D1-356 lf Deviation Alarm Check Y Deviation Alarm The deviation alarm check in the VELLIM block is applicable to the deviation (DV) between the manipulated output value (MV) converted to a value in the setpoint (SV) range and the setpoint value (SV). When the absolute value of the deviation (DV) exceeds the absolute value of the deviation alarm setpoint (DL), either a positive direction deviation alarm (DV+) or a negative direction deviation alarm (DV-) is generated. When an alarm has occurred, it the deviation (DV) absolute value drops lower than the absolute value of the deviation alarm setpoint (DL) minus the hysteresis value (HYS), the alarm is returned to normal state ‘There is no deviation check filter function in the VELLIM block deviation alarm check. The deviation (DV) thats subject tothe deviation alarm check ofthe VELLIM block is expressed inthe following format DV=Mvs-SV SSH-SSL Mvs = ———""—. (mv-MSL) +88 MSH=MSL. onanatsra ve Marpdodoupu va secon SV ange 53 SV sal tt Mist! Mw Salone When the deviation (DV) absolute value exceeds the absolute value of the deviation alarm setpoint (DL) and the deviation is for the positive direction, a positive direction deviation alarm (DV+) occurs. Ifthe deviation is for the minus direction, a negative direction deviation alarm (DV4) occurs. When an alarm has occurred, ifthe deviation (DV) absolute value drops lower than the absolute value of the deviation alarm setpoint (DL) minus the hyster- esis value (HYS), there is a recovery from the alarm, Further, when the same value as for the SV scale span (positive value) is setin the devia tion alarm setpoint (DL), neither a positive direction nor negative direction deviation alarm ‘occurs regardless of the deviation alarm check. ov Contons causing an alarm Dv=+0L ove-DL CCondons causing recovery trom alarm DL-HYs DLIHYS Figure Actions of Deviation Alarm Check in the Velocity Limiter Block (VELLIM) D1-357 © Deviation Alarm Check Settings ‘The type of deviation alarm check, deviation alarm setpoint (DL), and alarm hysteresis value can be set. The type of deviation alarm check is defined by the “deviation alarm check’ item in the Function Block Detail Builder, The types of deviation alarm checks are given below. The defaultis “detection of both directions.” + Detection of both directions: Monitors the deviation of both the positive and negative directions + Detection of single direction: Monitors the deviation of either the positive or negative direction only + Noslarm: No detection is performed When single direction is selected for the deviation alarm check type, only the deviation in the positive direction is monitored when the deviation alarm setpoint (DL) has a plus sign, and only the deviation in the negative direction is monitored when the deviation alarm setpoint has a minus sign. Setting of the deviation alarm check type can be performed in the sequence control block or CALCU, CALCU-C blocks in addition to the Function Block Detail Builder. The deviation alarm setpoint (DL) is set by the operation and monitoring function, + Deviation alarm setpoint (DL): Engineering unit data within the ~-SV scale span range Default is =“SV scale span When single direction is selected for the deviation alarm check type, add the sign (+ or-) for the direction to be detected to the deviation alarm setpoint (DL) engineering unit data, -value is done by the Function Block Detail Builder for each Setting for the alarm hystere: regulatory control block. + Hysteresis: Engineering unit data within the range of 0 to SV scale span, or percentage data for the SV scale span When specifying percentage data, add % after the numeric value, ‘The default is 1.0%.

You might also like