Professional Documents
Culture Documents
Dr.P.Kaliappan
IEEE Senior Member
ISA Senior Member
Fellow IE
Joint Director/HOD(MUAD)
Power Systems Division
Central Power Research Institute
Bangalore 560 080
E-mail: kaliappan@cpri.in
Mobile: +91 94491 49924
Type Testing
• Energy Meter
• Reliability
• Billing
• NABL Lab
• Influence quantities
Testing Major tests recommended No. of Criteria for
Samples conformity
Acceptance Routine
Type testing
testing testing
• Type Testing
• Acceptance testing
• Routine testing
Fully Automatic test Bench
Fully Automatic test Bench
Test of Insulation properties
• Impulse voltage: 6 kV
Insulation test
500 V DC
Test of Accuracy requirements:
Test on Limits of error (balanced & unbalanced)
Broad working range is checked ( from 1% or 5% of Ibasic)
Voltage variation:
Ibasic , pf=1 & 0.5lag V=±10% , ±20%,
below0.8Vref & upto 0.7Vref & below 0.7Vref
AC MAGNETIC COILS:
400AT – 0.5 mT.
2800AT – 10mT.
28000AT – 0.2T
• In the event of logging with dt & time , the +ve
variation may be beyond the limit of 4%
• Meter to record at Imax
DC MAGNETIC COILS :
1000AT – 0.67mT.
12000AT – 0.27T.
Test of Power Consumption
The limits on Power consumption in voltage & current circuit are not only important from
the point of consumption of power but also from the angle of limited rating of current &
voltage transformers used
Voltage Circuit :The active and apparent power consumptions of a composite Smart
Meter shall not exceed 5.0W and 15VA during the Idle Mode of Communication Module.
This applies to either one NAN or one WAN module present in the Smart Meter.
If a separate module for servicing to IHD is present, the above figures shall not exceed
6W and 18VA during the Idle mode of communication Module.
The additional power requirement during DATA transmission shall not exceed 7W per
communication module.
Current Circuit : The apparent power taken by each current Circuit of meter at maximum
current, Reference frequency and reference temperature shall not exceed a value in VA
equivalent to 0.08 % of Vref in Volts multiplied by 100% of Imax in amperes.
Test of Influence of supply voltage
Simulation of power
quality failure .
To check immunity of
meter to short duration
interruptions
Test of influence of short time overcurrent
Cause of failure:
• Saturation of CT core due high temp of CT primary
Influence of Self Heating
Causes of failure :
• Size of cables used for testing
• Size of Terminal block , Screws used for cables
• Inside arrangement of the CT
• Rivets/ screws used in the meter for connecting primary of CT
• Heating of terminals
Test of influence of Heating
Under normal condition of the use, electrical circuits and insulation shall not reach a temperature
which might adversely affect the operation of the meters.
The temperature rise at any point of the external surface of the meter shall not exceed by more
than 20ºC with an ambient temperature of 45 ºC.
To ensure there is no abnormal heating in the meter which raises the temp. of the body to a limit
which can create a safety risk for personnel or insulation of the meter itself
Meter is energized with 115% of reference voltage and Imax for Two hours.
After heating : IR & functional accuracy test is carried out.
Observation : Temperature rise of the terminal block and the meter case shall not be more than
20ºC at an ambient temp of 45 ºC .
Limits of % Error shall be within the permissible limits of Standard.
Test of Immunity to Earth fault
This test applies to 3 phase 4 wire meters
Test condition:
Earth fault condition is simulated in one of the 3 lines – all voltages increased to 1.1 times
Neutral of MUT is disconnected from Ground of Meter Test Equip.(MTE) & connected to
In this way 2 voltage terminals of MUT which are not affected by Earth fault are connected
Result:
After the test , MUT shall show no damage & shall operate correctly.
Test for Climatic Influence
The metering installations are generally not protected from climatic changes & hence a
meter shall not only withstand but also work properly in these climatic conditions
Dry heat test: To simulate storage conditions during which meter may be subjected to
extreme temp.
Meter in non-operating condition
Temp: +70ºC ± 2ºC , duration: 72 hrs.
Cold test :
Meter in non-operating condition
Temp: -25ºC ± 3ºC ( for indoor meters), duration: 72 hrs.
-40ºC ± 3ºC ( for outdoor meters) , duration : 16 hrs (as
per IEC standard)
Damp heat cyclic test: IS 9000 (part 5 / sec 1&2)
To determine the suitability of the components / equipment for use or storage under
condition of high humidity when combined with cyclic temp. changes and, in general ,
producing condensation on the surface of the specimen.
Test Conditions -
upper temp 40ºC ± 2ºC
RH 93 to 97 %
6 cycles, each Cycle of 24 hours
Meter in operating condition : Energized with Ref voltage
24 hrs after the end of test , the meter shall be subjected to insulation test
There are 2 ways for EMI to travel Immunity to Electromagnetic HF field: IEC 61000-4-3
1.Folllowing a physical path To determine immunity of the specimen to various levels of RF signals.
through wire / cable Ex: TV, AM/FM Radio ,cellular, navigation transmission
( conducted)
80MHz to 2000MHz and Test field strength: 10V/m
2. Through free space
( Radiated)
Fast Transient Burst Test:
Thank You