BC8002 Advance Control Unit Operating Manual

BC8002 Advance Control Unit


Manual Operation
Operating Manual of BC8002 Advanced Control Unit

TABLE OF CONTENTS
CHAPTER 1 SYSTEM OVERVIEW ········································································ 2
CHAPTER 2 APPEARANCE AND STRUCTURE ························································ 4
CHAPTER 3 FUNCTIONS AND PARAMETERS ························································ 5
1. Brief introduction of functions ············································································· 5
2. Performance parameter ····················································································· 8
CHAPTER 4 OPERATION PANEL OVERVIEW ························································ 9
CHAPTER 5 LCD OPERATION ···········································································10
1. User levels ··································································································· 10
2. Interface layout····························································································· 11
3. Keyboard and Indicators ·················································································· 13
4. User interface ······························································································· 15
CHAPTER 6 INTERLOCKING CONTROL PANEL ····················································32
1. Introduction ································································································· 32
2. Connecting diagram ······················································································· 33
3. Operation ···································································································· 34
CHAPTER 7 EXTINGUISHING PANEL ·································································35
1. Features ······································································································ 35
2. Diagrams ····································································································· 35
3. Operation ···································································································· 36
4. Installation and Commissioning ········································································· 37
CHAPTER 8 DETECTING AND REPAIRING ··························································38
1. Daily Examining ··························································································· 38
2. Trouble-shooting Guideline ·············································································· 38
3. Replaceable element table ·············································································· 41
4. Reclamation ································································································ 41
CHAPTER 9 SCHEMATIC DIAGRAM OF CONNECTING WIRES IN CONTROLLER ········42
1. Schematic diagram of wires connection ······························································· 42
2. Points to note ······························································································· 42

Siemens Building Technologies 1/40


Operating Manual of BC8002 Advanced Control Unit

Chapter 1 System Overview


BC80 intelligent fire alarm series products adopt advanced fire detection technology and data
processing technology. These products integrate Siemens Building Technology many years of rich
experiences in the research, development and production of fire alarm products.

Intelligent smoke detector and electric heat detector


 The smoke detector is designed with patented optical labyrinth structure and ASIC, with
homogenous response to both black and white smoke.
 The fixed and rate-of-rise heat detector is designed with the latest technology thermal sensor and
specific circuit to achieve the reliability.
 Produced with modern SMT technology and automatic testing procedures to ensure high product
quality.
 Sensitivity can be adjusted via controller according to the environment condition.
 With the automatic offset feature against environmental changes, unwanted alarm has been
effectively avoided.
 Fully compatible with BDS Series’ field devices through BCM8001line card.

Large screen display controller with outstanding performance


 Large (10 inch) LCD display.
 Windows style menu for easy operation, interlocking information and alarm information are
displayed on different windows separately.
 Analog curve of each detection point is dynamically displayed on screen. Users can view changes
of fire parameters of each detection point at any time.
 Up to 1000 history events are recorded for checking.
 Controller is in a self-detection state to ensure that system works reliably and securely.
 According to controller configuration, when no event occurs within 2 minutes and with no other
alarms, interlocking or fault messages, controller will automatically switch to a screen protection
mode to prolong the LCD’s lifespan. When any events occur, the LCD will automatically light up and
controller will automatically display the events that have occurred and interlock the corresponding
equipment according to the logic relation.
 Modular structure allows users to order controllers and various internal functional cards according
to their actual needs.
 The main board of controller has 8 programmable input or output (software setting) to meet
certain special needs.
 Controller has an 8 multi-line interlocking panel (optional) which is used for automatic control and
manual operations of important equipment.
 Multi-line interlocking panel can be expanded to achieve automatic control and manual operation
of more field devices.
 A single wall-mount controller can monitor maximum 1,524 points. BC80 system can form a
network with 32 controllers and monitor up to 48,768 points.
 Effective distance of A-Bus with twist pair wire (Φ≥1.5mm2) is 1,000m. All devices should be

Siemens Building Technologies 2/40


Operating Manual of BC8002 Advanced Control Unit

evenly districted.
 Effective distance of B-Bus with twist pair wire (Φ≥1.0mm2) is 1,00m.
 F-Bus is two wires with polarity free. Use of flame retardant twisted pair with Φ≥1.0mm2 is
recommended. Transmission distance reach up to 1,000m. All devices should be evenly districted.
 Controller has three kinds of user interfaces, which are Level 1 user interface, Level 2 user
interface and Level 3 user interface. Different operations can be carried out under different user
interfaces.
 Insert connection is adopted for all connecting wires, which makes installation, commissioning,
maintenance and repair convenient and fast.
 Anti-EMI.
 Controller can adjust detection sensitivity and automatically adapt to environmental changes, thus
greatly improve fire alarm reliability.
 Both direct on-site programming on controller and fast programming through computer are
available.
 Configuration file inside controller can be uploaded to computers via USB.

Siemens Building Technologies 3/40


Operating Manual of BC8002 Advanced Control Unit

Chapter 2 Appearance and Structure

(in:mm)

 By structure, BC8002 fire alarm controller is wall-mounted.


 There are 4 fixed installation holes on the base board of standard wall-mounted controller.
Knockoff hole, to be used as outbound wire hole, is reserved in the middle of the upper part or in
the middle part of the bottom part.

Siemens Building Technologies 4/40


Operating Manual of BC8002 Advanced Control Unit

Chapter 3 Functions and Parameters

1. Brief introduction of functions


Fire alarm
BC8002 will alarm, when the fire is sensed by detectors connected with the system; when the manual
call point is activated or when the equipment connected with the input module issues a corresponding
action. When fire alarm, the “Fire Alarm” light will be on, system will issue an alarm and the display
screen will automatically switch to the fire alarm window to display the fire alarm information. You can
operate menu by keyboard on panel. For detailed information, please refer to chapters 4 and 5.

Fault alarm
To ensure reliability of the fire alarms, the control unit will check all field devices and detection bus when
the system runs normally. When fault happens, the “Fault Alarm” light will be on, system will issue a
sound and the display screen will automatically switch to the fault window to display the relevant fault
information. You can operate menu by keyboard on panel. For detailed information, please refer to
chapters 4 and 5.

Fire alarm priority


The system has the fire alarm priority function. That is, when the system is at fault status, fire alarm
happens and the system will automatically change from fault alarm to fire alarm. After the fire alarm is
removed, it will automatically switch back to the previous fault status.

When there is a certain fault in the system and it is not recovered, it will affect the fire alarm priority
function. In the application, the following attention should be paid:
 Fire alarm can not be made normally in places where detector is damaged
 Bus is faulty. (such as bus is open or short)
 Power supply fault

Real time clock


Real time clock contains year, month, day, hour, minute and second. When system is at fire alarm, fault
or close status, real time clock chip can still count time. Real time clock may also be preset and calibrated
through operating the menu “Set time”. (This function can be operated by Level 2 and 3 user levels).

Automatic printing (Optional)


When fire alarm or fault or interlocking event occurs, printer will automatically print event’s name, text
and year, month, day, hour, minute and second.

System event statistics


This function is to check controller’s hardware and field devices. The check results, including the total
numbers of fault, fire alarm, interlocking and confirmation events and isolated devices are displayed at
the bottom of screen.

Siemens Building Technologies 5/40


Operating Manual of BC8002 Advanced Control Unit

Isolation and opening of devices


In the process of system operation, if a field device has been damaged, it should be isolated before it is
replaced. After the replacement, it should be opened again.
When there are isolated devices in the system, the “Isolation” light on the panel will be on.

Display isolated devices


If a device is faulty in system, it should be isolated to ensure the normal running of the whole system.
The isolated device can be displayed so that a new device can be timely replaced. Through operating the
corresponding function key, the controller can display all the isolated devices.

Display analog curve of devices


Controller can display the analog curve of filed devices so as to allow users to check changes of fire
parameters of each detection point.

Query device property


After a device for query is selected, all the information about the device will be displayed on the screen,
including address, type, current status etc.

Query history events


Controller can automatically record all events, including fire alarm, fault, activation, confirmation,
isolation and so on. It can record maximum 1,000 events.

Edit parameter
Set device parameters, including the address number, type, alarm threshold and address description of
field devices. Refer to the chapter on operations.

Modify interlocking relations


Select one point and then edit and modify logic interlocking relations.

Main power and battery


In BC8002, back-up batteries are provided. When the controller is in use, the main power and battery
switches on the upper part of the power supply box should be turned on. When main power is on, the
controller will automatically use the main power and charge batteries at the same time. When the main
power is off, the controller will automatically use batteries as back-up power supply to ensure the normal
working of the system. When the main power is on, the “Main Power” indicator on the panel is on. When
the battery is on, the “Battery” indicator is on. During the period when the battery is on, the main power
fault is displayed. When the battery voltage is lower than 20VDC, the controller will shut down
automatically to prevent battery damage from overdischarge.

Input and output


Controller can provide 8-line programmable inputs and outputs. The capacity of output is 28VDC
/40mA.Wire connection is shown in the figure below.

Siemens Building Technologies 6/40


Operating Manual of BC8002 Advanced Control Unit

Controller B-BUS On-site device


8-line input and output
(O/I

I/O 8 I/O 2 I/O 1

+28V GND

Schematic Diagram of Connection Between 8-line Collective Interlocking Control and On-Site Device

Automatic and manual mode


There are automatic and manual buttons on the panel of the controller. They can be used to set the
controller as manual mode or automatic mode. Under the manual mode, the “Manual” indicator will be
on. Even if the logic relation is satisfied, the system could not activate the interlocking equipment. This
equipment can only be activated or stopped manually. Under the automatic mode, when the logic
conditions are met, the interlocked equipment will be activated automatically.

Siemens Building Technologies 7/40


Operating Manual of BC8002 Advanced Control Unit

2. Performance parameter

Items Parameters

Max. Line number 12 lines

Max. points per line 127 points

Main Power 220VAC(+10%,-15%), 50Hz

Sealed Leaded Acid Battery 12VDC,17AH×2


Power consumption under monitoring
40~100W
mode
Maximum power consumption under
40~150W
alarm mode

Fuse capacity AC:2.0A; DC:8.0A

Working temperature –10˚C ~ +50˚C


Relative humidity ≤95%

Dimension 700×520×120mm

Weight (without battery) 22.0Kg

Use place Use indoors

Siemens Building Technologies 8/40


Operating Manual of BC8002 Advanced Control Unit

Chapter 4 Operation Panel Overview




  is the operation display panel (BT8002): located in the upper part of controller.
 BT8002 is used for manual operation, information entry and information display.
 BT8002 includes LCD screen, indicators, keyboard, and buzzer.
  is multi-line interlocking panel (BT8011): located in the lower part of controller.
 BT8011 is used for automatic control or manual operation of important equipment (such as pump
and fan).
 BT8011 has a total of 8 channels of outputs which are used to control on-site fire control
equipment. Output capacity: 28VDC /40mA. It has 8 channels of contact input which are used
for receiving confirmation signals coming from activated field devices, while the other 8
channels are reserved.
  is printer: located in the lower left part of controller.
 When fire alarm, fault or interlocking event occurs, printer will automatically print the type, user
text of the event and year, month, day, hour, minute and second.

Siemens Building Technologies 9/40


Operating Manual of BC8002 Advanced Control Unit

Chapter 5 LCD Operation

1. User levels

Fire Acti Conf Isol Total


2 — — 0 2 User levels:
“1”Level 1 user
— 2 0 0 2
“2”Level 2 user
2 2 0 0
“3”Level 3 user

Fig.1 User Level

 BC8002 includes three user levels. The user level displayed at the right corner of the screen (Fig.1).
 Level 1: any personnel
 Level 2: operator on duty
 Level 3: commissioning, maintenance and repair personnel
 Different user levels have different authorizations and user interface options are also different.
 The default user interface of system is Level 1. Corresponding password needs to be entered to log
in Level 2 and 3 user interfaces.
 Under Level 2 and 3 user interfaces, if no operation is performed by the user and no event occurs
within the pre-set time, the system will automatically switch to level 1 interface.
 If no operation is performed by the user and no event occurs within 2 minutes, the LCD back light
will be automatically turned off. By pressing any key, the user can light up the LCD display.

Siemens Building Technologies 10/40


Operating Manual of BC8002 Advanced Control Unit

2. Interface layout

View Operation Node Query Tools Help

 :
First alarm 2002-09-06 09:08:47 002 St Main board input output 03
Fire alarm Signal threshold 03001004
Fire alarm input 03001001 001 Start Main board input output 03
Follow-Up fire alarm Technical input 03001003

002 Fire alarm Main board input output

03

Flammable gas 03001002 




Fault PreA Fire Acti Conf Isol Total 2005-8-10


Alarm Dev No:
Ctrl Dev No :
Total No:
0
0
0

2


2

0
0
0 2
2 15:10:06

0 0 2 2 0 0 
Fig.2 Interface

  is tool view: located at the top of the screen.


 Include view, operation, node, query, tools and help.

 Different menus are displayed when different user interface levels are logged in.

  is browse view: located at the left part of the screen.


 At 1 user level, only “Event Viewer” and “Fault Viewer” can be displayed. At 2 or 3 user level, node

list can be displayed.

 When the ”Event Viewer” option is selected, the information of the alarm equipment will be

displayed.

Alarm equipment includes: detectors, input modules, manual call points and main board input.

 When the “Fault Viewer” option is selected, the fault information of field devices will be displayed.

 Current state is displayed based on priority class, which is arranged in a descending order: fire

alarm → fault → isolation → normal.

  is display view: located at the right part of the screen.


 When a certain point in tree structure is selected (at 2 or 3 user levels), the corresponding state
is displayed in the display view, including: address, type, status and so on.

Siemens Building Technologies 11/40


Operating Manual of BC8002 Advanced Control Unit

 When the fire alarm window is selected, the activation/confirmation information of the passive
equipment is displayed. .

Passive equipment includes: output module, main board I/O, interlocking panel I/O.

 When the fault window is selected, the fault information of the faulty equipment is displayed. .
 Current state is displayed based on priority class, which is arranged in a descending order: fire

alarm → fault → isolate → normal.

 When there is no alarm and fault, the system will automatically return to the initial view.

• is statistics view: located at the bottom of the screen.


 Provide real time statistics of fire alarms, faults, activation, confirmation and isolations of fire

control system.

Siemens Building Technologies 12/40


Operating Manual of BC8002 Advanced Control Unit

3. Keyboard and Indicators

Fig.3 Keyboard and indicators

 1 and 3 are indicator areas.

 The area 3 includes 12 indicators, arranged in the top-to-bottom order as: System fault, Fault,

Active, Confirm, Main power, Battery, Isolation, Test, Automatic, Manual, Silence and Reset.

Among these 12 indicators, only the last 4 ones can be operated.

 System fault: When system hardware or software can not work normally, the indictor is on.

 Fault: When fault occurs, the indicator is on. After all the faults are removed, the indicator

will be off.

 Active: When there is equipment (such as output module or output port on main board) is

activated, the indicator is on. When system is reset, the indicator will be off.

 Confirm: When controller gets a confirmation signal from an activated device, the indicator is

on. After the signal disappears, the indicator will be off.

 Main power: When the main power provides power for controller, the indicator is on. When

there is no power supply, the indicator will be off.

 Battery: When the built-in batteries are being used, the indicator is on.

 Isolation: When there are devices isolated, the indicator is on.

 Test: When there are devices being tested, the indicator is on.

Siemens Building Technologies 13/40


Operating Manual of BC8002 Advanced Control Unit
 Automatic: the button can only be operated in level 2 and 3 user interfaces. When the

indicator is on, all the interlocking devices can be controlled by controller according to the

logic relationship..

 Manual: the button can only be used in level 2 and 3 user interfaces. When the indicator is on,

all the interlocking devices can be controlled according to manual operation. Automatic

interlocking cannot be performed under the manual mode.

 Silence: When events occur, the indicator will flash. After the silence button is pressed, alarm

stops and the indicator is on. After all the events have been removed, the indicator will be off.

 Reset: the button can only be used in level 2 and 3 user interfaces. When the button is

pressed, the controller will eliminate alarm and reset the activated device to the normal

mode.

 The area 1 is a fire alarm indicator. Under the normal mode, the fire alarm indicator
is off. When there is fire alarm, the indicator lights up. After all the fire alarm evens
are eliminated, the fire alarm indicator turns off.

 2 is the keyboard.

 The upper part is a digit zone. Digit buttons are used to enter digits and text.
 The middle part includes C and OK keys. C key is used for cancel and return,
while OK key is used for confirm and enter.
 The lower part includes the direction keys and key. The direction keys offer the
choice of up, down, right and left direction, while key is a menu selection key.

Siemens Building Technologies 14/40


Operating Manual of BC8002 Advanced Control Unit

4. User interface

 Type of interface:
BC8002 includes three kinds of user interfaces: Level 1,Level 2 and Level 3 user interface (as shown

in Figs. 3-1, 3-2 and 3-3). Different users can respectively log into different user level interface.

 Login method:
 Level 1 user interface:
◘ This is the default interface of the system. In other
View Operation Node Query Tools Help
words, it is the initial view without any operation after ...☺ 西门子
BrowserViewer

. .
. SIEMENS R&D Building
EventViewer
the controller is switched on. .
Fault Viewer

Logout
◘ If the current interface is level 2 (3) user interface,

press key and enter “View” option→ Press the


Fig.3-1 Log Into Level 1
direction keys to “Logout”→ and press OK key to

confirm (as shown in Fig.3-1).

 Level 2 user interface:


◘ If the current interface is Level 1 user interface,
View Operation Node Query Tools Help

press key to enter “View” option → press the ...☺ 西门子


BrowserVieewe
. SIEMENS R&D Building
. .

EventViewer
direction keys to select “Login” → press OK key . 主楼
FaultViewer

to confirm→ input the correct password→ press OK Log in

key to confirm and enter. (as shown in Fig.3-2,3-3).

If a wrong character is entered, user may press key


Fig.3-2 Log Into Level 3
C to delete it.

◘ If the current interface is level 3 user interface,

press key to enter “View” option→ press the 请输入登录密码


Please Input Pswd:
direction keys to select “Logout”→ press OK key ****

to return to level 1 user interface→ refer to the

method for logging into Level 2 from Level 1 user

interface for the subsequent operations Fig.3-3 Input Password

Siemens Building Technologies 15/40


Operating Manual of BC8002 Advanced Control Unit

 Level 3 user interface: View Operation Node Query Tools Help

◘ If the current interface is level 1 user interface, press ...☺ 西门子


BrowserViewer
.

. .
SIEMENS R&D Building
EventViewer
key to enter the “View” option→ press the direction . 主楼
FaultViewer

keys to select “Login” → press OK Log in

key to enter → input correct password→ press OK

key to enter. (as shown in Fig.3-4,3-5).


Fig.3-4 Log Into Level 3
◘ If the current interface is level 2 user interface,

Press key to enter “View” option → press the

direction keys to select “Logout” → press OK key


请输入登录密码
Please Input Pswd:
****

to return to Level 1 user interface→ refer to the

method for logging into Level 2 user interface from

Level 1 user interface for the subsequent operations.


Fig.3-5 Input Password

Siemens Building Technologies 16/40


Operating Manual of BC8002 Advanced Control Unit

5. Operation

 Tool option list:

Tool bar

View Operation Node Query Tools Help

(4.1.1) (4.1.2) (4.1.3) (4.1.4) (4.1.5) (4.1.6)

—BrowserViewer —Isolate —Property —Isolation Devices —Set Time

—EventViewer —Open —Analog curve —Fire Devices —Check System —About


—FaultViewer —Activate —History —Fault Devices —Adjust LCD

—Login (Logout) —Stop (


— Record ) —Activate & Answer —Adjust Buzzer

—Test —Edit Para —Bus fault Devices —Save Config

—Walk test — ModifyLogic —Test Devices —AutoMap

—Normal —Walk test Devices

※ Notes on the list:

1. Items expressed only in text are displayed in Level 1, 2 and 3 user interfaces. For example:
“EventViewer”
2. Items in bold face and being underlined are only displayed in Level 2 and 3 user interfaces. They will
not be displayed in Level 1 user interface.
i. For example:“BrowserViewer”
3. Items in bold, being underlined and in shade are only displayed in Level 3 user interface. They will
not be displayed in Level 1 or 2 user interface.
i. For example:“Edit parameter”
4. “Record” items can only be displayed when “Historical record” items are opened.

 Entry method:
View Operation Node Query Tool Help
Press key → cursor stays at the “Tool Bar” by default. BrowserViewer

(as shown in Fig.4-1). EventViewer


FaultViewer
Log in

Fig.4-1 Tool

Siemens Building Technologies 17/40


Operating Manual of BC8002 Advanced Control Unit

5.1 View
 Functions:
Used for switching to different browse view, log into (Log out) level 1, 2 and 3 user interface.

BC8002 includes 3 views: BrowseViewer, EventViewer and FaultViewer.

 Entry method:
View Operation Node Query Tool Help
BrowserViewer
Press key → enter “View” option → press the direction
EventViewer
keys to select the desired item → press Ok key to confirm FaultViewer
Log in
enter or C
key to cancel and return (as shown in Fig.4-2).

 Drop-down option:

 BrowserViewer: used for displaying information of each Fig.4-2 Tool

node.

 EventViewer: used for displaying alarm information and activation information.

 FaultViewer: used for displaying fault information.

 Login (Logout)
:Log into Level 2 and 3 user interface(return to Level 1 user interface)

5.2 Operation
 Functions:
Perform corresponding operations on lines and devices, including isolate, open, activate, stop, test,

walktest, normal.

 All controllers, lines and devices can be displayed in the tree structure.

 Operable options may be different from different types of nodes. Specific items are listed

below.

Siemens Building Technologies 18/40


Operating Manual of BC8002 Advanced Control Unit

Operable No
Walk
options Isolate Open Activate Stop Test Normal Operational
test
Type of Nodes Items
Controller √
Mainboard I/Os √ √ √ √ √ √
Line √ √ √ √ √
Field devices √ √ √ √ √ √
Interlocking panel √ √ √ √ √ √
Extinguishing panel √ √ √ √ √ √
Power supply √

View Operatio Nod Quer Tools Help


 Entry method:
...☺ Isolate
Press the direction keys in the tree structure to select a . Open

. .
SIEMENS R&D Building
主楼
. Activate
point → press key → press the direction keys to Stop
Test
select the pull-down menu of “Operation” → press the WalkTest
Normal

direction keys to select the desired action → press OK

Fig.4-3
key to confirm or C key to cancel (as shown in Fig.4-3).

 Drop-down option:
 Isolate
◘ Functions: Set open points as an isolation state. If points are successfully isolated, the

controller will concurrently issue a prompt sound. View Operatio Node Quer Tools Help
...☺ Isolate
◘ Setup method:
. .

. Open
SIEMENS R&D Building
. 主楼
Activate
In the tree structure, press the direction keys to Stop
Test
WalkTest
select a point → press key→ press the direction
Normal

keys to select the pull-down menu of “Operation”→


Fig.4-4 Isolate
press the direction keys to select “Isolate” → press OK

key to confirm ( shown as Fig.4-4).

◘ System prompt:

If a point has been set as isolation state, the symbol to the left of the name of the node will be

displayed as “”.

◘ Isolated area:

When individual point is selected to be isolated, only the selected one will be isolated. If a line

is selected to be isolated, all the devices connected on the line will be isolated.

Siemens Building Technologies 19/40


Operating Manual of BC8002 Advanced Control Unit
 Open:
◘ Functions: Convert isolated points into normal working state.

◘ Setup method:
View Operation Node Quer Tools Help

In the tree structure, press the direction keys to ...☺ Isolate


.

. .
Open
SIEMENS R&D Building

select a node → press key → press the


. 主楼
Activate
Stop
Test
direction keys to select the pull-down menu of WalkTest
Normal
“Operation” →press the direction keys to select

“Open”→ press OK key to confirm enter (show Fig.4-5 Open

as Fig.4-5).

◘ System prompt:

If a isolated point is set as normal working state, the symbol to the left of the name of the point

will displays ☺ .

◘ Open area:

When an individual point is selected to be open, only the selected point will be opened. If a line

is selected to be opened, all the points connected on the line will be opened.

 Activate:

◘ Functions: Activate all the equipment that is linked up with the output modules/ports selected

in the tree structure.


View Operation Node Quer Tools Help
◘ Setup method: ...☺ Isolate
. .

. Open
SIEMENS R&D Building
In the tree structure, press the direction keys to . 主楼
Activate
Stop
Test
select interlocked devices → press key →
Walk Test
Normal
press the direction keys to select the pull-down

menu of “Operation” →press the direction keys to


Fig.4-6 Activate
OK
select “Activate”→ press key to enter (shown

as in Fig.4-6).

Siemens Building Technologies 20/40


Operating Manual of BC8002 Advanced Control Unit
 Stop:

◘ Functions: Stop all interlocked equipment that has been activated.

◘ Setup method:
View Operation Node Quer Tools Help

In the tree structure, press the direction keys to ...☺ Isolate

. .
. Open
SIEMENS R&D Building
. 主楼
Activate
select interlocked devices → press key → Stop
Test
press the direction keys to select the pull-down WalkTest
Normal
menu of “Operation” →press the direction keys to
Fig.4-7 Stop
select “Stop”→ press OK key to confirm enter

(shown as in Fig.4-7).

 Test:

◘ Function: Under the test state, all devices issues alarm normally and simulate interlocking but

there is no real interlocking.


View Operation Node Quer Tool Help
◘ Setup method:
...☺ Isolate

. .
. Open
SIEMENS R&D Building
In the tree structure, press the direction keys to . 主楼
Activate
Stop
select a point → press key → press the Test
WalkTest
direction keys to select the pull-down menu of Normal

“Operation” →press the direction keys to select Fig.4-8 Test

“Test”→ press OK key to confirm enter (as

shown in Fig.4-8).

 Walk test:

◘ Function: In the walk test state, all equipment can issue alarm normally and but no real

interlocking. In the walk test process, the user can set the walk test time (time setup is in the

“Edit parameter” option). When the pre-set time is exceeded, the controller will automatically

remove to normal working status and eliminate all the test events.

Siemens Building Technologies 21/40


Operating Manual of BC8002 Advanced Control Unit
◘ Setup method:
View Operatio Nod Quer Tool Help
In the tree structure, press the direction keys to ...☺ Isolate

. .
. Open
SIEMENS R&D Building
select a node → press key → press the 主楼
. Activate
Stop
Test
direction keys to select the pull-down menu of WalkTest
Normal
“Operation” → press the direction keys to select
OK Fig.4-9 Walk Test
“ Walk Test” → press key to confirm enter (as

shown in Fig.4-9).

 Normal:

◘ Function: return to the normal state from test status or walk test status.

No switchover between test and walk test state. View Operatio Nod Quer Tool Help
...☺ Isolate

. .
◘ Setup method: . Open
SIEMENS R&D Building
主楼
. Activate
In the tree structure, press the direction keys to Stop
Test
WalkTest
select a point → press key → press the
Normal

direction keys to select the pull-down menu of


Fig.4-10 Normal
“Operation” → press the direction keys to select

“ Normal” → press OK key to confirm enter (as

shown in Fig.4-9).

5.3 Node
 Function:
Display “Property”, “Analog Curve”, “History” and “Edit parameters” and “Modify logic expression”

of the node selected on display view.

 Entry method: View Operatio Nod Query Tool Help

In the tree structure, press the direction keys to select a ☺ Siemen Property
.....
..

Analog
SIEMENS R&D curve
Building
History
node → press key → press the direction keys to Edit Para
Modify Logic
enter the pull-down menu of “Node” → press the direction

keys to select the item that needs to be checked → press OK

key to confirm and enter or C key to cancel and exit. (as Fig.4-11

shown in Fig.4-11)

Siemens Building Technologies 22/40


Operating Manual of BC8002 Advanced Control Unit
 Drop-down option:
 Property: include node’s type, model, status, threshold value and so on.

 Analog curve: For the detector, the system displays real time analog parameter changes.

 History: Display all the events that have occurred at the node.

When the “History” option is entered for the first time, the tool bar will change, with the

“Record” column added. Meanwhile, all the historical records of the selected equipment will be

displayed. (this process takes a certain time)


◘ Entry method:
View Operati Nod Que Record Tool Help
Press key → press direction keys to select the ...☺Siemen All

.. ..
.. SIEMENS R&D Building
Fault
pull-down menu of “Node”→ press the direction keys .. Main Alarm
Control
Isolation
to select “History”→ press OK key → press the

direction keys to select the pull-down menu of “Record”

→ press the direction keys to select the item to be


Fig.4-12
queried→ press C key to confirm or to cancel

and exit (as shown in Fig.4-12).

◘ Drop-down option (record):

 All: Display all the historical records of selected point, which have occurred.

 Fault: Display the fault records of selected point,.

Alarm: Display the fire alarm records of selected point

 Control: Display the control information of selected point.

 Isolation: Display the isolation records of selected point.

Notes: After operators choose one of options mentioned above, a “Time Segment” frame will

turn up. The function of the frame is setting the checking period.

◘ Time setup

 Setup method:
Time Segment:
Use digit keys to enter the query time and press the up
Date Hr
and down direction keys to switch over between Fr 2005-09-04 14

windows. The date entry format is “yyyy-mm-dd. The


Date Hr
default value of the query termination time is the To 2005-09-05 16

current time (as shown in Fig.4-13).


Fig.4-13 Time Setup

Siemens Building Technologies 23/40


Operating Manual of BC8002 Advanced Control Unit

 Special specifications: Selectio

After the checking time is set, press key and


...☺
CharNum西门子

.. ..
..
Pinyin SIEMENS R&D Building
.. 主楼
“Selection” appearing on the top of LCD. Choose “OK” OK
Cancel
to confirm and “Cancel” to quite. (shown as Fig.4-14).

Fig.4-14 Text Edit

 Edit parameter:
◘ Functions:
Modify address, text (name), type and other parameters of a selected node or panels.

1. For different nodes, there will be different interfaces for parameter editing.

2. After the “Edit parameter” option has been selected, the screen enters a text edit state. At

this time, the bus address, text (name), type of the selected node are displayed (there are

different editing items for different types of node).

3. Text edit state:

Under the text edit state, there is only the “Selection” menu on tool bar.

◘ Text edit state

 Select:

◘ Function: Edit text. Bus(B) 01 (1-59)


Text R&D line
◘ Editing method:
Typ BCM 8001 Line card
After the “Edit parameter” option is entered, the No of 01

text editing window will be displayed on the left

side of the screen. On the text editing window, Fig.4-15 Letter


Input
press the up and down direction keys to select the

position to be edited → press digit keys to input

letters and digits →press to choose “OK” or

“Cancel” (as shown in Fig.4-15).

Method for using digit keys to input letters: press down digit keys → then, the entered

items are mutually converted between digits and letters→ when the converted item is the

content to be entered, release keys→ complete the entry of the needed characters→ press OK

Key to confirm or C Key to cancel the operation.

Siemens Building Technologies 24/40


Operating Manual of BC8002 Advanced Control Unit
The specific functions of the various digit keys are as follows:

- Hold down the digit keys (2-9): the entered items mutually convert between digits and
letters;

- Hold down the digit key (1) : the entered items mutually convert between the digit 1,

punctuation marks and special characters;

- Hold down the digit key (0): the entered items mutually convert between the digit 0,
‘<’ and ‘>’. When it is respectively changed to‘<’ and ‘>’, quit hold of the key and it

shows that the entered letters are respectively in block and low-case letters. When

block letters are entered, an upward arrow on the right low corner of the screen will

appear as prompt

At the time of editing, if wrong entries are made, C key can be used to cancel the

wrong characters.

If the text editing window only has the pull-down option to select, then press the

rightward direction key to open the pull-down menu and then use the direction key to

select an item.

 OK: Save changes in the short term and exit from the “Edit parameter” mode.
 Cancel: Do not save changes and exit from the “Edit parameter” mode。

◘ Special specifications:
Under the “Edit parameter” state, changes can only be saved in the short term. After the system

restarts or closed down, short term saved data will get lost. Therefore, users are recommended

to save their changes in the long term. Method for long-term saving: Under the text editing

state, press “OK” for short-term saving → log into level 3 user interface → press

key in level 3 user interface → press the direction keys to select “Tool” → press the

direction keys to select “Save Config” → press OK key to confirm and enter.

Siemens Building Technologies 25/40


Operating Manual of BC8002 Advanced Control Unit

 Modify Logic :
◘ Function:
View Operatio Nod Query Tool Help
To compile and modify the interlocking relation of a node.
☺Sieme Property
..... SIEMENS

..
Analog
R&D Building
After the “Modify Logic” option has been selected, History
Edit Para
Modify Logic
the screen enters a text editing state. Under it,

there is only the “Selection” column on the tool bar.

For introductory information on the text editing Fig.4-16 Modify Logic

state, please refer to “Edit parameter”.

◘ Modification method:

Enter the “Modify Logic” option→ interlocking relation is displayed on the left side of the

screen→ press digit keys and direction keys to modify interlocking relation → press key→

enter the pull-down menu of “Selection” → press the direction keys to select “OK” to save and

Exit or “Cancel” to exit without saving (as shown in Fig.4-16).

When wrong entries are made, C key can be used to delete it.

5.4 Query
 Function: Query the node under a certain status and display it in the browse view.

 Entry method:

Press the direction keys to select a node in the tree View Operatio Nod Quer Tool Help
...☺ Siemen Isolation
.. ..

.. SIEMENS R&DFire Devices


Building
structure → press Key → press the direction keys .. Main Fault Devices
Activate&
to enter the pull-down menu of “Query” → press the Bus Fault
Test Devices
Walktest
direction keys to select the item to be queried → press OK

Fig.4-17
key to confirm and enter or C key to cancel and exit

(as shown in Fig.4-13).

 Drop-down options:

 Isolated Devices: Query address of the isolated devices and display its property.

 Fire Devices: Query address of the fire devices and display its property.
 Fault Devices: Query address of the fault devices and display its property.

Siemens Building Technologies 26/40


Operating Manual of BC8002 Advanced Control Unit

 Activate&Answer : Query address of the activated devices and display its property.
 Bus Fault Devices: Query the bus address of communications fault.

 Test Devices: Query address of all tested equipment and display its property.

 Walk test Devices:Query address of all walk tested devices and display its property.

5.5 Tools
 Functions:

Set time, check system state, adjust LCD brightness and the sound volume of equipment’s alarm,

save data for a long time and automap.

 Entry method:
Vie OperationNodeQuery Tool Help
Press key → press the direction keys to select the ...☺Sieme Set time

.. ..
.. SIEMENS R&DCheck

pull-down Menu of “Tool” → press the direction keys to .. Main Adjust LCD
Adjust Buzzer
Save Config
select the item to be set up → press OK key to confirm Automap

and enter or C key to cancel and exit (as shown in


Fig 4-18 Tool
Fig.4-18).

Siemens Building Technologies 27/40


Operating Manual of BC8002 Advanced Control Unit
 Drop-down option:

 Set time :
◘ Function: Set system time. View OperationNode Query Tools Help
...☺ Siemen Set time
◘ Setup method:

.. ..
.. SIEMENS R&D Building Check
.. Main Adjust LCD
Press key → press the direction keys to select brightness
Adjust Buzzer
Save Config
Automap
the pull-down menu of “Tool” → press the

direction keys to select “Set time” → manually


Fig 4-19 Set Time
input time and date in the pop-up time setup

window → press key → enter to select the

pull-down menu of “Select” → press the direction

keys to select “OK” to save and exit or “Cancel” to

exit without saving (as shown in Fig.4-19).

Method to set up time and date:

- Press the up and down direction keys to switch between windows;

- Press digit keys to input the time and date in the corresponding window. The format to

set time is “hh:mm:ss”, while the date setup format is “yyyy:mm:dd” 。


Exit after “OK” is pressed. If the system consists of several controllers, the current

controller will inform all the other controllers to adjust time based on the current

controller time.

 check System :
◘ Function:

Check the working state of indicators, sound system, LCD and printer.

◘ Setup method:
View OperationNode Query Tools Help

Press key → press the direction keys to select ...☺ Siemen Set Time
.. ..

.. SIEMENS R&D Building


Check System
.. Main Adjust LCD
the pull-down menu of “Tool” → press the Adjust Buzzer
Save Config
direction keys to select “check system”→ press OK Automap

key to confirm and enter (as shown in Fig.4-20).


Fig4-20 System
Check

Siemens Building Technologies 28/40


Operating Manual of BC8002 Advanced Control Unit
When system check start, all indicators on the

panel will flash. The equipment concurrently

issues various kinds of sound and the upper

and lower screen of the LCD will experience

one alternate black and white change once,

printer will print automatically.

Check criteria:

Indicator — The normal state is that all the indicators are on. If a indicator is not on, it means

that the indicator is abnormal.

Sound—The normal state is buzzer issues all (four) kinds of sounds. If some tune cannot be

issued, it shows that the sound system is abnormal.

Screen—The normal state is all the screen areas are displayed normally.

Printer —The normal state is that the printer will print” printer is OK” automatically.

 Adjust LCD

◘ Function: Adjust LCD brightness.

◘ Setup method:
View Operation Node Query Tools Help
Press key → press the direction keys to select ...☺ Siemens Set Time
.. ..

.. SIEMENS R&D Building


Check System
the pull-down menu of “Tool”→ press the direction .. Main Adjust LCD
brightness
Adjust Buzzer
keys to select “Adjust LCD ” → brightness Save volume
Config
Automap
adjustment window pops up on the screen→ press

the up and down direction keys to adjust display


Fig4-21 Adjust LCD
screen brightness → press OK key to confirm and

enter (as shown in Fig.4-21).

◘ Special specifications:

Brightness adjustment is cyclic setup. That means, when the adjusted value reaches the

maximum value (minimum value) set by the system, it continues to make adjustment. The

value will automatically return to the minimum value (maximum value) set by the system.

Siemens Building Technologies 29/40


Operating Manual of BC8002 Advanced Control Unit

 Adjust buzzer :
◘ Function: Adjust controller’s buzzer volume.

◘ Setup method: View Operation Node Query Tools Help


...☺ Siemen Set Time
Press key → press the direction keys to select

.. ..
.. SIEMENS R&D Building
Check System
.. Main Adjust LCD
the pull-down menu of “Tool” → press the brightness
Adjust Buzzer
Save Config
Automap
direction keys to select “Adjust buzzer” → sound

volume adjustment window pops up on the screen


Fig4-22 Adjust Buzzer
→ press the up and down direction keys to adjust

sound volume→ press OK key to confirm and

enter. (as shown in Fig.4-22)

◘ Special specifications:
Press up direction key, volume is increased; Press down direction key, volume is decreased.

 Save Config : View Operation Node Query Tools Help


...☺ Siemen Set Time

.. ..
◘ Function: Save various modifications for long time .. SIEMENS R&D Building
Check System
.. Main Adjust LCD
brightness
Adjust Buzzer
◘ Setup method: Save Config
Automap
Press key → press the direction keys to

select the pull-down menu of “Tool” → press the


Fig4-23 Save Config
direction keys to select “Save Config” → press OK

key to confirm and enter (as shown in Fig.4-23)

 Automatic map :
◘ Function:

Automatically map all the devices connected in the line to the controller.

◘ Setup method:
View Operation Node Query Tools Help

Press key → press the direction keys to ...☺ Siemens Set Time
.. ..

.. SIEMENS R&D Building


Check System
select the pull-down menu of “Tool”→ press the .. Main Adjust LCD
brightness
Adjust Buzzer
Save Config
direction keys to select “Automatic map” →
Automap

press OK key to confirm and enter.

Fig4-24 Automap

Siemens Building Technologies 30/40


Operating Manual of BC8002 Advanced Control Unit

5.6 Help
 Function: Display software version, download time and modification time.

 Setup method: View Operation Nod Query Tool Help

Siemen About
Press key → press the direction keys to select the ☺

.. ..
..... SIEMENS R&D Building
.. Main
pull-down menu of “Help” → press the direction keys to

select “About” → press OK key to confirm and enter

or C key to cancel and exit (as shown in Fig.4-25).


Fig.4-25 Help

Siemens Building Technologies 31/40


Operating Manual of BC8002 Advanced Control Unit

Chapter 6 Interlocking Control Panel

1. Introduction

BT8011/BT8012 interlocking control panels are used for automatic/manual control of important
equipment (such as pump and fan).
 There are two kinds control signals can be chosen: Pulse and Level.
 BT8011/BT8012 communicates with the controller through B-BUS. OC output controls external
equipment through relays.
 All “activation”, “fault” and “confirmation” signals are displayed on the panel and there are
corresponding sounds prompt for them.
 The functions of “test” and “silence” are available.
 When the “Manual” light is on, it indicates manual operation is allowed. At this time, on-site
equipment can be activated/stopped by keyboard.
 When the “Automatic” light is on, it indicates automatic operation is allowed. At this time, the
controller is allowed to automatically interlock and control on-site equipment.
 3U panel structure.
The first five digits of the Dip-switch define the address of the current interlocking panel. The sixth
digit is used to define whether the interlocking panel communicates with the controller through
B-Bus. The seventh and eighth digits define the output mode of the interlocking panel. Detailed
information is given in the table below:

Name Status Function


1-5 - Set B-Bus address
On Not allowing B-Bus communication
6
Off Allowing B-Bus communication
On C1-C8, pulse output
7
Off C1-C8, level output
On C9-C16, pulse output
8
Off C9-C16, level output

Siemens Building Technologies 32/40


Operating Manual of BC8002 Advanced Control Unit

2. Connecting diagram

BT8011 Interlocking Panel

BT8012 Interlocking Panel

Siemens Building Technologies 33/40


Operating Manual of BC8002 Advanced Control Unit

3. Operation

3.1 Automatic mode:


 Requirements:
Both the controller and the interlocking panel are in the “Automatic” mode.
 Operation:
 The “Automatic” mode is the default mode of both controller and interlock after
they are switched on.
 Interlocking panel is in the “Manual” mode: By pressing the “Manual ” button
once, the panel will switch to “Automatic”.mode.
 Function:
Under this state, interlocking panel can interlock field devices automatically
(interlocking relationship is to be set by software), but direct manual control is not
allowed.

3.2 Manual mode


 Requirements:
Interlocking panel is in the “Manual ” mode. That is the “Manual ” indicator is on.
 Operation:
 If interlocking panel is in the “Automatic” mode, pressing “B (manual) -A
(automatic) - B (manual)” button, the interlocking panel will switches from the
“Automatic” mode to the “Manual” mode.
 Function:
Under this state, a controlled equipment can be activated/stopped manually, but no
automatic interlocking can be done.

Siemens Building Technologies 34/40


Operating Manual of BC8002 Advanced Control Unit

Chapter 7 Extinguishing Panel

1. Features

 BC8013 extinguishing panel is used for extinguishing section control. It can be set at automatic
mode or manual mode. It is mainly applied for rooms stored with importance devices or
electronic materials (IT room or switch-board room etc.) and file rooms, libraries or other
rooms which need special protection.
 One panel monitors 2 extinguishing sections, for each section, there are three outputs: output1,
output2, gas release and all activation will provide confirmation signals.
 Can be connected via B-Bus, address set by Dip-switch, Information of extinguishing section
can be displayed on the control unit. The parameters of BC8013 extinguishing panel can be
configured by the control unit or downloaded from PC-tool.
 Three kinds of activation/stop mode: automatic activation, manual activation and remote
activation/stop.
 Operation can be done on the control unit or in the remote protected area.
 External control wires are monitored automatically against the short circuit.
 Auto mapping is possible for commissioning.
 Fault is automatically detected and displayed on the panel.

2. Diagrams

Detection Bus
2

BC80 Control Unit


Field
B-Bus Power
+ - + -
2F1 2F2 2F3 V G
V,G can connect with
power BCB8001/8002/ IN4004 C C
8003 4.7K 4.7K 4.7K
K
IN4004 B B

Remote Remote
K is a +24V Stop Activate
relay
+ - + - + - + - C1 MT300 MT300
B-Bus Power B-Bus Power

1F1 2F1 Gas


1F2 BC8013 2F2 BC8013 Alarm Devices Realease
1F3
Section 1 2F3
Section 2 panel
G D1

1RS 1RA 1D3 1D2 1D1 2RS 2RA 2D3 2D2 2D1

G 2D1 2D2 G 2D3 2RS 2RA

3 8 10 6

3 8 10
Field

Siemens Building Technologies 35/40


Operating Manual of BC8002 Advanced Control Unit

3. Operation

 Two kinds of status of BC8013 extinguishing panel:


“Auto”: default status after switch-on, you also can press “auto” button to set the panel as
“auto” status. When fire alarms, control unit sends the activation command to the panel and
the panel will send signals to output1, output2, gas release ports in every 15 seconds (the
delay time can be set from 0 to 255 seconds via computer)..The red LED flashes when time
lapses. The red LED is on after activation command is sent out. The activation command is
used for activating alarm devices and extinguishing devices on site. After the device is
activated, the answer LED is on with green color.
“Manual”: the panel can be set as “manual” status by following steps: press “manual” button

press “auto” button
press “manual” button, then “manual” LED is on. When fire alarms,
press “emergency activation” button to activate extinguishing devices, the following steps are
the same as “auto” status.

 Remote activate/stop
BC8013 extinguishing panel has two input terminals (RA& RS). RA is remote activation input
terminal and RS is remote stop input terminal. Generally remote activate/stop button is installed
on site. When fire occurs, the operator will judge if extinguishing devices is necessary to
extinguish fire. If it is, he will press the remote activation button immediately. The extinguishing
panel will be at extinguishing status and activates all kinds of alarm devices and extinguishing
devices. When the site people find that fire is under control and extinguishing devices is not
necessary any more, he press the remote stop button to stop extinguishing devices. The current
status is kept.

 Emergency stop
At “manual” status, the “emergency stop” button can stop extinguishing command and the current
status is kept.

Siemens Building Technologies 36/40


Operating Manual of BC8002 Advanced Control Unit

4. Installation and Commissioning

 After finishing installation, don’t connect field devices and do the following check:
(1) Check all connection in the panel and 28VDC power supply, then switch it on.
(2) At normal status, press “Silence/Test” button to test panel; When buzzer is alarming, press
“Silence/Test” button to silence and LED is on. When emergency, fault or answer happens,
the LED flashes, to press “Silence/Test” button again, LED is on.
(3) Press “manual” button
press “auto” button
press “manual” button, then “manual” LED is
on and the panel is at “manual” status. At “manual” status, press “emergency activation”
button can carry out emergency activation command. At “auto” status, “emergency
activation” button is useless.
(4) “Auto” LED is on means the panel at “auto” status. If panels monitor more extinguishing
sections, each BC8013 should be given individual address.
(5) Remote activation/stop, to activate/stop extinguishing devices remotely by collective push
buttons.
(6) “Emergency stop” button is only available at “Manual” status. When you press the
“emergency stop” button, the LED will be on and block any activation which did not happen.
 After finishing the above mentioned commissioning, connect field extinguishing devices into
terminals based on connection drawing. If check is passed, switch it on. Once field device is
connected to the panel. The following items should be noticed:
Not allow to do any alarm test at the “auto” status;
Not allow to set the panel as “manual” status at normal time;
Ensure “remote activation” button and “remote stop” button to be available and at non-
activation status.
 Remark:
The panel must be checked and ensure all connection is correct, then switch it on;
the panel should be used and managed by specific person, any other person is not
allowed to operate it.
To be installed at dry place, avoid humidity.
Avoid shake and direct hit.
Ensure site activation/stop button at good status, avoid gas release by mistake.
Any problem should be handled in time and ensure panel at good working status.
Check panel manually at certain time.

Siemens Building Technologies 37/40


Operating Manual of BC8002 Advanced Control Unit

Chapter 8 Detecting and Repairing


1. Daily Examining

Person on duty should do daily check of control unit, and take corresponding record on duty. If fire alarm,
failure and other abnormal events (control unit will have audio warning, indicator flashing and event
display) happen, “Requirements of Event Treatment” shall be followed, till the control unit restores to its
normal state. The record shall be well kept.

2. Trouble-shooting Guideline

No. Failure content Possible reasons Repairing methods


Function keys, LED and Failure of signal wire and power Correct connection;
LCD screen and so on line; Replace corresponding
1.
is ineffective and The damage of corresponding hardware;
damaged hardware
Check if main power and battery Correctly supply power and
are on? make secure connection;
No power supply
2. Check of power connection is Replace Power supply;
indication
firmly secured?
Power supply is damaged
LCD brightness is not enough; Adjust LCD brightness;
Power supply is on, LCD without power supply or Examine power supply line
3. and control unit is main board power supply part is or replace main board;
“black screen” damaged;
LCD is damaged, Replace LCD;
System software or project Replace corresponding
Control unit does not
4. software is lost; software;
display any content.
CPU board is damaged, Replace CPU board;
No voltage; Replace power supply line
or main board;
5.
No sound Volume is not enough; Adjust buzzer volume;
Buzzer is damaged; Replace buzzer;
Project software is Modify software;
unconformable with devices on
site;
6. Control station fault Main board address is not set or Modify address setting;
unconformable with software
address;
Main board is damaged; Replace main board;

Setting of project software is Change project software;


7. Interlocking panel fault
unconformable with real status;

Siemens Building Technologies 38/40


Operating Manual of BC8002 Advanced Control Unit
No. Failure content Possible reasons Repairing methods
Communication wire, power Correct connection;
supply fault;
The address of Interlocking Change setting;
panel has not been set, or
address is unconformable with
software setting;
Interlocking panel is damaged; Change interlocking panel;
Software setting is wrong; Modify setting;
Main board input &
8. Main board input/output is Replace main board;
output fault
damaged;
Project software is Modify software;
unconformable with fact;
Exterior voltage overrun power Adjust exterior voltage
9. Power supply fault
requirements; scope;
Battery is damaged; Replace battery or main
Power supply is damaged; board ;
Project software is Change software setting;
unconformable with fact;
Line card has not been assigned Assign address or change
address or address is not address accordingly;
accordance with software
setting;
10. Line card fault
Line card is damaged; Change line card;
B-Bus communication or power Check communication lines
supply fault; and power lines;
F-Bus short circuit;
Field devices is damaged Change field devices;
seriously;
Connection fault; Check connection;
Project software is Change software setting;
unconformable with fact;
Field devices has not been Assign address or change
11. Field device fault
assigned address or address is address accordingly;
not accordance with software
setting;
Field device is damaged; Change field device;
Control unit and interlocking Change software setting;
panel are not on automatic state;
Interlocking relationship is not Replace damaged field
set correctly or interlocking devices;
12. Auto-interlocking fault relationship is not right;
Interlocking equipment is Examine connection;
damaged;
Power supply and interlocking
line fault;

Siemens Building Technologies 39/40


Operating Manual of BC8002 Advanced Control Unit
No. Failure content Possible reasons Repairing methods
Operating level is not right;
Control unit is not on manual
state;
13. Manual control fault Interlocking equipment is Replace damaged field
damaged; devices;
Power supply and interlocking Examine connection line;
line failure;
Operating level is not right; Change operating level;
Isolation and opening Operating method is not right;
14.
fail Operating panel is damaged; Replace operating panel;
Main board is damaged; Replace main board;
Operating level is not enough; Change operating level;
Test and manual
15. Operating method is not right;
releasing fail
CPU board is damaged; Replace CPU board;
Operating level is not enough; Change operating level;
Moving test and
16. Operating method is not right;
automatic releasing fail
CPU board is damaged; Replace CPU board;
Display error of Software error; Update software;
17. fair-alarm, activation CPU board is damaged; Replace CPU board;
and fault etc.
Operating level is not right; Change operating level;
Inquiring about history
18. Operating method is not right;
events fail
Main board is damaged; Replace main board;
Operating level is not right; Change operating level;
Display error of analog Operating method is not right;
19.
curve; CPU is busy;
CPU board id damaged; Replace CPU board;
Operating level is not right; Change operating level;
Site programming Operating method is not right;
20.
(modifying) fail CPU board is damaged; Replace CPU board;

Operating level is not right; Change operating level;


Operating method is not right;
Printing, closing and Power supply and signal line Correct connection;
21.
opening fail failure; Update software;
Printer parameter setting error; Replace printer;
Printer is damaged;
Operating level is not right or Change operating level;
operating method is not right,
Other operating failure
22. Software is lost or fault; Update software;
on the control unit
Some hardware is damaged; Replacing damaged
hardware;

Siemens Building Technologies 40/40


Operating Manual of BC8002 Advanced Control Unit

3. Replaceable element table

Name Model Replacement


Fuse capacity (battery) 8.0A Replace the same model product
Fuse capacity (main power) 2.0A Replace the same model product
Replacing the same model product is
Connecting terminal Phoenix
recommended.
For problems with other components, please contact manufacturer for replacement.

4. Reclamation

For abandoned control unit, please contact local office of manufacturer to make proper treatment. Any
discarding of control unit random is strictly forbidden.

Siemens Building Technologies 41/40


Operating Manual of BC8002 Advanced Control Unit

Chapter 9 Schematic Diagram of


Connecting Wires in Controller

1. Schematic diagram of wires connection

Connect with other


controllers

H H L H L H L H L H
SYNC H SYNC H A-BUS A-BUS B-BUS B-BUS
B-BUS

B-BUS

L L 电
L L □ 源

+

CPU CPU
BCC8002 Main board Connect with printer
BCM8001 BCM8001
Line card Line card
Signal line CPU
电 □─ 电 □─ Connect with display
源 + 源 +
F-BUS F-BUS 8-channel input/output

P1S1 P4S4 P1S1 P4S4


+28V I/O8 I/O1 GND

BT- BT+ - + - + - +
Power Power supply

BCB8001 Wall-Mount Power Supply


+□ ─ +□ ─ L H L H
Power Power B-BUS B-BUS
Signal line
BT8011/8012 Multiline Interlocking panel CPU
Output Rsp Ground Output Rsp Request
Battery Battery
C9 C16 D9 D16 GND GND C1 C8 D1 D8 A1 A8

2. Points to note

The diagram above is for reference use by repair and assembly personnel only. Non-repair personnel are
not recommended to dismantle internal connecting wires and components without permission.

Siemens Building Technologies 42/40