FIRST ANGLE PROJECTION ALL DIMENSIONS ARE IN MM

2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

NOTES:
S.NO HARDWIRED SIGNAL TO SG-DDCMIS 1. ALL DIMENSIONS ARE IN mm ONLY, UNLESS AND OTHERWISE SPECIFIED.
A 2. ALL CABLE ENTRY AND EXIT SHALL BE FROM BOTTOM. A
1 4 to 20 mA dew point signal to SD-DDCMIS 3. ALL TERMINAL ARE IN 2.5 SQ.MM , SCREW TYPE
POLYAMIDE MATERIAL WITH DIN RAIL CONNECTOR
2 Local select feedback 4. MAKE OF ALL ITEM SHALL BE AS PER NTPC QA APPROVED MAKE ONLY
5. DIMENSION AND LAYOUT SHOWN IN TENTATIVE ONLY( OVERALL DIMENSION
3 Common alarm feedback WILL NOT VARY)
6. CONTROL PANEL DEGREE PROTECTION AS PER IP 65

DPS-101

DPS-102

DPT-101
LS-101A

LS-101B

LS-102A

LS-102B

LS-103A

LS-103B
4 Remote select feedback 7. IR & HIGH VOLTAGE TEST AS PER QAP.

PB-101

PB-102

ES-101
G1 G2 G5 8.1 INCH COPPER FLAT IS MOUNTED IN PANEL FOR EARTHING PURPOSES.
5 Dyer ON/OFF feedback 9. PANEL COLOUR WILL BE RAL 9002 FOR FRONT AND BACK & RAL 5012
B FOR SIDES SURFACE FINISH RAL 7035, 50 MICRON B
6 Remote mode dryer Start/stop, 24V DC POWDER COATED MINIMUM, 100 MICRON PAINTED.

5 6 7 8 9 10 11 12 13 14 15 16 17 18 3 4 19

C 0V 24V 1X0 1X1 1X2 1X3 1X4 1X5 1X6 1X7 COM 2X0 2X1 2X2 2X3 2X4 2X5 2X6 X27 COM 0V 24V V1+ IN1- I1- COM1 IN2+ IN2- COM2 C

SDMC 14 SDMC 15
Fold-7 Fold-7

D D

R485 COMMINCATION
PORT TO SG-DDCMIS

IO1 GND IN4+ IN4- COM4 IN3+ IN3- COM3


1Y0 1Y1 1Y2 1Y3 1Y4 1Y5 1Y6 1Y7 2Y0 2Y1 2Y2 2Y3 2Y4 2Y5 2Y6 2Y7

20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 64 65 47 48 49 50 51
E E
4 to 20 mA
dew point signal
TE-101 TE-102
to SD-DDCMIS
HMI
it must not be used directly or indirectly in any way deterimental to the interest of the company.
The information on this document is the property of BHARAT HEAVY ELECTRICALS LIMITED

RELAY BANK 0V 24V


1
COPY RIGHT AND CONFIDENTIAL

F 36 37 38 39 40 41 42 43 44 F

1
4 to 20 mA
SS-101 Local select Common alarm Remote select Dyer ON/OFF Remote mode dryer
IL-111 feedback feedback feedback feedback Start/stop, 24V DC dew point signal
to SD-DDCMIS
45 46
2 1 G2 G3 G1 G4 G5
3 4
G
0 52 53 54 55 56 57 58 59 60 61 62 63
G

SMPS ( HARDWIRED SIGNAL TO SG-DDCMIS)


GLAND PLATE DETAILS
AL-101

1 2
IL-101

IL-102

IL-103

IL-104

IL-106

IL-107

IL-108

IL-109

IL-110
IL-105

SUMMITS
pure air & more
HOC AIR DRYER
CONTROL PANNEL

PANEL TAG NO : **********


DRAIN-101

DRAIN-102

DRAIN-103

DRAIN-104

SUMMITS HYGRONICS PVT. LTD.,


S.F .No . 192, Eari Th ottam , Kan na m p alayam , Co im b atore - 641 402.
Pho ne : +91 422 2689020, Fax : + 91 422 2682024
E-m ail : in fo@ aird ryer.in , W : w ww .airdryer.in

H
SS-102 H

Fold-6 V1 V2 V3 G3 G4 G1 G2 Fold-6
HMI
N L

230V AC 50 Hz Supply, 500 W


CONTROL SUPPLY REMOTE/LOCAL
Non-UPS Supply ON/OFF SS-102 PB-101 PB-102 SS-101

I IL-101 IL-102 IL-103 IL-104 IL-105 IL-106 I


Hinges
IL-107 IL-108 IL-109 IL-110 IL-111 ES-101

Digitally signed
Signature Not
by RVerified

J
Handa
LEFT SIDE VIEW
Date: 2015.07.30
09:57:20 IST
FRONT VIEW J
Reason: CAT I
Location:
SI.NO TAG NO DESCRIPTION MAKE SI.NO TAG NO DESCRIPTION MAKE SI.NO TAG NO DESCRIPTION MAKE NTPCEOC

1 SMPS SWITCH MODE POWER SUPPLY DELTA/OMRON 15 LS-102A/B LIMIT SWITCH FOR MAIN VALVE 2 ROTEX 29 IL-101 MAIN VALVE 1 ON/OFF INDICATION (230 VAC) SIEMENS
2 SS-101 REMOTE/LOCAL ON/OFF SELECTOR SWITCH SALZER 16 LS-103A/B LIMIT SWITCH FOR MAIN VALVE 3 ROTEX 30 IL-102 MAIN VALVE 2 ON/OFF INDICATION (230 VAC) SIEMENS
3 SS-102 CONTROL SUPPLY ON/OFF SELECTOR SWITCH SALZER 17 DPS-101 PRE FILTER DIFF. PRESSURE SWITCH BAUMER/HIRLEKAR 31 IL-103 MAIN VALVE 3 ON/OFF INDICATION (230 VAC) SIEMENS
4 V1 5/2 SOLENOID COIL FOR MAIN VALVE 1(230 VAC) JANATICS/ROTEX 18 DPS-102 AFTER FILTER DIFF. PRESSURE SWITCH BAUMER/HIRLEKAR 32 IL-104 DRAIN VALVE 1 ON/OFF INDICATION (230 VAC) SIEMENS
5 V2 5/2 SOLENOID COIL FOR MAIN VALVE 2(230 VAC) JANATICS/ROTEX 19 TE-101 DRYER INLET TEMPERATURE ELEMENT BAUMER 33 IL-105 DRAIN VALVE 2 ON/OFF INDICATION (230 VAC) SIEMENS
K
6 V3 5/2 SOLENOID COIL FOR MAIN VALVE 3(230 VAC) JANATICS/ROTEX 20 TE-102 DRYER OUTLET TEMPERATURE ELEMENT BAUMER 34 IL-106 DRAIN VALVE 3 ON/OFF INDICATION (230 VAC) SIEMENS
7 DRAIN-101 MOISTURE SEPERATOR DRAIN VALVE (230 VAC) SUMMITS 21 AL-101 DRYER TRIP ALARM (230 VAC) SIEMENS 35 IL-107 DRAIN VALVE 3 ON/OFF INDICATION (230 VAC) SIEMENS
8 DRAIN-102 PRE FILTER DRAIN VALVE (230 VAC) SUMMITS 22 DPT-101 DRYER OUTLET DEW POINT TRANSMITTER XENTAUR 36 IL-108 DRYER ON/OFF INDICATION (230 VAC) SIEMENS
9 DRAIN-103 AFTER FILTER DRAIN VALVE (230 VAC) SUMMITS 23 G1 REMOTE MODE ON/OFF CONTACTOR (230 VAC) SALZER/SIEMENS 37 IL-109 REMOTE MODE ON/OFF INDICATION (230 VAC) SIEMENS
10 DRAIN-104 REGENERATION COOLER DRAIN VALVE (230 VAC) SUMMITS 24 G2 LOCAL MODE ON/OFF CONTACTOR (230 VAC) SALZER/SIEMENS 38 IL-110 LOCAL MODE ON/OFF INDICATION (230 VAC) SIEMENS
11 PB-101 DRYER ON PUSH BUTTON SIEMENS 25 G3 COMMON ALARM CONTACTOR (230 VAC) SALZER/SIEMENS 39 IL-111 CONTROL SUPPLY ON/OFF INDICATION (230 VAC) SIEMENS
L
12 HMI HUMAN MACHINE INTERFACE SUMMITS 26 G4 DRYER ON/OFF CONTACTOR (230 VAC) SALZER/SIEMENS 40 PB-102 DRYER OFF PUSH BUTTON SIEMENS
COMPUTER FILE NAME:

13 SDMC 13 & 14 DRYER CONTROLLER SUMMITS 27 G5 REMOTE START/STOP CONTACTOR (230 VAC) SALZER/SIEMENS 41
14 LS-101A/B LIMIT SWITCH FOR MAIN VALVE 1 ROTEX 28 ES-101 EMERGENCY SWITCH STOP SIEMENS 41
42
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
SIZE-A0
Fold-5

Fold-4

Fold-3

Fold-2

Fold-1
DOCUMENT TITLE
ELECTRICAL & INTERNAL WIRING DIAGRAM FOR DRYER PANEL
BHEL DOC. NO. PE-V0-393-555-A703
NTPC DOC. NO 0370-102-PE-PVI-L-025
Elgi's Compliance on Compressor wiring Diagram-R0
Slno Customer Comment Elgi's reply 29.06.2015

The DEW POINT METER is to be Hard wired to SG


1 DDCMIS. Noted and Updated in the revised document
Hard wired AO to SG-DDCMIS