Abstract
The purpose of this study was to evaluate the floor impact sound isolation systems in reinforced concrete constructions.
The floor impact sounds were generated by the standard heavy-weight impact sources, a tyre drop tester1 and an impact
ball2. The noise and vibration from the impact sources were analyzed and the relationship between the sound levels and the
subjective responses was investigated. From the different residential building structures, it was found that heavy-weight
floor impact in a box frame-type concrete structure3 readily transmits sound to the space below through the bearing walls,
whereas the non-bearing walls of a rahmen structure4 do not readily transmit sound. It was also observed that a linear
relation exists between floor impact sound and vibration. In addition, when the noises were evaluated in in-situ conditions,
the allowable sound levels were found to be 46dB for the tyre drop tester and 54dB for the impact ball.
1
Tyre drop tester (Bang machine): Weight – 7.3±0.2kg; air-pressure level – (2.4±0.2)×105Pa; drop height – 85cm (KS A 2810-2 & JIS A 1418-2)
2
Impact ball: Weight – 2.5±0.1kg; drop height – 100cm (JIS A 1418-2)
3
Box frame-type concrete structure: Structural system which is structurally supported by the reinforced concrete wall.
4
Rahmen structure: Structural system which is structurally supported by the reinforced concrete column and beam.
631
Proceedings of ACOUSTICS 2004 3- 5 November 2004, Gold Coast, Australia
All measurements and recording were made in a generated by impact ball. We reproduced the situation
reinforced concrete structure four-bedroom apartment such that an adult (in 20s, 65-70kg) walks on the spot
(140m2). Eight units of the apartment were selected for instead of running and jumping children.
floor impact noise measurements. Measurements were
Auditory Experiments
made after the completion of construction and before
occupants moved in. The floor structures of eight units Electrostatic headphones were used for the binaural
consist of one standard floor that was maintained as an hearing experiment. Auditory experiments were
original structure and seven other structures that were performed in a testing booth that had approximately 25
constructed under different conditions for reducing floor dBA of background noise. Auditory experiments
impact noise. consisted of two experiments: one was on the loudness of
Table 1 shows the structural components and details. the floor impact noises and the other was on the
For example, 'P' indicates a plain reference structure and annoyance of the floor impact noise.
the treatments in the structural components are indicated
as 'F' for the construction of a floating floor, 'W' for the
treatment in the walls and 'C' for the treatment in the
ceiling. Thus, 'FWC' indicates a box frame type structure
having all sound isolation treatments.
Field measurements and analyses of floor impact
noise were conducted according to JIS A 1418. The
light-weight impact (tapping machine) noise was
analyzed at the overall equivalent sound pressure level
(Leq) and the heavy-weight impact (bang machine and
impact ball) noise at the maximum sound pressure level
(Lmax). The test results shown in this paper comply with
KS F 2863 & JIS A 1419; (L'n,AW, the inverse A weighted
normalized impact sound pressure level for light weight
impact sound and Li,Fmax,AW, the inverse A weighted (a) Light-weight impact noise
impact sound pressure level for heavy-weight impact
sound) which has a different curve of reference values for
impact sound (Octave band). KS F 2863 & JIS A 1419
states that light-weight impact noise must not exceed an
equivalent sound pressure level (Leq) in the frequency
range of 125-2,000Hz and heavy-weight impact noise
must not exceed a maximum sound pressure level (Lmax)
in the frequency range of 63~500 Hz.
Table 1. Details of treated conditions with different
sound isolations
Structural
Structural details (mm)
components
Reinforced concrete slab150 + Impact Isolator 10 + (b) Heavy-weight impact noise
Floor
Light-weight Concrete 80 + Cement Mortar 50 +
(F)
Papered Floor*
Concrete retaining wall 180 + Plaster bond (air
Wall
gap) 5 + Sound Isolation (Rubber) Sheet 2 +
(W)
Gypsum Board 9.5+ Wallpaper
Reinforced concrete slab 150 + Vibration
Ceiling Absorbing Hanger & light-weight steel ceiling
(C) structure 230 + Sound Isolation (Rubber) Sheet 2
+ Gypsum Board 9.5 + Wallpaper
* 2mm waxed paper covered as a traditional floor finish
632
Proceedings of ACOUSTICS 2004 3- 5 November 2004, Gold Coast, Australia
The subjective and category scale values were height of the bang machine tyre from 30-120cm. The
calculated from the subjects' responses to loudness and impact force of the impact ball was varied by varying the
annoyance differences. Figure 1 (a) illustrates that the free drop height from 20-200cm. As shown in the Figure
loudness and annoyance of light-weight impact noise 2, the center of the upper room was impacted by the bang
from F, FW and FWC treated structures were lower than machine and impact ball. The impact sound levels were
that produced by C and FC treated structures. When F, measured at the center of the lower room at a height of
FW and FWC were compared with P, they were 1.2m and the vibration acceleration levels were measured
evaluated on the subjective loudness scale at a value of on the slab and beneath the slab. The vibration
about '-1', which means a 'clear difference in accelerometer on the slab was used for a trigger signal
loudness'. Thus, the impact sound level of the floating and sound and vibration acceleration levels were
slabs (F, FW and FWC) represented a reduction of more measured 5 times and averaged.
than 5dB. FWC showed the maximum improvement in
both impact sound level and subjective and category Driving force
scale values (loudness and annoyance).
In Figure 1 (b) and (c), W, FW, WC and FWC
Ref. signal
structures were found to be effective treatments for
loudness and annoyance of heavy-weight impact
Floor system
noise. Although the reduction of the impact sound level
of the structures was less than 5dB, the subjective and
FFT Analyzer PC
category scale values indicated that these treatments had Acc. signal (PULSE, B&K)
a considerable effect on loudness and annoyance of
heavy-weight impact noise. FW and FWC also showed
considerable improvement in light-weight. Thus FW
seems to be the most effective treatment. Therefore, for Mic. signal
objective and subjective improvement of floor impact
noise, box frame-type reinforced concrete buildings need
sound isolation treatments in both floors and walls. An Figure 2. Experimental apparatus to measure the floor
effective method of sound and vibration isolation for impact sound and vibration simultaneously.
ceiling should be further developed.
The subjective responses of annoyance to both the
In the bang machine experiment, the impact force of
light-weight and heavy-weight floor impact noise levels
the bang machine varied with the air pressure level of the
should be lower than a subjective magnitude '4' to avoid
tyre and the height of drop. The impact force of the
annoyance. However, as shown in Figure 1, the category
impact ball can be varied by the drop height. The
scale value of annoyance is 5.8~8.6 for the light-weight
relationship between impact sound pressure level and
impact noise and 3.8~7.6 for the heavy-weight impact
vibration acceleration level for the bang machine and the
noise. These results indicate that only FWC could satisfy
impact ball are shown in Figure 3.
the annoyance level of heavy-weight impact noise below
the subjective magnitude '4'. Therefore, uncarpeted
98
floors need better sound isolation treatments such as
carpeting. 96
Impact sound pressure level [dB]
94
88 1.8 kgf/
In order to reduce the structure-born sound such as 86
y = 1.0171x + 0.8145 2.2 kgf/
2
floor impact sound in a multi-storey reinforced concrete R = 0.995 2.4 kgf/
84 2.6 kgf/
residential building, it is necessary to identify the 3.0 kgf/
relationship between floor impact sound and vibration. 82 impact ball
In this study, sound and vibration characteristics of a 80
bang machine and an impact ball at various impact forces 80 82 84 86 88 90 92 94 96 98
Acceleration [dB, ref=10-5m/s2]
were measured. The slab consisted of a 150mm thick
concrete slab, a 10mm thick resilient impact isolator, a Figure 3. Relation between floor impact sound and
55 mm light-weight concrete layer and 45 mm thick layer vibration levels using bang machine and impact ball.
of finishing mortar. The compressive strength of the
concrete was 240kg/cm2. The experimental results show a linear relationship
The impact force of the bang machine was varied by between overall floor impact sound level and vibration
varying the air pressure level of the bang machine tyre acceleration level despite the various floor impact forces.
from 1.8 to 3.0kgf/cm2 and by varying the free drop Therefore, a reduction of floor impact sound level can be
633
Proceedings of ACOUSTICS 2004 3- 5 November 2004, Gold Coast, Australia
achieved by reduction of the floor impact vibration easily transmitted to lower rooms through walls in the
acceleration level. box frame-type residential buildings because the
reinforced concrete walls between households were
The Floor Impact Sound in structurally coupled to the slab. However, the walls in
rahmen residential buildings in Korea are usually
Rahmen Structures constructed of dry wall which is not structurally coupled
with slab. Even in the rahmen structure residential
It has been reported that there is a limit for buildings, 2dB floor impact sound level differences
improving heavy-weight impact noise isolation between rooms which were constructed with dry walls
performance of the box frame-type reinforced concrete and rooms which had a wall constructed with structurally
residential buildings to meet the regulation of the coupled concrete wall were observed. The second and
Ministry of Construction and Transportation in Korea third reasons were the difference of structural system and
(MOCT). The floor impact sound levels in the regulation air space in ceiling.
are shown in Table 2. In order to improve the heavy-
weight impact noise isolation performance, improvement
Wooden floor 10mm
in structural systems such as increasing concrete slab Finishing mortar 40mm
thickness and application of rahmen structure have been Light-weight Con’c 70mm
Con’c slab 150mm
proposed [14]. Wide Beam GG
(1,000 X 430) Air space 530mm
Table 2. The regulation on the floor impact sound levels
Light-weight steel ceiling structure
in Korea
Light-weight Heavy-weight
[dB] Ceiling height 2,400mm
impact sound impact sound
(Tapping machine) (Bang machine)
Regulation of
58 (L'n,AW) 50 (Li,Fmax,AW5)
MOCT
GG
In this study, floor impact sound levels from ten
apartments in two rahmen structure multi-storey
residential buildings were measured prior to the tenants (a) Rahmen 1
moving in. Figure 4 shows the structural section of two
rahmen structure multi-storey residential buildings. In Wooden floor 10mm
GG
the rahmen structure residential building, the intra- Finishing mortar
Light-weigh Con’c 50mm
tenancy walls were dry wall and the inter-tenancy walls Con’c slab 230mm
were constructed as concrete walls. Measurements were Wide Beam
GG
made in the living room and two bedrooms at each (1,400 X 380) Air space 410mm
apartment when the finishing treatments processes were Light-weight steel ceiling structure
finished.
Table 3 shows the floor impact sound levels in the
rahmen structure residential buildings which were Ceiling height 2,250mm
averaged values of sixteen and twelve rooms at each site.
The average value of light-weight impact sound level
from the two sites was 56dB (L'n,AW). The heavy-weight
impact sound level was 44dB (Li,Fmax,AW) and the impact
sound level of the impact ball was 41dB (Li,Fmax,AW). The GG
634
Proceedings of ACOUSTICS 2004 3- 5 November 2004, Gold Coast, Australia
75 75
Table 3. Floor impact sound levels in rahmen structure Not annoying Annoying Very annoying
residential buildings 70 70
635
Proceedings of ACOUSTICS 2004 3- 5 November 2004, Gold Coast, Australia
In this study eight floor impact noise isolation [6] K. Gösele, “Zur bewertung der schalldämmung von
structures were evaluated objectively and subjectively. bauteilen nach sollkurven, ” Acustica 15, pp.264-270,
The results show that the objective and subjective 1965.
improvement of floor impact noise in box frame-type [7] W. Fasold. "Untersuchungen über den verlauf der
reinforced concrete buildings need sound isolation sollkurve für den trittschallschutz im wohnungsbau,"
treatments in both floors and walls. In addition spatial Acustica 15, pp.271-284, 1965.
factors of the floor impact noise should be taken into [8]D. Olynyk and T. D. Northwood, “Subjective
consideration for the subjective improvement of floor judgments of footstep-noise transmission through
impact noise [17]. floors,” J. Acoust. Soc. Am., 37, pp.1035-1039, 1965.
The results of the floor impact sound and vibration [9] D. Olynyk and T. D. Northwood “Assessment of
measurement results show that a linear relationship exists footstep noise through wood-joist and concrete
between overall floor impact sound and vibration floors,” J. Acoust. Soc. Am., 43, pp.730-733, 1967.
regardless of the various floor impact forces. From the [10] Federal Housing Admin, “Impact noise control in
different structures, it was found that heavy-weight floor multifamily dwellings,” FHA No,750, 1963.
impact in a box frame-type concrete structure is readily [11] K. Bodlund, “Alternative reference curves for
transmitted to the space below through the bearing walls, evaluation of the impact sound insulation between
whereas the non-bearing walls of a rahmen structure do dwellings,” Journal of Sound and Vibration, 102(3),
not readily transmit impact. pp.381-402, 1985
From the recent study on the comparison of [12] J. Parmanen, Comments and conclusions based on
frequency characteristics and subjective responses of the "Alternative reference curves for evaluation of the
three standard impact sources and actual human impact, impact sound insulation between dwellings," Journal
it was revealed that the noise from the impact ball was of Sound and Vibration, 213(4), pp.763-773, 1998.
similar to the noise of running and jumping children [18]. [13] J. Y. Jeon and J. H. Jeong, “Measurements of floor
When the noises were evaluated in in-situ conditions, the impact noise using a new impact ball,” Proc of
allowable sound levels were found to be 46dB for the Noise-Con 2003, 2003.
bang machine and 54dB for the impact ball. [14] S. H. Seo and J. Y. Jeon, “Noise and vibration
characteristics of the reinforced concrete slab
Acknowledgement impacted by heavy-weight source in an apartment
building,” ICA 2004, Japan: 2401-2402. 2004.
This work was supported by grant No. 03-1-11-2-002 [15] J. Y. Jeon, J. H. Jeong, M. Vorläder and R. Thaden,
from the core environment technology development “Evaluation of floor impact sound insulation in
project for next generation of the Korea Ministry of reinforced concrete buildings,” Acta Acustica Vol.
Environment. 90:313-318, 2004.
[16] J. Y. Jeon, “Subjective evaluation of floor impact
References noise based on the model of ACF/IACF,” Journal of
Sound and Vibration, 241(1): 147-155, 2001.
[1] H. Tachibana, H. Tanaka, M. Yasuoka, and S. [17] J. Y. Jeon, J. H. Jeong, and Y. Ando, "Objective and
Kimura, “Development of new heavy and soft subjective evaluation of floor impact noise," Journal
impact source for the assessment of floor impact of Temporal Design in Architectural and the
sound insulation of buildings,” Proc of Inter-noise Environment, 2(1):25-33, 2002.
98, 1998. [18] J. Y. Jeon, J. H. Jeong, "The use of the impact ball in
[2] H. Fukusima, A. Hattori, J. Yosimura, K. Inoue and evaluating floor impact sound, " Proc of Inter-noise
M. Yasuoka, “Introduction to sound insulation 2004, 2004.
regulations in the Japanese new law concerning the
labeling system and the system for quality securing
about newly-built house, -Part:2-,” Proc of Journal
of the Acoustical Society of Japan, pp.753-754, 2000.
[3] A. Warnock, “Low frequency impact sound
transmission through floor systems,” Proc of Inter-
noise 92, 1992.
[4] A. Warnock, “Low frequency impact sound
transmission through floor systems,” Proc of Inter-
noise 2000, 2000.
[5] A. Wornock, “Low-frequency impact sound rating of
floor systems,” Proc of Noise-Control Engineering
Journal, 2000, p.2611, 2000.
636