PAGE 1 OF 2 RELAY SETTINGS COORDINATION STUDY

SHDN-Z, 400/132/11KV SUBSTATION


MINISTRY OF ELECTRICITY WATER, STATE OF KUWAIT

11KV SIDE RELAY SETTING DETAILS

SETTING TABLE 11 KV
S/S RELAY PROTECTIONS Substation : SHAD-"Z",400 / 132 / 11 kV Substation DATE 11.04.23

Adopt. Settings
Feeder Number Feeder Name CTR VTR Function Type Make In Range
PSM TMS
400/1A C. Diff Solkar RF Reyrolle 1A Pr= NA NA
K01 Outgoing OC IEC-NI (Curve-A) 1.00 0.35
400/1A GE 350 GE 1A
EF IEC-NI (Curve-A) 0.20 0.27
400/1A C. Diff Solkar RF Reyrolle 1A Pr= NA NA
K02 Outgoing OC IEC-NI (Curve-A) 1.00 0.35
400/1A GE 350 GE 1A
EF IEC-NI (Curve-A) 0.20 0.27
400/1A C. Diff Solkar RF Reyrolle 1A Pr= NA NA
K03 Outgoing OC IEC-NI (Curve-A) 1.00 0.35
400/1A GE 350 GE 1A
EF IEC-NI (Curve-A) 0.20 0.27
400/1A C. Diff Solkar RF Reyrolle 1A Pr= NA NA
K04 Outgoing OC IEC-NI (Curve-A) 1.00 0.35
400/1A GE 350 GE 1A
EF IEC-NI (Curve-A) 0.20 0.27

200/1A (CT W1) Tr. DIFF 345 GE 1A XFMR diff function Trip

1600/1A (CT W2) Diff function minimum pickup 0.25*CT

Slope 1 30%
Break 1 0.85*CT
Break 2 3*CT
Slope 2 80%
Inrush inhibit function 2nd Harm block
Inrush inhibit level 20%
2nd Bias Slope Type setting Line
Inrush inhibit mode Per phase
Overexcitation inhibit mode 5th Harm block
K05 30 MVA TRAFO-1
Over excitation inhibit level 25%
Instantaneous differential Trip
Instantaneous diff.pickup 5.25*CT

1600/1A (PH CT) Tr. LV REF 345 GE 1A RGF function Trip

1600/1A (GND CT) CT input CT(W2)

RGF pickup 0.1*CT(W2)


RGF slope 0.12
RGF delay 0.10s
Ground current supervision Enabled
Ground supervision level 0.1*CTg(W2)
800/1A S.By. EF 350 GE 1A IEC EI(Curve C) 0.75 0.05
400/1A C. Diff Solkar RF Reyrolle 1A Pr= NA NA
K06 Outgoing OC IEC-NI (Curve-A) 1.00 0.35
400/1A GE 350 GE 1A
EF IEC-NI (Curve-A) 0.20 0.27
400/1A C. Diff Solkar RF Reyrolle 1A Pr= NA NA
K07 Outgoing OC IEC-NI (Curve-A) 1.00 0.35
400/1A GE 350 GE 1A
EF IEC-NI (Curve-A) 0.20 0.27
400/1A C. Diff Solkar RF Reyrolle 1A Pr= NA NA
K08 Outgoing OC IEC-NI (Curve-A) 1.00 0.35
400/1A GE 350 GE 1A
EF IEC-NI (Curve-A) 0.20 0.27
400/1A C. Diff Solkar RF Reyrolle 1A Pr= NA NA
K09 Outgoing OC IEC-NI (Curve-A) 1.00 0.35
400/1A GE 350 GE 1A
EF IEC-NI (Curve-A) 0.20 0.27

200/1A (CT W1) Tr. DIFF 345 GE 1A XFMR diff function Trip

1600/1A (CT W2) Diff function minimum pickup 0.25*CT

Slope 1 30%
Break 1 0.85*CT
Break 2 3*CT
Slope 2 80%
Inrush inhibit function 2nd Harm block
Inrush inhibit level 20%
2nd Bias Slope Type setting Line
Inrush inhibit mode Per phase
Overexcitation inhibit mode 5th Harm block
K10 30 MVA TRAFO-2
Over excitation inhibit level 25%
Instantaneous differential Trip
Instantaneous diff.pickup 5.25*CT

1600/1A (PH CT) Tr. LV REF 345 GE 1A RGF function Trip

1600/1A (GND CT) CT input CT(W2)

RGF pickup 0.1*CT(W2)


RGF slope 0.12
RGF delay 0.10s
Ground current supervision Enabled
Ground supervision level 0.1*CTg(W2)
800/1A S.By. EF 350 GE 1A IEC EI(Curve C) 0.75 0.05
400/1A C. Diff Solkar RF Reyrolle 1A Pr= NA NA
K11 Outgoing OC IEC-NI (Curve-A) 1.00 0.35
400/1A GE 350 GE 1A
EF IEC-NI (Curve-A) 0.20 0.27
400/1A C. Diff Solkar RF Reyrolle 1A Pr= NA NA
K12 Outgoing OC IEC-NI (Curve-A) 1.00 0.35
400/1A GE 350 GE 1A
EF IEC-NI (Curve-A) 0.20 0.27
PAGE 2 OF 2 RELAY SETTINGS COORDINATION STUDY
SHDN-Z, 400/132/11KV SUBSTATION
MINISTRY OF ELECTRICITY WATER, STATE OF KUWAIT

11KV SIDE RELAY SETTING DETAILS

400/1A C. Diff Solkar RF Reyrolle 1A Pr= NA NA


K13 Outgoing OC IEC-NI (Curve-A) 1.00 0.35
400/1A GE 350 GE 1A
EF IEC-NI (Curve-A) 0.20 0.27
LOCAL TRF-1000 OC 1A IEC-NI(Curve A) 0.66 0.35
K14 kVA, 100/1A 350 GE
EF 1A IEC-NI(Curve A) 0.10 0.05
11/0.415 kV
OC 1A IEC-NI(Curve A) 0.70 0.27
K15 BUS COUPLER 3000/1A 350 GE
EF 1A IEC-NI(Curve A) 0.20 0.12
OC 1A IEC-NI(Curve A) 0.70 0.27
K16 BUS SECTION 3000/1A 350 GE
EF 1A IEC-NI(Curve A) 0.20 0.12
LOCAL TRF-1000 OC 1A IEC-NI(Curve A) 0.66 0.35
K17 100/1A 350 GE
kVA, EF 1A IEC-NI(Curve A) 0.10 0.05
400/1A C. Diff Solkar RF Reyrolle 1A Pr= NA NA
K18 Outgoing OC IEC-NI (Curve-A) 1.00 0.35
400/1A GE 350 GE 1A
EF IEC-NI (Curve-A) 0.20 0.27
400/1A C. Diff Solkar RF Reyrolle 1A Pr= NA NA
K19 Outgoing OC IEC-NI (Curve-A) 1.00 0.35
400/1A GE 350 GE 1A
EF IEC-NI (Curve-A) 0.20 0.27
200/1A (CT W1) Tr. DIFF 345 GE 1A XFMR diff function Trip
1600/1A (CT W2) Diff function minimum pickup 0.25*CT
Slope 1 30%
Break 1 0.85*CT
Break 2 3*CT
Slope 2 80%
Inrush inhibit function 2nd Harm block
Inrush inhibit level 20%
2nd Bias Slope Type setting Line
Inrush inhibit mode Per phase
Overexcitation inhibit mode 5th Harm block
K20 30 MVA TRAFO-3
Over excitation inhibit level 25%
Instantaneous differential Trip
Instantaneous diff.pickup 5.25*CT
1600/1A (PH CT) Tr. LV REF 345 GE 1A RGF function Trip
1600/1A (GND CT) CT input CT(W2)
RGF pickup 0.1*CT(W2)
RGF slope 0.12
RGF delay 0.10s
Ground current supervision Enabled
Ground supervision level 0.1*CTg(W2)
800/1A S.By. EF 350 GE 1A IEC EI(Curve C) 0.75 0.05
400/1A C. Diff Solkar RF Reyrolle 1A Pr= NA NA
K21 Outgoing OC IEC-NI (Curve-A) 1.00 0.35
400/1A GE 350 GE 1A
EF IEC-NI (Curve-A) 0.20 0.27
400/1A C. Diff Solkar RF Reyrolle 1A Pr= NA NA
K22 Outgoing OC IEC-NI (Curve-A) 1.00 0.35
400/1A GE 350 GE 1A
EF IEC-NI (Curve-A) 0.20 0.27
400/1A C. Diff Solkar RF Reyrolle 1A Pr= NA NA
K23 Outgoing OC IEC-NI (Curve-A) 1.00 0.35
400/1A GE 350 GE 1A
EF IEC-NI (Curve-A) 0.20 0.27
400/1A C. Diff Solkar RF Reyrolle 1A Pr= NA NA
K24 Outgoing OC IEC-NI (Curve-A) 1.00 0.35
400/1A GE 350 GE 1A
EF IEC-NI (Curve-A) 0.20 0.27
400/1A C. Diff Solkar RF Reyrolle 1A Pr= NA NA
K25 Outgoing OC IEC-NI (Curve-A) 1.00 0.35
400/1A GE 350 GE 1A
EF IEC-NI (Curve-A) 0.20 0.27
200/1A (CT W1) Tr. DIFF 345 GE 1A XFMR diff function Trip
1600/1A (CT W2) Diff function minimum pickup 0.25*CT
Slope 1 30%
Break 1 0.85*CT
Break 2 3*CT
Slope 2 80%
Inrush inhibit function 2nd Harm block
Inrush inhibit level 20%
2nd Bias Slope Type setting Line
Inrush inhibit mode Per phase
Overexcitation inhibit mode 5th Harm block
K26 30 MVA TRAFO-4
Over excitation inhibit level 25%
Instantaneous differential Trip
Instantaneous diff.pickup 5.25*CT
1600/1A (PH CT) Tr. LV REF 345 GE 1A RGF function Trip
1600/1A (GND CT) CT input CT(W2)
RGF pickup 0.1*CT(W2)
RGF slope 0.12
RGF delay 0.10s
Ground current supervision Enabled
Ground supervision level 0.1*CTg(W2)
800/1A S.By. EF 350 GE 1A IEC EI(Curve C) 0.75 0.05
400/1A C. Diff Solkar RF Reyrolle 1A Pr= NA NA
K27 Outgoing OC IEC-NI (Curve-A) 1.00 0.35
400/1A GE 350 GE 1A
EF IEC-NI (Curve-A) 0.20 0.27
400/1A C. Diff Solkar RF Reyrolle 1A Pr= NA NA
K28 Outgoing OC IEC-NI (Curve-A) 1.00 0.35
400/1A GE 350 GE 1A
EF IEC-NI (Curve-A) 0.20 0.27
400/1A C. Diff Solkar RF Reyrolle 1A Pr= NA NA
K29 Outgoing OC IEC-NI (Curve-A) 1.00 0.35
400/1A GE 350 GE 1A
EF IEC-NI (Curve-A) 0.20 0.27
400/1A C. Diff Solkar RF Reyrolle 1A Pr= NA NA
K30 Outgoing OC IEC-NI (Curve-A) 1.00 0.35
400/1A GE 350 GE 1A
EF IEC-NI (Curve-A) 0.20 0.27