EC3 Series

Coldroom Controllers
Technical Data

The EC3-33x Series form a new generation of electronic


controllers for refrigeration and air conditioning. The controllers
feature a DIN rail mounted housing and a separate optional
display unit in the small industry standard housing form factor.
They offer maximum functionality such as superheat,
temperature and defrost controller with built-in TCP/IP
Ethernet communications and WebServer functionality. Any
®
standard WebBrowser (e.g. Internet Explorer or Mozilla
Firefox) can be used for monitoring or parameter setting.
The version with Echelon LON® network interface is for use in
more complex systems, where different controllers must
communicate with each other.

Features EC3-33x Series Controllers


• Superheat control with self-adapting algorithm and driver
circuit for stepper motor driven Electrical Control Valves
(EX5 … EX8)
• Air temperature control EC3 Series Coldroom Controller
• Defrost and fan management
with ECD-001 Display Unit
• Limitation of evaporating pressure (MOP)
• Feed-through of 4 … 20mA signal of evaporating pressure
transmitter to analogue output to operate multiple
controllers with a common pressure transmitter
• 2 digital inputs for compressor safety loop and coldroom
door contact
• 4 relay outputs for compressor, fan, defrost and alarm
• Support of two network technologies:
TCP/IP Ethernet with WebServer functionality allows
monitoring and configuration of controllers through a
®
standard WebBrowser (e.g. Internet Explorer or Mozilla
Firefox)
or Echelon FTT10 LON® technology for monitoring and
configuration through a supervisory system such as the
ALCO Monitoring Server AMS
• Alarm messaging by email (EC3-332)
• Integral backup battery to close Electrical Control Valve in
case of power loss
• Electrical connection via plug-in type screw terminals
• Aluminum housing for DIN rail mounting
Typical ordering package:
Features ECD-001 Display Unit • EC3-332 Coldroom Controller with K03-330 Terminal Kit
• Front panel mounted human interface for parameter and • EX5-U21 Electrical Control Valve with EX5-L30 Cable
status read-out and controller setup via keypad
• ECD-001 Display Unit with ECC-017 Cable
• 2½ digit LED display with automatic decimal point
• ECT-623 Transformer
• Indicator LEDs for compressor, fan, heater and alarm
• PT4-07S Pressure Transmitter with PT4-L30 Cable
• Connection to EC3 Series via ECC-017 or standard CAT5
patch cord with RJ45 connectors. • ECN-N30 Air Temperature Sensor
• Standard 71 x 29 mm cut-out dimensions • ECN-P30 Pipe Temperature Sensor
• IP65 protection class when mounted in front panel • ECN-F60 Fin Temperature Sensor

Selection Table
®
TCP/IP Ethernet LON FTT-10
Description Type Order Nr. Type Order Nr.
Coldroom Controller
EC3-332 807 632 EC3-331 807 631
Superheat control for EX5 ... EX8 Electrical Control Valves *
*For further details refer to: EX5, EX6, EX7, EX8 Electrical Control Valves datasheet EX58e35008.pdf

EC33e35041.doc Rev.: 06 1/8 26.10.2005


EC3 Series
Coldroom Controllers

Introduction
The EC3-33x series Controllers are for use in commercial compressor. Due to the positive shut-off capabilities of the EX5
refrigeration systems, primarily to control the refrigeration circuit … 8 valves a separate liquid line solenoid valve is not required.
of coldrooms. This includes the control of the refrigerant flow to Superheat Control
optimize superheat, maintain air temperature and the defrost The EC3 Series controls evaporator superheat by varying the
management. Alco Controls EX5… EX8 Electrical Control mass flow through the Electrical Control Valve (ECV). The
Valves must be used in conjunction with the EC3-33x units to controller automatically calculates the number of steps required
modulate refrigerant flow. for the correct valve opening by measuring pressure and
Two separate control loops are coordinated in the device: One temperature at the evaporator output. PT4-07S pressure
senses evaporating pressure and temperature to maintain transmitters and ECN-Pxx pipe type temperature sensors from
optimum superheat, while the other loop controls air ALCO Controls must be used.
temperature. The controller works in two operating modes: fixed superheat
Other functions include the management of defrost schedules and adaptive superheat. In the “fixed” mode, the superheat
and sequences, data monitoring and alarm handling. Though set-point is fixed to a user-defined value. In the “adaptive” mode
EC3 Controllers can operate as stand alone devices, they are the controller varies superheat set-points in the range between
best suited to networked solutions, which take advantage of the 3K and 15 K depending on system conditions to maintain stable
monitoring capabilities. operation. The pressure drop through a distributor or the glide
The EC3-33x Controllers are members of the range of EC2 and associated with certain refrigerants (e.g. R407C) can be
EC3 devices, which can be easily assembled into complete compensated in the controller.
control systems for commercial refrigeration. They all share the Temperature Control
benefits of remote access and data communication. Please
The ECN-Sxx air sensor is used for temperature control of the
refer to specific datasheets for details.
coldroom. The dead band control function is described in the
Application diagram below:
The functions of the EC3-33x Controllers are described in the
functional diagram below:

The horizontal axis represents the temperature, with St the set-


point for day operation and rd the difference at day, while r6 is
the set-point for night operation and r7 the difference at night.
The vertical axis represents cooling operation (1 = cooling, 0 =
no cooling).
A control parameter allows to switch off the evaporator fan
during “no cooling”.
A more precise temperature control can be achieved by using
the modulating temperature mode as shown below:

The horizontal axis represents the temperature, the vertical axis


the superheat setting. At high temperatures, the controller works
with minimum superheat. St is the set-point for day operation, at
which the superheat is already increased. rd specifies the
proportional band in which the superheat is modulated.
Equivalent is r6, the set-point for the night operation and r7 the
width of the proportional band at night. At a temperature of St
minus ½*rd (day) or r6 minus ½*r7 (night) the valve is closed.
In case the controller should be used in a heat pump for
With coil out temperature (1) and evaporating pressure (4) the heating, the function of the temperature controller can be
superheat is calculated to define the opening of the Electrical inversed:
Control Valve (11). Superheat can be set to a fixed value or an
adaptive mode may be used. Temperature sensor (2) is part of
the temperature control loop. The defrost heater (8) can be
activated locally by fixed timing intervals or remotely through the
When used with a standard condensing unit, the compressor
communications port. For defrost end termination the
relay can be used to switch the coil of power contactor. The
temperature sensor (3) can be used. Fan (10) and compressor
compressor relay is not used in a refrigeration system with a
(7) are controlled as well. One digital input is allocated to the
rack controller. In this application, the electrical control valve
compressor safety loop (5). Another digital input monitors the
closes when the thermostat set-point has been reached and the
door switch (6), which will activate an alarm if the door is not
rack will automatically pump down if there is insufficient demand
closed within a specified time. The analog output (12) feeds the
from the rest of the refrigeration system.
evaporating pressure transmitter signal to a 2nd EC3-33x or
other Controller on the same suction line thus eliminating the
need for a second pressure transmitter.
In case of power loss a battery built in the EC3-33x will close
the Electrical Control Valve (11) and avoid flooding of the
EC33e35041.doc Rev.: 06 2/8 26.10.2005
EC3 Series
Coldroom Controllers

Defrost Optional ECD-001 Display Unit


EC3-33x Series controllers allow local defrost management The ECD-001 may be attached to the EC3 Series Controller to
through the built-in defrost timer but also permit remote defrost provide a local display of system parameters, most commonly
scheduling through the networking connection. For remote temperatures. With the 2½ digit display temperatures within
defrost details please consult the operating instructions. ±199°C can be shown with a resolution of 1°C. The resolution
Two basic defrost modes are possible: improves to 0,1°C within a range of ±19.9°C. The display unit
can be switched from °C to °F. When displaying °F the same
Electrical / hot gas defrost resolution as above applies.
All timing parameters can be selected to cover specific defrost Indicator LEDs show the status of compressor, fan, defrost and
modes, see the diagrams below for the function of defrost alarm. A blinking LED indicates that the EC3 Controller is trying
output and fan output at defrost: to fulfill a task but is prevented from doing so by another
restraint in the system. An example of this would be the
Fan minimum compressor run time.

WebServer function of the EC3-332 with TCP/IP Ethernet


Defrost networking capabilities
Though the actual status of the controllers can be viewed on the
optional ECD-001 Display Unit, it is much more convenient to
do the viewing on a PC. All relevant parameters and modes are
Defrost can be activated after power up (d4 flag) and the delay
visible on a single WebPage simultaneously. For even more
(d5). Delay (d6) allows for pump down. The defrost will end
details and for setup and maintenance a click on one of the
either when the defrost termination temperature (dt) has been
screen tabs calls up a WebPage dedicated to specific task. All
exceeded or after the maximum defrost duration (dP). Other
of this can be done with a standard WebBrowser like the
delays take care for synchronization of multiple evaporators in
Internet Explorer®, the Mozilla Firefox or others. The picture on
the same system (dU), for drain (d7) and for injection (d8). The
page 4 shows the homepage of an EC3-332 with the monitoring
next defrost will occur after the specified defrost interval (dI).
WebPage of the controller.
Fans can be switched off at defrost (F3 flag) and switched on
after defrost and drip time delay (Fd). Echelon LON® Networking Capabilities of the EC3-331
End of defrost is detected by the dedicated defrost temperature The remote access, viewing and monitoring features of the
sensor ECN-F60. LON® version EC3 Series Controllers match and exceed the
capabilities of their TCP/IP counterparts. Though remote access
Natural Defrost requires the use of the Alco Controls AMS Monitoring Server or
Though natural defrost is possible with the EC3-33x Series, it is special third party LON® compliant hardware and software,
unlikely that such a defrost method is used in a coldroom. Since many more additional functions and features are available.
the EC3-33x Series is also applicable for other refrigeration The EC3-331 Controllers are equipped with LON-FTT10 (free
applications, natural defrost may well be applicable there. topology) transceiver types. This offers the installer greatest
Sensors flexibility in the way the controllers are connected to the LON®
network in addition to offering higher communication
Low cost NTC sensors are available with different cable lengths
transmission rates.
to meet specific customer's requirements for optimal positioning
of the sensors. All sensors are hermetically sealed for high When connected to the LON® network, the individual EC3
reliability and long life. Air sensors have a plastic housing, pipe Series controllers may be bound together through peer-to-peer
and fin sensors have metal housings for optimal thermal communication to form self-contained control loops for
conductivity and the fin sensor has an additional mounting clip. applications such as synchronised defrosting.
Retrieval and download of setups and data is very comfortable
Operation and Commissioning and easily achievable in LON® systems.
Operating and commissioning of an EC3-33x Controller may be Refer to the "Alco Networking Application" sheets for further
performed by using one of the following options: details.
- Locally or remote with a PC connected to the TCP/IP Ethernet
port of the EC3-332. Where to apply TCP/IP Ethernet vs. LON® Controllers
- Remotely via the AMS Server connected to the LON® port of In general TCP/IP Ethernet controllers are more applicable for
an EC3-331. smaller refrigeration systems with only a few pieces of
refrigeration equipment. No special hardware or special
- Locally through the 4-button keypad of an optional ECD-001.
software is needed and whoever can set up a small PC network
- Locally with the infrared remote control and the optional ECD- has all the necessary know-how to set up and operate EC2 and
001 display attached. EC3 TCP/IP Ethernet controllers.
For initial commissioning of a new installation depending on the In larger installations LON® has its merits. Network wiring is
networking technology of the EC3-33x the first two options are easier and less costly. Peer-to-peer communication is another
the most appropriate. Commissioning is done via dedicated benefit of LON® and data retrieval and storage are very easily
menus with meaningful default values, which make achievable. These advantages come at a price however: a
commissioning an EC3-33x a plug-and-play type of job. monitoring and server device like the Alco Controls AMS is
Anybody who is familiar with Microsoft Windows® based needed along with some special know-how in LON®
programs and WebBrowsers should find it very intuitive without technology. The associated cost therefore makes LON®
the need for special training. technology primarily applicable in large refrigeration plants with
many pieces of refrigeration equipment like Supermarkets or
large cold storage facilities.

EC33e35041.doc Rev.: 06 3/8 26.10.2005


EC3 Series
Coldroom Controllers

The top fields indicate the status of compressor, defrost heater, A logfile can be stored on the PC. The file format of the datalog
fan and alarm output relay (left) and the status of compressor is text with semicolon (;) separated fields. On the picture below
alarm loop and door switch inputs (right). The fields below show is a sample log file from an EC3-332 imported in Microsoft
temperatures and pressure of all sensors attached to the Excel®:
controller as well as the setpoints for air temperature and
superheat. The coil-in temperature is calculated from the
saturation pressure of the used refrigerant. All status messages
(thermostat, defrost and evaporator) are displayed in the lower
section with normal font, all active messages are in bold letters.
A rolling graph with air temperature and superheat data over a
period of approximately 10 minutes can be displayed: All WebPages, which allow the change of controller parameters
are password protected. Below is the example for the
thermostat configuration WebPage of an EC3-332 Controller.
The setpoints of day and night operation, as well as the settings
which will initiate an alarm can be easily reviewed and modified
if needed:

EC33e35041.doc Rev.: 06 4/8 26.10.2005


EC3 Series
Coldroom Controllers

Alarm and Maintenance Functions Safety Functions


EC3-33x provides many alarm codes to facilitate diagnosis. Various safety functions are available for use particularly when
Limit violation alarms are associated with temperature and the EC3-33x is controlling the compressor directly. These safety
pressure set point (high alarm, low alarm, sensor failure). features are used to prevent compressor damage and include:
The serial alarm loop of the compressor can be connected to a Limitation of maximum evaporating pressure (MOP), delay of
digital input. It will monitor compressor operation and signal compressor start after control reset, minimum time between two
shutdown in case the serial alarm loop is open due to high starts, minimum compressor off time, minimum compressor run
motor temperature or excessive pressure etc. time.
Alarm management includes the issuing of an alarm message Safe operating modes allow the system to continue to operate
through the network and to show the alarm code on the safely even when the signal is lost from a defective or
controllers display. The priorities and subsequent actions can disconnected sensor.
be individually defined for each alarm when connected to a PC Particularly useful facilities are the service functions, which
or an AMS monitoring server. enable the engineer to manually control the system during
The EC3-332 has the capability to send alarm messages commissioning. They include manual operation of compressor,
directly by email. fan and Electrical Control Valve, or special operating modes of
system for cleaning, permanent night operation, manual defrost
While the attached Display Unit ECD-001 indicates alarms as or others, see below:
blinking symbols only, the monitoring WebPage shows all
alarms in text form. All possible alarm messages are visible,
active alarms are highlighted bold, see below:

Wiring Diagram

ECD 001
WH BK BL BN
1 C 2 1 C 2 1 C 1 C

Alarm Comp HEAT FAN STEPPER MOTOR

DIGITAL OUTPUT 250V max 8A / 2A

EC3-33x
PCN: 807 xxx
Coldroom Controller EX5 / 6 / 7 / 8
Rev: 000 05.05 MAC ADDRESS: 00:12:0A.FD.00.00

SUPPLY DIGITAL INPUT 24V 4-20mA TEMPERATURE 4-20mA


24V AC 1 2 IN 1 2 3 OUT
COMP SUCTION COIL DEFROST SUCTION
SAFETY DOOR PRESSURE OUT AIR TERM. PRESSURE
COM

EC3-33x Coldroom Controller for Electrical Control Valves EX5 … EX8

EC33e35041.doc Rev.: 06 5/8 26.10.2005


EC3 Series
Coldroom Controllers

Accessories
Terminal Kits for EC3 Series:
Type Order Nr.
Terminal Kit for EC3-33x series K03-331 807 648

ECD Series Display Unit:


Display for EC3-200 to 500 ECD-001 807 641
Connection cable EC3 to ECD 1.5 m ECC-017 804 380

Electrical Control Valves with Stepper Motor Drive*


3 to 35kW EX5-U21 800 600
8 to 84kW EX6-I21 800 610
Nominal capacity R404A 8 to 84kW EX6-M21 800 611 ECN-Sxx
22 to 230kW EX7-U21 801 686
*) see datasheet EX58e35008.pdf 60 to 613kW EX8-M21 801 964
for details
60 to 613kW EX8-U21 801 970
Cable and connector 1.5m length EX5-C15 804656
assembly for EX5/EX6 3.0m length EX5-C30 804657
6.0m length EX5-C60 804658
ECN-Pxx
NTC Sensors (Air type) 1,5m cable length ECN-S15 804 304
(10 kΩ at 25°C) 3m cable length ECN-S30 804 305
6m cable length ECN-S60 804 284
NTC Sensors (Pipe type) 3m cable length ECN-P30 804 280
(10 kΩ at 25°C) 6m cable length ECN-P60 804 281
8m cable length ECN-P80 804 282
NTC Sensors (Fin type) ECN-Fxx
(10 kΩ at 25°C) 6m cable length ECN-F60 804 283

Pressure Transmitter -0.8…7bar PT4-07S 802 320


0…18bar PT4-18S 802 322
Cable Assembly for PT4 1.5m cable length PT4-L15 804 593
3.0m cable length PT4-L30 804 594
6.0m cable length PT4-L60 804 595

Transformer 230VAC Input, PT4-07S with


Din rail mounting, Class II 24V output, 50VA ECT-623 804 421 Plug / Cable Assembly PT4-Lxx
Infrared Remote Control
English EC2-IRE 804 345
Language: German EC2-IRD 804 346
French EC2-IRF 804 347
Spanish EC2-IRS 804 348
Italian EC2-IRI 804 349

ECT-623

EC2-IRE Remote Control

EC33e35041.doc Rev.: 06 6/8 26.10.2005


EC3 Series
Coldroom Controllers

Technical Data
EC3 Series Controller ECD-001 Display Unit
Supply voltage 24VAC ±10%, 50/60Hz Class II only Supply From EC3 Series Controller via
6.3mm spade earth connector connecting cable
Power consumption 28VA max. (EC3-33x) LED indicators Compressor, Fan, Defrost, Alarm,
LON-Service pin, IR status
Plug-in connector size Removable screw version Display LED Numeric segmental display, 2½-digits,
wire size 0.14 … 1.5mm2 red, with automatic decimal point
betw. ±19.9, switchable between °C
and °F
Communication TCP/IP Ethernet (EC3-332) Connecting cable 1,5m (ECC-017) or standard CAT5
®
LON FTT-10 (EC3-331) patch cord with RJ45 connectors
Temperature Temperature
storage -20 … +65°C storage -20 … +65°C
operating 0 … +60°C operating 0 … +60°C
Humidity 0 … 80% r.h. non condensing Humidity 0 … 80% r.h. non condensing
Protection class IP20 Protection class IP 65 (front protection with gasket)
Weight ~ 800g Weight ~ 52g
Mounting DIN rail mounted Mounting Panel mount (71 x 29 mm cutout)

Input and Output Configuration EC3-33x Controller


Description I/O Specification
Temperature inputs (3) 10kΩ @ 25 °C, Coil out temperature
-50 … 50 °C Air temperature
Defrost termination
Pressure transmitter input 24VDC, 4 … 20mA Evaporating pressure
Analog output (evaporating 24VDC, 4 … 20mA Evaporating pressure
pressure feed-through signal)
Digital inputs (2) 24VAC/DC Compressor Safety
Door contact
Output relays (4) SPDT contacts, AgCdO Compressor
Inductive (AC15) 250V / 2A, Alarm
Resistive (AC1) 250V / 8A
SPST contacts, AgCdO Heater
Inductive (AC15) 250V / 2A, Fan
Resistive (AC1) 250V / 8A
Stepper motor output For EX5 … EX8 Electrical Control Valves
Communications ®
RJ45 10MBit/sec. Ethernet or LON FTT10

EC33e35041.doc Rev.: 06 7/8 26.10.2005


EC3 Series
Coldroom Controllers

Physical Dimensions Drawings (mm)


EC3-Series Controller

ECD-001 Display Unit

ECT-623 Transformer
75 82
62

50 62 71

ALCO CONTROLS is not to be held responsible for erroneous literature for use by persons having the appropriate technical knowledge and
regarding capacities, dimensions, applications, etc. stated herein. skills, at their own discretion and risk. Since conditions of use are
Products, specifications and data in this literature are subject to change outside of ALCO'S control we can not assume any liability for results
without notice. The information given herein is based on technical data obtained or damages occurred due to improper application.
and tests which ALCO CONTROLS believes to be reliable and which This document replaces all former versions.
are in compliance with technical knowledge of today. It is intended only

Phone: Fax:
Emerson Electric GmbH & Co OHG Benelux +31 (0)77 324 0 234 +31 (0)77 324 0 235
ALCO CONTROLS Denmark & Finland +44 (0) 1635 876 161 +44 (0) 1635 877 111
Eastern Europe +32 (0)87 305 061 +32 (0)87 305 506
Postfach 1251
Français +33 (0)4 78 66 85 70 +33 (0)4 78 66 85 71
Heerstraße 111
Deutschland +49 (0)6109 6059 -0 +49 (0)6109 6059 40
D-71332 Waiblingen Italia +39 02 961 781 +39 02 961 788 888
Germany Middle East & Africa +97 148 832 828 +97 148 832 848
Phone ...49-7151-509-0 Poland +48 (0)22 458 9205 +48 (0)22 458 9255
Fax ...49-7151-509-200 Russia & Cis +7 095 981 9811 +7 095 981 9816
España & Portugal +34 93 41 23 752 +34 93 41 24 215
www.eCopeland.com/alcoliterature.cfm Sweden & Norway +44 (0) 1635 876 161 +44 (0) 1635 877 111
UK & Ireland +44 (0) 1635 876 161 +44 (0) 1635 877 111

EC33e35041.doc Rev.: 06 8/8 26.10.2005