Coldroom Controllers
Technical Data
Selection Table
®
TCP/IP Ethernet LON FTT-10
Description Type Order Nr. Type Order Nr.
Coldroom Controller
EC3-332 807 632 EC3-331 807 631
Superheat control for EX5 ... EX8 Electrical Control Valves *
*For further details refer to: EX5, EX6, EX7, EX8 Electrical Control Valves datasheet EX58e35008.pdf
Introduction
The EC3-33x series Controllers are for use in commercial compressor. Due to the positive shut-off capabilities of the EX5
refrigeration systems, primarily to control the refrigeration circuit … 8 valves a separate liquid line solenoid valve is not required.
of coldrooms. This includes the control of the refrigerant flow to Superheat Control
optimize superheat, maintain air temperature and the defrost The EC3 Series controls evaporator superheat by varying the
management. Alco Controls EX5… EX8 Electrical Control mass flow through the Electrical Control Valve (ECV). The
Valves must be used in conjunction with the EC3-33x units to controller automatically calculates the number of steps required
modulate refrigerant flow. for the correct valve opening by measuring pressure and
Two separate control loops are coordinated in the device: One temperature at the evaporator output. PT4-07S pressure
senses evaporating pressure and temperature to maintain transmitters and ECN-Pxx pipe type temperature sensors from
optimum superheat, while the other loop controls air ALCO Controls must be used.
temperature. The controller works in two operating modes: fixed superheat
Other functions include the management of defrost schedules and adaptive superheat. In the “fixed” mode, the superheat
and sequences, data monitoring and alarm handling. Though set-point is fixed to a user-defined value. In the “adaptive” mode
EC3 Controllers can operate as stand alone devices, they are the controller varies superheat set-points in the range between
best suited to networked solutions, which take advantage of the 3K and 15 K depending on system conditions to maintain stable
monitoring capabilities. operation. The pressure drop through a distributor or the glide
The EC3-33x Controllers are members of the range of EC2 and associated with certain refrigerants (e.g. R407C) can be
EC3 devices, which can be easily assembled into complete compensated in the controller.
control systems for commercial refrigeration. They all share the Temperature Control
benefits of remote access and data communication. Please
The ECN-Sxx air sensor is used for temperature control of the
refer to specific datasheets for details.
coldroom. The dead band control function is described in the
Application diagram below:
The functions of the EC3-33x Controllers are described in the
functional diagram below:
The top fields indicate the status of compressor, defrost heater, A logfile can be stored on the PC. The file format of the datalog
fan and alarm output relay (left) and the status of compressor is text with semicolon (;) separated fields. On the picture below
alarm loop and door switch inputs (right). The fields below show is a sample log file from an EC3-332 imported in Microsoft
temperatures and pressure of all sensors attached to the Excel®:
controller as well as the setpoints for air temperature and
superheat. The coil-in temperature is calculated from the
saturation pressure of the used refrigerant. All status messages
(thermostat, defrost and evaporator) are displayed in the lower
section with normal font, all active messages are in bold letters.
A rolling graph with air temperature and superheat data over a
period of approximately 10 minutes can be displayed: All WebPages, which allow the change of controller parameters
are password protected. Below is the example for the
thermostat configuration WebPage of an EC3-332 Controller.
The setpoints of day and night operation, as well as the settings
which will initiate an alarm can be easily reviewed and modified
if needed:
Wiring Diagram
ECD 001
WH BK BL BN
1 C 2 1 C 2 1 C 1 C
EC3-33x
PCN: 807 xxx
Coldroom Controller EX5 / 6 / 7 / 8
Rev: 000 05.05 MAC ADDRESS: 00:12:0A.FD.00.00
Accessories
Terminal Kits for EC3 Series:
Type Order Nr.
Terminal Kit for EC3-33x series K03-331 807 648
ECT-623
Technical Data
EC3 Series Controller ECD-001 Display Unit
Supply voltage 24VAC ±10%, 50/60Hz Class II only Supply From EC3 Series Controller via
6.3mm spade earth connector connecting cable
Power consumption 28VA max. (EC3-33x) LED indicators Compressor, Fan, Defrost, Alarm,
LON-Service pin, IR status
Plug-in connector size Removable screw version Display LED Numeric segmental display, 2½-digits,
wire size 0.14 … 1.5mm2 red, with automatic decimal point
betw. ±19.9, switchable between °C
and °F
Communication TCP/IP Ethernet (EC3-332) Connecting cable 1,5m (ECC-017) or standard CAT5
®
LON FTT-10 (EC3-331) patch cord with RJ45 connectors
Temperature Temperature
storage -20 … +65°C storage -20 … +65°C
operating 0 … +60°C operating 0 … +60°C
Humidity 0 … 80% r.h. non condensing Humidity 0 … 80% r.h. non condensing
Protection class IP20 Protection class IP 65 (front protection with gasket)
Weight ~ 800g Weight ~ 52g
Mounting DIN rail mounted Mounting Panel mount (71 x 29 mm cutout)
ECT-623 Transformer
75 82
62
50 62 71
ALCO CONTROLS is not to be held responsible for erroneous literature for use by persons having the appropriate technical knowledge and
regarding capacities, dimensions, applications, etc. stated herein. skills, at their own discretion and risk. Since conditions of use are
Products, specifications and data in this literature are subject to change outside of ALCO'S control we can not assume any liability for results
without notice. The information given herein is based on technical data obtained or damages occurred due to improper application.
and tests which ALCO CONTROLS believes to be reliable and which This document replaces all former versions.
are in compliance with technical knowledge of today. It is intended only
Phone: Fax:
Emerson Electric GmbH & Co OHG Benelux +31 (0)77 324 0 234 +31 (0)77 324 0 235
ALCO CONTROLS Denmark & Finland +44 (0) 1635 876 161 +44 (0) 1635 877 111
Eastern Europe +32 (0)87 305 061 +32 (0)87 305 506
Postfach 1251
Français +33 (0)4 78 66 85 70 +33 (0)4 78 66 85 71
Heerstraße 111
Deutschland +49 (0)6109 6059 -0 +49 (0)6109 6059 40
D-71332 Waiblingen Italia +39 02 961 781 +39 02 961 788 888
Germany Middle East & Africa +97 148 832 828 +97 148 832 848
Phone ...49-7151-509-0 Poland +48 (0)22 458 9205 +48 (0)22 458 9255
Fax ...49-7151-509-200 Russia & Cis +7 095 981 9811 +7 095 981 9816
España & Portugal +34 93 41 23 752 +34 93 41 24 215
www.eCopeland.com/alcoliterature.cfm Sweden & Norway +44 (0) 1635 876 161 +44 (0) 1635 877 111
UK & Ireland +44 (0) 1635 876 161 +44 (0) 1635 877 111