Professional Documents
Culture Documents
Abb Sd2b Manualrev13
Abb Sd2b Manualrev13
SD SERIES 2B
SWITCHGEAR MANUAL
ABB Ltd
Switchgear Division
Auckland
New Zealand Document #: SD2BMANUAL
Phone: +64 9 837 1234 Revision 13
Fax: +64 9 837 2950 30/03/2000
ABB
TABLE OF CONTENTS
2 INSTALLATION ................................................................................................3
2.1 GENERAL 3
2.2 TRANSPORT 3
2.3 MOUNTING 3
2.4 INTERCONNECTED UNITS 4
2.5 BUSBAR END COVER 4
2.6 CABLE BOXES 5
2.7 OIL FILLING 5
2.8 EARTH CONNECTION 5
2.9 GENERAL ARRANGEMENTS 6
4 OPERATION .....................................................................................................9
4.1 BASIC SWITCH 9
4.1.1 OFF TO ON .................................................................................................................................9
4.1.2 ON TO OFF .................................................................................................................................9
4.1.3 OFF TO EARTH..........................................................................................................................9
4.1.4 EARTH TO OFF..........................................................................................................................9
4.2 SWITCH FUSE 10
4.3 REPLACING FUSES 10
4.4 CABLE TESTING 11
4.5 INTERLOCKS 11
4.5.1 ON/OFF/EARTH .......................................................................................................................12
4.5.2 TEST ACCESS COVERS..........................................................................................................12
4.5.3 USING TEST DEVICE .............................................................................................................12
4.5.4 FUSE ACCESS COVER............................................................................................................12
5 MAINTENANCE ..............................................................................................13
5.1 GENERAL 13
5.2 CORROSION PROTECTION 13
ABB
1 GENERAL DESCRIPTION
1.1 APPLICATION
The SD Series 2 switch range is designed for use on distribution systems to switch 3-phase
currents up to 400-600A (depending on voltage) at voltages up to 12kV. SD switches are
available in a variety of configurations made up from a switch and an automatic tripping
switch fuse (activated by a fuse striker). These include an RMU (a ring main unit
comprising 2 switches & 1 switch fuse), single, double and triple switches and a single
switch fuse. Each switch and switch fuse has an associated cable earthing switch as part of
the module.
All these configurations can be supplied with extensibility to allow bus-interconnection to
build up a switchboard arrangement.
General arrangement and foundation details are shown in Figures 3 and 4 (pp 6 & 7).
1.1.1 ACCESSORIES
A wide range of accessories including earth fault indicators, voltage indicators and flush
front covers are available. Full details of these are contained in ABB document
SD2BACCESSORY.
1.2 SD RATINGS
SD2BMANUAL Page 1 of 13
Revision 13 30/03/00
ABB
The SD switch is an oil-filled switch using rose and poker contacts for main and earth
switches. The switches are operated by a manually charged spring bank. The spring bank
drives the poker contacts to the ON or OFF position.
Cable connection is made to the bushing stems projecting from the lower front of the tank.
(Section 2 deals with installation and cable connection).
The main switch moving contact operates horizontally across the bottom of the tank while
the earth contacts move vertically at the front. Three busbars run laterally across the width
of the tank interconnecting switch modules and, when required, extension bushings in the
tank sides.
In the case of a fused switch, the fuses are positioned between the sliding contact housing
and the busbar system by means of self-aligning contacts. This arrangement allows the fuse
carrier to be lifted clear of the oil (and out of the circuit) for fuse changing. The fused
switches use a fuse incorporating a fuse striker pin. This ensures that all phases are opened
when any fuse operates.
Mechanisms are charged by horizontal operating shafts that pass out through the front of the
tank where the drive dogs are attached. Shaft seals are provided to prevent ingress of
moisture and dust.
The switch status is shown by indicator flags, swivelling on the shaft bosses, which are
visible through the window located between each pair of shafts. The ON indicator is
connected to the main switch contact driving shaft at the lower rear by means of a flexible
cable. The EARTH indicator has a rod connecting it to the earth contact bridge at the lower
front. When both ON and EARTH flags are withdrawn, ie both contact sets are open, the
fixed OFF indicator is shown.
The top of the tank is closed by a lid assembly incorporating access covers for cable testing
and, in the case of a fused switch, fuse access. When the fuse access cover is raised the fuse
carrier assembly is lifted clear of the oil. A special test device can be inserted at the access
opening to test the cable.
Various interlocks are provided to prevent inadvertent unsafe operation and these are further
described in Section 4.5. Circuit mimic diagrams and operating directions are clearly
displayed adjacent to the operating dogs at the front of the tank. A rating label showing load,
fault current and voltage levels for the switch, with its serial numbering, is attached to the
lower front.
SD2BMANUAL Page 2 of 13
Revision 13 30/03/00
ABB
2 INSTALLATION
2.1 GENERAL
The weight of each unit is:
Without Oil Filled with Oil Oil Volume
(kg) (kg) (litre)
SD 115 160 50
SD2 190 275 95
SD3 250 375 140
SDAF3 250 370 135
SDAF 170 250 90
SDAF14 180 275 110
SDAF14-3 262 410 170
SDM 250 460 210
The switch and mechanism are factory set and require no attention before commissioning.
Switches are shipped, bolted to a pallet and protected with a packing cover. On receipt,
check each unit for transit damage, paying particular attention to insulation, and make good
any damaged paintwork.
The unit should be stored under cover in dry conditions. Units in storage should be filled
with clean dry oil.
Before putting the units into service, remove any storage oil and refill with clean dry oil.
2.2 TRANSPORT
The units are shipped from the factory without oil. When units are transported with oil, it is
possible that there will be seepage through the vent plug. The seepage volume will be only a
small volume and need cause no concern. The level of oil in the unit must be checked before
use.
2.3 MOUNTING
The equipment should be mounted on a concrete base designed to support the equipment
weight as detailed in the table above. The concrete base should be mounted on a suitably
prepared and compacted base. The concrete base should be smooth and must be installed
such that it is level. The maximum deviation in the height of the mounting pad must be less
than 5mm in any direction.
The units are fastened by four M12 bolts. Ensure the galvanised base piece is installed in the
service position as illustrated in Figure 1. The galvanised base piece is needed to separate
the stand from the ground to prevent corrosion of the stand. Ensure that there is free air
movement around the stand and prevent build up of material around the base of the stand.
SD2BMANUAL Page 3 of 13
Revision 13 30/03/00
ABB
(a) (b)
Figure 1: Base Piece Location. (a) For Transport. (b) For Service.
SD2BMANUAL Page 4 of 13
Revision 13 30/03/00
ABB
2.6 CABLE BOXES
The cable box will accommodate cables up to 300mm². The
centre of the bushing hole is approximately 687mm above
ground level. The width of the cable box varies with the type of
switch used, but has a minimum width of greater than 230mm.
Suitable Raychem kits that can be used with the SD range of
switchgear are detailed in Section 3.
687
the switch tank for cleanliness, loose packing etc, and then fill
with transformer oil that meets standards BS 148 and IEC 296.
The oil level mark corresponds to the correct level with covers
closed (fuse carriage lowered). If filling a fused unit with the
carriage raised, stop when oil is visible at the lower edge of
window, close cover and check level. Add oil as necessary to
reach correct level. Approximate oil capacities are shown in the >230
table in Section 2.1
Figure 2: Dimensions
within Cable Box.
SD2BMANUAL Page 5 of 13
Revision 13 30/03/00
ABB
2.9 GENERAL ARRANGEMENTS
630
630
630
515
815
440
646 751
1574
1574
1324
1282
1282
384 384
811
160 245.5 245.5 160
944 to centre line of bushings
(690 for short height stands)
31 692 31
208
60
Figure 4: Detailed front view (showing sweep of operating handle) and foundation plan for SDAF3.
SD2BMANUAL Page 6 of 13
Revision 13 30/03/00
ABB
320 566 811 524 811
FRONT VIEW
263 221 509 221 754 221 468 221 754 221
201 283 447 283 692 283 406 283 692 283
60
FOUNDATION PLAN 208
EDGE OF CONCRETE
131 132 132 246 132 131 246 246 132 234 234 131 246 246 132
221 754 221 509 221 464 221 468 221 754
283 692 283 447 283 402 283 406 283 692
Figure 5: Front View, Mounting Layout and Single Line Diagrams for
a Combination of 10" and 14" SD Equipment.
SD2BMANUAL Page 7 of 13
Revision 13 30/03/00
ABB
3 CABLE KITS
3.1 RAYCHEM KIT LIST
NOTE:
1. Raychem jointing instructions should be adhered to.
2. Use only sealed type cable lugs.
3. It is desirable that air circulation be allowed around raychem joints, sealed boxes are not
recommended.
4. A quick release inline boot is available which rolls over the cable termination
5. Tail length 450mm.
SD2BMANUAL Page 8 of 13
Revision 13 30/03/00
ABB
4 OPERATION
The following sections give a brief overview of the operation of the switches.
Comprehensive switching details are given in the detailed operating manual (Document #
SD2BOPERATION) available from ABB.
4.1.1 OFF TO ON
To operate from OFF to ON, first ensure the interlock bar is slid to the extreme right; the
tag will virtually touch the yellow earth dog. Attach the black socket of the operating handle
to the black (left-hand) dog so that the hinge does not collapse when down force is applied
(if it does, reverse it to use the other side of the black socket). To turn ON, press the handle
with a firm positive motion (clockwise with a standard handle) through the full 90° of
movement. The padlocking lug on the dog should now be close to the top bar and aligned
with the hole to allow a padlock to be passed through both. The mechanism will discharge
after approximately 600 of handle movement and the status indicator will show ON (white
letters against a red background).
4.1.2 ON TO OFF
If turning OFF immediately after turning ON, the handle must be removed and reversed
using the other socket to ensure the hinge is locked. This breakaway feature of the handle
ensures there is a minimum 3 second delay between OFF to ON and ON to OFF, avoiding
instinctive attempts to open the switch if closing onto a fault condition. To switch OFF,
raise the handle with a firm positive motion (anti-clockwise) through the 900 to bring the
padlocking lug to the lower padlocking bar. The status indicator will show OFF (white
letters against a green background).
SD2BMANUAL Page 9 of 13
Revision 13 30/03/00
ABB
Handle is raised (clockwise) in a reversal of 4.1.3 after changing drive sockets. OFF will
show in the window.
SD2BMANUAL Page 10 of 13
Revision 13 30/03/00
ABB
IF FOR SOME REASON A FUSE CARRIAGE HAS TO BE LOWERED WITHOUT
FUSES, ENSURE STIRRUPS ARE IN THE POSITION SHOWN BELOW.
STIRRUP
FUSE CARRIAGE
Note: The SD range of switch fuses is designed to operate with fuse links manufactured to
standards IEC 282:1985 and BS 2692:1986, heavy range (table 12) which calls for a striker
energy of 2 joules plus or minus 1 joule.
It is necessary to secure the test access cover before the earth can be removed. The switch is
now ready for putting back into service.
4.5 INTERLOCKS
SD2BMANUAL Page 11 of 13
Revision 13 30/03/00
ABB
Interlocked functions are referred to in each relevant section but a summary is made here for
quick reference.
4.5.1 ON/OFF/EARTH
It is not possible to switch both Main and Earth switches ON together. The sliding bar
mounted between the operating dogs must be positioned to select the operation required.
SD2BMANUAL Page 12 of 13
Revision 13 30/03/00
ABB
5 MAINTENANCE
5.1 GENERAL
This switchgear should be maintained in accordance with: the recommendations of British
Standard Code of Practice C.P. 1009 for the maintenance of insulating oil; British Standard
Code of Practice BS 5405:1976; the maintenance of electrical switchgear; the user's own
maintenance regulations; and the following instructions.
If the SD switchgear suffers problems, please contact your ABB supplier or Switchgear
Division at the following address for advice:
ABB Ltd
Switchgear Division
133 Central Park Drive
PO Box 83-203
Auckland 8
New Zealand
SD2BMANUAL Page 13 of 13
Revision 13 30/03/00