You are on page 1of 52

NATIONAL THERMAL POWER CORPORATION LIMITED.

DETAIL SURVEY REPORT


FOR
400 KV transmission line from NTPC Singraulli
stage III switchyard to NTPC Vindyanagar stage
IV & V.

Surveyed & Report Prepared By:


M/S DYNAMIC ENGINEERING
SERVICES
House of Pankaj Ghosh,
Vill:- Gohaildanga,P.O.-Kaigram
Dist.-Purba Bardhaman.
West Bengal, Pin: 713145.
Report no. DES/NTPC/SSTPS/400KV, Rev. 0 Date: 18.03.2023
P.O.No. 5500041503-045-1004 Date: 21.10.2022

|Page
List of Annexure
66 kV S/C Transmission Line from NTPC Lara to Intake Well at
Saradih Dam, NTPC Lara
NTPC LTD
Contents
Annexure /
Sr. No. Description Appendix
No.

1 Anexures Details I
2 Tower Schedule II
3 Wind Span And Weight Span Calculation III
4 Tower Summary IV
5 List of Houses V
6 Crossing Clearance Report VI
7 Tower Location Details VII
8 Power Line Crossing VIII
9 Ground Clearance Report IX
10 Sag Tension Calculation X
11 Tower Spotting Data XI
12 Sag Template Drawing XII
13 Transmission Line Details XIII
14 Tower Details XIV
15 Report Summary XV
16 Tree Schedule Xvi
17 Stringing Chart Xvii
1. Introduction :

a) NTPC Limited is planning to construct 400kV Double circuit transmission line ( 1no) from
proposed Singrauli-III 400KV switchyard to Vindyachal Super thermal Power plant
(VSTPP) Stage-IV switchyard and 400kV Double circuit transmission line ( 1no) from
proposed Singrauli-III 400KV switchyard to Vindyachal Super thermal Power plant
( VSTPP) Stage-V Stage-V) at Singrauli Super Thermal Power Station (SSTPS). For Power
Requirement of a new project. Contract has been awarded to M/s Dynamic Engineering
Services. for conducting survey and submission of detailed report for transmission line from
NTPC Singraulli stage III switchyard to NTPC Vindyanagar stage IV & V.

b) The Detail Survey has been carried out based on the feasibility to construct the transmission
lines and as per requirement of the client. The routes were selected after physical inspection
and validation of the various routes along with merits, de-merits, the most feasible routes
proposed based on physical and Geo-graphical site conditions in our Preliminary
Reconnaissance Survey.

c) This report covers the observation made during Detail Survey of the routes.

2. Scope of Work:-

a) Route SURVEY:-
The preliminary survey shall be carried out along the Transmission Line alignment by
successful bidder/contractor.

b) Profile Plotting & Tower Spotting:-

From the field book entries the route plan with route details and level profile shall be plotted
and prepared as per approved procedure. Reference levels at every 20 meters along the
profile are also to be indicated on the profile besides R/Ls at undulations. Areas along the
profile, which in the view of the Contractor are not suitable for tower spotting, shall also be
clearly marked on the profile plots. If the difference in levels is too high, the chart may be
broken up according to requirement. A 10mm overlap shall be shown on each following
sheet. The chart shall progress from left to right. Sheet shall be in accordance with the IS
Standard. For `as built’ profile these shall be in A1 size.

c) Sag Template:-

Based on respective conductor, earthwire and insulator, the Contractor shall prepare the sag
template drawing and tower spotting data and submit the same. Sag template prepared based
on the approved sag-template curve drawing shall only be used for tower spotting on the
profiles. Sag template curves, shall be prepared by the contractor indicating cold curve, hot
curve, ground clearance curve and support footing curve and the same shall be submitted.
d) Tower Spotting:-

With the help of approved sag template and tower spotting data, tower locations shall be
marked on the profiles. While locating the towers on the profile sheet, the following shall be
borne in mind:

i) Span:-
The number of consecutive spans between the section points shall not exceed 15 spans
Section point shall comprise of tension point with B type, C type or D Type towers as
applicable. For all crossing spans such as major road crossings, railway crossings, power
line crossings etc. the span shall not exceed 80% of design span.

ii) Extension:-
An individual span shall be as near to the normal design span as far as possible. In case an
individual span becomes too short with normal supports on account of undulations in ground
profile, one or both the0 supports of the span may be extended by inserting standard body
extension designed for the purpose according to technical specification.

iii) Road Crossing:-


At all important road crossings, the towers shall be fitted with double tension insulator
strings depending on the type of towers but the ground clearance at the roads under
maximum temperature and in still air shall be such that even with conductor broken in
adjacent span, ground clearance of the conductor from the road surfaces shall be in line with
IE rules. At all national highway crossings, tensions towers shall be used.

iv) Railways Crossings:-


1) At the time of detail survey all the railway crossings coming enroute the transmission
line shall be finalised as per the regulation laid down by the Railway Authorities. The
following are the important features of the prevailing regulations (revised in 1987):
2) The crossing shall be supported on D type tower on either side of railway line with
double tension insulator strings.
3) The crossing shall normally be at right angle to the railway track.
4) The crossing span shall be limited to 80% of design span.
5) The minimum distance of the crossing tower shall be at least equal to the height of the
tower plus 6 meters away measured from the centre of the nearest railway track.
6) No crossing shall be located over a booster transformer, traction switching station,
traction sub-station or a track cabin location in an electrified area.
7) Minimum ground clearance above rail level of the lowest portion of any conductor
under condition of maximum sag shall be maintained as per IE rules.
8) The approval for crossing railway track shall be obtained by the Owner from the
Railway Authority. However, six copies of profile and plan, tower and foundation
design and drawings, required for the approval from the Railway Authority shall
supplied by the Contractor to the Owner.
v) River Crossings:-
In case of major river crossing, towers shall be of suspension type and the anchor towers on
either side of the main river crossing shall be C type tower. Clearance required by
navigation authority shall be provided. For non navigable river, clearance shall be reckoned
with respect to highest flood level (HFL).

vi) Power Line Crossing:-


Where this line is to cross over another line of the same voltage or lower voltage, towers
with suitable extension shall be used. Provisions to prevent the possibility of its coming into
contact with other overhead lines shall be made in accordance with the Indian Electricity
Rules, 1956. The Contractor may be required to under-cross higher voltage lines by erecting
gantry structures.

vii) Telecommunication Line Crossing:-


The angle of crossing shall be as near 90 degree as possible. However, deviation to the
extent of 30 degree may be permitted under exceptionally difficult situations.When the angle
of crossing has to be below 60 degree, the matter will be referred to the authority incharge of
the telecommunication system. On a request from the Contractor, the permission of the
telecommunication authority may be obtained by the Owner. Also, in the crossing span
power line support will be as near the telecommunication line as possible, to obtain
increased vertical clearance between the wires.

viii) Details Enroute:-


All topographical details, permanent features, such as trees, building etc. 26m on either side
of the alignment shall be detailed on the profile plan.
i) Ash Pipe Line
Adequate clearances shall be maintained from ash pipe line and adjacent road.

e) Clearance from Ground, Building, Trees, etc.:-


Clearance from ground, buildings, trees and telephone lines shall be provided in conformity
with the Indian Electricity Rules, 1956 as amended upto date.

f) PRELIMINARY LINE SCHEDULE:-


The profile sheets, duly spotted, alongwith preliminary schedules indicating type of towers,
wind span, weight span, angle of deviation, river, power line, railway or road crossing and
other details shall be submitted for the approval of the Owner. After approval, the
Contractor shall submit six more sets of the approved reports along with two sets in soft
copy of final profile drawings to the Owner for record purpose.

g) ELECTRICAL SYSTEM DATA:-


Nominal voltage 400 kV
Highest system voltage 420 kV
Lighting Impulse voltage +-1425 kVp
Switching Impulse voltage + -1050 kVp
Power frequency withstand voltage (wet) 630 kV (rms)
Min.Creepage distance 25mm/kV
2023

Detail Survey Report Annexures


for 400kv DC NTPC Vind V to NTPC
Singrauli-III Transmission Line
(Option-2)

CLIENT: NATIONAL THERMAL POWER CORPORATION Ltd.

EXECUTED BY-
M/S DYNAMIC ENGINEERING SERVICES
House of Pankaj Ghosh, Vill:- Gohaildanga,
P.O.-Kaigram ,Dist.-Purba Bardhaman.
West Bengal, Pin: 713145.
Annexure - II
400kv DC NTPC Vind V to NTPC Singrauli-III Transmission Line (Option-2)
NTPC LTD
Tower Schedule-(Option-2)
Angle Point No. / Total Span Section
Location Type of Angle of Deviation
Tower No. / Length Remarks
No. Tower / Gantry ( ° ' "L / R )
Gantry No. (m) (m)

AP-1 AP-1 DD+0 0


294 Boundary Wall,Canal,Metal Road,11kv Line(2Nos)
AP-2 AP-2 DD+0 56°52'51"LT 294

317 Boundary Wall,Metal Road,11kv Line(2Nos),Rail Way Line,Gomty


AP-3 AP-3 DD+25 07°26'11"LT 317

291 Metal Road,132kv S/C TR. Line


AP-4 AP-4 SPL+45 47°15'55"LT 291

229 Metal Road,Canal,132kv S/C TR. Line,400kv D/C Tr. Line(2Nos)


AP-5 AP-5 SPL+50 26°45'14"LT 229

243 132kv DC Tr Line,400kv DC Tr Line


AP-6 AP-6 DD+25 78°15'18"RT 243
Metal Road,Boundary Wall,Building
235
Ex. Angle-
40°23'03"LT
Existing Pro. Angle-
Tower-5 Existing Tower-5 DD+0 12°24'02"LT 235
Annexure - III
400kv DC NTPC Vind V to NTPC Singrauli-III Transmission Line
(Option-2)
NTPC LTD
Wind Span and Weight Span Calculation-(Option-2)

Angle Point No. / Wind Span (m) Cold Curve Weight Span (m) Hot Curve Weight Span (m)
Location Type of Total Span
Tower No. /
No. Tower / Gantry (m)
Gantry No. Left Right Total Left Right Total Left Right Total

AP-1 AP-1 DD+0 0.00 147 147 0.00 65 65 0.00 35 35


294
AP-2 AP-2 DD+0 147 306 453 229 121 349 259 107 366
317
AP-3 AP-3 DD+25 306 304 610 197 20 217 211 -27 184
291
AP-4 AP-4 SPL+45 304 260 564 271 10 282 318 -28 290
229
AP-5 AP-5 SPL+50 260 236 496 219 140 359 258 146 404
243
AP-6 AP-6 DD+25 236 239 475 103 425 528 96 539 635
235
Existing Existing Tower-
Tower-5 5 DD+0 239 0.00 239 -189 0.00 -189 -303 0.00 -303
Annexure - IV
400kv DC NTPC Vind V to NTPC Singrauli-III Transmission Line (Option-2)
NTPC LTD
Tower Schedual Summary
Tower Tower Tower Tower Tower
Normal Tower Tower Tower
Type of Extension Extension Extension Extension Extension
Sr. No. Tower Extension Extension Extension
Tower Piece +12 Piece +15 Piece +18 Piece +25 Piece +30
+0 Piece +3 (m) Piece +6 (m) Piece +9 (m)
(m) (m) (m) (m) (m)

1 A 0 0 0 0 0 0 0 0 0
2 B 0 0 0 0 0 0 0 0 0
3 C 0 0 0 0 0 0 0 0 0
4 D 3 0 0 0 0 0 0 2 0
1
5 SPL+45
1
6 SPL+50
0
7 RIVER CROSSING
8 PI TYPE GANTRY 0
SINGLE SIDE 0
9 CROSS ARM
TOWER
CABLE 0
10
TERMINATION
Annexure - V
400kv DC NTPC Vind V to NTPC Singrauli-III
Transmission Line (Option-2)
NTPC LTD
No of Houses Falling on the Route of Transmission Line
Sr. No. Number of Families and houses Total Families
coming in Corridor
UP MP
1 NIL 18 18
Annexure - VI
400kv DC NTPC Vind V to NTPC Singrauli-III Transmission Line
(Option-2)
NTPC LTD
Crossing Clearence Details
Sr. No. From Crossing Type Distance of Interference Inerference Inerference Interference Clearence Clearence Difference Allowable
Location Width Height / Position Obtained Specified Status
Point From To Depth
(m) (m) (m) (m) (m)

1 AP1 Metal Road 194.08 211.892 17.812 0 Under Line 25.42 8.84 16.58 Allow
2 AP1 11kv Line 0 0 0 7.5 Under Line 19.30 5.49 13.81 Allow
3 AP1 11kv Line 0 0 0 7.5 Under Line 19.80 5.49 14.31 Allow
4 AP2 11kv Line 0 0 0 7.5 Under Line 22.70 5.49 17.21 Allow
5 AP2 11kv Line 0 0 0 7.5 Under Line 23.10 5.49 17.61 Allow
6 AP2 Metal Road 211.758 230.754 18.996 0 Under Line 33.30 8.84 24.46 Allow
7 AP2 Rail Line 264.040 273.466 9.426 0 Under Line 37.21 17.9 19.31 Allow
8 AP3 Metal Road 94.67 106.80 12.13 0 Under Line 43.44 8.84 34.6 Allow
9 AP3 132 Kv line 0 0 0 35.517 Under Line 16.50 5.49 11.01 Allow
10 AP4 Metal Road 25.80 35.77 9.97 0 Under Line 67.02 8.84 58.18 Allow
11 AP4 132 Kv line 0 0 0 33.170 Under Line 35.20 5.49 29.71 Allow
12 AP4 400 Kv line 0 0 0 46.904 Under Line 23.90 5.49 18.41 Allow
13 AP4 400 Kv line 0 0 0 45.935 Under Line 20.90 5.49 15.41 Allow
14 AP5 132 Kv line 0 0 0 39.559 Under Line 20.00 5.49 14.51 Allow
15 AP5 400 Kv line 0 0 0 44.356 Under Line 6.7 5.49 1.21 Allow
16 AP6 Metal Road 164.72 171.29 6.57 0 Under Line 36.77 8.84 Allow
27.93
17 AP6 11kv Line 0 0 0 8.5 Under Line 24.90 5.49 19.41 Allow
Annexure - VII
400kv DC NTPC Vind V to NTPC Singrauli-III Transmission Line (Option-2)
NTPC LTD
Tower Details
Location Angle Point No. / Type of Distance of Tower Point Tower Chainge in Easting Northing
No. Tower No. / Tower / Gantry Next Tower Elevation Height (KM)
Gantry No. (m) (m) (m)

AP-1 AP-1 DD+0 271.325 42.3 0.000 672146.712 2666732.853


294
AP-2 AP-2 DD+0 287.255 42.3 0.294 672102.300 2667023.337
317
AP-3 AP-3 DD+25 270.252 67.3 0.611 671813.310 2667154.591
291
AP-4 AP-4 SPL+45 274.525 87.3 0.902 671534.788 2667239.693
229
AP-5 AP-5 SPL+50 285.363 92.3 1.131 671336.943 2667124.199
243
AP-6 AP-6 DD+25 307.425 67.3 1.374 671204.732 2666920.388
235
Existing
Tower-5 Existing Tower-5 DD+0 284.525 42.3 1.609 670985.295 2667005.618
Annexure - VIII
400kv DC NTPC Vind V to NTPC Singrauli-III Transmission Line (Option-2)
NTPC LTD
Power Transmission Line Crossing Report
Sr. No. From Point Type of Distance of Heigh of Crossing Obtained Specified Differenced Allowable
Power Line Power Line Power Line Type Clearance Clearance Clearance Status
(m) (m) (m) (m) (m) (m)

AP1 11kv Line 7.5


1 234.20 Under Crosing 19.30 5.49 Allow
13.81
AP1 11kv Line 7.5
2 241.537 Under Crossing 19.80 5.49 Allow
14.31
AP2 11kv Line 7.5
3 170.11 Under Crossing 22.70 5.49 Allow
17.21
AP2 11kv Line 7.5
4 180.44 Under Crossing 23.10 5.49 Allow
17.61
AP3 132 Kv line
5 196.58 35.517 Under Crossing 16.50 5.49 Allow
11.01
AP4 132 Kv line 33.170
6 83.03 Under Crossing 35.20 5.49 Allow
29.71
AP4 400 Kv line 46.904
7 117.70 Under Crossing 23.90 5.49 Allow
18.41
AP4 400 Kv line 45.935
8 181.15 Under Crossing 20.90 5.49 Allow
15.41
AP5 132 Kv line 39.559
9 109.78 Under Crossing 20.00 5.49 Allow
14.51
AP5 400 Kv line 44.356
10 166.15 Under Crossing 6.7 5.49 Allow
1.21
AP6 11kv Line 24.90 5.49
11 171.29 8.5 Under Crossing Allow
19.41
Annexure - IX
400kv DC NTPC Vind V to NTPC Singrauli-III Transmission Line
(Option-2)
NTPC LTD
Ground Clearance Details
Sr. No. Tower / Gantry Tower / Gantry Tower / Gantry Refference Distance to Next Obtained Specified Differenced Allowable
No. Type Height Ground Level Tower Clearance Clearance Clearance Status
(m) (m) (m) (m) (m)

1 AP-1 DD+0 42.3 271.325 294 22.25 8.84 13.41 Allow


2 AP-2 DD+0 42.3 287.255 317 22.25 8.84 13.41 Allow
3 AP-3 DD+25 67.3 270.252 291 47.25 8.84 38.41 Allow
4 AP-4 SPL+45 87.3 274.525 229 67.25 8.84 58.41 Allow
5 AP-5 SPL+50 92.3 285.363 243 72.25 8.84 63.41 Allow
6 AP-6 DD+25 67.3 307.425 235 47.25 8.84 38.41 Allow
8 Existing 22.25 8.84 Allow
Tower-5 DD+0 42.3 284.525 13.41
Annexure - X
400kv DC NTPC Vind V to NTPC Singrauli-III Transmission Line (Option-2)
Sag Tension Calculation (NTPC)
Conductor
Entry Data
Conductor MOOSE ACSR
Span, L (m) 400
W Pressure (Kg/m2) 161
Starting Condition 32
FOS 4.545454545

Conductor Properties
UTS (Kg) 16428
Wt of Conductor, w (kg/m) 2.004
Wt of Cndctr/unit Area, δ (Kg/m/cm2) δ=w/A 0.336
Overall Diameter, d (mm) 31.770
Cross Sec Area, A (cm2) 5.97
Co-eff of Lin Expansion, α (/oC) 1.93E-05
Y Mod of Elasticity (Final), Ef 7.03E+05

Determination of K
Temp. 32 Deg, 0 % Wind
FOS/UTS 4.545454545
Working Tension, T1 (Kg) T= UTS/FOS 3614.16
2
Working Stress, f1 (Kg/cm ) f= T/A 605.39
Loading Factor, q1 q= √(P2+w2)/w 1
Co-efficient, k k= f-(L2δ2q2E f)/24f2 -836.37

Condition-1
Temp 0 Deg
Wind 0 %
2 2
Loading Factor, q1 q1= √(P +w )/w 1
Difference in Temperature, t (oC) t= Temp - Evrydy Temp -32
Formula for Determination of working Strees:
2 2 2 2
f1 [f1-(k-αtEf)] = (L δ q1 Ef)/24
Putting the value of k, α, t, Ef, L, δ, q2, the p
f1 = 694.272
Working Tension, T1 (Kg) T1= f1 * A 4144.805
Maximum Sag, s (m) s=w * L2/8T 1 9.67
Conductor
Condition-2
Temp 32 Deg
Wind 0 %
2 2
Loading Factor, q1 q1= √(P +w )/w 1
Difference in Temperature, t (oC) t= Temp - Evrydy Temp 0
Formula for Determination of working Strees:
2 2 2 2
f1 [f1-(k-αtEf)] = (L δ q1 Ef)/24
Putting the value of k, α, t, Ef, L, δ, q2, the value of f2 is:
f1 = 605.387
Working Tension, T1 (Kg) T1= f1 * A 3614.160
Maximum Sag, s (m) s=w * L2/8T1 11.09

Condition-3
Temp 75 Deg
Wind 0 %
2 2
Loading Factor, q1 q1= √(P +w )/w 1
Difference in Temperature, t (oC) t= Temp - Evrydy Temp 43
Formula for Determination of working Strees:
2 2 2 2
f1 [f1-(k-αtEf)] = (L δ q1 Ef)/24
Putting the value of k, α, t, Ef, L, δ, q2, the value of f2 is:
f1 = 521.651
Working Tension, T1 (Kg) T1= f1 * A 3114.255
Maximum Sag, s (m) s=w * L2/8T1 12.87

Condition-4
Temp 0 Deg
Wind 36 %
2 2
Loading Factor, q1 q1= √(P +w )/w 1.358049328
Difference in Temperature, t (oC) t= Temp - Evrydy Temp -32
Formula for Determination of working Strees:
2 2 2 2
f1 [f1-(k-αtEf)] = (L δ q1 Ef)/24
Putting the value of k, α, t, Ef, L, δ, q2, the value of f2 is:
f1 = 873.950
Working Tension, T1 (Kg) T1= f1 * A 5217.479
Maximum Sag, s (m) s=w * L2/8T1 7.68
Conductor
Condition-5
Temp 32 Deg
Wind 100 %
2 2
Loading Factor, q1 q1= √(P +w )/w 2.741285262
Difference in Temperature, t (oC) t= Temp - Evrydy Temp 0
Formula for Determination of working Strees:
2 2 2 2
f1 [f1-(k-αtEf)] = (L δ q1 Ef)/24
Putting the value of k, α, t, Ef, L, δ, q2, the value of f2 is:
f1 = 1348.190
Working Tension, T1 (Kg) T1= f1 * A 8048.697
Maximum Sag, s (m) s=w * L2/8T1 4.98

Condition-6
Temp 32 Deg
Wind 75 %
2 2
Loading Factor, q1 q1= √(P +w )/w 2.159742519
Difference in Temperature, t (oC) t= Temp - Evrydy Temp 0
Formula for Determination of working Strees:
2 2 2 2
f1 [f1-(k-αtEf)] = (L δ q1 Ef)/24
Putting the value of k, α, t, Ef, L, δ, q2, the value of f2 is:
f1 = 1121.881
Working Tension, T1 (Kg) T1= f1 * A 6697.630
Maximum Sag, s (m) s=w * L2/8T1 5.98
GROUND WIRE
Entry Data
Conductor EW 7/3.66
Span, L (m) 400
W Pressure (Kg/m2) 200
Starting Condition 0
FOS 1339.78

Conductor Properties
UTS (Kg) 6972
Wt of Conductor, w (kg/m) 0.583
Wt of Cndctr/unit Area, δ (Kg/m/cm2) δ=w/A 0.792
Overall Diameter, d (mm) 10.980
Cross Sec Area, A (cm2) 0.73646
Co-eff of Lin Expansion, α (/oC) 1.15E-05
Y Mod of Elasticity (Final), Ef 1.94E+06

Determination of K
Temp. 0 Deg, Wind Nill
FOS/UTS 1339.78
Working Tension, T1 (Kg) T= UTS/FOS 1339.78
2
Working Stress, f1 (Kg/cm ) f= T/A 1819.22
Loading Factor, q1 q= √(P2+w2)/w 1
Co-efficient, k k= f-(L2δ2q2E f)/24f2 -624.81

Condition-1
Temp 0 Deg
Wind 0 %
2 2
Loading Factor, q1 q1= √(P +w )/w 1
Difference in Temperature, t (oC) t= Temp - Evrydy Temp 0
Formula for Determination of working Strees:
2 2 2 2
f1 [f1-(k-αtEf)] = (L δ q1 Ef)/24
Putting the value of k, α, t, Ef, L, δ, q2, the value of f2 is:
f1 = 1819.216
Working Tension, T1 (Kg) T1= f1 * A 1339.780
Maximum Sag, s (m) s=w * L2/8T1 8.70
GROUND WIRE
Condition-2
Temp 32 Deg
Wind 0 %
2 2
Loading Factor, q1 q1= √(P +w )/w 1
Difference in Temperature, t (oC) t= Temp - Evrydy Temp 32
Formula for Determination of working Strees:
2 2 2 2
f1 [f1-(k-αtEf)] = (L δ q1 Ef)/24
Putting the value of k, α, t, Ef, L, δ, q2, the value of f2 is:
f1 = 1646.474
Working Tension, T1 (Kg) T1= f1 * A 1212.562
Maximum Sag, s (m) s=w * L2/8T1 9.62

Condition-3
Temp 75 Deg
Wind 0 %
2 2
Loading Factor, q1 q1= √(P +w )/w 1
Difference in Temperature, t (oC) t= Temp - Evrydy Temp 75
Formula for Determination of working Strees:
2 2 2 2
f1 [f1-(k-αtEf)] = (L δ q1 Ef)/24
Putting the value of k, α, t, Ef, L, δ, q2, the value of f2 is:
f1 = 1466.478
Working Tension, T1 (Kg) T1= f1 * A 1080.003
Maximum Sag, s (m) s=w * L2/8T1 10.80

Condition-4
Temp 0 Deg
Wind 36 %
2 2
Loading Factor, q1 q1= √(P +w )/w 1.684871456
Difference in Temperature, t (oC) t= Temp - Evrydy Temp 0
Formula for Determination of working Strees:
2 2 2 2
f1 [f1-(k-αtEf)] = (L δ q1 Ef)/24
Putting the value of k, α, t, Ef, L, δ, q2, the value of f2 is:
f1 = 2648.546
Working Tension, T1 (Kg) T1= f1 * A 1950.548
Maximum Sag, s (m) s=w * L2/8T1 5.98
GROUND WIRE
Condition-5
Temp 32 Deg
Wind 100 %
2 2
Loading Factor, q1 q1= √(P +w )/w 3.897205217
Difference in Temperature, t (oC) t= Temp - Evrydy Temp 32
Formula for Determination of working Strees:
2 2 2 2
f1 [f1-(k-αtEf)] = (L δ q1 Ef)/24
Putting the value of k, α, t, Ef, L, δ, q2, the value of f2 is:
f1 = 4563.026
Working Tension, T1 (Kg) T1= f1 * A 3360.486
Maximum Sag, s (m) s=w * L2/8T1 3.47

Condition-6
Temp 32 Deg
Wind 75 %
2 2
Loading Factor, q1 q1= √(P +w )/w 2.996809517
Difference in Temperature, t (oC) t= Temp - Evrydy Temp 32
Formula for Determination of working Strees:
2 2 2 2
f1 [f1-(k-αtEf)] = (L δ q1 Ef)/24
Putting the value of k, α, t, Ef, L, δ, q2, the value of f2 is:
f1 = 3771.013
Working Tension, T1 (Kg) T1= f1 * A 2777.200
Maximum Sag, s (m) s=w * L2/8T1 4.20
Annexure - XI
400kv DC NTPC Vind V to NTPC Singrauli-III Transmission Line (Option-1)
NTPC LTD
Tower Spotting Data
Sr. No. Description Tower / Conductor Details

1 Conductor ACSR MOOSE


2 Max. Temp 85 degree Celcius
3 Wind Zone 4- (47 m/s)
2 Degree 15 Degree 30 Degree 60 Degree
1 Deviation not to exceed 2 15 30 60
Vertical Load of Individual Span CON. GW
600/100 600/-200 600/-200 600/-300
2 32Deg. 100% Wind
3 Vertical load Limitations
a. Maximum Weight Span
Ground wire; effect of both spans 600 600 600 600
Effect of one span 360 360 360 360
Conductor : Effect of both Spans 600 600 600 600
Effect of one span 360 360 360 360
b. Minimum Weight Span
Ground wire; effect of both spans 200 0 0 0
Effect of one span 100 -200 -200 -300
Conductor : Effect of both Spans 200 0 0 0
A B C D
Permission Wind span (sum of adjacent
4 2º 1154 15º 800 30º 800 60º 800
spans/2)
For various deviation angles 1º 1154 14º 844 29º 842 59º 838
Based on the Condition that required 0º 800 13º 888 28º 886 58º 878
Ground Clearance is available 12º 932 27º 930 57º 916
11º 976 26º 972 56º 956
10º 1026 25º 1016 55º 994
5 Design Load Tension
Ground Wire: 3359 3330 3244 2909
Conductor 8084 7979 7774 6970
Annexure - XIII

400kv DC NTPC Vind V to NTPC Singrauli-III Transmission Line (Option-1)


NTPC LTD
Transmission Line Details
Sr. No. Description Line Details

1 Line of Owner NTPC LTD


2 Line Location NTPC SSTPS
3 Transmission Line Voltage and Type 400 kV
4 Number of Circuit D/C
5 Starting Point NTPC Singrauli-III
6 Ending Point NTPC Vindyanagar Stage-V
7 Line Length (km) 1.609
8 Rulling Span (m) 400
9 Allowable Maximum Wind Span (m) 600
10 Allowable Minimum Wind Span (m) -300
Annexure - XIV
400kv Quad NTPC singralu-III to NTPC Vindhyachal-IV Switchayrd

NTPC LTD
Tower Details
Sr. No. Tower Tower Height
A+0 B+0 C+0 D+0

Total Height 43.0 42.8 42.6 42.3

1 +6 49 48.8 48.6 48.3


2 +25 68 67.8 67.6 67.3
3 +45 88 87.8 87.6 87.3
4 +50 93 92.8 92.6 92.3
Annexure - XV

400kv DC NTPC Vind V to NTPC Singrauli-III Transmission Line (Option-2)


NTPC LTD
Report Summary
Angle Point No. / Section Remarks Wind Span (m) Hot Curve Weight Span (m) Cold Curve Weight Span (m)
LocationNo. Type of Angle of Deviation Total Span
Tower No. / Length
Tower / Gantry ( ° ' "L / R ) (m) Left Right Total Left Right Total Left Right Total
Gantry No. (m)

AP-1 AP-1 DD+0 0 0.00 147 147 0.00 65 65 0.00 35 35


294 Boundary Wall,Canal,Metal Road,11kv Line(2Nos)
AP-2 AP-2 DD+0 56°52'51"LT 294 147 306 453 229 121 349 259 107 366

317 Boundary Wall,Metal Road,11kv Line(2Nos),Rail Way Line,Gomty


AP-3 AP-3 DD+25 07°26'11"LT 317 306 304 610 197 20 217 211 -27 184

291 Metal Road,132kv S/C TR. Line


AP-4 AP-4 SPL+45 47°15'55"LT 291 304 260 564 271 10 282 318 -28 290

229 Metal Road,Canal,132kv S/C TR. Line,400kv D/C Tr. Line(2Nos)


AP-5 AP-5 SPL+50 26°45'14"LT 229 260 236 496 219 140 359 258 146 404

243 132kv DC Tr Line,400kv DC Tr Line


AP-6 AP-6 DD+25 78°15'18"RT 243 236 239 475 103 425 528 96 539 635

235 Metal Road,Boundary Wall,Building


Ex. Angle-
40°23'03"LT
Pro. Angle-
Existing Tower-5 Existing Tower-5 DD+0 12°24'02"LT 235 239 0.00 239 -189 0.00 -189 -303 0.00 -303
Annexure - XVI
400kv DC NTPC Vind V to NTPC Singrauli-III Transmission Line (Option-2)

NTPC LTD
Tree Schedule
Angle Point
Sr.No No. / Sections Type of Tree Nos.
HEIGHT (m) / Girth in( M)

0 AP-1-AP-2 EUCALIPOTASH 7.2 1 0.5


1 EUCALIPOTASH 7.2 1 0.5
2 EUCALIPOTASH 7.2 1 0.5
3 EUCALIPOTASH 7.2 1 0.5
4 EUCALIPOTASH 7.2 1 0.5
5 EUCALIPOTASH 7.2 1 0.5
6 EUCALIPOTASH 7.2 1 0.5
7 EUCALIPOTASH 7.2 1 0.5
8 EUCALIPOTASH 7.2 1 0.5
9 EUCALIPOTASH 7.2 1 0.5
10 JUNGLEE TREE 8.1 1 0.6
11 JUNGLEE TREE 8.1 1 0.6
12 JUNGLEE TREE 8.1 1 0.6
13 JUNGLEE TREE 8.1 1 0.6
14 JUNGLEE TREE 8.1 1 0.6
15 JUNGLEE TREE 8.1 1 0.6
16 EUCALIPOTASH 7.5 1 0.6
17 EUCALIPOTASH 7.5 1 0.6
18 EUCALIPOTASH 7.5 1 0.6
19 JUNGLEE TREE 8.5 1 0.6
20 JUNGLEE TREE 8.5 1 0.6
21 JUNGLEE TREE 8.5 1 0.6
22 JUNGLEE TREE 8.5 1 0.6
23 JUNGLEE TREE 8.5 1 0.6
24 JUNGLEE TREE 8.5 1 0.6
25 JUNGLEE TREE 8.5 1 0.6
26 JUNGLEE TREE 8.5 1 0.6
27 JUNGLEE TREE 8.5 1 0.6
28 JUNGLEE TREE 8.5 1 0.6
29 JUNGLEE TREE 8.5 1 0.6
30 JUNGLEE TREE 8.5 1 0.6
31 JUNGLEE TREE 8.5 1 0.6
32 JUNGLEE TREE 8.5 1 0.6
33 JUNGLEE TREE 8.5 1 0.6
34 JUNGLEE TREE 8.5 1 0.6
35 JUNGLEE TREE 8.5 1 0.6
36 JUNGLEE TREE 8.5 1 0.6
37 JUNGLEE TREE 8.5 1 0.6
38 EUCALIPOTASH 8.8 1 0.6
39 EUCALIPOTASH 8.7 1 0.6
40 EUCALIPOTASH 8.1 1 0.6
41 EUCALIPOTASH 7.2 1 0.5
42 EUCALIPOTASH 7.4 1 0.5
43 AP-2-AP-3 EUCALIPOTASH 7.6 1 0.5
44 EUCALIPOTASH 7.4 1 0.5
45 EUCALIPOTASH 7.4 1 0.5
46 EUCALIPOTASH 7.4 1 0.5
47 EUCALIPOTASH 7.4 1 0.5
48 EUCALIPOTASH 7.4 1 0.5
49 EUCALIPOTASH 7.4 1 0.5
50 EUCALIPOTASH 7.4 1 0.5
51 EUCALIPOTASH 8.1 1 0.6
52 EUCALIPOTASH 8.1 1 0.6
53 EUCALIPOTASH 8.1 1 0.6
54 EUCALIPOTASH 8.1 1 0.6
55 JUNGLEE TREE 8.5 1 0.6
56 JUNGLEE TREE 8.1 1 0.6
57 JUNGLEE TREE 8.1 1 0.6
58 JUNGLEE TREE 8.1 1 0.6
59 JUNGLEE TREE 8.1 1 0.6
60 JUNGLEE TREE 8.1 1 0.6
61 JUNGLEE TREE 8.1 1 0.6
62 JUNGLEE TREE 8.1 1 0.6
63 JUNGLEE TREE 8.1 1 0.6
64 JUNGLEE TREE 8.5 1 0.6
65 JUNGLEE TREE 8.5 1 0.6
66 JUNGLEE TREE 8.5 1 0.6
67 JUNGLEE TREE 8.5 1 0.6
68 JUNGLEE TREE 8.5 1 0.6
69 EUCALIPOTASH 8.5 1 0.6
70 EUCALIPOTASH 8.5 1 0.6
71 EUCALIPOTASH 8.5 1 0.6
72 EUCALIPOTASH 8.5 1 0.6
73 EUCALIPOTASH 8.5 1 0.6
74 EUCALIPOTASH 8.5 1 0.6
75 EUCALIPOTASH 8.5 1 0.6
76 EUCALIPOTASH 8.5 1 0.6
77 EUCALIPOTASH 8.5 1 0.6
78 AP3-AP-4 EUCALIPOTASH 8.5 1 0.6
79 EUCALIPOTASH 8.5 1 0.6
80 EUCALIPOTASH 8.5 1 0.6
81 EUCALIPOTASH 8.5 1 0.6
82 EUCALIPOTASH 8.5 1 0.6
83 EUCALIPOTASH 8.5 1 0.6
84 EUCALIPOTASH 8.5 1 0.6
85 EUCALIPOTASH 8.5 1 0.6
86 EUCALIPOTASH 8.5 1 0.6
87 EUCALIPOTASH 8.5 1 0.6
88 EUCALIPOTASH 8.5 1 0.6
89 EUCALIPOTASH 8.5 1 0.6
90 EUCALIPOTASH 8.5 1 0.6
91 EUCALIPOTASH 8.5 1 0.6
92 EUCALIPOTASH 8.5 1 0.6
93 EUCALIPOTASH 8.5 1 0.6
94 EUCALIPOTASH 8.5 1 0.6
95 JUNGLEE TREE 8.9 1 0.6
96 JUNGLEE TREE 8.9 1 0.6
97 JUNGLEE TREE 8.9 1 0.6
98 JUNGLEE TREE 8.9 1 0.6
99 JUNGLEE TREE 8.9 1 0.6
100 JUNGLEE TREE 8.9 1 0.6
101 JUNGLEE TREE 8.9 1 0.6
102 JUNGLEE TREE 8.9 1 0.6
103 JUNGLEE TREE 8.9 1 0.6
104 JUNGLEE TREE 8.9 1 0.6
105 JUNGLEE TREE 8.9 1 0.6
106 JUNGLEE TREE 8.9 1 0.6
107 JUNGLEE TREE 8.9 1 0.6
108 JUNGLEE TREE 8.9 1 0.6
109 JUNGLEE TREE 8.9 1 0.6
110 AP-4-AP-5 JUNGLEE TREE 8.9 1 0.6
111 EUCALIPOTASH 8.5 1 0.6
112 EUCALIPOTASH 8.5 1 0.6
113 EUCALIPOTASH 8.5 1 0.6
114 EUCALIPOTASH 8.5 1 0.6
115 EUCALIPOTASH 8.5 1 0.6
116 EUCALIPOTASH 8.5 1 0.6
117 EUCALIPOTASH 8.5 1 0.6
118 EUCALIPOTASH 8.5 1 0.6
119 EUCALIPOTASH 8.5 1 0.6
120 EUCALIPOTASH 8.5 1 0.6
121 EUCALIPOTASH 8.5 1 0.6
122 EUCALIPOTASH 8.5 1 0.6
123 EUCALIPOTASH 8.5 1 0.6
124 EUCALIPOTASH 8.5 1 0.6
125 EUCALIPOTASH 8.5 1 0.6
126 EUCALIPOTASH 8.5 1 0.6
127 EUCALIPOTASH 8.5 1 0.6
128 EUCALIPOTASH 8.5 1 0.6
129 EUCALIPOTASH 8.5 1 0.6
130 EUCALIPOTASH 8.5 1 0.6
131 EUCALIPOTASH 8.1 1 0.6
132 EUCALIPOTASH 8.1 1 0.6
133 EUCALIPOTASH 8.1 1 0.6
134 EUCALIPOTASH 8.1 1 0.6
135 EUCALIPOTASH 8.1 1 0.6
136 EUCALIPOTASH 8.1 1 0.6
137 EUCALIPOTASH 8.1 1 0.6
138 EUCALIPOTASH 8.1 1 0.6
139 EUCALIPOTASH 8.1 1 0.6
140 EUCALIPOTASH 8.1 1 0.6
141 EUCALIPOTASH 8.1 1 0.6
142 EUCALIPOTASH 8.1 1 0.6
143 EUCALIPOTASH 8.1 1 0.6
144 EUCALIPOTASH 8.1 1 0.6
145 EUCALIPOTASH 8.1 1 0.6
146 EUCALIPOTASH 8.1 1 0.6
147 EUCALIPOTASH 8.1 1 0.6
148 EUCALIPOTASH 8.1 1 0.6
149 EUCALIPOTASH 8.1 1 0.6
150 EUCALIPOTASH 8.1 1 0.6
151 EUCALIPOTASH 8.1 1 0.6
152 EUCALIPOTASH 8.1 1 0.6
153 EUCALIPOTASH 8.1 1 0.6
154 EUCALIPOTASH 8.1 1 0.6
155 EUCALIPOTASH 8.3 1 0.6
156 EUCALIPOTASH 8.3 1 0.6
157 EUCALIPOTASH 8.3 1 0.6
158 EUCALIPOTASH 8.3 1 0.6
159 AP-5-AP-6 EUCALIPOTASH 8.3 1 0.6
160 EUCALIPOTASH 8.3 1 0.6
161 EUCALIPOTASH 8.3 1 0.6
162 EUCALIPOTASH 8.3 1 0.6
163 JUNGLEE TREE 8.7 1 0.6
164 JUNGLEE TREE 8.7 1 0.6
165 JUNGLEE TREE 8.7 1 0.6
166 JUNGLEE TREE 8.7 1 0.6
167 JUNGLEE TREE 8.7 1 0.6
168 JUNGLEE TREE 8.7 1 0.6
169 JUNGLEE TREE 8.7 1 0.6
170 JUNGLEE TREE 8.7 1 0.6
171 JUNGLEE TREE 8.7 1 0.6
172 JUNGLEE TREE 8.7 1 0.6
173 JUNGLEE TREE 8.7 1 0.6
174 JUNGLEE TREE 8.7 1 0.6
175 JUNGLEE TREE 8.7 1 0.6
176 JUNGLEE TREE 8.7 1 0.6
177 JUNGLEE TREE 8.7 1 0.6
178 JUNGLEE TREE 8.7 1 0.6
179 JUNGLEE TREE 8.7 1 0.6
180 JUNGLEE TREE 8.7 1 0.6
181 JUNGLEE TREE 8.7 1 0.6
182 JUNGLEE TREE 8.7 1 0.6
183 JUNGLEE TREE 8.7 1 0.6
184 JUNGLEE TREE 8.7 1 0.6
185 JUNGLEE TREE 8.7 1 0.6
186 JUNGLEE TREE 8.7 1 0.6
187 JUNGLEE TREE 8.7 1 0.6
188 JUNGLEE TREE 8.7 1 0.6
189 JUNGLEE TREE 8.7 1 0.6
190 JUNGLEE TREE 8.7 1 0.6
191 JUNGLEE TREE 8.7 1 0.6
192 JUNGLEE TREE 8.7 1 0.6
193 JUNGLEE TREE 8.7 1 0.6
194 JUNGLEE TREE 8.7 1 0.6
195 JUNGLEE TREE 8.7 1 0.6
196 JUNGLEE TREE 8.7 1 0.6
197 JUNGLEE TREE 8.7 1 0.6
198 JUNGLEE TREE 8.7 1 0.6
199 JUNGLEE TREE 8.7 1 0.6
200 JUNGLEE TREE 8.7 1 0.6
201 JUNGLEE TREE 8.7 1 0.6
202 JUNGLEE TREE 8.7 1 0.6
203 JUNGLEE TREE 8.7 1 0.6
204 JUNGLEE TREE 8.7 1 0.6
205 JUNGLEE TREE 8.7 1 0.6
206 JUNGLEE TREE 8.7 1 0.6
207 JUNGLEE TREE 8.7 1 0.6
208 JUNGLEE TREE 8.7 1 0.6
209 JUNGLEE TREE 8.7 1 0.6
210 JUNGLEE TREE 8.7 1 0.6
211 JUNGLEE TREE 8.7 1 0.6
212 JUNGLEE TREE 8.7 1 0.6
213 JUNGLEE TREE 8.7 1 0.6
214 JUNGLEE TREE 8.7 1 0.6
215 JUNGLEE TREE 8.7 1 0.6
216 JUNGLEE TREE 8.7 1 0.6
217 JUNGLEE TREE 8.7 1 0.6
218 JUNGLEE TREE 8.7 1 0.6
219 JUNGLEE TREE 8.1 1 0.6
220 AP-6-EX.TOWER JUNGLEE TREE 8.1 1 0.6
221 JUNGLEE TREE 8.1 1 0.6
222 JUNGLEE TREE 8.1 1 0.6
223 JUNGLEE TREE 8.1 1 0.6
224 JUNGLEE TREE 8.1 1 0.6
225 JUNGLEE TREE 8.1 1 0.6
226 JUNGLEE TREE 8.1 1 0.6
227 JUNGLEE TREE 8.1 1 0.6
228 JUNGLEE TREE 8.1 1 0.6
229 JUNGLEE TREE 8.1 1 0.6
230 JUNGLEE TREE 8.1 1 0.6
231 JUNGLEE TREE 8.1 1 0.6
232 JUNGLEE TREE 8.1 1 0.6
233 JUNGLEE TREE 8.1 1 0.6
234 JUNGLEE TREE 8.1 1 0.6
235 JUNGLEE TREE 8.1 1 0.6
236 JUNGLEE TREE 8.1 1 0.6
237 JUNGLEE TREE 8.1 1 0.6
238 JUNGLEE TREE 8.1 1 0.6
239 EUCALIPOTASH 8.1 1 0.6
240 EUCALIPOTASH 8.1 1 0.6
241 EUCALIPOTASH 8.1 1 0.6
242 EUCALIPOTASH 8.1 1 0.6
243 EUCALIPOTASH 8.1 1 0.6
EUCALIPOTASH 8.1 1 0.6
244
245 EUCALIPOTASH 8.1 1 0.6
DOC. NO.:
400kV DC NTPC VIND V to NTPC SINGRAULI-III (Option-2)
INITIAL STRINGING CHART FOR CONDUCTOR (Wind Zone – IV)
Sheet No.: 1 of 6

SECTION FROM : AP1 SECTION TO : AP2 EQUIVALENT SPAN : 294.0

LIMITING CONDITION : 32DEG ° AND NILL WIND

TEMPARATURE : 32.0 DEG.C WIND PRESSURE : 0.0 KG/M2 ICE THICKNESS : 0.00 CM TENSION : 3614.2 KG

------------------------------------------------------------------------------------------------------------------------
| TEMPARATURE | TENSION | 294.0 |
------------------------------------------------------------------------------------------------------------------------
| LOCATION NO. | AP1 AP2
------------------------------------------------------------------------------------------------------------------------
| 0.0(-26.0) | 5601.0 | 3.866 |
| 5.0(-21.0) | 5367.8 | 4.034 |
| 15.0(-11.0) | 4939.1 | 4.384 |
| 20.0( -6.0) | 4743.5 | 4.565 |
| 22.0( -4.0) | 4668.6 | 4.638 |
| 27.0( 1.0) | 4489.8 | 4.823 |
| 30.0( 4.0) | 4388.0 | 4.934 |
| 32.0( 6.0) | 4322.4 | 5.009 |
| 35.0( 9.0) | 4227.3 | 5.122 |
| 38.0( 12.0) | 4135.9 | 5.235 |
| 40.0( 14.0) | 4077.1 | 5.311 |
| 45.0( 19.0) | 3936.8 | 5.500 |
| 48.0( 22.0) | 3857.2 | 5.613 |
| 53.0( 27.0) | 3731.5 | 5.803 |
| 65.0( 39.0) | 3462.7 | 6.253 |
| 75.0( 49.0) | 3269.3 | 6.623 |
| 85.0( 59.0) | 3099.3 | 6.986 |
------------------------------------------------------------------------------------------------------------------------

NOTES : 1. ALL LOADS ARE IN KG AND SAG IN METRES.


2. BRACKETED TEMPARATURES ARE VALUES AFTER CONSIDERING CREEP.
DOC. NO.:
400kV DC NTPC VIND V to NTPC SINGRAULI-III (Option-2)
INITIAL STRINGING CHART FOR CONDUCTOR (Wind Zone – IV)
Sheet No.: 2 of 6

SECTION FROM : AP2 SECTION TO : AP3 EQUIVALENT SPAN : 317.0

LIMITING CONDITION : 32DEG ° AND NILL WIND

TEMPARATURE : 32.0 DEG.C WIND PRESSURE : 0.0 KG/M2 ICE THICKNESS : 0.00 CM TENSION : 3614.2 KG

------------------------------------------------------------------------------------------------------------------------
| TEMPARATURE | TENSION | 317.0 |
------------------------------------------------------------------------------------------------------------------------
| LOCATION NO. | AP2 AP3
------------------------------------------------------------------------------------------------------------------------
| 0.0(-26.0) | 5363.6 | 4.693 |
| 5.0(-21.0) | 5157.9 | 4.880 |
| 15.0(-11.0) | 4781.6 | 5.264 |
| 20.0( -6.0) | 4610.3 | 5.460 |
| 22.0( -4.0) | 4544.7 | 5.539 |
| 27.0( 1.0) | 4388.0 | 5.737 |
| 30.0( 4.0) | 4298.8 | 5.856 |
| 32.0( 6.0) | 4241.2 | 5.935 |
| 35.0( 9.0) | 4157.5 | 6.055 |
| 38.0( 12.0) | 4077.1 | 6.174 |
| 40.0( 14.0) | 4025.2 | 6.254 |
| 45.0( 19.0) | 3901.3 | 6.452 |
| 48.0( 22.0) | 3830.7 | 6.571 |
| 53.0( 27.0) | 3719.0 | 6.769 |
| 65.0( 39.0) | 3478.1 | 7.237 |
| 75.0( 49.0) | 3303.0 | 7.621 |
| 85.0( 59.0) | 3147.5 | 7.998 |
------------------------------------------------------------------------------------------------------------------------

NOTES : 1. ALL LOADS ARE IN KG AND SAG IN METRES.


2. BRACKETED TEMPARATURES ARE VALUES AFTER CONSIDERING CREEP.
DOC. NO.:
400kV DC NTPC VIND V to NTPC SINGRAULI-III (Option-2)
INITIAL STRINGING CHART FOR CONDUCTOR (Wind Zone – IV)
Sheet No.: 3 of 6

SECTION FROM : AP3 SECTION TO : AP4 EQUIVALENT SPAN : 291.0

LIMITING CONDITION : 32DEG ° AND NILL WIND

TEMPARATURE : 32.0 DEG.C WIND PRESSURE : 0.0 KG/M2 ICE THICKNESS : 0.00 CM TENSION : 3614.2 KG

------------------------------------------------------------------------------------------------------------------------
| TEMPARATURE | TENSION | 291.0 |
------------------------------------------------------------------------------------------------------------------------
| LOCATION NO. | AP3 AP4
------------------------------------------------------------------------------------------------------------------------
| 0.0(-26.0) | 5634.0 | 3.765 |
| 5.0(-21.0) | 5397.0 | 3.930 |
| 15.0(-11.0) | 4961.2 | 4.276 |
| 20.0( -6.0) | 4762.2 | 4.454 |
| 22.0( -4.0) | 4686.1 | 4.527 |
| 27.0( 1.0) | 4504.2 | 4.710 |
| 30.0( 4.0) | 4400.7 | 4.820 |
| 32.0( 6.0) | 4333.9 | 4.895 |
| 35.0( 9.0) | 4237.1 | 5.006 |
| 38.0( 12.0) | 4144.2 | 5.119 |
| 40.0( 14.0) | 4084.4 | 5.194 |
| 45.0( 19.0) | 3941.8 | 5.381 |
| 48.0( 22.0) | 3860.9 | 5.494 |
| 53.0( 27.0) | 3733.3 | 5.682 |
| 65.0( 39.0) | 3460.5 | 6.130 |
| 75.0( 49.0) | 3264.5 | 6.498 |
| 85.0( 59.0) | 3092.5 | 6.859 |
------------------------------------------------------------------------------------------------------------------------

NOTES : 1. ALL LOADS ARE IN KG AND SAG IN METRES.


2. BRACKETED TEMPARATURES ARE VALUES AFTER CONSIDERING CREEP.
DOC. NO.:
400kV DC NTPC VIND V to NTPC SINGRAULI-III (Option-2)
INITIAL STRINGING CHART FOR CONDUCTOR (Wind Zone – IV)
Sheet No.: 4 of 6

SECTION FROM : AP4 SECTION TO : AP5 EQUIVALENT SPAN : 229.0

LIMITING CONDITION : 32DEG ° AND NILL WIND

TEMPARATURE : 32.0 DEG.C WIND PRESSURE : 0.0 KG/M2 ICE THICKNESS : 0.00 CM TENSION : 3614.2 KG

------------------------------------------------------------------------------------------------------------------------
| TEMPARATURE | TENSION | 229.0 |
------------------------------------------------------------------------------------------------------------------------
| LOCATION NO. | AP4 AP5
------------------------------------------------------------------------------------------------------------------------
| 0.0(-26.0) | 6394.9 | 2.054 |
| 5.0(-21.0) | 6084.0 | 2.159 |
| 15.0(-11.0) | 5497.4 | 2.390 |
| 20.0( -6.0) | 5223.4 | 2.515 |
| 22.0( -4.0) | 5117.7 | 2.567 |
| 27.0( 1.0) | 4863.4 | 2.701 |
| 30.0( 4.0) | 4717.9 | 2.784 |
| 32.0( 6.0) | 4623.8 | 2.841 |
| 35.0( 9.0) | 4487.2 | 2.928 |
| 38.0( 12.0) | 4356.0 | 3.016 |
| 40.0( 14.0) | 4271.5 | 3.075 |
| 45.0( 19.0) | 4070.6 | 3.227 |
| 48.0( 22.0) | 3957.0 | 3.320 |
| 53.0( 27.0) | 3778.9 | 3.476 |
| 65.0( 39.0) | 3404.7 | 3.858 |
| 75.0( 49.0) | 3143.8 | 4.179 |
| 85.0( 59.0) | 2921.7 | 4.496 |
------------------------------------------------------------------------------------------------------------------------

NOTES : 1. ALL LOADS ARE IN KG AND SAG IN METRES.


2. BRACKETED TEMPARATURES ARE VALUES AFTER CONSIDERING CREEP.
DOC. NO.:
400kV DC NTPC VIND V to NTPC SINGRAULI-III (Option-2)
INITIAL STRINGING CHART FOR CONDUCTOR (Wind Zone – IV)
Sheet No.: 5 of 6

SECTION FROM : AP5 SECTION TO : AP6 EQUIVALENT SPAN : 243.0

LIMITING CONDITION : 32DEG ° AND NILL WIND

TEMPARATURE : 32.0 DEG.C WIND PRESSURE : 0.0 KG/M2 ICE THICKNESS : 0.00 CM TENSION : 3614.2 KG

------------------------------------------------------------------------------------------------------------------------
| TEMPARATURE | TENSION | 243.0 |
------------------------------------------------------------------------------------------------------------------------
| LOCATION NO. | AP5 AP6
------------------------------------------------------------------------------------------------------------------------
| 0.0(-26.0) | 6213.1 | 2.381 |
| 5.0(-21.0) | 5917.9 | 2.500 |
| 15.0(-11.0) | 5364.4 | 2.757 |
| 20.0( -6.0) | 5107.8 | 2.896 |
| 22.0( -4.0) | 5009.0 | 2.953 |
| 27.0( 1.0) | 4772.1 | 3.100 |
| 30.0( 4.0) | 4636.8 | 3.190 |
| 32.0( 6.0) | 4549.5 | 3.251 |
| 35.0( 9.0) | 4422.8 | 3.344 |
| 38.0( 12.0) | 4301.3 | 3.439 |
| 40.0( 14.0) | 4223.0 | 3.503 |
| 45.0( 19.0) | 4037.1 | 3.664 |
| 48.0( 22.0) | 3931.9 | 3.762 |
| 53.0( 27.0) | 3766.9 | 3.927 |
| 65.0( 39.0) | 3419.3 | 4.326 |
| 75.0( 49.0) | 3175.3 | 4.658 |
| 85.0( 59.0) | 2966.0 | 4.987 |
------------------------------------------------------------------------------------------------------------------------

NOTES : 1. ALL LOADS ARE IN KG AND SAG IN METRES.


2. BRACKETED TEMPARATURES ARE VALUES AFTER CONSIDERING CREEP.
DOC. NO.:
400kV DC NTPC VIND V to NTPC SINGRAULI-III (Option-2)
INITIAL STRINGING CHART FOR CONDUCTOR (Wind Zone – IV)
Sheet No.: 6 of 6

SECTION FROM : AP6 SECTION TO : Existing T EQUIVALENT SPAN : 235.0

LIMITING CONDITION : 32DEG ° AND NILL WIND

TEMPARATURE : 32.0 DEG.C WIND PRESSURE : 0.0 KG/M2 ICE THICKNESS : 0.00 CM TENSION : 3614.2 KG

------------------------------------------------------------------------------------------------------------------------
| TEMPARATURE | TENSION | 235.0 |
------------------------------------------------------------------------------------------------------------------------
| LOCATION NO. | AP6 Existin
------------------------------------------------------------------------------------------------------------------------
| 0.0(-26.0) | 6316.6 | 2.190 |
| 5.0(-21.0) | 6012.3 | 2.301 |
| 15.0(-11.0) | 5439.7 | 2.543 |
| 20.0( -6.0) | 5173.1 | 2.674 |
| 22.0( -4.0) | 5070.4 | 2.728 |
| 27.0( 1.0) | 4823.6 | 2.868 |
| 30.0( 4.0) | 4682.5 | 2.954 |
| 32.0( 6.0) | 4591.4 | 3.013 |
| 35.0( 9.0) | 4459.1 | 3.102 |
| 38.0( 12.0) | 4332.0 | 3.193 |
| 40.0( 14.0) | 4250.3 | 3.255 |
| 45.0( 19.0) | 4055.9 | 3.411 |
| 48.0( 22.0) | 3946.0 | 3.506 |
| 53.0( 27.0) | 3773.6 | 3.666 |
| 65.0( 39.0) | 3411.1 | 4.056 |
| 75.0( 49.0) | 3157.6 | 4.381 |
| 85.0( 59.0) | 2941.1 | 4.704 |
------------------------------------------------------------------------------------------------------------------------

NOTES : 1. ALL LOADS ARE IN KG AND SAG IN METRES.


2. BRACKETED TEMPARATURES ARE VALUES AFTER CONSIDERING CREEP.
DOC. NO.:
400kV DC NTPC VIND V to NTPC SINGRAULI-III (Option-2)
FINAL STRINGING CHART FOR CONDUCTOR (Wind Zone – IV)
Sheet No.: 1 of 6

SECTION FROM : AP1 SECTION TO : AP2 EQUIVALENT SPAN : 294.0

LIMITING CONDITION : 32DEG ° AND NILL WIND

TEMPARATURE : 32.0 DEG.C WIND PRESSURE : 0.0 KG/M2 ICE THICKNESS : 0.00 CM TENSION : 3614.2 KG

------------------------------------------------------------------------------------------------------------------------
| TEMPARATURE | TENSION | 294.0 |
------------------------------------------------------------------------------------------------------------------------
| LOCATION NO. | AP1 AP2
------------------------------------------------------------------------------------------------------------------------
| 0.0 | 4524.6 | 4.785 |
| 5.0 | 4355.0 | 4.972 |
| 15.0 | 4048.2 | 5.349 |
| 20.0 | 3909.9 | 5.538 |
| 22.0 | 3857.2 | 5.613 |
| 27.0 | 3731.5 | 5.803 |
| 30.0 | 3660.1 | 5.916 |
| 32.0 | 3614.2 | 5.991 |
| 35.0 | 3547.5 | 6.104 |
| 38.0 | 3483.4 | 6.216 |
| 40.0 | 3442.1 | 6.290 |
| 45.0 | 3343.6 | 6.476 |
| 48.0 | 3287.5 | 6.586 |
| 53.0 | 3198.7 | 6.769 |
| 65.0 | 3007.0 | 7.201 |
| 75.0 | 2867.3 | 7.552 |
| 85.0 | 2742.7 | 7.894 |
------------------------------------------------------------------------------------------------------------------------

NOTES : 1. ALL LOADS ARE IN KG AND SAG IN METRES.


DOC. NO.:
400kV DC NTPC VIND V to NTPC SINGRAULI-III (Option-2)
FINAL STRINGING CHART FOR CONDUCTOR (Wind Zone – IV)
Sheet No.: 2 of 6

SECTION FROM : AP2 SECTION TO : AP3 EQUIVALENT SPAN : 317.0

LIMITING CONDITION : 32DEG ° AND NILL WIND

TEMPARATURE : 32.0 DEG.C WIND PRESSURE : 0.0 KG/M2 ICE THICKNESS : 0.00 CM TENSION : 3614.2 KG

------------------------------------------------------------------------------------------------------------------------
| TEMPARATURE | TENSION | 317.0 |
------------------------------------------------------------------------------------------------------------------------
| LOCATION NO. | AP2 AP3
------------------------------------------------------------------------------------------------------------------------
| 0.0 | 4418.6 | 5.697 |
| 5.0 | 4269.8 | 5.896 |
| 15.0 | 3999.8 | 6.293 |
| 20.0 | 3877.5 | 6.492 |
| 22.0 | 3830.7 | 6.571 |
| 27.0 | 3719.0 | 6.769 |
| 30.0 | 3655.3 | 6.887 |
| 32.0 | 3614.2 | 6.965 |
| 35.0 | 3554.4 | 7.082 |
| 38.0 | 3496.8 | 7.199 |
| 40.0 | 3459.6 | 7.276 |
| 45.0 | 3370.5 | 7.469 |
| 48.0 | 3319.5 | 7.583 |
| 53.0 | 3238.6 | 7.773 |
| 65.0 | 3062.5 | 8.220 |
| 75.0 | 2932.8 | 8.583 |
| 85.0 | 2816.2 | 8.938 |
------------------------------------------------------------------------------------------------------------------------

NOTES : 1. ALL LOADS ARE IN KG AND SAG IN METRES.


DOC. NO.:
400kV DC NTPC VIND V to NTPC SINGRAULI-III (Option-2)
FINAL STRINGING CHART FOR CONDUCTOR (Wind Zone – IV)
Sheet No.: 3 of 6

SECTION FROM : AP3 SECTION TO : AP4 EQUIVALENT SPAN : 291.0

LIMITING CONDITION : 32DEG ° AND NILL WIND

TEMPARATURE : 32.0 DEG.C WIND PRESSURE : 0.0 KG/M2 ICE THICKNESS : 0.00 CM TENSION : 3614.2 KG

------------------------------------------------------------------------------------------------------------------------
| TEMPARATURE | TENSION | 291.0 |
------------------------------------------------------------------------------------------------------------------------
| LOCATION NO. | AP3 AP4
------------------------------------------------------------------------------------------------------------------------
| 0.0 | 4539.6 | 4.673 |
| 5.0 | 4367.1 | 4.857 |
| 15.0 | 4055.1 | 5.231 |
| 20.0 | 3914.5 | 5.419 |
| 22.0 | 3860.9 | 5.494 |
| 27.0 | 3733.3 | 5.682 |
| 30.0 | 3660.8 | 5.794 |
| 32.0 | 3614.2 | 5.869 |
| 35.0 | 3546.5 | 5.981 |
| 38.0 | 3481.5 | 6.093 |
| 40.0 | 3439.7 | 6.167 |
| 45.0 | 3339.8 | 6.351 |
| 48.0 | 3283.0 | 6.461 |
| 53.0 | 3193.0 | 6.643 |
| 65.0 | 2999.2 | 7.073 |
| 75.0 | 2858.1 | 7.422 |
| 85.0 | 2732.5 | 7.763 |
------------------------------------------------------------------------------------------------------------------------

NOTES : 1. ALL LOADS ARE IN KG AND SAG IN METRES.


DOC. NO.:
400kV DC NTPC VIND V to NTPC SINGRAULI-III (Option-2)
FINAL STRINGING CHART FOR CONDUCTOR (Wind Zone – IV)
Sheet No.: 4 of 6

SECTION FROM : AP4 SECTION TO : AP5 EQUIVALENT SPAN : 229.0

LIMITING CONDITION : 32DEG ° AND NILL WIND

TEMPARATURE : 32.0 DEG.C WIND PRESSURE : 0.0 KG/M2 ICE THICKNESS : 0.00 CM TENSION : 3614.2 KG

------------------------------------------------------------------------------------------------------------------------
| TEMPARATURE | TENSION | 229.0 |
------------------------------------------------------------------------------------------------------------------------
| LOCATION NO. | AP4 AP5
------------------------------------------------------------------------------------------------------------------------
| 0.0 | 4913.1 | 2.674 |
| 5.0 | 4670.6 | 2.813 |
| 15.0 | 4230.2 | 3.105 |
| 20.0 | 4032.1 | 3.258 |
| 22.0 | 3957.0 | 3.320 |
| 27.0 | 3778.9 | 3.476 |
| 30.0 | 3678.5 | 3.571 |
| 32.0 | 3614.2 | 3.635 |
| 35.0 | 3521.5 | 3.730 |
| 38.0 | 3433.2 | 3.826 |
| 40.0 | 3376.6 | 3.890 |
| 45.0 | 3243.1 | 4.051 |
| 48.0 | 3168.0 | 4.147 |
| 53.0 | 3050.7 | 4.306 |
| 65.0 | 2804.3 | 4.684 |
| 75.0 | 2631.1 | 4.993 |
| 85.0 | 2481.5 | 5.294 |
------------------------------------------------------------------------------------------------------------------------

NOTES : 1. ALL LOADS ARE IN KG AND SAG IN METRES.


DOC. NO.:
400kV DC NTPC VIND V to NTPC SINGRAULI-III (Option-2)
FINAL STRINGING CHART FOR CONDUCTOR (Wind Zone – IV)
Sheet No.: 5 of 6

SECTION FROM : AP5 SECTION TO : AP6 EQUIVALENT SPAN : 243.0

LIMITING CONDITION : 32DEG ° AND NILL WIND

TEMPARATURE : 32.0 DEG.C WIND PRESSURE : 0.0 KG/M2 ICE THICKNESS : 0.00 CM TENSION : 3614.2 KG

------------------------------------------------------------------------------------------------------------------------
| TEMPARATURE | TENSION | 243.0 |
------------------------------------------------------------------------------------------------------------------------
| LOCATION NO. | AP5 AP6
------------------------------------------------------------------------------------------------------------------------
| 0.0 | 4818.3 | 3.070 |
| 5.0 | 4592.9 | 3.221 |
| 15.0 | 4184.8 | 3.535 |
| 20.0 | 4001.5 | 3.697 |
| 22.0 | 3931.9 | 3.762 |
| 27.0 | 3766.9 | 3.927 |
| 30.0 | 3673.9 | 4.026 |
| 32.0 | 3614.2 | 4.093 |
| 35.0 | 3528.0 | 4.193 |
| 38.0 | 3445.8 | 4.293 |
| 40.0 | 3393.1 | 4.359 |
| 45.0 | 3268.3 | 4.526 |
| 48.0 | 3198.0 | 4.625 |
| 53.0 | 3087.7 | 4.791 |
| 65.0 | 2854.7 | 5.182 |
| 75.0 | 2689.4 | 5.500 |
| 85.0 | 2545.5 | 5.811 |
------------------------------------------------------------------------------------------------------------------------

NOTES : 1. ALL LOADS ARE IN KG AND SAG IN METRES.


DOC. NO.:
400kV DC NTPC VIND V to NTPC SINGRAULI-III (Option-2)
FINAL STRINGING CHART FOR CONDUCTOR (Wind Zone – IV)
Sheet No.: 6 of 6

SECTION FROM : AP6 SECTION TO : Existing T EQUIVALENT SPAN : 235.0

LIMITING CONDITION : 32DEG ° AND NILL WIND

TEMPARATURE : 32.0 DEG.C WIND PRESSURE : 0.0 KG/M2 ICE THICKNESS : 0.00 CM TENSION : 3614.2 KG

------------------------------------------------------------------------------------------------------------------------
| TEMPARATURE | TENSION | 235.0 |
------------------------------------------------------------------------------------------------------------------------
| LOCATION NO. | AP6 Existin
------------------------------------------------------------------------------------------------------------------------
| 0.0 | 4871.8 | 2.840 |
| 5.0 | 4636.6 | 2.984 |
| 15.0 | 4210.3 | 3.286 |
| 20.0 | 4018.7 | 3.442 |
| 22.0 | 3946.0 | 3.506 |
| 27.0 | 3773.6 | 3.666 |
| 30.0 | 3676.4 | 3.763 |
| 32.0 | 3614.2 | 3.828 |
| 35.0 | 3524.4 | 3.925 |
| 38.0 | 3438.7 | 4.023 |
| 40.0 | 3383.9 | 4.088 |
| 45.0 | 3254.2 | 4.251 |
| 48.0 | 3181.2 | 4.349 |
| 53.0 | 3066.9 | 4.511 |
| 65.0 | 2826.4 | 4.894 |
| 75.0 | 2656.6 | 5.207 |
| 85.0 | 2509.6 | 5.512 |
------------------------------------------------------------------------------------------------------------------------

NOTES : 1. ALL LOADS ARE IN KG AND SAG IN METRES.


DOC. NO.:
400kV DC NTPC VIND V to NTPC SINGRAULI-III (Option-2)
FINAL STRINGING CHART FOR EARTH WIRE (Wind Zone – IV)
Sheet No.: 1 of 6

SECTION FROM : AP1 SECTION TO : AP2 EQUIVALENT SPAN : 294.0

LIMITING CONDITION : 32DEG ° AND NILL WIND

TEMPARATURE : 32.0 DEG.C WIND PRESSURE : 0.0 KG/M2 ICE THICKNESS : 0.00 CM TENSION : 1212.6 KG

------------------------------------------------------------------------------------------------------------------------
| TEMPARATURE | TENSION | 294.0 |
------------------------------------------------------------------------------------------------------------------------
| LOCATION NO. | AP1 AP2
------------------------------------------------------------------------------------------------------------------------
| 0.0 | 1418.1 | 4.442 |
| 5.0 | 1382.0 | 4.558 |
| 15.0 | 1314.4 | 4.792 |
| 20.0 | 1282.8 | 4.910 |
| 22.0 | 1270.6 | 4.958 |
| 30.0 | 1223.7 | 5.147 |
| 32.0 | 1212.6 | 5.195 |
| 35.0 | 1196.2 | 5.266 |
| 38.0 | 1180.2 | 5.337 |
| 40.0 | 1169.8 | 5.385 |
| 45.0 | 1144.6 | 5.503 |
| 48.0 | 1130.0 | 5.574 |
| 50.0 | 1120.5 | 5.622 |
| 53.0 | 1106.6 | 5.692 |
------------------------------------------------------------------------------------------------------------------------

NOTES : 1. ALL LOADS ARE IN KG AND SAG IN METRES.


DOC. NO.:
400kV DC NTPC VIND V to NTPC SINGRAULI-III (Option-2)
FINAL STRINGING CHART FOR EARTH WIRE (Wind Zone – IV)
Sheet No.: 2 of 6

SECTION FROM : AP2 SECTION TO : AP3 EQUIVALENT SPAN : 317.0

LIMITING CONDITION : 32DEG ° AND NILL WIND

TEMPARATURE : 32.0 DEG.C WIND PRESSURE : 0.0 KG/M2 ICE THICKNESS : 0.00 CM TENSION : 1212.6 KG

------------------------------------------------------------------------------------------------------------------------
| TEMPARATURE | TENSION | 317.0 |
------------------------------------------------------------------------------------------------------------------------
| LOCATION NO. | AP2 AP3
------------------------------------------------------------------------------------------------------------------------
| 0.0 | 1397.0 | 5.242 |
| 5.0 | 1364.7 | 5.366 |
| 15.0 | 1304.2 | 5.615 |
| 20.0 | 1275.8 | 5.740 |
| 22.0 | 1264.8 | 5.790 |
| 30.0 | 1222.7 | 5.990 |
| 32.0 | 1212.6 | 6.039 |
| 35.0 | 1197.7 | 6.114 |
| 38.0 | 1183.3 | 6.189 |
| 40.0 | 1173.9 | 6.238 |
| 45.0 | 1151.0 | 6.362 |
| 48.0 | 1137.7 | 6.437 |
| 50.0 | 1129.1 | 6.486 |
| 53.0 | 1116.3 | 6.560 |
------------------------------------------------------------------------------------------------------------------------

NOTES : 1. ALL LOADS ARE IN KG AND SAG IN METRES.


DOC. NO.:
400kV DC NTPC VIND V to NTPC SINGRAULI-III (Option-2)
FINAL STRINGING CHART FOR EARTH WIRE (Wind Zone – IV)
Sheet No.: 3 of 6

SECTION FROM : AP3 SECTION TO : AP4 EQUIVALENT SPAN : 291.0

LIMITING CONDITION : 32DEG ° AND NILL WIND

TEMPARATURE : 32.0 DEG.C WIND PRESSURE : 0.0 KG/M2 ICE THICKNESS : 0.00 CM TENSION : 1212.6 KG

------------------------------------------------------------------------------------------------------------------------
| TEMPARATURE | TENSION | 291.0 |
------------------------------------------------------------------------------------------------------------------------
| LOCATION NO. | AP3 AP4
------------------------------------------------------------------------------------------------------------------------
| 0.0 | 1421.1 | 4.343 |
| 5.0 | 1384.4 | 4.457 |
| 15.0 | 1315.9 | 4.690 |
| 20.0 | 1283.8 | 4.807 |
| 22.0 | 1271.4 | 4.854 |
| 30.0 | 1223.9 | 5.042 |
| 32.0 | 1212.6 | 5.089 |
| 35.0 | 1195.9 | 5.160 |
| 38.0 | 1179.8 | 5.231 |
| 40.0 | 1169.2 | 5.278 |
| 45.0 | 1143.7 | 5.396 |
| 48.0 | 1128.9 | 5.466 |
| 50.0 | 1119.3 | 5.513 |
| 53.0 | 1105.2 | 5.584 |
------------------------------------------------------------------------------------------------------------------------

NOTES : 1. ALL LOADS ARE IN KG AND SAG IN METRES.


DOC. NO.:
400kV DC NTPC VIND V to NTPC SINGRAULI-III (Option-2)
FINAL STRINGING CHART FOR EARTH WIRE (Wind Zone – IV)
Sheet No.: 4 of 6

SECTION FROM : AP4 SECTION TO : AP5 EQUIVALENT SPAN : 229.0

LIMITING CONDITION : 32DEG ° AND NILL WIND

TEMPARATURE : 32.0 DEG.C WIND PRESSURE : 0.0 KG/M2 ICE THICKNESS : 0.00 CM TENSION : 1212.6 KG

------------------------------------------------------------------------------------------------------------------------
| TEMPARATURE | TENSION | 229.0 |
------------------------------------------------------------------------------------------------------------------------
| LOCATION NO. | AP4 AP5
------------------------------------------------------------------------------------------------------------------------
| 0.0 | 1492.5 | 2.561 |
| 5.0 | 1443.4 | 2.648 |
| 15.0 | 1351.2 | 2.828 |
| 20.0 | 1308.0 | 2.922 |
| 22.0 | 1291.3 | 2.959 |
| 30.0 | 1227.7 | 3.113 |
| 32.0 | 1212.6 | 3.152 |
| 35.0 | 1190.4 | 3.210 |
| 38.0 | 1168.9 | 3.269 |
| 40.0 | 1155.0 | 3.309 |
| 45.0 | 1121.3 | 3.408 |
| 48.0 | 1102.0 | 3.468 |
| 50.0 | 1089.4 | 3.508 |
| 53.0 | 1071.1 | 3.568 |
------------------------------------------------------------------------------------------------------------------------

NOTES : 1. ALL LOADS ARE IN KG AND SAG IN METRES.


DOC. NO.:
400kV DC NTPC VIND V to NTPC SINGRAULI-III (Option-2)
FINAL STRINGING CHART FOR EARTH WIRE (Wind Zone – IV)
Sheet No.: 5 of 6

SECTION FROM : AP5 SECTION TO : AP6 EQUIVALENT SPAN : 243.0

LIMITING CONDITION : 32DEG ° AND NILL WIND

TEMPARATURE : 32.0 DEG.C WIND PRESSURE : 0.0 KG/M2 ICE THICKNESS : 0.00 CM TENSION : 1212.6 KG

------------------------------------------------------------------------------------------------------------------------
| TEMPARATURE | TENSION | 243.0 |
------------------------------------------------------------------------------------------------------------------------
| LOCATION NO. | AP5 AP6
------------------------------------------------------------------------------------------------------------------------
| 0.0 | 1474.6 | 2.918 |
| 5.0 | 1428.6 | 3.012 |
| 15.0 | 1342.2 | 3.206 |
| 20.0 | 1301.9 | 3.305 |
| 22.0 | 1286.3 | 3.346 |
| 30.0 | 1226.7 | 3.508 |
| 32.0 | 1212.6 | 3.549 |
| 35.0 | 1191.8 | 3.611 |
| 38.0 | 1171.7 | 3.673 |
| 40.0 | 1158.6 | 3.714 |
| 45.0 | 1127.1 | 3.818 |
| 48.0 | 1108.9 | 3.881 |
| 50.0 | 1097.1 | 3.922 |
| 53.0 | 1079.8 | 3.985 |
------------------------------------------------------------------------------------------------------------------------

NOTES : 1. ALL LOADS ARE IN KG AND SAG IN METRES.


DOC. NO.:
400kV DC NTPC VIND V to NTPC SINGRAULI-III (Option-2)
FINAL STRINGING CHART FOR EARTH WIRE (Wind Zone – IV)
Sheet No.: 6 of 6

SECTION FROM : AP6 SECTION TO : Existing T EQUIVALENT SPAN : 235.0

LIMITING CONDITION : 32DEG ° AND NILL WIND

TEMPARATURE : 32.0 DEG.C WIND PRESSURE : 0.0 KG/M2 ICE THICKNESS : 0.00 CM TENSION : 1212.6 KG

------------------------------------------------------------------------------------------------------------------------
| TEMPARATURE | TENSION | 235.0 |
------------------------------------------------------------------------------------------------------------------------
| LOCATION NO. | AP6 Existin
------------------------------------------------------------------------------------------------------------------------
| 0.0 | 1484.7 | 2.711 |
| 5.0 | 1436.9 | 2.801 |
| 15.0 | 1347.3 | 2.987 |
| 20.0 | 1305.3 | 3.083 |
| 22.0 | 1289.1 | 3.122 |
| 30.0 | 1227.3 | 3.279 |
| 32.0 | 1212.6 | 3.319 |
| 35.0 | 1191.0 | 3.379 |
| 38.0 | 1170.1 | 3.439 |
| 40.0 | 1156.6 | 3.480 |
| 45.0 | 1123.9 | 3.581 |
| 48.0 | 1105.0 | 3.642 |
| 50.0 | 1092.8 | 3.683 |
| 53.0 | 1074.9 | 3.744 |
------------------------------------------------------------------------------------------------------------------------

NOTES : 1. ALL LOADS ARE IN KG AND SAG IN METRES.