-), i RTN-6 Channel 3 IN-6 (+), IN-7 (-)
• All terminals marked RTN are connected internally. • All terminals marked RTN are connected internally.
• A 249 Ω current loop resistor is located between IN-x and i RTN-x terminals. • If multiple (+) or multiple (-) terminals are tied together, connect that tie point to
• If multiple (+) or multiple (-) terminals are tied together, connect that tie point to a RTN terminal to maintain the module’s accuracy.
a RTN terminal to maintain the module’s accuracy. • Terminals marked RTN or i RTN are not used for differential voltage wiring.
• Place additional loop devices (such as strip chart recorders) at the A location in the
current loop. IMPORTANT: When operating in 2 channel, High Speed mode, only use channels 0
and 2.
IMPORTANT: When operating in 2 channel, High Speed mode, only use channels 0
and 2.
Channel 0
i
Channel 0 +
IN-0 2 1 i RTN-0
IN-0 2 1 i RTN-0
IN-1 4 3 i RTN-1
Jumper IN-1 4 3 i RTN-1
IN-2 6 5 i RTN-2 Wires –
Shield Ground IN-2 6 5 i RTN-2
IN-3 8 7 i RTN-3
8 7
10 9 IN-3 i RTN-3
Channel 5 RTN RTN Shield Ground
10 9
12 11 RTN RTN
i IN-4 i RTN-4
+ 12 11
2-wire Channel 1 IN-4 i RTN-4
IN-5 14 13 i RTN-5
Transmitter 14 13
A IN-6 16 15 i RTN-6 IN-5 i RTN-5
16 15
IN-7 18 17 i RTN-7 – IN-6 i RTN-6
IN-7 18 17 i RTN-7
Not Used 20 19 Not Used
Not Used 20 19 Not Used
Not Used 22 21 Not Used
Not Used 22 21 Not Used
Not Used 24 23 Not Used
Shield Ground Not Used 24 23 Not Used
Not Used 26 25 Not Used
Not Used 26 25 Not Used
Not Used 28 27 Not Used
Not Used 28 27 Not Used
Not Used 30 29 Not Used
Not Used 30 29 Not Used
Not Used 32 31 Not Used
Not Used 32 31 Not Used
Not Used 34 33 Not Used
Not Used 34 33 Not Used
Not Used 36 35 Not Used
Not Used 36 35 Not Used
• All terminals marked RTN are connected internally. • All terminals marked RTN are connected internally.
• For current applications, all terminals marked iRTN must be wired to terminals • Terminals marked i RTN are not used for single-ended voltage wiring.
marked RTN.
• A 249 Ω current loop resistor is located between IN-x and i RTN-x terminals.
• Place additional loop devices (such as strip chart recorders) at the A location in the
current loop.
ANALOG INPUT
CAL
OK
1756-IF8H
1756-IF8I
1756-IF8I Module Wiring Diagram -Current Mode with External Loop Power
i
IN_0/V IN_1/V
+ + 2 1
IMPORTANT: Remember the following: 4-wire A IN_0/I/SRC IN_1/I/SRC
4 3
• In this wiring diagram, an external, user- 24V DC Transmitter
provided power supply provides 24V DC RTN_0 6 5 RTN_1
– – A Not used Not used
loop power. 8 7
• If separate power sources are used, do not IN_2/V 10 9
IN_3/V
exceed the specific isolation voltage as IN_2/I/SRC IN_3/I/SRC
Shield Ground 12 11
listed in the specifications.
RTN_2 14 13 RTN_3
• Place additional loop devices, for example,
strip chart recorders, at either ‘A’ location in Not used 16 15 Not used
the current loop. IN_4/V 18 17
IN_5/V
IN_4/I/SRC 20 19
IN_5/I/SRC
RTN_4 22 21 RTN_5
Not used 24 23
Not used
i IN_6/V 26 25 IN_7/V
2-wire – A IN_6/I/SRC 28 27 IN_7/I/SRC
Transmitter
+ 24V DC A RTN_6 30 29 RTN_7
+ – Not used 32 31 Not used
Not used 34 33 Not used
Shield Ground Not used 36 35 Not used
1756-IF8I Module Wiring Diagram -Current Mode with Internal Loop Power
IN_0/V 2 1 IN_1/V
IMPORTANT: Remember the following: 2-wire + A IN_0/I/SRC 4 3 IN_1/I/SRC
• In this wiring diagram, the module Transmitter
- A RTN-0 6 5 RTN-1
provides 24V DC loop power.
• If separate power sources are used, do i Not used 8 7 Not used
not exceed the specific isolation IN_2/V 10 9 IN_3/V
voltage as listed in the specifications. Shield Ground IN_2/I/SRC 12 11 IN_3/I/SRC
• Place additional loop devices, for
RTN_2 14 13 RTN_3
example, strip chart recorders, at either
Not used 16 15 Not used
‘A’ location in the current loop.
IN_4/V 18 17 IN_5/V
IN_4/I/SRC 20 19 IN_5/I/SRC
RTN-4 22 21 RTN-5
Not used 24 23 Not used
IN_6/V 26 25 IN_7/V
IN_6/I/SRC 28 27 IN_7/I/SRC
RTN_6 30 29 RTN_7
Not used 32 31 Not used
Not used 34 33 Not used
Not used 36 35 Not used
ANALOG INPUT
ST O
K
FLT
1756-IF8IH
IN2 12 11 IN3
RTN2 14 13 RTN3
Reserved 16 15 Reserved
Reserved 18 17 Reserved
IN4 20 19 IN5
RTN4 22 21 RTN5
Reserved 24 23 Reserved
i Reserved 26 25 Reserved
–
A IN6 28 27 IN7
+ A RTN6 30 29 RTN7
Reserved 32 31 Reserved
Reserved 34 33 Reserved
Not Used 36 35 Not Used
1756-IF16
Use this table when wiring your module in Differential mode. Use this table when wiring your module in Differential mode.
This channel Uses these terminals This channel Uses these terminals
Channel 0 IN-0 (+), IN-1 (-), i RTN-0 Channel 0 IN-0 (+), IN-1 (-)
Channel 1 IN-2 (+), IN-3 (-), i RTN-2 Channel 1 IN-2 (+), IN-3 (-)
Channel 2 IN-4 (+), IN-5 (-), i RTN-4 Channel 2 IN-4 (+), IN-5 (-)
Channel 3 IN-6 (+), IN-7 (-), i RTN-6 Channel 3 IN-6 (+), IN-7 (-)
Channel 4 IN-8 (+), IN-9 (-), i RTN-8 Channel 4 IN-8 (+), IN-9 (-)
Channel 5 IN-10 (+), IN-11 (-), i RTN-10 Channel 5 IN-10 (+), IN-11 (-)
Channel 6 IN-12 (+), IN-13 (-), i RTN-12 Channel 6 IN-12 (+), IN-13 (-)
Channel 7 IN-14 (+), IN-15 (-), i RTN-14 Channel 7 IN-14 (+), IN-15 (-)
• All terminals marked RTN are connected internally. • All terminals marked RTN are connected internally.
• A 249 Ω current loop resistor is located between IN-x and i RTN-x terminals. • If multiple (+) or multiple (-) terminals are tied together, connect that tie point to
• If multiple (+) or multiple (-) terminals are tied together, connect that tie point to a RTN terminal to maintain the module’s accuracy.
a RTN terminal to maintain the module’s accuracy. • Terminals marked RTN or i RTN are not used for differential voltage wiring.
• Place additional loop devices (such as strip chart recorders) at the A location in the
current loop. IMPORTANT: When operating in 4 channel, High Speed mode, only use channels 0, 2,
4, and 6.
IMPORTANT: When operating in 4 channel, High Speed mode, only use channels 0,
2, 4, and 6.
i +
IN-0 2 1 i RTN-0 IN-0 2 1 i RTN-0
IN-1 4 3 i RTN-1 IN-1 4 3 i RTN-1
Jumper –
IN-2 6 5 i RTN-2 IN-2 6 5 i RTN-2
Shield Wires
IN-3 8 7 i RTN-3 IN-3 8 7 i RTN-3
Ground Shield
RTN 10 9 RTN RTN 10 9 RTN
Ground
IN-4 12 11 i RTN-4 IN-4 12 11 i RTN-4
i +
2-wire 14 13
IN-5 14 13 i RTN-5 IN-5 i RTN-5
Transmitter A IN-6 16 15 i RTN-6 IN-6 16 15 i RTN-6
–
IN-7 18 17 i RTN-7 IN-7 18 17 i RTN-7
IN-8 20 19 i RTN-8 IN-8 20 19 i RTN-8
IN-9 22 21 i RTN-9 IN-9 22 21 i RTN-9
IN-10 24 23 i RTN-10 Shield IN-10 24 23 i RTN-10
IN-11 26 25 i RTN-11 Ground IN-11 26 25 i RTN-11
RTN 28 27 RTN RTN 28 27 RTN
IN-12 30 29 i RTN-12 IN-12 30 29 i RTN-12
IN-13 32 31 i RTN-13 IN-13 32 31 i RTN-13
IN-14 34 33 i RTN-14 IN-14 34 33 i RTN-14
IN-15 36 35 i RTN-15 IN-15 36 35 i RTN-15
• All terminals marked RTN are connected internally. • All terminals marked RTN are connected internally.
• For current applications, all terminals marked i RTN must be wired to terminals • Terminals marked i RTN are not used for single-ended voltage wiring.
marked RTN.
• A 249 Ω current loop resistor is located between IN-x and iRTN-x terminals.
• Place additional loop devices (such as strip chart recorders) at the A location in the
current loop.
ANALOG INPUT
CAL
OK
1756-IF16H
+ +- IN0+ 2 1 IN0-
24V DC
Power
Supply
- IN1+ 4 3 IN1-
IN2+ 6 5 IN2- When a common supply is used
you should tie the IN- to RTN.
IN3+ 8 7 IN3-
4 Wire HART Device
RTN 10 9 RTN
24V DC
+ + + IN4+ 12 11 IN4-
Power 4 Wire
Supply XMTR
IN5+ 14 13 IN5-
- - -
IN6+ 16 15 IN6-
IN7+ 18 17 IN7-
IN8+ 20 19 IN8-
IN9+ 22 21 IN9-
IN10+ 24 23 IN10-
ANALOG INPUT
IN11+ 26 25 IN11-
RTN 28 27 RTN
CAL
IN12+ 30 29 IN12-
OK IN13+ 32 31 IN13-
IN14+ 34 33 IN14-
IN15+ 36 35 IN15-
HART
1756-IG16
IMPORTANT: I/O cables must be shielded type and cable length must be <10 m
Simplified Schematic (32.8 ft) for maximum EMI noise immunity.
+5 DC
1.5 K
1K 74HCT14
560
IN
DC INPUT
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11 12 13 14 15K
1.5 K
1K 74HCT14
560
IN
DC COM
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
1756-IH16I
ControlLogix 125V DC isolated input module
+5V
DC-0 (-) GND-0 2 1 IN-0 DC-0 (+)
IN-0 GND-1 IN-1
Isolated 4 3
Wiring GND-2 6 5 IN-2
GND-0 DC-3 (-) GND-3 8 7 IN-3 DC-3 (+)
GND-4 10 9 IN-4
GND GND-5 12 11 IN-5
GND-6 14 13 IN-6
ControlLogix Display DC-7 (-) GND-7 16 15 IN-7 D C-7 (+ )
Backplane Jumper Bar GND-8 18 17 IN-8
Interface (Cut to Length) GND-9 20 19 IN-9
GND-10 22 21 IN-10
GND-11 24 23 IN-11
Nonisolated
Wiring GND-12 26 25 IN-12
GND-13 28 27 IN-13
Additional jumper bars are available GND-14 30 29 IN-14
as cat. no. 1756-JMPR. GND-15 32 31 IN-15
DC (-)
GND-15 34 33 Not Used
Not Used 36 35 Not Ysed DC (+)
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11 12 13 14 15K
1756-IH16ISOE
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11 12 13 14 15 K
1756-IM16I
L1
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11 12 13 14 15 K
1756-IN16
IN-O +5V 2 1
IN-1 IN-0
4 3
L2-0 L1
IN-3 IN-2
GND 6 5
IN-5 IN-4
L2 Group 0 8
Group 0
7
IN-7 IN-6
ControlLogix Display
Backplane 10 9
L2-0 L2-0
Interface
12 11
IN-9 IN-8
14 13
IN-11 IN-10
Group 1 16 15 Group 1
IN-13 IN-12
AC INPUT
18 17
IN-15 IN-14
ST 0 1 2 3 4 5 6 7 O 20 19
ST 8 9 10 11 12 13 14 15 K L2-1 L2-1
Daisy Chain to
Other RTBs
1756-IR6I
2 1
IN-1/A IN-0/A
4 3
IN-1/B IN-0/B
6 5
RTN-1/C RTN-0/C
8 7 3-wire RTD
IN-3/A IN-2/A
10 9
IN-3/B IN-2/B
12 11
RTN-3/C RTN-2/C Shield Ground
14 13
Not used Not used
16 15
IN-5/A IN-4/A
18 17
IN-5/B IN-4/B
20 19
RTN-5/C RTN-4/C
2 1
IN-1/A IN-0/A
4 3
IN-1/B IN-0/B
6 5
RTN-1/C RTN-0/C
8 7 4-wire RTD
IN-3/A IN-2/A
10 9 ANALOG INPUT
IN-3/B IN-2/B
12 11
CAL
RTN-3/C RTN-2/C Shield Ground
14 13 OK
Not used Not used
16 15
IN-5/A IN-4/A
18 17
IN-5/B IN-4/B
20 19
RTN-5/C RTN-4/C
1756-IRT8I
ControlLogix isolated RTD/Thermocouple analog input module.
CJC Sensor
RTD/TC/mV INPUT
ST O
K
FLT
1756-IT6I
2 1
+
IN-0 IN-0
4 3
Not Used Not Used
Cold 6 5
Junction
Sensor RTN-1 RTN-0
8 7 –
Lug
IN-3 IN-2
Thermocouple
ANALOG INPUT 10 9
CJC+ Not Used
CAL 12 11
RTN-3 RTN-2
OK 14 13
CJC- Not Used
16 15
One CJC, part number 94238301, is shipped with the module. A replacement can be
ordered as RP-94238301.
1756-IT6I2
CJC– CJC+
RTN-0 IN-0
Analog Input
RTN-1 IN-1
RTN- IN-4
RTN-5 IN-5
CJC– CJC+
Cold Junction
Wire Spade Lug
Sensor
Two CJCs, part number 94286501, are shipped with the module. Replacements can be
ordered as RP-94286501.
1756-IV16
IN-11 IN-10
16 15
Group 1 IN-13 IN-12 Group 1
18 17
DC-1 + DC-1 +
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 111213 1415 K
+ – DC COM
1756-IV32
+ –
DC COM
1756-OA8
L1-0 OUT-1
6 5
L1-0 OUT-3
ControlLogix Backplane Interface
10 9
Display Not Used
L1-0
12 11
18 17
L1-1 OUT-7
20 19
0 43 ms
Time
Daisy Chain to
Other RTBs
L1
AC OUTPUT
ST 0 1 2 3 4 5 6 7 O
K
1756-OA8D
L2 10 9
L1-0 OUT-3
Display Loss of Field Power 12 11
5A 20 19
Continuous @ 30 °C (86 °F) L1-1 L2-1
1A
Continuous @ 60 °C (140 °F)
500 mA L2
0 43 ms
Time Daisy Chain to
Other RTBs
L1
AC OUTPUT
ST 0 1 2 3 4 5 6 7 O
K
FLT 0 1 2 3 4 5 6 7
DIAGNOSTIC
On to Off 9.3 ms @ 60 Hz
11 ms @ 50 Hz
Current draw @ 5.1V 175 mA
Current draw @ 24V 250 mA
Total backplane power 6.89 W
Power dissipation, max 5.3 W @ 60 °C (140 °F)
Thermal dissipation 18.0 BTU/hr
Off-state leakage current, max 3 mA per point
On-state voltage drop, max 2.5V peak @ 0.5 A
3V peak @ 1 A
Current per point, max 1 A @ 30 °C (86 °F) linear derating
0.5 A @ 60 °C (140 °F) linear derating
Current per module, max 8 A @ 30 °C (86 °F) linear derating
4 A @ 60 °C (140 °F) linear derating
Surge current per point 8 A for 43 ms per point, repeatable every 2 s @ 30 °C (86 °F)
5 A for 43 ms per point, repeatable every 1 s @ 60 °C (140 °F)
Load current, min 10 mA per point
Scheduled outputs Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point Hold last state, On or Off (Off is default)
States in Program mode per point Hold last state, On or Off (Off is default)
Isolation voltage 125V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group
No isolation between individual group outputs
Routine tested @ 1200V AC for 2 s
Inhibit voltage, max Zero crossing 25V peak
Module keying Electronic, software configurable
Fusing Electronically fused per point
Removable terminal block 1756-TBNH
1756-TBSH
RTB keying User-defined mechanical
Slot width 1
Wire category 1(2)
North American temperature code T4A
Enclosure type None (open style)
(1) UL certification for 120V 50/60 Hz nominal. Rockwell Automation specified to 74…132V, 47…63 Hz.
(2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1.
1756-OA8E
OUT Group 0
L1-0 OUT-1
Group 0
L2 8 7
L1-0 OUT-2
Display Loss of Field Power 10 9
L1-0 OUT-3
12 11
Surge Current Chart
Daisy L1-1 OUT-4
Chain to 14 13
20 A Surge Other
L1-1 OUT-5
RTBs
16 15
L1-1 OUT-6
Current
18 17
L2
0 43 ms Daisy Chain to
Time Other RTBs
L1
AC OUTPUT
ST 0 1 2 3 4 5 6 7 O
FUSE 0 1 2 3 4 5 6 7K
ELECTRONICALLY FUSED
On to Off 9.3 ms @ 60 Hz
11 ms @ 50 Hz
Current draw @ 5.1V 200 mA
Current draw @ 24V 250 mA
Total backplane power 7.02 W
Power dissipation, max 5.5 W @ 60 °C (140 °F)
Thermal dissipation 18.76 BTU/hr
Off-state leakage current, max 3 mA per point
On-state voltage drop, max 4V peak @ 2 A
Current per point, max 2 A @ 60 °C (140 °F)
Current per group, max 4 A @ 30 °C (86 °F) linear derating
2 A @ 60 °C (140 °F) linear derating
Current per module, max 8 A @ 30 °C (86 °F) linear derating
4 A @ 60 °C (140 °F) linear derating
Surge current per point 20 A for 43 ms per point, repeatable every 2 s @ 60 °C (140 °F)
Load current, min 10 mA per point
Scheduled outputs Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point Hold last state, On or Off (Off is default)
States in Program mode per point Hold last state, On or Off (Off is default)
Isolation voltage 125V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group
No isolation between individual group outputs
Routine tested @ 1200V AC for 2 s
Inhibit voltage, max Zero crossing 25V peak
Module keying Electronic, software configurable
Fusing Electronically fused per point
Removable terminal block 1756-TBNH
1756-TBSH
RTB keying User-defined mechanical
Slot width 1
Wire category 1(2)
North American temperature code T4A
Enclosure type None (open style)
(1) UL certification for 120V 50/60Hz nominal. Rockwell Automation specified to 74…132V, 47…63 Hz.
(2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1.
1756-OA16
L1-0 L2-0
12 11
OUT-0
OUT-9 OUT-8
ControlLogix Backplane Interface 14 13
OUT-11 OUT-10
16 15
Per Group
5A
2A
500 mA
0 43 ms L1 L2
Time
AC OUTPUT
ST 0 1 2 3 4 5 6 7
FUSE O
K
ST 8 9 10 11 12 13 14 15
FUSE
On to Off 9.3 ms @ 60 Hz
11 ms @ 50 Hz
Current draw @ 5.1V 400 mA
Current draw @ 24V 2 mA
Total backplane power 2.1 W
Power dissipation, max 6.5 W @ 60 °C (140 °F)
Thermal dissipation 22.17 BTU/hr
Off-state leakage current, max 3 mA per point
On-state voltage drop, max 1.5V @ 0.5 A
5.7V @ load current < 50 mA
Current per point, max 0.5 A @ 60 °C (140 °F)
Current per group, max 2 A @ 60 °C (140 °F)
Current per module, max 4 A @ 60 °C (140 °F)
Surge current per point 5 A for 43 ms per point, repeatable every 2 s @ 60 °C (140 °F)
Surge current per group 15 A for 43 ms per point, repeatable every 2 s @ 60 °C (140 °F)
Load current, min 10 mA per point
Commutating voltage 4V/μs for loads > 50 mA
0.2V/μs for loads < 50 mA(2)
Scheduled outputs Synchronization within 16.7 s max, reference to the Coordinated System Time
States in Fault mode per point Hold last state, On or Off (Off is default)
States in Program mode per point Hold last state, On or Off (Off is default)
Isolation voltage 250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group
No isolation between individual group outputs
Routine tested @ 1400V AC for 2 s
Inhibit voltage, max Zero crossing 60V peak
Module keying Electronic, software configurable
Fusing Mechanically fused/group, 3.15 A @ 250V AC slow blow, 1500 A interruption current, Littelfuse p/n H2153.15
Removable terminal block 1756-TBNH
1756-TBSH
RTB keying User-defined mechanical
Slot width 1
1756-OA16I
+5V 1756-OA161
L1-0
Isolated Wiring
L1-13 28 27 OUT-13
L1-14 30 29 OUT-14
Continuous @ 30 °C (86 °F)
2A L1-15 32 31 OUT-15
Continuous @ 60 °C (140 °F) L1
1A L1-15 34 33 Not Used
Not Used 36 35 Not Used
L2
0 43 ms
Time
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11 12 13 14 15 K
On to Off 9.3 ms @ 60 Hz
11 ms @ 50 Hz
1756-OB8
2A 18 17
DC-1 (+) OUT-7
20 19
RTN OUT-1 RTN OUT-1
0 10 ms
Time Daisy Chain to
Other RTBs
+ –
DC COM
DC OUTPUT
ST 0 1 2 3 4 5 6 7 O
K
1756-OB8EI
32 31
2A Not Used 34 33 Not Used
Daisy Chain to
Other RTBs Not Used 36 35 Not Used
0 10 ms
Time
+ –
DC OUTPUT DC COM
ST 0 1 2 3 4 5 6 7 O
FUSE 0 1 2 3 4 5 6 7 K
ELECTRONICALLY FUSED
1756-OB8I
2A Other
RTBs
0 10 ms
Time
DC OUTPUT
ST 01234567 O
K
1756-OB16D
30 29
2A
GND-1 32 31 OUT-15
Continuous @ 60 °C (140 °F) GND-1 34 33 Not Used
Not Used 36 35 Not Used
0 10 ms Daisy Chain
to Other RTBs
Time
+ – DC COM
DC OUTPUT
ST 0 1 2 3 4 5 6 7
O
FLT 0 1 2 3 4 5 6 7
K
ST 8 9 10 11 12 13 14 15
FLT 8 9 10 11 12 13 14 15
DIAGNOSTIC
1756-OB16E
OUT-1 OUT-0
4 3
OUT-11 OUT-10
Surge 16 15
2A
OUT-13 OUT-12
Continuous @ 60 °C (140 °F)
Current
1A Group 1 18 17 Group 1
OUT-15 OUT-14
20 19
DC OUTPUT
ST 0 1 2 3 4 5 6 7
FUSE O
K
ST 8 9 10 11 12 13 14 15
FUSE
ELECTRONICALLY FUSED
1756-OB16I
DC OUTPUT
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11 12 13 14 15K
1756-OB16IEF
33
2A Not Used Not Used
36 35
Continuous 1A @ 60 °C (140 °F) DC(-)
1A
DC OUTPUT
ST 01 2 3 4 56 7
DIAG 01 2 3 4 5 6 7 O
K
ST 8 9 10 11 12 13 14 15
DIAG 8 9 10 11 12 13 14 15
PEER DEVICE
1756-OB16IEFS
ControlLogix DC (10…30V) scheduled, electronically-protected, sinking or sourcing, isolated, fast output module
33
2A Not Used Not Used
36 35
Continuous 1A @ 60 °C (140 °F) DC(-)
1A
DC OUTPUT
ST 0 1 2 3 4 5 6 7
FLT 0 1 2 3 4 5 6 7 O
K
ST 8 9 10 11 12 13 14 15
FLT 8 9 10 11 12 13 14 15
SCHEDULED
1756-OB16IS
DC OUTPUT
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11 12 13 14 15 K
1756-OB32
DC COM
DC OUTPUT
ST 0 1 2 3 4 5 6 7
1 11 11 1 O
ST 8 9 0 12 3 4 5
K
1 1 1 12 22 2
ST 6 7 8 90 1 2 3
2 2 2 22 23 3
ST 4 5 6 78 9 0 1
1756-OC8
+5V 2 1
DC-1(+) OUT-4
Surge Current Chart
14 13
DC-1(+) OUT-5
Surge Group 1 16 15 Group 1
4A
DC-1(+) OUT-6
18 17
2A 20 19
RTN OUT-1 RTN OUT-1
Daisy Chain to
Other RTBs
0 10 ms + –
Time
DC COM
DC OUTPUT
ST 0 1 2 3 4 5 6 7 O
K
1756-OF4
2 1 2 1 +
Not Used VOUT-0 i Not Used VOUT-0
4 3 4 3
Not Used IOUT-0 Current Not Used IOUT-0
6 5 A Output 6 5 –
RTN RTN Load RTN RTN
8 7 8 7
Not Used VOUT-1 Not Used VOUT-1
10 9 10 9 Shield
Not Used IOUT-1 Not Used IOUT-1 Ground
12 11 Shield 12 11
• Place additional loop devices (such as strip chart recorders) at the A location noted All terminals marked RTN are connected internally.
above.
• All terminals marked RTN are connected internally.
ANALOG OUTPUT
CAL
OK
1756-OF6CI
2 1 2 1
Place additional devices anywhere in the loop. Place additional devices anywhere in the loop.
ANALOG OUTPUT
CAL
OK
1756-OF6VI
1756-OF8
• Place additional loop devices (such as strip chart recorders) at the A location noted All terminals marked RTN are connected internally.
above.
• All terminals marked RTN are connected internally.
ANALOG OUTPUT
CAL
OK
1756-OF8H
1756-OF8H
ANALOG OUTPUT
CAL
OK
HART
1756-OF8I
ST O
K
FLT
1756-OF8IH
1756-OG16
OUT-1 Power –
OUT-0 OUT-1 OUT-0
4 3 4 3
OUT-3 OUT-2 OUT-3 OUT-2
+5 V DC 6 5 6 5
OUT-5 OUT-4 OUT-5 OUT-4
8 7
8 7
OUT-7 OUT-6
OUT-7 OUT-6
10 9
+ I/O Wire 10 9
+ DC DC-0(+) DC COM 0 DC-0(+)
12 11 DC COM 0
12 11
OUT-9 OUT-8 –
14 13 TTL OUT-9 OUT-8
14 13
OUT-11 OUT-10 Output
16 15 Device OUT-11 OUT-10
16 15
OUT-13 OUT-12 Capacitor
18 17 0.01 μF Typical OUT-13 OUT-12
OUT-15 OUT-14 (See notes below.) 18 17
20 19 OUT-15 OUT-14
DC-1(+) DC COM 1 20 19
DC-1(+) DC COM 1
Simplified Schematic
IMPORTANT: I/O cables must be shielded type and cable length
+5 DC
must be <10 m (32.8 ft) for maximum EMI noise immunity.
74AC14
OUT
DC OUTPUT
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11 12 13 14 15 K
74AC14
OUT
DC COM
1756-OH8I
DC OUTPUT
ST 0 1 2 3 4 5 6 7 O
K
1756-ON8
L1-0 OUT-0
4 3
L1-0 OUT-1
OUT-0 6 5
Group 0 L1-0 OUT-2 Group 0
ControlLogix Backplane Interface 8 7
L1-1 OUT-5
Current
16 15
Group 1 Group 1
L1-1 OUT-6
18 17
2A L1-1 OUT-7
20 19
L1
AC OUTPUT
ST 0 1 2 3 4 5 6 7 O
K
On to Off 9.3 ms @ 60 Hz
11 ms @ 50 Hz
Current draw @ 5.1V 200 mA
1756-OV16E
OUT-3 OUT-2
OUT-0 6 5
Group 0 OUT-5 OUT-4 Group 0
8 7
1A
0 10 ms + –
Time DC COM
Daisy Chain to Other RTBs Daisy Chain to Other RTBs
DC OUTPUT
ST 0 1 2 3 4 5 6 7
FUSE O
K
ST 8 9 10111213 1415
FUSE
ELECTRONICALLYFUSED
1756-OV32E
0 10 ms + _
Time
DC COM
DC OUTPUT
ST 0 1 2 3 4 5 6 7 F
0
1 1 1 11 1
ST 8 9 0 1 2 3 4 5 O
1 1 1 1 2 22 2 K
ST 6 7 8 9 0 1 2 3
2 2 2 2 2 23 3 F
ST 4 5 6 7 8 9 0 1 1
ELECTRONIC FUSING
1756-OW16I
ST 8 9 10 11 12 13 14 15K
1756-OX8I
ST 0 1 2 3 4 5 6 7 O
K
1756-CFM
2 1 2 1
Z0 12-24V DC Z1 12-24V DC Z0 12-24V DC Z1 12-24V DC
4 3 4 3
Z0 5V DC Z1 5V DC Z0 5V DC Z1 5V DC
6 5
6 5
Z0 Return Z1 RET Z0 Return Z1 RET
8 7
8 7
F0 F1
Input + F0 F1
10 9
Device 10 9
– F0 Return F1 Return
F0 Return F1 Return
12 11
12 11
Not Used Not Used
Not Used Not Used
Shield 14 13
14 13 Not Used Not Used
Ground
Not Used Not Used
16 15
16 15 Output 0 Output 1
Output 0 Output 1 18 17
18 17 Customer VCC Customer
Customer VCC Customer Common
+ 20 19 +
Common
20 19 Customer VCC Customer
Customer Load Common Load
Customer VCC
Common
– –
+
–
This wiring diagram can be used in applications with 50 mV (magnetic pickup), 1.3V
(TTL), or 4V (preamp level) thresholds. You must use RSLogix™ 5000 software to choose
the appropriate threshold level for your specific application.
The 1756-CFM module provides Totalizer mode for metering applications, or high-speed frequency measurements for
speed or rate control applications, on two channels connected to flowmeters.
2 1
12-24V DC + Z1 12-
Z0 12-24V DC
24V DC
– 4 3
Z0 5V DC Z1 5V DC
6 5
Shield Ground Z0 Return Z1 RET
8 7 METERING
Input + F0 F1
F Z F Z
Device 10 9 0 0 1 1
– F0 Return F1 Return
O
O O K
12 11
0 1
Shield Ground Not Used Not Used
14 13 DC I/O
Not Used Not Used
16 15
Output 0 Output 1
18 17
Customer VCC Customer
Common
20 19
Customer VCC Customer
Common
1756-HSC
The 1756-HSC module provides four high-speed, output-switching, on-off windows. The module uses pulses for counting
and frequency.
1756-LSC8XIB8I
Current Limiter
IN-x or CTR-x Opto-isolator Display
ControlLogix Backplane Interface
GND-x or CTR GND-x
GND-0 2 1 IN-0
DC-1 (-) GND-1 4 3 IN-1 DC-1 (+)
DC-2 (-) GND-2 6 5 IN-2 DC-2 (+)
GND-3 8 7 IN-3
Source Input Wiring GND-4 10 9 IN-4
DC-5 (-) GND-5 12 1 1 IN-5 (+) DC-5 (+)
DC-6 (-) GND-6 14 1 3 IN-6 (+) DC-6 (+)
GND-7 16 1 5 IN-7
Jumper Bar Cut to Length CTR-GND-0 18 1 7 CTR-0
CTR GND-1 20 1 9 CTR-1
Sink Input Wiring
CTR GND-2 22 2 1 CTR-2
CTR GND- 3 24 2 3 CTR-3
Nonisolated Wiring CTR GND-4 26 2 5 CTR-4 See page 235 for
CTR GND- 5 28 2 7 CTR-5 proximity sensor wiring.
CTR GND-6 30 2 9 CTR-6
CTR GND- 7 32 3 1 CTR-7
DC (-) CTR GND-7 34 3 3 Not Used DC (+)
Not Used 36 3 5 Not Used
COUNTER
ST 01234567 O
K
CTR 01234567
PEER DEVICE
The following diagram shows how to wire a proximity sensor to the module’s eight counters or eight hardware inputs.
Counters use incoming pulses for counts and frequency with two user-configurable On/Off windows per counter.
Hardware inputs provide standard input or counter control functionality.
Brown Black
12…24V DC
1756-PLS
OUTPUT 3 OUTPUT 11
INPUT 3 _ INPUT 11
10 9 10 9
INPUT 6
+ OUTPUT 14 INPUT 14
OUTPUT 6
18 17 18 17
The 1756-PLS module supports enhanced packaging applications. The module requires three contiguous slots in the
chassis.
1756-PLS Resolver
2 1
Indicator for Left Slot I/O Module Indicator for Left Resolver Module Indicator for Right Slot I/O Module
OUT 0 1 2 3 4 5 6 7 OUT 8 9 10 11 12 13 14 15
O O O
IN 0 1 2 3 4 5 6 7 K K IN 8 9 10 11 12 13 14 15 K
(1) UL certification for 24V DC nominal. Rockwell Automation specified to 10.8…31.2V DC.
(1) UL certification for 24V DC nominal. Rockwell Automation specified to 10.8…31.2V DC.
(2) Derate 16.7 mA/ °C above 30 °C (86 °F): 0.5 A @ 60 °C (140 °F).
(3) Derate 66.8 mA/ °C above 30 °C (86 °F): 2 A @ 60 °C (140 °F).
(4) Derate 133.6 mA/ °C above 30 °C (86 °F): 4 A @ 60 °C (140 °F).
• For more information on chassis specifications, see ControlLogix Chassis Specifications Technical Data, publication
1756-TD006.
• For more information on power supply specifications, see ControlLogix Power Supply Specifications Technical
Data, publication 1756-TD005.
• For more information on choosing the right power supply for your application, see the additional product
documentation, for example, a user manual, for your 1756 ControlLogix I/O module.
Removable terminal blocks (RTBs) provide a flexible interconnection between your plant
wiring and 1756 I/O modules. The RTB plugs into the front of the I/O module. The type
of module determines which RTB you need. You can choose screw-clamp or
spring-clamp RTBs.
RTBs are not shipped with I/O modules. You must order them separately. The standard
housing on the front of the wiring arm is not deep enough for 2.5 mm2 (14 AWG) wiring.
If you plan to use 2.5 mm2 (14 AWG) wiring, also order the extended housing.
ATTENTION: If separate power sources are used, do not exceed the specified isolation voltage: referring to each individual module’s
specifications on the preceding pages.
Wiring Systems
As an alternative to buying RTBs and connecting the wires yourself, you can buy a wiring system of the following:
• Interface modules (IFMs) that provide the output terminal blocks for digital I/O modules. Use the pre-wired cables
that match the I/O module to the IFM.
• Analog interface modules (AIFMs) that provide the output terminal blocks for analog I/O modules. Use the
pre-wired cables that match the I/O module to the AIFM.
• I/O module-ready cables. One end of the cable assembly is an RTB that plugs into the front of the I/O module. The
other end has individually color-coded conductors that connect to a standard terminal block.
Additional Resources
These documents contain additional information concerning related products from Rockwell Automation.
Resource Description
ControlLogix System User Manual, publication 1756-UM001 Provides information about using a ControlLogix system.
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation® industrial system.
Product Certifications website, http://www.ab.com Provides declarations of conformity, certificates, and other certification details.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required
to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this
document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.
Allen-Bradley, ControlLogix, RSLogix, Rockwell Software, Rockwell Automation, and LISTEN. THINK. SOLVE are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400