Professional Documents
Culture Documents
Cooling Capacity:
NEXT EVO DX
Precision air conditioner. The machines are designed for indoor installation.
20 models available, 2 versions for a wide selection opportunity.
EER up to 4,47.
On/off scroll compressors. The units are designed to be matched with remote condensers with axial
Single and double refrigerant circuit. fans (TEAM MATE series) or plug-fans (TEAM MATE PF series).
R410A Refrigerant charge.
rotary compressor (size E1, E2).
AC plug-fans (size E3, E4, E5, E6, E7, E8). Room air temperature:
OVER and UNDER versions. 14°C minimum temperature with wet bulb.
24°C maximum temperature with wet bulb.
Suitable for indoor installation.
35°C maximum temperature with dry bulb.
ELECTRICAL PANEL
In accordance with EN60204-1 norms, suitable for indoor installation,
FRAMEWORK complete wit:
Base in aluminium extrusion, painted with epoxy powders. Colour RAL Main switch with door lock safety on frontal panel;.
9005; Magnetothermic switches for supply fans. The supply fans equipped with
Frame in aluminium prole, painted with epoxy powders. The inner frame is EC electric motor and dont require contactors.
provided with seals for the panels. Colour RAL 9005; Transformer for auxiliary circuit and microprocessor supply.
Panels in galvanized steel sheet with protective surfaces treatment in Terminals:
compliance with UNI ISO 9227/ASTMB117 and ISO 7253, and painted with OUTLETS
epoxy powders. Colour RAL 7016 hammered; - Voltage free deviating contact for General Alarm 1
Panels insulated with polyurethane foam and seals to ensure air tight. - Voltage free contact for supply fans status.
Hinged front panels with quick release removal system. INLETS
Total front access for routine maintenance. - Emergency unit stop with signalling on display (external alarm).
Removable lateral and back side panels. - External enabling.
Air ow OVER version: Power supply 400/3/50+N.
- Air intake from the front through honeycomb type grille and air delivery
from the top. CONTROL SYSTEM
Air ow UNDER version: Microprocessor control system with graphic display for control and monitor of
- Air intake from the top and air delivery from the bottom. operating and alarms status. The system includes:
Compartment for electrical panel on unit front for direct access to control Built-in clock for alarms date and time displaying and storing;
and regulation devices; Built-in memory for the storing of the intervened events (up to 100 events
recorded);
FILTER SECTION Predisposition for connectivity board housing ( RCcom MBUS/JBUS, LON,
Washable air lters with G4 efciency, with cells in synthetic bre and BACnet for Ethernet (SNMP- TCP/IP), BACnet for MS/TP). The electronic
metallic frame (EN 779-2002). cards are optional accessories;
Air lters access: Main components hour-meter;
OVER version Non-volatile Flash memory for data storage in case of power supply faulty;
- Frontal access for all machines Menu with protection password;
UNDER version LAN connection (max 15 units).
- For machines size E1 E2 E3 frontal access
- For machine size E4 E5 E67 E7 E8 access from upper side
COOLING SECTION
Heat exchanger coil with internally corrugated copper tubes and high
efciency aluminium ns, specically developed to provide high heat
transfer and lower pressure drops.
Frame in galvanized steel or peralluman.
Condensate tray in peralluman with PVC exible discharge pipe.
Temperature sensors on air intake with control and regulation functions.
Temperature sensors on air delivery with function of temperature display.
REFRIGERANT CIRCUIT
Components for each refrigerant circuit:
Mechanical expansion valve.
Sight glass.
Filter dryer on liquid line.
Pressure transducers with indication, control and protection functions, on
low and high refrigerant pressure.
High pressure safety switch with manual reset.
Liquid receiver with accessories. The units are designed to be matched with remote condensers with axial fans
Refrigerant circuit with copper tubing with anticondensate insulation of the (TEAM MATE series) or plug-fans (TEAM MATE PF series).
suction line.
Plastic capillary hoses for pressure sensors connection.
R410A refrigerant charge and lubricant oil.
Valves on gas delivery and liquid return for coupling to remote air cooled
condenser.
0÷10V proportional signal to manage the condensing control system of the
remote air cooled condenser.
FANS SECTION
The fan section is contained within the machine and includes:
Centrifugal fans with backward curved blades with wing prole, single
suction and without scroll housings (Plug-fans), directly coupled to external
rotor electric motor.
Impeller in composite material exempt from rust formation.
AC type electric motor with xed speed.
Fan guard with rubber support (UNDER version)
SHR kW/kW 0,95 0,95 0,95 0,95 0,95 0,95 0,95 0,94 0,95 0,92 0,95
Unit power input kW 1,73 2,16 2,62 3,39 3,78 4,41 5,34 6,55 7,42 8,35 9,78
Supply fans n. 1 1 1 1 1 1 1 1 1 1 1
Air ow m3/h 2500 2700 2800 4000 4200 5700 6100 6400 8450 8450 10350
Nominal external static pressure Pa 20 20 20 20 20 20 20 20 20 20 20
Fans max external static pressure Pa 180 130 110 100 55 310 240 190 20 20 20
Compressors rotary rotary rotary rotary rotary scroll scroll scroll scroll scroll scroll
Quantity n. 1 1 1 1 1 1 1 1 1 1 1
Capacity steps n. 1 1 1 1 1 1 1 1 1 1 1
Air lters n. 1 1 1 1 1 2 2 2 2 2 2
Efciency G4 G4 G4 G4 G4 G4 G4 G4 G4 G4 G4
Refrigerant R410A R410A R410A R410A R410A R410A R410A R410A R410A R410A R410A
Refrigerant charge (2) kg 3,2 3,2 3,2 3,4 3,4 4,0 4,0 4,0 5,7 5,7 8,6
Gas circuits n. 1 1 1 1 1 1 1 1 1 1 1
Power supply (**) 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N
Max operating current (FLA) A 6,1 7,0 7,2 8,5 9,1 15,4 18,8 20,1 22,2 25,7 30,4
Unit starting current (LRA) A 33,3 40,3 37,5 54,5 54,5 66,9 77,9 103,9 130,9 141,9 122,0
Energy efciency indexes (1)
EER kW/kW 4,22 4,07 3,89 3,98 3,84 4,47 4,06 3,94 4,30 4,31 4,16
Sound pressure level - ISO 3744 (3)
On air delivery Under/Over dB(A) 58,0 59,6 60,4 62,6 63,6 63,5 65,0 66,0 72,0 75,1 71,2
On air intake Over dB(A) 49,8 50,2 51,9 51,3 53,0 53,9 57,7 55,1 57,8 58,9 58,8
Irradiated Over dB(A) 40,2 41,4 42,4 40,4 41,7 42,4 45,5 44,0 48,6 51,3 49,4
On air intake Under dB(A) 50,1 52,3 52,3 50,5 52,0 52,5 55,2 54,3 58,9 61,4 59,7
On front side Under dB(A) 40,9 42,1 43,2 41,3 42,9 43,4 46,3 45,1 49,6 52,0 50,5
Net weight Over kg 220 221 228 260 265 300 305 305 410 415 427
Net weight Under kg 230 231 238 270 275 320 325 325 420 425 437
Remote condenser (4) n.
TEAM MATE Mod. M 11 M 11 M 11 M 14 M 17 M 25 M 25 M 30 M 35 M 45 M 45
TEAM MATE PF Mod. T 11 T 11 T 11 T 14 T 21 T 24 T 24 T 33 T 38 T 44 T 44
Refrigerant connections
Gas delivery ODS Ø 16 16 16 16 16 18 18 18 22 22 28
Liquid return ODS Ø 12 12 12 12 12 16 16 16 16 16 22
Hydraulic connections - Condensate discharge F Ø 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
SHR kW/kW 0,91 0,93 0,91 0,95 0,95 0,95 0,94 0,91 0,88
Unit power input kW 10,78 8,59 11,69 13,20 14,77 17,68 19,59 21,56 25,37
Supply fans n. 1 1 1 2 2 2 2 2 2
Air ow m3/h 10350 8750 10850 15000 15600 20000 20000 20900 20900
Nominal external static pressure Pa 20 20 20 20 20 20 20 20 20
Fans max external static pressure Pa 20 20 20 137 70 20 20 20 20
Compressors scroll scroll scroll scroll scroll scroll scroll scroll scroll
Quantity n. 1 2 2 2 2 2 2 2 2
Capacity steps n. 1 2 2 2 2 2 2 2 2
Air lters n. 2 3 3 3 3 4 4 5 5
Efciency G4 G4 G4 G4 G4 G4 G4 G4 G4
Refrigerant R410A R410A R410A R410A R410A R410A R410A R410A R410A
Refrigerant charge (2) kg 8,6 9,0 9,0 9,8 9,8 16,2 16,2 17,4 17,4
Gas circuits n. 1 2 2 2 2 2 2 2 2
Power supply (**) 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N
Max operating current (FLA) A 36,7 27,8 35,7 40,1 44,3 53,7 60,9 73,5 79,8
Unit starting current (LRA) A 144,0 78,7 94,0 123,0 152,0 168,6 151,0 179,0 216,0
Energy efciency indexes (1)
EER kW/kW 4,11 4,25 4,03 4,13 4,15 4,22 4,15 4,17 4,02
Sound pressure level - ISO 3744 (3)
On air delivery Under/Over dB(A) 71,2 75,2 74,1 71,8 72,6 72,3 72,3 74,7 74,7
On air intake Over dB(A) 57,6 59,0 59,2 58,5 60,3 60,6 61,3 62,6 63,4
Irradiated Over dB(A) 48,0 51,5 50,5 48,7 49,9 50,7 51,0 53,0 53,3
On air intake Under dB(A) 59,9 61,6 60,8 59,0 60,1 61,0 61,3 63,3 63,6
On front side Under dB(A) 50,8 52,1 51,4 49,7 50,9 51,8 52,2 54,1 54,4
Net weight Over kg 435 520 530 610 630 688 695 785 785
Net weight Under kg 435 530 540 620 640 745 750 845 845
Remote condenser (4) n.
TEAM MATE Mod. M 50 M 25 M 25 M 30 M 35 M 45 M 45 M 50 M 60
TEAM MATE PF Mod. T 58 T 24 T 33 T 33 T 38 T 38 T 58 T 58 T69
Refrigerant connections
Gas delivery ODS Ø 28 2x18 2x18 2x18 2x18 2x22 2x28 2x28 2x28
Liquid return ODS Ø 22 2x12 2x16 2x16 2x16 2x16 2x22 2x22 2x22
Hydraulic connections - Condensate discharge F Ø 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD
1. Characteristics referred to entering air at 24°C-45%RH; 45°C condensing temperature.
2. Unit refrigerant charge. Remote condenser, connections pipes and optional are excluded.
3. Noise level at 1 meter in free eld (external static pressure 50 Pa)
4. For matching to other remote air cooled condensers please refer to RC WORLD selection program
(**) The remote condenser has separated power supply
G_ITC_RCW8.4 RCGROUP SpA 19632013 fiftycoolyears
IT Cooling NEXT EVO DX
Electric heater
Capacity kW
Capacity steps n. 1,0 1,0 1,0 1,0 1,0 2,0 2,0 2,0 3,0 3,0
Humidifier
Steam capacity kg/h 3 3 3 3 3 3 3 3 8 8
Power input kW 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 6,0 6,0
Extra circuit coil (1)
Electric heater
Capacity steps n. 3,0 3,0 3,0 3,0 3,0 3,0 3,0 3,0 3,0 3,0
Humidifier
Steam capacity kg/h 8 8 8 8 8 8 8 8 8 8
Power input kW 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0
Extra circuit coil (1)
1. Characteristics referred to entering air at 24°C 50%RH with chiller water at 7/12,5 °C and 0% glycol
2. Characteristics referred to entering air at 20°C with hot water at 75/60°C
a b