5CIM0-04D BMS Gateway

3.4 BMS [BNU-LW (PQNFB16A0)]


3.4.1 Features & functions
1. A conversion gateway between BMS System using LonWorks protocol and LG Air Conditioner using LGAP
protocol.
2. Can process max 64 indoor units. (valid indoor address : 00 ~ 3F)
3. FT-10 line is used to connect communication lines between BMS System and Lonworks Gateway.
4. Control & monitoring of the units.

Controlling items Monitoring items


On/Off command on/off status report
Operation mode setting Operation mode status report
Fan speed setting Fan speed status report
Temperature setting Temperature setting report
Lock setting Lock setting report
Room temperature report
Error code report

3.4.2 System connection


BMS System

LonWorks®
Network

Lighting Remote Utility


control checking control

Other LON Devices

Indoor units : Maximum 64 units


Indoor address : 00 ~ 3F

RS485

PI 485(PMNFP14A0)

PI 485(PMNFP14A0)

LonWorks ®
Gateway
PI 485(PMNFP14A0)
MPS Outdoor unit Indoor units
LGAP applied air conditioner
❈ PI 485 (PMNFP14A0) must be purchased separately

Others 694
BMS Gateway 5CIM0-04D

Indoor_nn (Object ID : 01~64)

nviOnOff_nn nvoOnOff_nn
SNVT_switch SNVT_switch
ID : 95 ID : 95

nviMode_nn nvoMode_nn
SNVT_hvac_mode SNVT_hvac_mode
ID : 108 ID : 108

nviFanSpeed_nn nvoFanSpeed_nn
SNVT_switch SNVT_switch
ID : 95 ID : 95

nviLock_nn nvoLock_nn
SNVT_switch SNVT_switch
ID : 95 ID : 95

nvoRoomTemp_nn
SNVT_temp_p
ID : 105

nviSetTemp_nn nvoSetTemp_nn
SNVT_temp_p SNVT_temp_p
ID : 105 ID : 105

nvoError_nn
SNVT_count
ID : 8

Control network variable Monitoring network variable

System connection for air conditioner only

PI 485(PMNFP14A0)
MPS

LON
GW
PI 485(PMNFP14A0) Multi V Plus

BMS System
Using LonWork
network
PI 485(PQNFP00A01) Multi V

LON
GW PI 485(PHNFP14A01) Duct

PI 485(PMNFP14A0) MPS

LON
GW
PI 485(PHNFP14A01)
CST

695 Others
5CIM0-04D BMS Gateway

3.4.3 Detailed wiring diagram

power line

Outdoor Main PCB


Bus_A

ON KSDO4H

L1 2 3 4
Bus_B
CN_CENTRAL PMNFP14A0

RS485 communication line

12V Adapter

3.4.4 Company supplied parts BMS


LG
Company

BD
Unit

indoor
Single
piping
Outdoor unit

LON gateway

Multi piping
indoor

Outdoor unit

Others 696
BMS Gateway 5CIM0-04D

3.4.5 Network Interface Connection

Select Air Select Network


Conditioner Type Type

ON KSDO 4H
ON KSDO4H

L1 2 3 4

* LGAP : LG Air conditioner Protocol

& MPS multi products.

ON KSDO4H
1 On, All others Off: & MPS Inverter product

ON KSDO4H
2 On, All others Off: MPS variable product

CAUTION

The wrong setting of air-conditioner switch causes malfunctioning of the whole system.
Switch setting must be done carefully.

697 Others
5CIM0-04D BMS Gateway

3.4.6 Addressing of Indoor Unit


• Addressing of Indoor Unit
Using wired remote controller 1. Press the Program & Set/Clr keys at the same time to activate the settings.
2. Set the indoor unit address using the temperature controller buttons.
AUTO SWING OPERATION SET TEMP
Room Temp
FAN SPEED SUB FUNCTION Allowed Range : 00 - FF
HI AUTO Heater Preheat
MED JET Defrost Humidify ex)
Time
LO
ZONE
Filter
1 2
Out door
3 4 3 A
Timer Operation unit Program set
On Off
Set no. Time 01 03 05 07 09 11 13 15 17 19 21 23

Group No. Indoor unit No.

Timer Cancel

3. To complete the address setting, press the Program & Set/Clr keys at the
Program Week Holiday
Program Plasma same time for 3 seconds.
Set/Clr

Hour Min RESET

Set/Clr

Using wireless remote controller

A. Address setting mode


1) Keep pressing upper left side key continuously and press RESET button once.
Now the system is ready for address setting.(The left key should be pressed
over 3 seconds)
2) Set the indoor unit address using the temperature controller buttons.
Allowed Range : 00 - FF
Address ex)
check
3 Group No.
Address
ON OFF setting A Indoor unit No.

SET CANCEL

PLASMA 3) After setting address, press ON/OFF key once towards indoor unit.
4) The indoor unit shows the set address and it means completion of address
setting process. (The address displaying time and its way can depend upon
the type of indoor unit )

B. Address check mode


1) Keep pressing upper right side key continuously and press RESET button
once. Now the system is ready for address checking.(The right key should be
pressed over 3 seconds)
2) Press ON/OFF key once towards the indoor unit which shows set address on
the display(The address displaying time and its way can depend upon the type
of indoor unit )
3) Reset the remote controller to use it in the normal operation mode.
❈ Some remote controllers may not be supported by above functions according to the production date of wired/wireless
remote controllers. As it has no concern with customers’ use, use the remote controller available for the address setting
during installation.
❈ It would be added how to set address of the simple central-control indoor unit.

Others 698