TABLE OF CONTENTS
CHAPTER 1 SYSTEM OVERVIEW ········································································ 2
CHAPTER 2 APPEARANCE AND STRUCTURE ························································ 4
CHAPTER 3 FUNCTIONS AND PARAMETERS ························································ 5
1. Brief introduction of functions ············································································· 5
2. Performance parameter ····················································································· 8
CHAPTER 4 OPERATION PANEL OVERVIEW ························································ 9
CHAPTER 5 LCD OPERATION ···········································································10
1. User levels ··································································································· 10
2. Interface layout····························································································· 11
3. Keyboard and Indicators ·················································································· 13
4. User interface ······························································································· 15
CHAPTER 6 INTERLOCKING CONTROL PANEL ····················································32
1. Introduction ································································································· 32
2. Connecting diagram ······················································································· 33
3. Operation ···································································································· 34
CHAPTER 7 EXTINGUISHING PANEL ·································································35
1. Features ······································································································ 35
2. Diagrams ····································································································· 35
3. Operation ···································································································· 36
4. Installation and Commissioning ········································································· 37
CHAPTER 8 DETECTING AND REPAIRING ··························································38
1. Daily Examining ··························································································· 38
2. Trouble-shooting Guideline ·············································································· 38
3. Replaceable element table ·············································································· 41
4. Reclamation ································································································ 41
CHAPTER 9 SCHEMATIC DIAGRAM OF CONNECTING WIRES IN CONTROLLER ········42
1. Schematic diagram of wires connection ······························································· 42
2. Points to note ······························································································· 42
evenly districted.
Effective distance of B-Bus with twist pair wire (Φ≥1.0mm2) is 1,00m.
F-Bus is two wires with polarity free. Use of flame retardant twisted pair with Φ≥1.0mm2 is
recommended. Transmission distance reach up to 1,000m. All devices should be evenly districted.
Controller has three kinds of user interfaces, which are Level 1 user interface, Level 2 user
interface and Level 3 user interface. Different operations can be carried out under different user
interfaces.
Insert connection is adopted for all connecting wires, which makes installation, commissioning,
maintenance and repair convenient and fast.
Anti-EMI.
Controller can adjust detection sensitivity and automatically adapt to environmental changes, thus
greatly improve fire alarm reliability.
Both direct on-site programming on controller and fast programming through computer are
available.
Configuration file inside controller can be uploaded to computers via USB.
(in:mm)
Fault alarm
To ensure reliability of the fire alarms, the control unit will check all field devices and detection bus when
the system runs normally. When fault happens, the “Fault Alarm” light will be on, system will issue a
sound and the display screen will automatically switch to the fault window to display the relevant fault
information. You can operate menu by keyboard on panel. For detailed information, please refer to
chapters 4 and 5.
When there is a certain fault in the system and it is not recovered, it will affect the fire alarm priority
function. In the application, the following attention should be paid:
Fire alarm can not be made normally in places where detector is damaged
Bus is faulty. (such as bus is open or short)
Power supply fault
Edit parameter
Set device parameters, including the address number, type, alarm threshold and address description of
field devices. Refer to the chapter on operations.
)
8-line input and output
(O/I
+28V GND
Schematic Diagram of Connection Between 8-line Collective Interlocking Control and On-Site Device
2. Performance parameter
Items Parameters
Dimension 700×520×120mm
is the operation display panel (BT8002): located in the upper part of controller.
BT8002 is used for manual operation, information entry and information display.
BT8002 includes LCD screen, indicators, keyboard, and buzzer.
is multi-line interlocking panel (BT8011): located in the lower part of controller.
BT8011 is used for automatic control or manual operation of important equipment (such as pump
and fan).
BT8011 has a total of 8 channels of outputs which are used to control on-site fire control
equipment. Output capacity: 28VDC /40mA. It has 8 channels of contact input which are used
for receiving confirmation signals coming from activated field devices, while the other 8
channels are reserved.
is printer: located in the lower left part of controller.
When fire alarm, fault or interlocking event occurs, printer will automatically print the type, user
text of the event and year, month, day, hour, minute and second.
1. User levels
BC8002 includes three user levels. The user level displayed at the right corner of the screen (Fig.1).
Level 1: any personnel
Level 2: operator on duty
Level 3: commissioning, maintenance and repair personnel
Different user levels have different authorizations and user interface options are also different.
The default user interface of system is Level 1. Corresponding password needs to be entered to log
in Level 2 and 3 user interfaces.
Under Level 2 and 3 user interfaces, if no operation is performed by the user and no event occurs
within the pre-set time, the system will automatically switch to level 1 interface.
If no operation is performed by the user and no event occurs within 2 minutes, the LCD back light
will be automatically turned off. By pressing any key, the user can light up the LCD display.
2. Interface layout
:
First alarm 2002-09-06 09:08:47 002 St Main board input output 03
Fire alarm Signal threshold 03001004
Fire alarm input 03001001 001 Start Main board input output 03
Follow-Up fire alarm Technical input 03001003
03
0 0 2 2 0 0
Fig.2 Interface
Different menus are displayed when different user interface levels are logged in.
When the ”Event Viewer” option is selected, the information of the alarm equipment will be
displayed.
Alarm equipment includes: detectors, input modules, manual call points and main board input.
When the “Fault Viewer” option is selected, the fault information of field devices will be displayed.
Current state is displayed based on priority class, which is arranged in a descending order: fire
When the fire alarm window is selected, the activation/confirmation information of the passive
equipment is displayed. .
Passive equipment includes: output module, main board I/O, interlocking panel I/O.
When the fault window is selected, the fault information of the faulty equipment is displayed. .
Current state is displayed based on priority class, which is arranged in a descending order: fire
When there is no alarm and fault, the system will automatically return to the initial view.
control system.
The area 3 includes 12 indicators, arranged in the top-to-bottom order as: System fault, Fault,
Active, Confirm, Main power, Battery, Isolation, Test, Automatic, Manual, Silence and Reset.
System fault: When system hardware or software can not work normally, the indictor is on.
Fault: When fault occurs, the indicator is on. After all the faults are removed, the indicator
will be off.
Active: When there is equipment (such as output module or output port on main board) is
activated, the indicator is on. When system is reset, the indicator will be off.
Confirm: When controller gets a confirmation signal from an activated device, the indicator is
Main power: When the main power provides power for controller, the indicator is on. When
Battery: When the built-in batteries are being used, the indicator is on.
Test: When there are devices being tested, the indicator is on.
indicator is on, all the interlocking devices can be controlled by controller according to the
logic relationship..
Manual: the button can only be used in level 2 and 3 user interfaces. When the indicator is on,
all the interlocking devices can be controlled according to manual operation. Automatic
Silence: When events occur, the indicator will flash. After the silence button is pressed, alarm
stops and the indicator is on. After all the events have been removed, the indicator will be off.
Reset: the button can only be used in level 2 and 3 user interfaces. When the button is
pressed, the controller will eliminate alarm and reset the activated device to the normal
mode.
The area 1 is a fire alarm indicator. Under the normal mode, the fire alarm indicator
is off. When there is fire alarm, the indicator lights up. After all the fire alarm evens
are eliminated, the fire alarm indicator turns off.
2 is the keyboard.
The upper part is a digit zone. Digit buttons are used to enter digits and text.
The middle part includes C and OK keys. C key is used for cancel and return,
while OK key is used for confirm and enter.
The lower part includes the direction keys and key. The direction keys offer the
choice of up, down, right and left direction, while key is a menu selection key.
4. User interface
Type of interface:
BC8002 includes three kinds of user interfaces: Level 1,Level 2 and Level 3 user interface (as shown
in Figs. 3-1, 3-2 and 3-3). Different users can respectively log into different user level interface.
Login method:
Level 1 user interface:
◘ This is the default interface of the system. In other
View Operation Node Query Tools Help
words, it is the initial view without any operation after ...☺ 西门子
BrowserViewer
. .
. SIEMENS R&D Building
EventViewer
the controller is switched on. .
Fault Viewer
Logout
◘ If the current interface is level 2 (3) user interface,
EventViewer
direction keys to select “Login” → press OK key . 主楼
FaultViewer
. .
SIEMENS R&D Building
EventViewer
key to enter the “View” option→ press the direction . 主楼
FaultViewer
5. Operation
Tool bar
1. Items expressed only in text are displayed in Level 1, 2 and 3 user interfaces. For example:
“EventViewer”
2. Items in bold face and being underlined are only displayed in Level 2 and 3 user interfaces. They will
not be displayed in Level 1 user interface.
i. For example:“BrowserViewer”
3. Items in bold, being underlined and in shade are only displayed in Level 3 user interface. They will
not be displayed in Level 1 or 2 user interface.
i. For example:“Edit parameter”
4. “Record” items can only be displayed when “Historical record” items are opened.
Entry method:
View Operation Node Query Tool Help
Press key → cursor stays at the “Tool Bar” by default. BrowserViewer
Fig.4-1 Tool
5.1 View
Functions:
Used for switching to different browse view, log into (Log out) level 1, 2 and 3 user interface.
Entry method:
View Operation Node Query Tool Help
BrowserViewer
Press key → enter “View” option → press the direction
EventViewer
keys to select the desired item → press Ok key to confirm FaultViewer
Log in
enter or C
key to cancel and return (as shown in Fig.4-2).
Drop-down option:
node.
Login (Logout)
:Log into Level 2 and 3 user interface(return to Level 1 user interface)
5.2 Operation
Functions:
Perform corresponding operations on lines and devices, including isolate, open, activate, stop, test,
walktest, normal.
All controllers, lines and devices can be displayed in the tree structure.
Operable options may be different from different types of nodes. Specific items are listed
below.
Operable No
Walk
options Isolate Open Activate Stop Test Normal Operational
test
Type of Nodes Items
Controller √
Mainboard I/Os √ √ √ √ √ √
Line √ √ √ √ √
Field devices √ √ √ √ √ √
Interlocking panel √ √ √ √ √ √
Extinguishing panel √ √ √ √ √ √
Power supply √
. .
SIEMENS R&D Building
主楼
. Activate
point → press key → press the direction keys to Stop
Test
select the pull-down menu of “Operation” → press the WalkTest
Normal
Fig.4-3
key to confirm or C key to cancel (as shown in Fig.4-3).
Drop-down option:
Isolate
◘ Functions: Set open points as an isolation state. If points are successfully isolated, the
controller will concurrently issue a prompt sound. View Operatio Node Quer Tools Help
...☺ Isolate
◘ Setup method:
. .
. Open
SIEMENS R&D Building
. 主楼
Activate
In the tree structure, press the direction keys to Stop
Test
WalkTest
select a point → press key→ press the direction
Normal
◘ System prompt:
If a point has been set as isolation state, the symbol to the left of the name of the node will be
displayed as “”.
◘ Isolated area:
When individual point is selected to be isolated, only the selected one will be isolated. If a line
is selected to be isolated, all the devices connected on the line will be isolated.
◘ Setup method:
View Operation Node Quer Tools Help
. .
Open
SIEMENS R&D Building
as Fig.4-5).
◘ System prompt:
If a isolated point is set as normal working state, the symbol to the left of the name of the point
will displays ☺ .
◘ Open area:
When an individual point is selected to be open, only the selected point will be opened. If a line
is selected to be opened, all the points connected on the line will be opened.
Activate:
◘ Functions: Activate all the equipment that is linked up with the output modules/ports selected
. Open
SIEMENS R&D Building
In the tree structure, press the direction keys to . 主楼
Activate
Stop
Test
select interlocked devices → press key →
Walk Test
Normal
press the direction keys to select the pull-down
as in Fig.4-6).
◘ Setup method:
View Operation Node Quer Tools Help
. .
. Open
SIEMENS R&D Building
. 主楼
Activate
select interlocked devices → press key → Stop
Test
press the direction keys to select the pull-down WalkTest
Normal
menu of “Operation” →press the direction keys to
Fig.4-7 Stop
select “Stop”→ press OK key to confirm enter
(shown as in Fig.4-7).
Test:
◘ Function: Under the test state, all devices issues alarm normally and simulate interlocking but
. .
. Open
SIEMENS R&D Building
In the tree structure, press the direction keys to . 主楼
Activate
Stop
select a point → press key → press the Test
WalkTest
direction keys to select the pull-down menu of Normal
shown in Fig.4-8).
Walk test:
◘ Function: In the walk test state, all equipment can issue alarm normally and but no real
interlocking. In the walk test process, the user can set the walk test time (time setup is in the
“Edit parameter” option). When the pre-set time is exceeded, the controller will automatically
remove to normal working status and eliminate all the test events.
. .
. Open
SIEMENS R&D Building
select a node → press key → press the 主楼
. Activate
Stop
Test
direction keys to select the pull-down menu of WalkTest
Normal
“Operation” → press the direction keys to select
OK Fig.4-9 Walk Test
“ Walk Test” → press key to confirm enter (as
shown in Fig.4-9).
Normal:
◘ Function: return to the normal state from test status or walk test status.
No switchover between test and walk test state. View Operatio Nod Quer Tool Help
...☺ Isolate
. .
◘ Setup method: . Open
SIEMENS R&D Building
主楼
. Activate
In the tree structure, press the direction keys to Stop
Test
WalkTest
select a point → press key → press the
Normal
shown in Fig.4-9).
5.3 Node
Function:
Display “Property”, “Analog Curve”, “History” and “Edit parameters” and “Modify logic expression”
In the tree structure, press the direction keys to select a ☺ Siemen Property
.....
..
Analog
SIEMENS R&D curve
Building
History
node → press key → press the direction keys to Edit Para
Modify Logic
enter the pull-down menu of “Node” → press the direction
key to confirm and enter or C key to cancel and exit. (as Fig.4-11
shown in Fig.4-11)
Analog curve: For the detector, the system displays real time analog parameter changes.
History: Display all the events that have occurred at the node.
When the “History” option is entered for the first time, the tool bar will change, with the
“Record” column added. Meanwhile, all the historical records of the selected equipment will be
.. ..
.. SIEMENS R&D Building
Fault
pull-down menu of “Node”→ press the direction keys .. Main Alarm
Control
Isolation
to select “History”→ press OK key → press the
All: Display all the historical records of selected point, which have occurred.
Notes: After operators choose one of options mentioned above, a “Time Segment” frame will
turn up. The function of the frame is setting the checking period.
◘ Time setup
Setup method:
Time Segment:
Use digit keys to enter the query time and press the up
Date Hr
and down direction keys to switch over between Fr 2005-09-04 14
.. ..
..
Pinyin SIEMENS R&D Building
.. 主楼
“Selection” appearing on the top of LCD. Choose “OK” OK
Cancel
to confirm and “Cancel” to quite. (shown as Fig.4-14).
Edit parameter:
◘ Functions:
Modify address, text (name), type and other parameters of a selected node or panels.
1. For different nodes, there will be different interfaces for parameter editing.
2. After the “Edit parameter” option has been selected, the screen enters a text edit state. At
this time, the bus address, text (name), type of the selected node are displayed (there are
Under the text edit state, there is only the “Selection” menu on tool bar.
Select:
Method for using digit keys to input letters: press down digit keys → then, the entered
items are mutually converted between digits and letters→ when the converted item is the
content to be entered, release keys→ complete the entry of the needed characters→ press OK
- Hold down the digit keys (2-9): the entered items mutually convert between digits and
letters;
- Hold down the digit key (1) : the entered items mutually convert between the digit 1,
- Hold down the digit key (0): the entered items mutually convert between the digit 0,
‘<’ and ‘>’. When it is respectively changed to‘<’ and ‘>’, quit hold of the key and it
shows that the entered letters are respectively in block and low-case letters. When
block letters are entered, an upward arrow on the right low corner of the screen will
appear as prompt
At the time of editing, if wrong entries are made, C key can be used to cancel the
wrong characters.
If the text editing window only has the pull-down option to select, then press the
rightward direction key to open the pull-down menu and then use the direction key to
select an item.
OK: Save changes in the short term and exit from the “Edit parameter” mode.
Cancel: Do not save changes and exit from the “Edit parameter” mode。
◘ Special specifications:
Under the “Edit parameter” state, changes can only be saved in the short term. After the system
restarts or closed down, short term saved data will get lost. Therefore, users are recommended
to save their changes in the long term. Method for long-term saving: Under the text editing
state, press “OK” for short-term saving → log into level 3 user interface → press
key in level 3 user interface → press the direction keys to select “Tool” → press the
direction keys to select “Save Config” → press OK key to confirm and enter.
Modify Logic :
◘ Function:
View Operatio Nod Query Tool Help
To compile and modify the interlocking relation of a node.
☺Sieme Property
..... SIEMENS
..
Analog
R&D Building
After the “Modify Logic” option has been selected, History
Edit Para
Modify Logic
the screen enters a text editing state. Under it,
◘ Modification method:
Enter the “Modify Logic” option→ interlocking relation is displayed on the left side of the
screen→ press digit keys and direction keys to modify interlocking relation → press key→
enter the pull-down menu of “Selection” → press the direction keys to select “OK” to save and
When wrong entries are made, C key can be used to delete it.
5.4 Query
Function: Query the node under a certain status and display it in the browse view.
Entry method:
Press the direction keys to select a node in the tree View Operatio Nod Quer Tool Help
...☺ Siemen Isolation
.. ..
Fig.4-17
key to confirm and enter or C key to cancel and exit
Drop-down options:
Isolated Devices: Query address of the isolated devices and display its property.
Fire Devices: Query address of the fire devices and display its property.
Fault Devices: Query address of the fault devices and display its property.
Activate&Answer : Query address of the activated devices and display its property.
Bus Fault Devices: Query the bus address of communications fault.
Test Devices: Query address of all tested equipment and display its property.
Walk test Devices:Query address of all walk tested devices and display its property.
5.5 Tools
Functions:
Set time, check system state, adjust LCD brightness and the sound volume of equipment’s alarm,
Entry method:
Vie OperationNodeQuery Tool Help
Press key → press the direction keys to select the ...☺Sieme Set time
.. ..
.. SIEMENS R&DCheck
pull-down Menu of “Tool” → press the direction keys to .. Main Adjust LCD
Adjust Buzzer
Save Config
select the item to be set up → press OK key to confirm Automap
Set time :
◘ Function: Set system time. View OperationNode Query Tools Help
...☺ Siemen Set time
◘ Setup method:
.. ..
.. SIEMENS R&D Building Check
.. Main Adjust LCD
Press key → press the direction keys to select brightness
Adjust Buzzer
Save Config
Automap
the pull-down menu of “Tool” → press the
- Press digit keys to input the time and date in the corresponding window. The format to
controller will inform all the other controllers to adjust time based on the current
controller time.
check System :
◘ Function:
Check the working state of indicators, sound system, LCD and printer.
◘ Setup method:
View OperationNode Query Tools Help
Press key → press the direction keys to select ...☺ Siemen Set Time
.. ..
Check criteria:
Indicator — The normal state is that all the indicators are on. If a indicator is not on, it means
Sound—The normal state is buzzer issues all (four) kinds of sounds. If some tune cannot be
Screen—The normal state is all the screen areas are displayed normally.
Printer —The normal state is that the printer will print” printer is OK” automatically.
Adjust LCD
◘ Setup method:
View Operation Node Query Tools Help
Press key → press the direction keys to select ...☺ Siemens Set Time
.. ..
◘ Special specifications:
Brightness adjustment is cyclic setup. That means, when the adjusted value reaches the
maximum value (minimum value) set by the system, it continues to make adjustment. The
value will automatically return to the minimum value (maximum value) set by the system.
Adjust buzzer :
◘ Function: Adjust controller’s buzzer volume.
.. ..
.. SIEMENS R&D Building
Check System
.. Main Adjust LCD
the pull-down menu of “Tool” → press the brightness
Adjust Buzzer
Save Config
Automap
direction keys to select “Adjust buzzer” → sound
◘ Special specifications:
Press up direction key, volume is increased; Press down direction key, volume is decreased.
.. ..
◘ Function: Save various modifications for long time .. SIEMENS R&D Building
Check System
.. Main Adjust LCD
brightness
Adjust Buzzer
◘ Setup method: Save Config
Automap
Press key → press the direction keys to
Automatic map :
◘ Function:
Automatically map all the devices connected in the line to the controller.
◘ Setup method:
View Operation Node Query Tools Help
Press key → press the direction keys to ...☺ Siemens Set Time
.. ..
Fig4-24 Automap
5.6 Help
Function: Display software version, download time and modification time.
Siemen About
Press key → press the direction keys to select the ☺
.. ..
..... SIEMENS R&D Building
.. Main
pull-down menu of “Help” → press the direction keys to
1. Introduction
BT8011/BT8012 interlocking control panels are used for automatic/manual control of important
equipment (such as pump and fan).
There are two kinds control signals can be chosen: Pulse and Level.
BT8011/BT8012 communicates with the controller through B-BUS. OC output controls external
equipment through relays.
All “activation”, “fault” and “confirmation” signals are displayed on the panel and there are
corresponding sounds prompt for them.
The functions of “test” and “silence” are available.
When the “Manual” light is on, it indicates manual operation is allowed. At this time, on-site
equipment can be activated/stopped by keyboard.
When the “Automatic” light is on, it indicates automatic operation is allowed. At this time, the
controller is allowed to automatically interlock and control on-site equipment.
3U panel structure.
The first five digits of the Dip-switch define the address of the current interlocking panel. The sixth
digit is used to define whether the interlocking panel communicates with the controller through
B-Bus. The seventh and eighth digits define the output mode of the interlocking panel. Detailed
information is given in the table below:
2. Connecting diagram
3. Operation
1. Features
BC8013 extinguishing panel is used for extinguishing section control. It can be set at automatic
mode or manual mode. It is mainly applied for rooms stored with importance devices or
electronic materials (IT room or switch-board room etc.) and file rooms, libraries or other
rooms which need special protection.
One panel monitors 2 extinguishing sections, for each section, there are three outputs: output1,
output2, gas release and all activation will provide confirmation signals.
Can be connected via B-Bus, address set by Dip-switch, Information of extinguishing section
can be displayed on the control unit. The parameters of BC8013 extinguishing panel can be
configured by the control unit or downloaded from PC-tool.
Three kinds of activation/stop mode: automatic activation, manual activation and remote
activation/stop.
Operation can be done on the control unit or in the remote protected area.
External control wires are monitored automatically against the short circuit.
Auto mapping is possible for commissioning.
Fault is automatically detected and displayed on the panel.
2. Diagrams
Detection Bus
2
Remote Remote
K is a +24V Stop Activate
relay
+ - + - + - + - C1 MT300 MT300
B-Bus Power B-Bus Power
1RS 1RA 1D3 1D2 1D1 2RS 2RA 2D3 2D2 2D1
3 8 10 6
3 8 10
Field
3. Operation
Remote activate/stop
BC8013 extinguishing panel has two input terminals (RA& RS). RA is remote activation input
terminal and RS is remote stop input terminal. Generally remote activate/stop button is installed
on site. When fire occurs, the operator will judge if extinguishing devices is necessary to
extinguish fire. If it is, he will press the remote activation button immediately. The extinguishing
panel will be at extinguishing status and activates all kinds of alarm devices and extinguishing
devices. When the site people find that fire is under control and extinguishing devices is not
necessary any more, he press the remote stop button to stop extinguishing devices. The current
status is kept.
Emergency stop
At “manual” status, the “emergency stop” button can stop extinguishing command and the current
status is kept.
After finishing installation, don’t connect field devices and do the following check:
(1) Check all connection in the panel and 28VDC power supply, then switch it on.
(2) At normal status, press “Silence/Test” button to test panel; When buzzer is alarming, press
“Silence/Test” button to silence and LED is on. When emergency, fault or answer happens,
the LED flashes, to press “Silence/Test” button again, LED is on.
(3) Press “manual” button
press “auto” button
press “manual” button, then “manual” LED is
on and the panel is at “manual” status. At “manual” status, press “emergency activation”
button can carry out emergency activation command. At “auto” status, “emergency
activation” button is useless.
(4) “Auto” LED is on means the panel at “auto” status. If panels monitor more extinguishing
sections, each BC8013 should be given individual address.
(5) Remote activation/stop, to activate/stop extinguishing devices remotely by collective push
buttons.
(6) “Emergency stop” button is only available at “Manual” status. When you press the
“emergency stop” button, the LED will be on and block any activation which did not happen.
After finishing the above mentioned commissioning, connect field extinguishing devices into
terminals based on connection drawing. If check is passed, switch it on. Once field device is
connected to the panel. The following items should be noticed:
Not allow to do any alarm test at the “auto” status;
Not allow to set the panel as “manual” status at normal time;
Ensure “remote activation” button and “remote stop” button to be available and at non-
activation status.
Remark:
The panel must be checked and ensure all connection is correct, then switch it on;
the panel should be used and managed by specific person, any other person is not
allowed to operate it.
To be installed at dry place, avoid humidity.
Avoid shake and direct hit.
Ensure site activation/stop button at good status, avoid gas release by mistake.
Any problem should be handled in time and ensure panel at good working status.
Check panel manually at certain time.
Person on duty should do daily check of control unit, and take corresponding record on duty. If fire alarm,
failure and other abnormal events (control unit will have audio warning, indicator flashing and event
display) happen, “Requirements of Event Treatment” shall be followed, till the control unit restores to its
normal state. The record shall be well kept.
2. Trouble-shooting Guideline
4. Reclamation
For abandoned control unit, please contact local office of manufacturer to make proper treatment. Any
discarding of control unit random is strictly forbidden.
H H L H L H L H L H
SYNC H SYNC H A-BUS A-BUS B-BUS B-BUS
B-BUS
B-BUS
L L 电
L L □ 源
+
─
CPU CPU
BCC8002 Main board Connect with printer
BCM8001 BCM8001
Line card Line card
Signal line CPU
电 □─ 电 □─ Connect with display
源 + 源 +
F-BUS F-BUS 8-channel input/output
BT- BT+ - + - + - +
Power Power supply
2. Points to note
The diagram above is for reference use by repair and assembly personnel only. Non-repair personnel are
not recommended to dismantle internal connecting wires and components without permission.