Boiler#4 Interlocks

S.No. Tag No. Description Value(alarm/Tripping)

Safety InterlockProcess Interlock


Furnace pressure very low -150

Blr#4 ID Fan
B4ID52

1 Local Stop
Winding Temp. Hi Hi 120/130
DE side-8/13;NDE
Vibration Hi Hi
Side-8/12
Motor Brg. Temp. Hi Hi 85/95
Fan Brg. Temp. Hi Hi 100/110

Furnace pressure Not Ok 150


Process Interlock

Drum Level very Low 15


ID Fan Not Running
Any One Of Wall Seal Blower running
Wall Seal Pressure LO LO Less Then 1000

Local Stop
Blr#4 SA Fan
B4SA51

2
Safety Interlock

Winding Temp. Hi Hi 120/130

Vibration Hi Hi NDE Side-8/10


Motor Brg. Temp. Hi Hi 80/90
Fan Brg. Temp. Hi Hi 100/110

Both Emergency PB Operated

Furnace Pressure Not Ok (-)150/150


Process Interlock

Drum Level Very Low 15


Blr#4 PA Fan

ID Fan Not Running


SA Fan Not Running
B4PA50

Local Stop

Safety Interlock
Winding Temp. Hi Hi 130/140
Vibration Hi Hi NDE Side-8/10
Motor Brg. Temp. Hi Hi 85/95
Fan Brg. Temp. Hi Hi 100/110
Blr#4 Wall Seal Blower

Process Interlock ID Fan Not Running

4 B4BL54

Safety Interlock Local Stop


Feeder
Blr#4 Draig Chain
Process Interlock Boiler Interlock Not Ok

B4DCF64
5

Local Stop
Drive Not In DCS
Safety Interlock
Zero Speed Switch
DCF-56 Close limit switch
Time Delay Remarks

after 15 Seconds
After 120 Seconds

Except R1 & B2
Phase 100/130

Auto Start If
Pressure is less then
1000
S.No. Tag No. Description

ID FAN NOT RUNNING


PA FAN NOT RUNNING
SA FAN NOT RUNNING
DRUM LEVEL NOT OK
FURNACE PRESSURE NOT OK
WALL SEAL BLOWER PRESSURE NOT OK
BOTH EMERGENCY PB OPERATED
TOTAL AIR FLOW LESS THEN 25 % MCR
BOILER INTERLOCK

INSTRUMENT AIR PRESSURE LO LO


COMPACT SEPARATOR #1 TEMP. HI HI
COMPACT SEPARATOR #2 TEMP. HI HI

EMERGENCY PB OPERATED

1
Either LL-15 or HH-90
Either LL-(-)150 or HH-150
Less then 1000 After 15 Sec.

4.5 Kg/Cm2
1000 Deg C
1000 Deg C