Professional Documents
Culture Documents
SETTING TABLE 11 KV
S/S RELAY PROTECTIONS Substation : SHDN-"A",132 / 11 kV Substation DATE 11.04.23
Adopt. Settings
Feeder Number Feeder Name CTR VTR Function Type Make In Range
PSM TMS
400/1A C. Diff Solkar RF Reyrolle 1A Pr= NA NA
K01 Outgoing OC IEC-NI (Curve-A) 1.00 0.35
400/1A GE 350 GE 1A
EF IEC-NI (Curve-A) 0.20 0.27
400/1A C. Diff Solkar RF Reyrolle 1A Pr= NA NA
K02 Outgoing OC IEC-NI (Curve-A) 1.00 0.35
400/1A GE 350 GE 1A
EF IEC-NI (Curve-A) 0.20 0.27
400/1A C. Diff Solkar RF Reyrolle 1A Pr= NA NA
K03 Outgoing OC IEC-NI (Curve-A) 1.00 0.35
400/1A GE 350 GE 1A
EF IEC-NI (Curve-A) 0.20 0.27
400/1A C. Diff Solkar RF Reyrolle 1A Pr= NA NA
K04 Outgoing OC IEC-NI (Curve-A) 1.00 0.35
400/1A GE 350 GE 1A
EF IEC-NI (Curve-A) 0.20 0.27
200/1A (CT W1) Tr. DIFF 345 GE 1A XFMR diff function Trip